Vacon X5 DeviceNet Board Installation Manual DPD00
Vacon X5 DeviceNet Board Installation Manual DPD00
Need Help?
This manual answers most installation and startup questions
that may arise. However, if you have any problems,
please let your first call be to us.
Vacon, Inc.
Chambersburg, PA 17202
Normal business hours:
(North America)
and Vacon, Inc. are trademarks of Vacon Plc, a member of Vacon Group.
All other product names are trademarks of their respective companies.
vacon
Applicable Documents
This manual is supplied as a supplement to the X5 AC Drive Users Manual (DPD 00089, previously Form 1434).
Description
25100064C
32100391
vacon
Installation Procedures
!
WARNING
SENSITIVE EQUIPMENT
This assembly contains static-sensitive components. It should be handled only by a static-safe installer,
using a grounded wrist strap.
Failure to observe this precaution may cause premature equipment failure.
DANGER
HAZARDOUS VOLTAGE
Disconnect all power before servicing a drive unit or its components. WAIT 5 MINUTES until the DC
bus capacitors discharge.
Ensure that any other power sources that may feed control logic have been disconnected.
DO NOT short across DC bus capacitors or touch unshielded components or terminal strip screw
connections with voltage present.
Install all covers before applying power or starting and stopping the drive.
The user is responsible for conforming to all applicable code requirements with respect to grounding
all equipment.
Many parts in a drive, including printed circuit boards, operate at line voltage. DO NOT TOUCH. Use
only electrically-insulated tools.
Before servicing any drive.
Disconnect all power.
Place a DO NOT TURN ON label on the drive disconnect.
Lock the disconnect in the open position.
Failure to observe these precautions will cause shock or burn, resulting in severe personal injury
or death.
Figure 1 shows the layout of the option board and the location of important components on it.
vacon
Switch 7-6
Set Baud Rate
Switch 5-0
Set MAC / Node Address
DeviceNet
Terminal Block
Before you can install the option board, you must first remove the drive cover.
Figure 2 shows the locations of the cover screws. The torque range for the X5 Size 1 cover is 18-26 in/lbs.
vacon
The option board is installed just above the control board in all configurations (a Size 1 unit is shown in Figure 3 for
reference). The screws labeled A must be removed from the X5; those labeled B need only to be loosened to
accept the board slot.
.
vacon
Next, install the flexible circuit to finish the interface to the control board. (Refer to Figure 4.) To install the flexible
circuit, first remove the keypad frame (necessary in this size unit). The frame is attached with two screws in opposite
corners; the screws thread into fasteners in the plastic assembly. After the flexible circuit is installed, replace these
screws, limiting the installation torque to 12 in-lbs..
The option kit includes five 115 VAC inputs, two additional programmable relays, and an encoder interface. The
details of the terminals on the board related to the 115 VAC interface and the encoder are shown in Table 1 on
page 7:
Table 1: Encoder Interface Terminals
Terminal
Description
vacon
DI-A
DI-B
DI-C
DI-D
DI-E
ACn
NO3
RC3
NC3
NO4
RC4
NC4
A+
A-
B+
B-
C+
C-
VDC
Ecom
Note that the connections described in Table 1 work only when the encoder has an internal pull-up resistor on the
open collector. Alternatively, it might be preferable to pull the + channel high, and attach the open collector to the channel. For example, if using Channel A, A+ on the option board would be tied to VDC, and A- would be connected
to the open collector coming from the encoder. The advantage in this method is that no pull-up/down resistors are
needed; if the encoder has an internal pull-up, this does not affect anything.
vacon
On state
100 kHz
Off state
< 10 VAC
Input voltage
Input frequency
58-62 Hz
Suggested pull-up
resistor
Terminal block wire
limitations
5 VDC
500 ohms
12 VDC
1k ohms
24 VDC
3.3k ohms
12-24 AWG
90-140 VAC
On/off delay
30 ms maximum
12-24 AWG
(1) PID feedback plus optimal motor turning in SLV mode employed
Parameter Name
Range
Default Value
219
0-16383
1024
220
10-1000 ms
20 ms
221
0-20.0%
0%
Parameter 219, Encoder Pulses per Revolution, can either be extracted from the encoder nameplate or the data
sheet supplied with it. Parameter 220, Encoder Filter Time, is used to filter the encoder signal in the event of noise.
Parameter 221 is for limiting the response of the drive, in the event of the loss of encoder signal.
Two other parameters are provided to allow more flexibility in encoder selection, and to improve PID application
usage:
Parameter #
Parameter Name
Range
Default Value
EncoderType
Quadrature
or Single
Channel
Quadrature
223
224
Encoder Range
0-24000 rpm
0 rpm
Parameter 223, Encoder Type, allows the use of either quadrature or single-channel types of encoders.
Parameter 224, Encoder Range, improves PID application flexibility. This parameter should be used in situations
where the encoder feedback signal is not always directly proportional to the motor speed, for example, a winder
using an encoder mounted on an idler pulley feeding a winding spool. The PID may be attempting to maintain a
constant linear speed on the wound media, but as the diameter of the media on the spool changes, the motor
turning the spool needs to vary its speed to maintain the linear speed at the idler pulley.
When parameter 224 is set to 0, it is ignored, and the PID calculates the feedback percentage based on parameter
301, Maximum Frequency. When this parameter is set to a non-zero value, the PID uses instead Parameter 224s
setting to calculate the feedback percentage.
Encoder feedback works similarly to an analog input as configured in parameters 850 (PID Configure), 851 (PID
Feedback), 852 (PID Prop Gain), 853 (PID Int Gain), and 859 (PID Derivative Gain). The feed forward options are
suggested for setting parameter 850. More specific details on each of the listed parameters can be found in the X5
Users Manual (DPD 00089).
10
vacon
The encoder interface can easily serve as one of the inputs to the X5s Keeper Function (data logging). See the X5
Users Manual for more information.
Both the Vmet and Imet output from the drive can be configured to indicate the status of the encoder. Parameters
700 (Vmet) and 702 (Imet) that relate to the setup and calibration of the Vmet and Imet outputs, both have selections
related to the status of the encoder input.
The Program Sequencer function can also key off the encoders home pulse. To make use of this function, the
encoders home pulse (1 pulse per revolution) must be connected to the C- input of the encoder board.
DeviceNet
Connections
Communications
Interface
CAN
Transfer cable
Isolation
500 VDC
Baud rate
Product code
0x03 (X5)
Product type
Vendor ID
509
Device Net
Other
Network size
Network length
Up to 64 nodes
Selectable end-to-end network distance varies with speed
Baud rate
Distance
125 Kbps
500 m
250 Kbps
250 m
500 Kbps
100 m
Data packets
0-8 bytes
Bus topology
Linear (trunkline / dropline); power and signal on the same network cable
Bus addressing
System features
vacon
11
Figure 6: Thick or thin cable can be used for either trunklines or droplines
The X5DNET01 DeviceNet board is connected to the fieldbus through a 5-pin pluggable bus connector. (See Figure
1 on page 5 for the location of the bus connector.) Communication with the control board of the frequency converter
takes place through the flexible circuit applied last during the installation process.
DeviceNet Terminals
Table 4 describes the DeviceNet terminal assignments:
Table 4: DeviceNet Terminals
Terminal
Description
Signal Reference
V-
CAN_L
Drain
CAN_H
V+
12
vacon
LED Indications
The DeviceNet Option Board includes two LED status indicators: Network Status and Module Status. See Figure 1
on page 5 for the location of these LEDs on the board. Network status provides information on the network
connection status and module status provides information on the DeviceNet module itself. The following tables
explain the meaning of the status LEDs:
Table 5: Network Status LED
Network Status
LED
This means...
OFF
Green
Green (flashing)
Red (flashing)
Red
This means...
OFF
Green
Module Status
LED
Green (flashing)
Red (flashing)
Red
Baud Rate
Switch 7
Switch 6
125K
250K
500K
500K
The MAC ID is a 6-bit digital value (ranges from 0-63) controlled by switches 0-5. Switch 5 is the most significant;
switch 0 is the least significant.
Note: If power is applied to the option board before the value of the baud rate or MAC ID is changed, power must be
cycled before the new settings take effect.
vacon
13
I/O Messaging
Explicit Messaging
I/O Messaging
Input / Output (I/O) polling messages are for time-critical, control-oriented data. The messages are transferred
between the devices all the time and are used for continuous control of the frequency converter. They provide a
dedicated, special-purpose communication path between a producing application (master) and one or more
consuming applications (slaves). They are exchanged across single- or multi-cast connections and typically use
high-priority identifiers. I/O polling messages contain no protocol in the 8-byte data field. The meaning of the
message is implied by the connection ID (CAN identifier). Before messages are sent using these IDs, both the device
sending and receiving them must be configured. The configuration contains the source and destination object
attribute addresses for the master and the slave.
The polling message flow is shown in Figure 7.
Data (Output Assembly)
Slave
X5
Master
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
70
Ref from
Net
Ctrl from
Net
Ready
Running
2 (Rev)
Drive State
3
0
Bit 0
Faulted
Running
1 (Fwd)
Warning
Faulted
Running
1 (Fwd)
Warning
Faulted
Ref from
Net
171
Bit 1
0
71
(Default)
Bit 2
Running
1 (Fwd)
Ctrl from
Net
Ready
Running
2 (Rev)
Drive State
14
vacon
172
Byte
Bit 7
Bit 6
Bit 5
0
1
182
Bit 3
181
Bit 4
Bit 2
Bit 1
Bit 0
Ref from
Net
Ctrl from
Net
Ready
Running
2 (Rev)
Running
1 (Fwd)
Warning
Faulted
Drive State
10
11
12
13
vacon
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
0
20
Bit 1
Fault Reset
Bit 0
Run Fwd
1
2
0
21
(Default)
Bit 2
NetRef
NetCtrl
Fault Reset
Run Rev
Run Fwd
Fault
Warning
Faulted
Fault Reset
Run Rev
Run Fwd
1
2
NetRef
NetCtrl
121
122
NetRef
NetCtrl
131
132
10
11
12
13
15
16
vacon
The default active output assembly is 21 and the default input assembly is 71. The active assemblies are configured
using class 0x80.
I/O messages 20, 21, 70, and 71 are standard Common Industrial Protocol (CIP) assemblies.
I/O messages 121, 122, 131, 132, 171, 172, 181, and 182 are vendor-specific messages that allow for customized
assemblies.
The values of the following parameters indicate which drive parameters are read or written to by the I/O assembly:
Table 10: Parameter Assignments (Parameters 880-894)
Parameter #
Parameter Name
880
FBus Read 1
Range
103 (Output Voltage)
881
FBus Read 2
882
FBus Read 3
0-65535
Default
883
FBus Read 4
884
FBus Read 5
890
FBus Write 1
891
FBus Write 2
892
FBus Write 3
893
FBus Write 4
894
FBus Write 5
0-65535
Examples
Examples 1 and 2 on the following pages show how using the FBus Write 2 = Parameter 402 would allow the I/O
assembly to set the drives acceleration rate.
Example 1: Input Assemblies
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
(Page 1 of 2)
Bit 3
0
70
Running 1 (Fwd)
Ready
Running 2 (Rev)
Drive State
0
1
171
Bit 1
Bit 0
Faulted
0
71
Bit 2
At Ref
Ready
Running 2 (Rev)
Running 1 (Fwd)
Warning
Faulted
Running 1 (Fwd)
Warning
Faulted
Drive State
vacon
Instance
172
Byte
Bit 7
Bit 6
Bit 5
Bit 3
182
(Page 2 of 2)
181
Bit 4
17
Bit 2
Bit 1
Bit 0
Running 1 (Fwd)
Warning
Faulted
Ready
Running 2 (Rev)
Drive State
10
11
12
13
18
vacon
Instance
Byte
Bit 7
Bit 6
Bit 5
0
20
Bit 3
Bit 2
Bit 1
Fault Reset
Bit 0
Run Fwd
1
2
3
0
21
Bit 4
NetCtrl
Fault Reset
Run Rev
Run Fwd
Run Rev
Run Fwd
Run Rev
Run Fwd
1
2
NetRef
NetCtrl
Fault Reset
121
122
3
0
NetCtrl
Fault Reset
131
132
10
11
12
13
vacon
19
Table 11 on page 20 explains the state transitions pictured in the flow diagram in Figure 8.
Start Forward, Start Reverse, Change to Forward, Change to Reverse, and Stop (Not Faulted Stop) are static outputs
of the control supervisor state machine. They are commands to the drive when CtrlFromNet = 1. When CtrlFromNet
= 0, control commands are from another source.
When performing changes to achieve programmed Safe State:
Run / Stop / Direction can be changed because CtrlFromNet must equal 1 when in the Enabled state.
vacon
Fwd Mode
Rev Mode
Idle Mode
Run 2 (Rev)
Old State
Results
Run1 (Fwd)
Input Conditions
CtrlFromNet
20
Event
New State
Power_Off
NonExist
Action
Faulted = 0
Ready = 0
x
(except
NonExist)
Reset
Startup
FwdMode = 0
RevMode = 0
Run1 Var = 0
Run2 Var = 0
Faulted = 0
Ready = 0
NonExist
Power_On
Startup
FwdMode = 0
RevMode = 0
Run1 Var = 0
Run2 Var = 0
Startup
Ready
Drive Fault
Faulted
Faulted = 1
FaultCode = x
Ready = 0
Ready
Run (Fwd)
Enabled
FwdMode = 1
(Start Forward)
Ready
Run (Rev)
Enabled
RevMode = 1
(Start Reverse)
Enabled
Drive Fault
Initialization
Complete
Drive Fault
Faulted
Faulted = 1
FaultCode = x
Startup
Ready
Fault_Stop
Ready = 1
Faulted = 1
FaultCode = x
(Initiate Faulted
Stop)
FwdMode = 0
RevMode = 0
Ready = 0
Enabled
Stop
Stopping
(Initiate Stop)
Enabled
ChangeDir (Fwd)
Enabled
FwdMode = 1
RevMode = 0
(Change to Forward)
Enabled
ChangeDir (Rev)
Enabled
FwdMode = 0
RevMode = 1
(Change to Reverse)
vacon
21
Results
Rev Mode
Fwd Mode
Idle Mode
Run 2 (Rev)
Old State
Run1 (Fwd)
CtrlFromNet
Input Conditions
Event
New State
Action
Faulted = 1
FaultCode = x
(Initiate Faulted
Stop)
Enabled
SafeFault
Fault_Stop
FwdMode = 0
RevMode = 0
Ready = 0
Run1 Var = 0
Run2 Var = 0
FwdMode =
Run1 Var =
NOT PresetDir
Enabled
SafeChange
Enabled
RevMode = 0
Run2 Var =
PresetDir
SpeedRef =
Preset Speed
TorqueRef =
Preset Torque
Stopping
Drive Fault
Fault_Stop
Faulted = 1
FaultCode = x
(Initiate Faulted
Stop)
Ready = 0
Stopping
Run (Fwd)
Enabled
FwdMode = 1
(Start Forward)
Stopping
Run (Rev)
Enabled
RevMode = 1
(Start Reverse)
Stopping
Stop_Complete
Ready
Fault_Stopped
Fault_Stop_ Complete
Faulted
Faulted
Fault_Reset
Ready
Faulted = 0
Ready = 1
Explicit Messaging
Explicit Messaging is used in commissioning and configuring the drive via the DeviceNet board. Explicit messages
provide multipurpose, point-to-point communication paths between two devices. They provide the typical request /
response-oriented network communication used to perform node configuration and problem diagnosis. Explicit
messages typically use low-priority identifiers and contain the specific meaning of the message right in the data
field. This includes the service to be performed and the specific object attribute address.
22
vacon
Class
Object
0x01
Identity
0x03
DeviceNet
0x05
DeviceNet Connection
0x28
Motor Data
0x29
Control Supervisor
0x2A
AC/DC Drive
0x65
Parameter
0x80
I/O Configuration
WORD
16-bit word
UINT
INT
16-bitsigned integer
BOOL
Boolean
SINT
Short integer
DINT
Double integer
LINT
Long integer
USINT
UDINT
ULINT
10
REAL
11
LREAL
12
ITIME
13
Duration (short)
TIME
14
Duration
FTIME
15
LTIME
16
Duration (long)
DATE
17
TIME_OF_DAY
18
Time of day
DATE_AND_TIME
19
STRING
20
8-bit-per-character string
STRING2
21
16-bit-per-character string
STRINGN
22
N-bytes-per-character string
SHORT_STRING
23
BYTE
24
8-bit string
DWORD
25
32-bit string
LWORD
26
64-bit string
24-hour support 1-877-822-6606
vacon
23
Reset Service
The X5 units identity object (class 0x01) supports only the type 0 reset service. The reset emulates power being
cycled to the DeviceNet interface.
Fault Tracking
Following is a cross-reference listing of X5 AC drive faults and broadcast DeviceNet faults.
Table 14: Cross-Reference List of X5 and DeviceNet Fault Codes
DeviceNet
Fault
X5 Drive
Fault
DeviceNet
Fault
X5 Drive
Fault
DeviceNet
Fault
X5 Drive
Fault
1000
3300
17
6310
2110
4210
6320
30
2120
11
4300
19 / 21
7100
33
2200
5112
7110
15
2220
18
5120
7120
16
2221
20
5200
10
7200
34
2222
28
5210
23
7310
22
2300
5300
24 / 29
7500
25
3110
13
5400
27
61441
26
3130
12
5430
31
3120
14 / 32
6100
Table xx below lists the advanced fault codes for the drive fault (F38) related to the option board. Faults not listed in
the table use the drive fault code rather than the DeviceNet defined fault code. For more information on drive faults,
see the X5 Users Manual.
The option board status LEDs are described on page 12 of this manual.
Table 15: Advanced Fault Codes
Advanced
Fault Code
Fault
Possible Cause
Corrective Measures
Check option board status LEDs,
ribbon cable connection, and
cycle power. Replace option
board if necessary.
Invalid ID
24
vacon
Attr.
No.
Attribute Name
Services
Default,
Minimum,
Maximum
Data
Type
Description
Vendor ID
Get_Attribute_Single
509
509
509
Device Type
Get_Attribute_Single
2
2
2
Product Code
Get_Attribute_Single
3
3
3
Revision
Get_Attribute_Single
0x1301
N/A
N/A
Status
Get_Attribute_Single
N/A
0
255
25
Human-readable identification
Serial Number
Get_Attribute_Single
0
N/A
0xFFFFFFFF
Product Name
Get_Attribute_Single
X5
X5
X5
State
Get_Attribute_Single
N/A
0
5
Attr.
No.
Attribute Name
Services
Default,
Minimum,
Maximum
Data
Type
Description
1
0x01
Revision
Get_Attribute_Single
2
2
2
vacon
Attr.
No.
Attribute Name
Services
Default,
Minimum,
Maximum
Data
Type
Description
1
0x01
MAC ID
Get_Attribute_Single
Set_Attribute_Single
0
0
63
Node address
2
0x02
Baud Rate
Get_Attribute_Single
Set_Attribute_Single
0
0
2
3
0x03
BOI
Get_Attribute_Single
Set_Attribute_Single
0
0
1
Bus-Off Interrupt
4
0x04
Bus-Off Counter
Get_Attribute_Single
Set_Attribute_Single
0
0
255
Get_Attribute_Single
N/A
N/A
N/A
MAC ID Switch
Changed
Get_Attribute_Single
0
0
1
7
0x07
Get_Attribute_Single
0
0
1
8
0x08
MAC ID Switch
Value
Get_Attribute_Single
0
0
63
9
0x09
Get_Attribute_Single
0
0
3
5
0x05
Allocation
Information
6
0x06
25
26
vacon
Attribute Name
Services
Default,
Minimum,
Maximum
(1)
Data
Type
Description
6
0x06
RatedCurrent[100mA]
Get_Attribute_Single
Set_Attribute_Single
360
0
65535
7
0x07
RatedVoltage[V]
Get_Attribute_Single
Set_Attribute_Single
230
100
690
9
0x09
RatedFrequency[Hz]
Get_Attribute_Single
Set_Attribute_Single
60
0
400
12
0x0C
PoleCount
Get_Attribute_Single
2
2
16
15
0x0F
BaseSpeed[RPM]
Get_Attribute_Single
Set_Attribute_Single
1760
1
24000
Attr.
No.
Attribute Name
Services
Default,
Minimum,
Maximum
Data
Type
Description
3
0x03
Run1
Get_Attribute_Single
Set_Attribute_Single
0
0
1
4
0x04
Run2
Get_Attribute_Single
Set_Attribute_Single
0
0
1
5
0x05
NetCtrl
Get_Attribute_Single
Set_Attribute_Single
0
0
1
6
0x06
State
7
0x07
Running1
Get_Attribute_Single
N/A
0
7
Get_Attribute_Single
N/A
0
1
vacon
8
0x08
Running2
Get_Attribute_Single
N/A
0
1
9
0x09
Ready
Get_Attribute_Single
N/A
0
1
10
0x0A
Faulted
Get_Attribute_Single
N/A
0
1
Fault Occurred:
0 = No faults present
1 = Fault occurred (latched)
Get_Attribute_Single
Set_Attribute_Single
0
0
1
Get_Attribute_Single
N/A
0
65535
Get_Attribute_Single
N/A
0
1
12
0x0C
13
0x0D
15
0x0F
FaultRat
FaultCode
CtrlFromNet
Attr.
No.
Attribute Name
Services
Default,
Minimum,
Maximum
Data
Type
3
0x03
AtReference
Get_Attribute_Single
N/A
0
1
Description
4
0x04
NetRef
Get_Attribute_Single
Set_Attribute_Single
0
0
1
6
0x06
DriveMode
Get_Attribute_Single
1
1
1
7
0x07
SpeedActual(RPM)
Get_Attribute_Single
N/A
0
10000
8
0x08
SpeedRef(RPM)
Get_Attribute_Single
Set_Attribute_Single
1800
0
12000
Speed reference
Units: RPM
27
28
vacon
Services
Default,
Minimum,
Maximum
Data
Type
Description
CurrentActual(100m
A)
Get_Attribute_Single
N/A
0
1000
17
0x11
OutputVoltage(V)
Get_Attribute_Single
N/A
0
690
Output voltage
Units: Volts
18
0x12
AccelTime(100ms)
Get_Attribute_Single
Set_Attribute_Single
30
1
32000
Acceleration time
Time from HighSpdLimit
Units: 100ms
19
0x13
DecelTime(100ms)
Get_Attribute_Single
Set_Attribute_Single
30
1
32000
Deceleration time
Time from HighSpdLimit to 0
Units: 100ms
20
0x14
LowSpdLimit(RPM)
Get_Attribute_Single
Set_Attribute_Single
0
0
12000
21
0x15
HighSpdLimit(RPM)
Get_Attribute_Single
Set_Attribute_Single
1800
0
12000
29
0x1D
RefFromNet
Get_Attribute_Single
N/A
0
1
Attr.
No.
Attribute Name
9
0x09
Attr.
#
1
0x01
Attribute Name
N/A
Services
Get_Attribute_Single
Set_Attribute_Single
Default,
Minimum,
Maximum
(1)
Data
Type
Description
N/A
N/A
N/A
This class is a vendor-specific object that provides direct DeviceNet access to all X5 parameters, including those not
defined by DeviceNet. The instance corresponds to the parameter number. For example, if the user wants to set
Preset Frequency 1 to 8.2 Hz, the user would issue a SET_ATTRIBUTE_SINGLE request for Class 101 (0x65), instance
303, attribute 1, with a value of 82.
For the full list of drive parameters, see the X5 Users Manual, Chapter 7.
vacon
Attr.
No.
Attribute Name
Services
Default,
Minimum,
Maximum
Data
Type
Description
1
0x01
Input Assembly
Get_Attribute_Single
Set_Attribute_Single
71
70
182
2
0x02
Output Assembly
Get_Attribute_Single
Set_Attribute_Single
21
20
132
3
0x03
4
0x04
Input Assembly
Output Assembly
Get_Attribute_Single
Set_Attribute_Single
Get_Attribute_Single
Set_Attribute_Single
1
0
5
1
0
5
29
production:
Suzhou, China
Vacon Suzhou Drives Co. Ltd.
Building 11A
428# Xinglong Street, SIP
Suchun Industrial Square
Suzhou 215126
telephone: + 86 512 62836630
fax: + 86 512 62836618
Naturno, Italy
Vacon S.R.I
Via Zone Industriale, 11
39025 Naturno
production:
Chambersburg, USA
3181 Black Gap Road
Chambersburg, PA 17202
TB Wood's (India) Pvt. Ltd.
#27, 'E' Electronics City
Hosur Road
Bangalore - 560 100
India
Tel. +91-80-30280123
Fax. +91-80-30280124
germany
Vacon GmbH
Gladbecker Strasse 425
45329 Essen
telephone: +49 (0)201 806 700
fax: +49 (0)201 806 7099
slovakia
Vacon s.r.o. (Branch)
Seberiniho 1
821 03 Bratislava
Tel. +421 243 330 202
Fax. +421 243 634 389
spain
Vacon Drives Ibrica S.A.
Miquel Servet, 2. P.I. Bufalvent
08243 Manresa
telephone: +34 93 877 45 06
fax: +34 93 877 00 09
india
Vacon Drives & Control Plc
Plot No 352
Kapaleeshwar Nagar
East Coast Road
Neelangarai
Chennai-600041
Tel. +91 44 244 900 24/25
sweden
Vacon AB
Anderstorpsvgen 16
171 54 Solna
telephone: +46 (0)8 293 055
fax: +46 (0)8 290 755
italy
Vacon S.p.A.
Via F.lli Guerra, 35
42100 Reggio Emilia
telephone: +39 0522 276811
fax: +39 0522 276890
the netherlands
Vacon Benelux BV
Weide 40
4206 CJ Gorinchem
telephone: +31 (0)183 642 970
fax: +31 (0)183 642 971
norway
Vacon AS
Bentsrudveien 17
3080 Holmestrand
telephone: +47 330 96120
fax: +47 330 96130
romania
Vacon Romania - Reprezentanta
Cuza Voda 1
400107 Cluj Napoca
Tel. +40 364 118 981
Fax. +40 364 118 981
russia
ZAO Vacon Drives
Ul. Letchika Babushkina 1,
Stroenie 3
129344 Moscow
telephone: +7 (495) 363 19 85
fax: +7 (495) 363 19 86
ZAO Vacon Drives
2ya Sovetskaya 7, office 210A
191036 St. Petersburg
telephone: +7 (812) 332 1114
fax: +7 (812) 279 9053
thailand
Vacon South East Asia
335/32 5th-6th floor
Srinakarin Road, Prawet
Bangkok 10250
Tel. +66 (0)2366 0768
ukraine
Vacon Drives Ukraine (Branch)
42-44 Shovkovychna Str.
Regus City Horizon Tower
Kiev 01601, Ukraine
Tel. +380 44 459 0579
Fax +380 44 490 1200
united arab emirates
Vacon Middle East and Africa
Block A, Office 4A 226
P.O.Box 54763
Dubai Airport Free Zone
Dubai
Tel. +971 (0)4 204 5200
Fax: +971 (0)4 204 5203
united kingdom
Vacon Drives (UK) Ltd.
18, Maizefield
Hinckley Fields Industrial Estate
Hinckley
LE10 1YF Leicestershire
telephone: +44 (0)1455 611 515
fax: +44 (0)1455 611 517
united states
Vacon, Inc.
3181, Black Gap Road
Chambersburg, PA 17202
telephone: +1 (877) 822-6606
fax: +1 (717) 267-0140