501

MANUAL START
DEEP SEA ELECTRONICS PLC

Issue 2
VH 25/05/01

DESCRIPTION
The Model 501K-1 is a Manual
Engine Control Module, which
has been designed to manually
control the engine via a key
switch on the front panel. The
module is used to start and stop
the engine, indicating fault
conditions; automatically shutting
down the engine and indicating
the engine failure by LED giving
true first up fault annunciation.
Operation of the module is via a
three
position
key
switch
mounted on the front panel with
STOP(O), RUN(I) and START(II)
positions. In the O position the
DC supply is removed from the
module and the run relay and
alarm output are de-energised. If
the switch is turned to the I
position the module is powered
up and the run relay is energised,
activating the engine fuel/ignition
system and the protection holdoff timer is initiated. If the switch
is moved to the II position and
held against the spring return, a
positive supply is applied to the
relevant output terminal and on to
the starter motor.
Once the
engine has started the switch
should be released and allowed
to return to the I position.
Operation of any of the following
alarms; Low Oil Pressure, High
Engine Temperature, Auxiliary
Shutdown,
Overspeed
(Optional), will cause the run
relay to de-energise. This will
remove the fuel/ignition supply
from the engine and bring it to
rest. The alarm output will be
activated giving a positive DC
output.

Each alarm channel has its own


LED indicator and once activated
no further alarm conditions will be
accepted. The alarm output and
relevant LED will remain active
until the unit is reset by turning the
switch to the O position.
Overspeed Protection (Optional)
is achieved by the fitment of an
additional PCB in the module. This
provides
integral
overspeed
protection derived from either the
generator HZ output or the engine
magnetic pick-up (specified on
ordering). The overspeed circuit
continuously monitors the engine
speed and will shut down the
engine immediately if a pre-set
speed level is exceeded. This trip
level is adjustable from 90% to
130% of full rated speed and is
suitable of both 50Hz or 60Hz
systems.
During engine cranking and for a
short
time
afterwards
the
protection hold-off timer is active
and the relevant alarms inputs are
inhibited. This enables the engine
to start and achieve normal running
conditions. Once the timer has
expired the inputs are enabled
providing normal protection from
the module.
Charge Failure warning is also
provided by monitoring the WL
terminal on the charge alternator.
This operates on a similar principal
to the warning lamp fitted in a
motor vehicle, should the output
fail the charge fail LED will
illuminate. The module will also
provide the alternator excitation
current via this connection.

SPECIFICATION
DC Supply:
9 to 33 V Continuous.
Cranking Dropouts:
Able to survive voltage dips during
cranking. This is achieved without
the need for internal batteries.
Alternator Input Range:
15 - 305 V AC RMS
Alternator Input Frequency:
50 - 60 Hz at rated engine speed.
Magnetic Input Range:
0.5 V to +/- 80 V
Magnetic Input
Frequency:2300Hz to 6000 Hz at
rated engine speed.
Start Relay Output:
16 Amp DC at supply voltage.
Run Relay Output:
16 Amp DC at supply voltage.
Alarm Output:
1 Amp DC at supply voltage.
Dimensions:
72 X 72 X 118.5 (Excluding Keyswitch)
Operating Temperature Range:
-30 to +70C
Installation:
Front panel mounting via suitable
cut-out. Retaining clips supplied.
Cable connections via locking plug
and socket type connectors.
Calibration:
Speed trip setting and meter
calibration adjustment
potentiometer are accessible from
the rear of the module.

CASE DIMENSIONS
Meter

Trip

72.0mm

65.5mm

11
14

10

72.0mm

111.0mm

Panel Cut-out: 68mmx68mm


7.5mm

TYPICAL CONNECTIONS