Perhitungan Struktur Shelter - Meyerhoff Anly
Perhitungan Struktur Shelter - Meyerhoff Anly
Perhitungan Struktur Shelter - Meyerhoff Anly
FOR:
WAREHOUSE & WORKSHOP BULDING
PROJECT:
SKG RANTAU PANJANG
1. MODEL DESIGN
P=
15 m
2 PURLIN CALCULATION
Purlin Design Analysis
* Span of Purlin
Purlin is model as a simple beam analysis
Distance between frame is
Distance between purlin is
Roof slope
Put sagrod in the middle of it
L frame
Lsag =
3
Lframe=
Lpurlin=
=
1.6667
* Dimensionering
try lip channel:
A=
w=
Ix
Iy=
Wx=
Wy=
material
E=
metal sheet roofing
150x150x20x3,2
8.61 cm2
6.76 kg/m
280 cm4
28 cm4
37.4 cm3
8.19 cm3
2000000 kg/cm2
Wroof=
5 kg/m2
ceiling hanger
Wceiling=
10 kg/m2
ME
Wme=
0 kg/m2
* Loading
a. DEAD LOAD
Self weight of purlin+bolt
Metal steel roofing
Ceiling+hanger
Mec + elec
W1
W2
W3
W4
Wtot
b. LIVE LOAD
Considering roof live load:
Point load in the middle of purlin
Uniform load from rain water is loading in purlin
WLL=
(040-0,8xalfa)
# according to PPIUG, it should be taken not greater than 20 kg/m2
used
LLmax=
20 kg/m2
qLL=
c. WIND LOAD
qwind=
- compression wind
Wcomp=
20 kg/m
35 kg/m2
-13.76 kg/m
- sunction wind
Wsunc=
14 kg/m
d. EARTHQUAKE LOAD
No need for purlin analysis
e. LOAD COMBINATION
- Dead load + Live load
- Dead load + wind load
* Forces analysis in Purlin
7.67
21.08
34.20
93.97
b. calculate DL + LL (uniformload)
DL:
qx_DL=
q_DL sin a=
qy_DL=
q_DL cos a=
LL:
qx_LL=
qLL sin a=
qy_LL=
qLL cos a=
7.67
21.08
6.84
18.79
My2=
Then the force that determines the bending moment is taken largely fro
c. Calculate DL + WL
qx_Wlsunc=
qy_Wcomp=
qy_Wsunc=
0 kg/m
-13.76 kg/m
14 kg/m
qy_s2=
=
qy_c2=
34.84 kg/m
so compress wind load that is calculated
My
16.92 kg.m
4902293.49
all
2065356.68
25.0 mm
DL + LL (point load)
5319603.338
<
16000000
4
3
qy_DL
L
Py
Lframe
5
frame
1
x1
b. Checking
deflection
384
E Ix
48
E Ix
L frame
all =
=4
25
200 Lframe
3
qx_DL
DL+LL point load
5
2
1 Px Ls ag
y 1
384
E Iy
48
E Iy
Resultant
x1 2 y1 2
1 7.5 mm
DL+LL
uniform
load load)
DL
+ LL
(uniform
5
x2
384
y 2
5
384
qy Lframe
1
E Ix
qx Ls ag
1
E Iy
x2=
x2 5.8 mm
y2=
y 2 0.3 mm
Resultant
x2 2 y2 2
2 5.8 mm
DL
+ WL
DL+WL
x3
y 3
5
384
5
384
qy_c Lframe
2
E Ix
qx_c Lsag
2
E Iy
x3 x3
5.1 mm
y 3y3
0.1 mm
Resultant
Resultant:
3
x3 2 y 3 2
3 5.1 mm
Taken for analysis of deflection is the greatest deflection from the above
three loading conditions:
Shg, 3=
5.06468E-007 mm
Taken for analysis of deflection is the greatest deflection from the above
act
<
7.54408E-007
all
-->
25
=input
=result
5m
1m
20 deg
>>>DON'T CHANGE!
H=
4m
L=
12 m
=
=
=
=
( w + 0,1 w ) =
W roof x L purlin =
W ceil x L purlin =
W ME x L purlin =
7.436 kg/m
5 kg/m
10 kg/m
0 kg/m
+
22.436 kg/m
P=
WLL=
ater than 20 kg/m2
100 kg
39.72 kg/m2
kg/m
kg/m
kg
kg
Mx1=
183.35 kg.m
My1=
16.92 kg.m
kg/m
kg/m
kg/m
kg/m
14.51 kg/m
39.88 kg/m
as follow:
124.61 kg.m
11.34 kg.m
Mox=
183.35 kg.m
Moy=
16.92 kg.m
qx_DL + qx_Wlsuct
7.67 kg/m
qy_DL - qy_Wlsuct
7.08 kg/m
>
qy_s2=
7.08 kg/m
as follow:
108.87 kg.m
5.99 kg.m
183.35 kg.m
My
16.92 kg.m
kg/m2
kg/m2
-->
OK
mm
x1=
7.43E-07 mm
y1=
1.29E-07 mm
Sehingga, 1=
7.54E-07
5.79E-07 mm
Sehingga, 2=
2.60E-08 mm
5.062808E-007 mm
1.376711E-008 mm
5.80E-07 mm
OK
183.35
108.87
5.99
16.92
mm
The seismic load was automatical calculated based on dynamic analysis method by structure analysis program.
This Code considers 100% earthquake action in one direction, in combination with 30 % earthquake action in its perp
direction.
ELx = Fx + 0.3 Fy
ELy = Fy + 0.3 Fx
Where :
ELx : Seismic Load in X direction
ELy : Seismic Load in Z direction
The Parameter of Structural Design for Regular Shape Building
C
I
R
Wt
Earthquake response factor based on Zone factor (Zone 4) and Fundamental Period of Vibration (T) given
following figure Spectral Response with Soil type will be considered as hard soil (Zone 4).
: Important factor, 1.0
: Earthquake reduction factor
Bracing frame of steel structure : R = 5.5
:
Geometric Data:
h
d
bf
tw
tf
A
I33
I22
fy
E
g
Av2
Av3
S33
S22
r33
r22
L33
L22
K33
K22
Cm
Forces:
P
=
M33 =
M22 =
V2
=
V3
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
0.3
0.291
0.15
0.0065
0.009
0.005
0.000069
0.000005
240
200000
9.81
tw.d
=
5/3.tf.bf
=
I33/(h/2)
=
I22/(bf/2)
=
(I33/A)^0,5 =
(I22/A)^0,5 =
4.29
4.29
1
1
0.85
m
m
m
m
m
m2
m4
m4
Mpa
MPa
m/sec2
0.00189 m2
0.00225 m2
0.00046 m3
0.00007 m3
0.11747 m
0.03162 m
m
m
-29.48 kN
41.98 kN.m
-0.04 kN.m
-8.7 kN
0.01 kN
Allowable stress
Allowable stress increment factor:
bending major
Fb33
=
bending minor
Fb22
=
tension
Fat
=
shear
Fv
=
compression
Fac
K33 x L33
=
36.51891
r33
K22 x L22
r22
135.6617
1
1600
1600
1600
960
x
x
x
x
1
1
1
1
=
=
=
=
Cc
= (2p^2E/Fy)^0,5
1203.516
135.66171162 <
(non slender)
>
slender =
So:
Fa
5.896
139.56058
Mpa
91.26087 Mpa
fa/Fa=
0.04
0.6
Mpa
771
Mpa
55.9
Mpa
Mpa
Crc =
Crt
CR=
0.17
4.60
Mpa
0.05
0.0044
4.630E-005
Mpa
<
0CIVSPC001
depth of beam
distance C/C flange
width of beam
thickness of web
thickness of flange
cross section area
inertia moment in major axis
inertia moment in minor axis
yield strength of steel
elasticity moduli of steel
gravity
effective shear area in major axis
effective shear area in minor axis
section moduli in major axis
section moduli in minor axis
radii of gyration in major axis
radii of gyration in minor axis
lenght of member in major axis
lenght of member in minor axis
effective lenght factor in major axis
effective lenght factor in minor axis
moment coefficient
1600
1600
1600
960
kg/cm2
kg/cm2
kg/cm2
kg/cm2
=
=
=
=
160 Mpa
160 Mpa
160 Mpa
96 Mpa
200
slender =
135.6617
139.561 Mpa
Fac
0.17
OK
FOUNDATION DESAIN
A
The condensate drum and pump is designed to be supported with shallow foundation. The ultimate bearing capacity o
foundation will be calculated based on Meyerhoff theory as follows:
Where:
qult
c
q
Nc, Nq, N
Fcs, Fqs, Fs
soil type:
For clay/silty clay
c=
=
Ysat=
Y'=
b. Dimension of footing
Coloum
Footing
A.
Loading Data
Load from Load combination which provides Pu max (service condition)
Vertical reaction force=
3.33 ton
Weight of foundation=
coloum
0.25 ton
backfilling
0.62 ton
footing
1.34 ton
a.
b.
5.55 ton
0.96 ton
c.
0.85 m
Total moment
B.
C.
4.04 t/m4
0.91 t/m4
0 deg
1.11 m
1.6 m
=
=
=
Inclination factor
Fci=
Fqi=
Fyi=
1.157
1
1
q ultimate
SF
q all
D.
102.07 t/m2
3
34.02 t/m2
Bmin=
0.10 m
1
1
1
0.25
1.34
0.08
0.08
0.19
0.19
Resistance moment
Mr
3.83 ton.m
SF overtuning
Sfo
4.69 >
0.5
13.82
A.
Loading Data
Load from Load combination which provides Hu max (service condition)
Vertical reaction force=
2.91 ton
Weight of foundation=
coloum
0.25 ton
backfilling
0.62 ton
footing
1.34 ton
a.
b.
5.13 ton
1.11 ton
c.
0.85 m
Total moment
B.
C.
4.04 t/m4
0.91 t/m4
=
=
=
0 deg
1.03 m
1.6 m
Shape factor
Fcs=
Fqs=
Fys=
5.14
1
0
Inclination factor
Fci=
Fqi=
Fyi=
1.157
1
1
q ultimate
SF
q all
D.
101.27 t/m2
3
33.76 t/m2
1.125
1
0.743
Bmin=
0.09 m
1
1
1
0.25
1.34
0.08
0.08
0.19
0.19
Resistance moment
Mr
3.53 ton.m
SF overtuning
Sfo
0.5
11.16
3.74 >
is calculated as follows:
clay
or clay/silty clay
0,6*NSPT =
0 deg
1.8 t/m3
0.8 t/m3
15 t/m2
ton/m2
bp=
Lp=
a=
b=
Bf=
Lf=
h=
d=
depth of footing
0.35 m
0.5 m
0.3 m
0.3 m
1.4 m
1.6 m
0.25 m
0.175 m
0.55 m
=
=
0.82 ton.m
0 ton.m
0.816 ton.m
>>
use B=
1.4 OK
condition)
t
t
t
t
t
t
y1
y2
2 OK
0.7 m
0.7 m
1.14 m
0.26 m
0.7 m
0.7 m
=
=
0.94 ton.m
0 ton.m
0.94 ton.m
>>
use B=
1.4 OK
t
t
t
t
t
t
y1
y2
2 OK
0.7 m
0.7 m
1.14 m
0.26 m
0.7 m
0.7 m
A.
Loading Data
Load from Load combination which provides Pu max (service condition)
Vertical reaction force=
3.89 ton
Weight of foundation=
coloum
0.25 ton
backfilling
0.62 ton
footing
1.34 ton
a.
b.
c.
6.11 ton
0.75 ton
0.85 m
=
=
Total moment
B.
C.
3.95 t/m4
1.51 t/m4
1.19 m
1.6 m
5.14
1
0
Depth factor
Fcd
Fqd
Fyd
=
=
=
0 deg
1.157
1
1
Shape factor
Fcs=
Fqs=
Fys=
1.145
1
0.703
Inclination factor
Fci=
Fqi=
Fyi=
1
1
1
q ultimate
SF
q all*1,3
D.
103.65 t/m2
3
44.91 t/m2
Bmin=
0.08 m
>>
0.25 t
1.34 t
0.08 t
0.08 t
0.19 t
0.19 t
Resistance moment
Mr
4.22 ton.m
SF overtuning
Sfo
6.62 >
0.5
19.06
A.
a.
b.
c.
Loading Data
Load from Load combination which provides Pu max (service condition)
Vertical reaction force=
3.33 ton
Weight of foundation=
coloum
0.25 ton
backfilling
0.62 ton
footing
1.34 ton
Total of vertical load
5.55 ton
0.96 ton
0.85 m
=
=
Total moment
B.
C.
3.95 t/m4
1.51 t/m4
=
=
=
0 deg
1.11 m
1.6 m
5.14
1
0
1.157
1
1
Shape factor
Fcs=
Fqs=
Fys=
1.134
1
0.743
Inclination factor
Fci=
Fqi=
Fyi=
1
1
1
q ultimate
SF
q all*1,3
D.
102.66 t/m2
3
44.49 t/m2
Bmin=
0.08 m
>>
0.25 t
1.34 t
0.08 t
0.08 t
0.19 t
0.19 t
Resistance moment
Mr
3.83 ton.m
SF overtuning
Sfo
0.5
13.82
4.69 >
0.64 ton.m
0 ton.m
0.6375 ton.m
use B=
y1
y2
OK
1.4 OK
0.7 m
0.7 m
1.14 m
0.26 m
0.7 m
0.7 m
0.82 ton.m
0 ton.m
0.82 ton.m
use B=
y1
y2
OK
1.4 OK
0.7 m
0.7 m
1.14 m
0.26 m
0.7 m
0.7 m
REINFORCEMENT ANALYSIS
A
0.85
0.82
0.82
2.22 ton
0.99 t/m
4.83 t/m2
2.10 t/m2
W/m2
q1:
q2:
*
2.
2.22
0.99
4.86
1.70
2.22
0.99
4.78
2.65
2.22
0.99
4.83
2.10
Mu
h
dc
db
d
b
f'c
fy
Ecu
Es
Ecu
f
jd
=
=
=
=
=
=
=
=
=
=
=
=
=
As
a
=
=
0.6657 ton.m
250 mm
75 mm
13 mm
168.5 mm
1000 mm
21 Mpa
400 Mpa
21538.11 MPa
200000 MPa
0.003
0.8
147.4375 mm
6657451.17 Nmm
(clean cover)
(bar diameter - first assumption)
(first assumption)
d= h- (dc+0,5db)
per 1 mm
132.81 mm2
2.98 mm
117.24 mm2
try:
D
=
Asb =
n
=
13 mm
132.67 mm2
1 unit
Use:
n
=
5 unit
As =
663.33 mm2
spacing =
Min spacing=
a=
200 dipakai>
30
200 mm
spacing
14.8644258 mm
3.766629 ton.m
450
As min
482.6025
As min
As min <
589.75
589.75
As
663.325 OK
0.02142
Conclusion, use:
= 0.016065
2706.9525 >
OK
D
=
0.75
h
=
250 mm
dc =
75 mm
db =
13 mm
d
=
168.5 mm
b
=
1000 mm
f'c =
21 Mpa
fy
=
400 Mpa
Ecu =
21538.11 MPa
Es =
200000 MPa
ecu =
0.003
f
=
0.8
jd
=
147.4375 mm
As
13
663.325 mm2
200
350
500
40
internal column
edge
20
corner
b1
b2
c
2(b1+b2)=b0
518.5
668.5
1.43
2374
Vc1=
732819.63869 =
Vc2=
739218.3404 =
Vc3=
611039.11564 =
diambil Vc=
61.103911564 ton
Vc
45.8279337
>
OK
Pu
3.89
ton
t/m
t/m2
t/m2
ton
t/m
t/m2
t/m2
ton
t/m
t/m2
t/m2
>
min spacing
OK
SR=
0.194
<
OK
mm2
mm2
mm2
mm
mm
nternal column
mm
mm
mm2
73.28196 ton
73.92183 ton
61.10391 ton
SETTLEMENT
A
ELASTIC ELEMENT
Correlation value of Es with cohesion (clay):
> For clay normally consoldated
Es = 250 cu - 500 cu
> For clay overconsolidated
Es = 750cu - 1000cu
where c = undrained cohesion clay
Es values used in this design is Es = 750 Cu = 750 x 15 t/m2
11250 t/m2
From the table above, the value of Poisson's ratio s used in this design is 0.35.
Se
Bq 0
1 s2 r
Es
Where:
S
B
=Elasticsettlement(m)
=Foundationwidth(m)
=Workingload(T/m2)
=Modulusyoung (T/m2)
=PoissonsRatio
=1.0fromthebelowtableforL/B=1.14
3.33 ton
0.35 m
0.5 m
0.3 m
0.3 m
1.4 m
1.6 m
0.25 m
1.596 ton
0.6195 ton
5.5455 ton
15 t/m2
1.8 t/m3
0.8 t/m3
11250 t/m2
0.35
2.73 t/m2
1.142857143
1
Based on the results of soil investigation and labs results the value of elastic settlement is:
Se=
0.000298 m
B. CONSOLIDATION SETTLEMENT
0.298116 mm
Based on the results of soil investigation, soil consists of clay soil with water table elevation are at ground surface. In
addition, soil investigation also get NSPT value below the water table is 23->60. This soil is categorized into the type
of very stiff to hard silty clay. The consolidation settlement will be very small and could be negleted.
ST = Se + Sc = 0.298116 mm
Hence the differential settlement occurred on this case is
= 0.088873 mm
While on steel building the criteria for differential settlement is
L
250
=
L=
6400
250
25.6 mm
Since the differential settlement is less than the used criteria, hence the differential settlement aspect is safe on this
analysis