Time Selective Protection: - Discrimination of Operation Times
Time Selective Protection: - Discrimination of Operation Times
Time Selective Protection: - Discrimination of Operation Times
tIDM
T
IL
I0>
tDT
1
I0>
I0>>
= tolerance of the
relay op.time
t M = marginal time
tM = Delay of an auxiliary relay (if used)
+ Possible delay of operation due
saturation of CT. In theory this could
be same as the time constant of DCcomponent. In practice 20 ms is
enough because all protection stages
will be delayed.
50
50
30
20
150
ms
ms
ms
ms
ms
0.35 x t1 + 150ms
1+
100
where t1 = op.time of the relay of the closest location
E1 = error of
E2 = error of
Load 0A
Earth Fault
105A
Relay 1
- current setting = 15A
- time multiplier = ???
- normal inverse
- high-set = 105A
Relay 2
- current setting = 30A
- time multiplier = 0,15
- normal inverse
t IDMT
t1x(1-E1/100)/(1-E2/100)-1)
op.time of CB
retardation time
marginal
203
50
30
20
303
ms
ms
ms
ms
ms
1+ 1
100
= t1
1 + t R + tCB + t M
1 E2
100
tIDM
T