ANR96 IM125-U-A v4.1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 58

ANR96

ELECTRICAL MULTIFUNCTION ANALYZER

abb

ANR96

NETWORK ANALYZER

OK

User Manual
IM 125-U-A v. 4.1

ANR96 IM125-U-A v4.1.doc

ABB
ABB S.p.A. Divisione SACE
Apparecchi Modulari
Viale dell industria, 18
20010 Vittuone (MI) Italy
Tel.: 02.9034.1 Telefax: 02.9034.7609
http://bol.it.abb.com

ANR96 - USER MANUAL


Information in this document is subject to change without notice and does not represent a commitment on the part of
ABB Spa.
This documentation is consigned to the customer to enable the correct and safe operation of the instrument; any
other use of documentation is strictly prohibited.
The information contained herein is the property of ABB Spa, and by law, no part of it may be reproduced,
transcribed, stored in any retrieval system, or translated into any language by means (even for internal purposes by
the customer) without the express written permission of ABB Spa.
In addition, no part of this manual may be transmitted in any form by any means, including photocopying and
recording, for any purposes, without the express written permission of ABB Spa.
In case of Copyright violation the customer is directly responsible.
TERMS OF WARRANTY
The warranty is valid for the period of twelve months after material receipt.
The warranty covers free repair or replacement of equipment parts, which are recognized as faulty due to
manufacturing defects.
Warranty does not cover those parts which results defective due to misuse or improper use, incorrect installation or
maintenance, operation by unauthorized personnel, damage during transportation, or which in any case do not show
manufacturing defects of the equipment.
Not included in the warranty terms are technical interventions regarding equipment installation to electrical systems.
The manufacturer declines any responsibility for eventual injury or damage to persons, animals or things as result of
failure to follow the instructions in the user manual or caused by improper use of equipment.
The expenses of transport as well as the relative risks of same both to and from the place of repair, will be the sole
responsibility of the user.
This warranty expires after the date of purchase and any assistance required after said date including spare parts,
labour, transport of personnel and material will be charged to the user following the tariffs in force for Technical
Assistance Service at the time of such requested service.
In any case the replacement of the equipment as well as the extension of warranty after such breakdown is excluded.

-2-

ANR96 - USER MANUAL

INDEX
1)

MAIN INFORMATION _________________________________________________________5


1.1)

INTRODUCTION _________________________________________________________5

1.2)

DESCRIPTION ___________________________________________________________5

1.3)

CE CONFORMITY AND STANDARDS ________________________________________5

2)

TECHNICAL FEATURES ______________________________________________________6


2.1)

GENERAL SPECIFICATIONS_______________________________________________6

2.2)

MEASURING METHOD AND ACCURACY_____________________________________8

2.3)

PROGRAMMABLE PARAMETERS (SETUP SECTION) __________________________8

2.4)

MEASURED VARIABLES __________________________________________________9

2.5)

CALCULATED VARIABLES ________________________________________________9

2.6)

MEASURING & CALCULATION FORMULAS _________________________________10

3)

INSTRUMENT DESCRIPTION _________________________________________________12

4)

INSTALLATION ____________________________________________________________13
4.1)

SAFETY _______________________________________________________________13

4.2)

OPERATOR SAFETY ____________________________________________________13

4.3)

MOUNTING ____________________________________________________________14

5)

INTERNAL BATTERY________________________________________________________15
5.1)

6)

REPLACEMENT INTERNAL BATTERY ______________________________________15


CONNECTION______________________________________________________________16

6.1)

POWER SUPPLY________________________________________________________16

6.2)

VOLTAGE INPUTS ______________________________________________________17

6.3)

CURRENT INPUTS ______________________________________________________17

6.4)

WIRING DIAGRAM ______________________________________________________17

7)

OPTION BOARDS __________________________________________________________19

8)

INPUTS / OUTPUTS _________________________________________________________20


8.1)
8.1.1)
8.2)
8.2.1)

DIGITAL INPUTS ________________________________________________________20


DIGITAL INPUTS (OPTION)____________________________________________21
DIGITAL OUTPUTS ______________________________________________________22
DIGITAL OUTPUTS (OPTION)__________________________________________23

8.3)

ANALOG OUTPUT (OPTION) ______________________________________________24

8.4)

SERIAL OUTPUTS ______________________________________________________26

8.4.1)

RS485 CONNECTION NOT SHIELDED __________________________________26

-3-

ANR96 - USER MANUAL


8.4.2)

RS485 CONNECTION SHIELDED _______________________________________27

8.4.3)

RS232 CONNECTION ________________________________________________27

8.4.4)

MODEM CONNECTION _______________________________________________28

8.4.5)

OPTION RS485______________________________________________________29

9)

USE ______________________________________________________________________30
9.1)

10)

FUNCTION KEYS _______________________________________________________30


REAL TIME VALUES ________________________________________________________30

10.1)

VISUALIZATION TREE ___________________________________________________31

10.2)

MEASURES VISUALIZATION______________________________________________32

10.3)

STATUS AND INFORMATION PAGES ______________________________________40

11)

SETUP ____________________________________________________________________42

11.1)

SETUP ITEMS __________________________________________________________42

11.2)

MAIN MENU SETUP _____________________________________________________43

11.3)

GENERAL _____________________________________________________________44

11.4)

SERIAL COMM _________________________________________________________45

11.5)

AVERAGE _____________________________________________________________45

11.6)

ENERGY ______________________________________________________________46

11.7)

STORAGE _____________________________________________________________48

11.8)

DIGITAL OUTPUT _______________________________________________________50

11.9)

DIGITAL INPUT _________________________________________________________51

11.10)

ANALOG OUTPUT (OPTION) ____________________________________________53

11.11)

RESET ______________________________________________________________54

11.12)

EXIT SETUP __________________________________________________________54

12)

LIST OF MEASURES ________________________________________________________54

13)

PROBLEMS AND SOLUTIONS ________________________________________________56

14)

ANR SERIAL COMMUNICATION PROTOCOL ____________________________________57

15)

Notes _____________________________________________________________________57

-4-

ANR96 - USER MANUAL

1)

MAIN INFORMATION

1.1)
INTRODUCTION
ANR96 was engineered and tested in compliance with IEC 348 class 1 standards for operating
voltages up to 600 Vac rms, considering the VDE 0110 group C isolation standards for operating
voltages up to 500 Vac rms.
The present manual contains all of the information warnings that must be followed up by the operator
to ensure a right use of the equipment and to maintain the safe operating conditions.
1.2)
DESCRIPTION
The ANR96 is an instrument which has been designed to monitor, store and analyze all electrical
variable in a distribution line.
All the relevant data are displayed and, if desired, stored on internal RAM and transmitted to a remote
PC, via RS485 (standard) on which the compatible management software has been installed.
It is possible to monitor via digital outputs (2 dig. out. Standard + 2 dig. out options) alarms, sirens or
strategically factory loads.
ANR96 with optional harmonic analyzes can carry out network harmonic content analyzes with FFT
st
method up to the 31 harmonic, very useful to locate network disturbances.
The ANR can perform accurate deep and complete energy analyzes.
A fundamental feature of ANR96 is the easy way to integrate new additional options and the
upgrading of the firmware using serial port and flash technology.
All parameters are displayed on a graphic LCD display light-back with a resolution of 128x128 dots.
Displaying and programming mode are carried out by means of a 5 buttons keyboard.
1.3)
CE CONFORMITY AND STANDARDS
The instrument was tested in compliance with EMC 89/336/EEC and complies with the following
standards:
EMISSIONS = EN 50081-2, 1992 - EN 55022-CLASS B CISPR 22
IMMUNITY = EN 50082-1, 1992 - EN 61000-6-2
SAFETY = EN 61010-2

-5-

ANR96 - USER MANUAL

2)

TECHNICAL FEATURES

2.1)

GENERAL SPECIFICATIONS

Power supply/Auxiliary voltage


85-265 V 50/60 Hz/dc.
20-60 V
50/60 Hz/dc (option).
Isolation voltage
3700 Vac rms x 1 minute.
Voltage input
3 inputs, range 10-600Vrms between phase-phase.
Over voltage up to 750 Vac permanent, beyond this value it is imperative to use voltage transformers.
Over voltage category: III (fixed installation)
Pollution degree: 2 (normally not conductive; temporary conductive for condensation)
Resistor input: >2 M.
Burden 0.2 VA.
Current input
3 isolated inputs (internal CT) range
Over current max
Burden

Model ANR96
10mA-5A rms
10A (100A for 1 second)
0.2 VA

Model ANR96-1A
4mA-1A rms
2A (10A for 1 second)
0.04 VA

Consumption
4VA typical.
6VA max, full optional.
Serial output
Standard: 1 output RS485 and 1 RS232 (half duplex isolated, signals Tx/Rx, Gnd).
Option: 1 a second RS485 (the option has an output 0 - 5V galvanic insulation).
Programmable baud rate from 1.200 to 19.200 bps.
Communication protocol: standard ASCII and MODBUS-RTU.
Input signals
Standard: 2 passive opt isolated inputs (1000 V), 12 - 24 Vcc.
Option: 4 passive opt isolated inputs (1000 V), 12 - 24 Vcc (total 6 inputs).
Output signals
Standard: 2 photomos outputs 12-230 Vca-cc / 150mA max or 2 Relay outputs (on request).
Options: 2 photomos outputs 12-230 Vca-cc / 150mA max or 1 analog output 0-20 or 4-20 mA
galvanic insulation.
Memory data retention
RAM: 128 KB (useful 50KB); 1 Mbytes (all useful) option.
No volatile memory data using internal battery
Data retention: 5 years (typical) at +25C (77F).
Stored variables: Average power, Min/max values, Harmonics (option), Samples.
Display interface
128x128 dot graphic LCD at high contrast (adjustable) and with LED backlit. Dimension 50x50mm.
Keyboard interface
5 functional keys for paging and programming.
-6-

ANR96 - USER MANUAL


Operating temperature
From -10C (14F) to +50C (122F).
Storage temperature
From -15C (5F) to +70C (158F).
Operating humidity
90% not condensing.
Protection standards
IP 52 front (EN60529) - IP65 with gasket (on request)
IP 20 screw and terminals
Weight and dimension
0,430 kg app. (equipped with 2 digital outputs, 2 digital inputs, RS485 and RS232, Memory
128Kbytes), 96x96x130 mm.
abb

96 mm

96 mm

ANR96

NETWORK A NALYZER

OK

96 mm

-7-

106 mm

15

ANR96 - USER MANUAL


2.2)

MEASURING METHOD AND ACCURACY

Measuring range
30-500Hz.
Measuring method
64 sampling per period for V1 and I1, V2 and I2, V3 and I3.
Measuring interval 0,1 second.
Instrument accuracy
Model ANR96
Voltage
< 0.5 %
Current
< 0.5 %
Power
<1%
Energy
<1%
Power Factor
<1%
Standard
EN 61036

Model ANR96-05
< 0.25 %
< 0.25 %
< 0.5 %
< 0.5 %
< 0.5 %
EN60687

Sampling frequency
45 Hz=2.280 or at 60 Hz = 3,88kHz
Zero self-regulation
Offset
0,1 second.
RTC - REAL TIME CLOCK
Accuracy: 5 PPM, standard CEI-EN 61038

2.3)
PROGRAMMABLE PARAMETERS (SETUP SECTION)
VT and CT ratio.
Mode, insertion type (4 wires, 3 wires, Aron).
Integration time of Average parameters.
Sampling frequency.
Address or logical number of equipment.
Date and time.
Time-bands of power consumption in different periods.
Storage section (Min/max, Harmonics, average power and Sampling values).
All parameters concerning the input/output section (serial port, analog output, digital input and output).
Preset energy counters.

-8-

ANR96 - USER MANUAL


2.4)
MEASURED VARIABLES
PHASE VOLTAGE (Rms)
LINE CURRENT (Rms)
FREQUENCY
TEMPERATURE

VL1-N - VL2-N - VL3-N


IL1 - IL2 - IL3
FL1 (Hz)
T(C)

2.5)
CALCULATED VARIABLES
LINE VOLTAGE (Rms)
THREE-PHASE SYSTEM VOLTAGE (Rms)

VL1-L2 - VL2-L3 - VL3-L1


V

THREE-PHASE SYSTEM CURRENT (Rms)


AVERAGE THREE-PHASE SYSTEM CURRENT
MAXIMUM AVERAGE THREE-PHASE SYSTEM CURRENT
AVERAGE LINE CURRENT
MAXIMUM AVERAGE LINE CURRENT
NEUTRAL CURRENT
AVERAGE NEUTRAL CURRENT
MAXIMUM AVERAGE NEUTRAL CURRENT

I
Iavg
Imaxavg
IL1avg-IL2avg-IL3avg
IL1maxavg - IL2maxavg - IL3maxavg
IN
INavg
INmaxavg

POWER FACTOR
THREE-PHASE SYSTEM POWER FACTOR

PFL1 - PFL2 - PFL3


PF

COS
THREE-PHASE SYSTEM COS

COS L1, COS L2, COS L3


COS

APPARENT POWER
THREE-PHASE SYSTEM APPARENT POWER
ACTIVE POWER
THREE-PHASE SYSTEM ACTIVE POWER
REACTIVE POWER
THREE-PHASE SYSTEM REACTIVE POWER
AVERAGE ACTIVE POWER
AVERAGE REACTIVE POWER

S L1 - S L2 - S L3 (VA)
S (VA)
P L1 - P L2 - P L3 (W)
P (W)
Q L1 - Q L2 - Q L3 (VAr)
Q (VAr)
PAVG (W)
QAVG (VAr)

THREE-PHASE SYSTEM ACTIVE ENERGY


THREE-PHASE SYSTEM TRANSFERRED ACTIVE ENERGY
THREE-PHASE SYSTEM INDUCTIVE REACTIVE ENERGY
THREE-PHASE SYSTEM CAPACITIVE REACTIVE ENERGY
Total counters and time bands are available.

Wh+
WhVArh+
VArh-

TOTAL HARMONIC DISTORTION - THD (%) CURRENT AND VOLTAGE


HARMONIC ANALYZES (Option)
Analyzes up to the 31st harmonic of both voltage and current for each phase.
VL1-N, VL2-N, VL3-N; IL1, IL2, IL3 (%)

-9-

ANR96 - USER MANUAL


2.6)

MEASURING & CALCULATION FORMULAS


P

Phase Voltage RMS

v 2LiN k

k 1

V LiN

P
P

Line Current RMS

i 2LiN k

k 1

I Li

P
P

Active Power

W Li

vL k iL k
i
iN

k 1

P
P

v L k i L k
i
iN
k 1

Reactive Power

Appearent Power

A Li V LiN I LiN

Cos

cos Li

Power Factor

PF Li

Active Energy

WhLi W Lidt
0

Li

W Li
2
W 2L Q L
i
i

W Li
A Li

-10-

ANR96 - USER MANUAL

Reactive Energy

Qh

Q dt
Li
Li
0
P

Line Voltage

V L ij

3 - Phase Line Voltage

V 3

3 - Phase System Current


3 - Phase Active Power
3 - Phase Reactive Power
3 - PhaseAppea rent
Active Energy
Reactive Energy

v 2Lij k

k 1

P
V L12 V

L 23 V L 32
3

I L1 I

L 2 I L3
3
W 3 W L1 W L2 W L3
Q3 Q Q Q
L1
L2
L3
A3 A L1 A L2 A L3

Wh 3 Wh 3dt
0

Qh 3 Qh 3dt
0
I 3

Harmonic analyzes:
Cooley Tukey algorithm.

H(k)

N1
N1
2 nk
2 nk
h(n) cos
j h(n) sin

N
N
n 0
n 0
for 0 k N - 1

N 64

-11-

ANR96 - USER MANUAL

3)

INSTRUMENT DESCRIPTION

The front panel of the ANR96 is described on the following section:


abb

ANR96

2
N ETWORK ANALYZER

OK

1 DISPLAY
Back lighted graphic LCD 50x50mm, 128x128 dot, dot pitch 0.35mm x 0.35mm, dot size
0.32mmx0.32mm, high viewing direction 60, positive and negative visualization at low reflection.
2 TASTIERA
In the Acquisition Mode the "up" and "down" arrows allows to skip through the measuring page of the
instrument while in the Setup Mode all the buttons including "Enter" key allows to program the
instrument.

-12-

ANR96 - USER MANUAL

4)

INSTALLATION

4.1)

SAFETY

On receipt of the instrument and prior to installation, make sure it is intact and has not been damaged during
shipment.
Before installing, make sure the operating voltage and mains voltage are compatible.
The instrument power supply must not be earthed.
The instrument is equipped with a fuse on the power supply type: 5x20mm 315mA 250V Fast (es. Schurter FSF).

Always disconnect the instrument from all power sources before opening it for maintenance and/or repairs.
The instrument's capacitor may still be charged even after it has been disconnected from all power sources.
Maintenance and/or repairs must only be carried out by qualified and authorized personnel.
If in any doubt about the instrument's safety take it out of service and implement the necessary procedures to
prevent its inadvertent use.
Instrument operation is no longer safe:
A) when the instrument shows clear signs of damage.
B) when the instrument does not work.
C) after long storage in extreme conditions.
D) after serious damage during shipment.

4.2)

OPERATOR SAFETY

Carefully read the following pages before installing and using the purchased instrument.
Maintenance and/or repairs must only be carried out by qualified and authorized personnel.
To ensure proper and safe use of the instrument and its correct maintenance and/or repairs, authorized personnel
must follow normal safety procedures at all times.
SYMBOLS

READ CAREFULLY THE CONTAINED INSTRUCTIONS

-13-

ANR96 - USER MANUAL


4.3)
MOUNTING
The unit needs to be installed on front panel of mains control/switchboards, wiring and connections
must be carried out following the EMC (Electro-Magnetic-Compatibility) procedures.
Plug in screw terminal blocks are used for appropriate wiring. There is a security locking on the current
inputs terminal block.
Suggested is to install the equipment on vibration free switchboards and with an environmental
temperature ranging between -10 C and +50C.
The panel cut-out of the unit is the following:
92mm
abb

ANR96

92mm

96 mm

R3

NETWORK ANALYZER

OK

96 mm
Following the picture below mentioned, insert the instrument from the front side of the switchboard;
from behind insert black support guide on the screw of the instrument, once the black support guide
fits on the screw and is pushed against the instrument and the internal panel, screw the nut until the
instrument is fixed on the panel.

There are n.2 support guides to mount on opposite side of instrument.

-14-

ANR96 - USER MANUAL

5)

INTERNAL BATTERY

To avoid to lose the setup and all storing data, the instrument is equipped of an internal battery
(CR2450).
5.1)
REPLACEMENT INTERNAL BATTERY
Only a qualified and authorized technical person can change the internal battery.
This operation will delete all storing data and it will restore the default setup with the exception of the
password and the code to enable the harmonics and time bands. Using the software NRG (or relative
serial commands) its possible to download all storing data to avoid to losing same.
The next figure shows where is located the battery inside the instrument.
4 WAY PIN STRIP

3 WAY PIN STRIP

Instruction to change the internal battery:


1) Its necessary to cut off the power supply of instrument and to disconnect all inputs and all outputs.
2) Using a screwdriver remove the rear and the frame (to unscrew the 4 screws and to act on 4
retention hook).
3) Its necessary to pay attention to presence of residual voltage inside the instrument. Dont touch
any other component different from the battery circuit.
4) To extract the instrument from the case rear.
5) Its necessary to extract the circuit with the battery. Disconnect the 4 way pin strip. To make this
its necessary to move the battery circuit away from the circuit with 12 pole terminal board; its not
necessary to force too much. Finally extract the 3 way pin strip.
6) Change the battery. Put the positive pole in the high direction.
7) Proceed at the contrary of the disconnected operation to reinstate the battery circuit: insert the 3
way pin strip and after like described at the point 5) reinstate the 4 way pin strip.
8) The 4 pin strip must meet with their relative support.
9) Insert the instrument in the case
10) Replace the frame. Screw the 4 screws. Close the rear. Restore all the connection and turn on the
instrument.
11) In the Warnings page is possible to check the condition of battery (BATTERY OK).

-15-

ANR96 - USER MANUAL

TX

COM

RX

Di1+

Di1-

Di2+

12 11 10

Di2-

Do1+

CONNECTION
Do1-

6)

Do2Do2+

L1V
L2V
L3V

CE

S1 S2 S1 S2 S1 S2

I1

I2

I3

Vaux

6.1)
POWER SUPPLY
The instrument doesnt work without power supply.

Before powering the instrument verify always to insert the right value (85-265 Vac/dc
standard; 20-60 Vac/dc OPTION).

The instrument is equipped with an internal protection fuse on the power supply, type 5x20mm
dimensions, 315mA 250V, Fast (i.e. Schurter FSF). If the instrument is off, with presence of power
supply, its necessary to verify the internal fuse.
In case of fuse replacement, disconnect the instrument from the power supply, current plus voltage
input and all input/output sections (digital input/output, analog output, RS485/RS232 serial port etc.),
then using a screwdriver remove the rear and change the fuse that is near the power supply connector
(in the low part of instrument). Only a qualified and authorized technical person can change the fuse.
Extract the interrupted fuse using a screwdriver and with a plier insert the new fuse.
The instrument's power supply does not require any earth connection.

-16-

ANR96 - USER MANUAL


6.2)

VOLTAGE INPUTS
ANR96 can measure voltages up to a maximum 600 Vrms between phase-phase, further
that value it is imperative to use voltage transformer. When using voltage transformer, make
sure to respect the input and output polarities.

Use cables with maximum cross-section of 2.5mm2 attach them to the voltage measurement screw
terminals.
Connect the instrument following up the wiring diagrams described on chapter 6.4).
ANR96 was developed and tested in accordance with IEC 348 class 1 standards for operating
voltages up to 600 Vac rms.
6.3)
CURRENT INPUTS
Connect the instrument following up the wiring diagrams described on chapter 6.4).

WARNING: before connecting the current inputs to the terminals of the instrument are
advised that the maximum allowable current input must be and not exceed 5A.

WARNING: to prevent accidentally disconnection of the current input, ANR96 is equipped


with screw able current input, in order to avoid negligence, operator must first shutdown the
system and short circuit the secondary wiring of the current transformer, if used, and
unscrews the current input terminals.
WIRING DIAGRAM
+
L1
-

abb

+
L2
+
L3
-

ANR96

L1
L2
L3
N

N ETWO RK ANA LYZE R

OK

L2
L3

S1
P1

LOAD

L1

S2
P2

3 wires insertion, 2 current transformers (Aron)


+
L1
+
L2
+
L3
-

abb

ANR96

N ETWO RK ANA LYZE R

OK

L1
L2
L3

S1
P1

L1
L2
L3
N

LOAD

6.4)

S2
P2

3 wires insertion, 2 current transformers and 2 voltage transformers (Aron)

-17-

ANR96 - USER MANUAL


+
L1
-

abb

+
L2
+
L3
-

ANR96

L1
L2
L3
N

N ET WO RK A NA LYZER

OK

L2

S1
P1

L3
N

LOAD

L1

S2
P2

4 wires insertion, 3 current transformers and 3 voltage transformes


+
L1
-

abb

+
L2
+
-L3

ANR96

L1
L2
L3
N

N ET WO RK A NA LYZER

OK

L2

S1
P1

L3
N

LOAD

L1

S2
P2

4 wires insertion, 3 current transformers

+
L1
-

abb

+
L2
+
-L3

S1
P1

L1
L2
L3
N

N ETWO R K ANA LYZE R

OK

S2
P2

LOAD

L1
N

ANR96

Single fase insertion, 1 current transformer

+
L1
+
L2
+
L3
-

abb

ANR96

L1
L2
L3
N

N ETWO R K ANA LYZE R

OK

L2
L3
N

S1
P1

LOAD

L1

S2
P2

4 wires insertion, 3 current trnsformers and 2 voltage transformers

-18-

ANR96 - USER MANUAL

7)

OPTION BOARDS

The following table shows the right combination of option board:


OPTION
4 INPUTS (Di3Di6)
2 OUTPUTS (Do3, Do4)
RS485 (COM2) (*)
ANALOG OUTPUT (OUT)
RAM

1st Combination
Yes
No
No
No
Yes/No

CONTEMPORARY OPTIONS

2st Combination
No
No
No
Yes
Yes/No

3st Combination
No
No
Yes
No
Yes/No

(*) This module has an output 0-5Vcc.


Only during the assembly of instrument its possible to mount the option board.

-19-

4st Combination
No
Yes
No
No
Yes/No

ANR96 - USER MANUAL

8)

INPUTS / OUTPUTS

8.1)
DIGITAL INPUTS
The ANR96 has 2 opt isolated inputs, power supply from 12 -24Vdc.
+12 24 Vdc

TX

TX

RX

COM

12 11 10

Di1+

Di1-

COM
RX
3

Di2+

Di2-

Di1+

Di2Di2+
Di17

Do1+

Do1-

12 11 10

A
B

Do1Do1+

+12 24 Vdc

Do2Do2+

L1V
L2V
L3V

CE

S1 S2 S1 S2 S1 S2

I1

I2

I3

Vaux

For the digital inputs setup please consult the chapter 11.9).
If long distances must be covered, the wires connected to the ANR96 needs to be wired in a separate
channel from the power supply cables, if an intersection occurs between the power supply cable and
the analog wires, please remember to cross the intersection at 90 degrees, in order to cut the
generated magnetic fields.

-20-

ANR96 - USER MANUAL


8.1.1)
DIGITAL INPUTS (OPTION)
This option has 4 digital inputs.
With this option the instrument will be equipped with 6 digital inputs and 2 digital outputs.
Do2Do2+
COM
Di6
Di5
Di4

12 24 Vdc

Di3

+12 24 Vdc

Do2Do2+
COM
Di6
Di5
Di4
Di3

L1V
L2V
L3V

CE

TX

RX

CO M

Di1 +

12 11 10

Di 1-

Di2 +

TX

COM
RX

Di1+
4

Di 2-

Do 1+

Do 1-

12 11 10

Di2Di2+
Di1-

A
B

Do1Do1+

+12 24 Vdc

S1 S2 S1 S2 S1 S2

I1

I2

Vaux

I3

Do2Do2+
COM
Di6
Di5
Di4

12 24 Vdc

TX

COM
RX
2

L2V
L3V

-21-

S1 S2 S1 S2 S1 S2

I1

I2

Do2Do2+
COM
Di6
Di5
Di4
Di3

L1V

CE

TX

C OM

RX

D i1+

12 11 10

D i1 -

D i2+

D i2 -

D o1 +

D o1 -

Di1+

Di2Di2+
Di1-

12 11 10

Do1Do1+

Di3

I3

Vaux

ANR96 - USER MANUAL


8.2)
DIGITAL OUTPUTS
During the assembly the instrument can be depicted with 2 PHOTOMOS outputs or 2 RELAY outputs.
Each outputs can be programmed as min/max threshold, external band, always ON, and pulse
emission.
Power supply from 12 to 230 Vac-dc, max load 150mA, the typical value of the PHOTOMOS output
resistance ON is 8(RONmax= 12).
The relay specifications are the following:
- Maximum power:
62,5 VA, 30 W
- Maximum voltage:
250 VAC, 220 VDC
- Maximum current:
2A
The typical currents are:
- 0.5A @ 125 Vac
- 2 A @ 30 Vdc
- 0.3 A @ 110Vdc

Di2-

Di2+

Di1-

Di1+

C OM

TX

RX

12 11 10

Do1 -

Do1+

Do1+

Do1 -

Do2Do2+

Do2Do2+

L1V
L2V
L3V

S1 S2 S1 S2 S1 S2

L1

L2

L3

L N

Vaux

The signs + and - on outputs in the picture have electric meaningless.


If long distances must be covered, the wires connected to the ANR96 needs to be wired in a separate
channel from the power supply cables, if an intersection occurs between the power supply cable and
the analog wires, please remember to cross the intersection at 90 degrees, in order to cut the
generated magnetic fields.

-22-

ANR96 - USER MANUAL


8.2.1)
DIGITAL OUTPUTS (OPTION)
This option has 2 digital outputs (PHOTOMOS).
With this option the instrument will be equipped with 2 digital inputs and 4 digital outputs.

Do2Do2+

Di2+

Di1-

Di1+

C OM

L2V

Do3Do3+
Do4Do4+

L3V

S1 S2 S1 S2 S1 S2

L2

Do2Do2+

L1V

L1

TX

Di2-

RX

10

12 11

Do1+

Do1 -

Do1Do1+

Do3Do3+
Do4Do4+

L3

L N

Vaux

-23-

ANR96 - USER MANUAL


8.3)
ANALOG OUTPUT (OPTION)
The analog output is optional. See the chapter 11.10) to program it (0-20mA or 4-20mA). In this
configuration the instrument will be equipped with 2 digital inputs, 2 digital outputs and 1 analog
output.
Output is at galvanic insulation with maximum load impedance of 500. The connection to other
peripherals as recorders, ammeters, remote indicators etc., must be carried out using a maximum
2
cable size of 2.5mm .

020mA
420mA

Max
500

OUT-

TX

RX

Di1+

Di2+

COM

Di2-

Di1-

12 11 10

Do1-

Do1+

OUT+

Do2Do2+

L1V
L2V
L3V

OUTOUT+

CE

S1 S2 S1 S2 S1 S2

I1

I2

Vaux

I3

If long distances must be covered, the wires connected to the ANR96 needs to be wired in a separate
channel from the power supply cables, if an intersection occurs between the power supply cable and
the analog wires, please remember to cross the intersection at 90 degrees, in order to cut the
generated magnetic fields.

-24-

ANR96 - USER MANUAL

4 mA

20 mA

The ANR96 gives a current signal (range 420mA or 020mA) proportional at the measures of the
selected parameter. The output is bi-directional: the current can be directly or inversely proportional to
reference value programmed. Bi-directional means reversal of reference value and not inversion of
current.
Examples:

S = Apparent Power

0 mA
P = Active power

P
0

Max.-1000W

20 mA

12 mA

Min.1000W

4 mA

20 mA

10 mA

Max. 10000VA

Min. 2000VA

P.F. = Power Factor

P.F.
+0,5
20 mA

0 mA

-0,5

Q = Reactive power

Q
Min.-2500VAr

-25-

Max.-7000VAr

ANR96 - USER MANUAL


8.4)
SERIAL OUTPUTS
Through the combination of an asynchronous serial RS485 and RS232 communication line it is
possible to exchange information between the instrument and PC, PLC or other compatible systems.
All transmitted characters are in ASCII (American Standard Code for Information Interchange) format.
RS485 allows a multi-drop connection, in order to link-up several instruments on the same network, on
the other hand RS232 allows a single point connection.
This last connection must be carried out when both systems are turned off and disconnected from the
power line, in order to avoid damages on the serial output.
RS232 may be 9 or 25 pin connection, please follow up the enclosed table:
Signal
DCD
RX
TX
DTR
GND
DSR
RTS
CTS
RI

Description
Data Carrier Detect
Receive Data
Transmit Data
Data Terminal Ready
Signal GrouND
Data Set Ready
Request To Send
Clear To Send
Ring Indicator

DB9
1
2
3
4
5
6
7
8
9

DB25
8
3
2
20
7
6
4
5
22

ANR96
2
1
3

The maximum suggested length of a RS 485 connection is about 1200 mt., while for a RS232
connection about 5 mt.
For longer distances, cables with low attenuation, or connection to line amplifier are recommended.
Up to maximum 32 units can be wired on the same serial line (RS485), exceeding this number it is
imperative to insert a signal repeater, each repeater can manage up to 32 instruments.
The polling time is directly proportional to the instruments number connected on the same serial line.
RS485 CONNECTION NOT SHIELDED

L3V

L N

Vaux

CE

I2

RX

TX

Di1+

COM

Do2Do2+

S1 S2 S1 S2 S1 S2

I1

TX

RX

Di2+

Di1-

Di1+

COM

Di2-

Di2+

10

L3V

I3

L1V
L2V

I2

Di1-

12 11

Do1+

Do1-

TX

L2V

S1 S2 S1 S2 S1 S2

I1

D i2-

Do2Do2+

L1V

CE

Do1 +

12 11 10

Do1 -

RX

Di1+

COM

TX

10

RX

Di2+

Di1-

Di1+

COM

Di2-

Di2+

1 2 11

Di1-

D i2-

Do1 -

Max 32 ANR; max 1200

Do1 +

12 11 10

Do1-

Do1+

RS232/RS485
converter

8.4.1)

I3

L N

Vaux

Once a RS485 network has been configured; to communicate between the Host (computer) and the
instrument(s) (ANR) a serial interface converter must be wired between PC and instrument(s) as
mentioned on the above picture.
In serial line over 500 mt, connect a line termination resistor (Rt=100 - 120) between the two
twisted pair cables leading from the converter at the end of the network (last connected instrument).
Its recommended to use always twisted pair cable with minimum cross-section of 0.36mm2 (22AWG)
and capacity less than 60 pF/m (i.e. BELDEN cable type EIA RS485-Ref.3105A).

-26-

ANR96 - USER MANUAL


8.4.2)

RS485 CONNECTION SHIELDED

RS232
Rt

Max 32 ANR ; max 1200 mt

L3V

L N

CE

Vaux

TX

Do2Do2+

S1 S2 S1 S2 S1 S2

I1

RX

Di1+

COM

TX

RX

L2V

I3

Di2+
8

L1V

L3V

I2

Di1-

10

Di1+

11

CO M

Di2-

12

Di2+

Di1 -

D i2-

Do 1-

Do1+

Do 1+

TX

Do1-

L2V

S1 S2 S1 S2 S1 S2

I1

12 11 10

Do2Do2+

L1V

CE

RX

Di1+

COM

TX

Di2+

Di1-

RX

Di1+

CO M

Di28

Di2+

10

Di1 -

12 1 1

D i2-

Do 1-

12 11 10

Do 1+

Do1+

Do1-

RS232/RS485 B
converter
A

I2

I3

Vaux

Although the signal is given by the difference between A and B voltage, a ground connection is
needed to eliminate or to reduce the common mode noise induced (into the bus).
To reduce the EMI interferences need to connect the shield directly to a ground at one end and with a
series RC network at the other end.
R = 100 C = 33F.
The max length of the stubs is 20cm.
8.4.3)

RS232 CONNECTION

RX

TX

Di1+

COM

TX

RX

Di1-

10

CO M

Di2+

12 11

Di1+

Di2+

Di2-

Di2-

Di1 -

Do 1+

Do 1-

12 11 10

Do1+

Do1-

RS232

Do2Do2+

L1V
L2V
L3V
N

CE

S1 S2 S1 S2 S1 S2

I1

I2

I3

Vaux

If a RS232 communication line is shorter of 5 mt. and a multidrop network will not use, its not
necessary to use a serial line converter because the serial output is compatible with the PC, as shown
on the above mentioned picture.
A RS232 could reach 15mt. but the presence of noises in the industrial application could cause
breakdown in the communication.
The connection from ANR serial port RS232 to PC RS232 serial port is a PTP, Pin To Pin, connection.
SIGNAL
ANR96
DB9 (PC)
TX
1
PIN 2
RX
2
PIN 3
GND
3
PIN 5

-27-

ANR96 - USER MANUAL


8.4.4)

MODEM CONNECTION
ab b

ANR96

N ET W OR K A N ALY ZER

OK

ab b

ANR96

N ET W OR K A N ALY ZER

OK

ab b

Its possible to manage the supervisioning of energy


consumption through remote structures as modem
application in order to cover big distances.

ANR96

N ET W OR K A N ALY ZER

OK

ab b

ANR96

N ET W OR K A N ALY ZER

OK

RS232 RS485

Transmit Data
Receive Data
Signal GrouND

To make the remote connection it needs to program the remote modem (connected to the ANR
network). To program this modem the user has to use any communication program like
HyperTerminal. The Hayes commands to program a standard modem are the following:
AT&D0&S0&C0&R1
ATS0=2
ATX3
AT&W0Y0
The meaning of the commands is the following (AT is the command prefix):
&D0: ignore DTR.
&S0: ignore DSR.
&C0: ignore CD.
&R1: ignore RTS.
S0=2: set at two as the ring number after the which the modem automatically reply (the number can
be different by 2, but it must be different by 0).
&W0: store the configuration in the register 0 of the modems not volatile memory.
Y0: set the configuration stored in the register 0 of the modems not volatile memory as the default
configuration at the starting or the reset of modem.
See the modems user manual.

-28-

ANR96 - USER MANUAL


8.4.5)
OPTION RS485
With this option the instrument will be equipped with 2 digital inputs, 2 digital outputs and 2 serial
ports.

Personal Computer

Modem

L2V

S1 S2 S1 S2 S1 S2

I2

A
B
0V
+5V

L3V

I1

I3

Do2Do2+
A
B
0V
+5V

Do2Do2+

L1V

CE

TX

RX

Di1+

COM

Di2+

Di2-

Di1-

10

12 11

Do1+

Do1-

Rs485

Vaux

-29-

ANR96 - USER MANUAL

9)

USE

9.1)

FUNCTION KEYS

UP & DOWN KEYS


The UP and DOWN keys allows to skip through the real time pages and to
select the programming level or to modify values during the input in the setup
menu.

LEFT & RIGHT KEYS


The LEFT and RIGHT keys allow to visualize the real time sub pages and to
move the cursor in the field of input data in the setup menu. To skip from real
time pages and to go in the menu setup its necessary to press simultaneously
both these keys. To come back at real time pages to repeat the same
operation. Other functions allow to see average values, minimum and maximum, storage and
harmonic components. When its possible to accede at these function two little arrows appear on the
displays bottom bar.

ENTER KEY
ENTER key, if pressed for at least 3 seconds on any of the real time pages
(instantaneous value pages) sets the current visualized page as MAIN PAGE.
In the SETUP menu the ENTER key allows to enter in the setting menu or submenu in
order to program and/or set values and confirm the operation/s.

DISPLAY CONTRAST
It is possible to regulate the contrast of the display directly from the keyboard,
pressing simultaneously the UP key with the ENTER key, the display will
change in lighter. To change the display in darker, it is necessary to press
simultaneously the DOWN key with the ENTER key.

OK
OK
OK

SYSTEM RESET
To reset the unit directly from the keyboard without
entering in the Setup menu (where from there it is also
possible to reset the unit through Reset Global on chapter
11.11), operator may press simultaneously the 4 arrow
keys, after 2 seconds the complete unit will be re-set.

10)

REAL TIME VALUES

The real time pages show all the possible performed measurement of the instrument during the
evolution. All visualized pages may be set as main page by the operator, this means that the preferred
page may be set as the one to be visualized. To set the main page the operator shall press the
"ENTER" key for at least 2 seconds, the symbol of the main page is shown with a "#" on the top right
side of the display. The visualization of real time measure includes a sequence of principal pages, that
its possible to see pressing UP and DOWN keys, and secondary pages that its possible to see
pressing LEFT and RIGHT keys when these symbols ( and ) compare.

-30-

ANR96 - USER MANUAL


10.1)

VISUALIZATION TREE
22
1

3 - Phase
System

L1 Phase

L2 Phase

L1 Phase V-C

L2 Phase V-C

L3 Phase V-C

Phase Voltage

Line Voltage

Line Current

Avg Current

Max
Avg Current

Thd Voltage

Thd Current

K Factor

3 Phase
Powers

Active Powers

Reactive
Powers

Power Factor

Cos

User Page

L3 Phase

Apparent
Powers

Phasor

**

Counters

Average
Powers

10

Total Energies

11

12

TB Energy
2 Months Ago
P1-P2

TB Energy
Previous Mont
P1-P2

TB Energy
Previous Month
P3-P4

13

TB Energy
This Year
P1-P2

14

Total Energy
TB
P1-P2

TB Energy
Today
P1-P2

TB Energy
This Month
P1-P2

15

TB Energy
Today
P3-P4

TB Energy
This Month
P3-P4
TB Energy
This Year
P3-P4

Max.Demand

TB Energy
2 Days Ago
P1-P2

TB Energy
2 Years Ag
P1-P2

TB Energy
2 Days Ago
P3-P4

TB Energy
2 Months Ago
P3-P4
TB Energy
2 Years Ago
P3-P4

TB Energy
Yesterday
P1-P2

TB Energy
Previous Year
P1-P2

TB Energy
Yesterday
P3-P4

TB Energy
Previous Year
P3-P4

Total Energy
TB
P3-P4

Min/Max
3 Phase
Voltage

Min/Max
L1 Voltage

Min/Max
L2 Voltage

Min/Max
L3 Voltage

Min/Max
3 Phase
Current

Min/Max
L1 Current

Min/Max
3 PH Avg
Watt

Min/Max
3 Ph Power
Factor

Min/Max
3 Ph Va
Power

Min/Max
3 Ph Watt
Power

Min/Max
L3 Current

Min/Max
L2 Current

16

THD Volt-Curr

H.V. 20-29

17

IL1
Harmonics

VL1
Harmonics

H.V. 00-09

VL2
Harmonics

18

Clock
Calendar

19

Storage
Avg Powers

Storage
Min./Max

20

Digital
Output

Digital
Input

21

Warnings
Connection

Warnings
Battery

22

Info

H.V. 10-19

VL3
Harmonics

Storage
Harmonics

H.V. 30-31

IL2
Harmonics

H.I 00-09

H.I. 10-19

H.I. 20-29

H.I. 30-31

IL3
Harmonics

Storage
Samples

* options
**Note: Page displayed only if the Digital Input is set
as COUNTER.

-31-

ANR96 - USER MANUAL


10.2)

MEASURES VISUALIZATION

Variable reading of three - phase system


(V - kV) RMS three - phase system voltage [VL-L]
(A - kA) RMS three - phase system current [I]
(W - kW - MW - GW) three - phase system active power [W]
(PF) three - phase system power factor [PF]
(F) frequency L1 [F1]

Variable reading of phase L1


(V - kV) RMS voltage L1 phase [V1]
(A - kA) RMS current L1 [I1]
(W - kW - MW - GW) active power L1[W1]
(PF) power factor L1 [PF1]

Variable reading of phase L2


(V - kV) RMS voltage L2 phase [V2]
(A - kA) RMS current L2 [I2]
(W - kW - MW - GW) active power L2 [W2]
(PF) power factor L2 [PF2]

Variable reading of phase L3


(V - kV) RMS voltage L3 phase [V3]
(A - kA) RMS current L3 [I3]
(W - kW - MW - GW) active power L3 [W3]
(PF) power factor L3 [PF3]

Voltage and current wave forms L1 line


In the L1 Phase V-C page are showed the voltage and current wave forms
with their peak values and crest factors. The wave form of the current has
the lower amplitude.

-32-

ANR96 - USER MANUAL

Voltage and current wave forms L2 line


In the L2 Phase V-C page are showed the voltage and current wave forms
with their peak values and crest factors. The wave form of the current has
the lower amplitude.

Voltage and current wave forms L3 line


In the L3 Phase V-C page are showed the voltage and current wave forms
with their peak values and crest factors. The wave form of the current has
the lower amplitude.

Variable reading of phase voltage


(V - kV) rms voltage between L1 and L2 [V1-2]
(V - kV) rms voltage between L2 and L3 [V2-3]
(V - kV) rms voltage between L3 and L1 [V3-1]
percentage of unbalance phase voltage [Vunb]
Note: the unbalance voltage appears only if its defined in setup.

Variable reading of line voltage


(V - kV) rms voltage L1 [V1]
(V - kV) rms voltage L2 [V2]
(V - kV) rms voltage L3 [V3]
(V - kV) average line voltage [Vavg]
percentage of unbalance line voltage [Vunb]
Note: the unbalance voltage appears only if its defined in setup.

Variable reading of line current


(A - kA) rms current L1 [I1]
(A - kA) rms current L2 [I2]
(A - kA) rms current L3 [I3]
(A - kA) rms neutral current N (showed only with connection 4 wires) [IN]

-33-

ANR96 - USER MANUAL


Variable reading average line, three-phase system and neutral current
(A - kA) rms average three - phase system current [Iav]
(A - kA) rms average current L1 [I1av]
(A - kA) rms average current L2 [I2av]
(A - kA) rms average current L3 [I3av]
(A - kA) rms average current N [Inav]
Note: The average current is calculated in the average time set in the setup.
The average neutral current will be showed only if the insertion type is 4
wires.
Variable reading maximum average line, three-phase system and
neutral current
(A - kA) rms maximum average three - phase system current [Iav]
(A - kA) rms maximum average current L1 [I1av]
(A - kA) rms maximum average current L2 [I2av]
(A - kA) rms maximum average current L3 [I3av]
(A - kA) rms maximum average current N [Inav]
Note: The maximum average current is calculated in the average time set in
the setup. The maximum average neutral current will be showed only if the
insertion type is 4 wires.

Variable reading THD of voltage


(Thd) total harmonic distortion of voltage L1 phase [Thd1]
(Thd) total harmonic distortion of voltage L2 phase [Thd2]
(Thd) total harmonic distortion of voltage L3 phase [Thd3]

Variable reading THD of current


(Thd) total harmonic distortion of current L1 phase [Thd1]
(Thd) total harmonic distortion of current L2 phase [Thd2]
(Thd) total harmonic distortion of current L3 phase [Thd3]

Variable reading K factor


k factor L1 phase
k factor L2 phase
k factor L3 phase

-34-

ANR96 - USER MANUAL


Variable reading three-phase powers
(W - kW - MW - GW) three - phase system active power [P]
(VAr - kVAr - MVAr - GVAr) three - phase system reactive power [Q]
(VA - kVA - MVA - GVA) three - phase system apparent power [S]
(P.F.) three phase system power factor [PF]

Variable reading phase active power


(W - kW - MW - GW) three - phase system active power [P]
(W - kW - MW - GW) active power L1 [P1]
(W - kW - MW - GW) active power L2 [P2]
(W - kW - MW - GW) active power L3 [P3]

Variable reading phase reactive power


(VAr - kVAr - MVAr - GVAr) three - phase system reactive power [Q]
(VAr - kVAr - MVAr - GVAr) reactive power L1 [Q1]
(VAr - kVAr - MVAr - GVAr) reactive power L2 [Q2]
(VAr - kVAr - MVAr - GVAr) reactive power L3 [Q3]

Variable reading phase apparent power


(VA - kVA - MVA - GVA) three - phase system apparent power [S]
(VA - kVA - MVA - GVA) apparent power L1 [S1]
(VA - kVA - MVA - GVA) apparent power L2 [S2]
(VA - kVA - MVA - GVA) apparent power L3 [S3]

-35-

ANR96 - USER MANUAL

Variable reading phase power factor


(P.F.) three phase system power factor [PF]
(P.F.) power factor L1 [PF1]
(P.F.) power factor L2 [PF2]
(P.F.) power factor L3 [PF3]

Variable reading phase cos


(cos) three phase system cos [cos
(cos) cos L1 [cos
(cos) cos L2 [cos
(cos) cos L3 [cos

Phasor (option)
Fresnel diagram.
Phase angles in degree, voltage, current and PF for each line.

User page
The user can define in the setup menu (General-User Page) the variables
to display in this page.

-36-

ANR96 - USER MANUAL

Variable reading counters


This page shows the 8 counters available.
Note: This page appear only if the digital inputs are set like COUNTERS.

Variable reading consumption of active and reactive energy (Normal)


(kWh) positive active energy counter [kWh+]
(kWh) negative active energy counter [kWh-]
(kVArh) inductive reactive energy counter [kVArh+]
(kVArh) capacitive reactive energy counter [kVarh-]
Note: If Energy Type is set like Heavy the measure units are expressed in
MWh and MVArh.

Variable reading average powers


(W - kW - MW - GW) average active power [P]
(VAr - kVAr - MVAr - GVAr) average reactive power [Q]
(VA - kVA - MVA - GVA) average apparent power [S]

Max.Demand
Max demand of each band and total.

-37-

ANR96 - USER MANUAL


Variable reading time-band energy counters (option)
20 pages to display the active energy counters (positive
and negative) and reactive (capacitive and inductive)
divided in 4 programmable time bands (P1 - P2 - P3 - P4).
The 20 pages are: consumption present year and the
two previous, consumption present month and the two
previous, consumption of today and the two day
previous, and total counter of bands.
In a voice of menu setup (paragraph 11.6) its possible
to program times, days and months in which the energy
count is added at the different bands.
External signals, connected to digital inputs, and with a
right programming, can change the bands in the time.
If the energy is Heavy the values are displayed in MWh
and MVArh.

Variable reading MIN & MAX values


12 pages (selected by left and right keys) show minimum and maximum of the value of 12
parameters taken after last reset. Date and time of reading are displayed on these pages.
Its possible to see the values of these parameters:
three - phase system voltage (VL-L)
L1 phase voltage (VL1)
L2 phase voltage (VL2)
L3 phase voltage (VL3)
three - phase system current ()
L1 phase current (IL1)
L2 phase current (IL2)
L3 phase current (IL3)
three - phase system active power (W)
three - phase system apparent power (VA)
three - phase system power factor (PF)
three - phase system average active power (Wav)

-38-

ANR96 - USER MANUAL


Variable reading Thd of voltage and current (harmonics orders option)
A page shows the total harmonic distortion of voltage and of current:
(Thd) total harmonic distortion of voltage L1 phase [Thd1]
(Thd) total harmonic distortion of voltage L2 phase [Thd2]
(Thd) total harmonic distortion of voltage L3 phase [Thd3]
(Thd) total harmonic distortion of current L1 phase [Thd1]
(Thd) total harmonic distortion of current L2 phase [Thd2]
(Thd) total harmonic distortion of current L3 phase [Thd3]
st
8 pages show the harmonic components (up to 31 ) of voltage
and current of each line in numerical form.

Variable reading total harmonic distortion and harmonic components


of voltage and current (option).
st
6 pages of visualization of THD and harmonic components (up to 31 with
fundamental frequency 50-60Hz) of voltage and current of each line
expressed in numerical and graphic form. Once entering in the harmonic
analyzes page, it may be possible with the right + enter & left + enter keys
st
to page through the order of the harmonics up to the 31 . The pages show
the histograms, the order of the harmonic and value referred to the
fundamental.

-39-

ANR96 - USER MANUAL


10.3)
STATUS AND INFORMATION PAGES
The status and/or information pages include:
the displaying of clock and internal calendar
the condition of internal RAM memory
the condition of digital I/O
warnings
general info of the instrument

Clock/Calendar
time format: hours, minutes, second (hh:mm:ss)
date format: day, month, year (dd/mm/yyyy)
day of the week

Condition internal RAM memory


4 pages (selectable with LEFT and RIGHT keys) of information on
condition internal RAM memory.
The internal memory is divided in 4 sections:
storage values average powers [Avg. Powers]
storage values relative minimum and maximum [Min/Max]
storage values harmonic components [Harmonics]
storage values samples [Samples]
Each section is displayed in own sub page.
The page shows the following information:
Type of section of memory (for examples samples).
Status, "ON" if memory enabled or "OFF" if memory disabled.
Record(s), number of stored events in memory.
Memory (Kb)
Available, static memory, expressed in Kb, which is available to store
data for this section.
Used, dynamic memory, expressed in Kb, which is used by data already stored (record stored).
Free, dynamic memory, expressed in Kb, which is free to store data.
Used & Free memory are working together, blocks of memory are transferred from Free memory to
Used memory in order to store the values on the RAM of the instrument. Initially the available memory
will be totally free but at own exhaustion it will be totally used. These information are very important to
avoid to delete stored data, to choose how to storage the data on the basis of available memory.

Digital I/O
The page shows the "ON" "OFF" status of the digital
inputs and digital outputs.
The symbol "---" indicates that none output/input is
present on the hardware (these are inputs / outputs
optional).

-40-

ANR96 - USER MANUAL


Warnings
To see warnings are available 2 pages.
The first page shows the situation of the connection of the instrument,
regarding the connection of current transformer in the current input and the
phase sequence for the voltage input. If at least one of current transformer
is inverted, the display shows Warning TA, otherwise TA OK. If the
sequence of phases at voltage inputs is inverted will appear WARNING!,
otherwise Phases sequence OK. The message No Info, Please Wait
appears during the elaboration to establish the phases sequence.
The information on phase, appears only if the three phase system voltage is
higher of 10V, otherwise the display shows: Low voltage, No Info.
If the voice of menu Setup | General | Warnings is Yes, the warnings page of inversion of current
transformer and phases sequence will be display automatically alternatively at the default page each
time that happens an inversion.
The second page shows the situation of internal battery.
If the voltage level of internal battery is lower of 2.3V on display will appear
Battery LOW, otherwise Battery OK. This page will be displayed
independently of the voice of menu Setup | General | Warnings when the
voltage level is lower of 2.3V.
Warning. If theres no battery or its voltage level is lower than 2.3V the
instrument will lose all storing data in RAM, minimums, maximums, energy
counter, and the setup).

General info
Information page shows the main instrument configuration as model,
firmware version, serial number, inputs/outputs configuration, protocol
communication, etc.
These informations identify the instrument and its configuration before
possible upgrade and for this reason they are very important.

-41-

ANR96 - USER MANUAL

11)

SETUP

11.1)

SETUP ITEMS

GENERAL
KCT

KCT-Pri. (15000)
KCT-Sec. (1;5)

KVT

KVT-Pri. (1400000)
KVT-Sec. (1750)
Mode (4 wires -3 wires -Aron)
B.Light (0360)
Display (Positive-Negative)
DefPage Time (10900 sec.)
SYNC.
Mode(EXT-INT)
Freq. (5500)
CLOCK
Set Clock
Day Light (Enable-Disable)
PASSWORD
Value (00009999)
ACCESS (000000999999)
User Page
Measure 1 (list of parameter)
...............
Measure5 (list of parameter)
V Unbalance (VLL-VLN)
SERIAL COMM
Protocol (ASCII; Modbus)
Address (Modbus: 01255; ASCII: 01128)
COM1
Baud (120019200)
Parity(none-even-odd)
DataBit (7-8)
Type (RS232-RS485)
COM2
Baud (120019200)
Parity (none-even-odd)
Type (RS232-RS485)
AVERAGE
Sync Avg (Int.Rtc-Ext.DI-Int+Ext)
Type (fixed-Mobile)
Time Avg (1-2-3-5-6-10-12-15-20-30-60)
ENERGY
Type (Normal-Heavy)
PRESET
ENERGIES
KWh+ (099999999.9)
KWh- (099999999.9)
KVArh+ (099999999.9)
KVArh- (099999999.9)
COUNTERS
Counter1 (099999999.9)
.........
Counter8 (099999999.9)
TIMEBANDS
Update day (131)
Period Id (0115)
BAND
Start
Month
Day
Stop
Month
Day
WeekDay
Time1
StartHour
StartMin
Type (P1,P2,P3,P4,P5,P6,P7,P8)
.........
Time12
StartHour
StartMin
Type (P1,P2,P3,P4,P5,P6,P7,P8)

HOLIDAYS
Day Index (140)
Month (112)
Day (131)
STORAGE
MIN MAX
Enable (On-Off)
Measures (list of parameters)
Rate-min. (19999)
AVG.POW.Enable (On-Off)
HARM. Enable (On-Off)
TRIGGER
Enable (On-Off)
Time-min. (19999)
DIGITAL OUTPUT
Out Index (16)
Type (AlwaysOff-EnergyPulse-Min.Thresold-MaxThresold-Band-AlwaysOn)
Measure Code (list of parameters)
Value
Time (50500)
Hysteresis (099)
Inf Value
Sup Value
DIGITAL INPUT
Type (Not used, Clock Sync., Period, Counters, Ext.DI)
COUNT->INPUT
K1Dig.Inp. (08)
.........
K8Dig.Inp. (08)
COUNTER NAME
Cnt1(User Def,KWh+,KWh-,
KVarh+,KVarh-,Water,Gas)
.........
Cnt8(User Def,KWh+,KWh-,
KVarh+,KVarh-,Water,Gas)
SET WEIGHTS
K1(01999.99)
.........
K8(01999.99)
ANALOG OUTPUT
Out Index (14)
Type (0-20mA; 4-20mA)
Measure Code (list of parameters)
Min.
Max.
RESET
RESET MEASURES
All (Yes-No)
Energies (Yes-No)
TimeBands (Yes-No)
Min/Max (Yes-No)
Reset Setup (Yes-No)

Reset Global (Yes-No)


EXIT SETUP

Note: Remember always to confirm the entering, exiting or programming always with the ENTER
key, the last modification will be kept in the non volatile memory of the equipment until further reset of
the system.
-42-

ANR96 - USER MANUAL


11.2)
MAIN MENU SETUP
The main menu or SETUP page is configured in the following way:
GENERAL, includes the settings of KCT (current ratio), KTV (voltage
ratio), MODE (4 wires, 3 wires, Aron), MEASURE TIME (time constant of
measure filter), WARNINGS, B.LIGHT (Backlit on display timing),
DISPLAY (positive or negative visualization), DEF. PAGE TIME (time of
wait before to come back to default page), SYNC. (frequency
synchronization), CLOCK (clock settings), PASSWORD (pin-code to
avoid that someone not authorized could modify the setup), ACCESS
(code to enable option function like harmonics and/or time-bands), USER
PAGE (to set the measures to display in user page) and V UNBALANCE.
SERIAL COMM, includes the settings of PROTOCOL (ASCII or MODBUS), ADDRESS (logical
number, node or address), COM1 (serial port 1, integrated), COM2 (serial port 2, expansion board).
AVERAGE, includes the settings of SYNC. AVG (synchronism of calculation average), TYPE (fixed
or mobile), TIME AVG (integration time for the calculation of the average parameters) and DT
MOBILE (sliding time of window mobile).
ENERGY, includes the setting of TYPE (energy counters in kWh or in MWh), PRESET (allows to set
the initial value of total ENERGY counter and the generic COUNTERS) and TIMEBANDS (with all
parameters to manage the power consumption in different periods)
STORAGE, includes the settings of MINMAX (minimum and maximum values storing), AVG.POW.
(the average consumption of active and reactive powers storing), HARM. (harmonic storing up to the
st
31 order for both current and voltage for each line), TRIGGER (start of storing from pulse on digital
input).
DIGITAL OUTPUT, sets the OUT INDEX number of digital output, TYPE (type of alarm; always on,
max. threshold, min. threshold, external band, energy pulse, always off), MEASURE CODE (the
parameter to associate with the digital output), VALUE (the value to set as threshold or, pulse),
TIME (delay time by enabling the digital output or duration of impulse), HYSTERESIS, INFVALUE
and SUPVALUE (lower value and higher value for alarm of external band).
DIGITAL INPUT, sets the type of acquisition: Not used, Clock Synchronization, Periods, Counters
(INPUT, NAME, WEIGHT) or External Synchronization.
ANALOG OUTPUT, set the analog output number, OUT INDEX, TYPE (disable, 0-20mA and 420mA), MEASURE CODE (the parameter to associate at analog output), MIN and MAX (lower value
and higher value of the variable to associate at current output).
RESET, allows to make a RESET MEASURES, RESET SETUP, RESET STORAGE, RESET
COUNTER, RESET MAX DEMAND and RESET GLOBAL.
EXIT SETUP, allows the operator to exit from the main menu or setup page in order to reach the
instantaneous value page. Before exiting the page the instrument will question the operator if he
might to save the STORAGE Setup in case one or more parameters have been modified.
All the above mentioned voices will be described on the following chapters.

-43-

ANR96 - USER MANUAL


11.3)
GENERAL
The general menu is subdivided in the following sub menu:
KCT, allows to set the current transforming ratio setting the primary and
secondary values of the CT, if its used, in order to show the measured
values in primary terms. Primary Range: 15000A; Secondary Range: 1
or 5A (for ANR96-1A is fixed to 1). I.e. Set KCT-Pri.=200 and KCT-Sec.=1
if a CT used is an 200/1 A.
KVT, allows to set the voltage transforming ratio setting the primary and
secondary values of the VT, if its used, in order to show the measured
values in primary terms. Primary Range: 1400000V; Secondary Range:
1750V. I.e. Set KVT-Pri.=20000 and KVT-Sec.=100 if a VT used is an
20000/100V.
Mode, concerns the operation or measuring mode, it is possible to select
4 wires, 3 wires and Aron, following the connection mode as described on
chapter 6.4).
Measure Time, is the filter time in the visualization measure. The range is
050. The 0 value indicates none average on the measures, others
values indicates the average time (in seconds). If this value is very big
and the average powers storing is active, the values stored could be
wrong. Its better to set a value less than 5 seconds.
Warnings, enables [Yes] or disables [No] the visualization every 15 second of the warnings page
alternatively at default page if current transformer connection is wrong or there is an inversion of the
phase sequence. The condition of battery low, it will appear independently of the set of this voice.
B.Light, is the time (from 0 to 360 seconds) in which the display remains on, after the keyboards
inactivity. To hold the display always on, it has to be set the value as 0. The brightness of display
declines about 10% every 1000 hour of work.
Display, its possible to choose between positive visualization (dark characters on clear
background) and negative visualization (clear characters on dark background).
Def. Page Time, is the time of wait before to come back to default page. Range 10900 seconds.
Synchronization, to set the fundamental frequency.
Mode: internal or external (VL1).
Freq.: programmable frequency value (range 5500Hz).
Set Clock, sets the internal clock of the instrument with relative date. The
format of the date is: dd:mm:yy and of the time is: hh:mm:ss
Day Light allow to set the yearly summer time change. Its possible to
enable the time shift of the summer time and the return at the solar time
at the fixed data. The instrument manages the summer time from the
1997 to the 2030.
Password, its possible to set a numeric password to modify the SETUP.
The default password is 0000: the setup can be always opened and its always possible to change
any parameter. If the password is different by 0000 (from 0001 to 9999), at the entrance of setup,
the password will be request. if the password is ignored, it will be possible to see every parameter
but it will be impossible to modify it. Only with the correct password its possible to change every
parameter. To set the new password as 0000, the instrument come back at default status. Call the
constructor to have an emergency password if you lose the password.
Access, allows to input a code of 6 digits to enable the calculation end
the visualization of the harmonics and/or the time-bands. These options
are both enabled if its an H instrument: the code is on a report. These
options are disabled if its an L instrument but one or both can be
enabled. To make this its necessary to give the serial number and the
option(s) to enable at ABB Spa that will send the access code
corresponding at the instrument and the selected option(s).
User Page, select 5 parameters to visualize in the relative page.
V Unbalance calculates the voltage unbalance between the line or phase.
-44-

ANR96 - USER MANUAL


11.4)
SERIAL COMM
The SERIAL COMM menu allows the programming of the communication
parameters of the COM1 and the option COM2.
Protocol, can be chosen between ASCII and MODBUS.
Address, is the address, node or logic number from 01 to 255 in
MODBUS or from 01 to 128 in ASCII. This number identifies the node in a
network and consequently the instrument or the peripheral of a serial
multidrop network.
This parameter is set freely. This parameter is set automatically using
NRG software with ASCII protocol while with MODBUS protocol it must be set.
COM1/COM2, are configured by the following submenus:
- Baud, transmission speed, programmable from 1200 to 19200 bps.
- Parity, parity sequence, programmable NONE-EVEN and ODD.
- DataBit, number of data bits, programmable 7 or 8 bit.
- Type, (only for COM2) is the type of serial output: its defined by hardware and for this reason its
not managed.
The COM1 have two outputs: one as RS232 and the other as RS485 (standard EIA/TIA-422 EIA/TIA485).
The COM2 is optional and only RS485.
11.5)
AVERAGE
The AVERAGE menu allows the settings of parameters in the calculation of
average values.
Sync Avg, defines the type of the synchronism for the start and the stop
of the average calculation. Three mode of use are available:
- Int.Rtc.: use the internal clock as time based line. The average
calculation start when the clock changes the minute.
- Ext.DI: use the digital input 2 (Di2) to synchronize the start and the stop
of the average calculation. The digital input will be set as ExtDI automatically.
- Int+Ext: mixed mode. The digital input will be set as ExtDI automatically.
No congruent operation of digital input type and Sync. Avg will involve the
visualization of the warning message on the display (see for example in
this figure).
Type, defines the type of the window used to the average calculation:
fixed (the updating depends of the Average time) or mobile (the updating
depends of dt Mobile).
Time Avg, integration time for the calculation of the average parameters.
dt Mobile, defines the updating time in window mobile of the average
parameters.

-45-

ANR96 - USER MANUAL


11.6)
ENERGY
In the ENERGY menu its possible to modify the unit of measurement of
energies, to set at the initial value the generic and energy counters, to
manage on the time-bands.
Type, allows to choose the unit of measurement for the energy counter
kWh (Normal) or MWh (Heavy).
PRESET, allows to set at initial value the energy counters and generic
counters.
- ENERGIES, its possible to set energy total counters at initial value.
These values are expressed in kWh and kVArh; the visualization on
total energies page will be congruent with the type of energy (Normal or
Heavy). The time bands counters dont consider the preset values. Only
total energy counters consider these values.
This function is useful for example to compare the consumption with an
energy counter already in use.
- COUNTERS, its possible to set the 8 generic counters at initial value.
TIMEBANDS, it possible subdivide the energy consumption in 12 time
bands. In this way its possible to value the energy costs where the
energy suppliers apply the time band tariff or its necessary to divide the
consumption in different period. To program the time bands function to
accede at the TIMEBANDS menu with the following sub menu:
- Update day, sets the day in which change the month in the time bands
(range 031). If the value is 0, from the last day of each month the
energy is increased in the counter of the next month. If the value is
between 1 and 15, from the day fixed the energy is increased in the
counter of the actual month, before of this value the energy is increased
in the previous month. If the value is between 16 and 31, from the day
fixed the energy is increased in the counter of the next month, before of this value the energy is
increased in the actual month. If the actual month has fewer days than the value fixed, the energy
will be increased into the next month counter from the last day of the month.
- Period Id, period number. 15 periods to set different time bands. For each period its possible to
program:
- BAND, to program the selected period.
- Start / Stop, to program the start and the stop of the selected period.
Month, is a number from 1 to 12 that defines the months (1 January,
2 February, ecc.) of the year corresponding at the start (or the end) of
the selected period.

Day, is a number from 1 to 31 that defines the day of the month


corresponding at the start (or the end) of the selected period.
The programming is the same of the month programming.

-46-

ANR96 - USER MANUAL

WeekDay, defines the days of the week in the selected period in which
the tariff programming is active.
Use the LEFT and RIGHT keys to select the day of the week and the
UP and DOWN keys to enable or disable the day.

Time (1 - 12), defines the time of the day in which the energy counters
are subdivided in the 4 time bands P1, P2, P3, P4, to set the time
bands are available 8 different times.
Inside the Time its possible to set the hour (StartHour) and the
minutes (StartMin.) in which the time band starts. Select Type, insert
the band P1, P2, P3 or P4 to link at the consumptions.
The set band will finish when another band will start or at the end of the
day. For example if the energy consumption from 8.00 to 12.00 are in
the band P2 and from 12.00 to 18.00 in the band P3 its necessary to
set 8.00 like start time (StartHour and StartMin) in TIME 1 with band P2
(Type), 12.00 like start time (StartHour and StartMin) in TIME 2 with band P3 (Type) and 18.00 like
start time (StartHour and StartMin) in TIME 3 with band P1 (Type); in this way the P1 band will
maintain until 8.00 of the day after without other programming.
P1 band is the most economic and the P4 band is the most expensive.
HOLIDAYS
Its possible to program the days in the year in which the time bands
programmed are not used and the energy consumption end up in the
economic band (P1). This function can be useful in holiday or in days in
which the energy suppliers apply different tariff of others days.
Its possible to program:
Day Index, allows to set 52 different days like holidays. After the index,
define the day of the year.
Month, is the month of the day in programming. One number from 1 to 12
defines the month (1 January, 2 February, etc.)
Day, is the day of the month corresponding at the holyday: from 1 to 31.
Example:
New years day 1 January
Day index = 1
Month = 01 (January)
Day = 01
Christmas 25 December:
Day index = 2
Month = 12 (December)
Day = 25
The consumption of this special feature, if used, will be saved, always, into the tariff P1.

-47-

ANR96 - USER MANUAL


11.7)
STORAGE
The STORAGE menu allows the programming of the data to store. 4
archives of storing exist:
- relative minimums and maximums
- average powers
- harmonic components
- samples (only with NRG software or serial command)
The storage is organized as FIFO (first in first out) type memory. When the
memory is full older data will be overwritten by new data.
MINMAX
The acquisition time is expressed in minutes, up to 12 MIN & MAX values
are stored.
Enable, confirming the ENABLE voice the operator may enable (ON) or
disable (OFF) the acquisition of MIN & MAX values.

Measures, parameters to store.


Select the variable to store in the minimums and maximums with the
LEFT and RIGHT keys, enable or disable this variable with UP and
DOWN keys.

Rate min., acquisition time.


This is the acquisition time of minimum and maximum values: range 1
9999 minutes. For example to store the minimum and the maximum value
of programmed parameters each 15 minutes its necessary to set 15.
If the storing of minimum and maximum values is enabled the values shows
in the relative page are updated at the same acquisition time set for the
storing in memory. Minimum and maximum values are not absolute any more.
AVG.POW. (Average Power)
Storing of average active and reactive power. Its possible to enable or disable the storing. The
sampling time is set at 15 minutes but its modifiable (Time Avg).
HARM. (Harmonics)
st
Up to the 31 harmonics are stored for each line both of voltage and current channels.
Enable, the operator may enable or disable the storing of harmonic values.
The sampling time is fixed at 15 minutes and its not modifiable.

-48-

ANR96 - USER MANUAL


TRIGGER
Enable, the operator may enable or disable the TRIGGER function.
If Enable is OFF the enabled archives store the measures with the
relative rate, all of time.
If Enable is ON, the enabled archives store the measures with the
relative rate only after the receiving of a pulse on digital input 2 (DI2). The
storing will be active for the set time in Time-min. If there is no enabled
archives the trigger function has no effect.
Time-min. defines when the storing time is active.
With a logic level 1 (voltage present) on the digital input 2 (DI2) the timer relative to Time-min will be
reset and the storing enabled. Only when the signal go down, the counting starts. The range is
19999 minutes and the default value is 60 minutes.

No congruent set between TRIGGER storage enabled and Type of the


digital input will involve the visualization of the warning message on the
display (see for example in this figure). An affirmative answer will enable
the TRIGGER function and the setting of the digital input will be set to Not
Used.

If any of the above mentioned parameters relative to MINMAX, AVG.POW.


and HARM. has been enabled for storage, by exiting the setup menu a brief
message will appear, asking the operator to erase all the previous stored
data, in the memory, in order to enable a new recording campaign at empty
memory with no residual informations.
The data downloaded on PC using NRG software or communication
protocol does not come deleted and for this reason its possible to recover
them using the function of communication protocol.

-49-

ANR96 - USER MANUAL


11.8)
DIGITAL OUTPUT
The digital outputs can be programmed to function like alarm (overload,
load management for consumption optimization, etc.), or pulses emission
for energy calculation or remote activation using software NRG.
Out Index, expresses the number of output, from 1 to 6 (DO1 and DO2
standard), to select or program, which are present on the hardware of the
instrument.
Type, allows to select the type of functioning as:
- Always Off: digital output is always disabled.
- Energy Pulse: pulse emission proportional at energy registered and depending the programming
used (valid only for Energies).
- Min. Threshold: the output is enabled if the value of the selected variable is lower of the
programmed value.
- Max. Threshold: the output is enabled if the value of the selected variable is higher of the
programmed value.
- Band: the output is enabled if the value of the selected variable is lower of the programmed
minimum value or higher of the programmed maximum value.
- Always On: digital output is always enabled.
Measure Code, is the measure (see cap.12) to associate at the digital output. To program the digital
output as pulse emission its necessary to select an energy variable.
Value, intervention threshold value (i.e., for overcoming 340V program 340.0, or 150kW program
150000,0) or pulse weight (i.e., if the active positive energy pulses must be emitted every 1 kWh
program 1.00) programmable from 0,01 to 100 kWh/pulse.
Time, is the threshold delay for intervention expressed in second (0-655 seconds) or duration time
of Pulse expressed in milliseconds (50-500 ms).
Hysteresis, its the percentage of alarms value under which the alarm come back in off condition:
its programmable from 0 to 99% (example: max threshold of active power at 150kW with 10%
hysteresis means the alarm come back in off condition when the active power will be 15015=135kW). Its not available in Pulse mode.
InfValue and SupValue, low limit and high limit of alarm in band way.
Note: digital output management for P.F.-cos.
In the P.F. and cos the absolute minimum is considered the 0 capacitive and the absolute maximum
the 0 inductive.
To set an alarm when the cos is less than e.g. 0.9 inductive (in the direction of 0 inductive) its
necessary to set MAX threshold mode. Instead of this, to set an alarm when cos is more than e.g.
0.9 inductive (in the direction of 0 capacitive) its necessary to set MIN threshold mode. In BAND mode
there will be alarm when the cos value will be extern to the set band (infvaluesupvalue): the infvalue
must be the value nearest at the 0 capacitive.
Example:
IND

0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1

Min threshold
0

-0.1 -0.2 -0.3 -0.4 -0.5 -0.6 -0.7 -0.8 -0.9


CAP

-1
IND
1

0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1

Max threshold
0

-0.1 -0.2 -0.3 -0.4 -0.5 -0.6 -0.7 -0.8 -0.9

-1

CAP

IND
1

Band
0

-0.1 -0.2 -0.3 -0.4 -0.5 -0.6 -0.7 -0.8 -0.9


CAP
ON

OFF

-50-

-1

0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1

ANR96 - USER MANUAL


11.9)
DIGITAL INPUT
In the DIGITAL INPUT menu its possible to program the digital input
function for both standards and options. The 2 standards digital input can
be programmed how follow:
Type, defines the type of operation:
- NOT USED: if none input is selected or enabled.
- CLOCK SYNCRONIZATION: Synchronization of the internal clock.
When the impulse arrives on digital input, the internal clocks seconds
counter is cleared if its between 00 and 29, while if its between 30 and
59, its cleared and the minutes counter go on the next minute.
Example:
17:31:23 (hh:mm:ss) will be 17:31:00
08:45:55 (hh:mm:ss) will be 08:46:00
- PERIOD: to change the bands for the energy counter with time bands.
The following table shows the time band selected depending of the status of digital inputs:
DIGITAL INPUT 2
DIGITAL INPUT 1
BAND SELECTED
OPEN
OPEN
P1
OPEN
CLOSED
P2
CLOSED
OPEN
P3
CLOSED
CLOSED
P4
CLOSED: there is a voltage from 12Vcc and 24Vcc.
OPEN: the voltage is 0Vcc.

The change of band happens when the instrument recognizes a change of status on one of digital
input at least.
At the moment of the digital inputs enabling like Periods and at the ANRs turn on with the
enabling already set, the energy counters increment continue on the last band enabled
independently of the digital inputs status until the change of the minute of the internal clock or the
change of the status of one of digital input.
- COUNTERS: the generic counters are enabled. When an input receives a pulse, the counter,
joined at this input, is increased by the value that depends of the weight set.
- Ext.DI: the function depends of the Sync. Avg set in the menu AVERAGE (par. 11.5). If Sync. Avg
is Int.Rtc a signal (1224Vcc) on the digital input 1 change the band (from P1 to P2 and vice
versa) while a signal (1224Vcc) on the digital input 2 is used to synchronize the average and the
average powers storing (if enabled) with a de-bounce time of 30 seconds. The digital inputs are
set automatically to Ext.DI if the Sync. Avg is set to Ext.DI or Int+Ext.
No congruent operation of digital input Type and Sync. Avg will involve
the visualization of the warning message on the display (see for example
in this figure). An affirmative answer will confirm the new setting on the
digital input and the setting of Sync. Avg to Int.Rtc.

No congruent set between the Type of digital inputs and the TRIGGER
storage will involve the visualization of the warning message on the
display (see for example in this figure). An affirmative answer will confirm
the new setting on the digital input and the disabling of the trigger storage
function.

-51-

ANR96 - USER MANUAL

An item selected in the menu TYPE of the digital inputs will be accepted
only if the reset of the counters is confirmed.

Count. => Input, define the correspondence between the index of the
counter and the digital input. Its necessary to set the index of the digital
input to join at each counter used. The counter isnt able to count if the
index inserted is 0.
Note: Its possible to join the same input at more counters.

Counter Name, allows to define the name for each counters. Using the
up and down keys its possible to choose the counter that will be
selected with the Enter key. In the same way its possible to choose and
set the name of the counter. The first item allows to set a user definition,
the others are names already fixed.
- USER DEF. The name of the counter is defined by the user.
When this item is selected, a field appear to input the name of the
counter. To input the name its necessary to use the right and left
keys to select the type to modify, while its possible to use up and
down keys to change it.
Pressing the up key, the sequence of the type is the following:
ABCDEFGHIJKLMNOPQRSTUVWXYZabcdefghijklmnopqrstuvwx
y z SPACE 0 1 2 3 4 5 6 7 8 9; then the sequence begin from A again. Naturally, pressing the
down key the sliding happen on the contrary.
- kWh+
- kWh- kVArh+
- kVArh- Water
- Gas
Set Weights, allows to set, for each counter, the weight of the pulse. The
value set is the number of pulse for unit of increase of the counter (ex. to
see to increase the counter of one unit each 5 pulse, its necessary to set
the value 5).

-52-

ANR96 - USER MANUAL


11.10) ANALOG OUTPUT (OPTION)
Selecting the analog output voice, the following programming page
appears:

Out Index, expresses the number of output to select or program, which


are present on the hardware of the instrument.

Type, allows to select the value of current output, (disabled, 0-20mA, 420mA).
Through the up & down keys, it may be possible to select the type of the
output current, by pressing the ENTER key the configuration is saved.

Measure Code, is the measure (see cap.12) to associate at the analog


output.

Min., full-scale value of the lower limit of the programmed value (Measure
Code).
Once the minimum full-scale has been programmed, the instrument
automatically will associate the minimum current value (0 or 4 mA) at this
value.

Max., full-scale value of the upper limit of the programmed value


(Measure Code).
Once the maximum full-scale has been programmed, the instrument
automatically will associate the maximum current value (20 mA) at this
value.

If the minimum end-scale value is lower of maximum end-scale value, the out of current will be directly
proportional at variable set, otherwise it will be inversely proportional. Minimum and maximum can be
negative value.
-53-

ANR96 - USER MANUAL


11.11) RESET
The Reset page allows to cancel some operation or the complete operation
of the setup system, reset modes are classified in four groups.
RESET MEASURES, reset all values or selected group of measure. In
particular:
All, reset all of measures (minimum and maximum, energy counter, time
bands).
Energies, reset total energy counters.
TimeBands, reset time bands.
Min/Max, reset minimums and maximums.
Reset Setup, delete all definition in the setup and the instrument come
back to default setup.
Reset Storage, delete all data stored in the memory.
Reset Counter, delete all counters joined at digital inputs.
Reset Max.Demand, delete max demand values.
Reset Global, reset complete of the instrument (Setup, measures stored,
RAM).
11.12) EXIT SETUP
The last voice of the setup menu is EXIT SETUP, which allows the operator to leave the instrument
setup and go back to the REAL TIME VISUALIZATION PAGES.
Operator may also exit the setup by pressing simultaneously the RIGHT & LEFT button one or more
time depending of the branch in which you are.

12)

LIST OF MEASURES

To program the variables in setup for:


- digital outputs (alarm and pulse)
- analog outputs
its necessary to use these codes:
3Ph.V

Three-phase voltage

L1N V
L2N V
L3N V

L1 phase voltage
L2 phase voltage
L3 phase voltage

L12 V
L23 V
L31 V

Voltage between L1 and L2 phases


Voltage between L2 and L3 phases
Voltage between L3 and L1 phases

3Ph.I

Three-phase current

L1 I
L2 I
L3 I

L1 phase current
L2 phase current
L3 phase current

THDI L1
THDI L2
THDI L3

THD current L1 phase


THD current L2 phase
THD current L3 phase

3Ph.PF

Three-phase power factor

L1 PF
L2 PF
L3 PF

L1 phase power factor


L2 phase power factor
L3 phase power factor
-54-

ANR96 - USER MANUAL


3 Ph.Cos

Three-phase Cos

L1 Cos
L2 Cos
L3 Cos

L1 phase Cos
L2 phase Cos
L3 phase Cos

3Ph.VA

Three-phase apparent power

L1 VA
L2 VA
L3 VA

L1 phase apparent power


L2 phase apparent power
L3 phase apparent power

3Ph.W

Three-phase active power

L1 W
L2 W
L3 W

L1 phase active power


L2 phase active power
L3 phase active power

3Ph.VAr

Three-phase reactive power

L1 VAr
L2 VAr
L3 VAr

L1 phase reactive power


L2 phase reactive power
L3 phase reactive power

3Ph.Wh+
3Ph.VArh+
3Ph.Wh3Ph.Varh-

Three-phase positive active energy


Three-phase inductive reactive energy
Three-phase negative active energy
Three-phase capacitive reactive energy

THDV L1
THDV L2
THDV L3

THD voltage L1 phase


THD voltage L2 phase
THD voltage L3 phase

Avg.W
Avg.I
Avg.Var

Average three-phase active power


Average three-phase current
Average three-phase reactive power

Temp.

Temperature

L1Avg.I
L2Avg.I
L3Avg.I

Average current L1 phase


Average current L2 phase
Average current L3 phase

Neutr.I

Neutral current

Vunb
Iunb

Voltage unbalance
Current unbalance

KFact1
KFact2
KFact3

L1 phase K factor
L2 phase K factor
L3 phase K factor

-55-

ANR96 - USER MANUAL

13)

PROBLEMS AND SOLUTIONS

If you have a problem setting up or using your instrument, you may be able to solve it yourself.
Before calling your retailer or nearest distributor you should try the suggested actions that are
appropriate to your problem.
Problem
The instrument doesnt turn on.

Possible cause
- The power supply is
disconnected or wrong.
- The internal fuse is interrupted.

The display is completely dark


or clear.

- Contrast badly adjusted

The instrument doesnt


communicate with the NRG
software (or other
communication software).

- Communication wires.
- Communication protocol.
- Wiring system and
communication parameters.

The instrument communicates


with the PC but the
communication is interrupted.
The instrument loses the CODE
or the PASSWORD.

- Not shielded wires.


- Lack of terminations.
- E2prom lost data.

Suggested
- Verify the connection and the
presence of power supply.
- See the chap. cap. 6.1) to
verify and/or to change the
internal fuse.
- Adjust contrast as described
on 9.1)
- Verify the correct wiring.
- Verify that the communication
protocol of the instrument
coincides with the one used in
the sw.
- Verify the wiring type (RS232
or RS485) and the settings of
the serial port of the instrument.
- Use shielded wires.
- Connect terminations as par.
8.4.1) and 8.4.2).
- to try again to input another
time the data lost.

If the problem have not been solved, or for other information not covered in the present manual,
please contact with our Technical Assistance Department.
Before contacting, it is suggested to collect the maximum information regarding the installation, and
mainly the following data:
1.
2.
3.
4.

Model and serial number from the label on the top of the instrument housing.
Purchase receipt.
Description of problem.
System configuration (hardware fitted, firmware release etc.).

-56-

ANR96 - USER MANUAL

14)

ANR SERIAL COMMUNICATION PROTOCOL

The Electrical Multifunction Analyzer ANR series are disposal with two communication standard
protocols:

ASCII

MODBUS-RTU
and optional

PROFIBUS with external module

TCP/IP Ethernet with external module


The standard communication protocol has been optimised for the connection of the analysers with the
NRG management software, allowing to use all the available functions (automatic search of the unit in
the network, automatic data downloading, etc.).
Even so the NRG software supports the MODBUS protocol.
About all the information of protocols communication to see specific user manual (ANR SERIAL
COMMUNICATION PROTOCOL).

15)

Notes

WARNING: ABB Spa declines all liability for any damage to people or property caused by improper or
incorrect use of its products.
ABB Spa reserves the right to change product specifications without prior notice.
-57-

ANR96 - USER MANUAL

ABB
ABB S.p.A. Divisione SACE
Apparecchi Modulari
Viale dell industria, 18
20010 Vittuone (MI) Italy
Tel.: 02.9034.1 Telefax: 02.9034.7609
http://bol.it.abb.com
-58-

You might also like