806 B 04/11 C
Data: November 2004
Supersedes: 806B 04/04 B
:DWHUFRROHGVFUHZFKLOOHUV
(&23/86
&RROLQJFDSDFLW\IURPN:WRN:
+]5HIULJHUDQW+)&D
Code requirements
All water cooled units are designed and manufactured in accordance with applicable selections of the following
which are equivalent to American Air-conditioning industry applicable codes:
Rating of chillers: EN 12055.
Construction of pressure vessel: TUV Standards (on request).
Electrical codes: IEC 204-1 CEI 44-5 Elect. & Safety Codes
Safety Codes: CEI-EN 602041 Codes.
Manufacturing Quality Stds: ISO 9001:2000.
Compressor Load
Building Load
tim e
Compressor Load
Building Load
Unmatched serviceability
Field serviceability has not been sacrificed. Inspection covers allows visual inspection of the main screw and
gaterotors.
Zero clearance fit between the two gaterotors and main screw rotor virtually eliminates leakage between
the high and low-pressure sides during compression. Special gaterotor material made from an advanced
composite, temperature stable material makes a zero clearance design possible.
The McPower air-cooled chiller is equipped with the most advanced means of refrigerant flow control
available. An electronic expansion valve coupled with the MicroTech II C Plus controller's control logic
provides excellent operating efficiencies both at full and part load operation.
Full factory testing of the unit with water hookups helps provides a trouble-free start-up. Extensive quality
control checks during testing means that each equipment protection and operating control is properly
adjusted and operates correctly before it leaves the factory. Factory-installed options minimize field
expenses and startup labor.
The rugged design of the single-screw compressor allows it to be tolerant of liquid slugging. McPower
screw chiller will start and operate under conditions that would often destroy other compressors.
Very low loading enhances the bearing and compressor reliability. Due to symmetrical compression
taking place on both sides of the main screw rotor, balanced forces result in the elimination of the large
radial force loads inherent in twin-screw compressors.
Integral to the basic design of the single-screw compressor, the main screw rotor shaft and the gaterotor
shafts cross at right angles in the compressor. The result is ample space to locate heavy duty bearings
and increase compressor reliability since no limitations are placed on bearing design as found in twinscrew compressors.
A
Screw
Gaterotor
Gaterotor
Single Screw Compressor
General characteristics
Structure
The chiller is equipped with brackets directly installed on heat exchangers. The evaporator and the suction piping
are appropriately insulated to prevent condensation. Unit is provided with lifting holes.
Screw compressors
The StargateTM single-screw compressor has a well balanced compression mechanism which cancels the screw
rotor load in both the radial and axial directions. Inherent to the basic single-screw compressor design is the
virtually load-free operation, that gives main bearing design life of 3-4 times greater than twin-screws, and
eliminates expensive and complicated thrust balancing schemes. The two exactly opposed gaterotors create two
exactly opposed compression cycles. Compression is made at the lower and upper parts of the screw rotor at the
same time, thus cancelling the radial loads. Also, both ends of the screw rotor are subjected to suction pressure
only, which cancels the axial loads and eliminates the huge thrust loads inherent in twin-screw compressors (see
images and drawings in this page).
Oil injection is used for these compressors in order to get high COP at high condensing pressure. The oil supplied
to the compressor performs three basic functions: oil for capacity control actuation, oil for bearing lubrication, oil for
sealing. The oil is injected via fixed ports in the casing around the rotor.
Compressors have an infinitely variable capacity control down to 25% of its total capacity. This control is made by
means of capacity slides controlled by microprocessors.
The compressor is furnished with an integrated high efficiency oil separator to maximise oil extraction.
The compressor is provided with a liquid injection circuit to reach high sealing and oil cooling.
Standard start is star-delta type; Soft start type is available (as option) in order to have lower inrush current in
almost all work conditions and to provide smooth, slow stepless acceleration and controlled slow deceleration
reducing mechanical and electrical stress for even greater compressor/motor life.
as HFC 407C
Evaporator
The units is supplied with new optimised counter-flow evaporator single refrigerant pass that allows a perfect oil
circulation and so a perfect oil return to the compressor. It is direct expansion with refrigerant inside the tubes and
water outside (shell side) with carbon steel tube sheets, with straight copper tubes that are spirally wound
internally for higher efficiencies, expanded on the tube plates. The external shell, is linked with an electrical heater
to prevent freezing up to -28 C ambient temperature, commanded by a thermostat and is covered with a closed
cell insulation material. Each evaporator has 1 or 2 circuits, one for each compressor and is manufactured in
accordance to PED approval. The evaporator water outlet connections are provided with Victaulic Kit.
Condensers
Condensers are shell and cleanable, through-tube type. The unit has indenpendent condensers, one per circuit.
Each condenser has a carbon steel and seamless, integrally finned high efficiency copper tubes, roll expanded
into heavy carbon steel tube sheets. Water heads are removable and include vent and drain plugs. Condensers
come complete with liquid shut-off valve, spring loaded relief valve.
Certifications
All the ECOPLUS units are CE marked (89/392). McQuay Italia obtained ISO 9001:2000.
Q = 35,83 X
P (kW)
T(C)
1
N
where:
Q = Minimum content of the plant expressed in litres
P = Cooling capacity of the plant expressed in kW
T = Entering/leaving water temperature difference of the evaporator expressed in C
N = Number of compressors.
This should be the minimum quantity of water through the chiller in each operating condition, also when
therminal hydronic units are switched off.
Therefore for a more accurate determination of the water quantity, it is advisable to contact the designer of the
plant.
Chillers enabled to work in partial failure condition thanks to the distributed multiprocessor logic system
Full routine operation at condition of:
Display of condensing-evaporating temperature and pressure, suction and discharge superheat temperature
for each circuit
Soft Load
Return Reset
System security
Phase monitor
Freeze protection
An evaporators flow controller input (stops the unit)
Remote on/off input.
Regulation type
Proportional + integral + derivative regulation on the input probe of the evaporator water leaving temperature.
MicroPlantTM:
Solution for: tele-maintenance and supervisory systems
MicroTech II C Plus can be monitored locally or via modem by MicroPlantTM supervision program, that runs on PC
systems under Windows 95 98.
MicroPlantTM allows:
Units ON / OFF
Rubber type antivibration mounts - Supplied separately, these are positioned under the base of the unit for
floor installation.
Sound proof cabinet - Made of sheet metal and internally insulated, the sound proof cabinet is around the
compressor/s to reach the best performance in noise reduction.
Heat Pump version Water to water heat pump reversible on the water circuit are suitable to produce hot water
for domestic and industrial applications.
Witness tests - The units are normally tested at the test bench prior to the shipment. On request, a second test
can be carried out, at customers presence, in accordance with the procedures indicated on the test form. (Not
available for units with Glycol mixtures).
Soft start Electronic starting device to reduce inrush current. An overload protection is included (no need of
compressors thermal relays).
Over / Under Voltage Phase monitor to control the minimum and maximum voltage value that the user can set.
Installation notes
Warning
Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and
regulations, and who are experienced with this type of equipment. Must be avoided the unit installation in places
that could be considered dangerous for all the maintenance operations.
Handling
The chiller is mounted on heavy wooden skids to protect the unit from accidental damage and to permit easy
handling and moving. It is recommended that all moving and handling be performed with the skids under the unit
when possible and that the skids not be removed until the unit is in the final location.
Spreader bars must be used to protect the control cabinet and the other areas of the chiller.
Location
A levelled and sufficiently strong floor is required. If necessary, additional structural members should be provided
to transfer the weight of the unit to the nearest beams.
Rubber-in-shear isolators can be furnished and field placed under each corner of the package. A rubber antiskid
pad should be used under isolators if hold-down bolts are not used. Vibration isolator in all water piping connected
to the chiller are recommended to avoid straining the piping and transmitting vibration and noise.
55
50
45
40
Please, refer
to the note to
operate chiller
in this area
35
30
25
20
-10
-8
-6
-4
-2
10
12
14
16
18
Note: the use of glycol is necessary for evaporator leaving water temperature below +3C
C
C
4
8
Cooling capacity
correction factor
Power input
corretion factor
COP
correction factor
0,0176
0,0440
0,0880
0,1320
1,000
0,978
0,957
0,938
1,000
0,986
0,974
0,962
1,000
0,992
0,983
0,975
Cooling capacity
correction factor
Power input
corretion factor
COP
correction factor
0,0440
0,0880
0,1320
1,000
0,990
0,981
1,000
1,018
1,036
1,000
0,973
0,945
-3
10
0,991
0,996
1,013
1,070
-8
20
0,982
0,992
1,040
1,129
-15
30
0,972
0,986
1,074
1,181
-23
40
0,961
0,976
1,121
1,263
-35
50
0,946
0,966
1,178
1,308
2
10
0,842
0,95
0
20
0,785
0,94
-2
20
0,725
0,92
-4
30
0,670
0,89
-6
30
0,613
0,87
-8
30
0,562
0,84
Nomenclature
Ecoplus 120 . 2 SE ST 134
Ecoplus
Water cooled
Screw chiller
050 146
Unit size
1
2
Nof compressors
SE
XE
Standard efficiency
High efficiency
ST
ME
LR
Standard version
Condenserless version
Version with liquid receiver
134
050.1
060.1
073.1
100.2
kW
kW
No.
No.
kg
%
165,5
42,1
1
1
50
25
201,2
50,7
1
1
50
25
252,8
64,9
1
1
50
25
333,9
84,3
2
2
100
12.5
No./l
bar
1 / 60
10,5
1 / 56
10,5
1 / 123
10,5
1 / 118
10.5
No./l
bar
1 / 13
10,5
1 / 15
10,5
1 / 15
10,5
2 / 26
10,5
kg
kg
mm
mm
mm
1393
1470
3435
920
1860
1401
1480
3435
920
1860
1503
1650
3435
920
1860
2687
2840
4280
860
1880
Note: (1) Nominal cooling capacity and power input are based on: 12/7 C entering/leaving evaporator water temperature;
30/35 C entering/leaving condenser water temperature.
110.2
120.2
133.2
146.2
kW
kW
No.
No.
kg
%
372,2
93,1
2
2
100
12,5
402,5
101,4
2
2
100
12,5
448,3
115,1
2
2
100
12.5
493,7
129,0
2
2
100
12.5
No./l
bar
1 / 113
10,5
1 / 113
10,5
1 / 173
10,5
1 / 168
10,5
No./l
bar
2 / 28
10,5
2 / 30
10,5
2 / 30
10,5
2 / 30
10,5
kg
kg
mm
mm
mm
2697
2850
4280
860
1880
2702
2860
4280
860
1880
2757
2970
4280
860
1880
2762
2970
4280
860
1880
Note: (1) Nominal cooling capacity and power input are based on: 12/7 C entering/leaving evaporator water temperature;
30/35 C entering/leaving condenser water temperature.
050.1
060.1
073.1
100.2
kW
kW
No.
No.
kg
%
186,4
39,7
1
1
50
25
223,3
48,1
1
1
50
25
276,5
59,3
1
1
50
25
366,3
79,3
2
2
100
12.5
No./l
bar
1 / 125
10,5
1 / 120
10,5
1 / 110
10,5
1 / 170
10.5
No./l
bar
1 / 22
10,5
1 / 25
10,5
1 / 25
10,5
2 / 44
10.5
kg
kg
mm
mm
mm
1520
1670
3435
920
1860
1530
1675
3435
920
1860
1545
1680
3435
920
1860
2800
3015
4280
860
1880
Note: (1) Nominal cooling capacity and power input are based on: 12/7 C entering/leaving evaporator water temperature;
30/35 C entering/leaving condenser water temperature.
110.2
120.2
133.2
146.2
kW
kW
No.
No.
kg
%
408,2
87,2
2
2
100
12,5
443,6
95,0
2
2
100
12,5
496,0
104,8
2
2
100
12.5
540,5
114,4
2
2
100
12.5
No./l
bar
1 / 285
10,5
1 / 285
10,5
1 / 280
10,5
1 / 280
10,5
No./l
bar
2 / 47
10,5
2 / 50
10,5
2 / 59
10,5
2 / 68
10,5
kg
kg
mm
mm
mm
2945
3280
4280
860
1880
2955
3290
4280
860
1880
2975
3315
4280
860
1880
2990
3340
4280
860
1880
Note: (1) Nominal cooling capacity and power input are based on: 12/7 C entering/leaving evaporator water temperature;
30/35 C entering/leaving condenser water temperature.
050.1
A
A
A
A
81
112
288
124
110.2
A
A
A
A
174
246
353
271
060.1
073.1
400 V - 3f 50 Hz
92
111
133
164
288
288
147
165
120.2
133.2
400 V - 3f 50 Hz
184
202
266
299
357
366
294
312
100.2
163
225
349
248
146.2
221
329
371
330
Note: (1) Allowed voltage tolerance 10%. Voltage unbalance between phases must be within 3%.
(2) Absorbed current referred to nominal condition: 12/7 C entering/leaving evaporator water temperature; 30/35 C
entering/leaving condenser water temperature.
(3) Absorbed current referred to the following conditions: 14/9 C entering/leaving evaporator water temperature;
45/50C entering/leaving condenser water temperature.
(4) Inrush compressors current for unit with one compressor OR 75% of nominal absorbed current of compressor n1 +
inrush current of last compressor (n2).
(5) Compressor FLA (Full Load Ampere).
050.1
A
A
A
A
79
108
288
124
110.2
A
A
A
A
167
234
351
271
060.1
073.1
400 V - 3f 50 Hz
89
103
128
154
288
288
147
165
120.2
133.2
400 V - 3f 50 Hz
175
188
253
276
354
359
294
312
100.2
157
215
347
248
146.2
201
299
363
330
Note: (1) Allowed voltage tolerance 10%. Voltage unbalance between phases must be within 3%.
(2) Absorbed current referred to nominal condition: 12/7 C entering/leaving evaporator water temperature; 30/35 C
entering/leaving condenser water temperature.
(3) Absorbed current referred to the following conditions: 14/9 C entering/leaving evaporator water temperature;
45/50C entering/leaving condenser water temperature.
(4) Inrush compressors current for unit with one compressor OR 75% of nominal absorbed current of compressor n1+
inrush current of last compressor (n2).
(5) Compressor FLA (Full Load Ampere).
-5
63 Hz
58
58
58
60
60
60
60
60
dBA
69,7
69,7
69,7
71,7
71,7
71,7
71,7
71,7
Note: Average sound pressure level rated in accordance to ISO 3744, free field semispheric conditions.
-5
63 Hz
55,9
55,9
55,9
57,9
57,9
57,9
57,9
57,9
dBA
64,7
64,7
64,7
66,7
66,7
66,7
66,7
66,7
Note: Average sound pressure level rated in accordance to ISO 3744, free field semispheric conditions.
10
Distance (m)
15
20
25
050.1
060.1
073.1
100.2
110.2
120.2
133.2
146.2
0
0
0
0
0
0
0
0
8,7
8,7
8,7
8,7
8,4
8,3
8,3
8,3
13,7
13,7
13,7
13,7
13,4
13,3
13,3
13,3
16,9
16,9
16,9
16,9
16,5
16,4
16,4
16,4
19,2
19,2
19,2
19,2
18,8
18,7
18,7
18,7
21,1
21,1
21,1
21,1
20,6
20,5
20,5
20,5
ECOPLUS
unit size
ECOPLUS
050.1
ECOPLUS
060.1
ECOPLUS
073.1
ECOPLUS
100.2
ECOPLUS
110.2
ECOPLUS
120.2
ECOPLUS
133.2
ECOPLUS
146.2
Evaporator
leaving water
temp. (C)
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
157,6
162,4
167,4
172,3
177,5
182,6
191,5
197,3
203,4
209,5
215,7
222,0
240,7
248,2
255,9
263,6
271,5
279,5
317,9
327,6
337,7
347,8
358,2
368,8
354,2
365,2
376,5
387,8
399,4
411,3
383,2
394,9
407,0
419,1
431,6
444,1
426,9
440,0
453,4
467,0
480,8
494,8
470,5
484,9
499,6
514,5
529,7
545,1
30
Power
input
(kW)
36,5
36,8
37,0
37,3
37,6
37,8
44,0
44,3
44,7
45,0
45,3
45,6
56,3
56,8
57,3
57,8
58,3
58,8
73,2
73,7
74,2
74,7
75,3
75,8
80,8
81,4
82,0
82,6
83,2
83,8
88,1
88,7
89,3
90,0
90,6
91,3
99,9
100,7
101,5
102,3
103,1
103,9
111,8
112,8
113,8
114,7
115,7
116,7
Cool.
cap. (kW)
151,1
155,8
160,6
165,5
170,5
175,5
183,6
189,4
195,3
201,2
207,2
213,3
230,4
237,7
245,1
252,8
260,4
268,2
304,7
314,3
324,0
333,9
344,0
354,3
339,5
350,2
361,1
372,2
383,6
395,0
367,5
378,9
390,7
402,5
414,6
426,8
409,2
422,0
435,0
448,3
461,6
475,3
450,7
464,8
479,2
493,7
508,4
523,3
35
Power
input
(kW)
41,2
41,5
41,8
42,1
42,3
42,6
49,6
50,0
50,4
50,7
51,1
51,5
63,3
63,8
64,4
64,9
65,5
66,1
82,5
83,1
83,7
84,3
84,9
85,5
91,1
91,8
92,4
93,1
93,8
94,5
99,3
100,0
100,7
101,4
102,2
102,9
112,5
113,4
114,2
115,1
116,1
117,0
125,8
126,8
127,9
129,0
130,1
131,2
Cool.
cap. (kW)
144,3
148,9
153,6
158,4
163,3
168,1
175,5
181,1
186,7
192,5
198,4
204,4
219,8
226,8
234,0
241,3
248,7
256,3
291,1
300,3
309,8
319,5
329,3
339,3
324,2
334,6
345,3
356,1
367,0
378,2
351,1
362,3
373,7
385,2
397,0
408,9
390,8
403,1
415,8
428,7
441,7
455,0
430,2
443,8
457,7
471,8
486,2
500,7
40
Power
input
(kW)
46,2
46,5
46,8
47,2
47,5
47,8
55,7
56,1
56,5
56,9
57,3
57,7
70,8
71,4
72,0
72,6
73,2
73,8
92,6
93,2
93,9
94,5
95,2
95,9
102,2
102,9
103,7
104,4
105,1
105,9
111,5
112,2
113,0
113,8
114,6
115,4
126,1
127,0
128,0
129,0
129,9
131,0
140,9
142,0
143,1
144,3
145,4
146,6
Cool.
cap. (kW)
137,4
141,8
146,4
151,0
155,6
160,5
166,9
172,3
177,8
183,4
189,1
194,9
208,5
215,4
222,3
229,4
236,5
243,8
276,9
285,8
295,1
304,5
313,9
323,6
308,3
318,4
328,7
339,1
349,8
360,6
333,9
344,7
355,8
367,0
378,3
390,0
371,3
383,4
395,6
408,0
420,7
433,4
408,6
421,8
435,2
448,8
462,6
476,7
45
Power
input
(kW)
51,7
52,0
52,4
52,7
53,0
53,4
62,3
62,7
63,1
63,5
63,9
64,4
79,0
79,6
80,2
80,8
81,4
82,1
103,5
104,2
104,9
105,6
106,3
107,0
114,3
115,0
115,8
116,6
117,4
118,2
124,6
125,4
126,2
127,0
127,9
128,8
140,8
141,8
142,8
143,8
144,9
145,9
157,2
158,3
159,5
160,7
161,9
163,2
Cool.
cap. (kW)
130,1
134,4
138,7
143,3
147,8
152,4
157,7
162,9
168,3
173,8
179,2
184,9
196,6
203,1
209,8
216,6
223,5
230,5
262,0
270,8
279,7
288,8
298,1
307,5
291,5
301,3
311,2
321,4
331,7
342,2
315,6
326,1
336,8
347,6
358,6
369,9
350,7
362,3
374,1
386,1
398,3
410,7
385,5
398,3
411,2
424,3
437,6
451,1
Power
input
(kW)
57,6
58,0
58,3
58,7
59,0
59,4
69,4
69,8
70,2
70,6
71,1
71,5
87,8
88,4
89,0
89,6
90,3
91,0
115,4
116,1
116,8
117,5
118,3
119,0
127,3
128,1
128,9
129,7
130,5
131,3
138,8
139,6
140,4
141,3
142,2
143,1
156,8
157,7
158,8
159,8
160,9
162,0
174,8
176,0
177,2
178,4
179,7
181,0
Note: (1) Nominal cooling capacity and power input are based on T=5C entering/leaving condenser water temperature;
evaporator fouling factor=0,0176 m2 C/kW; condenser fouling factor=0,0440 m2 C/kW.
ECOPLUS
unit size
ECOPLUS
050.1
ECOPLUS
060.1
ECOPLUS
073.1
ECOPLUS
100.2
ECOPLUS
110.2
ECOPLUS
120.2
ECOPLUS
133.2
ECOPLUS
146.2
Evaporator
leaving water
temp. (C)
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
176,3
182,2
188,3
194,5
200,9
207,2
211,4
218,4
225,6
232,9
240,3
247,8
261,6
270,4
279,2
288,3
297,5
306,9
346,6
358,0
369,8
381,7
394,0
406,4
386,1
399,0
412,2
425,5
439,2
453,1
419,9
433,7
447,8
462,3
476,9
491,9
469,4
484,8
500,7
516,8
533,1
549,8
511,7
528,4
545,4
562,7
580,3
598,3
30
Power
input
(kW)
34,6
34,7
34,9
35,0
35,2
35,3
41,9
42,1
42,3
42,5
42,7
42,9
51,6
51,9
52,2
52,5
52,8
53,0
68,9
69,3
69,6
69,9
70,2
70,5
75,9
76,2
76,6
76,9
77,3
77,6
82,7
83,1
83,4
83,8
84,2
84,6
91,2
91,6
92,1
92,5
92,9
93,3
99,6
100,0
100,4
100,9
101,3
101,7
Cool.
cap. (kW)
168,8
174,6
180,5
186,4
192,6
198,9
202,5
209,3
216,3
223,3
230,6
237,9
250,6
259,0
267,7
276,5
285,4
294,6
332,1
343,2
354,6
366,3
378,1
390,2
370,0
382,4
395,2
408,2
421,5
435,0
402,5
415,9
429,6
443,6
457,9
472,5
450,0
465,0
480,4
496,0
512,0
528,3
490,9
507,2
523,8
540,5
557,7
575,4
35
Power
input
(kW)
39,1
39,3
39,5
39,7
39,9
40,1
47,3
47,6
47,9
48,1
48,4
48,7
58,3
58,6
59,0
59,3
59,7
60,1
78,1
78,5
78,9
79,3
79,7
80,0
85,9
86,4
86,8
87,2
87,7
88,1
93,6
94,1
94,5
95,0
95,5
96,0
103,3
103,8
104,3
104,8
105,3
105,8
112,7
113,2
113,8
114,4
114,9
115,4
Cool.
cap. (kW)
161,1
166,7
172,3
178,2
184,1
190,1
193,3
199,9
206,7
213,5
220,5
227,6
239,2
247,4
255,7
264,3
273,0
281,8
317,0
327,8
338,9
350,2
361,7
373,5
353,3
365,3
377,7
390,3
403,1
416,3
384,5
397,6
410,9
424,5
438,3
452,4
430,0
444,7
459,5
474,7
490,2
506,0
469,5
485,2
501,4
517,8
534,5
551,6
40
Power
input
(kW)
44,0
44,3
44,5
44,7
45,0
45,2
53,2
53,5
53,8
54,1
54,5
54,8
65,5
65,9
66,3
66,7
67,1
67,5
87,8
88,3
88,8
89,2
89,7
90,2
96,7
97,2
97,7
98,2
98,7
99,3
105,3
105,9
106,4
107,0
107,5
108,1
116,2
116,8
117,4
118,0
118,6
119,2
126,9
127,5
128,1
128,8
129,4
130,1
Cool.
cap. (kW)
153,1
158,4
164,0
169,6
175,4
181,3
183,8
190,1
196,6
203,3
210,1
217,0
227,3
235,3
243,3
251,5
260,0
268,5
301,5
312,0
322,7
333,6
344,7
356,2
335,9
347,6
359,6
371,7
384,3
397,0
365,8
378,4
391,3
404,5
417,9
431,6
409,2
423,3
437,8
452,5
467,5
482,9
447,1
462,5
478,0
494,0
510,2
526,7
45
Power
input
(kW)
49,3
49,6
49,8
50,1
50,4
50,6
59,6
59,9
60,3
60,6
60,9
61,3
73,2
73,7
74,1
74,5
75,0
75,4
98,4
98,9
99,4
99,9
100,4
101,0
108,3
108,8
109,4
110,0
110,6
111,2
118,0
118,6
119,2
119,8
120,4
121,0
130,2
130,8
131,5
132,2
132,8
133,5
142,1
142,8
143,5
144,2
144,9
145,7
Cool.
cap. (kW)
144,8
150,0
155,3
160,8
166,3
172,0
173,7
179,8
186,2
192,6
199,2
205,9
214,8
222,5
230,2
238,1
246,3
254,5
285,4
295,6
305,9
316,5
327,3
338,4
317,8
329,1
340,6
352,5
364,5
376,9
346,0
358,2
370,7
383,5
396,4
409,7
387,3
401,0
415,0
429,2
443,7
458,6
423,6
438,5
453,5
469,0
484,6
500,6
Power
input
(kW)
55,0
55,3
55,5
55,8
56,1
56,4
66,5
66,8
67,1
67,5
67,8
68,2
81,6
82,0
82,5
82,9
83,4
83,9
109,8
110,3
110,8
111,4
112,0
112,5
120,8
121,4
122,0
122,6
123,2
123,8
131,6
132,2
132,9
133,5
134,2
134,9
145,2
145,9
146,6
147,3
148,0
148,8
158,6
159,3
160,1
160,8
161,6
162,4
Note: (1) Nominal cooling capacity and power input are based on T=5C entering/leaving condenser water temperature;
evaporator fouling factor=0,0176 m2 C/kW; condenser fouling factor=0,0440 m2 C/kW.
Unit
ECOPLUS
050.1
ECOPLUS
060.1
ECOPLUS
073.1
ECOPLUS
100.2
ECOPLUS
110.2
ECOPLUS
120.2
ECOPLUS
133.2
ECOPLUS
146.2
Leaving desuper-heaters
water temperature C
35
40
45
50
Heating
capacity
Heating
capacity
Heating
capacity
Heating
capacity
Heating
capacity
(kW)
(kW)
(kW)
(kW)
(kW)
21
10
6
22
17
10
35
28
19
42
20
12
43
27
16
44
34
20
57
45
29
70
56
38
22
18
11
29
23
16
36
34
30
44
36
22
51
41
27
58
46
32
65
57
46
72
68
60
23
22
17
30
28
24
37
35
31
46
44
34
53
50
41
60
56
48
67
63
55
74
70
62
24
23
20
31
29
26
38
36
32
48
46
40
55
52
46
62
58
52
69
65
58
76
72
64
25
24
21
32
30
27
39
37
33
50
48
42
57
54
48
64
60
54
71
67
60
78
74
66
45
50
55
45
50
55
45
50
55
45
50
55
45
50
55
45
50
55
45
50
55
45
50
55
Note: (1) Leaving evaporator water temperature 7C - T 5C; T condenser water temperature 5C.
Heating capacity correction factors for different evaporator leaving water temp.
Evaporator leaving water temp.
1,062
1,029
1,000
0,973
0,941
0,914
(FRSOXV
(FRSOXV
(FRSOXV
(FRSOXV
(FRSOXV
(FRSOXV
(FRSOXV
(FRSOXV
3UHVVXUHGURSN3D
:DWHUIORZUDWHOV
ECOPLUS
Unit Size
050.1
060.1
073.1
100.2
110.2
120.2
133.2
146.2
Evaporator
Leaving Water
Temperature (C)
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
40
Total
Heat
[kW]
189,1
194,1
199,2
204,4
209,6
215,0
45
Cooling Power
Cap.ty Input
[kW]
[kW]
145,2
42,3
149,9
42,5
154,7
42,6
159,6
42,8
164,6
43,0
169,7
43,2
Total
Heat
[kW]
187,5
192,4
197,3
202,4
207,6
212,9
Cooling Power
Cap.ty Input
[kW]
[kW]
138,6
47,5
143,2
47,6
147,8
47,8
152,6
48,0
157,4
48,2
162,4
48,5
50
Total
Heat
[kW]
186,1
190,8
195,6
200,6
205,6
210,9
Cooling Power
Cap.ty Input
[kW]
[kW]
131,7
53,1
136,1
53,3
140,7
53,5
145,3
53,7
150,0
53,9
154,8
54,1
Total
Heat
[kW]
184,8
189,4
194,2
199,0
203,9
208,9
184,5
45,0
229,5
176,8
50,8
227,6
168,7
57,0
225,7
160,2
63,7
223,9
190,4
45,2
235,6
182,5
51,0
233,5
174,3
57,2
231,5
165,6
64,0
229,6
196,4
45,4
241,8
188,4
51,2
239,6
180,0
57,5
237,5
171,2
64,2
235,4
202,5
45,6
248,1
194,3
51,4
245,7
185,8
57,7
243,5
176,8
64,5
241,3
208,7
45,8
254,5
200,4
51,7
252,1
191,7
58,0
249,7
182,5
64,7
247,2
215,0
46,0
261,0
206,5
51,9
258,4
197,7
58,2
255,9
188,3
65,0
253,3
234,2
55,9
290,1
224,2
63,0
287,2
213,7
70,6
284,3
202,7
78,8
281,5
241,8
249,6
257,5
265,5
273,7
56,2
56,5
56,8
57,0
57,3
298,0
306,1
314,3
322,5
331,0
231,6
239,1
246,8
254,6
262,6
63,3
63,6
63,9
64,3
64,6
294,9
302,7
310,7
318,9
327,2
220,9
228,2
235,7
243,3
251,0
70,9
71,3
71,6
72,0
72,4
291,8
299,5
307,3
315,3
323,4
209,6
216,7
223,9
231,3
238,8
79,1
79,5
79,9
80,3
80,7
288,7
296,2
303,8
311,6
319,5
305,9
75,1
381,0
292,9
84,7
377,6
279,5
95,0
374,5
265,5
106,2
371,7
315,7
75,4
391,1
302,5
85,0
387,5
288,8
95,4
384,2
274,5
106,6
381,1
325,7
75,7
401,4
312,2
85,4
397,6
298,2
95,8
394,0
283,7
107,1
390,8
335,9
76,0
411,9
322,2
85,7
407,9
307,9
96,2
404,1
293,1
107,5
400,6
346,3
76,3
422,6
332,3
86,1
418,4
317,7
96,6
414,3
302,6
107,9
410,5
356,8
76,6
433,4
342,5
86,5
429,0
327,7
97,0
424,7
312,4
108,4
420,8
341,2
82,7
423,9
326,7
93,2
419,9
311,7
104,6
416,3
295,9
117,0
412,9
352,2
83,1
435,3
337,5
93,6
431,1
322,1
105,1
427,2
306,0
117,4
423,4
363,4
83,4
446,8
348,4
94,1
442,5
332,7
105,5
438,2
316,3
117,9
434,2
374,8
83,8
458,6
359,5
94,5
454,0
343,5
106,0
449,5
326,8
118,4
445,2
386,5
84,1
470,6
370,8
94,9
465,7
354,5
106,4
460,9
337,5
118,9
456,4
398,3
84,4
482,7
382,3
95,3
477,6
365,7
106,9
472,6
348,4
119,4
467,8
4
5
6
7
8
9
369,2
90,1
459,3
353,8
101,6
455,4
337,6
114,0
451,6
320,6
127,5
448,1
381,0
90,5
471,5
365,2
102,0
467,2
348,8
114,5
463,3
331,4
127,9
459,3
393,0
90,8
483,8
376,9
102,4
479,3
360,2
115,0
475,2
342,5
128,4
470,9
405,2
91,2
496,4
388,8
102,9
491,7
371,7
115,4
487,1
353,7
129,0
482,7
417,6
91,6
509,2
400,9
103,3
504,2
383,5
115,9
499,4
365,2
129,5
494,7
430,2
92,0
522,2
413,2
103,8
517,0
395,5
116,4
511,9
376,9
130,0
506,9
4
5
6
7
8
9
4
5
6
7
8
9
413,3
426,5
439,9
453,6
467,5
481,7
100,7
101,2
101,7
102,1
102,6
103,0
514,0
527,7
541,6
555,7
570,1
584,7
395,9
408,8
421,9
435,2
448,8
462,6
113,5
114,0
114,6
115,1
115,6
116,2
509,4
522,8
536,5
550,3
564,4
578,8
377,8
390,3
403,0
416,0
429,2
442,6
127,3
127,9
128,5
129,0
129,6
130,2
505,1
518,2
531,5
545,0
558,8
572,8
358,6
370,8
383,1
395,7
408,5
421,6
142,3
142,9
143,5
144,1
144,7
145,4
500,9
513,7
526,6
539,8
553,2
567,0
457,3
471,9
486,8
502,0
517,4
533,0
111,4
112,0
112,5
113,1
113,6
114,2
568,7
583,9
599,3
615,1
631,0
647,2
438,0
452,3
466,8
481,5
496,5
511,8
125,5
126,1
126,7
127,4
128,0
128,6
563,5
578,4
593,5
608,9
624,5
640,4
417,9
431,7
445,8
460,2
474,8
489,6
140,7
141,4
142,0
142,7
143,4
144,1
558,6
573,1
587,8
602,9
618,2
633,7
396,7
410,1
423,8
437,7
451,8
466,2
157,2
157,8
158,5
159,2
160,0
160,7
553,9
567,9
582,3
596,9
611,8
626,9
Note: Values are based on T=5C entering/leaving condenser water temperature; T=5C entering/leaving evaporator water
temperature and with evaporator fouling factor=0,0176 m2 C/kW, condenser fouling factor=0,0440 m2 C/kW.
806 B 04/11 C pag. 22/32
ECOPLUS
Unit Size
050.1
060.1
073.1
100.2
110.2
120.2
133.2
146.2
Evaporator
Leaving Water
Temperature (C)
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
4
5
6
7
8
9
167,1
172,9
178,8
184,8
191,0
197,3
200,8
207,7
214,7
221,8
229,1
236,6
248,9
257,4
266,1
275,0
284,1
293,4
328,4
339,6
351,1
362,8
374,7
386,9
366,0
378,6
391,4
404,4
417,8
431,4
398,0
411,5
425,3
439,4
453,7
468,3
444,8
459,9
475,3
491,0
507,0
523,4
484,8
501,0
517,6
534,5
551,7
569,3
37,1
37,2
37,3
37,4
37,5
37,6
44,6
44,8
44,9
45,1
45,2
45,3
54,7
54,9
55,1
55,3
55,5
55,7
74,1
74,3
74,5
74,7
74,9
75,1
81,5
81,8
82,0
82,2
82,5
82,7
88,8
89,1
89,4
89,6
89,8
90,1
98,1
98,4
98,7
99,0
99,2
99,5
107,3
107,6
107,9
108,2
108,5
108,8
40
Total
Heat
[kW]
204,2
210,1
216,1
222,2
228,5
234,9
245,4
252,5
259,6
266,9
274,3
281,9
303,6
312,3
321,2
330,3
339,6
349,1
402,5
413,9
425,6
437,5
449,6
462,0
447,5
460,4
473,4
486,6
500,3
514,1
486,8
500,6
514,7
529,0
543,5
558,4
542,9
558,3
574,0
590,0
606,2
622,9
592,1
608,6
625,5
642,7
660,2
678,1
45
Cooling Power
Cap.ty Input
[kW]
[kW]
159,6
165,2
171,0
176,8
182,8
189,0
192,0
198,7
205,5
212,4
219,5
226,7
237,9
246,2
254,7
263,3
272,1
281,1
314,0
324,8
336,0
347,3
358,9
370,8
349,9
362,1
374,5
387,2
400,2
413,4
380,7
393,8
407,2
420,9
434,8
449,0
425,5
440,2
455,2
470,4
486,0
501,9
464,1
479,9
496,1
512,5
529,3
546,4
41,9
42,0
42,2
42,3
42,5
42,6
50,4
50,6
50,7
50,9
51,1
51,3
61,7
62,0
62,2
62,5
62,7
63,0
83,7
83,9
84,2
84,5
84,8
85,0
92,0
92,3
92,7
93,0
93,3
93,6
100,3
100,6
101,0
101,3
101,6
101,9
110,8
111,2
111,5
111,9
112,2
112,6
121,1
121,5
121,9
122,3
122,7
123,1
Total
Heat
[kW]
201,5
207,2
213,2
219,1
225,3
231,6
242,4
249,3
256,2
263,3
270,6
278,0
299,6
308,2
316,9
325,8
334,8
344,1
397,7
408,7
420,2
431,8
443,7
455,8
441,9
454,4
467,2
480,2
493,5
507,0
481,0
494,4
508,2
522,2
536,4
550,9
536,3
551,4
566,7
582,3
598,2
614,5
585,2
601,4
618,0
634,8
652,0
669,5
Cooling Power
Cap.ty Input
[kW]
[kW]
151,9
157,3
162,9
168,6
174,4
180,4
182,8
189,3
195,9
202,6
209,5
216,5
226,6
234,6
242,8
251,2
259,7
268,4
299,0
309,5
320,3
331,3
342,6
354,1
333,2
345,0
357,1
369,4
381,9
394,8
362,7
375,5
388,5
401,7
415,2
429,1
405,5
419,8
434,3
449,1
464,3
479,7
442,7
458,0
473,7
489,7
506,0
522,7
47,0
47,2
47,4
47,5
47,7
47,9
56,6
56,8
57,0
57,2
57,4
57,6
69,3
69,5
69,8
70,1
70,4
70,7
93,9
94,3
94,6
94,9
95,2
95,6
103,4
103,7
104,1
104,4
104,8
105,2
112,6
113,0
113,4
113,8
114,2
114,6
124,4
124,8
125,3
125,7
126,1
126,6
136,1
136,5
137,0
137,4
137,9
138,3
50
Total
Heat
[kW]
198,9
204,5
210,3
216,1
222,1
228,3
239,4
246,1
252,9
259,8
266,9
274,1
295,9
304,1
312,6
321,3
330,1
339,1
392,9
403,8
414,9
426,2
437,8
449,7
436,6
448,7
461,2
473,8
486,7
500,0
475,3
488,5
501,9
515,5
529,4
543,7
529,9
544,6
559,6
574,8
590,4
606,3
578,8
594,5
610,7
627,1
643,9
661,0
Cooling Power
Cap.ty Input
[kW]
[kW]
143,9
149,2
154,6
160,1
165,7
171,5
173,2
179,5
185,9
192,4
199,1
205,8
214,7
222,4
230,3
238,4
246,7
255,1
283,5
293,7
304,2
314,9
325,8
336,9
315,8
327,2
338,9
350,8
363,0
375,5
343,8
356,2
368,8
381,7
394,8
408,2
384,6
398,4
412,5
426,8
441,5
456,5
420,2
435,1
450,3
465,8
481,6
497,7
52,6
52,8
53,0
53,1
53,3
53,5
63,2
63,4
63,7
63,9
64,1
64,4
77,4
77,7
78,0
78,3
78,6
78,9
105,1
105,4
105,7
106,1
106,5
106,8
115,6
115,9
116,3
116,7
117,1
117,6
125,9
126,3
126,8
127,2
127,6
128,1
139,1
139,6
140,0
140,5
141,0
141,5
152,2
152,6
153,1
153,6
154,1
154,6
Total
Heat
[kW]
196,5
202,0
207,6
213,2
219,0
225,0
236,4
242,9
249,6
256,3
263,2
270,2
292,1
300,1
308,3
316,7
325,3
334,0
388,6
399,1
409,9
421,0
432,3
443,7
431,4
443,1
455,2
467,5
480,1
493,1
469,7
482,5
495,6
508,9
522,4
536,3
523,7
538,0
552,5
567,3
582,5
598,0
572,4
587,7
603,4
619,4
635,7
652,3
Note: Values are based on T=5C entering/leaving condenser water temperature; T=5C entering/leaving evaporator water
temperature and with evaporator fouling factor=0,0176 m2 C/kW, condenser fouling factor=0,0440 m2 C/kW.
806 B 04/11 C pag. 23/32
806 B 04/11 C pag. 24/32
EN 12055
TUV Standards (on request)
IEC 204-1 CEI 44-5 Elect. & Safety Codes
CEI-EN 602041 Codes
ISO 9001:2000
REFRIGERANT
Will be accepted only HFC 134a.
UNIT DESCRIPTION
Each chiller consist of single or multiple semi-hermetic rotary screw compressor, direct expansion
avaporator, water cooled condenser section, control system and all components necessary for safe and
controlled unit operation.
NOISE LEVEL AND VIBRATIONS
Sound pressure level at 1 meter distance in free field, semispheric conditions, shall not exceed dBA.
The sound pressure levels must be rated in accordance to ISO 3744. Other types of rating unacceptable.
Vibration level should not exceed 2 mm/s.
DIMENSIONS
Unit length shall not exceed . mm, unit width shall not exceed . mm, unit height shall not
exceed . mm.
CHILLER COMPONENTS
Compressors
9The compressors shall be field serviceable, semi-hermetic, single-screw type with one main helical
rotor meshing with two opposed gaterotor. Twin-screw compressor will no accepted because of the
large bearing loads inherent with this design. For a Single-screw compressor the two exactly
opposed gaterotors create two exactly opposed compression cycles which results in balanced forces
acting on the rotor compressor. The gaterotors will be constructed of a carbon impregnated
engineered composite material. The gaterotor supports will be constructed of cast iron.
9The oil injection shall be used for these compressors in order to get high COP also at high
condensing pressure and low sound pressure levels in each load condition.
9Refrigerant system differential pressure shall provide oil flow throught service replaceble, 0.5 micron,
full flow, cartridge type oil filter internal to compressor. Filter bypass or oil pump not acceptable.
9The compressors oil cooling must be realized by liquid injection. External dedicated heat exchanger
and additional piping to carry the oil from the compressor to heat exchanger and viceversa will be
not accepted.
9The compressor shall be provided with a integrated high efficiency, oil separator and with built-in oil
filter. The oil separator shall be provided with two sight-glasses, one each side, to check the level of
oil in the reservoir at the bottom of the separator.
9The compressor shall be direct electrical drive, without gear transmission between the screw and the
electrical motor. The motors compressor shall be designed for star/delta. Soft start should be
available as option.
9 The compressor casing shall be provided with ports to realize economized refrigerant cycles.
9Shall be present two thermal protection realized by a thermistor for high temperature protection to
motor and a thermistor for discharge gas high temperature protection.
9The compressor shall be provided with an automatic spring return of capacity control valve to the
minimum load position to ensure compressor starting always at minimum motor load so with the
minimum mechanical stress.
9The compressor discharge connection shall be fitted with a check valve and with a stop valve.
9The compressor discharge shall be fitted with a head pressure control valve.
Evaporator
9The units shall be supplied with shell and tubes counter-flow evaporator single refrigerant pass. It will
be direct expansion with refrigerant inside the tubes and water outside (shell side) with carbon steel
tube sheets, with straight copper tubes that are spirally wound internally for higher efficiencies,
expanded on the tube plates.
9The external shell, shall be linked with an electrical heater to prevent freezing up to -28 C ambient
temperature, commanded by a thermostat and shall be insulated with flexible, closed cell
polyurethane insulation material.
9The evaporator will have 1 or 2 circuits, one for each compressor and shall be single refrigerant pass
to ensure a simplier oil circulation so to ensure always a perfect oil return to the compressor.
9Evaporator is manufactured in accordance to PED approval.
Condensers
9Condensers will be shell and cleanable, through-tube type.
9The unit will have one condensers per circuit.
9Each condenser shall have a carbon steel and seamless, integrally finned high efficiency copper
tubes, roll expanded into heavy carbon steel tube sheets.
9Water heads shall be removable and include vent and drain plugs.
9Condensers will come complete with liquid shut-off valve, spring loaded relief valve.
Refrigerant circuit
9The unit must have refrigerant circuits completely independent of each other with one compressor
per circuit.
9Each circuit shall include: electronic expansion valve, exthernal high efficiency oil separator,
compressor discharge shut-off valve, a liquid line shut-off valve with charging connection,
replaceable core filter-drier, sight glass with moisture indicator and insulated suction line. Suction
line shut-off valve should be available as option.
Display Capabilities
The controller as a minimum shall be capable of monitoring and displaying the following data: Alarms
Phase Monitor
Freeze Protection
Evaporator Flow
Low Gas Pressure (per comp.)
Transition Fault, (per comp.)
Oil Diff. press. (per comp.)
Low Oil Pressure (per comp.)
High Gas Pressure Trip (per comp.)
Motor Overload, (per comp.)
Transducer faults
Units Off-Line
External fault
Processor Faults
Maintenance requirements
Operating Conditions
Ent./ Lvg. Evaporator fluid Temp.
Ent.ering Condenser fluid Temp.
Operating Chilled Fluid Setpoint
Oil / Discharge gas Press. (per comp.)
Condensing Press. (per comp.)
Evaporator Press. (per comp.)
Unit Enabled
Compressor Enabled
Water Setpoint Reset
Demand Limit or Current Limit
(Site Selectable)
806 B 04/11 C pag. 30/32
We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding.