02.susol MCCB E 1306
02.susol MCCB E 1306
02.susol MCCB E 1306
biz
Super Solution
LSIS continues
the value and the prominence of LG
Electric Technology
The R&D Center analyzes and researches core technologies related
to power equipment.
SCADA
The R&D Center carries out projects and technology research in the
fields of SCADA and DAS.
Simulator
The R&D Center predicts probable electrocution hazards by
conducting simulated analyses of power generation phenomena,
and develops simulation technologies and products that can
optimize the constituent facilities.
Environmental Test /
Non-stop High Temperature Test
Power Testing
& Technology Institute
PT&T is a KOLAS-qualified (Korea Laboratory
Accreditation Scheme) accredited testing laboratory
and provides worldwide testing service with its
1500MVA-capacity High Power Laboratory, High
Voltage Laboratory and Reliability Testing
Laboratory.
PT&T is also fully recognized by foreign testing and
certification bodies of high reputation as CESI of Italy,
KEMA of Netherlands, UL of America, etc. for its low
voltage testings.
Available Tests
- Electro-Mechanical Tests
- Insulation Performance Tests
- Short-Circuit Tests
- Reliability Evaluation Tests
- Arc Tests
- Environmental Tests
Solution provider
Automation Industry |
Automation Equipment, Industrial IT & RFID
LSIS, a leading pioneer of the domestic automation business,
developed the first ever PLC, Inverter (AC Drive), and DCS in Korean
automation history. We now provide Total Solutions through the
diverse application of our own products, ranging from controllers to
control systems that are based on sophisticated technology and
proven experience, to bring innovative change to distribution
systems and logistics.
Chonan Plant (Korea)
Low voltage
circuit breakers
Super Solution
Contents
Overview
A-1
Main characteristics
A-2
Accessories
A-3
A-4
Characteristics curves
A-5
Dimensions
A-6
Technical information
A-7
Ministry of Commerce
>>>
Super Solution
Circuit breakers
For protection of motor &
its control device
Disconnecting switches
For controlling and
disconnecting circuits
Super solution
Super Performance
Super Breaking capacity
Super Optimum coordination
Super Extensive applications
MCCB
Communication
Sub_supervision PC
PLC
RS485 (DNP)
Communication unit
RS485 (Modbus)
Profibus-DP
Devices
SUB_Supervision PC
MCCB(MODBUS) SUB_Supervision PC
MCCB
Number of poles
RTU23
RTU33
RTU43
3*
3*
3*
TS100
TS160
Applicable
TS250
circuit breaker
TS400
TS630
TS800
Protection charicteristics
Sensitivity
In(A)
(adjustable)
(adjustable)
(adjustable)
0.03-0.3-1-3-10
0.03-0.3-1-3-10
0.03-0.3-1-3-10
Intentional time
(adjustable)
(adjustable)
(adjustable)
delay(ms)
0-60-150-300-600
0-60-150-300-600
0-60-150-300-600
Time delay **
Rated voltage
Max. breaking
(adjustable)
(adjustable)
(adjustable)
time(ms)
40-140-240-450-880
40-140-240-450-880
40-140-240-450-880
AC 50/60 Hz
220~460V / 460~690V
220~460V / 460~690V
220~460V / 460~690V
MCCB
Main characteristics
A-1. Overview
Range of LS low voltage circuit breakers
A-1-1
General
A-1-3
A-1-4
Structure
A-1-5
A-1-7
A-1-9
Switching mechanism
A-1-11
Degree of protection
A-1-12
Ordering
A-1-13
Main switchboard
Type of circuit breaker
Rated current, In
Breaking capacity, Icu
Service breaking capacity (% Icu),Ics
Utilization category
Applied standard
ACB
MCCB
630~6300A
1000~1600A
65~150kA
50~150kA
100%
75~100%
A, B
IEC 60947-2
IEC 60947-2
Susol/Metasol
Susol
AH, AS, AN
TS
Brand name
Image of brand
Series
* 1pole MCCB
A-1-1
Final distribution
MCCB
MCCB
MCB
16~800A
3~1200A
1~125A
37~150kA
10~85kA
6~10kA
100%
100%
50~100%
IEC 60947-2
Susol
Metasol
TE, TD, TS
AB series
BK series
A-1-2
General
All Susol circuit breakers offer positive contact indication and are suitable for isolation in
compliance with standards IEC 60947-1 and 2.
Susol circuit-breakers are suitable for protection of
- Power distribution systems supplied by transformers or generators
- Motor and generator
A switch-disconnector of Susol circuit breakers is available for for circuit control and isolation.
A-1-3
CE conformity marking
The CE conformity marking shall indicate conformity to all the obligations imposed on the
manufacturer, as regards his products, by virtue of the European Community directives providing
for the affixing of the CE marking.
When the CE marking is affixed on a product, it represents a declaration of the manufacturer or of
his authorized representative that the product in question conforms to all the applicable provisions
including the conformity assessment procedures. This prevents the Member States from limiting
the marketing and putting into service of products bearing the CE marking, unless this measure is
justified by the proved non-conformity of the product.
IECEE CB SCHEME
The IECEE CB Scheme is the world's first truly international system for acceptance of test reports
dealing with the safety of electrical and electronic products. It is a multilateral agreement among
participating countries and certification organizations. A manufacturer utilizing a CB test report
issued by one of these organizations can obtain national certification in all other member countries
of the CB Scheme.
The Scheme is based on the use of international (IEC) Standards. If some members' national
standards are not yet completely harmonized with IEC Standards, national differences are
permitted if clearly declared to all other members. The CB Scheme utilizes CB Test Certificates to
attest that product samples have successfully passed the appropriate tests and are in compliance
with the requirements of the relevant IEC Standard and with the declared national differences of
various member countries.
The main objective of the Scheme, is to facilitate trade by promoting harmonization of the national
standards with international Standards and cooperation among product certifiers worldwide in order
to bring product manufacturers a step closer to the ideal concept of "one product, one test, one
mark, where applicable'.
A-1-4
Structure
Mechanism unit
Unvarying contact force
regardless of over travel
RTA (Rapid Toggle Area)
Open speed of moving contact is
rapid by optimized cam curve
regardless of trip signal
Force
Angle
Unvarying contact force
A-1-5
Structure
Molded case
UL94 V-0 flame retarded
High strength
Handle
Function of indications
- ON OFF TRIP
Resetting
When the handle indicates "tripped"
position it must first be reset by moving
the handle to the OFF position and
then closing is possible
Trip-Free even if the handle is held at
ON, the breaker will trip if an over
current flows
Suitable for Verification of the main
contact position under abnormal
conditions because the handle doesnt
indicate open position
Arc-Extinguishing unit
PASQ Type Quenching Chamber
Very superior to increasing arc
voltage during short time
PASQ ;
- Puffer Assisted Self-Quenching
- Patented by LSIS
Hybrid
chamber
Grid
Assy
A-1-6
Rated frequency
Symbol indicating
suitability for isolation
as defined by IEC 947-2
A-1-7
Standard
Manufacturer
Utilization category
160AF
250AF
630AF
800AF
1600AF
TE100S
TE160S
TE100N
TE160N
TD100N
TD160N
TS100N
TS160N
TS250N
-
TS400N
TS630N
-
TS800N
-
TS1000N
TS1250N
TS1600N
-
TD100H
TD160H
-
TS100H
TS160H
TS250H
TS400H
TS630H
-
TS800H
-
TS1000H
TS1250H
TS1600H
TD100L
TD160L
-
TS100L
TS160L
TS250L
TS400L
TS630L
-
TS800L
-
TS1000L
-
37kA
50kA
50kA
65kA
65kA
50kA
85kA
85kA
85kA
100kA
70kA
150kA
150kA
150kA
150kA
150kA
Upstream connections
Fixing hole
Certificate plate
Indication of closed (I/ON) position
Brand name
Operating handle
Fixing hole
Downstream connections
A-1-8
On Susol circuit breakers, the thermal-magnetic and electronic trip units are interchangeable and
may be rapidly fitted to the circuit breakers.
It is therefore easy to change the protection of a given circuit following a modification in an
installation. On TS400 and 630 circuit breakers, the electronic trip units are interchangeable plug-in
modules. Trip unit ETM offers a large number of protection settings.
Each Trip devices has different types of protection depending on the associated trip unit:
Standard protection
Protection of networks supplied by line distribution
Protection of long cables
Protection of DC networks
Protection of motor-starters
Service connection circuit breaker (for special subscriber contracts)
Susol TD100, TD160 circuit breakers may be equipped with either FTU or FMU.
The trip units are not interchangeable types and can be supplied only after fixed with circuit breakers.
Ampere ratings
MCCB frame type
Type of
trip unit
TE100
TD100
TE160
Built in unit
TS100
TS250
FTU
FMU
16, 20, 25, 32, 40, 16, 20, 25, 32, 40,
TD160
TS160
Inter
changeable
80, 100
80, 100
Electronic release
MTU
ETS
ETM
160
40, 80
100
160
250
125, 160
300, 400
300, 400
320
TS630
500, 630
500, 630
500, 630
500
TS800
700, 800
800
800
630
trip unit
125, 160, 200, 250 125, 160, 200, 250 125, 160, 200, 250
300, 400
TS400
A-1-9
DSU
ATU
630, 800
400
630
800
FTU
Fixed-thermal, fixed-magnetic
FTU
Im=2500A
Ir
Electronic
trip unit
Im
FMU
Adjustable-thermal, fixed-magnetic
ATU
Adjustable-thermal, adjustable-magnetic
Thermal magnetic
trip unit
ATU
0.9
0.8
7
1
Ir
TS250
9
5
10
1848
2112
Im
FMU
MTU
Magnetic only
MTU
1584
1320
2376
2640
Im
220A
3P
Disconnecting switch
DSU
3P
FTU
ATU
ETS
Electronic (LSI)
ETM
ETM
A-1-10
Switching mechanism
Double contactor structure
Optimize
ON position
Repulsion force
Shape of contactor
Induce easily the arc mobility to grid
direction
Rapidly redeploy the arc from moving
contactor
Prevent contact tip from erosion
Unvarying
contact
Force
Angle
Fig. 3 ON position
OFF position
Push to trip in OFF position
* Reset pin moment < Main spring moment
Stability of endurance
600.0
500.0
400.0
300.0
200.0
100.0
0.0
0.00E+00
4.00E+06
3.00E+06
1.20E+07
1.60E+07
2.00E+07
Life
TRIP position
Enables tripping mechanically from
outside, for confirming the operation of
the accessory switches and the manual
resetting function
Fig. 5 TRIP position
A-1-11
Degree of protection
The table indicates the degrees of protection guaranteed by Susol circuit-breakers according to
several type of installation. Basically, the fixed parts are always preset with IP20 degree of
protection.
IP65 degree of protection can be obtained with the circuit-breaker installed in a switchboard fitted
with an extended rotary handle operating mechanism transmitted on the compartment door.
IP
Protection of
persons against
access to hazardo
us parts with:
IP20
Wire
IP30
Wire
IP20
or
IP30
Wire
IP40
Wire
IP40
Wire
IP40
Wire
IP65
Wire
Type
Degree of protection
Circuit breaker
Circuit breaker
Totally protected
with cover frame
against ingress of
and rotary
dust and water jets fromany direction
extended handle
A-1-12
Ordering
Susol TE, TD, TS up to 800AF MCCB
TS250
Ampere frame
FTU
Type
250
Rated current
Poles
100
Standard
2P
2Pole
160
Normal
3P
3Pole
100
High
4P*
4Pole
160
Current limit
TE
TD
Standard
Plug-in
AX
Accessories
Note) Please refer to A-3
100
Trip unit
160
TS
250
400
630
800
Thermal FTU
magnetic FMU
trip unit ATU
Electronic ETS
trip units ETM
TS250
Ampere frame
TS
Type
100
160
High
250
Current limit
400
630
800
Normal
MTU
220
Magnetic only
trip unit
Rated current
Poles
3P
AF
Rated current
TS100 1.6, 3.2, 6.3, 12, 20, 32, 50, 63, 100
TS160 32, 50, 63, 80, 100, 160
TS250 100, 160, 220
TS400 320
TS630 500
TS800 630
A-1-13
3Pole
Standard
Plug-in
AX
Accessories
Note) Please refer to A-3
TS250
NA
DTU
250
Ampere frame
MCCB
Disconnect
Switch Unit
Rated current
Poles
TD
160
3P
3Pole
Standard
Plug-in
100
160
TS
250
400
630
800
AF
Rated current
TD160
160
TS100
100
TS160
160
TS250
250
TS400
400
TS630
630
TS800
800
A-1-14
Ordering
Susol TS 1600AF MCCB
TS1600
Ampere frame
TS
1600A
Trip relay
Poles
1000
Normal
3P
3Pole
1250
Ammeter
4P
4Pole
Connection type
-
Standard
Rear
REAR
1600
Type
Power meter
Supreme meter
Connection
Rated current
Normal
800A
N-R-S-T
High
1000A
R-S-T-N
Current limit
1250A
Switch-
1600A
NA
disconnector
A-1-15
Trip relay
Normal
A
A
Ammeter
Self-Power, 60Hz
Self-Power, 50Hz
Without comm.
Self-Power, 60Hz
DC 24V~60V, 60Hz
Comm.
Self-Power, 50Hz
DC 24V~60V, 50Hz
P
P
Power meter
Comm.
DC 24V~60V, 60Hz
DC 24V~60V, 50Hz
S
S
Supreme meter
Comm.
DC 24V~60V, 60Hz
DC 24V~60V, 50Hz
A-1-16
A-2-1
A-2-3
A-2-5
A-2-7
A-2-11
A-2-15
A-2-17
A-2-19
A-2-25
A-2-31
A-2-37
A-2-40
A-2-49
A-2-57
A-2-59
Switch-Disconnectors
Electrical characteristics
A-2-61
A-2-63
A-2-63
A-2-65
Overview
N(Normal), NV type
A(Ammeter) type
P(Power meter) type
S(Supreme meter) type
Operation characteristic
Measurement function
ZSI -Zone Selective Interlocking (A, P, S type)
Remote reset and digital I/O (A, P, S type)
Communication
Event & fault recording (P, S type)
System information
System block diagram
Installation and Handling
A-2-66
A-2-67
A-2-69
A-2-71
A-2-73
A-2-75
A-2-77
A-2-78
A-2-79
A-2-80
A-2-81
A-2-81
A-2-82
A-2-83
DC
TE100
TE160
TD100
TD160
100
160
100
[A]
16~100
100,125,160
160
1P: 16, 20, 25, 32,
40, 50, 63, 80,
100,125, 160
2, 3P: 100, 125, 160
[V]
[V]
[kV]
[V]
3,4
690
500
8
750
3,4
690
500
8
750
[AF]
1, 2, 3, 4
240(1P), 690
250(1P), 500
8
750
N
L
N
H
L
30(1P) 50(1P)
85
100 200
200
85
100
50
85
150
50
85
150
50
70
130
50
70
130
30
50
65
30
50
65
5
8
10
5
8
10
16(1P) 25(1P)
42
65
100
100
42
65
42
65
100
42
65
100
100% 100% 100% 100% 100% 100%
[kA]
50
85
50
85
380/415V
440/460V
480/500V
660/690V
[kA]
[kA]
[kA]
[kA]
37
25
18
6
50
37
25
8
37
25
18
6
50
37
25
8
250V
[kA]
37
50
37
50
37
100%
50
100%
37
100%
50
100%
105
187
105
187
187
220
440
77.7
52.5
36
9.2
105
77.7
52.5
13.6
77.7
52.5
36
9.2
105
77.7
52.5
13.6
105
105
63
8
330
286
143
17
[kA]
[kA]
[kA]
[kA]
Category of utilization
Isolation behavior
Trip unit (release)
Thermal-Magnetic
fixed-thermal, fixed-magnetic
FTU
adjustable-thermal, fixed-magnetic
FMU
adjustable-thermal, adjustable-magnetic
ATU
magnetic only
MTU
Electronic
LSI
ETS
LSI
ETM
Option Earth-fault protection, Ig
Zone selective interlocking, ZSI
Ammeter
Communication
Earth-leakage protection module
Connection
fixed
front-connection
rear-connection
plug-in
front-connection
rear-connection
Mechanical life
[operations]
Electrical life @ 415 V AC
[operations]
Basic dimensions, WHD 1-pole
[mm]
(front connection)
3-pole
[mm]
4-pole
[mm]
Weight
1-pole
[kg]
(front connection)
3-pole
[kg]
4-pole
[kg]
Reference standard
A-2-1
2, 3, 4
690
500
8
750
H
187
154
105
14
A
25000
10000
7613082
10113082
1.05
1.35
IEC60947-2
25000
10000
7613082
10113082
1.05
1.35
IEC60947-2
25000
10000
9014086
12014086
1.5
1.8
IEC60947-2
105(1P)
187
105
105
63
8
105(1P)
220
187
154
105
14
A
440
330
286
143
17
25000
10000
3514086
9014086
12014086
0.57
1.5
1.8
IEC60947-2
TS100
TS160
TS250
TS400
TS630
TS800
100
160
250
400
630
800
300, 400
500, 630
700, 800
2, 3, 4
690
500
8
750
H
2, 3, 4
690
500
8
750
H
2, 3, 4
690
500
8
750
H
100
120
50
50
42
10
2, 3, 4
690
500
8
750
H
2, 3, 4
690
500
8
750
H
2, 3, 4
690
500
8
750
H
200
100
120
200
100
120
200
100
120
200
100
120
200
100
120
200
85
70
65
15
150
130
85
20
50
50
42
10
85
70
65
15
150
130
85
20
50
50
42
10
85
70
65
15
150
130
85
20
65
65
42
10
85
85
65
20
150
130
85
35
65
65
42
10
85
85
65
20
150
130
85
35
65
65
42
10
100
100
85
20
150
130
100
35
50
85
100
50
85
100
50
85
100
50
85
100
50
85
100
50
85
100
50
100%
85
100%
220
264
440
220
264
440
220
264
440
220
264
440
220
264
440
220
264
440
105
105
88
17
187
154
143
30
A
330
286
187
40
105
105
88
17
187
154
143
30
A
330
286
187
40
105
105
88
17
187
154
143
30
A
330
286
187
40
143
143
88
17
187
187
143
40
A
330
286
187
74
143
143
88
17
187
187
143
40
A
330
286
187
74
143
143
88
17
220
220
187
40
A
330
286
220
74
100
50
85
100
100% 100% 100% 100%
50
100%
85
100
100% 100%
25000
10000
10516086
14016086
2
2.6
IEC60947-2
25000
10000
10516086
14016086
2
2.6
IEC60947-2
25000
10000
10516086
14016086
2
2.6
IEC60947-2
50
85
100
50
100% 100% 100% 100%
20000
6000
140260110
186.5260110
5.4
7.2
IEC60947-2
85
100
100% 100%
20000
6000
140260110
186.5260110
5.4
7.2
IEC60947-2
50
85
100% 100%
100
100%
10000
3000
210320135
280320135
15.1
19.6
IEC60947-2
A-2-2
Function
Protection of power distribution
Overload protection: Thermal protection with a fixed or adjustable threshold
Short-circuit protection: Magnetic protection with a fixed or adjustable pick-up
Protection of the fourth pole
4P3T type (neutral unprotected)
4P4T type 50% (neutral protection at 0.5In)
4P4T type 100% (neutral protection at 1In)
Operation
Trip bar
ATU
Bimetal
Armature
Ratings
Ratings(A)
In
20
25
32
40
50
63
80
100
125
160
300
400
500
630
800
TE100
TD100
TE160
TD160
TS100
TS160
TS250
TS400
TS630
TS800
A-2-3
TE100 to TS800
16
200 250
FTU
Im=2500A
Ir
Im
ATU
0.9
0.8
9
5
Ir
10
Im
A-2-4
FTU
Im=1600A
160A
0.9
0.8
Ir Im
FMU
0.8
Im=1600A
160A
Ir Im
FMU
Trip unit function
- FTU : Fixed thermal & magnetic unit
- FMU : Adjustable thermal, fixed magnetic unit
MCCB frame type
- TE100 : TE100N, TE100H, TE100L
- TD100 : TD100N, TD100H, TD100L
- TE160 : TE160N, TE160H, TE160L
- TD160 : TD160N, TD160H, TD160L
A-2-5
Ir
Im
at 40 In
16
20
25
32
40
50
63
80
100
125
160
TE/TD100
TE/TD160
Overload protection(thermal)
Current setting(A) Ir
FTU
Fixed
FMU
Fixed 400A
Fixed 10In
FMU
Fixed 400A
Fixed 10In
Protection of N pole
4P3T
Neutral No protection
4P4T
Setting details
Thermal overload protection
Trip unit type
Setting
Ir
16
20
TE/TD100FTU
Fixed
16
20
TE/TD100FMU
0.8
12.8
16
20
25.6
32
40
50.4
64
80
0.9
14.4
18
22.5
28.8
36
45
56.7
72
90
16
63
25
32
25
32
40
50
40
50
63
63
80
100
125
160
80
100
20
25
32
40
50
80
100
TE/TD160FTU
Fixed
100
125
TE/TD160FMU
0.8
80
100
128
0.9
90
112.5
144
100
125
160
160
Setting
current, Ir
16
20
25
32
40
50
63
80
100
125
160
In10
400
400
400
400
400
500
630
800
1000
0.8In
Fixed
In10
400
400
400
400
400
500
630
800
1000
0.9In
Fixed
In10
400
400
400
400
400
500
630
800
1000
1000
1.0In
Fixed
In10
400
400
400
400
400
500
630
800
Fixed
In10
0.8In
Fixed
In10
0.9In
Fixed
In10
1.0In
Fixed
In10
TE/TD160FTU
TE/TD160FMU
current, Im
Fixed
TE/TD100FTU
TE/TD100FMU
Setting
A-2-6
FTU
Im=2500A
Ir
Im
ATU
0.9
0.8
Ir
Im
10
9
5
A-2-7
8
9
10
Ir
Im
at 40 In
TS100
TS160
TS250
40
50
63
80
100
125
160
200
250
Overload protection(thermal)
Current setting(A) Ir
FTU
FMU
ATU
Fixed
Adjustable 0.8 toIn
Adjustable 0.8 toIn
Fixed 10In
Fixed 10In
Adjustable 5, 6, 7, 8, 9, 10In (6 settings)
Protection of N pole
4P3T
4P4T
Neutral No protection
Neutral protection (100% Ir)
FTU
Trip unit function
- FTU: Fixed thermal, fixed magnetic unit
MCCB frame type
- TS100: TS100N, TS100H, TS100L
- TS160: TS160N, TS160H, TS160L
- TS250: TS250N, TS250H, TS250L
TS250
FMU
Trip unit function
- FMU: Adjustable thermal, fixed magnetic unit
MCCB frame type
- TS100: TS100N, TS100H, TS100L
- TS160: TS160N, TS160H, TS160L
- TS250: TS250N, TS250H, TS250L
TS250
ATU
Trip unit function
- ATU: Adjustable thermal, adjustable magnetic unit
MCCB frame type
- TS160: TS160N, TS160H, TS160L
- TS250: TS250N, TS250H, TS250L
A-2-8
TS160ATU
TS250FTU
TS250FMU
TS250ATU
A-2-9
Setting
Ir
50
63
80
100
125
160
200
250
Fixed
40
50
63
80
100
0.8In
32
40
50
64
80
0.9In
36
45
57
72
90
1.0In
40
50
63
80
100
Fixed
100
125
160
0.8In
80
100
128
0.9In
90
113
144
1.0In
100
125
160
0.8In
100
128
0.9In
113
144
1.0In
125
160
Fixed
125
160
200
250
0.8In
100
128
160
200
0.9In
113
144
180
225
1.0In
125
160
200
250
0.8In
100
128
160
200
0.9In
113
144
180
225
1.0In
125
160
200
250
Setting
current, Ir
TS100FTU
TS100FMU
0.8In
0.9In
1.0In
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
0.8In
Adjustable
0.9In
Adjustable
1.0In
Adjustable
0.8In
0.9In
1.0In
Fixed
Fixed
Fixed
Fixed
0.8In
Adjustable
0.9In
Adjustable
1.0In
Adjustable
0.8In
0.9In
1.0In
TS160FTU
TS160FMU
TS160ATU
TS250FTU
TS250FMU
TS250ATU
Setting
current, Im
In10
In10
In10
In10
In10
In10
In10
In10
In5
In6
In7
In8
In9
In10
In5
In6
In7
In8
In9
In10
In5
In6
In7
In8
In9
In10
In10
In10
In10
In10
In5
In6
In7
In8
In9
In10
In5
In6
In7
In8
In9
In10
In5
In6
In7
In8
In9
In10
50
500
500
500
500
-
63
630
630
630
630
-
80
800
800
800
800
-
100
1000
1000
1000
1000
1000
1000
1000
1000
-
125
1250
1250
1250
1250
625
750
875
1000
1125
1250
625
750
875
1000
1125
1250
625
750
875
1000
1125
1250
1250
1250
1250
1250
625
750
875
1000
1125
1250
625
750
875
1000
1125
1250
625
750
875
1000
1125
1250
160
1600
1600
1600
1600
800
960
1120
1280
1440
1600
800
960
1120
1280
1440
1600
800
960
1120
1280
1440
1600
1600
1600
1600
1600
800
960
1120
1280
1440
1600
800
960
1120
1280
1440
1600
800
960
1120
1280
1440
1600
200
-
250
-
2000
2000
2000
2000
1000
1200
1400
1600
1800
2000
1000
1200
1400
1600
1800
2000
1000
1200
1400
1600
1800
2000
2500
2500
2500
2500
1250
1500
1750
2000
2250
2500
1250
1500
1750
2000
2250
2500
1250
1500
1750
2000
2250
2500
A-2-10
FTU
Im=6300A
Ir
0.9
630A
0.8
Im
Ir
Im
FMU
0.9
0.8
630A
Im=6300A
1
Ir
Im
t
0.9
0.8
ATU
6
0.9
0.8
7
6
A-2-11
Im
9
5
10
9
5
Ir
630A
10
Ir
Im
300
400
500
630
TS400
TS630
Overload protection(thermal)
Current setting(A) Ir
FTU
In=Ir (Fixed)
FMU
ATU
Fixed 10In
FMU
Fixed 10In
ATU
Protection of N pole
4P3T
Neutral No protection
4P4T
ATU
Trip unit function
- FTU : Fixed thermal & magnetic unit
- FMU : Adjustable thermal & fixed magnetic unit
- ATU : Adjustable thermal & adjustable magnetic unit
MCCB frame type
- TS400 : TS400N, TS400H, TS400L
- TS630 : TS630N, TS630H, TS630L
A-2-12
Setting details
Thermal overload protection
Trip unit type
TS400FTU
TS400FMU
TS400ATU
TS630FTU
TS630FMU
TS630ATU
A-2-13
Setting
Ir
300
400
500
630
Fixed
300
400
0.8
240
320
0.9
270
360
300
400
0.8
240
320
0.9
270
360
300
400
Fixed
500
630
0.8
400
504
0.9
450
567
500
630
0.8
400
504
0.9
450
567
500
630
Setting details
Magnetic short-circuit protection
Trip unit type
Setting
current, Ir
TS400FTU
TS400FMU
0.8In
0.9In
1.0In
0.8In
TS400ATU
0.9In
1.0In
TS630FTU
TS630FMU
0.8In
0.9In
1.0In
0.8In
TS630ATU
0.9In
1.0In
Setting
current, Im
Fixed
In10
Fixed
In10
Fixed
In10
Fixed
In10
In5
In6
In7
Adjustable
In8
In9
In10
In5
In6
In7
Adjustable
In8
In9
In10
In5
In6
In7
Adjustable
In8
In9
In10
Fixed
In10
Fixed
In10
Fixed
In10
Fixed
In10
In5
In6
In7
Adjustable
In8
In9
In10
In5
In6
In7
Adjustable
In8
In9
In10
In5
In6
In7
Adjustable
In8
In9
In10
400
4000
4000
4000
4000
2000
2400
2800
3200
3600
4000
2000
2400
2800
3200
3600
4000
2000
2400
2800
3200
3600
4000
-
500
5000
5000
5000
5000
2500
3000
3500
4000
4500
5000
2500
3000
3500
4000
4500
5000
2500
3000
3500
4000
4500
5000
630
6300
6300
6300
6300
3150
3780
4410
5040
5670
6300
3150
3780
4410
5040
5670
6300
3150
3780
4410
5040
5670
6300
A-2-14
TS800 FTU
- Fixed thermal fixed magnetic trip unit
TS800 FMU
FTU
0.9
Im=8000A
Ir
800A
0.8
Im
TS800 FMU
- Adjustable thermal fixed magnetic trip unit
0
FMU
0.9
0.8
Im=8000A
1
Ir
800A
Im
Ir
Im
TS800 ATU
t
0.9
0.8
TS800 ATU
- Adjustable thermal adjustable magnetic trip unit
ATU
0.9
0.8
7
6
800A
10
10
0
Im
Ir
Im
ATU
Trip unit function
- FTU : Fixed thermal & magnetic unit
- FMU : Adjustable thermal & fixed magnetic unit
- ATU : Adjustable thermal & adjustable magnetic unit
MCCB frame type
- TS800 : TS800N, TS800H, TS800L
A-2-15
9
5
9
5
Ir
Rating(A) at 40 In
TS800
800
Overload protection(thermal)
FTU
Fixed 10In
FMU
Fixed 10In
ATU
Current setting(A) Ir
Protection of N pole
FTU
Fixed
FMU
4P3T
Neutral No protection
ATU
4P4T
Setting details
Thermal overload protection
Trip unit type
TS800FTU
TS800FMU
TS800ATU
Setting
Ir
700
800
Fixed
0.8
0.9
1
700
-
800
640
720
800
0.8
0.9
1
640
720
800
Setting
current, Ir
TS800FTU
TS800FMU
0.8In
0.9In
1.0In
0.8In
TS800ATU
0.9In
1.0In
Setting
current, Im
Fixed
In10
Fixed
In10
Fixed
In10
Fixed
In10
In5
In6
In7
Adjustable
In8
In9
In10
In5
In6
In7
Adjustable
In8
In9
In10
In5
In6
In7
Adjustable
In8
In9
In10
800
8000
8000
8000
8000
4000
4800
5600
6400
7200
8000
4000
4800
5600
6400
7200
8000
4000
4800
5600
6400
7200
8000
A-2-16
Ratings
Trip units
ETS23
40
80
160
250
400
630
800
Applicable to
ETS33
ETS43
TS100 N/H/L
TS160 N/H/L
TS250 N/H/L
TS400 N/H/L
TS630 N/H/L
TS800 N/H/L
160
320
630
Rated
current,
In (A)
16
32
40
64
80
100
250
400
Setting values
Overload protection (long time)
Setting current (A), Ir
Tripping time (s)
0.4, 0.45, 0.5, 0.55, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.0In,
13 setting
Fixed at 6Ir , tolerance20%
A-2-17
Fixed at 11In
800
.7
.6
1.0
.4
alarm
2
1.5
.9
.5
.8
90%
105%
ETS33
10
tr
.3
tsd
tsd
.2
.1
Ir
Isd
Ii
In 630A
.3
.05
TEST
tsd
Ir Isd
Ii
.6
.7
.8
.4
1.0
alarm
2
1.5
.9
.5
90%
105%
ETS43
10
.3
.2
.1
TEST
.3
.05
tsd
In 800A
A-2-18
Test connector
Short time tripping delay
Ir
.7
.8
.9
.5
tr
Overload protection
(long time)
1.0
.4
td
1.5
10
.3
.2
tsd
.1
tsd
.05
.3
Ir
Isd
Ii
Icu
1.5, 2, 3, 4, 5, 6, 7, 8, 10Ir
9 settings, tolerance 15%
setting time (ms)
50
operation time (ms) 30t70
100
200
70t140 140t240
300
240t350
4 settings
Fixed at 11In
23
In250A
Trip unit frame
- 23 for TS100, TS160, TS250
- 33 for TS400, TS630
- 43 for TS800
Rated current, In
- 40, 80A for TS100
- 40, 80, 160A for TS160
- 40, 80, 160, 250A for TS250
A-2-19
32
40
64
80
100
160
250
320
400
40
80
630
800
Trip unit
for TS100
for TS160
for TS250
Setting details
Overload protection (long time)
.7
.6
TS100
40
TS160
80
40
80
TS250
160
160
250
1.0
.4
Circuit breakers
.8
.9
.5
Ir
Setting value
tr
td
0.4
16
32
16
32
64
16
32
64
100
0.45
18
36
18
36
72
18
36
72
113
0.5
20
40
20
40
80
20
40
80
125
0.55
22
44
22
44
88
22
44
88
138
tsd
tsd
Ir
Isd
Ii
Icu
0.6
24
48
24
48
96
24
48
96
150
0.65
26
52
26
52
104
26
52
104
163
0.7
28
56
28
56
112
28
56
112
175
0.75
30
60
30
60
120
30
60
120
188
0.8
32
64
32
64
128
32
64
128
200
0.85
34
68
34
68
136
34
68
136
213
0.9
36
72
36
72
144
36
72
144
225
0.95
38
76
38
76
152
38
76
152
238
40
80
40
80
160
40
80
160
250
Ir
tr
Fixed at 6Ir
tolerance20%
tsd
tsd
Ir
Isd
Ii
Icu
A-2-20
Circuit breakers
2
1.5
t
TS100
40
TS160
80
40
80
TS250
160
40
80
160
250
10
Ir
Setting value
tr
td
0.4
tsd
tsd
Ir
Isd
Ii
Icu
24
48
24
48
96
24
48
96
150
0.45
27
54
27
54
108
27
54
108
169
0.5
30
60
30
60
120
30
60
120
188
0.55
33
66
33
66
132
33
66
132
206
0.6
36
72
36
72
144
36
72
144
225
0.65
39
78
39
78
156
39
78
156
244
42
84
42
84
168
42
84
168
263
0.75
45
90
45
90
180
45
90
180
281
0.8
48
96
48
96
192
48
96
192
300
0.85
51
102
51
102
204
51
102
204
319
0.9
54
108
54
108
216
54
108
216
338
0.95
57
114
57
114
228
57
114
228
356
60
120
60
120
240
60
120
240
375
0.7
1.5
0.4
32
64
32
64
128
32
64
128
200
0.45
36
72
36
72
144
36
72
144
225
0.5
40
80
40
80
160
40
80
160
250
0.55
44
88
44
88
176
44
88
176
275
0.6
48
96
48
96
192
48
96
192
300
0.65
52
104
52
104
208
52
104
208
325
0.7
56
112
56
112
224
56
112
224
350
0.75
60
120
60
120
240
60
120
240
375
400
0.8
64
128
64
128
256
64
128
256
0.85
68
136
68
136
272
68
136
272
425
0.9
72
144
72
144
288
72
144
288
450
0.95
76
152
76
152
304
76
152
304
475
500
80
160
80
160
320
80
160
320
0.4
48
96
48
96
192
48
96
192
300
0.45
54
108
54
108
216
54
108
216
338
0.5
60
120
60
120
240
60
120
240
375
0.55
66
132
66
132
264
66
132
264
413
0.6
72
144
72
144
288
72
144
288
450
0.65
0.7
A-2-21
78
156
78
156
312
78
156
312
488
84
168
84
168
336
84
168
336
525
0.75
90
180
90
180
360
90
180
360
563
0.8
96
192
96
192
384
96
192
384
600
0.85
102
204
102
204
408
102
204
408
638
0.9
108
216
108
216
432
108
216
432
675
0.95
114
228
114
228
456
114
228
456
713
120
240
120
240
480
120
240
480
750
Circuit breakers
2
1.5
t
TS100
40
TS160
80
40
80
TS250
160
40
80
160
250
256
400
10
Ir
Setting value
tr
td
0.4
tsd
tsd
Ir
Isd
Ii
Icu
128
64
128
256
64
128
0.45
72
144
72
144
288
72
144
288
450
0.5
80
160
80
160
320
80
160
320
500
0.55
88
176
88
176
352
88
176
352
550
0.6
96
192
96
192
384
96
192
384
600
0.65
0.7
104
208
104
208
416
104
208
416
650
112
224
112
224
448
112
224
448
700
0.75
120
240
120
240
480
120
240
480
750
0.8
128
256
128
256
512
128
256
512
800
0.85
136
272
136
272
544
136
272
544
850
0.9
144
288
144
288
576
144
288
576
900
0.95
152
304
152
304
608
152
304
608
950
160
320
160
320
640
160
320
640
1000
500
0.4
80
160
80
160
320
80
160
320
0.45
90
180
90
180
360
90
180
360
563
0.5
100
200
100
200
400
100
200
400
625
0.55
110
220
110
220
440
110
220
440
688
0.6
120
240
120
240
480
120
240
480
750
0.65
130
260
130
260
520
130
260
520
813
140
280
140
280
560
140
280
560
875
0.75
150
300
150
300
600
150
300
600
938
1000
0.7
0.8
160
320
160
320
640
160
320
640
0.85
170
340
170
340
680
170
340
680
1063
0.9
180
360
180
360
720
180
360
720
1125
0.95
190
380
190
380
760
190
380
760
1188
200
400
200
400
800
200
400
800
1250
0.4
96
192
96
192
384
96
192
384
600
0.45
108
216
108
216
432
108
216
432
675
0.5
120
240
120
240
480
120
240
480
750
0.55
132
264
132
264
528
132
264
528
825
0.6
144
288
144
288
576
144
288
576
900
0.65
0.7
156
312
156
312
624
156
312
624
975
168
336
168
336
672
168
336
672
1050
0.75
180
360
180
360
720
180
360
720
1125
0.8
192
384
192
384
768
192
384
768
1200
0.85
204
408
204
408
816
204
408
816
1275
0.9
216
432
216
432
864
216
432
864
1350
0.95
228
456
228
456
912
228
456
912
1425
240
480
240
480
960
240
480
960
1500
A-2-22
Circuit breakers
2
1.5
t
TS100
40
TS160
80
40
80
TS250
160
40
80
160
250
448
700
10
Ir
Setting value
tr
td
0.4
tsd
tsd
Ir
Isd
Ii
Icu
224
112
224
448
112
224
0.45
126
252
126
252
504
126
252
504
788
0.5
140
280
140
280
560
140
280
560
875
0.55
154
308
154
308
616
154
308
616
963
0.6
168
336
168
336
672
168
336
672
1050
0.65
0.7
182
364
182
364
728
182
364
728
1138
196
392
196
392
784
196
392
784
1225
0.75
210
420
210
420
840
210
420
840
1313
0.8
224
448
224
448
896
224
448
896
1400
1488
0.85
238
476
238
476
952
238
476
952
0.9
252
504
252
504
1008
252
504
1008
1575
0.95
266
532
266
532
1064
266
532
1064
1663
280
560
280
560
1120
280
560
1120
1750
800
0.4
128
256
128
256
512
128
256
512
0.45
144
288
144
288
576
144
288
576
900
0.5
160
320
160
320
640
160
320
640
1000
0.55
176
352
176
352
704
176
352
704
1100
0.6
192
384
192
384
768
192
384
768
1200
0.65
208
416
208
416
832
208
416
832
1300
224
448
224
448
896
224
448
896
1400
0.75
240
480
240
480
960
240
480
960
1500
0.7
0.8
256
512
256
512
1024
256
512
1024
1600
0.85
272
544
272
544
1088
272
544
1088
1700
0.9
288
576
288
576
1152
288
576
1152
1800
0.95
304
608
304
608
1216
304
608
1216
1900
320
640
320
640
1280
320
640
1280
2000
0.4
160
320
160
320
640
160
320
640
1000
0.45
180
360
180
360
720
180
360
720
1125
0.5
200
400
200
400
800
200
400
800
1250
0.55
220
440
220
440
880
220
440
880
1375
0.6
240
480
240
480
960
240
480
960
1500
0.65
0.7
A-2-23
10
260
520
260
520
1040
260
520
1040
1625
280
560
280
560
1120
280
560
1120
1750
1875
0.75
300
600
300
600
1200
300
600
1200
0.8
320
640
320
640
1280
320
640
1280
2000
0.85
340
680
340
680
1360
340
680
1360
2125
0.9
360
720
360
720
1440
360
720
1440
2250
0.95
380
760
380
760
1520
380
760
1520
2375
400
800
400
800
1600
400
800
1600
2500
Time delay
(tsd)
.2
.1
.3
.05
t
Ir
50
100
200
300
4 settings
70t140 140t240
240t350
tr
td
tsd
tsd
Ir
Isd
Ii
Icu
Ir
tr
td
Fixed at 11In
tsd
tsd
Ir
Isd
Ii
Icu
A-2-24
.6
Ir
.7
.8
.9
.5
tr
Overload protection
(long time)
1.0
.4
td
1.5
10
.3
.2
tsd
.1
tsd
.05
.3
Ir
Isd
Ii
Icu
1.5, 2, 3, 4, 5, 6, 7, 8, 10Ir
9 settings, tolerance 15%
setting time (ms)
50
operation time (ms) 30t70
100
200
70t140 140t240
300
240t350
4 settings
Fixed at 11In
33
In630A
Trip unit frame
- 23 for TS100, TS160, TS250
- 33 for TS400, TS630
- 43 for TS800
Rated current, In
- 160, 250, 400A for TS400
- 160, 250, 400, 630A for
TS630
A-2-25
32
40
64
80
100
160
250
320
400
630
800
Trip unit
for TS400
for TS630
Setting details
Overload protection (long time)
.7
.6
Circuit breakers
Trip unit rating, In(A)
160
250
TS630
400
160
250
400
630
1.0
.4
Setting value
Ir
TS400
.8
.9
.5
tr
0.4
64
100
160
64
100
160
252
0.45
72
113
180
72
113
180
284
0.5
80
125
200
80
125
200
315
0.55
88
138
220
88
138
220
347
0.6
96
150
240
96
150
240
378
0.65
104
163
260
104
163
260
410
0.7
112
175
280
112
175
280
441
0.75
120
188
300
120
188
300
473
0.8
128
200
320
128
200
320
504
0.85
136
213
340
136
213
340
536
0.9
144
225
360
144
225
360
567
td
tsd
tsd
Ir
Isd
Ii
Icu
0.95
152
238
380
152
238
380
599
160
250
400
160
250
400
630
Ir
tr
Fixed at 6Ir
tolerance20%
tsd
tsd
Ir
Isd
Ii
Icu
A-2-26
Circuit breakers
2
1.5
t
TS400
160
250
TS630
400
160
250
400
630
10
Ir
Setting value
tr
td
tsd
tsd
Ir
Isd
Ii
Icu
0.4
96
150
240
96
150
240
378
0.45
108
169
270
108
169
270
425
0.5
120
188
300
120
188
300
473
0.55
132
206
330
132
206
330
520
0.6
144
225
360
144
225
360
567
156
244
390
156
244
390
614
168
263
420
168
263
420
662
0.75
180
281
450
180
281
450
709
0.8
192
300
480
192
300
480
756
0.85
204
319
510
204
319
510
803
0.9
216
338
540
216
338
540
851
0.95
228
356
570
228
356
570
898
240
375
600
240
375
600
945
504
0.65
0.7
1.5
0.4
128
200
320
128
200
320
0.45
144
225
360
144
225
360
567
0.5
160
250
400
160
250
400
630
0.55
176
275
440
176
275
440
693
0.6
192
300
480
192
300
480
756
0.65
208
325
520
208
325
520
819
224
350
560
224
350
560
882
0.75
240
375
600
240
375
600
945
1008
0.7
0.8
256
400
640
256
400
640
0.85
272
425
680
272
425
680
1071
0.9
288
450
720
288
450
720
1134
0.95
304
475
760
304
475
760
1197
320
500
800
320
500
800
1260
0.4
192
300
480
192
300
480
756
0.45
216
338
540
216
338
540
851
0.5
240
375
600
240
375
600
945
0.55
264
413
660
264
413
660
1040
0.6
288
450
720
288
450
720
1134
0.65
0.7
A-2-27
312
488
780
312
488
780
1229
336
525
840
336
525
840
1323
0.75
360
563
900
360
563
900
1418
0.8
384
600
960
384
600
960
1512
0.85
408
638
1020
408
638
1020
1607
0.9
432
675
1080
432
675
1080
1701
0.95
456
713
1140
456
713
1140
1795
480
750
1200
480
750
1200
1890
2
1.5
t
Circuit breakers
TS400
160
250
TS630
400
160
250
400
630
10
Ir
Setting value
tr
td
0.4
tsd
tsd
Ir
Isd
Ii
Icu
256
400
640
256
400
640
1008
0.45
288
450
720
288
450
720
1134
0.5
320
500
800
320
500
800
1260
0.55
352
550
880
352
550
880
1386
0.6
384
600
960
384
600
960
1512
1638
0.65
416
650
1040
416
650
1040
448
700
1120
448
700
1120
1764
0.75
480
750
1200
480
750
1200
1890
0.8
512
800
1280
512
800
1280
2016
2142
0.7
0.85
544
850
1360
544
850
1360
0.9
576
900
1440
576
900
1440
2268
0.95
608
950
1520
608
950
1520
2394
640
1000
1600
640
1000
1600
2520
0.4
320
500
800
320
500
800
1260
0.45
360
563
900
360
563
900
1418
0.5
400
625
1000
400
625
1000
1575
0.55
440
687.5
1100
440
688
1100
1733
0.6
480
750
1200
480
750
1200
1890
0.65
520
813
1300
520
813
1300
2048
560
875
1400
560
875
1400
2205
0.75
0.7
600
938
1500
600
938
1500
2363
2520
0.8
640
1000
1600
640
1000
1600
0.85
680
1063
1700
680
1063
1700
2678
0.9
720
1125
1800
720
1125
1800
2835
0.95
760
1188
1900
760
1188
1900
2993
800
1250
2000
800
1250
2000
3150
0.4
384
600
960
384
600
960
1512
0.45
432
675
1080
432
675
1080
1701
0.5
480
750
1200
480
750
1200
1890
2079
0.55
528
825
1320
528
825
1320
0.6
576
900
1440
576
900
1440
2268
0.65
624
975
1560
624
975
1560
2457
672
1050
1680
672
1050
1680
2646
0.7
0.75
720
1125
1800
720
1125
1800
2835
0.8
768
1200
1920
768
1200
1920
3024
0.85
816
1275
2040
816
1275
2040
3213
0.9
864
1350
2160
864
1350
2160
3402
0.95
912
1425
2280
912
1425
2280
3591
960
1500
2400
960
1500
2400
3780
A-2-28
Circuit breakers
2
1.5
t
TS400
160
250
TS630
400
160
250
400
630
10
Ir
Setting value
tr
td
0.4
tsd
tsd
Ir
Isd
Ii
Icu
448
1120
448
700
1120
1764
1984
0.45
504
788
1260
504
788
1260
0.5
560
875
1400
560
875
1400
2205
0.55
616
963
1540
616
963
1540
2425
0.6
672
1050
1680
672
1050
1680
2646
0.65
0.7
728
1138
1820
728
1138
1820
2867
784
1225
1960
784
1225
1960
3087
0.75
840
1313
2100
840
1313
2100
3308
0.8
896
1400
2240
896
1400
2240
3528
0.85
952
1488
2380
952
1488
2380
3749
0.9
1008
1575
2520
1008
1575
2520
3969
0.95
1064
1663
2660
1064
1663
2660
4190
1120
1750
2800
1120
1750
2800
4410
0.4
512
800
1280
512
800
1280
2016
0.45
576
900
1440
576
900
1440
2268
0.5
640
1000
1600
640
1000
1600
2520
0.55
704
1100
1760
704
1100
1760
2772
0.6
768
1200
1920
768
1200
1920
3024
0.65
832
1300
2080
832
1300
2080
3276
896
1400
2240
896
1400
2240
3528
0.75
960
1500
2400
960
1500
2400
3780
4032
0.7
0.8
1024
1600
2560
1024
1600
2560
0.85
1088
1700
2720
1088
1700
2720
4284
0.9
1152
1800
2880
1152
1800
2880
4536
0.95
1216
1900
3040
1216
1900
3040
4788
1280
2000
3200
1280
2000
3200
5040
0.4
640
1000
1600
640
1000
1600
2520
0.45
720
1125
1800
720
1125
1800
2835
0.5
800
1250
2000
800
1250
2000
3150
0.55
880
1375
2200
880
1375
2200
3465
0.6
960
1500
2400
960
1500
2400
3780
0.65
0.7
A-2-29
700
10
1040
1625
2600
1040
1625
2600
4095
1120
1750
2800
1120
1750
2800
4410
0.75
1200
1875
3000
1200
1875
3000
4725
0.8
1280
2000
3200
1280
2000
3200
5040
0.85
1360
2125
3400
1360
2125
3400
5355
0.9
1440
2250
3600
1440
2250
3600
5670
0.95
1520
2375
3800
1520
2375
3800
5985
1600
2500
4000
1600
2500
4000
6300
Time delay
(tsd)
.2
.1
.3
.05
t
Ir
50
100
200
300
4 settings
70t140 140t240
240t350
tr
td
tsd
tsd
Ir
Isd
Ii
Icu
Ir
tr
td
Fixed at 11In
tsd
tsd
Ir
Isd
Ii
Icu
A-2-30
.6
Ir
.7
.8
.9
.5
tr
Overload protection
(long time)
1.0
.4
td
1.5
10
.3
.2
tsd
.1
tsd
.05
.3
Ir
Isd
Ii
Icu
1.5, 2, 3, 4, 5, 6, 7, 8, 10Ir
9 settings, tolerance 15%
setting time (ms)
50
operation time (ms) 30t70
100
200
70t140 140t240
300
240t350
Fixed at 11In
43
In800A
Trip unit frame
- 23 for TS100, TS160, TS250
- 33 for TS400, TS630
- 43 for TS800
Rated current, In
- 630, 800A for TS800
A-2-31
4 settings
32
40
64
80
100
160
250
320
400
630
800
Trip unit
for TS800
Setting details
Overload protection (long time)
.7
.6
TS800
.9
.5
630
800
1.0
.4
Circuit breakers
.8
Ir
Setting value
tr
0.4
td
252
320
0.45
284
360
0.5
315
400
tsd
tsd
Ir
Isd
Ii
Icu
0.55
347
440
0.6
378
480
0.65
410
520
0.7
441
560
0.75
473
600
0.8
504
640
0.85
536
680
0.9
567
720
0.95
599
760
630
800
Ir
tr
Fixed at 6Ir
tolerance20%
tsd
tsd
Ir
Isd
Ii
Icu
A-2-32
Circuit breakers
2
1.5
t
TS800
630
800
10
Ir
Setting value
tr
td
tsd
tsd
Ir
Isd
Ii
Icu
378
0.45
425
540
0.5
473
600
0.55
520
660
0.6
567
720
614
780
0.65
0.7
1.5
480
662
840
0.75
709
900
0.8
756
960
0.85
804
1020
0.9
850.5
1080
0.95
898
1140
945
1200
640
0.4
504
0.45
567
720
0.5
630
800
0.55
693
880
0.6
756
960
0.65
819
1040
0.7
882
1120
0.75
945
1200
0.8
1008
1280
0.85
1071
1360
0.9
1134
1440
0.95
1197
1520
1600
1260
0.4
756
960
0.45
851
1080
0.5
945
1200
0.55
1040
1320
0.6
1134
1440
0.65
1229
1560
1323
1680
0.75
1418
1800
0.8
1512
1920
0.85
1607
2040
0.9
1701
2160
0.7
A-2-33
0.4
0.95
1796
2280
1890
2400
1.5
Circuit breakers
TS800
630
800
10
Ir
Setting value
tr
td
0.4
tsd
tsd
Ir
Isd
Ii
Icu
1280
0.45
1134
1440
0.5
1260
1600
0.55
1386
1760
0.6
1512
1920
0.65
0.7
1638
2080
1764
2240
0.75
1890
2400
0.8
2016
2560
0.85
2142
2720
0.9
2268
2880
0.95
2394
3040
2520
3200
1600
0.4
1260
0.45
1418
1800
0.5
1575
2000
0.55
1733
2200
0.6
1890
2400
0.65
2048
2600
2205
2800
0.75
2363
3000
3200
0.7
0.8
2520
0.85
2678
3400
0.9
2835
3600
0.95
2993
3800
3150
4000
0.4
1512
1920
0.45
1701
2160
0.5
1890
2400
0.55
2079
2640
0.6
2268
2880
0.65
0.7
2457
3120
2646
3360
0.75
2835
3600
0.8
3024
3840
0.85
3213
4080
0.9
3402
4320
0.95
3591
4560
3780
4800
A-2-34
2
1.5
t
Circuit breakers
TS800
630
800
10
Ir
Setting value
tr
td
tsd
tsd
Ir
Isd
Ii
Icu
1764
2240
0.45
1985
2520
0.5
2205
2800
0.55
2426
3080
0.6
2646
3360
2867
3640
3087
3920
0.75
3308
4200
0.8
3528
4480
0.85
3749
4760
0.9
3969
5040
0.95
4190
5320
4410
5600
0.65
0.7
0.4
2016
2560
0.45
2268
2880
0.5
2520
3200
0.55
2772
3520
0.6
3024
3840
0.65
3276
4160
3528
4480
0.75
3780
4800
0.7
0.8
4032
5120
0.85
4284
5440
0.9
4536
5760
0.95
4788
6080
5040
6400
0.4
2520
3200
0.45
2835
3600
0.5
3150
4000
0.55
3465
4400
0.6
3780
4800
0.65
4095
5200
4410
5600
0.75
4725
6000
0.8
5040
6400
0.85
5355
6800
0.9
5670
7200
0.7
A-2-35
0.4
10
0.95
5985
7600
6300
8000
Time delay
(tsd)
.2
.1
.3
.05
t
Ir
50
100
200
300
4 settings
70t140 140t240
240t350
tr
td
tsd
tsd
Ir
Isd
Ii
Icu
Ir
tr
td
Fixed at 11In
tsd
tsd
Ir
Isd
Ii
Icu
A-2-36
Ratings
Rated current, In(A)
Rated current
Trip unit
In (A)
ETM33
ETM43
160
250
400
630
800
Circuit breakers
TS400 N/H/L
TS630 N/H/L
TS800 N/H/L
ETM33
ETM33
ETM43
64
80
100
160
250
400
630
800
Applicable circuit breakers
A-2-37
TS400 N/H/L
TS630 N/H/L
TS800 N/H/L
Time delay
(tsd)
50
100
200
300
30t70
70t140
140t240
240t350
4 settings
I2t is off
100
200
300
400
ZSI (Z)
4 settings
I2t is off
A-2-38
Ir = 625A
It = 540A
Indication LED
tr
Ir = 760A
It = 695A
Isd
ON
ON
tsd
OFF
lg
ta
li
OFF
A-2-39
Ir = 625A
It = 540A
Indication LED
Battery
Test connector
Alarm LED
90% Ir : ON,
105% Ir or more: ON-OFF
Alarm indication
90%
105%
alarm
Ir
Isd
Ig
The LED lights and remains lit when the load exceeds 90 % of Ir.
The LED blinks for an overload(105% Ir), warning that the circuit breaker may trip.
Fault indications
LEDs indicate the type of fault that caused tripping:
Ir : overload
Isd : short-circuit ( short time, instantaneous)
Ig : earth fault
If push the TR button to indicate the tripping reason, the indication LED of tripping is ON.
The information is however stored in memory and the LED can be reilluminated by pressing the TR button.
The LED automatically goes off and the memory is cleared when the circuit breaker is reset.
In normal condition, if push TR button, all indication LED is ON for testing auxiliary power and LED.
A-2-40
.8
.9
.95
.9
.7
.6
.85
.8
.5
12
8
6
4
tr
12
tr(6Ir)
4
Isd
2
1.5
ON
ON
.5
.6
.3
.2
2
.3 I t
10
.3
.2
.2
.1
.1
.05
.05
on tsd off
tsd
li
tg
OFF
.4
OFF
lg
.4
.8
.3
1
off
.2
I2t
Instantaneous protection
Ii = Instantaneous threshold
10
1.5
.7
11
.4
.3
.2
.1
.1
on tg off
33
In600A
Trip unit frame
- 33 for TS400, TS630
- 43 for TS800
Rated current, In
- 160, 250, 400A for TS400
- 160, 250, 400, 630A for TS630
A-2-41
16
32
40
64
80
100
160
250
320
400
630
800
for TS400
for TS630
.9
.7
.6
.5
TS400ETM
160
250
400
Setting
tr
Isd
ON
ON
value
Coarse, Io
Fine, Ir
ta
0.8
64
100
160
0.85
68
106.25
170
0.9
72
112.5
180
0.95
76
118.75
190
200
tsd
OFF
lg
Setting
value
li
OFF
0.5
I
0.6
0.7
0.8
0.9
80
125
0.8
76.8
120
192
0.85
81.6
127.5
204
0.9
86.4
135
216
0.95
91.2
142.5
228
96
150
240
0.8
89.6
140
224
0.85
95.2
148.75
238
0.9
100.8
157.5
252
0.95
106.4
166.25
266
112
175
280
0.8
102.4
160
256
0.85
108.8
170
272
0.9
115.2
180
288
0.95
121.6
190
304
128
200
320
0.8
115.2
180
288
0.85
122.4
191.25
306
0.9
129.6
202.5
324
0.95
136.8
213.75
342
144
225
360
0.8
128
200
320
0.85
136
212.5
340
0.9
144
225
360
0.95
152
237.5
380
160
250
400
A-2-42
.9
.7
TS630ETM
.6
.5
160
250
400
630
Setting
tr
Isd
Setting
value
value
Coarse, Io
Fine, Ir
0.8
ON
ON
ta
64
100
160
252
0.85
68
0.9
72
106.25
170
267.75
112.5
180
0.95
283.5
76
118.75
190
299.25
80
125
200
315
tsd
OFF
lg
li
OFF
0.5
I
0.6
0.7
0.8
0.9
0.8
76.8
120
192
302.4
0.85
81.6
127.5
204
321.3
0.9
86.4
135
216
340.2
0.95
91.2
142.5
228
359.1
96
150
240
378
0.8
89.6
140
224
352.8
0.85
95.2
148.75
238
374.85
0.9
100.8
157.5
252
396.9
0.95
106.4
166.25
266
418.95
112
175
280
441
0.8
102.4
160
256
403.2
0.85
108.8
170
272
428.4
0.9
115.2
180
288
453.6
0.95
121.6
190
304
478.8
128
200
320
504
0.8
115.2
180
288
453.6
0.85
122.4
191.25
306
481.95
0.9
129.6
202.5
324
510.3
0.95
136.8
213.75
342
538.65
144
225
360
567
0.8
128
200
320
504
0.85
136
212.5
340
535.5
0.9
144
225
360
567
0.95
152
237.5
380
598.5
160
250
400
630
Setting example : In
Io
Ir
A-2-43
400A
0.5
0.6
0.7
0.8
0.9
0.8
0.85
0.9
0.95
0.6
0.7
0.8
0.9
0.8 0.85
0.9
0.95
1.5
1.5
10
10
2
.3 I t
tsd
0.05...0.3s
0.05...0.3s
.2
.1
.1
.05
tsd
.3
.2
.05
on tsd off
lg
0.2....1In
lg
.6
0.2....1In
.8
1
off
.3
.2
0.1....0.4s
tg
.7
.4
0.1....0.4s
tg
.4
I2t
.4
.3
.3
.2
.2
.1
.1
on tg off
A-2-44
Intentional
delay: 0.2s
CB1
Instantaneous
protection
operation
Intentional
delay: 0.1s
CB2
Fault 2
Instantaneous
protection operation
Fault 1
A-2-45
CB3
Zone
Selective Interlocking
Transmitted data :
Protection setting values
Highest current of the three phases
Measurement: R, S, T and N phase current
Fault reading: Type of fault (Overload, short-circuit, etc)
The setting of communication address using TR button and LCD display (Ammeter).
Power source: DC24V Power is required.
Combination of options
A(Ammeter)
E(Earth fault protection)
A+E
A +C(Communication)
A+E+C
A-2-46
A-2-47
ETM33 A
ETM33 A+C
ETM33 Z+A
ETM33 Z+A+C
ETM33 E
ETM33 Z+E
ETM33
ETM33 Z
A-2-48
Ir = 760A
It = 695A
Battery
Test connector
90%
105%
alarm
Ir
Isd
Ig
A-2-49
Alarm indication
The LED lights and remains lit when the load exceeds 90 % of Ir.
The LED blinks for an overload(105% Ir), warning that the circuit breaker may trip.
Fault indications
LEDs indicate the type of fault that caused tripping:
Ir : overload
Isd : short-circuit (short time, instantaneous)
Ig : earth fault
The information is however stored in memory and the LED can be reilluminated by pressing the TR button.
The LED automatically goes off and the memory is cleared when the circuit breaker is reset.
In normal condition, if push TR button, all indication LED is ON for testing auxiliary power and LED.
.8
.9
.95
.9
.7
.6
.85
.8
.5
t
12
8
6
tr
12
tr(6Ir)
4
Isd
7
8
2
.3 I t
10
.2
.1
.1
.05
.05
on tsd off
tsd
li
tg
OFF
.5
.6
.4
.7
I2t
10
1.5
Instantaneous protection
Ii = Instantaneous threshold
11
.4
.4
.8
.3
.3
.3
1
off
.2
.2
.2
.3
.2
OFF
lg
ON
2
1.5
ON
.1
.1
on tg off
43
In800A
Trip unit frame
- 33 for TS400, TS630
- 43 for TS800
Rated current, In
- 630, 800A for TS630
A-2-50
16
32
40
64
80
100
160
250
320
400
for TS800
.9
.7
.6
.5
TS800ETM
630
800
Setting
tr
Isd
ON
ON
value
Coarse, Io
Fine, Ir
ta
0.8
252
320
0.85
267.75
340
0.9
283.5
360
0.95
299.25
380
tsd
OFF
lg
Setting
value
li
OFF
0.5
I
0.6
0.7
0.8
0.9
A-2-51
315
400
0.8
302.4
384
0.85
321.3
408
0.9
340.2
432
0.95
359.1
456
378
480
0.8
352.8
448
0.85
374.85
476
0.9
396.9
504
0.95
418.95
532
441
560
0.8
403.2
512
0.85
428.4
544
0.9
453.6
576
0.95
478.8
608
504
640
0.8
453.6
576
0.85
481.95
612
0.9
510.3
648
0.95
538.65
684
567
720
0.8
504
640
0.85
535.5
680
0.9
567
720
0.95
598.5
760
630
800
630
800
0.6
0.7
0.8
0.9
0.8 0.85
0.9
0.95
1.5
1.5
10
10
2
.3 I t
tsd
0.05...0.3s
0.05...0.3s
.2
.1
.1
.05
tsd
.3
.2
.05
on tsd off
lg
0.2....1In
lg
.6
0.2....1In
.8
1
off
.3
.2
0.1....0.4s
tg
.7
.4
0.1....0.4s
tg
.4
I2t
.4
.3
.3
.2
.2
.1
.1
on tg off
A-2-52
Intentional
delay: 0.2s
CB1
Instantaneous
protection
operation
Intentional
delay: 0.1s
CB2
Fault 2
Instantaneous
protection operation
Fault 1
A-2-53
CB3
Zone
Selective Interlocking
Transmitted data:
Protection setting values
Highest current of the three phases
Measurement: R, S, T and N phase current
Fault reading: Type of fault (Overload, short-circuit, etc)
The setting of communication address using TR button and LCD display (Ammeter).
Power source: DC24V Power is required.
Combination of options
A(Ammeter)
E(Earth fault protection)
A+E
A +C(Communication)
A+E+C
A-2-54
A-2-55
ETM43 A
ETM43 A+C
ETM43 Z+A
ETM43 Z+A+C
ETM43 E
ETM43 Z+E
ETM43
ETM43 Z
A-2-56
TS100
Frame size
[A]
TS250
250
100
160
100, 160
[AF]
Rated current, In
TS160
No. of poles
Rated operational
AC
[V]
690
690
690
voltage, Ue
DC
[V]
500
500
500
[kV]
[V]
750
750
750
[kA]
100
120
200
100
120
200
100
120
200
380/415V
[kA]
50
85
150
50
85
150
50
85
150
440/460V
[kA]
50
70
130
50
70
130
50
70
130
480/500V
[kA]
42
65
85
42
65
85
42
65
85
660/690V
[kA]
10
15
20
10
15
20
10
15
20
100%
100%
100%
100%
100%
100%
100%
100%
100%
220/240V
220/240V
[kA]
220
264
440
220
264
440
220
264
440
380/415V
[kA]
105
187
330
105
187
330
105
187
330
440/460V
[kA]
105
154
286
105
154
286
105
154
286
480/500V
[kA]
88
143
187
88
143
187
88
143
187
660/690V
[kA]
17
30
40
17
30
40
17
30
40
Category of utilization
Isolation behavior
front-connection
rear-connection
front-connection
magnetic only
Connection
fixed
plug-in
MTU
Mechanical life
[operations]
25000
25000
25000
[operations]
10000
10000
10000
10516086
10516086
10516086
IEC60947-2
IEC60947-2
IEC60947-2
rear-connection
3-pole
[mm]
3-pole
[kg]
(front connection)
Weight
(front connection)
Reference standard
A-2-57
TS400
TS630
TS800
400
630
800
320
500
630
690
690
690
500
500
500
750
750
750
100
120
200
100
120
200
100
120
200
65
85
150
65
85
150
65
100
150
65
85
130
65
85
130
65
100
130
42
65
85
42
65
85
42
85
100
10
20
35
10
20
35
10
20
35
100%
100%
100%
100%
100%
100%
100%
100%
100%
220
264
440
220
264
440
220
264
440
143
187
330
143
187
330
143
220
330
143
187
286
143
187
286
143
220
286
88
143
187
88
143
187
88
187
220
17
40
74
17
40
74
17
40
74
20000
20000
10000
6000
6000
3000
140260110
140260110
210320135
5.4
5.4
15.1
IEC60947-2
IEC60947-2
IEC60947-2
A-2-58
L1
L2
L3
Breaker
Contactor
O/L
T1
T2
T3
M
Magnetic only
release
Motor
Configuration
Trip unit identification
MTU
Magnetic only release
MCCB frame type
- TS100: TS100N, TS100H, TS100L
- TS160: TS160N, TS160H, TS160L
- TS250: TS250N, TS250H, TS250L
- TS400: TS400N, TS400H, TS400L
- TS630: TS630N, TS630H, TS630L
- TS800: TS800N, TS800H, TS800L
A-2-59
In
TS100 to TS800
1.6
3.2
6.3
12
20
32
50
63
100
160
220
320
500
TS160
TS250
TS400
TS630
TS800
N / H / L TS100
630
Im
setting
6..12In (6 Point)
Setting details
MTU In
6In
..
..
..
..
12In
MTU In
6In
..
..
..
..
12In
1.6
3.2
6.3
12
20
32
50
63
10
20
40
70
120
190
300
400
12
24
48
84
144
228
360
480
14
28
56
98
168
266
420
560
16
32
64
112
192
304
480
640
18
36
72
126
216
342
540
720
20
40
80
140
240
380
600
800
100
160
220
320
500
630
600
960
1320
1920
3000
3780
720
1152
1584
2304
3600
4536
840
1344
1848
2688
4200
5292
960
1536
2112
3072
4800
6048
1080
1728
2376
3456
5400
6804
1200
1920
2640
3840
6000
7560
TS100 MTU
- Adjustable magnetic only unit
MTU
560
480
400
640
720
800
Im
63A
3P
TS160 MTU
- Adjustable magnetic only unit
MTU
1344
1152
960
1536
1728
1920
Im
160A
3P
TS250 MTU
- Adjustable magnetic only unit
MTU
1848
1584
1320
2112
2376
2640
Im
220A
Im = 6...12In
3P
14
12
4600
3800
3000
Im
5400
6200
10
16
18
20
500A
7000
Im
A-2-60
Switch-Disconnectors
TD series
Frame size
Conventional thermal current, Ith
TD160NA
TS100NA
TS160NA
[AF]
160
100
160
[A]
160
100
160
2, 3, 4
2, 3, 4
2, 3, 4
690
690
No. of poles
Rated operational voltage,
AC
[V]
690
Ue
DC
[V]
500
500
500
160
100
160
[kV]
[V]
750
750
750
3.1
2.8
3.6
Rated short-time
1s
[A rms]
2200
2000
2500
3s
[A rms]
2200
2000
2500
[A rms]
960
690
960
front-connection
rear-connection
front-connection
rear-connection
25000
25000
25000
[kA peak]
20s
Isolation behavior
Trip unit (release)
disconnector unit
Connection
fixed
plug-in
DSU
Mechanical life
[operations]
[operations]
10000
10000
10000
[mm]
9014086
10516086
10516086
(front connection)
[mm]
12014086
14016086
14016086
1.5
4-pole
Weight
3-pole
[kg]
(front connection)
4-pole
[kg]
Reference standard
1.8
2.6
2.6
IEC60947-3
IEC60947-3
IEC60947-3
The switch-disconnectors are different from the circuit-breakers in the absence of the
conventional protection unit. They keep the overall dimensions, connection systems
and accessories unchanged from the corresponding circuit-breakers. Installation
standards require upstream protection. However, thanks to their high-set magnetic
release, TD160 ... TS800 DSU are self protected.
A-2-61
Switch-Disconnectors
TS series
TS250NA
TS400NA
TS630NA
TS800NA
250
400
630
800
250
400
630
800
2, 3, 4
2, 3, 4
2, 3, 4
2, 3, 4
690
690
690
690
500
500
500
500
250
400
630
800
750
750
750
750
4.9
7.1
8.5
12
3500
5000
6300
8000
3500
5000
6300
8000
1350
1930
2320
2560
25000
20000
20000
10000
10000
6000
6000
3000
10516086
140260110
140260110
210320135
14016086
186.5260110
186.5260110
280320135
5.4
5.4
15.1
2.6
7.2
7.2
19.6
IEC60947-3
IEC60947-3
IEC60947-3
IEC60947-3
A-2-62
Frame size
(AF)
TD100
TD160
TS100
TS160
TS250
TS400
TS630
TS800
100
160
100
160
250
400
630
800
300, 400
500, 630
700, 800
(Pole)
125, 160
200, 250
2, 3, 4
2, 3, 4
2, 3, 4
2, 3, 4
2, 3, 4
2, 3, 4
2, 3, 4
2, 3, 4
1000V
4P
4P
4P
4P
4P
4P
4P
4P
750V
3P
3P
3P
3P
3P
3P
3P
3P
500V
2P
2P
L
2P
L
2P
L
2P
L
2P
L
2P
L
2P
Rated service
Type
breaking
1000V (4P)
42
65 100 42
(DC)
750V (3P)
42
65 100 42
500V (2P)
42
65 100 42
Trip unit
FTU (fixed-thermal,
fixed-magnetic)
FMU (adjustable-thermal,
fixed-magnetic)
ATU (adjustable-thermal,
adjustable-magnetic)
Load
Load
DC500V (2P)
A-2-63
DC750V (3P)
Load
DC1000V (4P)
Load
Designation
TS400, TS630
TS800
N/H/L
N/H/L
N/H/L
Type
Rated current
630, 800A
Poles
4 (N-R-S-T, R-S-T-N)
4 (N-R-S-T, R-S-T-N)
4 (N-R-S-T, R-S-T-N)
AC750V
AC750V
AC750V
8kV
8kV
8kV
Insulation voltage, Ui
Impulse withstand voltage, Uimp
Short-circuit breaking capacity, Icu
AC 50/60Hz
220/240V
100
120
200
100
120
200
100
120
200
380/415V
50
85
150
50
85
150
50
85
150
440/460V
50
70
130
50
70
130
50
70
130
480/500V
42
65
85
42
65
85
42
65
85
660/690V
10
15
20
10
15
20
10
15
20
Ics
Utilization category
Reverse connection (Line/Load)
Tripping device
100% Icu
100% Icu
100% Icu
Available
Available
Available
Electronics
Electronics
Electronics
ETS
Thermal
Io, Ir
Instant.
Neutral protection
Ir = 0.8~1.0 Io (5settings)
Ir = 0.8~1.0 Io (5settings)
12 In
12 In
12 In
4P3d
No protection
No protection
No protection
4P3d+N/2
0.5 Ir
0.5 Ir
0.5 Ir
tr (6Ir)
Im
It
4P4d
1.0 Ir
1.0 Ir
1.0 Ir
Min
10mm2 or 8 AWG(40A)
70mm2(160A)
Max
120mm2 or 250kcmil(250A)
240mm2 2(800A)
Tighetning Torque
MCCB (W H D)
140 160 86
Cable
A-2-64
TS1000
TS1250
TS1600
Ampere frame
1000
1250
1600
Pole
3, 4
3, 4
3, 4
1250
1600
Type
TS1000
Rated current,(A)
In
-5~40C
800, 1000
Uimp
Ue
TS1600
50C
800, 1000
1250
1560
65C
800, 1000
1250 *
1420
1000
1000
Ui
TS1250
1000
AC50/60Hz
690
690
690
DC
Rated short-circuit breaking capacity
IEC60947-2
220/240V
55
75
200
55
75
55
75
AC50/60Hz
380/415V
50
70
150
50
70
50
70
440/460V
50
65
130
50
65
50
65
480/500V
40
50
100
40
50
40
50
660/690V
35
45
35
45
35
45
250V 2P
500V 2P
750V 3P
100%
75%
100%
100%
75%
100%
75%
(sym)
DC
Rated service
%Icu
AC50/60Hz 1s
25
3s
kA peak
12
-
50
30
25
25
50
50
Isolation
Category
10000
4000
10000
10000
In/2
6000
4000
5000
5000
In
5000
3000
4000
2000
In/2
4000
3000
3000
2000
In
2000
2000
2000
1000
Electrical life
440V
(operations)
690V
Pollution degree
Dimension (mm)
3
3-pole
(H W D)
4-pole
Weight (kg)
3-pole
13
4-pole
16.8
A-2-65
N type
A type
P type
S type
Externals
Current
protection
Other
protection
L / S / I / G / Thermal
L / S / I / G / Thermal
ZSI(Protective coordination)
Earth leakage (Option)
Current (R / S / T / N)
Measurement
function
Fine adjustment
Digital Output
3DO (Fixed)
L, S/I, G Alarm
IDMTL setting
Communication
Power supply
RTC timer
LED for
trip info.
Fault recording
Self Power
-Power source
works over 25% of
current of In (one pole)
Available
Long time delay
Short time delay/Instantaneous
Ground fault
-
Event recording
Operating
Reset button button
L / S / I / G / Thermal(Continuous)
ZSI(Protective coordination)
Earth leakage(Option)
Over/Under current
Over/Under frequency
Unbalance(Voltage/Current)
Reverse power
3 Phase Voltage/Current
RMS/Vector
Power(P, Q, S), PF(3-Phase)
Energy(Positive/Negative)
Frequency, Demand
Modbus/RS-485
Profibus-DP
Self Power
- Power source works over
25% of current of In (one pole)
- External power source are
required for comm.
AC/DC 100~250V
DC 24~60V
Available
Available
N type
N type
10 records
(Fault/Current/Date and Time)
Reset, Menu
Up/Down, Left/Right, Enter
P type
P type
3 Phase Voltage/Current
RMS/Vector
Power(P, Q, S), PF(3-Phase)
Energy(Positive/Negative)
Frequency, Demand
Voltage/Current harmonics
(1st~63th)
3 Phase Waveforms
THD, TDD, K-Factor
P type
P type
P type
P type
Modbus / RS-485
Profibus-DP
AC/DC 100~250V
DC 24~60V
256 records
(Fault/Current/Date and Time)
256 records(Content, Status, Date)
A type
Available
N type
256 records
Last fault wave recording (3 Phase)
P type
A type
A-2-66
Alarm SP
Ir
Isd
Ii
Ig
Ig: Ground fault current setting, tg: Ground fault tripping delay setting
Test terminal: OCR test terminal (Connected with OCR tester)
A-2-67
t
Ir
tr
lsd
tsd
Ii
I
Iu = In...
Ir = Iu...
tr@(1.5lr)
tr@(6.0lr)
tr@(7.2lr)
Isd = Ir...
Ig
tsd
0.7
0.85
50
2
1.38
0.8
0.88
100
4
2.7
0.9
0.9
200
8
5.5
1.0
0.93
300
12
8.3
0.95
400
16
11
0.98
500
20
13.8
1.0
Off
Off
Off
1.5
10
Off
0.2
0.2
0.3
0.3
0.4
0.4
160
260
360
240
340
440
I t Off
0.05 0.1
I2t On
0.1
Min. Trip
20
80
Time(ms)
Max. Trip
80
140
Time(ms)
Ii = In...
2
3
4
50(10ms)
10
12
15
Off
Ig = In...
0.2
0.7
0.8
1.0
Off
tg
tg
0.6
0.83
25
1
0.69
(I2t Off)
Instantaneous
Current setting (A)
Tripping time
Ground fault
Pick-up (A)
Accuracy: 10%(Ig0.4In)
20%(Ig0.4In)
0.5
0.8
12.5
0.5
0.34
(I2t Off)
0.3
0.4
0.5
0.6
0.05 0.1
I2t Off
I2t On
0.1
Min. Trip
20
80
Time(ms)
Max. Trip
80
140
Time(ms)
0.2
0.2
0.3
0.3
0.4
0.4
160
260
360
240
340
440
Ir = In...
tr@(1.2Ir)
tr@(3Ir)
tr@(6Ir)
0.8
10
0.99
0.24
0.9
15
1.49
0.36
1.0
20
1.99
0.48
1.05
25
2.48
0.59
1.1
30
2.98
0.71
1.15
40
3.97
0.95
1.2
50
4.97
1.19
1.25
60
5.96
1.43
Off
100
9.93
2.38
Isd = In...
2.5
2.7
3.5
4.5
Off
I t Off
0.05 0.1
I2t On
0.1
Min. Trip
20
80
Time(ms)
Max. Trip
80
140
Time(ms)
0.2
0.2
0.3
0.3
0.4
0.4
160
260
360
240
340
440
10
12
14
16
Off
tsd
(I2t Off)
Instantaneous
Current setting (A)
Tripping time
Ii = In...
2
4
6
50(10ms)
A-2-68
Overload protection
-Long-time delay
-Thermal
Short-circuit protection
-Short-time delay / Instantaneous
-I2t On/Off optional (for short-time delay)
Ground fault protection
-I2t On/Off optional
Realization of protective coordination by ZSI
(Zone Selective Interlocking)
High-performance and high-speed MCU built-in
-Accurate measurement with tolerance of 1.0%
Alarm SP
Ir
Isd
Ii
Ig
Comm
Reset
Esc
Iu, Ir: Long-time current setting, tr: Long-time tripping delay setting
Isd: Short-time current setting, tsd: Short-time tripping delay setting
Ii: Instantaneous current setting
Ig: Ground fault current setting, tg: Ground fault tripping delay setting
Test terminal: OCR test terminal (Connected with OCR tester)
A-2-69
Ir
tr
lsd
tsd
Ii
I
Iu = In...
0.5
0.6
Ir = Iu...
0.8
0.7
0.8
0.9
tr@(1.5lr)
12.5 25
50
100
tr@(6.0lr)
0.5
100ms
tr@(7.2lr)
Isd = Ir...
1.0
0.93 0.95 0.98
1.0
200
300
400
500
Off
12
16
20
Off
5.5
8.3
11
13.8
Off
1.5
10
Off
Short time
Current setting (A)
Accuracy: 10%
Time delay (s)
@ 10Ir
tsd
I2t Off
0.05 0.1
0.2
0.3
0.4
I2t On
0.1
0.2
0.3
0.4
20
80
160
260
360
80
140
240
340
440
10
12
15
Off
0.4
0.5
0.6
0.7
0.8
1.0
Off
10
20
30
Off
Min. Trip
(I2t Off)
Time(ms)
Max. Trip
Time(ms)
Instantaneous
Current setting (A)
Ii = In...
Tripping time
50(10ms)
Ground fault
Pick-up (A)
Accuracy: 10%(Ig0.4In)
Ig = In...
0.2
0.3
20%(Ig0.4In)
Ig
tg
tg
I2t Off
0.05 0.1
0.2
0.3
0.4
I2t On
0.1
0.2
0.3
0.4
20
80
160
260
360
80
140
240
340
440
0.5
140
230
350
800
950
140
230
350
800
Min. Trip
(I2t Off)
Time(ms)
Max. Trip
Time(ms)
In
Alarm
Accuracy: 15%
Time(ms)
Trip
Time(ms)
A-2-70
Alarm SP
Ir
Isd
Ii
Ig
Comm
Reset
Esc
A-2-71
tr
lsd
tsd
Ii
I
Long time
Current setting (A)
Time delay (s)
Accuracy: 15% or below
100ms
Short time
Current setting (A)
Accuracy: 10%
Time delay (s)
@ 10Ir
Ir = In...
tr@(1.5lr)
tr@(6.0lr)
tr@(7.2lr)
0.4
12.5
0.5
0.34
0.5
25
1
0.69
0.6
50
2
1.38
0.7
100
4
2.7
0.8
200
8
5.5
0.9
300
12
8.3
1.0
400
16
11
500
20
13.8
Off
Off
Off
Isd = Ir...
1.5
10
Off
0.2
0.2
0.3
0.3
0.4
0.4
80
160
260
360
140
240
340
440
tsd
(I2t Off)
Instantaneous
Current setting (A)
Tripping time
Ground fault
Pick-up (A)
Accuracy: 10%(Ig0.4In)
20%(Ig0.4In)
Ig
I n
0.05 0.1
0.1
20
Time(ms)
Max. Trip
80
Time(ms)
Ii = In...
2
3
4
50(10ms)
10
12
15
Off
Ig = In...
0.2
0.7
0.8
1.0
Off
10
20
30
Off
tg
tg
I2t Off
I2t On
Min. Trip
(I2t Off)
I2t Off
I2t On
Min. Trip
0.3
0.4
0.5
0.6
0.05 0.1
0.1
0.2
0.2
0.3
0.3
0.4
0.4
80
160
260
360
140
240
340
440
230
350
800
950
230
350
800
20
Time(ms)
Max. Trip
80
Time(ms)
In
0.5
Alarm
140
Time(ms)
Trip
140
Time(ms)
Other protection
Under voltage
Over voltage
Voltage unbalance
Reverse power
Over power
Current unbalance
Over
60Hz
frequency
50Hz
Under
60Hz
frequency
50Hz
Ip = Ir x
0.6
0.65 0.7
0.75 0.8
0.85 0.9
0.95
tp@(1.2Ip)
15
25
35
Off
Setting range
80V ~ 0V_Pick-up
UV_Pick-up ~ 980V
6% ~ 99%
10~500 kW
500~5000 kW
6% ~ 99%
UF_Pick-up ~ 65
UF_Pick-up ~ 55
55Hz ~ OF_Pick-up
45Hz ~ OF_Pick-up
Pick-up
Step
1V
1V
1%
1kW
1kW
1%
1Hz
1Hz
1Hz
1Hz
10
Accuracy
5%
5%
2.5% or (*10%)
10%
10%
2.5% or (*10%)
0.1Hz
0.1Hz
0.1Hz
0.1Hz
20
30
Time delay(s)
Setting range Step Accuracy
1.2~40sec
0.2~40sec
0.1sec
0.1sec
1.2~40sec
A-2-72
Fault recording
-Records Max. up to 256 fault information about fault
type, fault phase, fault value, occurrence time of fault
-Fault wave recording: records the latest fault wave
Event recording
-Records events of device related to setting change,
operation and state change. (Max. up to 256)
SBO (Select Before Operation)
-High reliability for control and setting change method
Power quality analysis
-Measurement for 1st~63th harmonics
-THD, TDD, k-Factor
-Voltage/current waveform capture
3 DO(Digital output)
-Programmable for alarm, trip and general DO
Communication
-Modbus/RS485
-Profibus-DP
Alarm SP
Ir
Isd
Ii
Ig
Comm
Reset
Esc
A-2-73
tr
lsd
tsd
Ii
I
Long time
Current setting (A)
Time delay (s)
Accuracy: 15% or below
100ms
Short time
Current setting (A)
Accuracy: 10%
Time delay (s)
@ 10Ir
Iu = In...
tr@(1.5lr)
tr@(6.0lr)
tr@(7.2lr)
0.4
12.5
0.5
0.34
0.5
25
1
0.69
0.6
50
2
1.38
0.7
100
4
2.7
0.8
200
6
5.5
0.9
300
12
8.3
1.0
400
16
11
500
20
13.8
Off
Off
Off
Isd = Ir...
1.5
10
Off
0.2
0.2
0.3
0.3
0.4
0.4
80
160
260
360
140
240
340
440
tsd
(I2t Off)
Instantaneous
Current setting (A)
Tripping time
Ground fault
Pick-up (A)
Accuracy: 10%(Ig0.4In)
20%(Ig0.4In)
Ig
I n
0.05 0.1
0.1
20
Time(ms)
Max. Trip
80
Time(ms)
Ii = In...
2
3
4
50(10ms)
10
12
15
Off
Ig = In...
0.2
0.7
0.8
1.0
Off
10
20
30
Off
tg
tg
I2t Off
I2t On
Min. Trip
(I2t Off)
I2t Off
I2t On
Min. Trip
0.3
0.4
0.5
0.6
0.05 0.1
0.1
0.2
0.2
0.3
0.3
0.4
0.4
80
160
260
360
140
240
340
440
230
350
800
950
230
350
800
20
Time(ms)
Max. Trip
80
Time(ms)
In
0.5
Alarm
140
Time(ms)
Trip
140
Time(ms)
Other protection
Under voltage
Over voltage
Voltage unbalance
Reverse power
Over power
Current unbalance
Over
60Hz
frequency
50Hz
Under
60Hz
frequency
50Hz
Ip = Ir x
0.6
0.65 0.7
0.75 0.8
0.85 0.9
0.95
tp@(1.2Ip)
15
25
35
Off
Setting range
80V ~ 0V_Pick-up
UV_Pick-up ~ 980V
6% ~ 99%
10~500 kW
500~5000 kW
6% ~ 99%
UF_Pick-up ~ 65
UF_Pick-up ~ 55
55Hz ~ OF_Pick-up
45Hz ~ OF_Pick-up
Pick-up
Step
1V
1V
1%
1kW
1kW
1%
1Hz
1Hz
1Hz
1Hz
10
Accuracy
5%
5%
2.5% or (*10%)
10%
10%
2.5% or (*10%)
0.1Hz
0.1Hz
0.1Hz
0.1Hz
20
30
Time delay(s)
Setting range Step Accuracy
1.2~40sec
0.2~40sec
0.1sec
0.1sec
1.2~40sec
A-2-74
N, A type
.8
Ir
.9
.7
.88
.9
tr
.6
.83
.5
Iong time
.8
In
.93
.85
.95
.98
P, S type
.7
.8
20
.5
.9
(S)
12
.5
16
20
1
.4
Ir
Iong time
.5
In
off
@6 Ir
tr
off
@6 Ir
tr
.6
Iu
Ir
tsd
6
3
2
1.5
(S)
.3
10
.2
.4
.4
off
.1
short time
.05
on 2 off
Ir
I t
Isd
tsd
Instantaneous (I)
The function for breaking fault current above the setting value within
Ii
12
15
2
off
instantaneous
In
Ii
A-2-75
.5
.6
tg
.7
.4
(S)
.4
.3
.4
.8
.3
.2
.3
.2
.1
.2
off
.1
ground fault
.05
on 2 off
In
I t
Ig
tg
(ms)
800
900
10
350
350
20
230
230
0.5
time delay to protect the circuit from earth leakage. (A, P, S type)
800
140
140
30
Earth Leakage trip alarm
I n
R S T N
ZCT or External
CT
- When using a standard ZCT provided by LS, the setting range is from 0.5 to 30A which is
based on its primary current. But MCCB installed like A type (displayed on the left side)
should only be cable-connected and its rated current should be less than 1600A.
- When using other CT selected by customers, the setting range is from 0.5 to 5A based on
its secondary current.(Secondary output rating : 5A)
Hence, under 100:5A CT, if trip relay is set to 0.5A, earth-leakage exceeding 10A will
activate its operation (0.5A20 = 10A)
ZCT or External
CT
A-2-76
A type
Measurement function
Class.
Measurement
element
Line current
Ia,Ib,Ic
Current
Normal current
I1
Voltage
Angle
P type
Power
Reverse current
I2
Vab,Vbc,Vca
Phase voltage
Va,Vb,Vc
Normal voltage
V1
Freq.
Unbalance
S type
80A~65,535A
1%
60~690V
0~360
V2
Line-to-current
VabVbc, VabVca
Phase-to-phase
VaVb,VaVc
Phase-to-current
Active power
kW
1kW~99,999kW
3%
Reactive power
kVar
1kVar~99,999kVar
3%
Apparent power
kVA
1kVA~99,999kVA
3%
WHa(ab), WHb(bc),
kWh
WHc(ca), WH
MWh
1kWh~9999.99MWh
3%
1kVarh~9999.99MVarh
3%
1kWh ~9999.99MWh
3%
VARHa(ab), VARHb(bc),
kVarh
VARHc(ca), VARH
Mvarh
Reverse active
rWHa(ab), rWHb(bc),
kWh
energy
rWHc(ca), rWH
MWh
Frequency
Power factor(PF)
Unbalance rate
Iunalance, Vunbalance
0.0~100.0
Peak demand
kW
1kW~99999kW
Current demand
Peak demand
80A~65,535A
Voltage
1st~63th harmonics of
harmonics
Va(ab),Vb(bc),Vc(ca)
60~690V
Current harmonics
Hz
45~65Hz
+: Lead, -: Lag
80A~65,535A
THD, TDD
0.0~100.0
K-Factor
0.0~100.0
Vr Vs Vt Vn
Vr Vs Vt
Voltage
module
3P4W wiring
A-2-77
13
14
15
16
17
18
19
20
V1
V2
V3
Vn
1
2
3
4
5
6
7
8
9
10
11
12
1
1
Voltage module
1
2
3
4
5
6
7
8
9
10
11
12
1%
demand
Harmonics
Accuracy
Line-to-line
Active power
Demand
Display range
Reverse voltage
Reactive energy
Power factor
Unit
3%
Line voltage
Active energy
Energy
Detailed element
Voltage
module
3P3W wiring
13
14
15
16
17
18
19
20
V1
V2
V3
Vn
Zone-selective interlocking drops delay time that eliminates faults for breakers.
It minimizes the shock that all kinds of electric machineries get under
fault conditions.
1. In case of that short time-delay or ground fault accident occurs at ZSI built in system,
the breaker at accident site sends ZSI signal to halt upstream breakers operation.
2. To eliminate a breakdown, trip relay of MCCB at accident site activates trip operation
without time delay.
3. The upstream breaker that received ZSI signal adhere to pre-set short time-delay or
ground fault time-delay for protective coordination in the system.
However upstream breaker that did not receive its signal will trip instantaneously.
4. For ordinary ZSI operation, it should arrange operation time accordingly so that downstream
circuit breakers will react before upstream ones under overcurrent/short time delay/
ground fault situations.
5. ZSI connecting line needs to be Max. 3m.
Z4
Z3
Z2
Z1
ZSI input
Fault A
Z4
Z3
Z2
Z1
ZSI output
ZSI input
Fault B
Z4
Z4
Z4
Z3
Z3
Z3
Z2
Z2
Z2
Z1
Z1
Z1
1) Occurrence of fault A
- Only breaker performs instantaneous trip operation.
2) Occurrence of fault B
- Breaker performs instantaneous trip operation,
breaker performs trip operation after prearranged delay time
- But if breaker did not break the fault normally,
breaker performs instantaneous trip operation to protect system.
A-2-78
V2
V3
Vn
E1
Z3
Z1
Common
Reset
ZCT
V1
ZSI input
Voltage module
ZSI output
485+
R11
R22
513
544
534
524
Power supply
R2
R1
485-
Trip
Relay
A-2-79
Digital
Output
LTD
Z2
GTD
Z4
S/I
Trip relay
Long Short Instantaneous Ground Overload OVR UVR rPower Vunbal Iunbal OFR UFR OPR
Alarm
time time
DO1(524)
P, S DO2(534)
type
DO3(544)
DO1(524)
A type DO2(534)
DO3(544)
Not available
Note
Programmable
Fixed
Modbus/RS-485
Operation mode: Differential
Distance: Max. 1.2km
Cable :
General RS-485 shielded twist
2-pair cable
Baud rate :
9600bps, 19200bps, 38400bps
Transmission method: Half-Duplex
Termination: 150
SCADA system
Modbus/RS-485
Profibus-DP
Profibus-DP module is installed
separately (Option)
Operation mode: Differential
Distance: Max. 1.2km
Cable :
Profibus-DP shielded twist 2-pair cable
Baud rate: 9600bps~12Mbps
Transmission method: Half-Duplex
Termination: 150
Standard: EN 50170 / DIN 19245
Ethernet/TCP/IP
Area
controller
TCP/IP/Ethernet
TCP/IP
CNC
Profibus-FMS
PC
DCS
PLC
Profibus-DP
Profibus-DP
communication module
(Option)
Profibus-DP
communication
module (Option)
PLC
Modbus/RS-485
A-2-80
When there are events such as setting change, Info. change, error of self-diagnose,
state change, P and S type record Max. up to 256 information of the events in accordance with
time(ms). In addition, they can record Max. up to 256(up to 10 for A type) information of the faults
such as fault cause, fault phase, fault value and so on in accordance with time(ms).
Setting display
1000 A
R
100%
50%
Password
input
1.H/W Set
2.Relay Set
3.Events
4.Sys Info
5.L/R [L]
1.Event
2.Clear All
3.Fault
4.Clear All
1. EventL
2007/05/15
20:29:41
Sta Change
10. EventL
2007/04/15
10:11:24
Cfg Change
Power On
Comm Set up
Setting display
1000 A
R
100%
50%
Password
input
1.H/W Set
2.Relay Set
3.Events
4.Sys Info
5.L/R [L]
1.Event
2.Clear All
3.Fault
4.Clear All
1. Trip
2007/04/26
08:35:52
OCR-Short
9. Trip
2007/04/11
09:11:32
UVR
Phase T
Phase R
930A
System information
P and S type can indicate information as followings with the information of the MCCB.
- Present time: year/month/date/hour/minute/ms
- MCCB current ratings
- N-phase current ratings: 100%
- Frequency information: 60Hz / 50Hz
- Closing numbers of breaker: CB ON numbers
- Trip relay operating time: OCR ON time
- ON time of breaker: CB ON time
- S/W ver. information
Setting display
1000 A
R
100%
50%
A-2-81
1.H/W Set
2.Relay Set
3.Events
4.Sys Info
5.L/R [L]
Password
input
System Info
Date Time
2007/05/15 21:23:30
Rating
1000 A
Ex-Func 4POCGR
Freq
60 Hz
CB ON# 23
Ver-Arm 1.41
System Info
Date Time
2007/05/15 21:23:30
Rating
1000 A
Ex-Func 4POCGR
T-OPER 220 h
T-CB ON 180 h
Ver-Msp 1.01
OV
N
ACB Trip
ACB
Vcc/+9V/-9V
CN2-1
CN2-11
Filter
Amp.
CN2-3
CN2-13
Signal CT
CN2-5
CN2-15
Vcc
CPU
Output
Power PCB
Assy
+5V
+24V
Display
(LED, LCD)
Main PCB
Assy
MTD
CN2-6
Output
CN2-8
Main PCB
Assy
CN2-7
CN2-16
CN2-14
Setting
part
GND 24
CN2-4
Vcc
Self
power
RY0 (K1)
CN4-2
GTD contact
+24V
GND+24V
Power CT
Main PCB
Assy
RY1 (K2)
CN4-4
STD/INST contact
+5V
RY2 (K3)
-5V
CN4-6
LTD contact
CN2-2
CN4-9
SMPS
CN4-10
Power PCB
Assy
CN4-8
Common contact
Trip relay
Additional source
AC/DC 100~250V
DC 24~60V
CN1-1
ZSI output+ terminal
CN1-2
ZSI output- terminal
CN1-3
ZSI input+ terminal
CN1-4
ZSI input- terminal
CN1-9
CN1-10
VDM
CN1-11
CN1-12
CN1-5
Remote reset+ terminal
CN1-6
Remote reset- terminal
CN1-7
Earth
CN1-8
CN1-7
Earth leakage+ terminal
CN1-8
Earth leakage- terminal
CN3-5
UTXO
CN3-1
URXO
CN3-3
GND 24V
CN3-7/9
AD GND
CN3-10
Test
Main PCB
Assy
Comm.
Power PCB
Assy
CN4-1
485+ terminal
CN4-3
485- terminal
A-2-82
Terminal,172773-1, AMP
25ea
Drawing No.
Part Name
Functions
OCR
76671176262
A Type
76671176263
76671176264
P, S Type
P, S Type
Marking
04 03
01
485+
Comm. +
06 05
02
485-
Comm. -
08 07
03
R1
Power +
10 09
04
R2
Power -
05
524
06
534
07
544
08
513
09
Z3
ZSI Out +
10
Z4
ZSI Out -
11
Z1
ZSI In +
12
Z2
13
R11
Remote Reset +
14
R22
Remote Reset -
15
E1 or B1
Earth Leakage +
16
E2 or B2
Earth Leakage -
17
V1
VR Input
18
V2
VS Input
19
V3
VT Input
20
VN
V Input Common
02
01
12
11
14
13
16
15
18
17
20
19
01
02
A-2-83
Description
ZSI In -
Terminal ASS'Y,
Short ZSI IN
No. 11, 12 Shorted
Caution
TRIP or OFF STATE
10P Connector
Part Name
76671176264
12P Connector
No. 15, B1
No. 16, B2
A-2-84
Type
] ,OCR,TS1600
[AG AC]
[A ZK PS CKA]
[AE AX PX SX]
76671176262
76671176263
76671176264
WIRE ASSY, [
] ,OCR,TS1600
No
Type
[AG AC]
[A ZK PS CKA]
[AE AX PX SX]
NG0
33
PC1
76671176262
76671176263
76671176264
NG5
34
PC2
AG0
35
PC6
AG1
36
PC7
AG2
37
PK1
AG5
38
PK2
AG6
39
PK6
AG7
40
PK7
AZ0
41
PX1
10
AZ1
42
PX2
11
AZ2
43
PX6
12
AZ5
44
PX7
13
AZ6
45
PA1
14
AZ7
46
PA2
15
AE0
47
PA6
16
AE1
48
PA7
17
AE2
49
SC1
18
AE5
19
AE6
50
SC2
51
SC6
20
AE7
52
SC7
21
AC1
53
SK1
22
AC2
54
SK2
23
AC6
55
SK6
24
AC7
56
SK7
25
AK1
57
SX1
26
AK2
58
SX2
27
AK6
59
SX6
28
AK7
60
SX7
29
AX1
61
SA1
30
AX2
62
SA2
31
AX6
63
SA6
32
AX7
64
SA7
65
NV1
66
NV6
A-2-85
A-3. Accessories
Accessories for TE series
Overview
Electrical auxiliaries
Rotary handles
Terminals
Insulation
Interlock
A-3-1
A-3-2
A-3-5
A-3-6
A-3-7
A-3-8
A-3-9
A-3-10
A-3-14
A-3-16
A-3-19
A-3-24
A-3-26
A-3-27
A-3-32
A-3-34
A-3-35
A-3-39
A-3-40
A-3-41
A-3-45
A-3-46
A-3-47
A-3-51
A-3-53
A-3-56
A-3-57
Circuit breaker
Insulation barrier
Electrical auxiliaries
A-3-1
Contact
MCCB
ON
OFF
TRIP
AX
AL
Rating
Conventional thermal current, Ith
5A
Current, Ie
Voltage, Ue
AC 50/60Hz
DC
Resistive load
Inductive load
125V
250V
500V
30V
125V
0.4
0.4
250V
0.2
0.2
A-3-2
The shunt trip opens the mechanism in response to an externally applied voltage signal. The
releases include coil clearing contacts that automatically clear the signal circuit when the
mechanism has tripped.
The shunt release can be installed in the right accessory compartment of the MCCBs.
- Range of operational voltage
AC: 0.7~1.1Vn, DC: 0.8~1.1Vn
- Frequency(Only AC): 45Hz ~ 65 Hz
Rating
Power consumption
Control voltage, Ue
Voltage
A-3-3
AC (VA)
DC (W)
mA
AC/DC 12V
0.35
0.36
30
AC/DC 24V
0.64
0.65
27
AC/DC 48V
1.09
1.1
23
AC/DC 60V
1.2
1.22
20
AC/DC 100~130V
0.73
0.75
5.8
AC/DC 200~250V
1.21
1.35
5.4
AC 380~450V
1.67
3.8
AC 440~500V
1.68
3.5
Max.opening time
50ms (max.)
8.2 kgfcm
The undervoltage release automatically opens a circuit breaker when voltage drops to a value
ranging between 20% to 70% of the line voltage. The operation is instantaneous, and after tripping,
the circuit breaker cannot be re-closed again until the voltage returns to 85% of line voltage.
Continuously energized, the undervoltage release must be operating before the circuit breaker can
be closed. The undervoltage release can be easily installed in the right accessory compartment of
the MCCBs.
- Range of tripping voltage: 0.2 ~ 0.7Vn
- MCCB making is possible voltage: 0.85Vn (Exceed)
- Frequency (Only AC): 45Hz ~ 65Hz
Rating
Power consumption
Control voltage, Ue
Voltage
AC (VA)
DC (W)
mA
AC/DC 24V
0.64
0.65
27
AC/DC 48V
1.09
1.1
23
AC/DC 100~110V
0.73
0.75
5.8
AC/DC 200~220V
1.21
1.35
5.4
AC 380~440V
1.67
3.8
AC 440~480V
1.68
3.5
Max.opening time
50ms (max.)
8.2 kgfcm
Operating
Trip
20~70% Vn
voltage range
Reset/Closing
0.85Vn
Maximum possibilities
Position
Type
TE160
3/4P
Left-hand seat
Right-hand seat
AX
AL
AX
AL
SHT/UVT
A-3-4
The rotary handle operating mechanism is available in either the direct version or in the extended
version on the compartment door.
It is always fitted with a compartment door lock and on a request it can be supplied with a key lock
in the open position.
Rotary handle
TE160
DH1E
Rotary handle
TE160
EH1E
Degree of protections
Type
Degree of protection
IP
IP40
A-3-5
IP55
Front connection
Extended terminal
- As an optional part of circuit breaker
- Can increase the pitch of the terminals
MCCB
Pole
Type
TE100
3P
ET13E
TE160
4P
ET14E
Feature
Rear connection
Rear connection terminals are used to adapt Susol TE circuit breakers to switchboards or
other application that require rear connection.
These can be connected directly to circuit breakers without any modification.
Flat terminals
MCCB
Pole
Type
TE100
3P
RTF13
TE160
4P
RTF14
Feature
A-3-6
Insulation by barrier
These allow the insulation characteristics between the phases at the connections to be increased.
They are mounted from the front, even with the circuit-breaker already installed, inserting them into
the corresponding slots.
They are incompatible with both the insulating terminal covers.
It is possible to mount the phase separating partitions between two circuit-breakers side by side.
Type
Applied MCCB
B13C
TE100, TE160
Set quantity
3P
4P
4pcs
6pcs
A-3-7
TE100, TE160
Terminal cover
pole
Long type
Short type
3P
ITL13E
ITS13E
4P
ITL14E
ITS14E
This mechanical interlocking device is very useful and simple for consisting of manual sourcechangeover system.
MCCB
Operation
Frame type
TE100, TE160
Interlock
pole
3P
MIT13E
4P
MIT14E
Interlock handle
Interlock bar
A-3-8
Insulation barrier
Motor operator
Direct rotary handle
Extended rotary handle
Aux. handle
Locking devices (Removable, Fixed)
A-3-9
The following devices are installed into all TD & TS circuit breakers regardless of frame size.
And, the electrical auxiliaries can be easily installed in the accessory compartment of the circuit
breakers which is cassette type.
UVT
Technical data
Consumption
Power
consumption
Applicable
AC (VA)
DC (W)
mA
AC/DC 24V
0.64
0.65
27
AC/DC 48V
1.09
1.10
23
AC/DC 110~130V
0.73
0.75
5.8
AC 200~240V/DC 250V
1.21
1.35
5.4
TD100, TD160,
AC 380~440V
1.67
3.8
TS100, TS160,
AC 440~480V
1.68
3.5
TS250, TS400,
50
MCCBs
TS630, TS800
8.2kgfcm
0.7~1.35Vn
~0.85Vn
8.2kgfcm
A-3-10
SHT
Technical data
Consumption
AC (VA)
DC 12V
Applicable
mA
0.36
30
0.58
0.58
24
MCCBs
Power
AC/DC 24V
consumption
AC/DC 48V
1.22
1.23
25
TD100, TD160,
AC/DC 110~130V
1.36
1.37
10.5
TS100, TS160,
AC 220~240V/DC250V
1.80
1.88
7.5
TS250, TS400,
AC 380~500V
1.15
2.3
TS630, TS800
50
8.2kgfcm
8.2kgfcm
Click
A-3-11
DC (W)
Auxiliary switch (AX), Alarm switch (AL) and Fault alarm switch (FAL)
Auxiliary switch (AX)
Auxiliary switch is for applications requiring remote ON and OFF indication.
Each switch contains two contacts having a common connection.
One is open and the other closed when the circuit breaker is open, and vice-versa.
AX
AL
MCCB
Position
ON
OFF
TRIP
AXa1
AXa1
AXc1
of AX
AXc1
AXb1
AXb1
Position
of
AXa1
AXa1
AXc1
AXc1
AL, FAL
AXb1
AXb1
Technical data
Conventional thermal current Ith
Rated operational current Ie
5A
Voltage
- Direct current DC
TD100
Ie
Resistance
Inductance
125V
250V
500V
30V
125V
0.4
0.4
250V
0.2
0.2
TD160
TS100
TS160
TS250
TS400
TS630
TS800
A-3-12
Accessory
TD160
TS250
TS630
TS800
AX
R (Left)
AL
SHT or UVT
AX
AL
FAL
T (Right)
Note) FAL can be applied to only MCCB with electronic trip release.
TD160
TS250
TS630
TS800
AL
AX AX
AX
AL
*FAL
AX
AX AX AX
SHT/
UVT
AX AX AX
AL AL
AL
SHT/
UVT
*FAL
*FAL
SHT/
UVT
SHT/
UVT
A-3-13
Rotary handles
The rotary handle operating mechanism is available in either the direct version or in the extended
version on the compartment door.
It is always fitted with a compartment door lock and on a request it can be supplied with a key lock
in the open position.
Rotary handle
TD100,TD160
DH1
TS100,TS160,TS250
DH2
TS400,TS630
DH3
TS800
DH4
Locked
Unlocked
Padlockable device
TD100, TD160
DHK1
DHK2
TS400, TS630
DHK3
TS800
DHK4
Lock function
OFF position
MCCB
Padlockable device
TD100,TD160
EH1
TS100,TS160,TS250
EH2
TS400,TS630
EH3
TS800
EH4
A-3-14
Rotary handles
Degree of protections
Type
Degree of protection
IP
IP40
Totally protected
Circuit breaker with cover frame and
rotary extended handle
against ingress of
dust and water jets from any
direction
A-3-15
IP65
Padlockable device
TD100,TD160
PL1
TS100,TS160,TS250
PL2
TS400,TS630
PL3
TS800
PL4
Function
OFF position
Cover Aux.
Pad-lock
5~8
30
Padlock dimensions
A-3-16
Padlockable device
TD100,TD160
PHL1
TS100,TS160,TS250
PHL2
TS400,TS630
PHL3
TS800
PHL4
Function
5~8
How to use
The locking device for the toggle handle is designed to be easily attached to
the front of circuit-breaker.
Please set the toggle handle in the position of On or Off.
Install the lock device onto the front of auxiliary cover of circuit breaker.
Folding the wings of lock device as shown in picture 3.
The padlock to be used shall be that which is commercially available with
the nominal dimension. (30mm nominal dimension, 5~8mm diameter)
TD100, 160
TS100 ~
TS800
A-3-17
30
Padlock dimensions
Unlocked
MCCB
Padlockable device
TD100,TD160
DHK1
TS100,TS160,TS250
DHK2
TS400,TS630
DHK3
TS800
DHK4
Function
OFF position
1
2
Open Panel Door
Reledsing
A-3-18
Front connection
Terminal mounter
- It is supplied with Susol MCCBs as an standard part of circuit breaker.
- Connecting part with terminal for bus bar, cable with lug
MCCB
Type
TD100,TD160
TM1
TS100,TS160,TS250
TM2
TS400,TS630
TS800
Cable
Applicable to
Type
Conductor size
possibilities
TD100, 160
SBT13
1 Set (3EA)
SBT14
1 Set (4EA)
SBT23
1 Set (3EA)
SBT24
1 Set (4EA)
IBT33
1 Set (3EA)
IBT34
1 Set (4EA)
Note1)
TS400, 630
Note2)
PB12, 13
IBT13
1 Set (3EA)
IBT14
1 Set (4EA)
IBT23
1 Set (3EA)
IBT24
1 Set (4EA)
Note2)
PB22, 23
Note) 1. IBT3 for TS630 can be applied in case that rate current is upto 400A.
2. IBT13, 14 and IBT23, 24 are for Plug-in base.
A-3-19
L(mm)
21
S(mm2)Cu/Al
2.5~95
120~147
L(mm)
21
S(mm2)Cu/Al
10~150
120~147
L(mm)
30
S(mm2)Cu/Al
70~300
367~428
L(mm)
18
S(mm2)Cu/Al
2.5~95
306
L(mm)
21
S(mm2)Cu/Al
10~150
306
Front connection
Extended box terminals (Copper cables/bars and aluminum cables)
- The extended box terminals for TD and TS circuit breakers can be used for cooper cables/bars
and aluminum cables. There are four (4) kinds of terminals.
- For TD100, TD160: 1-cable connector (EBT13, EBT14)
- For TS100, TS160, TS250: 1-cable connector (EBT23, EBT24)
- For TS400, TS630: 2-cable connector (EBT33, EBT34)
- For TS800: 3-cable connector (EBT43, EBT44)
Cable
Applicable to
Type
Conductor size
possibilities
1-cable connector
TD100, 160
2-cable connector
TS400, 630
EBT13
1 Set (3EA)
EBT14
1 Set (4EA)
EBT23
1 Set (3EA)
EBT24
1 Set (4EA)
EBT33
1 Set (3EA)
EBT34
1 Set (4EA)
L(mm)
20
S(mm2)Cu/Al
2.5~95
306
L(mm)
24
S(mm2)Cu/Al
10~150
306
L(mm)
33 or 62
S(mm2)Cu/Al
285 to 2240
367~428
L(mm)
25~48
S(mm2)Cu/Al
385 to 3240
367~428
TS800
EBT43
1 Set (3EA)
EBT44
1 Set (4EA)
3-cable connector
A-3-20
Front connection
Spreaders
- As an optional part of circuit breaker
- Can increase the pitch of the terminals
MCCB
102.5
A
30
30
20
Type
2P
SP12a
3P
SP13a
4P
SP14a
2P
SP12b
3P
SP13b
4P
SP14b
2P
SP22a
3P
SP23a
4P
SP24a
2P
SP22b
3P
SP23b
4P
SP24b
Size A
(mm)
35
33
22
8.2
Pole
102.5
TD100, 160 3P
A
30
30
30
TD100, TD160
20
33
22
8.2
45
TD100, 160 4P
100
35
35
24
45
31
20
8.2
100
35
35
35
24
31
20
8.2
A-3-21
52.5
Feature
Front connection
Spreaders
- As an optional part of circuit breaker
- Can increase the pitch of the terminals
MCCB
27
Pole
Type
2P
SP32a
3P
SP33a
4P
SP34a
2P
SP32b
3P
SP33b
4P
SP34b
2P
SPS32
3P
SPS33
4P
SPS34
2P
SPS42
3P
SPS43
4P
SPS44
Size(mm)
A
52.5
41
70
54
46.5
41
70
81.5
Feature
TS400, 630 3P
TS400, TS630
27
TS400, 630 4P
49
TS800 3P
TS800
49
TS800 4P
A-3-22
Rear connection
Rear connection terminals are used to adapt Susol TD and TS circuit breakers to switchboards or
other applications that require rear connection.
These can be connected directly to circuit breakers without any modification
There are two kinds of rear connection terminals.
- Flat type
- Round type
Flat type
Flat vertical terminals
MCCB
2-pole
3-pole
4-pole
TD100,TD160
RTB12
RTB13
RTB14
TS100,TS160,TS250
RTB22
RTB23
RTB24
TS400,TS630
RTB32
RTB33
RTB34
TS800
RTB42
RTB43
RTB44
4-pole
2,3-pole
TD160,TS250
BOLT, HEX, SOCKET, P.S/W, M6, L15
Torque: M6 (51.1 ~ 64.9kgf cm)
TS630
TS800
Flat type
45
8=360
45
8=360
Round type
Round threaded terminals
MCCB
4-pole
2,3-pole
Round type
A-3-23
2-pole
3-pole
4-pole
TD100,TD160
RTR12
RTR13
RTR14
TS100,TS160,TS250
RTR22
RTR23
RTR24
TS400,TS630
TS800
TS100,TS160,TS250
TS400,TS630
Long type covers
TS800
Terminal cover
Pole
Long type
Short type
2P (1) , 3-pole
ITL13
ITS13
4-pole
ITL14
ITS14
2P (1), 3-pole
ITL23
ITS23
4-pole
ITL24
ITS24
2P (1), 3-pole
ITL33
ITS33
4-pole
ITL34
ITS34
2P (1), 3-pole
ITL43
ITS43
4-pole
ITL44
ITS44
A-3-24
Insulation by barrier
These allow the insulation characteristics between the phases at the connections to be increased.
They are mounted from the front, even with the circuit-breaker already installed, inserting them into
the corresponding slots.
They are incompatible with both the insulating terminal covers.
It is possible to mount the phase separating partitions between two circuit-breakers side by side.
Type
A-3-25
Set quantity
TD100, TD160
4pcs
4pcs
B-33C
TS400, TS630
4pcs
B-43C
TS800
4pcs
B-23C
Insulation barriers
Applied MCCB
This mechanical interlocking device is very useful and simple for consisting of manual sourcechangeover system.
Operation
MCCB
Frame type
TD100,TD160
TS100,TS160,TS250
Left MCCB: ON/OFF is possible
Right MCCB: Off lock
Interlock
Pole
TS400,TS630
TS800
3-pole
MIT13
4-pole
MIT14
3-pole
MIT23
4-pole
MIT24
3-pole
MIT33
4-pole
MIT34
3-pole
MIT43
4-pole
MIT44
Interlock handle
Interlock bar
A-3-26
Plug-in device
The plug-in base is the fixed part of the plug-in version of the circuit-breaker.
It will be installed directly on the back plate of panel.
The circuit-breaker is racked out by unscrewing the top and bottom fixing screws.
Plug-in base makes it possible to extract and/or rapidly replace the circuit breaker
without having to touch connections for ship and important installations.
MCCB
TD100, TD160
TS400, TS600
TS800
Pole
Arrangement
Type
Single line
PB12
Means
Single line
PB13
Double line
PB12D2
Double line
PB13D2
Single line
PB22
Single line
PB23
Single line
PB32
Single line
PB33
Single line
PB42
Single line
PB43
Front connection
DIN-rail
Back cover
Rear connection
A-3-27
type
Normal type Plug-in MCCB: PB
- MCCB rating: TD100~TS800
- generally used in switchgears
D2 type
Double-row type Plug-in MCCB: PB
- MCCB rating: TD100, 160
- generally used in branch circuits
A-3-28
Assembling procedure
TD100, TD160
1. Conversion to Plug-in MCCB
Disassemble terminal mounter.
HEX, Socket bolt(M615)
58kgf cm
Upper contact
M312 (Tap)
Safety device
M480
Screw up M480 after
Instolling MCCBs
to boses
M480
A-3-29
M412
Assembling procedure
TS100, TS160, TS250
1. Conversion to Plug-in MCCB
Disassemble terminal mounter.
HEX, Socket bolt(M615)
58kgf cm
Upper contact
M312 (2EA)
Safety device
M480 (4EA)
A-3-30
Assembling procedure
TS400, TS630
TS800
Contact upper
Upper contact
M38 (2EA)
Safety device
M312 (2EA)
Safety device
A-3-31
Electric auxilialy circuit(AX, AL, SHT, UVT) from Breaker via one to
three connector KIT(nine wires each). These are made of moving part on Breaker and
fixed part on plug-in base up to 800AF.
Breaker Max.
TD160
TS250
TS400/630
TS800
Q'ty
1
Fixed part
Moving part
CONNECTOR KIT,TD160
BASE CONNECTOR,TD160
CONNECTOR KIT,TS250
BASE CONNECTOR,TS250
CONNECTOR KIT,TS400/630
BASE CONNECTOR,TS630
CONNECTOR KIT,TS800
BASE CONNECTOR,TS800
TD160
Moving part
Fixed part
T Phase
2AX
R Phase
AL
SUT or UVT
Lead wire
Connector base
TS250
Moving part
T Phase
AX
Lead wire
Fixed part
R Phase
AX
AL
SUT or UVT
Connector base
A-3-32
TS400/630
Moving part
Fixed part
T Phase
AL
R Phase
3AX
SUT or UVT
Lead wire
Connector
base
TS800
Moving part
Fixed part
T Phase
2AL
R Phase
3AX
SUT or UVT
Lead wire
Connector
base
Fixed part
C: Red
E: Yellow
F: Blue
G: Brown
H: Orange
I: Gray
A-3-33
A: Black
D: Green
A: Black
B: White
C: Red
D: Green
E: Yellow
F: Blue
G: Brown
H: Orange
I: Gray
AL, FAL
Accessory KIT
Motor operator
Motor operators can also be operated by manual.The motor drives a mechanism which switches
TD & TS toggle handle to the ON and OFF/RESET positions.
- The manual actuator handle is located on the front of the cover.
- Manual or Automatic operation can be selected.
The motor operator is an essential device for constructing a remote operated automatic sourcechangeover system to ensure a continuous supply of electrical power at following certain
installations:
- Commercial sector: Hospital, Tall building, Bank, Insurance companies, Shopping centers
- Industry: Ships, Assembly lines at plant, Military sites, Port and Railway installation
MCCB
Type
Control voltage
TS250 + MOP2
Actuation
Response time
current
(ms)
(A)
DC 24V
TD100, TD160
MOP1 AC 100~240V/
Closing Opening
Consumption
(W)
Mechanical
No. of
per hour
2.5A
(DC 24V)
310
200
14
25,000
120
350
230
14
25,000
120
500
350
35
20,000
60
700
420
35
10,000
20
MOP2 DC 24V
AC 100~110V/
TS400,TS 630
MOP3
DC 110V
AC 230/
TS800
MOP4
DC 220V
5A
(DC 24V)
2A
(AC)
Wiring connection
Standard connection
Circuit breaker On and Off controlled by remote operation and manual operation
P1
P2
S1
Power
Ue
S2
S4
1. 2Nm
ON
OFF
P2
S1
S2
S4
ALb
Power
Ue
ALa
ALc
ON OFF
A-3-34
Manual operation
1) Insert the manual handle into the slot of Motor Operator surface and rotate it clockwise.
2) It must be rotated just 180 clockwise for safe operation of micro switch in the motor operator.
3) Return the manual handle after the manual operation
4) Turn the slide switch back to the position of AUTO.
CAUTION: When the circuit breaker is tripped by trip button in the OFF status,
it is impossible to operate motor operator automatically It must be reset by manual operation.
Manual handle
Automatic operation
1) Set the slide switch to AUTO, then internal power is closed automatically.
2) Operating frequency should be less than these below regulated values.
TD 160N/H/L, TS250N/H/L:180 operations per hour
3) Use the ON/OFF switch in the range of regulated values.
4) It may interfere near communication equipments because of internal switching power supply.
Its recommended that a noise filter be installed to power supply.
5) Please do not input ON/OFF signals at the same time during the automatic operation.
6) If the circuit breaker has a UVT attached inside, charge a UVT on the rated voltage before
performing MOTOR OPERATOR.
A-3-35
Motor operator
Feature
On position indication (Red color)
Trip position indication (White color)
Off position indication (Green color)
Button for push to trip
(available for only for TD160AF and TS630AF)
On/Off/Reset selection lever
Manual/Auto selection lever
TS630.... MOP-3
A-3-36
The Susol circuit breaker can offer protection against earth leakage currents by using an add-on
residual current device (RCD). In particular, the TS100, TS160 and TS250 circuit breakers can be
combined with the RTU23 of residual current device, the TS400 and TS600 circuit breakers can be
combined with the RTU33 of residual current device and the TS800 circuit breaker can be
combined with the RTU43 of residual current device. In all cases the RCD unit interfaces directly
below the circuit breaker trip unit area without the use of any secondary wiring or connections.
The Susol circuit breaker and an RCD unit combination can be connected like any stand-alone
breaker and are available as fixed or plug-in devices. The main connection interface of the RCD is
an exact replacement of the breaker connection area, thus allowing the use of all standard breaker
terminals.
Overview
Apart from the protection against overloads typical of automatic circuit breakers, the residual
current circuit breaker derived from them also guarantee protection of people against earth leakage
currents, thereby ensuring protection against direct contacts, indirect contacts and fire hazards.(ELCB)
The RCD unit has numerous current and time settings and an override blocking the time settings
when set to 30mA. The earth leakage test button tests the electrical and mechanical operation of
the device. In order to allow for a dielectric test of the breaker and RCD combination without
damaging the electronics, the dielectric plug is placed within the setting area. The RCD unit may be
equipped with an alarm switch (FAL) to remotely indicate tripping due to an earth leakage current.
Compliance with standards :
- IEC 60947-2 (industrial), Appendix B
- IEC 61009 ( residential)
- IEC 60755, class A, immunity to DC components up to 6mA
- VDE664, operation down to -25C
Remote indications :
RCD unit may be equipped with an alarm contact (FAL-fault alarm switch) to remotely indicate
tripping due to an earth leakage current.
Power supply :
RCD unit are self-supplied internally by the distribution-system voltage and therefore do not require
any external source. They continue to function even when supplied by only two phases.
A-3-37
Configuration
Intermediate terminal shield
Test push-button
Reset push-button
Sealable fixing screw for
Trip time delay settings(2)
Sensitivity settings
Slot for FAL auxiliary switch
(optional)
Sealing point for plate blocking access
to the settings
Rating plate
- Lift this plug before the dielectric test
- If the sensitivity is set to 30 mA, there is no time delay.
Whatever the time-delay setting.
Schematic diagram
A-3-38
RCD type
Number of poles
Applicable
circuit breaker
RTU23
RTU33
RTU43
3*
3*
3*
TS100
TS160
TS250
TS400
TS630
TS800
Protection characteristics
Sensitivity
In(A)
(adjustable)
(adjustable)
(adjustable)
0.03-0.3-1-3-10
0.03-0.3-1-3-10
0.03-0.3-1-3-10
Intentional time
(adjustable)
(adjustable)
(adjustable)
delay(ms)
0-60-150-300-600
0-60-150-300-600
0-60-150-300-600
Time delay **
Rated voltage
Max. breaking
(adjustable)
(adjustable)
(adjustable)
time(ms)
40-140-240-450-880
40-140-240-450-880
40-140-240-450-880
AC 50/60 Hz
220~460V / 460~690V
220~460V / 460~690V
220~460V / 460~690V
A-3-39
Combination
The addition of the RCD unit does not affect circuit breaker characteristics.
- Conformity with standards
- Protection degrees, class II insulation front face
- Suitability for isolation as defined by IEC 60947-2
- Electrical characteristics
- Trip unit characteristics
- Installation and connection methods
- Indication, measurement and control accessories
- Installation and connection accessories
RTU23
MCCB
MCCB+RCD
LHD(mm)
RCD
MCCB+RCD
RTU33
RTU43
10516086
140260110
210320135
10524086
140370110
210450135
1058086
140110110
210130135
2.7
8.08
16.28
2.52
4.6
Weight(kg)
RCD
Type
Accessory
0.96
Bottom
FAL(fault alarm switch)
A-3-40
The following accessories for mounting, connection, insulation, handle operation are standard
items and are packed with Susol TD & TS series circuit breakers.
TD100N/H/L
TD160N/H/L
B-23C
M820
M375(1P)
M475
1P: 2pcs
3P: 6pcs
4P: 8pcs
1P: 2pcs
3P: 2pcs
4P: 4pcs
3P: 4pcs
4P: 6pcs
TS100N/H/L
TS160N/H/L
TS250N/H/L
B-23C
M820
3P: 6pcs
4P: 8pcs
M475
3P: 2pcs
4P: 4pcs
3P: 4pcs
4P: 6pcs
TS400N/H/L
TS630N/H/L
B-33C
M1030
3P: 6pcs
4P: 8pcs
M585
3P: 4pcs
4P: 4pcs
M5
3P: 4pcs
4P: 4pcs
3P: 4pcs
4P: 6pcs
TS800N/H/L
B-4
M1235
3P: 6pcs
4P: 8pcs
A-3-41
M6100
3P: 4pcs
4P: 4pcs
3C
M6
3P: 4pcs
4P: 4pcs
3P: 4pcs
4P: 6pcs
1pc
Plate protection
Busbar
Lug terminal
Vertical busbar
Extension busbar
Rear connection
Auxiliary handle
Removable padlock (PL)
Electrical auxiliary
Direct rotary handle
Voltage module
A-3-42
The following devices are installed into TS1000 to 1600AF circuit breakers regardless of frame
size. And, the electrical auxiliaries can be easily installed in the accessory compartment of the
circuit breakers which is cassette type.
AX1
AX2
AX3
AL
SHT/UVT
FUAL
AX
AL
ON
OFF
TRIP
AXa1
AXa1
AXc1
of AX
AXc1
AXb1
AXb1
Position
of
AL
A-3-43
AXa1
AXa1
AXc1
AXc1
AXb1
AXb1
Normal position
UAL
a
b
a
b
au
CB no trip
fuc
af
FAL
FAL operation
a
b
a
b
au
UAL operation
UAL
a
b
a
b
au
fuc
FUAL
af
FAL
a
c
b
UAL
a
c
b
au
Rya 1
Rya 2 Rya 2
fuc
AC or DC
Power
Ry
UAL
signal
Lamp
FAL Lamp
signal
Caution: Please use Lock up Circuit following under figure Example of lock up circuit for
FUAL
Caution: When MCCB is tripped by SHT or UVT, the FAL signal appears for 20ms that is time
of being transferred from bcontact to a contact of control relay
Caution: When MCCB is tripped by SHT or UVT, the transfer time of Relay signal(Ryb2 off
Rya2 on) is 20ms. if FAL signal is connected with other sequence circuit such as
Latch circuit or other look up circuit it may cause to be miss operation. So, please do
not use latch circuit or look up circuit with FAL signal.
A-3-44
AC [V]
24~30
0.6~1.1 Vn
48~60
48
0.6~1.1 Vn
100~130
100~130
0.56~1.1 Vn
200~250
200~250
0.56~1.1 Vn
380~480
0.56~1.1 Vn
Inrush
Steady-state
Less
200
than
40ms
Note) Operating voltage range is the min. rated voltage standard for each rated voltage(Vn).
Opening
order
C1
C2
Wire type
*
The dotted
to
Userline
be made by the
Wiring Diagram
customer
Wiring Diagram
A-3-45
Operating
voltage
DC/AC 48 [V]
#14 AWG
#16 AWG
#14 AWG
#16 AWG
(2.08mm )
(1.31mm )
(2.08mm )
(1.31mm2)
100%
95.7m
61m
457.8m
287.7m
85%
62.5m
38.4m
291.7m
183.2m
AC [V]
24~30
48~60
48
100~130
100~130
200~250
200~250
380~480
Drop out
Inrush
Steady-state
Less
0.65~0.85 Vn
0.44~0.6 Vn
200
than
50ms
Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).
Opening
order
D1
D2
#16 AWG
#14 AWG
#16 AWG
(2.08mm )
(1.31mm )
(2.08mm )
(1.31mm2)
100%
48.5m
30.5m
233.2m
143.9m
85%
13.4m
8.8m
62.5m
39.3m
Wire type
*
The dotted
to
Userline
be made by the
Wiring Diagram
customer
Wiring Diagram
Operating
voltage
DC/AC 48 [V]
#14 AWG
2
A-3-46
OCR tester
Configuration
R
ENT.
ESC
START
STOP
Signal setting/Delete
Waveform generation/Stop
50Hz 60Hz
Hz
A-3-47
Select frequency
- UVT is a device which makes ACB tripped automatically to prevent the accident on load side due
to under voltage or power breakdown.
There are two types, Instantaneous type and time delay type.
- It can be installed on the rail or to the cradle.
- Instantaneous type: only available with UVT coil.
- Time delay type: available by connecting UVT coil and UVT time delay controller.
- Common use for the all types.
1. The rated voltage and characteristic of UVT time delay controller
Rated voltage [Vn]
DC [V]
AC [V]
48~60
48
100~130
100~130
200~250
200~250
380~480
Pick up
Drop out
Inrush
Steady-state
0.65~0.85 Vn
0.44~0.65Vn
200
Trip time[s]
0.5, 1,
1.5, 3
Note) Operating voltage range is the min. rated standard for each rated voltage (Vh).
2. Wiring
1. Wiring for general type
Rated
voltage
(Vn)
Rated
voltage
(Vn)
Delay trip
function
14
16
14
16
D2
Instantaneous
trip
function
D1
D2
D1
ACB
ACB
Rated
voltage
(Vn)
Rated
voltage
(Vn)
A-3-48
The rotary handle operating mechanism is available in either the direct version or in the extended
version on the compartment door.
It is always fitted with a compartment door lock and on a request it can be supplied with a key lock
in the open position. There are direct rotary handletwo and extended rotary handle.
S Type
LOAD
LINE
R Type
LOAD
LINE
LOAD
B Type
B Type
380 (3P) Minimum
450 (4P) Minimum
205 Minimum
280 Minimum
4- 7
8.5
203
217
201
212
4- 7
25.5
t1.2~3.2
155.5
204.5
267
A-3-49
46
33
196
210
134
145
t1.2~3.2
204.5
267
Note) 1. In case of disassembling and assembling the main cover, screw should be tightened in specific torque of1.5N.m (15.3kgf.cm)
2. In case of disassembling and assembling the main cover by over tightening torque, the parts of MCCB can be damaged.
Door locking
OFF State
ON State
Caution
- If the door is opened with much pressure when
the position of handle is ON or TRIP, the handle
lock lever will be damaged
Key lock
After locking handle, be sure that the key removed.
Locking by rotary handle with a key lock
A locking can be done by using the rotary handle which has key
lock device.
The lock is used to lock the circuit-breaker in the OFF position.
5~6
A-3-50
S Type
Shaft
R Type
Handle
78
t1.2~3.2
246
681 Maximum (SHAFT Max. 469)
A-3-51
108
4- 6
24
108
Open OK
Release
lever
OFF State
Door locking
Locking at ON or
OFF position
ON State
Caution
- If the door is opened with much pressure when
the position of handle is ON or TRIP, the handle
lock lever will be damaged
Degree of protections
Type
Degree of protection
IP
IP40
Totally protected
Circuit breaker with cover frame and
rotary extended handle
against ingress of
dust and water jets from any
IP65
direction
A-3-52
Removable padlock(PL)
This device allows the handle to be locked in the OFF position.
Locking in the OFF position guarantee isolation according to IEC 60947-2.
The locking device for the toggle handle can be installed in 3-pole and 4-pole
circuit-breakers. Maximum three (3) padlocks with shackle diameters ranging from 5
to 8mm may be used. (Padlocks are not supplied)
Cover
PAD LOCK
A-3-53
A-3-54
Vertical busbar
Busbars
Bare cables
Lug terminals may be used to connect four 85 up to 240 copper or aluminum cables for each
phases. Bare cable connection is possible for rating up to and including 1250A
Lug terminal
L(mm)
S() Cu/Al
Torque(kgfcm)
A-3-55
25~55
485 to 4240
564
Crimped Terminals
Crimped terminals are combined with the vertical and extension busbars.
One to four cables with crimped terminals(300 ) may be connected.
To ensure stability, connectors must be fixed and insulated between the terminal extensions.
Vertical busbar
Extension busbars
A-3-56
Busbars
Vertical busbar
Crimped Terminals
Crimped terminals enable connection of one to four cables with crimped terminals(300 )
To ensure stability, connectors must be fixed and insulated between the terminal extensions
Extension busbars
A-3-57
Terminal cover
Mounted on fixed, front-connection devices,
it insulates power-connection points.
Barrier
These barriers are insulated between the phases for increase insulation level.
It also can be easily mounted, even the circuit-breaker already installed, inserting them in
the corresponding slots.
They are incompatible with both the insulating terminal covers.
It is possible to mount the phase separating partitions between two circuit-breakers side
Plate protection
paking unit: 1ea/3Pole, 1ea/4Pole
3Pole
4Pole
A-3-58
The following accessories for mounting, connection, insulation, handle operation are standard
items and are packed with Susol TD & TS series circuit breakers.
Barrier Interphase
3P: 2ea, 4P: 3ea
Nut(M5): 4ea
Nut(M10), S/W, P/W
3P: 12, 4P: 16
Components
A-3-59
Handle
Test Button
Moving Contactor
Load Terminal
Contact Spring
Arc Chute
Main Spring
Link Assy
Power CT
Handle Cover
Terminal Bolt
Moving Tip
Main Cover
Wall Holder Contactor
Fixed Tip
A-4-1
A-4-2
Safety clearance
A-4-3
Example of installation
A-4-6
A-4-7
A-4-8
TD100, TD160
TS100,TS160,
TS250
TS400, TS630
TS800
Screw for
mounting
1Pole:2EA(M375)
3Pole:2EA(M475) 3Pole:2EA(M475) 3Pole:4EA(M585) 3Pole:4EA(M6100)
4Pole:4EA(M475) 4Pole:4EA(M475) 4Pole:4EA(M585) 4Pole:4EA(M6100)
Nut for
mounting
3Pole:4EA
3Pole:4EA
4Pole:4EA
4Pole:4EA
Screw for
connection
of terminals,
Spreader
1Pole:2EA(M820)
3Pole:6EA(M820) 3Pole:6EA(M820) 3Pole:6EA(M1030) 3Pole:6EA(M1235)
4Pole:8EA(M820) 4Pole:8EA(M820) 4Pole:8EA(M1030) 4Pole:8EA(M1235)
Torque:
Max 78kgfcm
A-4-1
Torque:
Max 147kgfcm
Torque:
Max 490kgfcm
Torque:
Max 630kgfcm
Terminal (mm)
Conductor (mm)
TD100
8
18
TD160
23
M820
22
Max 78kgfcm
TS100
20
TS160
TS250
28
>8
>8
M820
21
10
10
22
25
25
Max 147kgfcm
TS400
30
M10L30
15
TS630
26.1
Max 490kgfcm
TS800
33
16.5
M1235
12
12
3745
15 3745 19
51
26
=
50
=
50
=
50
Max 630kgfcm
A-4-2
When installing a circuit breaker, safety clearances must be kept between the breaker and panels,
bars and other protection devices installed nearby. These safety clearances are depend on the
ultimate breaking capacity and are defined by tests carried out in accordance with standard IEC
60947-2.
When a short circuit interruption occur, high temperatures pressures are present in and above the
arc chambers of the circuit-breaker. In order to allow the pressure to be distributed and to prevent
fire and arcing or short-circuit currents, safety clearances are required.
30
TD100H, TD160H
35
30
TD100L, TD160L
35
30
35
30
35
30
35
30
TS400N, TS630N
60
50
TS400H, TS630H
60
50
TS400L, TS630L
60
50
TS800N
100
80
TS800H
100
80
TS800L
100
80
TD100N, TD160N
240V
415V
A-4-3
35
30
35
30
35
30
35
30
TS400N, TS630N
60
50
TS400H, TS630H
60
50
TS400L, TS630L
60
50
TS800N
100
80
TS800H
100
80
TS800L
100
80
Direct
connection
of cable
TD100L, TD160L
Connection by
using a cable
terminal or
ring
terminal
C1
30
30
35
C1
35
TD100H, TD160H
TD100N, TD160N
C(mm)
C1
240V
C1(mm)
415V
Connection
by using a
cable
terminal with
extended
terminal
50
50
50
50
100
100
100
200
200
200
200
200
200
50
50
100
100
100
200
D4
D4
(mm)
D3
D2
TD100L, TD160L
D3
(mm)
D1
TD100H, TD160H
D2
(mm)
TD100N, TD160N
D1
(mm)
200
200
200
200
200
Note) If uninsulated conductors are used for connection, please insulate by taping to
the point where the conductors overlap with the insulation barrier or to the root of the circuit breaker.
240V
TD100N, TD160N
25
15
TD100H, TD160H
25
15
TD100L, TD160L
25
15
25
15
25
15
25
15
TS400N, TS630N
20
15
TS400H, TS630H
20
15
TS400L, TS630L
20
15
TS800N
45
20
TS800H
45
20
TS800L
45
20
A-4-4
20
TD100H, TD160H
20
TD100L, TD160L
20
10
10
10
TS400N, TS630N
10
TS400H, TS630H
10
TS400L, TS630L
10
TS800N
10
TS800H
10
TS800L
10
(mm)
TD100H, TD160H
TD100L, TD160L
TS400N, TS630N
TS400H, TS630H
TS400L, TS630L
TS800N
TS800H
TS800L
A-4-5
TD100/160
TS100/160/250
M475
35
35
25
2
90
90
35
TS400/630
60
M575
20
90
90
60
TS800
100
M6100
45
90
90
100
A-4-6
The quality of busbar connections depends, among other things, on the tightening torques used for
nuts and bolts. Over-tightening may have the same consequences as under-tightening.
The correct tightening torques for the connection of busbars to the circuit breaker terminals are
indicated in the table below.
MAX. 2W50t10
example) 3W80t5
example) 3W80t5
example) 2W60t10
example) 3W80t5
example) 2W60t10
example) 2W50t10
example) 3W80t5
Insulation distance
Examples
Tightening torques for busbar
Bolt
M10
Drilling diameter
Tightening torque
(mm)
(kgfcm)
11
240~500
Insulation distance
Dimension(mm)
X
A-4-7
Utillsation voltage
X minimum
Ui600V
8mm
Ui1000V
14mm
TS1000
TS1250
TS1600
Maximum
current
T:40C
Number of busbars
t=5mm
t=10mm
T:50C
T:60C
Number of busbars
Number of busbars
t=5mm
t=10mm
t=5mm
t=10mm
800
2b.5t50
1b.10t50
2b.5t50
1b.10t50
2b.5t50
1b.10t60
1000
3b.5t50
1b.10t60
3b.5t50
2b.10t50
3b.5t60
2b.10t50
2b.10t50
3b.5t60
2b.10t50
3b.5t50
2b.10t40
3b.5t50
2b.5t80
2b.10t40
2b.5t80
1400
2b.5t80
2b.10t40
2b.5t80
2b.10t50
3b.5t80
2b.10t60
1600
3b.5t80
2b.10t60
3b.5t80
2b.10t60
3b.5t80
3b.10t50
1250
TS1000
TS1250
TS1600
Maximum
current
T:40C
Number of busbars
T:50C
T:60C
Number of busbars
Number of busbars
t=5mm
t=10mm
t=5mm
t=10mm
t=5mm
t=10mm
800
2b.5t50
1b.10t50
2b.5t50
1b.10t50
2b.5t50
1b.10t50
1000
2b.5t50
1b.10t50
2b.5t50
1b.10t50
2b.5t60
1b.10t60
1250
2b.5t60
1b.10t60
3b.5t50
2b.10t40
3b.5t50
2b.10t40
1400
2b.5t80
1b.10t80
2b.5t80
2b.10t50
3b.5t60
2b.10t50
1600
3b.5t60
2b.10t50
3b.5t60
2b.10t50
3b.5t80
2b.10t60
A-4-8
A-5-1
A-5-3
A-5-6
A-5-7
A-5-11
A-5-12
A-5-14
A-5-15
A-5-17
A-5-18
A-5-20
A-5-21
A-5-21
A-5-23
A-5-24
A-5-25
A-5-26
A-5-27
A-5-28
Current-limiting curves
A-5-31
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TE100
FTU
FMU
16~100A
FTU:Ir=1In
FMU:Ir=0.8~1In
FTU/FMU:Im=10In
Min. 400A
A-5-1
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TE160
FTU
FMU
100~160A
FTU:Ir=1In
FMU:Ir=0.8~1In
FTU/FMU:Im=10In
Min. 400A
A-5-2
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TD100
FTU
FMU
16~100A
A-5-3
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TD160
FTU
FMU
100~160A
A-5-4
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS100
FTU
FMU
40~100A
A-5-5
Characteristics curves
Circuit breakers with magnetic only trip units
TS100
Magnetic only
MTU
1.6~100A
TS160
Magnetic only
MTU
32~160A
In
TS100 to TS800
1.6
3.2
6.3
12
20
32
50
63
100
N / H / L TS100
TS160
160
220
320
500
TS250
TS400
TS630
TS800
630
Im
Setting
6..12 In (6 Point)
A-5-6
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS160
FTU
FMU
100, 125, 160A
A-5-7
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS160
ATU
100, 125, 160A
A-5-8
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS250
FTU
FMU
125~250A
A-5-9
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS250
ATU
125~250A
A-5-10
Characteristics curves
Circuit breakers with magnetic only trip units
TS250
Magnetic only
MTU
100, 160, 220A
In
TS100 to TS800
1.6
3.2
6.3
12
20
TS160
63
100
TS250
TS400
TS630
TS800
Im
160
-
Setting
6..12
A-5-11
50
TS100
32
In (6 Point)
220
320
500
630
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS400
FTU
FMU
300, 400A
A-5-12
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS400
ATU
300, 400A
A-5-13
Characteristics curves
Circuit breakers with magnetic only trip units
TS400
MTU
320A
In
TS100 to TS800
1.6
3.2
6.3
12
20
32
50
63
100
N / H / L TS100
TS160
160
220
320
500
TS250
TS400
TS630
TS800
630
Im
Setting
6..12 In (6 Point)
A-5-14
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS630
FTU
FMU
500, 630A
A-5-15
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS630
ATU
500, 630A
A-5-16
Characteristics curves
Circuit breakers with magnetic only trip units
TS630
MTU
500A
In
TS100 to TS800
1.6
3.2
6.3
12
20
TS160
63
100
TS250
TS400
TS630
TS800
Im
160
-
Setting
6..12
A-5-17
50
TS100
32
In (6 Point)
220
320
500
630
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS800
FTU
700, 800A
FMU
800A
A-5-18
Characteristics curves
Circuit breakers with thermal-magnetic trip units
TS800
ATU
800A
A-5-19
Characteristics curves
Circuit breakers with magnetic only trip units
TS800
MTU
630A
In
TS100 to TS800
1.6
3.2
6.3
12
20
32
50
63
100
N / H / L TS100
TS160
160
220
320
500
TS250
TS400
TS630
TS800
630
Im
Setting
6..12 In (6 Point)
A-5-20
Characteristics curves
Circuit breakers with electronic trip unit (ETS)
TS100 to TS800
ETS23
ETS33
ETS43
A-5-21
Characteristics curves
Circuit breakers with electronic trip unit (ETM)
TS400
TS630
TS800
ETM33
ETM43
A-5-22
Characteristics curves
Long-time delay (L)
TS1600
5000
2000
Ir = 0.4...1 In
1000
500
200
100
50
40
30
tr = 0.5...20s
20
20
12
10
t(s)
5
4
3
4
2
1
1
0.5
0.4
0.3
0.2
0.1
0.05
Ir
A-5-23
20
10
0.7
0.01
0.5
0.02
Characteristics curves
Short-time delay (S)
5000
2000
1000
500
Isd = 1.5...10 Ir
200
100
50
40
30
20
10
t(s)
5
4
3
2
1
0.4
0.3
0.4
0.2
0.2
I2t ON
0.4
0.3
0.3
0.2
I2t OFF
0.1
0.1
0.1
0.05
0.05
20
10
0.01
0.7
0.02
0.5
TS1600
Ir
A-5-24
Characteristics curves
Instantaneous (I)
Ground fault (G)
TS1600
100
50
40
30
20
Ig = 0.2...1 In
10
5
4
3
2
t(s)
1
I2t ON
0.4
0.4
0.3
0.3
0.2
0.2
0.2
0.1
I2t OFF
0.1
0.1
0.4
0.3
0.05
0.05
Ii = 2...15 In
A-5-25
In
10
4
5
0.7
0.4
0.5
0.3
0.2
0.1
0.07
0.01
0.05
0.02
Characteristics curves
IDMTL
10000
5000
2000
EIT
1000
500
VIT
200
100
SIT
t(s)
50
20
DT
10
20
10
0.05
0.7
0.5
TS1600
Ir
A-5-26
Characteristics curves
Pre Trip Alarm
TS1600
500
200
100
50
40
35
30
20
15
10
5
5
4
3
t(s)
2
1
1
0.4
0.3
0.2
0.1
0.05
Ip
A-5-27
30
20
10
0.7
0.01
0.5
0.02
Characteristics curves
Specific let-through energy curves
2
220/240V
Thermal stress
10
TS1600
TS1000
10
TS800
3
10
TS630
TS250
3
TD160
10
TE160
2
2
10
20
30
40
60
100
200
300
A-5-28
Characteristics curves
Specific let-through energy curves
2
380/415V
Thermal stress
10
TS1600
5
TS1000
10
TS800
5
TS630
10
TS250
5
TD160
3
TE160
10 5
2
2
A-5-29
10
20
30
40
60
100
200
300
Characteristics curves
Specific let-through energy curves
2
480/500V
Thermal stress
10
TS1600
5
TS1000
10
TS800
5
TS630
2
10
TS250
5
TD160
3
TE160
10
2
2
10
20
30
40
60
100
200
300
A-5-30
Characteristics curves
Current-limiting curves
200
220/240V
Peak current
TS1000
100
80
70
TS800
60
50
TS630
40
30
TS250
20
TD160
TE160
10
8
7
6
A-5-31
10
20
30
40
60
100
200
300
Characteristics curves
Current-limiting curves
200
380/415V
Peak current
TS1000
100
80
70
TS800
60
TS630
50
40
TS250
30
TD160
20
TE160
10
8
7
6
4
2
10
20
30
40
60
100
200
300
A-5-32
Characteristics curves
Current-limiting curves
200
480/500V
Peak current
100
TS1000
80
70
TS800
60
50
TS630
40
30
TS250
TD160
20
TE160
10
8
7
4
2
A-5-33
10
20
30
40
60
100
200
300
A-6. Dimensions
Susol MCCB TE100, 160 series
TE100, 160
A-6-1
A-6-2
A-6-3
A-6-4
A-6-5
A-6-6
A-6-7
A-6-13
A-6-19
A-6-22
A-6-28
A-6-30
A-6-30
A-6-31
A-6-37
A-6-38
A-6-39
A-6-40
A-6-41
A-6-42
A-6-43
A-6-44
A-6-45
Overall dimensions
TE100/160
[mm]
45
81
110
130
21.5
CL
70
82
89.5
CL
25
50
76
25
50
25
101
Min
2.5mm2
Max.
70mm2
Wire size
L
T W
L(mm)
17.5
W(mm)
13.5
T(mm)
Torque
8Nm
Panel drilling
25
25
CL
78
CL
47
83
CL
CL
CL
CL
110
CL
A-6-1
M4 OR 5
110
CL
47
83
103
Overall dimensions
TD160
[mm]
60
81
CL
22
140
122
107.5
86
27
14.5
28
35
77
81
86
92
106.9
1P
Conductor
10
18
20
M820
Terminal section
21.5
23
Panel drilling
M3 or 4
CL
83
107.5
CL
CL
CL
62
CL
CL
29
28
37
1P
1P
A-6-2
Overall dimensions
TD100/160
[mm]
50
75
Insulation barrier
B-23C
4.5
69
Mounting hole
27
60
C
L
81
C
L
22
140
122
109.6
107
14.5
52
Trip button
B-23C
77
81
86
92
106.9
60
90
30
60
120
2, 3P
Conductor
10
18
20
M820
Terminal section
4P
21.5
23
Panel drilling
30
2, 3P
CL
CL
30
30
4P
CL
CL
CL
83
107
107
CL
A-6-3
CL
83
M4 or 5
CL
92
122
2, 3P
4P
Overall dimensions
TS100/160/250
[mm]
50
75
Insulation barrier
69
11
CL
Mounting hole
CL
CL
22
CL
60
Mounting hole
27
160
140
125
B-23C
Trip button
Trip button
B-23C
70
105
75
81
86
93
109.7
35
2, 3P
70
140
4P
4P R
Conductor
10
20
25
M820
Terminal section
35
70
140
21.5
28
Panel drilling
C
L
35
2,3P
M4 TAP or 5 Hole
C
L
35
CL
CL
CL
N
CL
CL
100
C
L
100
M4 TAP or 5 Hole
100
125
N
C
L
C
L
125
M4 TAP or 5 Hole
125
C
L
CL
107
142
142
2,3P
4P
4P R
35
70
70
4P
4P R
A-6-4
Overall dimensions
TS400/630
[mm]
53
46.5
93.5
53
41
25
53
53
53
Mounting hole
Mounting hole
CL
CL
CL
CL
31
34.5
260
230
202
200
166
260
27
71
6
10
53
53
13
116
75
44.1
8
53
46.5
26.5
Trip button
Trip button
27
30
45
46.5
59
140
97.5
105
110
123
157
46.5
186.5
46.5
46.5
46.5
186.5
4P
2,3P
Terminal section
30
46.5
46.5
4P R
Conductor
26.1
15
30
15
M5 L30
13
Panel drilling
46.5
2,3P
A-6-5
46.5
46.5
93
93
4P
4P R
CL
N
CL
CL
142
188.5
2,3P
4P
168
CL
168
200
CL
CL
M5 TAP or 6 Hole
CL
168
N
CL
M5 TAP or 6 Hole
CL
200
M5 TAP or 6 Hole
200
CL
CL
188.5
4P R
Overall dimensions
TS800
[mm]
89
42
10
70
70
70
70
70
70
70
Mounting hole
82.8
Mounting hole
CL
CL
CL
26.7
9 37.3
CL
320
287
278
254.6
198.6
35
Trip button
Trip button
49
70
80
210
119
128
135
148.5
198
2,3P
280
4P
4P R
Conductor
14
33
32
51
15.5
Panel drilling
278
C
L
70
2, 3P
C
L
M6 TAP or 7 Hole
C
L
C
L
70
70
4P
M6 TAP or 7 Hole
C
L
70
70
4P R
C
L
C
L
N
278
M6 TAP or 7 Hole
278
4P C
L
200.6
1235
50
16.5
Terminal section
280
C
L
212
2, 3P
200.6
320
33.3
7
13.4
115
81.5
37
8
16
70
C
L
282
4P
A-6-6
Overall dimensions
Direct rotary handles
DH1E for TE100/160
[mm]
OFF
77.5
92.1
A-6-7
110
t 1.2~3.2
114.9
101.5
4-5
68.2
121
Overall dimensions
Direct rotary handles
DH1 & DHK1 for TD100/160
[mm]
90
t1.2~3.2
81.3
71.8
13.5
60
77
117
81
Panel drilling
Way of installation
Over 20mm
84
96.3
Panel shaft
4-5
Trip
Trip
93
105
A-6-8
Overall dimensions
Direct rotary handles
DH2 & DHK2 for TS100/160/250
[mm]
t=1.2~3.2
105
78.5
91.8
10.7
60
96
75
119
Panel drilling
Way of installation
Over 20mm
Trip
83
95
Panner shaft
4-5
Trip
108
121
A-6-9
Overall dimensions
Direct rotary handles
DH3 & DHK3 for TS400/630
[mm]
t1.2~3.2
97.5
131
147.5
18.75
140
93
129
170.5
Panel drilling
Way of installation
Over 20mm
Trip
133
149
Panel shaft
4-7
Trip
143
159
A-6-10
Overall dimensions
Direct rotary handles
DH4 & DHK4 for TS800
[mm]
t=1.2~3.2
210
119
211
192.5
Panel drilling
Way of installation
Over 20mm
Trip
MCCB
162
173
Panner shaft
4-7
Trip
213
225
A-6-11
186.6
165.4
23
140
Overall dimensions
Direct rotary handles
Dimension table for D-handles
TD100/TS250
[mm]
TS630/TS800
t1.2~3.2
D
E
B
C
B
C
D
E
A
F
Applicable to
TD160
TS250
TS630
TS800
A (mm)
117
119
170.5
211
B (mm)
71.8
78.5
131
165.4
C (mm)
81.3
91.8
147.5
186.6
D (mm)
90
105
140
210
E (mm)
60
60
93
140
F (mm)
81
96
129
192.5
A-6-12
Overall dimensions
Extended rotary handles
EH1E for TE100/160
[mm]
OFF
t 1.2~3.2
min 165
max 589(shaft 459mm)
2-6
47
53
47
A-6-13
Overall dimensions
Extended rotary handles
EH1 for TD100/160
[mm]
90
t1.2~3.2
Min. 163
Max. 585 (Shaft 469mm)
81.3
71.8
13.5
60
81
Panel drilling
Way of installation
2-6
53
47
OFF
OFF
47
A-6-14
Overall dimensions
Extended rotary handles
EH2 for TS100/160/250
[mm]
t=1.2~3.2
78.5
91.8
10.7
105
60
96
Min. 163
Max. 585 (Shaft 469mm)
Panel drilling
Way of installation
2-6
53
47
OFF
OFF
47
A-6-15
Overall dimensions
Extended rotary handles
EH3 for TS400/630
[mm]
t1.2~3.2
131
147.5
18.75
140
93
Min. 228
Max. 645 (Shaft 469mm)
129
Panel drilling
Way of installation
4-6
OFF
108
78
OFF
108
A-6-16
Overall dimensions
Extended rotary handles
EH4 for TS800
[mm]
t=1.2~3.2
165.4
186.6
23
210
140
Min. 275
Max. 687 (Shaft 469mm)
192.5
Panel drilling
Way of installation
4-6
108
78
108
A-6-17
OFF
OFF
Overall dimensions
Extended rotary handles
Dimension table for E-handles
F
C
F
C
[mm]
B
E
TS630/TS800
B
E
t1.2~3.2
TD100/TS250
D
A
D
Model
Applicable to
A (mm)
EH1
EH2
EH3
EH4
TD160
TS250
TS630
TS800
Min. 163
Min. 163
Min. 228
Min. 275
Max. 585
Max. 585
Max. 645
Max. 687
B (mm)
71.8
78.5
131
165.4
C (mm)
60
60
93
140
D (mm)
81
96
129
192.5
E (mm)
81.3
91.8
147.5
186.6
F (mm)
90
105
140
210
Shaft (mm)
469
469
469
469
A-6-18
Overall dimensions
Mechanical interlocking device
MIT13E, MIT14E for TE100/160
[mm]
82
47
4~6
30mm
83
70
A-6-19
Overall dimensions
Mechanical interlocking device
MIT13, MIT23, MIT33, MIT43
[mm]
A (mm)
B (mm)
TD160
83
86
TS250
102
86
TS630
168
110
TS800
201
135
Dimension of lock
5~8mm
30mm
A-6-20
Overall dimensions
Mechanical interlocking device
Mounting dimension for MIT
[mm]
A-6-21
2, 3Pole MCCBs
C(mm)
D(mm)
E(mm)
4Pole MCCBs
C(mm)
D(mm)
E(mm)
TD100/160
107
90
30
TD100/160
107
90
60
TS100/160/250
125
105
35
TS100/160/250
125
105
70
TS400/630
200
139.5
46.5
TS400/630
200
139.5
93
TS800
278
210
70
TS800
278
210
140
Overall dimensions
Plug-in device
Plug-in devices for TD100/160
[mm]
A
F
G
TD100/160
TD100/160
A(mm)
90
B(mm)
92
C(mm)
122
D(mm)
189.2
E(mm)
32.5
F(mm)
47
G(mm)
75
A-6-22
Overall dimensions
Plug-in device
Plug-in devices for TS100/160/250/400/630/800
[mm]
F
F
G
TS100/160/250/400/630
TS800
TS100/160/250
A-6-23
TS400/630
TS800
A(mm)
105
140
210
B(mm)
103.5
186.4
220
C(mm)
140
230
287
D(mm)
220
335.2
451
E(mm)
48.2
73
110
F(mm)
66
94.2
140
G(mm)
73
102
Overall dimensions
Plug-in device
Mounting to front plate
[mm]
B
A
Applicable to
A (mm)
TD100/160
TS100/160/250
TS400/630
TS800
30
35
46.5
70
B (mm)
90
105
140
210
C (mm)
160
182
290
387
D (mm)
E (mm)
173
M4 or 5
Front plate
202
314
422
M4 or 5
M5 or 6
M6 or 7
A-6-24
Overall dimensions
Plug-in device
Rail mounting
[mm]
Rail
Applicable to
TS400/630
TS800
A (mm)
30
70
100
156
B (mm)
76
77.8
101.6
104.2
C (mm)
14
28
32
43
D (mm)
A-6-25
TD100/160
M4 or 5
TS100/160/250
M6 or 7
M6 or 7
M8 or 9
Overall dimensions
Plug-in device
Mounting to rear plate with cover back
[mm]
Rear plate
Cover back
Applicable to
TD100/160
TS100/160/250
TS400/630
TS800
A (mm)
30
35
46.5
70
B (mm)
140
154
216
343
M4 or 5
M5 or 6
M6 or 7
C (mm)
M4 or 5
A-6-26
Overall dimensions
Plug-in device
Mounting for TD100/160
M4
375.2
26
5.3
34
62
34
92
34
[mm]
34
92
5.3
32.5
90
47
75
30
M4 or 5
30
A-6-27
326
262
14
4-M4 or 5
Overall dimensions
Terminal cover
ITS13E, ITS14E for TE100/160
24.5
150
[mm]
76
69.5
101
64.5
230
76
69.5
101
A-6-28
Overall dimensions
Terminal cover
ITS and ITL for TD100/160, TS100/160/250/400/630/800
[mm]
A
D(D')
C(C')
C(C')
Applicable to
Frame type
TD100, TD160
TS400, TS630
TS800
A-6-29
Type
Pole
Long
Dimension(mm)
Short
C
C
D
D
(Long type) (Short type) (Long type) (Short type)
type
type
2P, 3P
ITL13
ITS13
90
80.8
48.5
30.5
4P
ITL14
ITS14
120
80.8
32
25
2P, 3P
ITL23
ITS23
105
80.8
102
36.3
4P
ITL24
ITS24
140
80.8
98
32.3
2P, 3P
ITL33
ITS33
140
105
144.5
54.8
4P
ITL34
ITS34
186
105
138.5
48.8
2P, 3P
ITL43
ITS43
210
127.8
181.5
61.5
4P
ITL44
ITS44
280
127.8
172.5
52.5
196
160
321.4
190
479.4
300
600
360
Overall dimensions
Rear connection
RTF13, RTF14 for TE100/160
42.5
92.5
18
[mm]
13.8
135
25
25
70
25
130
150
8Nm
(82kgfcm)
8Nm
(82kgfcm)
A-6-30
Overall dimensions
Extended terminal
ET13E, ET14E for TE100/160
[mm]
21.5
50
45
81
50
130
170
190
8Nm
(82kgfcm)
25
70
16
82
76
5M ax
16
M
ax
8Nm
(82kgfcm)
A-6-31
Overall dimensions
Rear terminals
[mm]
TD100
TD160
30
122
30
30
TS100
TS160
TS250
35
140
35
35
TS400
TS630
46.5
230
46.5
46.5
TS800
287
70
70
70
A-6-32
Overall dimensions
Rear terminals
TD100 / TD160
[mm]
Bar type
4P(120)
2,3P(90)
122
8.6
44
88
10
30
30
Round type
30
4P(120)
122
2,3P(90)
36
54
80
98
M8
30
Panel drilling
18
5
30
30
30
30 30
2, 3P
A-6-33
30
30
30 30
4P
52
52
113.1
122
113.1
122
R2
90
2, 3P
120
4P
Overall dimensions
Rear terminals
TS100 / TS160 / TS250
[mm]
Bar type
4P(140)
2,3P(105)
140
8.2
43
11
89
35
35
Round type
35
4P(120)
140
2,3P(90)
36
54
82
100
M8
35
Panel drilling
35
35
20
5
35
35
35
35
2, 3P
35
35
4P
52
R2
52
125
140
125
140
R2
105
140
35
2, 3P
4P
A-6-34
Overall dimensions
Rear terminals
TS400 / TS630
[mm]
Bar type
4P(186.5)
2,3P(140)
230
13
50
114
15
46.5
Panel drilling
46.5
46.5
35
5
R2
46.5
A-6-35
46.5
46.5 46.5
2, 3P
4P
52 over
52 over
200
230
200
230
R2
140
2, 3P
186.5
4P
Overall dimensions
Rear terminals
TS800
[mm]
Bar type
4P(280)
2,3P(210)
287
13
37
16
81
70
122
168
Panel drilling
70
70
50
5
50
5
70
70
70
70
2, 3P
70
70
4P
52 over
R2
52 over
255
287
255
287
R2
210
280
2, 3P
4P
70
A-6-36
Overall dimensions
Circuit breaker with motor operator
MOP1, MOP2, MOP3, MOP4
TD100N/H/L
[mm]
TD160N/H/L
TS100N/H/L
TS160N/H/L
88
61.2
TS250N/H/L
TS400N/H/L
45
52.5
81
45
195
90
105
140
140
93.5
TS630N/H/L
186.5
268.5
140
103.7
TS800N/H/L
65
105
65
130
140
130
210
A-6-37
65
105
128
308
280
Overall dimensions
Wiring connection
Motor operator
Standard connection
Circuit breaker On and Off controlled by remote operation and manual operation
P1
1. 2Nm
P2
S1
Power
Ue
S2
S4
ON
OFF
Connection with FAL (only for the breakers with electronic trip unit ETS or ETM)
1) The below connection diagram is the method of using a FAL for circuit breakers with electronic
trip unit.
2) After clearing the fault surely, manual reset is mandatory in case of tripping due to an electrical
fault.
P1
P2
S1
S2
S4
ALb
Power
Ue
ALa
ALc
ON OFF
A-6-38
Overall dimensions
Wiring diagram(State of operation)
ETS23/ETS33/ETS43
The diagram is shown in the following conditions:
Fixed version circuit-breaker (depending on type of circuit-breaker)
Circuit breakers open.
Releases not tripped
L3
L1 L2 L3
OZ1
Downstream
Circuit Breaker
IZ2
IZ1
OZ2
OZ1
Upstream
Circuit Breaker
OZ2
L2
IZ1
L1
OZ2
OZ1
OZ2
IZ1
IZ2
C1
ETS23
ETS33
ETS43
COMMUNICATION
RS485 Modbus-RTU
C2
P1 G1
P2 G2
ETM33
ETM43
P1 +
P2
A-6-39
DC24V
Overall dimensions
TS 1000, 1250, 1600A
Front Type
[mm]
Insulation barrier
320
Plate protection
25
25
283.5
Mounting hole
5.5
115.7
11
250
C
L
C
L
37.2
C
L
212
270
327
212
270
327
5.5
70
70
70
199
210
70
269
280
70
47.5
115.7
149.8
152.5
155.5
162.7
190.6
16.5
16.5
Trip button
Panel drilling
ON BACKPLATE
ON RAILS
4P
212
99.5
99.5
199
4P
4- 5.5 or M5
4- 5.5 or M5
212
4- 5.5 or M5
212
4- 5.5 or M5
3P
99.5
99.5
199
269
212
3P
269
67
200
199
95
199
15
119
119
67
4P
95
3P
4P
15
3P
200
A-6-40
Overall dimensions
TS 1000, 1250, 1600A
Front Type Busbar
[mm]
307
267
77
50
77
2525
Insulation barrier
404
362
18
77
25 25
25
77
25 25
115.7
16.5
15
Plate protection
Mounting hole
283.5
5.5
11
11
25
C
L
C
L
37.2
C
L
212
270
327
374
404
212
270
327
374
404
5.5
70
70
70
Trip button
199
210
Panel drilling
70
269
280
47.5
70
115.7
149.8
152.5
155.5
162.7
190.6
ON RAILS
3P
4P
212
4- 5.5 or M5
212
4- 5.5 or M5
99.5
99.5
199
269
A-6-41
67
199
200
199
95
15
119
119
67
4P
95
3P
4P
15
3P
200
Overall dimensions
TS 1000, 1250, 1600A
Rear Type
[mm]
210
199
114.7
280
269
Insulation barrier
84
43.5
14
15
42
135
372
C
L
C
L
37.2
C
L
212
258
212
258
283.5
Mounting hole
Trip button
31
31
115.7
149.8
152.5
155.5
162.7
190.6
44 70
25
44
Insulation barrier
70
11
11
25
70
70
70
Panel drilling
ON BACKPLATE
ON BACKPLATE
4P
3P
4- 5.5 or M5
75
140
99.5
199
212
25
60
25
60
270
235
75
212
200
165
75
212
75
60
60
75
212
75
60
75
75
60
4P
4- 5.5 or M5
60
4- 5.5 or M5
4- 5.5 or M5
60
3P
210
99.5
99.5
99.5
199
269
269
67
200
199
95
199
15
119
119
67
4P
95
3P
4P
15
3P
200
A-6-42
Overall dimensions
Rotary handles
Direct rotary handles for TS 1600AF
[mm]
A Type
380 (3P) Minimum
450 (4P) Minimum
205 Minimum
203
217
8.5
4.5
4- 7
46
33
196
210
t1.2~3.2
155.5
204.5
267
B Type
205 (3P) Minimum
275 (4P) Minimum
201
212
4.5
280 Minimum
4- 7
25.5
134
145
t1.2~3.2
204.5
267
t1.2~3.2
246
681 Maximum (SHAFT Max. 469)
A-6-43
108
4- 6
24
108
Overall dimensions
Locking devices
Mechanical interlock for TS 1600AF
[mm]
TS1600
212
81
199
4P
TS1600
11
269
TS1600
212
81
199
4P
TS1600
11
269
A-6-44
Overall dimensions
Terminals
Front connection with bars for TS1600
Top terminal
[mm]
13.5
15 15
44
25
2-M10 Bolts
25
50
Bottom terminal
15 15
2-M10 Bolts
25
44
2- 11
12.8
15
12.5
60
12 max.
25
50
38
25
25
80
Left or right
busbar for 3P
77
50
25
15
25
5- 11
25
52
A-6-45
15
5- 11
15
21
5- 11
52
82
52
82
30
30
15
25
82
52
82
15
30
52
5- 11
77
50
77
25
15
77
50
21
Middle busbar
for 3P
12.5
30
25
60
25
50
15
12 max.
15
15
12 max.
25
52
25
52
25
52
Overall dimensions
Terminals
Front or Rear connection with vertical busbar for TS1600
[mm]
25
50
25
80
27
25
25
100
21
15
50/60/80/100
15
25
15
101
12 max.
15
25
25 12.5
60
89
25
26.5
12 max.
15
12 max.
15
12 max.
12 max.
25
25
15
15
20
Extension Busbar
50
80
23
184
150
50
5- 11
25
25
25
5- 13
25
A-6-46
A-7-1
A-7-7
Application
Primary use of transformer
Protection of lighting & heating circuits
Protection of resistance welding circuits
Use of circuit-breakers for capacitor banks
Using circuit-breakers in DC networks
Circuit breakers for 400Hz networks
Protection of several kinds of loads
A-7-8
A-7-10
A-7-11
A-7-12
A-7-15
A-7-16
A-7-18
Protective coordination
Discrimination & Cascading
Cascading, network 220/240V
Cascading, network 380/415V
Motor protection cascading, network 220/240V
Motor protection cascading, network 380/415V
Protection discrimination table, Discrimination
Motor protection discrimination table
Type 2 Coordination according to IEC60947-4-1
A-7-20
A-7-21
A-7-25
A-7-30
A-7-31
A-7-33
A-7-43
A-7-45
A-7-53
A-7-55
A-7-57
A-7-59
A-7-63
A-7-64
A-7-65
A-7-67
Technical information
Temperature derating
A derating of the rated operational current of the Susol TD and TS molded case circuit breaker is
necessary if the ambient temperature is greater than 40C. Namely, when the ambient temperature
is greater than 40C, overload-protection characteristics are slightly modified.
Electronic trip units are not affected by variations in temperature.
But, the maximum permissible current in the circuit breaker depends on the ambient temperature.
Derating chart
- Connection type: Standard
- Trip unit: FTU, FMU, ATU
MCCB
TD100
TD160
TS100
TS160
TS250
TS400
TS630
TS800
Rating
(A)
10C
20C
30C
40C
45C
50C
60C
70C
16
16
16
16
16
16
15
14
13
20
20
20
20
20
19
19
18
16
25
25
25
25
25
24
23
22
21
32
32
32
32
32
31
30
28
26
40
40
40
40
40
39
38
35
33
50
50
50
50
50
48
47
44
41
63
63
63
63
63
61
59
56
52
80
80
80
80
80
78
75
71
66
100
100
100
100
100
97
94
88
82
125
125
125
125
125
121
117
110
103
160
160
160
160
160
155
150
141
131
40
40
40
40
40
39
38
35
33
50
50
50
50
50
48
47
44
41
63
63
63
63
63
61
59
56
52
80
80
80
80
80
78
75
71
66
100
100
100
100
100
97
94
88
82
125
125
125
125
125
121
117
110
103
160
160
160
160
160
155
150
141
131
200
200
200
200
200
194
188
176
164
250
250
250
250
250
242
234
220
205
300
300
300
300
300
291
281
264
246
400
400
400
400
400
388
375
353
328
500
500
500
500
500
484
469
441
410
630
630
630
630
630
610
591
555
517
800
800
800
800
800
775
750
705
656
A-7-1
Technical information
Temperature derating
Derating chart
- Connection type: Plug-in
- Trip unit: FTU, FMU, ATU
MCCB
TD100
TD160
TS100
TS160
TS250
TS400
TS630
TS800
Rating
(A)
10C
20C
30C
40C
45C
50C
60C
70C
16
16
16
16
16
16
20
20
20
20
20
19
15
14
13
19
18
16
25
25
25
25
25
32
32
32
32
32
24
23
22
21
31
30
28
26
40
40
40
40
50
50
50
50
40
39
38
35
33
50
48
47
44
41
63
63
63
80
80
80
63
63
61
59
56
52
80
80
78
75
71
66
100
100
100
100
100
97
94
88
82
125
125
125
125
125
121
117
110
103
160
160
160
160
160
155
150
141
131
40
40
40
40
40
39
38
35
33
50
50
50
50
50
48
47
44
41
63
63
63
63
63
61
59
56
52
80
80
80
80
80
78
75
71
66
100
100
100
100
100
97
94
88
82
125
125
125
125
125
121
117
110
103
160
160
160
160
160
155
150
141
131
200
200
200
200
200
194
188
176
164
250
250
250
250
250
242
234
220
205
300
300
300
300
300
291
281
264
246
400
400
400
400
400
388
375
353
328
500
500
500
500
500
484
469
441
410
630
630
630
630
630
610
591
555
517
800
800
800
800
800
775
750
705
656
A-7-2
Technical information
Size of busbar
Temperature derating
The table below indicates the maximum rated current value for each type of connection,
depending on the ambient temperature.
Connection
T
TS1000
40
45
50
55
60
65
70
800
800
800
800
800
800
800
1000
1000
1000
1000
1000
1000
1000
TS1250
1250
1250
1250
1250
1250
1240
1090
TS1600
1600
1600
1560
1510
1470
1420
1360
45
50
55
60
65
70
Connection
T
Vertical rear
40
800
800
800
800
800
800
800
1000
1000
1000
1000
1000
1000
1000
TS1250
1250
1250
1250
1250
1250
1250
1180
TS1600
1600
1600
1600
1600
1600
1510
1460
TS1000
A-7-3
Technical information
Derating table
T:30C
T:35C
T:40C
T:45C
IP40
IP40
IP40
IP40
IP40
IP40
TS1000 N/H/L
1000
1000
1000
1000
1000
1000
TS1250 N/H
1250
1250
1250
1250
1250
1250
TS1600 N/H
1350
1350
1300
1250
1200
1150
Model
T:50C
T:30C
T:35C
T:40C
T:45C
IP40
IP40
IP40
IP40
IP40
IP40
TS1000 N/H/L
1000
1000
1000
1000
1000
1000
TS1250 N/H
1250
1250
1250
1250
1250
1200
TS1600 N/H
1450
1400
1350
1300
1250
1200
Model
T:50C
A-7-4
Technical information
Derating table
T:30C
T:35C
T:40C
T:45C
IP40
IP40
IP40
IP40
IP40
IP40
TS1000 N/H/L
1000
1000
1000
1000
1000
1000
TS1250 N/H
1250
1250
1250
1250
1250
1250
TS1600 N/H
1600
1600
1600
1550
1500
1450
Model
A-7-5
T:50C
Technical information
Installation recommendation
(numerals 0 to 6, or letter
(numerals 0 to 8, or letter
Non-protected
Protected against solid foreign objects
of 50mm
and greater
Protected against solid foreign objects
of 12.5mm
and greater
Protected against solid foreign objects
of 2.5mm
and greater
Protected against solid foreign objects
of 1.0mm
and greater
Dust-protected
Dust-tight
Definition
The object probe sphere of 50mm ,
shall not fully penetrate
The object probe sphere of 12.5mm ,
shall not fully penetrate
The object probe sphere of 2.5mm ,
shall not penetrate at all
The object probe of 1.0mm ,
shall not penetrate at all
Ingress of dust is not totally prevented, but dust shall not
penetrate in a quantity to interfere with satisfactory
operation of the apparatus or to impair safety
No ingress of dust
Non-protected
Protected against vertically falling
water drops
Protected against vertically falling
water drops when enclosure tilted
up to 15
Definition
Vertically falling drops shall have no harmful effects
Vertically falling drops shall have no harmful effects
when the enclosure is tilted at any angle up to 15 on
either side of the vertical
Water sprayed at an angle up to 60 on wither side of
the vertical shall have no harmful effects
Water splashed against the enclosure from and
direction shall have no harmful effects
Water projected in powerful jets against the enclosure
from and direction shall have no harmful effects
Water projected in powerful jets against the enclosure
from any direction shall have no harmful effects
Ingress of water in quantities causing harmful effects shall
not be possible when the enclosure is temporarily immersed
in water under standardized conditions of pressure and time
Ingress of water in quantities causing harmful effects
shall not be possible when the enclosure is
continuously immersed in water under conditions which
shall be agreed between manufacturer and used but
which are more severs than for numeral 7
A-7-6
Technical information
Power dissipation / Resistance
MCCB
Plug-in
MCCB
20
25
32
40
50
63
80
100
0.70
R (m)
5.60
5.60
3.80
3.80
1.84
1.34
1.10
0.91
1.43
2.24
2.38
3.89
2.94
3.35
4.37
5.82
7.00
4.30
6.72
7.13
11.67
8.83
10.05
13.10
17.47
21.00
0.78
R (m)
5.68
5.68
3.88
3.88
1.92
1.42
1.18
0.99
1.45
2.27
2.43
3.97
3.07
3.55
4.68
6.34
7.80
4.36
6.82
7.28
11.92
9.22
10.65
14.05
19.01
23.40
200
250
0.52
0.25
AF
Fixed
Rating (A)
100
125
R (m)
0.70
0.61
0.50
7.00
9.53
12.80
21.00 28.59
38.40
0.78
0.69
7.80 10.78
14.85
23.40 32.34
44.54
Rating (A)
MCCB
Plug-in
MCCB
MCCB
Plug-in
MCCB
Fixed
50
63
80
100
160
3.37
2.86
2.86
1.36
0.96
0.76
0.62
5.39
7.15
11.35
8.70
9.60
11.88
15.87
20.80 15.79
16.18
21.45
34.05
26.11
28.80
35.63
47.62
62.40 47.38
3.43
2.92
2.92
1.42
1.02
0.82
0.68
R (m)
0.58
0.31
5.49
7.30
11.59
9.09
10.20
12.81
17.41
23.20 19.54
16.46
21.90
34.77
27.26
30.60
38.44
52.22
69.60 58.63
400
R (m)
0.30
0.30
0.26
0.21
26.82
47.68
65.25
83.35
73.81
73.81
221.44
221.44
R (m)
500
Rating (A)
630
700
800
0.12
0.12
0.34
0.34
0.30
0.25
0.14
0.14
30.42
54.08
75.25
99.23
86.61
86.61
259.84
259.84
AF
R (m)
TS1000L
630
800
1000
1250
1600
630
800
1000
0.027
0.027
0.027
0.027
0.027
0.046
0.046
0.046
10.7
17.3
27.8
45.1
76.0
18.3
30.0
48.3
32.1
51.8
83.4
135.4
228.1
54.8
90.1
144.9
A-7-7
125
Rating (A)
MCCB
R (m)
AF
Fixed
0.58
AF
Fixed
160
Technical information
Application
Primary use of transformer
Application for transformer protection
Transformer excitation surge current may possibly exceed 10 times rated current, with a danger of
nuisance tripping of the MCCB. The excitation surge current will vary depending upon the supply
phase angle at the time of switching, and also on the level of core residual magnetism.
So, its recommended to select proper circuit breakers according to the continuous current carrying
capacity of transformer. It requires to consider separately whether transformer is single phase or
three phase. The below table indicates the proper molded case circuit breaker suitable for each
transformer.
AC220V
Capacity of 3 phase
transformer (kVA)
Capacity of single
phase transformer (kVA)
Breaking capacity (kA)
(sym)
Below 1500
Below 2000
Below 300
85
100
TD100H
TD100N
160
Below 3000
42
100
Frame (A)
Below 1500
TS100N
TD160H
TD160N
TS160N
120
200
TD100L
TS100H
TS100L
TD160L
TS160H
TS160L
250
TS250N
TS250H
TS250L
400
TS400N
TS400H
TS400L
630
TS630N
TS630H
TS630L
800
TS800N
TS800H
TS800L
AC460V
Capacity of 3 phase
transformer (kVA)
Breaking capacity (kA)
(sym)
100
160
Frame (A)
250
Below 2000
50
TD100N
Below 3000
65
70
Below 4000
85
100
TD100H
TD100L
TS100N
TS100H
TS100L
TD160N
TD160H
TD160L
TS160N
TS160H
TS160L
TS250N
TS250H
TS250L
130
400
TS400N
TS400H
TS400L
630
TS630N
TS630H
TS630L
800
TS800N
TS800H
TS800L
A-7-8
Technical information
Application
Primary use of transformer
Application for transformer protection
(MCCBs for Transformer-Primary Use)
Transformers are used to change in the supply voltage, for both medium and low voltage supplies.
The choice of the protection devices should be considered transient insertion phenomena, during
which the current may reach values higher than the rated full load current; the phenomenon decays
in a few seconds.
The peak value of the first half cycle may reach values of 15 to 25 times the effective rated current.
For a protective device capable of protecting these units this must be taken into account.
Manufacturers data and tests have indicated that a protective device feeding a transformer must be
capable of carrying the following current values without tripping.
1 phase 230V
MCCB rated
current
(A)
16
Trip unit
3 to 4
5 to 6
9 to 11
4 to 5
6 to 8
11 to 14
20
5 to 6
8 to 10
14 to 17
25
6 to 7
10 to 13
18 to 22
32
7 to 9
13 to 16
22 to 28
40
9 to 12
16 to 20
28 to 35
50
12 to 14
20 to 25
35 to 44
63
15 to 18
26 to 32
44 to 55
80
18 to 23
32 to 40
55 to 69
100
FTU
23 to 29
40 to 50
69 to 87
125
FMU
29 to 37
51 to 64
89 to 111
160
ATU
37 to 47
64 to 80
111 to 138
200
46 to 58
80 to 100
138 to 173
250
55 to 69
96 to 120
166 to 208
300
74 to 92
128 to 160
221 to 277
400
92 to 115
160 to 200
277 to 346
500
116 to 145
202 to 252
349 to 436
630
129 to 161
224 to 280
388 to 484
700
147 to 184
256 to 320
443 to 554
800
A-7-9
3 phase 400V
MCCB rated
current
(A)
4 to 7
6 to 13
11 to 22
40
Trip
unit
Ir max
setting
0.8
9 to 19
16 to 32
27 to 56
100
0.8
15 to 30
25 to 52
44 to 90
160
0.8
23 to 46
40 to 80
70 to 139
250
37 to 74
64 to 128
111 to 222
400
58 to 115
100 to 200
175 to 346
630
0.8
74 to 184
127 to 319
222 to 554
800
ETS
ETM
0.8
0.8
Technical information
Application
Protection of lighting & heating circuits
In the lighting & heating circuits, switching-surge magnitudes and times are normally not sufficient
to cause serious tripping problems. But, in some cases, such as incandescent lamps, mercury arc
lamps, metal halide and sodium vapour, or other large starting-current equipment, the proper
selection should be considered.
Upon supply of a lighting installation, for a brief period an initial current exceeding the rated current
(corresponding to the power of the lamps) circulates on the network. This possible peak has a
value of approximately 1520 times the rated current, and is present for a few milliseconds; there
may also be an inrush current with a value of approximately 1.53 times the rated current, lasting
up to some minutes. The correct dimensioning of the switching and protection devices must take
these problems into account. Generally, it is recommended to make the maximum operating
current not to exceed 80% of the related current.
AC220V
The maximum
operating
current (A)
12
16
20
25
32
40
50
64
80
100
128
160
200
240
320
400
504
560
640
100
120
TD100H
200
TD100L
TD100N
TD100H
TS100N
TD100L
TS100H
TD100L
TS100L
TD160H
TS160N
TS160H
TD160L
TS160L
TS250N
TS250H
TS250L
TS400N
TS400H
TS400L
TS630N
TS630H
TS630L
TS800N
TS800H
TS800L
TD160N
AC460V
The maximum
operating
current (A)
The rated
current of
MCCB (A)
12
16
20
25
32
40
50
64
80
100
128
160
200
240
320
400
504
560
640
16
20
25
32
40
50
63
80
100
125
160
200
250
300
400
500
630
700
800
50
65
70
85
100
TD100N
TS100N
TD100H
TS100H
TD100L
TS100L
TD160N
TS160N
TD160H
TS160H
TD160L
TS160L
TS250N
TS250H
TS250L
130
TS400N
TS400H
TS400L
TS630N
TS630H
TS630L
TS800N
TS800H
TS800L
A-7-10
Technical information
Application
Protection of resistance welding circuits
Short circuit protection for resistance welding devices can be obtained by applying molded case
circuit breaker properly. These breakers permit normally high welding currents, but trip
instantaneously if a short circuit develops.
It's recommended to select proper circuit breaker according to the characteristics of welding
devices as the follow table.
TD100N/H/L 100A
15
35
TS100N/H/L 100A
TD100N/H/L 50A
TD160N/H/L 100A
TS100N/H/L 50A
TS160N/H/L 100A
TD100N/H/L 100A
TD160N/H/L 125A
30
65
TS160N/H/L 125A
TS250N/H/L 125A
TS100N/H/L 100A
TD160N/H/L 100A
TS160N/H/L 100A
TD160N/H/L 125A
55
140
TS250N/H/L 250A
TS160N/H/L 125A
TS250N/H/L 125A
A-7-11
Technical information
Application
Use of circuit-breakers for capacitor banks
Application for protection of capacitor circuit
C
Capacitor circuit
In order to reduce system losses (less than 0.5W/kvar in low voltage) and voltage drops in the
power distribution system, reactive power compensation or power factor correction is generally
undertaken. As a result, the power fed into the system is used as active power and costs will be
saved through a reduction in the capacitive and inductive power factors. The compensation can be
carried out by the fixed capacitors and automatic capacitor banks. However, the disadvantages of
installing capacitors are sensitivity to over-voltages and to the presence of nonlinear loads.
L1
L2
L3
1
Examples of equipment which consume reactive energy are all those receivers which require
magnetic fields or arcs in order to operate, such as:
- Asynchronous motors: An asynchronous motor is a large consumer of inductive reactive energy.
The amount of reactive power consumed is between 20% and 25% of the
rated power of the motor (depending on its speed).
Breaker
Contactor
O/L
- Power Transformers: Power transformers are normally always connected. This means that
reactive energy is always consumed. Also, as a consequence of its
inductive nature, the reactive energy increases when the transformer is
loaded.
T2 T3
T1
C
M
Motor
- Discharge lamps, Resistance-type soldering machines, Dielectric type heating ovens, Induction
heating ovens, Welding equipments, Arc furnaces
L1
L2
L3
1
Breaker
Contactor
At the instant of closing a switch to energize a capacitor, the current is limited only by the
impedance of the network upstream of the capacitor, so that high peak values of current will occur
for a brief period, rapidly falling to normal operating values.
O/L
T1
T2 T3
C
M
According to the relevant standards IEC 60831-1/IEC 70, capacitors must function under normal
operating conditions with the current having a RMS value up to 1.3 times the rated current of the
capacitor. Additionally, a further tolerance of up to 15% of the real value of the power must be
taken into consideration. The maximum current with which the selected circuit-breaker can be
constantly loaded, and which it must also be able to switch, is calculated as follows:
Motor
L1
L2
L3
1
Breaker
Breaker
Maximum expected rated current= Rated current of the capacitor bank1.5 (RMS value)
Contactor
C
O/L
T1
T2
T3
M
Motor
A-7-12
Technical information
Application
Use of circuit-breakers for capacitor banks
220V, 50/60Hz Circuit
Capacitor rating
kVAR
5
Single-phase circuit
Three-phase circuit
Capacitor rated
MCCB rated
Capacitor rated
MCCB rated
current (A)
current (A)
current (A)
current (A)
22.7
40
20
10
45.5
80
26.2
40
15
68.2
125
39.4
63
20
90.9
160
52.5
80
25
113.6
200
65.6
100
30
136.4
225
78.7
125
40
181.8
300
105.0
160
50
227.3
400
131.2
200
75
340.9
630
196.8
300
100
454.5
700
262.4
400
150
681.8
393.7
630
200
909.1
524.9
800
300
1363.6
787.3
400
1818.2
1049.8
Notes) 1. The MCCB rated current should be approx. 150% of the capacitor rated current.
2. The MCCB short-circuit capacity should be adequate for the circuit short-circuit capacity.
A-7-13
13.1
Technical information
Application
Use of circuit-breakers for capacitor banks
440V, 50/60Hz Circuit
Capacitor rating
kVAR
Single-phase circuit
Three-phase circuit
Capacitor rated
MCCB rated
Capacitor rated
MCCB rated
current (A)
current (A)
current (A)
current (A)
11.4
20
6.6
16
10
22.7
40
13.1
20
15
34.1
63
19.7
32
20
45.5
80
26.2
40
25
56.8
100
32.8
50
30
68.2
125
39.4
63
40
90.9
160
52.5
80
50
113.6
200
65.6
100
75
170.5
300
98.4
160
100
227.3
400
131.2
200
150
340.9
500
196.8
300
200
454.5
700
262.4
400
300
681.8
393.7
630
400
909.1
524.9
800
Notes) 1. The MCCB rated current should be approx. 150% of the capacitor rated current.
2. The MCCB short-circuit capacity should be adequate for the circuit short-circuit capacity.
A-7-14
Technical information
Application
Using circuit-breakers in DC networks
Susol circuit-breakers for protection of power distribution with thermal overload and magnetic shortcircuit trip units are suitable for usage in DC networks.
The circuit-breakers with electronic overcurrent releases are not suitable for DC networks.
Circuit-breaker selection criteria
The followings are the most important criteria for selection of suitable circuit breaker for DC
networks.
The rated current determines the rating and size of the circuit-breaker (Equipment)
The rated voltage determines the number of poles in series necessary for breaking
The maximum short-circuit current at the connection point determines the breaking capacity
Setting range of the trip values
Thermal overload protection: Same setpoints as in 50/60Hz circuits
Instantaneous short-circuit protection: The response threshold increases by maximum 40%.
The following wiring diagrams are recommended since the current must flow through all
current paths in order to conform to the thermal tripping characteristic curve.
-(N)
-(N)
+(P)
+(P)
Load
Load
Model
Trip unit
TD100N,TD160N
Applicable to DC circuits
42
50
65
85
100
TS100N,TS160N, TS250N
TS400N, TS630N
TS800N
TD100H, TD160H
Thermal
magnetic
FTU
TS400H, TS630H
FMU
TS800H
ATU
TD100L, TD160L
TS100L, TS160L, TS250L
TS400L, TS630L
TS800L
Electronic
A-7-15
ETS, ETM
Technical information
Application
Circuit breakers for 400Hz networks
When circuit breakers are used at high frequencies, the breakers in many cases require to be
derated as the increased resistance of the copper sections resulting from the skin effect produced
by eddy currents at 400Hz.
Standard production breakers can be used with alternating currents with frequencies other than
50/60 Hz (the frequencies to which the rated performance of the device refer, with alternating
current) as appropriate derating coefficients are applied.
K1
K2
16
0.8
20
0.8
25
0.8
32
0.8
40
0.8
50
0.8
63
0.8
80
0.8
0.8
0.8
0.8
200
0.8
250
0.8
FTU
100
FMU
125
160
ATU
TS250N, TS250H, TS250L
300
0.8
400
0.8
500
0.8
630
0.8
0.8
700
Note) K1Multiplier factor of rated current (In)
K2-Multiplier factor of instantaneous current due to the induced magnetic fields
FTU-Fixed Thermal and magnetic trip unit
FMUAdjustable thermal and fixed magnetic trip unit
ATUAdjustable thermal and magnetic trip unit
A-7-16
Technical information
Application
Circuit breakers for 400Hz networks
Electronic trip units
The use of electronics offers the advantage of greater operating stability when the frequency is
varied. However, the devices are still subjected to frequency related temperature effects which may
sometimes pose restrictions on their use. Column K1 of the table below gives the maximum
permissible current to be used for the current setting (knob position).
Rated current
(A)
in 400 Hz
40
80
160
250
400
630
K2
0.4 to 1
ETS
ETM
800
Note) ATUAdjustable thermal and magnetic trip unit
K1Multiplier factor of rated current (In)
K2-Multiplier factor of instantaneous current due to the induced magnetic fields
ETSElectronic trip unit (Standard)
ETMElectronic trip unit (Multi-function)
A-7-17
K1
0.4 to 1
0.4 to 0.9
0.4 to 0.9
0.4 to 0.8
0.4 to 0.8
0.4 to 0.75
0.97
Technical information
Application
Protection of several kinds of loads
Application for protection of several kinds of loads
It requires to select proper circuit breakers according to the characteristics of loads when they are
installed to protect several kinds of loads. It's needed to consider the maximum operating current
and the capacity of loads in total so as to select the rated current of breakers.
Selection of circuit breaker protecting the several loads simultaneously
The kind of loads
Permissible current
in cable or wire: IW
of circuit breaker: Ib
In case of,
IM IL
M IM1
Ib
Iw
M IM2
IL1
IW IM + IL
Choose the low value among
IL2
In case of,
IM IL,
Ib
Iw
IM 50A
two formulas:
M IM1
M IM2
Ib 2.5IW
IL1
Iw 1.25IM + IL
Its permitted to select the above value
IL2
In case of,
IM IL, Ib
M IM1
Iw
IM 50A
M IM2
IL1
IL2
The rated current of breakers as the main circuit of 3 phase inductive loads (AC 220V)
Capacity of
loads In total
(below kW)
3
4.5
6.3
8.2
12
15.7
19.5
23.2
30
37.5
45
52.5
63.7
75
86.2
97.5
112.5
125
150
175
The maximum
4.8
20
32
40
50
63
100
100
125
160
200
200
250
300
400
400
500
500
630
700
800
8
32
32
40
50
63
100
100
125
160
200
200
250
300
400
400
500
500
630
700
800
11.1 17.4
32
32 50
40 50
50 50
63 63
100 100
100 100
125 125
160 160
200 200
200 200
250 250
300 300
400 400
400 400
500 500
500 500
630 630
700 700
800 800
37 45
55 75 90
26 34
48 65
63
80
80
100
100
125
160
200
200
250
300
400
400
500
500
630
700
800
125
125
125
160
200
200
250
300
400
400
500
500
630
700
800
200
200
200
200
200
250
300
400
400
500
500
630
700
800
100
100
100
100
125
160
200
200
250
300
400
400
500
500
630
700
800
160
160
160
160
200
200
250
300
400
400
500
500
630
700
800
200
250
250
250
250
300
400
400
500
500
630
700
800
300
300 400
300 400
300 400
400 400
400 400
500 500
500 500
630 630
700 700
800 800
500
500
500
500
500
500
630
700
800
500
500
500
500
500
630
700
800
630
630
700
700
700
800
700
700
700
800
800
A-7-18
Technical information
Application
Protection of several kinds of loads
The rated current of breakers as the main circuit of 3 phase inductive loads (AC 440V)
Capacity The maximum
Capacity of the highest motor (kW / A)
of loads
operating
0.75
1.5
2.2
3.7
5.5
7.5
11 15 18.5 22 30 37 45 55 75 90 110 132
In total
current
(below kW)
(below A) 4.8 8 11.1 17.4 26 34 48 65 79 93 125 160 190 230 310 360 220 250
3
7.5
16 16
16
16 32
4.5
10
16 16
6.3
15
20 20
20 32 40
8.2
20
32 32
32 32 40 50
12
25
32 32
32 32 40 50
15.7
38
50 50
50 50 50 50 63 80
19.5
45
50 50
50 50 50 50 63 80 100
23.2
50
63 63
63 63 63 63 63 80 100 125
30
63
80 80
37.5
75
100 100 100 100 100 100 100 100 100 125 160
45
88
100 100 100 100 100 100 100 100 100 125 160 200
52.5
100
125 125 125 125 125 125 125 125 125 125 160 200 250
63.7
125
160 160 160 160 160 160 160 160 160 160 160 200 250 250
75
150
200 200 200 200 200 200 200 200 200 200 200 200 250 250
86.2
175
200 200 200 200 200 200 200 200 200 200 200 200 250 300 400
97.5
200
250 250 250 250 250 250 250 250 250 250 250 250 250 300 400 400 500
112.5
225
250 250 250 250 250 250 250 250 250 250 250 250 250 300 400 400 500 500
125
250
300 300 300 300 300 300 300 300 300 300 300 300 300 300 400 400 500 500
150
300
400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 500 500
175
350
400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 500 630 630
200
400
500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 700 700
250
500
630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 800 800
300
600
700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 700 800 800
350
700
800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800
400
700
800 800 800 800 800 800 800 800 800 800 800 800 800 800 800 800
Notes) The above mentioned technical data is defined under the usage conditions as follows ;
1. The circuit breaker is tripped within 10seconds in 600% of the current of the fully operating loads.
2. The start-up input current is set within 1700% of the current of the fully operating loads.
3. The capacity of highest motor is also applied when several loads starts up simultaneously.
A-7-19
Technical information
Protective coordination
Discrimination & Cascading
The primary purpose of a circuit protection system is to prevent damage to series
connected equipment and to minimize the area and duration of power loss.
The first consideration is whether an air circuit breaker or molded case circuit
breaker is the most suitable. The next is the type of system to be used.
The two major types are: Discrimination and cascading.
Discrimination
According to IEC60947-2, the discrimination can be defined as follows.
Total discrimination (total selectivity)
Over-current discrimination where, in the presence of two over-current protective devices in series,
the protective device on the load side effects the protection without causing the other protective
device to operate.
Main breaker
Comtinuous supply
Branch breaker
Short-circuit point
Healthy circuit
<Discrimination>
Cascading
Main breaker
Branch
breaker
This is an economical approach to the use of circuit breakers, whereby only the main (upstream)
breaker has adequate interrupting capacity for the maximum available fault current.
The MCCBs downstream cannot handle this maximum fault current and rely on the opening of the
upstream breaker for protection.
The advantage of the cascade back-up approach is that it facilitates the use of low cost, low fault
level breakers downstream, thereby offering savings in both the cost and size of equipment.
As Susol TD & TS circuit breakers have a very considerable current limiting effect, they can be
used to provide this cascade back-up protection for downstream circuit breakers.
Fault point
<Cascading>
A-7-20
Technical information
Protective coordination
Cascading, network 220/240V
Complementary technical information
Main: Susol TD/TS series
Main breaker
Branch breaker
Rated breaking
capacity (kArms)
ABS33c
AB
Susol
TD
&
TS
A-7-21
30
100
200
50
50
65
85
50
100
200
100
120
200
50
65
65
65
85
ABN53c
30
50
50
65
50
50
65
85
100
100
ABS53c
35
65
65
85
65
65
85
100
120
120
ABH53c
100
ABN63c
30
50
65
65
65
65
65
85
120
85
120
85
ABS63c
35
65
85
100
85
85
100
85
100
100
ABN103c
35
85
100
120
85
100
120
100
120
120
200
100
ABS125c
85
ABH125c
100
ABN203c
65
ABS203c
85
ABH203c
100
ABN403c
50
ABS403c
75
ABH403c
85
ABL403c
125
ABN803c
50
ABS803c
85
ABL803c
125
TD100N
85
TD100H
100
TD160N
85
TD160H
100
TS100N
100
TS100H
120
TS160N
100
TS160H
120
TS250N
100
TS250H
120
TS400N
100
TS400H
120
TS630N
100
TS630H
120
TS800N
100
TS800H
120
TS1000N
55
TS1000H
75
TS1250N
55
TS1250H
75
100
200
100
200
200
100
120
200
120
200
120
200
200
200
200
Technical information
Protective coordination
Cascading, network 220/240V
Complementary technical information
Main: Susol TS series
Main breaker
Branch breaker
Rated breaking
capacity (kArms)
ABS33c
AB
Susol
TD
&
TS
30
120
200
100
120
200
65
65
85
50
50
65
65
ABN53c
30
85
100
100
50
50
ABS53c
35
100
120
120
65
65
85
ABH53c
100
120
120
ABN63c
30
65
85
65
65
85
65
100
120
200
ABS63c
35
85
100
100
85
85
100
ABN103c
35
100
120
120
85
100
120
100
100
120
100
120
150
120
150
100
120
150
100
ABS125c
85
ABH125c
100
ABN203c
65
85
85
100
85
85
ABS203c
85
100
100
120
100
120
150
ABH203c
100
120
150
100
120
150
ABN403c
50
85
100
100
ABS403c
75
100
120
120
ABH403c
85
100
120
150
ABL403c
125
ABN803c
50
ABS803c
85
ABL803c
125
TD100N
85
TD100H
100
200
100
100
120
200
120
200
100
100
120
200
120
200
100
200
120
200
TD160N
85
120
200
120
200
120
200
TD160H
100
120
200
120
200
120
200
TS100N
100
120
200
120
200
120
200
TS100H
120
TS160N
100
TS160H
120
TS250N
100
TS250H
120
TS400N
100
TS400H
120
TS630N
100
TS630H
120
TS800N
100
TS800H
120
TS1000N
55
TS1000H
75
TS1250N
55
TS1250H
75
200
120
200
100
120
200
120
200
200
200
120
200
120
200
200
120
200
200
200
200
120
200
200
A-7-22
Technical information
Protective coordination
Cascading, network 220/240V
Complementary technical information
Main: Susol TS series
Main breaker
Branch breaker
Rated breaking
capacity (kArms)
ABS33c
AB
Susol
TD
&
TS
A-7-23
TS630N
TS630H
TS630L
TS800N
TS800H
TS800L
100
120
200
100
120
200
30
ABN53c
30
ABS53c
35
ABH53c
100
ABN63c
30
ABS63c
35
ABN103c
35
ABS125c
85
100
120
150
ABH125c
100
100
120
150
ABN203c
65
85
85
100
ABS203c
85
100
120
150
ABH203c
100
100
120
150
ABN403c
50
85
100
100
85
100
100
ABS403c
75
100
120
120
100
120
120
ABH403c
85
100
120
150
100
120
ABL403c
125
ABN803c
50
ABS803c
85
ABL803c
125
TD100N
85
TD100H
100
200
150
200
100
120
120
120
150
200
100
200
200
100
200
200
85
120
200
120
200
TD160H
100
120
200
120
200
TS100N
100
120
200
120
200
TS100H
120
TS160N
100
TS160H
120
TS250N
100
TS250H
120
TS400N
100
TS400H
120
TS630N
100
TS630H
120
TS800N
100
TS800H
120
TS1000N
55
TS1000H
75
55
TS1250H
75
100
120
120
TD160N
TS1250N
100
120
120
200
120
200
200
120
200
120
200
200
120
200
200
200
120
200
200
120
200
120
200
200
120
200
200
200
200
120
200
200
Technical information
Protective coordination
Cascading, network 220/240V
Complementary technical information
Main: Susol TS series
Main breaker
Branch breaker
Rated breaking
capacity (kArms)
ABS33c
AB
Susol
TD
&
TS
75
200
55
75
55
75
75
200
55
75
55
75
55
75
55
75
30
ABN53c
30
ABS53c
35
ABH53c
100
ABN63c
30
ABS63c
35
ABN103c
35
ABS125c
85
ABH125c
100
ABN203c
65
ABS203c
85
ABH203c
100
ABN403c
50
ABS403c
75
200
ABH403c
85
200
ABL403c
125
ABN803c
50
55
200
55
75
200
ABS803c
85
ABL803c
125
200
200
TD100N
85
200
TD100H
100
200
TD160N
85
200
TD160H
100
200
TS100N
100
200
TS100H
120
200
TS160N
100
200
TS160H
120
200
TS250N
100
200
TS250H
120
200
TS400N
100
200
TS400H
120
200
TS630N
100
200
TS630H
120
200
TS800N
100
200
TS800H
120
200
TS1000N
55
200
TS1000H
75
200
TS1250N
55
200
TS1250H
75
200
75
75
75
75
A-7-24
Technical information
Protective coordination
Cascading, network 380/415V
Complementary technical information
Main: Susol TD/TS series
Main breaker
Branch breaker Rated breaking
capacity (kArms)
AB
Susol
TD
&
TS
A-7-25
85
150
50
85
150
50
85
150
ABS33c
14
25
30
30
25
30
30
30
40
40
ABN53c
14
35
50
50
35
50
50
35
65
65
ABS53c
18
50
65
65
50
65
65
50
70
70
ABH53c
50
ABN63c
14
25
30
30
25
30
30
30
40
40
ABS63c
18
35
50
50
35
50
50
35
65
65
ABN103c
18
50
65
65
50
65
65
50
70
70
ABS125c
37
50
65
65
50
65
65
50
70
70
ABH125c
50
ABN203c
26
ABS203c
37
ABH203c
50
ABN403c
37
ABS403c
50
ABH403c
65
ABL403c
85
ABN803c
37
ABS803c
65
ABL803b
85
TD100N
50
TD100H
85
TD160N
50
TD160H
85
TS100N
50
TS100H
85
TS160N
50
TS160H
85
TS250N
50
TS250H
85
TS400N
65
TS400H
85
TS630N
65
TS630H
85
TS800N
65
TS800H
85
TS1000N
50
TS1000H
70
TS1250N
50
TS1250H
70
85
150
85
150
150
85
150
85
150
150
150
150
85
150
150
Technical information
Protective coordination
Cascading, network 380/415V
Complementary technical information
Main: Susol TS series
Main breaker
Branch breaker
Rated breaking
capacity (kArms)
AB
Susol
TD
&
TS
85
150
50
85
150
ABS33c
14
30
40
40
30
40
40
ABN53c
14
35
65
65
35
65
65
ABS53c
18
50
70
70
50
70
70
ABH53c
50
ABN63c
14
30
40
40
30
65
70
40
40
65
85
150
50
70
85
85
100
70
ABS63c
18
35
65
65
35
65
65
ABN103c
18
50
70
70
50
70
70
ABS125c
37
50
70
70
40
65
70
ABH125c
50
70
70
70
85
ABN203c
26
35
50
50
40
50
ABS203c
37
40
65
70
50
70
85
ABH203c
50
70
85
85
100
ABN403c
37
70
85
ABS403c
50
85
100
ABH403c
65
85
120
ABL403c
85
ABN803c
37
ABS803c
65
ABL803b
85
TD100N
50
TD100H
85
TD160N
50
TD160H
85
TS100N
50
TS100H
85
TS160N
50
TS160H
85
TS250N
50
TS250H
85
TS400N
65
TS400H
85
TS630N
65
TS630H
85
TS800N
65
TS800H
85
TS1000N
50
TS1000H
70
TS1250N
50
TS1250H
70
50
150
85
150
85
150
85
150
85
150
85
150
150
65
85
150
85
150
65
85
85
150
65
85
150
150
150
65
85
150
85
150
150
150
150
150
150
150
150
85
150
150
150
150
65
85
150
150
150
85
150
150
A-7-26
Technical information
Protective coordination
Cascading, network 380/415V
Complementary technical information
Main: Susol TS series
Main breaker
Branch breaker Rated breaking
capacity (kArms)
ABS33c
AB
Susol
TD
&
TS
A-7-27
TS630N
TS630H
TS630L
TS800N
TS800H
TS800L
65
85
150
65
100
150
50
70
85
85
100
70
50
70
85
85
100
65
100
120
100
150
14
ABN53c
14
ABS53c
18
ABH53c
50
ABN63c
14
ABS63c
18
ABN103c
18
ABS125c
37
ABH125c
50
ABN203c
26
40
50
ABS203c
37
50
70
85
ABH203c
50
85
100
ABN403c
37
70
85
ABS403c
50
85
100
ABH403c
65
85
120
ABL403c
85
ABN803c
37
65
85
100
ABS803c
65
65
100
120
ABL803b
85
TD100N
50
TD100H
85
TD160N
50
TD160H
85
TS100N
50
TS100H
85
TS160N
50
TS160H
85
TS250N
50
TS250H
85
TS400N
65
TS400H
85
TS630N
65
TS630H
85
TS800N
65
TS800H
85
TS1000N
50
TS1000H
70
TS1250N
50
TS1250H
70
50
150
65
85
150
65
100
150
100
150
150
65
85
150
150
65
100
150
65
85
150
65
100
150
65
85
150
85
150
65
100
150
65
100
150
150
150
100
150
85
150
150
150
85
150
150
150
65
150
150
150
150
100
150
150
150
100
150
Technical information
Protective coordination
Cascading, network 380/415V
Complementary technical information
Main: Susol TS series
Main breaker
Branch breaker
Rated breaking
capacity (kArms)
ABS33c
AB
Susol
TD
&
TS
70
150
50
70
50
70
70
150
50
70
50
70
14
ABN53c
14
ABS53c
18
ABH53c
50
ABN63c
14
ABS63c
18
ABN103c
18
ABS125c
37
ABH125c
50
ABN203c
26
ABS203c
37
ABH203c
50
ABN403c
37
ABS403c
50
70
150
70
70
ABH403c
65
70
150
70
70
ABL403c
85
ABN803c
37
ABS803c
65
ABL803b
85
TD100N
50
TD100H
85
TD160N
50
TD160H
85
TS100N
50
TS100H
85
TS160N
50
TS160H
85
TS250N
50
TS250H
85
TS400N
65
TS400H
85
TS630N
65
TS630H
85
TS800N
65
TS800H
85
TS1000N
50
TS1000H
70
TS1250N
50
TS1250H
70
50
150
50
70
70
150
150
50
70
50
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
150
70
150
150
70
150
150
70
150
150
70
150
150
70
150
150
70
150
150
70
150
150
70
150
150
70
150
150
70
150
150
A-7-28
Technical information
Protective coordination
Motor protection cascading, network 220/240V
Main: Susol TD/TS series
Branch: Susol MCCB
Main breaker
Branch breaker
Rated breaking
capacity (kArms)
Susol
TD
&
TS
TD100N
85
TD100H
100
TD160N
85
TD160H
100
TS100N
100
TS100H
120
TS160N
100
TS160H
120
Main breaker
Branch breaker
Rated breaking
capacity (kArms)
Susol
TD
&
TS
100
100
200
85
200
100
100
200
100
120
200
100
120
200
100
120
200
100
120
200
120
200
120
200
120
200
120
200
TD160H
100
120
200
120
TS100N
100
120
200
120
TS100H
120
TS160N
100
TS250H
120
Rated breaking
capacity (kArms)
TD100N
85
TD100H
100
TD160N
85
TD160H
TS100N
TS100H
120
Susol TS160N
TD TS160H
100
TS250N
100
100
200
120
200
120
100
TS800H
120
200
120
200
200
120
200
120
200
120
200
200
120
200
200
200
200
100
120
200
100
120
200
100
100
100
120
200
120
200
120
200
200
120
200
200
120
200
120
200
120
200
120
200
120
200
100
200
120
200
120
200
120
200
120
200
120
TS800N
200
TS800L
120
TS630H
200
120
100
TS800H
120
120
200
TS800N
100
100
120
TS630L
100
TS630N
200
TS630H
200
TS400H
100
120
TS630N
120
120
100
200
200
100
200
200
200
TS400N
120
120
120
200
120
TS250H
200
200
200
120
100
120
120
200
100
85
120
200
TD160N
100
100
120
200
85
TS250N
200
100
200
100
TS160H
200
200
TD100H
Main breaker
A-7-29
85
TD100N
Branch breaker
&
TS
200
200
200
200
200
200
200
200
200
120
200
200
Technical information
Rated breaking
capacity (kArms)
Susol
TD
&
TS
75
200
TD100N
85
TD100H
100
200
TD160N
85
200
TD160H
100
200
TS100N
100
200
TS100H
120
200
TS160N
100
200
TS160H
120
200
TS250N
100
200
TS250H
120
200
TS400N
100
200
TS400H
120
200
TS630N
100
200
TS630H
120
200
TS800N
100
200
TS800H
120
200
TS1000N
55
200
TS1000H
75
200
TS1250N
55
200
TS1250H
75
200
55
75
55
75
200
75
75
75
75
A-7-30
Technical information
Protective coordination
Motor protection cascading, network 380/415V
Main: Susol TD/TS series
Branch: Susol MCCB
Main breaker
Branch breaker
Rated breaking
capacity (kArms)
Susol
TD
&
TS
TD100N
50
TD100H
85
TD160N
50
TD160H
85
TS100N
50
TS100H
85
TS160N
50
TS160H
85
Main breaker
Branch breaker
Rated breaking
capacity (kArms)
Susol
TD
&
TS
TD100N
50
TD100H
85
TD160N
50
TD160H
85
TS100N
50
TS100H
85
TS160N
50
TS160H
85
TS250N
50
TS250H
85
Main breaker
Branch breaker
Rated breaking
capacity (kArms)
Susol
TD
&
TS
A-7-31
TD100N
50
TD100H
85
TD160N
50
TD160H
85
TS100N
50
TS100H
85
TS160N
50
TS160H
85
TS250N
50
TS250H
85
TS400N
65
TS400H
85
TS630N
65
TS630H
85
TS800N
65
TS800H
85
100
85
200
85
150
100
85
150
200
100
150
120
85
150
85
200
150
150
150
150
85
150
150
120
200
85
150
100
120
85
150
85
150
85
120
150
65
85
150
85
150
65
85
65
85
85
150
150
150
150
150
150
65
85
65
85
150
85
150
150
150
150
200
150
150
150
150
85
100
150
150
85
200
150
150
150
150
150
TS630N
TS630H
TS630L
TS800N
TS800H
TS800L
100
120
200
100
120
200
65
85
150
65
100
150
65
85
150
65
85
150
65
100
65
100
150
85
150
65
85
150
65
100
65
100
85
150
150
150
150
150
150
150
150
85
150
150
150
65
150
150
150
150
100
150
150
150
100
150
150
150
100
150
Technical information
Rated breaking
capacity (kArms)
Susol
TD
&
TS
TD100N
50
TD100H
85
TD160N
50
TD160H
85
TS100N
50
TS100H
85
TS160N
50
TS160H
85
TS250N
50
TS250H
85
TS400N
65
TS400H
85
TS630N
65
TS630H
85
TS800N
65
TS800H
85
TS1000N
50
TS1000H
70
TS1250N
50
TS1250H
70
75
70
200
150
55
75
55
75
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
150
70
150
150
70
150
150
70
150
150
70
150
150
70
150
150
70
150
150
70
150
150
70
150
150
70
150
150
A-7-32
Technical information
Protective coordination
Protection discrimination table, Discrimination
Complementary technical information
Main: Susol MCCB 100~800AF
Branch
breaker
Main breaker
Trip unitsThermal
magnetic
AB125
AB203 S
A-7-33
Trip unitsThermal
magnetic
TD160N/H/L
AB100 N
TD100N/H/L
Rating (A)
~10
15
20
30
40
50
60
75
100
15
20
30
40
50
60
75
100
125
15
20
30
40
50
60
75
100
125
100
125
150
175
200
225
250
100
125
150
175
200
225
250
100
125
150
175
200
225
250
20
25
32
40
50
63
80
100
100
125
160
0.4
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.63
0.63
0.63
0.63
0.63
0.63
0.8
0.8
0.8
0.8
0.8
0.8
0.8
T
T
9
9
9
8
8
T
T
9
9
9
8
8
8
0.5
0.5
0.5
0.5
0.5
0.63
0.63
0.63
0.63
0.63
0.8
0.8
0.8
0.8
0.8
0.8
10
9
9
9
8
8
8
10
10
9
9
8
8
8
8
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.63
0.63
0.63
0.63
0.63
0.63
0.8
0.8
0.8
0.8
0.8
0.8
0.8
10
9
9
9
8
8
8
10
10
9
9
8
8
8
8
T
T
9
9
9
8
8
8
8
10
10
9
9
8
8
8
8
8
10
10
9
9
8
8
8
8
0.5
Technical information
TS100N/H/L
TS160N/H/L
TS250N/H/L
TS400N/H/L
TS630N/H/L
TS800N/H/L
50
63
80
100
100
125
160
125
160
200
250
300
400
500
630
800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
10
10
10
10
10
10
8
11
10
10
8
8
11
11
11
11
11
8
11
11
11
11
11
8
12.5
11
11
11
11
8
8
10
10
10
10
10
10
8
11
10
10
8
8
11
11
11
11
11
8
11
11
11
11
11
8
12.5
11
11
11
11
8
8
T
T
T
T
T
T
T
T
T
12.5
12.5
11
11
11
11
11
11
11
12.5
12.5
11
11
11
11
11
11
11
8
8
T
T
T
T
T
T
T
T
T
15
15
15
15
15
12.5
12.5
12.5
12.5
15
15
15
15
15
12.5
12.5
12.5
12.5
T
T
T
T
T
T
T
T
T
15
15
15
15
15
12.5
12.5
12.5
12.5
15
15
15
15
15
12.5
12.5
12.5
12.5
T
T
T
T
T
T
T
T
T
18
15
15
15
15
12.5
12.5
12.5
12.5
18
15
15
15
15
12.5
12.5
12.5
12.5
8
T
T
T
T
T
T
T
T
T
18
18
18
15
15
12.5
12.5
12.5
12.5
18
18
18
15
15
12.5
12.5
12.5
12.5
8
8
T
T
T
T
T
T
T
T
T
T
T
20
20
20
20
20
20
20
25
25
20
20
20
20
20
20
20
T
T
15
12.5
11
11
11
18
18
15
12.5
11
11
11
18
18
15
12.5
11
11
11
T
T
T
T
T
T
T
T
T
T
T
T
T
20
20
20
20
20
25
25
25
25
20
20
20
20
20
T
T
15
12.5
12.5
11
11
18
18
15
12.5
12.5
11
11
18
18
15
12.5
12.5
11
11
T
T
T
T
T
T
T
T
T
T
T
T
T
T
20
20
20
20
25
25
25
25
25
20
20
20
20
T
T
15
15
12.5
12.5
12.5
18
18
15
15
12.5
12.5
12.5
18
18
15
15
12.5
12.5
12.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
25
25
25
25
25
25
25
25
25
T
T
15
15
12.5
12.5
12.5
18
18
15
15
12.5
12.5
12.5
18
18
15
15
12.5
12.5
12.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
28
28
28
28
28
28
28
8
8
8
8
8
8
8
8
A-7-34
Technical information
Protective coordination
Protection discrimination table, Discrimination
Complementary technical information
Main: Susol TD 100/160
Branch
breaker
Main breaker
TD100N/H/L
TD160N/H/L
Rating (A)
16
20
25
32
40
50
63
80
100
100
125
160
0.4
0.5
0.5
0.5
0.63
0.8
20
0.5
0.5
0.63
0.8
25
0.5
0.5
0.63
0.8
0.5
0.63
0.8
40
0.63
0.8
50
0.63
0.8
0.8
1.25
16
32
N
63
80
1.6
100
0.5
0.5
0.63
0.8
20
0.5
0.5
0.63
0.8
25
0.5
0.5
0.63
0.8
0.5
16
0.5
0.63
0.8
40
0.63
0.8
50
0.63
32
TD100 H
63
80
Trip units100
Thermal
16
magnetic
20
2
2
1.25
1.6
0.5
0.63
0.8
0.5
0.63
0.8
0.5
0.5
0.63
0.8
0.5
0.63
0.8
40
0.63
0.8
50
0.63
0.8
0.8
63
2
2
0.5
32
L
2
2
0.5
25
0.5
0.8
0.8
80
1.25
100
1.6
100
1.6
125
1.25
160
TD160 H
100
1.6
125
1.25
160
L
100
1.6
125
1.25
160
A-7-35
Technical information
Protective coordination
Protection discrimination table, Discrimination
Complementary technical information
Main: Susol TS 100/160/250(Electronic)
Branch
breaker
Main breaker
TS100N/H/L
TS160N/H/L
Rating (A)
40
50
63
80
100
100
125
160
125
160
200
250
16
0.5
0.5
0.5
0.63
0.8
36
36
36
20
0.5
0.5
0.5
0.63
0.8
36
36
36
25
0.5
0.5
0.5
0.63
0.8
36
36
36
0.5
0.63
0.8
36
36
36
40
0.63
0.8
36
36
36
50
0.63
0.8
36
36
36
63
0.8
36
36
36
80
0.8
1.25
1.25
36
36
36
1.6
36
36
36
0.5
0.5
0.63
0.8
36
36
36
20
0.5
0.5
0.63
0.8
36
36
36
25
0.5
0.5
0.63
0.8
36
36
36
0.5
100
16
0.5
0.63
0.8
36
36
36
40
0.63
0.8
36
36
36
50
0.63
0.8
36
36
36
63
0.8
36
36
36
80
Trip units100
Thermal
16
magnetic
20
0.8
1.25
1.25
36
36
36
1.6
36
36
36
32
TD100 H
0.5
0.5
0.63
0.8
36
36
36
0.5
0.5
0.63
0.8
36
36
36
0.5
0.5
0.63
0.8
36
36
36
0.5
0.63
0.8
36
36
36
40
0.63
0.8
36
36
36
50
0.63
0.8
36
36
36
63
0.8
36
36
36
80
0.8
1.25
1.25
36
36
36
100
1.6
36
36
36
100
1.6
2.6
1.25
2.6
1.25
2.6
1.25
25
32
L
TS250N/H/L
32
N
0.5
1.25
125
160
100
TD160 H
1.6
1.25
125
160
100
L
125
160
1.6
1.25
A-7-36
Technical information
Protective coordination
Protection discrimination table, Discrimination
Complementary technical information
Main: Susol TS 400/630/800(Electronic)
Branch
breaker
TD100 H
TD160 H
A-7-37
Main breaker
TS400N/H/L
TS630N/H/L
TS800N/H/L
Rating (A)
300
400
500
630
800
16
20
25
32
40
50
63
80
100
16
20
25
32
40
50
63
80
Trip units100
Thermal
16
magnetic
20
25
32
40
50
63
80
100
100
125
160
100
125
160
100
125
160
Technical information
Protective coordination
Protection discrimination table, Discrimination
Complementary technical information
Main: Susol 1000/1250/1600
Branch
breaker
TD100 H
TD160 H
Main breaker
TS1000L
TS1000N/H
TS1250N/H
TS1600N/H
Rating (A)
800
1000
800
1000
1250
1600
16
20
25
32
40
50
63
80
100
16
20
25
32
40
50
63
80
Trip units100
Thermal
16
magnetic
20
25
32
40
50
63
80
100
100
125
160
100
125
160
100
125
160
A-7-38
Technical information
Protective coordination
Protection discrimination table, Discrimination
Complementary technical information
Main: Susol TS 100/160/250(Electronic)
Branch
breaker
Main breaker
TS100N/H/L
TS160N/H/L
Rating (A)
40
50
63
80
100
100
125
160
125
160
200
250
40
0.63
0.8
2.6
50
0.63
0.8
2.6
0.8
2.6
1.25
2.6
1.6
2.6
2.6
63
80
100
TS100 H
TS250N/H/L
40
0.63
50
0.63
63
0.8
0.8
2.6
0.8
2.6
5
5
80
1.25
2.6
100
1.6
2.6
40
0.63
0.8
2.6
50
0.63
0.8
2.6
0.8
2.6
80
1.25
2.6
100
1.6
2.6
100
1.6
2.6
125
Trip units160
Thermal
100
magnetic
TS160 H
125
1.25
1.25
2.6
1.25
2.6
1.25
63
5
1.6
1.25
160
L
100
1.6
125
1.25
160
125
N
1.25
2.5
2.5
160
200
250
125
TS250 H
1.25
2.5
2.5
160
200
250
125
160
200
250
A-7-39
1.25
2.5
2.5
Technical information
Protective coordination
Protection discrimination table, Discrimination
Complementary technical information
Main: Susol TS 400/630/800(Electronic)
Branch
breaker
TS100 H
Main breaker
TS400N/H/L
TS630N/H/L
TS800N/H/L
Rating (A)
300
400
500
630
800
40
50
63
80
100
40
50
63
80
100
40
50
63
80
100
100
125
Trip units160
Thermal
100
magnetic
TS160 H
125
160
100
125
160
125
N
160
200
250
125
TS250 H
160
200
250
125
160
200
250
A-7-40
Technical information
Protective coordination
Protection discrimination table, Discrimination
Complementary technical information
Main: TS1000/1250/1600
Branch
breaker
TS100 H
Main breaker
Branch: TS100/160/250
TS1000L
TS1000N/H
TS1250N/H
TS1600N/H
Rating (A)
800
1000
800
1000
1250
1600
40
50
63
80
100
40
50
63
80
100
40
50
63
80
100
100
125
Trip units160
Thermal
100
magnetic
TS160 H
125
160
100
125
160
125
160
200
250
125
160
200
250
125
160
200
250
TS250 H
A-7-41
Technical information
Protective coordination
Protection discrimination table, Discrimination
Complementary technical information
Main: Susol TS 400/630/800(Electronic)
Branch
breaker
N
TS400 H
L
N
TS630 H
L
N
TS800 H
L
Main breaker
TS400N/H/L
TS630N/H/L
TS800N/H/L
Rating (A)
300
400
300
400
300
400
300
400
Trip units- 500
Thermal 630
magnetic 500
630
500
630
800
800
800
500
630
800
8
8
8
8
8
8
8
T
10
T
10
T
10
10
10
10
10
10
10
8
8
8
8
L
N
TS800 H
L
N
TS1000 H
L
TS1000L
Main breaker
Rating (A)
Trip unitsElectronic
300
400
300
400
300
400
500
630
500
630
500
630
800
800
800
800
1000
800
1000
800
1000
TS1250N/H
TS1600N/H
1000
800
1000
1250
1600
18
18
18
18
30
30
12
18
18
18
18
30
30
12
12
12
12
12
12
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
25
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
25
25
25
25
50
50
12
12
T
T
25
50
A-7-42
Technical information
Protective coordination
Motor protection discrimination table
Main breaker
Branch
breaker
Trip unit
Rating (A)
TD100N/H/L
FMU
TD160N/H/L
FMU
TS100N/H/L
TS160N/H/L
TS250N/H/L
TS400N/H/L
TS630N/H/L
MTU
MTU
MTU
MTU
MTU
TS100N/H/L
ETS
TS160N/H/L
TS250N/H/L
TS400N/H/L
ETS
ETS
ETS
A-7-43
16
20
25
32
40
50
63
80
100
100
125
160
100
150
220
320
500
40
80
100
150
220
320
16
20
25
80
100
6.4
6.4
6.4
8
8
8
8
Technical information
TD160N/H/L
100
12.5
12.5
12.5
12.5
FMU
125
12.5
12.5
12.5
12.5
12.5
TS250N/H/L
TS100N/H/L
ATU
ETS
160
200
250
12.5
12.5
12.5
12.5
12.5
12.5
20
20
20
20
20
20
20
25
25
25
25
25
25
25
25
40
80
80
1
1
1
0.9
0.9
0.9
TS160N/H/L
TS250N/H/L
ETS
160
1.75
1.75
1.75
1.75
1.75
1.75
250
36
36
36
36
36
36
36
36
TS400N/H/L
TS630N/H/L
ETS/ETM
400
630
T
T
T
T
T
T
T
T
T
T
12.5
12.5
36
36
36
1.75
3.6
3.6
T
T
T
TS800N/H/L
ETS/ETM
630
800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
A-7-44
Technical information
Protective coordination
Type 2 Coordination according to IEC60947-4-1
MCCB
Performance: Ue=200/240V
MCCB
TD100
85kA
100kA
200kA
TS100
100kA
120kA
200kA
Motor
MC
MCCB
TOR
Contactor
kW
Type
Rating Ir (A)
Type
Type
0.37
1.8
TD100
16
MC-9
MT-32
1.6-2.5
0.55
2.75
TD100
16
MC-32
MT-32
2.5-4
0.75
3.5
TD100
16
MC-32
MT-32
2.5-4
1.1
4.4
TD100
16
MC-40
MT-63
4-6
1.5
6.1
TD100
16
MC-40
MT-63
5-8
2.2
8.7
TD100
16
MC-40
MT-63
9-13
11.5
TD100
16
MC-40
MT-63
9-13
3.7
13.5
TD100
16
MC-40
MT-63
12-18
14.5
TD100
16
MC-40
MT-63
12-18
5.5
20
TD100
20
MC-40
MT-63
16-22
7.5
27
TD100
32
MC-40
MT-63
24-36
32
TD100
32
MC-85
MT-95
28-40
10
35
TD100
40
MC-85
MT-95
28-40
11
39
TD100
40
MC-85
MT-95
34-50
15
52
TD100
63
MC-85
MT-95
45-65
18.5
64
80
MC-85
MT-95
54-75
80
MC-85
MT-95
63-85
100
MC-85
MT-95
70-95
TD100
TS100
22
75
TD100
TS100
25
85
TD100
TS100
A-7-45
Technical information
Protective coordination
Type 2 Coordination according to IEC60947-4-1
MCCB
Performance: Ue=380/415V
MCCB
TD100
50kA
85kA
150kA
TS100
50kA
85kA
150kA
Motor
MCCB
kW
0.37
1.03
0.55
1.6
0.75
1.1
2.6
1.5
3.5
2.2
6.6
3.7
4
MC
TOR
Contactor
Type
Rating Ir (A)
Type
Type
TD100
16
MC-9
MT-32
1-1.6
TD100
16
MC-9
MT-32
1-1.6
TD100
16
MC-9
MT-32
1.6-2.5
TD100
16
MC-32
MT-32
2.5-4
TD100
16
MC-32
MT-32
2.5-4
TD100
16
MC-40
MT-63
4-6
TD100
16
MC-40
MT-63
5-8
7.7
TD100
16
MC-40
MT-63
6-9
8.5
TD100
16
MC-40
MT-63
7-10
5.5
11.5
TD100
16
MC-40
MT-63
9-13
7.5
15.5
TD100
16
MC-40
MT-63
12-18
18.5
TD100
20
MC-40
MT-63
16-22
10
20
TD100
20
MC-40
MT-63
16-22
11
22
TD100
25
MC-40
MT-63
16-22
15
30
TD100
32
MC-85
MT-95
24-36
18.5
37
40
MC-85
MT-95
28-40
50
MC-85
MT-95
34-50
63
MC-85
MT-95
45-65
63
MC-85
MT-95
45-65
80
MC-85
MT-95
54-75
80
MC-85
MT-95
63-85
80
MC-85
MT-95
63-85
100
MC-85
MT-95
70-95
TD100
TS100
22
44
TD100
TS100
25
52
TD100
TS100
30
60
TD100
TS100
33
68
TD100
TS100
37
72
TD100
TS100
40
79
TD100
TS100
45
85
TD100
TS100
A-7-46
Technical information
Protective coordination
Type 2 Coordination according to IEC60947-4-1
MCCB
Performance: Ue=440V
MCCB
TD100
42kA
72kA
130kA
TS100
42kA
72kA
130kA
Motor
MCCB
MC
TOR
Contactor
kW
Type
Rating Ir (A)
Type
Type
0.37
0.99
TD100
16
MC-9
MT-32
0.63-1
0.55
1.36
TD100
16
MC-9
MT-32
1-1.6
0.75
1.68
TD100
16
MC-9
MT-32
1.6-2.5
1.1
2.37
TD100
16
MC-9
MT-32
1.6-2.5
1.5
3.06
TD100
16
MC-18
MT-32
2.5-4
2.2
4.42
TD100
16
MC-25
MT-32
4-6
5.57
TD100
16
MC-25
MT-32
4-6
3.7
7.1
TD100
16
MC-32
MT-32
5-8
7.9
TD100
16
MC-32
MT-32
6-9
5.5
10.4
TD100
20
MC-32
MT-32
9-13
7.5
13.7
TD100
20
MC-32
MT-32
12-18
16.9
TD100
20
MC-40
MT-63
12-18
11
20.1
TD100
25
MC-40
MT-63
16-22
15
26.5
TD100
32
MC-40
MT-63
24-36
40
MC-50
MT-63
28-40
40
MC-50
MT-63
34-50
50
MC-50
MT-63
34-50
63
MC-65
MT-95
45-65
63
MC-65
MT-95
45-65
80
MC-65
MT-95
54-75
80
MC-85
MT-95
54-75
100
MC-85
MT-95
63-85
18.5
32.8
TD100
TS100
22
39
TD100
TS100
25
45.3
TD100
TS100
30
51.5
TD100
TS100
33
58
TD100
TS100
37
64
TD100
TS100
40
67
TD100
TS100
45
76
TD100
TS100
A-7-47
Technical information
Protective coordination
Type 2 Coordination according to IEC60947-4-1
MCCB
Performance: Ue=480/500V
MCCB
TD100
30kA
50kA
65kA
TS100
42kA
65kA
85kA
Motor
MCCB
kW
0.37
0.55
0.75
MC
TOR
Contactor
Type
Rating Ir (A)
Type
Type
TD100
16
MC-9
MT-32
0.63-1
1.21
TD100
16
MC-9
MT-32
1-1.6
1.5
TD100
16
MC-9
MT-32
1-1.6
1.1
TD100
16
MC-9
MT-32
1.6-2.5
1.5
2.6
TD100
16
MC-32
MT-32
2.5-4
2.2
3.8
TD100
16
MC-32
MT-32
2.5-4
TD100
16
MC-40
MT-63
4-6
3.7
5.9
TD100
16
MC-40
MT-63
5-8
6.5
TD100
16
MC-40
MT-63
5-8
5.5
TD100
16
MC-40
MT-63
7-10
7.5
12
TD100
16
MC-40
MT-63
9-13
13.9
TD100
16
MC-40
MT-63
12-18
11
15
TD100
16
MC-85
MT-95
12-18
15
18.4
TD100
20
MC-85
MT-95
16-22
18.5
23
TD100
25
MC-85
MT-95
18-25
22
28.5
TD100
32
MC-85
MT-95
24-36
40
MC-85
MT-95
28-40
40
MC-85
MT-95
34-50
50
MC-85
MT-95
34-50
50
MC-85
MT-95
45-65
63
MC-85
MT-95
45-65
63
MC-85
MT-95
54-75
25
33
TD100
TS100
30
39.4
TD100
TS100
33
45
TD100
TS100
37
50
TD100
TS100
40
55
TD100
TS100
45
60
TD100
TS100
A-7-48
Technical information
Protective coordination
Type 2 Coordination according to IEC60947-4-1
MCCB
Performance: Ue=660/690V
N
TD100
42kA
72kA
130kA
TS100
42kA
72kA
130kA
kW
Type
Rating Ir (A)
Type
Type
0.37
0.6
TD100
16
MC-9
MT-32
0.4~0.63
0.55
0.9
TD100
16
MC-9
MT-32
0.63-1
0.75
1.1
TD100
16
MC-9
MT-32
1-1.6
1.1
1.5
TD100
16
MC-9
MT-32
1-1.6
1.5
TD100
16
MC-32
MT-32
1.6-2.5
2.2
2.8
TD100
16
MC-32
MT-32
2.5-4
Motor
MCCB
TOR
Contactor
3.8
TD100
16
MC-32
MT-32
2.5-4
3.7
4.4
TD100
16
MC-40
MT-63
4-6
4.9
TD100
16
MC-40
MT-63
4-6
5.5
6.6
TD100
16
MC-40
MT-63
5-8
7.5
8.9
TD100
16
MC-40
MT-63
7-10
10.6
TD100
16
MC-85
MT-95
9-13
11
11.5
TD100
16
MC-85
MT-95
9-13
15
14
TD100
16
MC-85
MT-95
12-18
18.5
17.3
TD100
20
MC-85
MT-95
16-22
22
21.3
TD100
25
MC-85
MT-95
18-25
25
25.4
TD100
32
MC-85
MT-95
24-36
30
30.3
TD100
32
MC-85
MT-95
24-36
33
34.6
40
MC-85
MT-95
28-40
40
MC-85
MT-95
34-50
50
MC-85
MT-95
34-50
50
MC-85
MT-95
34-50
TD100
TS100
37
39
TD100
TS100
40
42
TD100
TS100
45
44
TD100
TS100
A-7-49
MC
MCCB
Technical information
Protective coordination
Type 2 Coordination according to IEC60947-4-1]
440V - N type
Current[A]
440V
MCCB
Type
Contactor
Rating
Type
[A]
Setting
Short circuit
breaking capacity
range [A]
Ir[kA]
Iq[kA]
1.1
2.37
TD100N
16
MC-12b
MT-32
2.5~4
50
1.5
3.06
TD100N
16
MC-18b
MT-32
2.5~4
50
2.2
4.42
TD100N
16
MC-22b
MT-32
4~6
50
5.77
TD100N
16
MC-22b
MT-32
5~8
50
7.90
TD100N
16
MC-32a
MT-32
6~9
50
5.5
10.40
TD100N
16
MC-32a
MT-32
9~13
50
7.5
13.70
TD100N
20
MC-32a
MT-32
12~18
50
11
20.10
TD100N
32
MC-40a
MT-32
18~25
50
15
26.50
TD100N
40
MC-40a
MT-32
22~32
50
18.5
32.80
TS100N
40
MC-50a
MT-63
28~40
50
22
39.00
TS100N
50
MC-50a
MT-63
34~50
50
30
51.50
TS100N
63
MC-65a
MT-63
45~65
50
37
64.00
TS100N
80
MC-75a
MT-95
54~75
50
45
76.00
TS100N
100
MC-85a
MT-95
63~85
50
55
90.00
TS100N
100
MC-100a
MT-95
70~95
50
59
97.00
TS160N
100
MC-130a
MT-150
80~105
50
75
125
TS160N
160
MC-150a
MT-150
110~150
10
50
90
146
TS160N
160
MC-185a
MT-225
120~185
10
50
110
178
TS250N
200
MC-185a
MT-225
160~240
10
50
132
215
TS250N
250
MC-225a
MT-225
160~240
10
65
160
256
TS400N
300
MC-400a
MT-400
200~330
18
65
200
330
TS400N
400
MC-400a
MT-400
260~400
18
65
220
353
TS400N
400
MC-400a
MT-400
260~400
18
65
250
401
TS630N
500
MC-630a
MT-800
260~400
18
65
300
481
TS630N
500
MC-630a
MT-800
400~630
18
65
A-7-50
Technical information
Protective coordination
Type 2 Coordination according to IEC60947-4-1]
440V - H type
A-7-51
Current[A]
440V
MCCB
Type
Contactor
Rating
Type
[A]
Setting
Short circuit
breaking capacity
range [A]
Ir[kA]
Iq[kA]
1.1
2.37
TD100H
16
MC-12b
MT-32
2.5~4
50
1.5
3.06
TD100H
16
MC-18b
MT-32
2.5~4
50
2.2
4.42
TD100H
16
MC-22b
MT-32
4~6
50
5.77
TD100H
16
MC-22b
MT-32
5~8
50
7.90
TD100H
16
MC-32a
MT-32
6~9
50
5.5
10.40
TD100H
16
MC-32a
MT-32
9~13
50
7.5
13.70
TD100H
20
MC-32a
MT-32
12~18
70
11
20.10
TD100H
32
MC-40a
MT-32
18~25
70
15
26.50
TD100H
40
MC-40a
MT-32
22~32
70
18.5
32.80
TS100H
40
MC-50a
MT-63
28~40
70
22
39.00
TS100H
50
MC-50a
MT-63
34~50
70
30
51.50
TS100H
63
MC-65a
MT-63
45~65
70
37
64.00
TS100H
80
MC-75a
MT-95
54~75
70
45
76.00
TS100H
100
MC-85a
MT-95
63~85
70
55
90.00
TS100H
100
MC-100a
MT-95
70~95
70
59
97.00
TS160H
100
MC-130a
MT-150
80~105
70
75
125
TS160H
160
MC-150a
MT-150
110~150
10
70
90
146
TS160H
160
MC-185a
MT-225
120~185
10
70
110
178
TS250H
200
MC-185a
MT-225
160~240
10
70
132
215
TS250H
250
MC-225a
MT-225
160~240
10
70
160
256
TS400H
300
MC-400a
MT-400
200~330
18
85
200
330
TS400H
400
MC-400a
MT-400
260~400
18
85
220
353
TS400H
400
MC-400a
MT-400
260~400
18
85
250
401
TS630H
500
MC-630a
MT-800
260~400
18
85
300
481
TS630H
500
MC-630a
MT-800
400~630
18
100
Technical information
Protective coordination
Type 2 Coordination according to IEC60947-4-1]
440V - L type
Current[A]
440V
MCCB
Type
Contactor
Rating
Type
Setting
Short circuit
breaking capacity
Ir[kA]
Iq[kA]
1.1
2.37
TD100L
16
MC-12b
MT-32
2.5~4
50
1.5
3.06
TD100L
16
MC-18b
MT-32
2.5~4
50
2.2
4.42
TD100L
16
MC-22b
MT-32
4~6
50
5.77
TD100L
16
MC-22b
MT-32
5~8
50
7.90
TD100L
16
MC-32a
MT-32
6~9
50
5.5
10.40
TD100L
16
MC-32a
MT-32
9~13
50
7.5
13.70
TD100L
20
MC-32a
MT-32
12~18
100
11
20.10
TD100L
32
MC-40a
MT-32
18~25
100
15
26.50
TD100L
40
MC-40a
MT-32
22~32
100
18.5
32.80
TS100L
40
MC-50a
MT-63
28~40
130
22
39.00
TS100L
50
MC-50a
MT-63
34~50
130
30
51.50
TS100L
63
MC-65a
MT-63
45~65
130
37
64.00
TS100L
80
MC-75a
MT-95
54~75
130
45
76.00
TS100L
100
MC-85a
MT-95
63~85
130
55
90.00
TS100L
100
MC-100a
MT-95
70~95
130
59
97.00
TS160L
100
MC-130a
MT-150
80~105
130
75
125
TS160L
160
MC-150a
MT-150
110~150
10
130
[A]
range [A]
90
146
TS160L
160
MC-185a
MT-225
120~185
10
130
110
178
TS250L
200
MC-185a
MT-225
160~240
10
130
132
215
TS250L
250
MC-225a
MT-225
160~240
10
130
160
256
TS400L
300
MC-400a
MT-400
200~330
18
130
200
330
TS400L
400
MC-400a
MT-400
260~400
18
130
220
353
TS400L
400
MC-400a
MT-400
260~400
18
130
250
401
TS630L
500
MC-630a
MT-800
260~400
18
130
300
481
TS630L
500
MC-630a
MT-800
400~630
18
130
A-7-52
Technical information
How to calculate short-circuit current value
Various short-circuit
The purpose of calculating short circuit values
Selection of circuit breakers, fuse.
Adjusting metering devices
Consideration for mechanical resistance
Consideration for thermal resistance
Various value of short-circuit current should be
applied to the tests for upper factors.
Symmetrical current for AC and asymmetrical
current for DC are used for classifying short
circuit current.
Their differences should be essentially
considered in the basic step of making network
plan.
Symmetrical short-circuit current real value
Short-circuit current is composed of AC and
DC as it shows on <Fig.1>. The short-circuit
which indicates the real value of AC is called
as symmetrical short-current real value, l
(rms)sym. This current is the essential factor of
selecting MCCB, ACB, fuse.
AC+ DC
(asymmetrical short-circuit current)
DC
AC
A-7-53
Technical information
How to calculate short-circuit current value
Various short-circuit
c. Reactance of motor
Motor works as generator and supply short
circuit current in the condition of an accident
circuit such as <Fig.2>.
Generation factor of firm motor should be
considered in a low voltage circuit where a
circuit breaker operates quickly and in a high
voltage circuit for the selection of fuse.
Reactance of motor can be regarded in the
range of 25% normally.
Interphase
voltage
Between RS
400V 30kW
Short-circuit
Between ST
Between TR
R current
S current
T current
d. Distribution impedance
Impedance of cable and busduct do control
short-circuit remarkably in low voltage
network. Refer to <Table.5>, <Table.6>.
e. Others
MCCB, ACB CT are equipments for the
network of low voltage.
The impedance of these equipment which is
calculated from short-circuit current value
should be considered.
Generally, the impedance of those equipment
is that of rated current (normal condition), if
operators apply that impedance value,
bigger reactance value may be applied to
calculated short-circuit current value.
A-7-54
Technical information
How to calculate short-circuit current value
With percent impedance
Ohm formula (), percent impedance formula
(%), unit formula (per unit) can be applied to
calculate short-circuit current value.
]
Ohm formula [
Short-circuit current value is calculated by
converting into ohm value []
Percent impedance formula (%) Each
impedance is converted into the impedance
of base value and base voltage.
And the required amount for electric demand
should be shown as percent unit.
And apply that value in ohm formula.
Unit formula
The base value equals 1.0. and all value of
network shows in the way of decimal system.
Applying any of upper calculation formulas to
achieve short-circuit current value, it shows
equal value. To select a certain formula for
doing it, operator can select one of those
formula which is proper to oneself. Below is
percent impedance formula.
Finding base value
The rated current of transformer shall be the
base value.
Base capacity PB= PTkVA
Base voltage VB= VTV
Base current IB= IT =
PT
3
10A
3VT
VB2
VT2
=
3
PB10 PT103
ZC
ZB
(% converting formula)
A-7-55
Technical information
How to calculate short-circuit current value
3
2
Calculating impedance
Calculate impedance as <Fig.4 (b)> in
impedance map < Fig.4 (a)>
%Z = %R + j %X
%Z =
(%R)2+ (%X)2
P B10 3
100
3VB%Z
IB 100
A
%Z
A-7-56
Technical information
How to calculate short-circuit current value
With a simple formula
For its special cases, calculating exact value
should be needed, in the other hand, for the
practical use, we recommend simple formula.
Finding a base value
It shall be the rated current of transformer.
PB= PT [kVA]
VB= VT [V]
IB= IT [A]
VTB []
ZB=
PT103
Ref 1) Calculation in the random voltage E Voltage line
which is mostly close to E shall be selected to
calculate it .
i.e. in case of 220V, (200V line value)200/220
Ref 2) Calculation for a certain impedance Zt (%)
Impedance line which is mostly close to Zt (%)
shall be selected to calculate it.
i.e. 420V, Zt= 4.5%
%Z=4% Line value (or 5% line) 4 (or 5)/4.5
Ref 3) When the value is out of lines or over 200VA or
below 100kA, multiply 10 times to the calculated
values.
<Fig.7> Transformer capacity and short-circuit current
<Fig.6> Base value
%X1 =
IB
(%RT)2+ (%X1+%XT)2
100
A
PB
100 [%]
Q103
A-7-57
IB
100
A
%X1+%XT
Technical information
How to calculate short-circuit current value
1 phase short-circuit
(Each current)=
3
3 phases short-circuit current
2
(or
)
General busduct
<Fig.9> Decreasing coefficient of short-circuit
current by reactance: d
Busduct
Ratings
(A)
Material
Cu
Size [mm]
[/m]
200
325
400
640
600
650
800
675
1000
6100
1200
6125
1500
6150
2500
25015000
50011000
100115000
1500125000
25000
Variables
Maximum
asymmetrical
real value
3 phases
short-circuit
asymmetrical
current
average value
Maximum
asymmetrical
instantaneous
value
1.0
1.03
1.13
1.18
1.25
1.33
1.0
1.02
1.07
1.09
1.13
1.17
1.48
1.64
1.94
2.05
2.17
2.29
A-7-58
Technical information
How to calculate short-circuit current value
Calculation example
Calculation1) Short-circuit current value will be achieved by simple formula and percent impedance
formula for <Fig.13>
<Fig.13>
750
100= 0.075%
1000103
b. Impedance of transformer
%RT= 1.4%
%XT= 4.8%
c. 1Tr impedance
%RT1 = 1.15750
20
1.68750
%XT1 =
20
1
= 21.6%
2
1
= 31.5%
2
d. Reactance of transformer
750
1201.5
750
%Xm2 =
1401.5
750
%Xm3 =
1001.5
750
%Xm4 =
1151.5
%Xm1 =
A-7-59
25= 104%
25= 89%
25= 125%
25= 108.7%
e. Impedance of cable
Converting impedance of whole metal
tube
[2100mm2 10m]
%RC1= 0.0001810 1 100= 0.38%
0.237
2
1
0.0001310
%XC1=
100= 0.27%
0.237
2
[125mm2 20m]
%RC2= 0.0001420 100= 1.18%
0.237
0.0001320
%XC2=
100= 1.09%
0.237
[250mm2 50m]
%RC3= 0.0000750 100= 1.47%
0.237
0.0001350
%XC3=
100= 2.74%
0.237
[14mm2 30m]
%RC4= 0.0001330 100= 16.45%
0.237
0.0001530
%XC4=
100= 1.88%
0.237
Technical information
How to calculate short-circuit current value
Unlimited bus
3
IF2 (rms)1sym= 7989
= 6919
A
2
39.06
= 0.72
cos2=
54.2
<Fig.14>
Calculating impedance
Calculate it in serial/parallel type formula
a. Fault point F1
b. Fault point F2
713
4= 3920A
3420
%Z1=
(2.57)2+ (5.53)2
= 6.1[%]
%Z2=
(39.06)2+ (37.55)2
= 54.2[%]
A-7-60
Technical information
How to calculate short-circuit current value
Calculation example
(5) Decreasing short-circuit current for cable
a. At point F1
2100mm2 10m
2100mm2 10m= 100mm2 5m
IA 2024420
=
= 29.1
10420
10E
Coefficient b= 0.935
Short-circuit current value at point C
Ic (rms)sym= 0.93524420= 22850A
125mm2 20m
IC
2022850
=
= 108.9
10420
10E
IF1 (rms) sym= 0.785244850= 17940A
b. At point F1
14mm2 30m
IC 3024420
=
= 174.4
10420
10E
Coefficient b= 0.249
ID (rms)3sym= 0.2424420= 6080A
Decreasing by the reactance (1Tr)dp
Convert the value of %X of 1Tr to
base capacity
XD= 7502/20= 75%
Impedance of primary part at 1Tr
XA =
IB
1031
100 =
100[%]
6080
ID
A-7-61
3
= 7076A
2
= 1.13
= 1.94
IF21 (rms)asym= 1.137076= 7945A
IF21max= 1.947076= 13727A
<Table.2> Comparison of short-circuit
Fault point
Symmetrical
short-circuit
current real
value
3 phases
average
asymmetrical
current real
value
Maximum
asymmetrical
current real
value
Percent impedance
calculation value
Simple formula
calculation value
Percent impedance
F1
F2
16900A 6919A
17940A 7076A
106% 102%
17407A
20272A
116%
calculation value
Simple formula
calculation value
Percent impedance
calculation value
Simple formula
calculation value
17745A 6919A
22425A 7995A
126%
115%
Technical information
How to calculate short-circuit current value
A
Z2=0.01%(1000kVA)
Tr2 500kVA 6.6/3.3kV
Z3=4%
tot
= 0.25+0.01+8
= 8.26%
B
M 100kW M 200kW
Tr2 100kVA 3.3kV/220V
Z4=2.5%
20kWu=8.5%
cos=0.8
1000kVA
Z5=1.0%
1000kVA
Z5=1.0%
M
<Fig.16>
500
kVA
1000
36.6
kV
1000
Rated current InB at point B
InB=
100
kVA
1000
33.3
kV
1000
InC=
1000kVA1000100
= 2118A
33.3kV10008.26
Breaking capacity of breaker [MVA]
MVA= 3 short-circuit current [kA]
line to line voltage[kV]
ISB=
= 43.7
A
= 17.5
A
20
kW
1000
3220
V
0.850.8
= 77.2
A
1
= 32.58%
1
1
1
33.26 + 2001 + 8001
1000
kVA1000100
= 8055A
3220V32.58%
Incoming 25%
Calculation formula
Rated current In =
Z=0.25(%)
b) Short-circuit ISA
ISA=
1000kVA1000100
36.6kV10000.25%
Transformer capacity
3Rated voltage
Short-circuit current Is =
Transformer capacity100
3Rated voltage%Z
= 34990A
A-7-62
Technical information
How to calculate short-circuit current value
Combination of transformer and impedance
<Table. 3> Combination of transformer and impedance
Transformer
3 phases transformer
Impedance
6.3kV/210V Oil Tr. 6.3kV/210V Mold Tr. 20kV/420V Mold Tr. 20kV/420V Oil Tr.
Transformer capacity (VA) ZT[%] RT[%] XT[%] ZT[%] RT[%] XT[%] ZT[%] RT[%] XT[%] ZT[%] RT[%] XT[%]
20
2.19 1.94 1.03
30
2.45 1.92 1.53 4.7
2.27 4.12
50
2.47 1.59 1.89 4.7
1.94 4.28
75
2.35 1.67 1.66 4.4
1.56 4.11
100
2.54 1.65 1.96 4.6
1.5 4.24
150
2.64 1.64 2.07 4.2
1.29
4.0
200
2.8 1.59 2.31 4.5
1.17 4.35
300
3.26 1.46 2.92 4.5
1.2 4.33
500
3.61 1.33 3.36 4.7
0.08 4.69 5.0
1.56 4.76
6.0
1.0 5.92
750
4.2 1.55
3.9 6.0
0.8 5.95 5.0
1.40 4.80
6.0
0.9 5.93
1000
5.0 1.35 4.82 7.0
0.7 6.96 5.0
1.26 4.84
6.0
0.8 5.95
1500
5.1 1.22 4.95 7.0
0.6 6.97 5.5
1.2 5.37
7.0 0.75 6.96
2000
5.0
1.2 4.85 7.5
0.65 7.47 5.5
1.1 5.39
7.0
0.7 6.96
A-7-63
1 phase transformer
6.3kV/210V Oil Tr.
2.5
2.37
2.57
2.18
2.05
2.27
2.48
3.39
3.15
2.23
4.19
2.07
1.84
1.76
1.58
1.47
1.46
1.49
1.31
1.31
1.28
1.09
1.40
1.49
1.87
1.50
1.42
1.74
1.98
3.13
2.87
2.96
4.03
14.9
14.0
14.8
13.6
11.0
8.87
7.70
5.75
5.08
5.05
4.03
4.55
4.29
3.26
2.72
2.33
2.04
1.90
14.9
14.0
14.8
13.6
11.0
8.85
7.68
5.69
4.97
4.92
3.93
4.50
4.22
3.18
2.81
2.18
1.82
1.60
0.268
0.503
0.523
0.494
0.558
0.562
0.571
0.619
1.05
1.16
0.904
0.637
0.768
0.725
0.775
0.823
0.937
1.02
Insulator
wiring in
building
0.00031
0.00026
0.00022
Resistance
()
/
cable
1meter
0.0089
0.0056
0.0022
0.0033
0.0023
0.0013
0.00082
0.00062
0.00048
0.00037
0.00030
0.00023
0.00018
0.00014
0.00012
0.00009
0.00007
0.00005
Technical information
How to calculate short-circuit current value
Various short-circuit
<Table.6> Impedance sample of bus and busduct (50Hz)
[10-4/m]
Ampere
rating
(A)
600
1.257
0.323
1.297
1.385
0.387
1.438
800
0.848
0.235
0.879
0.851
0.282
0.896
1000
0.641
0.185
0.667
0.645
0.222
0.682
1200
0.518
0.152
0.540
0.523
0.183
0.554
1350
0.436
0.129
0.454
0.443
0.155
0.469
1500
0.378
0.113
0.394
0.386
0.135
0.409
1600
0.360
0.107
0.375
0.367
0.128
0.389
2000
0.286
0.084
0.298
0.293
0.101
0.310
2500
0.218
0.065
0.228
0.221
0.078
0.235
3000
0.180
0.054
0.188
0.184
0.064
0.195
3500
0.143
0.042
0.149
0.146
0.051
0.155
4000
0.126
0.038
0.131
0.129
0.045
0.136
4500
0.120
0.036
0.125
0.122
0.043
0.130
5000
0.095
0.028
0.099
0.098
0.034
0.103
50Hz
60Hz
[10-4/m]
Ampere
rating
(A)
600
0.974
0.380
1.045
0.977
0.456
1.078
800
0.784
0.323
0.848
0.789
0.387
0.879
1000
0.530
0.235
0.580
0.536
0.282
0.606
1200
0.405
0.185
0.445
0.412
0.222
0.468
1350
0.331
0.152
0.364
0.338
0.183
0.384
1500
0.331
0.152
0.364
0.338
0.183
0.384
1600
0.282
0.129
0.311
0.289
0.155
0.328
2000
0.235
0.107
0.259
0.241
0.128
0.273
2500
0.166
0.076
0.182
0.169
0.091
0.192
3000
0.141
0.065
0.155
0.144
0.078
0.164
3500
0.122
0.056
0.135
0.127
0.068
0.143
4000
0.110
0.051
0.121
0.113
0.061
0.126
4500
0.094
0.043
0.104
0.096
0.052
0.109
5000
0.082
0.038
0.091
0.084
0.045
0.096
5500
0.078
0.035
0.086
0.080
0.043
0.091
6500
0.068
0.028
0.074
0.071
0.031
0.077
50Hz
60Hz
A-7-64
Technical information
How to calculate short-circuit current value
Calculation example
Using a certain graph, you can find and
calculate the short-circuit current value which is
at one position of network. No matter the
condition of network is different, you can do the
calculation through adjusting variables.
Graph note
P coordinatesTransformer capacity (kVA)
Is 1 coordinatesShort-circuit current value
(kA)
Is 2 coordinatesShort-circuit current value
affected cable condition (kA)
Line - % impedance of transformer (%)
Line - Length of cable (m)
Line - Square mm of cable (mm2)
Line - Is2 (kA)
Remark) line shows the length of hard vinyl cable (600V IV)
Remark
1. Its not considered the transformer contribution.
Multiply 4 times the rated current of
transformer in cases.
2. The real short-circuit current value is littler
lower that its calculated value by the way we
suggest because we take the rated voltage
as AC200V, 400V. So the current value
should be calculated in the consideration of
stability
3. The calculated value is symmetrical real
value.
A-7-65
Memo
A-7-66
Technical information
How to calculate short-circuit current value
Calculation graph
(1) Short-circuit current value at point A (ISA)
At P coordinates, find (f) which is the point which is to match transformer capacity 500kVA
and A line. Then move (f) to Is1 direction and finally find (g).
ISA= 29kVA (g)
(2) Short-circuit current value at point B (ISB)
Find value h of B line (20mm) at g (= 29kA) of Is1 coordinates
Move h parallely to the direction of Is1, and find value I at the cross point with C line (200mm)
Move I parallely to the direction of Is2, and find value j at the cross point with D line (g= 29kA)
ISB= 19kA (k)
B length of cable
A-7-67
Technical information
A-7-68
Certifications
Type
Cerficate
Approvals
Safety certi
IEC
UL
cUL
GB
Gosstandart
CE
Europe
UL
U.S.A
cUL
U.S.A
CCC
China
GOST
Russia
Certificates
KEMA
Mark
and
name
Type
MCCB
Susol
MCCB
Susol UL
Korea
TE100S
TE100N
TD100N
TD100H
TD100L
TD160N
TD160H
TD160L
TS100N
TS100H
TS100L
TS160N
TS160H
TS160L
TS250N
TS250H
TS250L
TS400N
TS400H
TS400L
TS630N
TS630H
TS630L
TS800N
TS800H
TS800L
TS100 ETS
TS160 ETS
TS250 ETS
TS400 ETS
TS400 ETM
TS630 ETS
TS630 ETM
TS800 ETS
TS800 ETM
TS1000N
TS1250N
TS1600N
TS1000H
TS1250H
TS1600H
TS1000L
TD125NU
TD125HU
TS250NU
TS250HU
TS400NU
TS400NU
TS800NU
TS800HU
Note) : Completion
A-7-69
KEMA
Netherlands
Certifications
Approvals
Type
Mark
and
name
Type
TD
100AF
TD
160AF
TS
100AF
TS
160AF
TD100E
TD100S
TD100P
TD100N FTU
TD100N FMU
TD100H FTU
TD100H FMU
TD100L FTU
TD100L FMU
TD160E
TD160S
TD160P
TD160N FTU
TD160N FMU
TD160H FTU
TD160H FMU
TD160L FTU
TD160L FMU
TS100E
TS100E ETS
TS100S
TS100S ETS
TS100P
TS100P ETS
TS100N FTU
TS100N FMU
TS100N ETS
TS100H FTU
TS100H FMU
TS100H ETS
TS100L FTU
TS100L FMU
TS100L ETS
TS160E
TS160E ETS
TS160S
TS160S ETS
TS160P
TS160P ETS
TS160N FTU
TS160N FMU
TS160N ATU
TS160N ETS
TS160H FTU
TS160H FMU
TS160H ATU
TS160H ETS
TS160L FTU
TS160L FMU
TS160L ATU
TS160L ETS
1867
KR
Korea
LR
U.K
BV
France
ABS
U.S.A
GL
Germany
DNV
Norway
RINA
Italy
Note) : Completion
A-7-70
Marine certifications
Approvals
Type
Mark
and
name
Type
TS
250AF
TS
400AF
TS
630AF
TS250E
TS250E ETS
TS250S
TS250S ETS
TS250P
TS250P ETS
TS250N FTU
TS250N FMU
TS250N ATU
TS250N ETS
TS250H FTU
TS250H FMU
TS250H ATU
TS250H ETS
TS250L FTU
TS250L FMU
TS250L ATU
TS250L ETS
TS400E
TS400E ETS
TS400E ETM
TS400S
TS400S ETS
TS400S ETM
TS400P
TS400P ETS
TS400P ETM
TS400N FTU
TS400N FMU
TS400N ATU
TS400N ETS
TS400N ETM
TS400H FTU
TS400H FMU
TS400H ATU
TS400H ETS
TS400H ETM
TS400L FTU
TS400L FMU
TS400L ATU
TS400L ETS
TS400L ETM
TS630E
TS630E ETS
TS630E ETM
TS630S
TS630S ETS
TS630S ETM
TS630P
TS630P ETS
TS630P ETM
Note) : Completion
A-7-71
1867
KR
Korea
LR
U.K
BV
France
ABS
U.S.A
GL
Germany
DNV
Norway
RINA
Italy
Certifications
Approvals
Type
Mark
and
name
Type
TS
630AF
TS
800AF
TS630N FTU
TS630N FMU
TS630N ATU
TS630N ETS
TS630N ETM
TS630H FTU
TS630H FMU
TS630H ATU
TS630H ETS
TS630H ETM
TS630L FTU
TS630L FMU
TS630L ATU
TS630L ETS
TS630L ETM
TS800E
TS800E ETS
TS800E ETM
TS800S
TS800S ETS
TS800S ETM
TS800P
TS800P ETS
TS800P ETM
TS800N FTU
TS800N FMU
TS800N ATU
TS800N ETS
TS800N ETM
TS800H FTU
TS800H FMU
TS800H ATU
TS800H ETS
TS800H ETM
TS800L FTU
TS800L FMU
TS800L ATU
TS800L ETS
TS800L ETM
1867
KR
Korea
LR
U.K
BV
France
ABS
U.S.A
GL
Germany
DNV
Norway
RINA
Italy
Note) : Completion
A-7-72
Global Networks
Dalian, China
Dalian LSIS Co.,Ltd
Beijing, China
LSIS Beijing Office
Qingdao, China
LSIS Qingdao Office
Dubai, U.A.E.
LSIS (Middle East) FZE
Chengdu, China
LSIS Chengdu Office
Hanoi, Vietnam
LSIS-VINA Co.,Ltd
LSI Hanoi Office
Shanghai, China
LS Industrial Trading (Shanghai) Co., Ltd
LSIS Shanghai Office
Guangzhou, China
LSIS Guangzhou Office
For your safety, please read user's manual thoroughly before operating.
Contact the nearest authorized service facility for examination, repair, or adjustment.
Please contact a qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions
Any maintenance and inspection shall be performed by the personnel having expertise concerned.
HEAD OFFICE
LS-ro 127 (Hogye-dong) dongan-gu Anyang-si
Gyeonggi-do Korea
Tel. (82-2)2034-4887, 4873, 4148
Fax. (82-2)2034-4648
www.lsis.biz
Global Network
LSIS (Middle East) FZE
Dubai, U.A.E.
Address: LOB 19 JAFZA VIEW TOWER Room 205, Jebel Ali Freezone P.O. Box 114216, Dubai, United Arab Emirates
Tel: 971-4-886 5360 Fax: 971-4-886-5361 e-mail: dhleef@lsis.biz
CHEONG-JU PLANT
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,
Cheong Ju, 361-720, Korea
2013. 06
Low voltage circuit breakers (E) 2006. 02/(15) 2013. 06 Printed in Korea STAFF