Neutral Earthing Resistor

Introduction
A neutral earthing resistor (NER) is normally connected to the transformer neutral. The function of
the neutral earthing resistor is to generate the active current traditional earth fault protection needs
to be able to detect one phase to groun faults (earth faults)
Swedish Neutrals NERs are delivered with overload protection, local control panel and remote
control interface. The NERs are availible both for indoor and outdoor use.
Swedish Neutral has delivered NERs since 1991 to Swedish and European customers.

www.swedishneutral.se

Neutral Earthing Resistor


Swedish Neutral offers NERs of four different types:

NER connected to One-Phase Transformer


NER connected to Grounding Transformer
NER connected to Arc Suppression Coil
Primary NER

Main Circuit Neutral Earthing Resistors


NER connected to One-Phase Transformer

NER connected to Arc Suppression Coil

R
R

Primary NER

NER connected to Grounding Transformer

Neutral Earthing Resistor

Air cooled stainless steel resistor elements


Integrated overload protection
Local control panel with remote control interface
Hermetically sealed design of One-Phase Transformers and Grounding Transformers
Built in voltage transformer as option
Built in current transformer as option
Manufactured in co-operation with SGB, one of Europes largest transformer manufacturers

Neutral Earthing Resistor connected to Grounding Transformer 11kV/3 15A 30s

Layout Drawings
NER connected to One-Phase Transformer indoor use

S w e di s h N e u t ral
P1

Legend
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.

Resistor
Local control panel
Mounting holes 10mm
Low voltage bushing for auxiliary and control voltage
Neutral connection M12
Earth connection M12
Rating plate
Lifting lugs
Service hatch
One-phase transformer
Air intake
Air out
High voltage bushing for high voltage cable
Protective Earth

Fjrr / Lok al

Till

Frn

NER connected to One-Phase Transformer outdoor use

Legend
1.
2.
3.
4.
5.
6.
7.
8.
10.
11.
12.
13.

Resistor
Local control panel
Mounting holes 16mm (option wheels)
Low voltage bushing for auxiliary and control voltage.
Neutral bushing Elastimold: Loadbreak/Deadbreak, DIN, Pfisterer
Earth connection M12
Rating plate
Lifting lugs
One-phase transformer
Air intake
Air out
Protective Earth

NER connected to Grounding Transformer indoor use

S w e dis h N e u tral
P1

Legend
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.

Resistor
Local control panel
Mounting holes 10mm
Low voltage bushing for auxiliary and control voltage
Neutral bushing M12
Earth connection M12
Rating plate
Lifting lugs
Service hatch
Grounding Transformer
Air intake
Air out
High voltage bushing for high voltage cable
Protective Earth

NER connected to Grounding Transformer outdoor use

Legend
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.

Resistor
Local control panel
Mounting 16mm (option wheels)
Low voltage bushing for auxiliary and control voltage
High voltage bushing Elastimold: Loadbreak/Deadbreak, DIN, Pfisterer
Neutral bushing M12
Rating plate
Lifting lugs
Grounding Transformer
Air intake
Air out
Protective Earth

NER connected to Arc Suppression Coil

S w e d is h N e u tra l

NER connected to Arc Suppression Coil (oil free)

S w e d is h N e u tra l

Legend
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.

Current transformer (option)


Local control panel
Mounting holes (16mm) (option hjul).
Low voltage bushing for auxiliary and control voltage
High voltage bushing Elastimold: Loadbreak/Deadbreak, DIN, Pfisterer
Earth connection M12
Rating plate
Parking stand
Lifting lugs
Service hatch
Transport lugs
Cable tray (option)
Protective earth
Resistor

Primary Neutral Earthing Resistor

Legend
1.
2.
3.
4.
5.
6.

Resistor
Neutral connection M12
Earth connection M12
Air intake
Air out
Protective earth

Primary Neutral Earthing Resistor 22kV/3 600A 10s

Technical Specification
Voltage
Curent
Operation
Cooling
Frequency
Installation
Auxilliary winding voltage
Insulation
Temperature range
Oil

Up to 70/3 kV
Up to 100A larger sizes on request
Continous or short time (10 s)
ONAN (ANSI/IEE C57.12.00)
Class AA or Class AFA (ANSI/IEE C57.12.01)
50 or 60 Hz
Indoor or outdoor
690 V and 345 V
Depending on voltage (IEC70076-3)
-40 to +40 C, other temperatures on request
Nynas: Nytro Taurus
Starke & Sohn: Transformer Oil U
Midel 7131
Other oils on request