PCD3 Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 145

Manual

PCD3 series

Document 26-789; Edition EN17 2014-09-16

Saia-Burgess Controls AG

Content

0 Index

0 Index
0.1 Document History................................................................................................0-4
0.2 Brands and trademarks ......................................................................................0-4
1

Graphical index

2 Overview
2.1 Introduction
.........................................................................................................2-1
2.2 Instructions for connecting Saia-PCD controllers to the internet.......................2-1
2.3 Planning an application.......................................................................................2-2
2.4 Cabling
................................................................................................................2-5
2.4.1 Cable layout....................................................................................................2-5
2.4.2 Cable routing...................................................................................................2-5
2.5 Addressing and cabling rows..............................................................................2-6
2.5.1 Labelling module holders and modules...........................................................2-7
3

PCD3.Mxxx0 Classic CPUs and module holders


3.1 System overview.................................................................................................3-1
3.2 General technical details ....................................................................................3-3
3.3 System resources...............................................................................................3-5
3.3.1 Program blocks...............................................................................................3-5
3.3.2 Computation ranges for count types...............................................................3-5
3.3.3 Media
...............................................................................................................3-6
3.4 PCD3 CPUs........................................................................................................3-7
3.4.1 PCD3.M3xx0 and PCD3.M5xx0/PCD3.M6xx0 ...............................................3-7
3.4.2 PCD3.Mxx60 ..................................................................................................3-9
3.4.3 Block diagram for PCD3.Mxx0........................................................................3-11
3.4.4 Hardware and firmware versions for the PCD3.Mxxx0...................................3-12
3.5 Expansion with PCD3 components.....................................................................3-13
3.6 Mounting CPUs and module holders..................................................................3-14
3.6.1 Mounting position and ambient temperature...................................................3-15
3.7 Dimensions
.........................................................................................................3-15
3.8 Power supply and connection plan.....................................................................3-17
3.8.1 External power supply.....................................................................................3-17
3.8.2 Earthing and connection plan..........................................................................3-18
3.8.3 Internal power supply......................................................................................3-19
3.9 Operating states..................................................................................................3-19
3.10 Connections to the PCD3.Mxxx0........................................................................3-21
3.11 Partitioning options for user memory..................................................................3-23
3.12 Data storage in case of power failure..................................................................3-24
3.12.1 Battery module PCD3.R010 for PCD3.M3xxx.................................................3-24
3.13 Memory space on the PCD3...............................................................................3-26
3.13.1 General............................................................................................................3-26
3.13.2 Program backup and restore on backup flash.................................................3-31
3.13.3 Transferring an application with flash card......................................................3-33
3.13.4 Backup program after download option...........................................................3-34
3.13.5 Backup/restore of RAM texts/DBs at run-time.................................................3-35

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

0-1

Saia-Burgess Controls AG

3.14 Memory module PCD3.R600 for flash cards (FCs).............................................3-38


3.14.1 System overview.............................................................................................3-38
3.14.2 Technical data.................................................................................................3-38
3.14.3 Operation ........................................................................................................3-39
3.14.4 Displays and switches.....................................................................................3-41
3.14.5 Flash card........................................................................................................3-42
3.14.6 User program backup to the flash card...........................................................3-43
3.14.7 Order details....................................................................................................3-43
3.15 Hardware clock (Real Time Clock)......................................................................3-44
3.16 Hardware watchdog............................................................................................3-44
3.17 Software watchdog..............................................................................................3-46
3.18 Interrupt inputs....................................................................................................3-47
3.18.1 Basics..............................................................................................................3-47
3.18.2 PCD3.Mxxx0 interrupt inputs 24VDC....................................................................3-47
3.19 Operating mode switch (Run/Halt)......................................................................3-48
3.19.1 Run/halt push button.......................................................................................3-48
3.19.2 Run/halt switch ...............................................................................................3-48
3.20 Manual and emergency operation.......................................................................3-49
3.21 Module holder.....................................................................................................3-50
3.21.1 Internal supply to PCD3.C200 module holders...............................................3-50
3.21.2 LIO module holders.........................................................................................3-50
3.21.3 Connections to PCD3.Cxxx LIO module holders............................................3-52
4

RIO (remote input/output) head stations


4.1 Internal supply to PCD3.T76x head stations.......................................................4-1
4.2 RIO head station module holders........................................................................4-2
4.3 Connections to PCD3.T76x RIO head station for 4 modules..............................4-3
4.4 Diagnostic information on RIOs..........................................................................4-5
4.4.1 Diagnostic module...........................................................................................4-6
4.5 Profibus-DP or Profi-S-Net network line termination resistors............................4-10

Communication interfaces
5.1 Summary of onboard interfaces and plug-in interface modules..........................5-2
5.1.1 Onboard interfaces..........................................................................................5-3
5.1.2 Plug-in communication interfaces ..................................................................5-3
5.2 Protocols on serial ports......................................................................................5-4
5.2.1 Protocols supported by the firmware...............................................................5-4
5.2.2 Serial-S-Net.....................................................................................................5-5
5.2.3 Profi-S-Net.......................................................................................................5-5
5.2.4 Ether S-Net......................................................................................................5-5
5.2.5 Protocols implemented in the user program....................................................5-5
5.3 USB PGU interface for connecting programming units.......................................5-6
5.4 RS-232 connector (Port 0) as communication interface and as
connection for programming unit (PCD3.M5xx0/M6xx0 only).............................5-7

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

Content

0-2

Saia-Burgess Controls AG

5.5 Serial interfaces on I/O module Slot 0 (Port 1)....................................................5-9


5.5.1 General remarks on the PCD3.F1xx...............................................................5-9
5.5.2 RS-422/485 with PCD3.F110..........................................................................5-10
5.5.3 RS-232 with PCD3.F121 (suitable for modem)...............................................5-12
5.5.4 Current loop with PCD3.F130.........................................................................5-13
5.5.5 RS-485 with PCD3.F150.................................................................................5-15
5.5.6 MP-Bus with PCD3.F180................................................................................5-17
5.6 Serial interfaces on I/O module slots 0 - 3..........................................................5-19
5.6.1 General remarks on the PCD3.F2xx...............................................................5-19
5.6.2 Communication ports on the PCD3.Mxxxx......................................................5-19
5.6.3 Module overview.............................................................................................5-20
5.6.4 Port x.0: RS-422/485 auf Modul PCD3.F210..................................................5-23
5.6.5 Port x.0: RS-232 on PCD3.F221 module (for modem)....................................5-24
5.6.6 Port x.0: Belimo MP-Bus on module PCD3.F281............................................5-25
5.7 LIOs and RIOs....................................................................................................5-26
6
7

Content

Input/output (I/O) modules


Configuration
7.1 CPUs
...................................................................................................................7-1
7.1.1 Configuring the Saia PCD with Saia PG5......................................................................................... 7-1
7.1.2 "Hardware settings" option..............................................................................7-5
7.2 RIOs
....................................................................................................................7-7
7.2.1 Example project with Saia PG5 and Profibus-S-IO........................................7-7
7.2.2 Web server......................................................................................................7-17
7.2.3 Device-specific web pages..............................................................................7-18
7.2.4 Application-specific web pages.......................................................................7-30

8 Maintenance
8.1 Changing the battery on the PCD3.M5xx0/M6xx0..............................................8-1
A Annex
A.1 Icons
....................................................................................................................A-1
A.2 Definitions of serial interfaces.............................................................................A-2
A.2.1 RS-232............................................................................................................A-2
A.2.2 RS-485/422.....................................................................................................A-3
A.2.3 TTY/current loop..............................................................................................A-5
A.3 Order details........................................................................................................A-6
A.4 Contact ...............................................................................................................A-10

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

0-3

Content

Saia-Burgess Controls AG

0.1

Document History

Version
EN02
EN03
EN04
EN05
EN06

Date
2003-11-01
2004-08-15
2004-10-01
2005-01-31
2005-07-01

EN07
EN08
EN09
EN10

2006-10-01
2007-07-10
2009-03-01

EN11
EN12
EN13

2010-03-05
2010-03-24
2010-05-17
2010-07-12
2010-07-26
2010-11-10
2010-11-10
2011-06-28

EN14

2011-09-22
2011-09-29
2011-10-25

EN15

2012-04-05
2012-04-13
2012-11-15
2012-11-20
2013-05-10
2013-12-06
2014-02-07
2014-08-07
2014-09-16

EN16
EN17

0.2

2010-01-21

Changed Remarks
Translation
2004-10-01 Revision
Incorporation of CPUs
Changes
2005-11-15 Incorporation of new modules, sequence as
per price list, other additions and changes
2007-07-10 Further detailed additions and changes
2007-07-15 Further detailed additions and changes
2009-03-15 Further changes
2009-10-09 - 3 Removed the DIN40040
- 3.10 Port #3 of the PCD3.M5430
- 6.1.6 List of outphased I/O-modules
- 3.10 configuration of Port #10, Pin 6
- 6.13.1 Resolution A / D converter W525
2010-07-26 - 3.2, 3.12 Buffer time Super Cap
2010-07-26 - 5.5.6 Wiring concept PCD3.F180
- 6.8.1 Wiring concept PCD3.W2x0
2010-11-10 - 3.4 Profi-S-Net 1,5 MBit/s not for the M5340
2010-11-10 - 6.8.2 Ground connection of PCD3.W3x0
- Chapters 3, 5 and 6: External 24V power
supply and Ethernet + full duplex
2011-09-23 - Ch5 Using the SBC S-Bus
- New CPU-types PCD3.Mxx60
- Label-Creator replaced by the
Label-Editor of the Device-Configurator
2012-11-21 - Ch3.2 Storage temp. change -20 to -25 C
2012-11-21 - ChA.5 Adress changed
2012-11-21 - Ch9 Chapter deleted
2012-11-22 - Ch8.1 Buffer time Super Cap reduced
- Ch3.14 Behavior of the Diagnostic LED
- new Logo and new company name
2014-02-07 - Ch2 Internet Security
- Chapitre 6 externalis 27/600
2014-09-16 - Ch3.21.1 fraction bar has been shifted

Brands and trademarks


SaiaPCD and SaiaPG5
are registered trademarks of Saia-Burgess Controls AG.
Technical modifications are based on the current state-of-the-art technology.
Saia-Burgess Controls AG, 2014 All rights reserved.
Published in Switzerland

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

0-4

Graphical index

Saia-Burgess Controls AG

Graphical index
The graphical index singles out some highlights from the Hardware manual for the
PCD3 Series, and allows you to click on the text frames or directly on a component/
connector to jump straight to the corresponding section. The facility to jump to any
section from the table of contents is still to be completed.

Plug-in serial interfaces


in Slot 03, Section 5
LEDs for operating states,
Section 3.9
Ethernet, Section 5

Battery changing,
Section 8.1

Earthing, Section 3.8.2

Flash card,
Section 3.13

Run/Stop
switch,
Section 3.19.2
RS-232/PGU
(Port 0)
Section 3.10

Communication,
Section 5

Expansion,
Section 3.5

S-Net/RS485
(Port 10)
Section 3.10

LEDs for operating states,


Section 3.9

Terminal block for supply, watchdog, interrupt inputs and Port 2,


Section 3.10

Communication, Section 5

USB port,
Section 5

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

1-1

Overview

Saia-Burgess Controls AG

Introduction

2 Overview
2.1 Introduction

This manual covers the technical aspects of the PCD3 components. The following
terms are used frequently:
CPU

Central processing unit: the heart of the Saia PCD

RIOs

Remote I/Os: inputs and outputs connected to the CPU via a field bus
such as Profibus

LIOs

Local I/Os: these are connected to the CPU via the I/O bus or a RIO
(i.e. with the shortest possible cables)

Modules

Input/output elements, mounted in a housing, matched to the PCD3


system

Module holder

CPU, RIO or LIO, to which modules may be attached

The aim of this section is to present the essentials of planning and installing control
systems with PCD3 components. It covers the following topics:

Planning an application

Cabling

Addressing and cabling rows

Details of hardware, software, configuration, maintenance and troubleshooting are


described in separate sections. The Appendix contains an explanation of the icons
used, and the company address.

2.2

Instructions for connecting Saia-PCD controllers to the internet

When Saia PCD controllers are connected directly to the internet, they are also
a potential target of cyber attacks. For secure operation, appropriate protective
measures must always be taken.
PCD controllers include simple, built-in protection features. However, secure
operation on the internet is only ensured if external routers are used with a firewall
and encrypted VPN connections.
For more information, please refer to our support site:
www.sbc-support.com/security

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

2-1

Overview

Saia-Burgess Controls AG

Planning an application
2.3

Planning an application

The following aspects should be considered when planning PCD3 applications:



The internal load current taken by the I/O modules from the +5V and V+ supply

must not exceed the maximum supply current specified for the CPUs, RIOs or

LIOs (PCD3.C200)

The CPU or the RIO type determines the maximum number of module carriers

The total length of the I/O bus is limited by technical factors; the shorter, the
better

The PCD3.C200 is used to extend the I/O bus or for the internal power supply (+5V
and V+) to a module segment. Please note the following rules:

Use no more than six PCD3.C200s in one configuration, or the time delay will
exceed the I/O access time

Use a maximum of five PCD3.K106/116 cables

After each cable (at the start of a row), insert a PCD3.C200


Exception: In a small configuration with no more than 3 LIOs, these can be
supplied from the PCD2.Mxxx. A PCD3.C200 is not needed

Where an application is mounted in a single row (max. 15 LIOs), after every


five PCD3.C100s a PD3.C200 must be inserted to amplify the bus signal
(unless the configuration ends with the fifth PCD3.C100)

If the application is mounted in multiple rows, the restricted length of cable


means that only three LIOs (1x PCD3.C200 + 2x PCD3.C100) may be
mounted in one row

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

2-2

Overview

Saia-Burgess Controls AG

Planning an application
When planning an application, we recommend the following procedure:

Select the I/O modules according to your requirements. Where possible, use
PCD3 I/O modules with 16 connections; these have 16 red LEDs.

From the number of I/O modules, calculate the required number of module
holders. Check that the number of module holders is allowed:

PCD3
I/O bus connection for expansion units
Number of inputs/outputs or I/O module
sockets:

M3020
M3120
no
641)
4

M3320
M3330

M5xx0

M6xx0

yes
10231) 2)
64

1) Using digital I/O modules PCD3.E16x or A46x with 16 I/Os each


2) On all PCD3 units, address 255 is reserved for the watchdog. The I/Os reserved for the watchdog cannot be used,
and no analogue and H modules can be used on the sockets with base address 240

Arrange module holders in row(s) according to the mounting area available

Connecting material required


Arrangement with one PCD3.Mxx0; LIOs in one row

Max. 15 PCD3.LIOs in a row, no extension cable, with PCD3.K010 connector
only

Connecting material for this arrangement:
n PCD3.K010 connectors between PCD3 module holders


Arrangement with one PCD3.Mxx0; LIOs in multiple rows


Max. 3 PCD3.LIOs side-by-side and one row beneath the other, with extension
cables for the rows beneath (max. 15 PCD3.LIOs)


Connecting material for this arrangement:
n PCD3.K106/116 extension cables to connect the last PCD3 module holder

in one row with the first PCD3 module carrier in the next row; n x PCD3.K010

connectors between PCD3 module holders

Arrangement of a RIO node with the LIOs side-by-side

Max. 3 PCD3.LIOs total

Connecting material for this arrangement:
n PCD3.K010 connectors between PCD3 module holders
For all arrangements: After every five PCD3.C100 module holders, insert a
PCD3.C200 base unit as an I/O bus amplifier

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

2-3

Overview

Saia-Burgess Controls AG

Planning an application

Use the table in the section on "Current consumption of the modules" to



calculate the load current on the internal +5V supply (use the worst-case /
highest values)

Check that the max. supply current is sufficient for the CPU, RIO or PCD3.
C200. To supply a module segment separately, use a PCD3.C200 instead of a
PCD3.C1xx. Check that the load current for all segments does not exceed the
max supply current for the CPU/RIO/PCD3.C200. The max. supply current can
be found in the section on "Internal supply"

Calculate consumption from the 24 V supply. The current consumption for the
PCD3 configuration can be determined from the section on "Current
consumption of the modules" (use the worst-case / highest values)

Note that in most applications the outputs place the heaviest load on the 24 V supply.
For 16 outputs with a load current of 0.5 A each, the loading will be 8 A with all
outputs connected.

Do not forget the appropriate connecting cables for the module holders
Calculate the number of terminal blocks required for the I/Os, and order
separately. Screw or spring clamp terminal blocks can be ordered as required.
Not all modules require the same type of socket connection.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

2-4

Saia-Burgess Controls AG

Overview
Cabling

2.4

Cabling

2.4.1

Cable layout

It is advisable to wire the I/O modules from a cable channel.

Cables to connections on the lower part of the module carriers (supply, earth) should
preferably be wired from a cable channel below the module holders.
Following these rules will ensure that the LEDs are visible and the bus connections
remain accessible.
2.4.2

Cable routing

230V supply lines and signal lines must be laid in separate cables at least 10cm
apart. Even within the switching cabinet, it is advisable to leave space between
power and signal lines.
Digital signal / bus lines and analogue signal / sensor lines should be laid in
separate cables
It is advisable to use shielded cables for analogue signal lines.
The shield should be earthed at the entry or exit to the switching cabinet. The
shields should be as short as possible and of the largest possible cross-section.
The central earthing point should be > 10 mm and connected to the PE ground
wire by the shortest route
The shield is generally connected to one side of the switching cabinet only, unless
there is a potential equalization with significantly lower resistance than the shield
resistance
Inductivities installed in the same switching cabinet, e.g. contactor coils, should be
provided with suitable suppressors (RC elements)
Switching cabinet components with high field intensity, e.g. transformers or
frequency inverters, should be shielded with separator plates with a good ground
connection.
Surge protection for long distances or external lines





Where lines are laid outside the building, or over longer distances, suitable surge
protection measures should be applied. For bus lines in particular, these
measures are essential.
With lines laid outside, the shield must have adequate current-carrying capacity
and be earthed at both ends.
The surge conductors should be installed at the input to the switching cabinet.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

2-5

Overview

Saia-Burgess Controls AG

Addressing and cabling rows


2.5

Addressing and cabling rows

The address of a module is determined by its module position in the configuration.


PCD3 CPUs: Module addresses begin with base address 0 (zero) on socket 1

(addresses 0 to 15) and go up in increments of 16 to address 63 on

socket 4, regardless of the number of inputs/outputs (16, 8 or 4 )
PCD3 LIOs:

Determined by the module position in the configuration; go up in


increments of 16

PCD3 RIOs:

There is no direct access to the I/Os; the entries are defined by the
network configurator.
32

48

64

128

Frontview

16

Frontview
Frontview

176

Frontview

Frontview

Frontview

192

368

Frontview

Frontview

Frontview
Frontview

Frontview

Frontview

next row up to
max. 1023

Extension cables connect the module holder at the right-hand end of a row with the
first module holder at the left of the next row. The address of the first module in a
second or third row equals the address of the last module in the previous row +16.
To simplify cabling, the module locations for the PCD3 module holders are labelled
0 to 3. For more precise addressing, each module holder and each module also has
an address field in the bottom right corner of the housing. The use of these address
fields is described in the next section.
Address 255 is reserved for the watchdog relay. Modules that use this address must
not be installed in module position 16. For more details, please refer to the section on
the "Hardware watchdog".

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

2-6

Overview

Saia-Burgess Controls AG

Addressing and cabling rows


Each additional PCD3.C100/C200 module holder provides space for 4 further I/O
modules; at the end of the bus, a PCD3.C110 provides space for 2 further I/O modules. The connection to the next row is via the PCD3.K106/116 26-core extension
cable.
Forces arising with too small cable radii (smaller than the natural radius) may damage
the plug connection.

The extension cables must not be plugged in or removed with the controller
connected to the power supply.
2.5.1

Labelling module holders and modules

The sockets for the PCD3 module holders are labelled 0 to 3.


Every module holder has an address field in the bottom right corner of the housing
Example:
0

0-L3

1-L3

2-L3

3-L3

0-L4

1-L4

2-L4

3-L4
3

F rontview

F rontview
Frontview

Frontview

L3

L4

All PCD3 module holders and the PCD3.K106/116 extension cable are provided with
a matching set of labels for additional markings.

64
128
192
256
320
384
448
512
576
640
704
768
832
896
960

64
128
192
256
320
384
448
512
576
640
704
768
832
896
960

80
144
208
272
336
400
464
528
592
656
720
784
848
912
976

96
160
224
288
352
416
480
544
608
672
736
800
864
928
992

112
176
240
304
368
432
496
560
624
688
752
816
880
944
1008

0
0
16
32
48

4 310 8686 0

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

2-7

Overview

Saia-Burgess Controls AG

Addressing and cabling rows


Since the middle of 2005, all PCD3 I/O modules have been fitted with a means of
attaching a label clip. These clips can be snapped on to the right or left (e.g. where
there are no LEDs) of the connector. Prepunched labels can be inserted into the
clips. The clips, including prepunched labels (A4 sheets) are available as accessories
under item-number 4 310 8723 0.

(4 310 8723 0)

Older module housings


without attachment
facility

New module housings with


attachment facility

The prepunched labels can be edited using a the Device Configurator from
PG5V2.0:



Open the porgramming tool PG5V2.0


Start the Device Configurator from the menu Device
Open the Label Editor from the menu Tools
Select I/O module and edit preset text to your own requirements
(font, colour, borders etc.)
Print the prepunched labels on the A4 sheets provided
Peel label off the A4 sheet
Push the label under the transparent clip from left to right

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

2-8

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

System overview

PCD3.Mxxx0 Classic CPUs and module holders


The CPUs in the xx7 series are described in a separate manual.

3.1

System overview
CPU for centralized applications
PCD3.CPU
PCD3.LIO

SBC-S-Net

RIO for decentralized applications


PCD3.RIO

PCD3.LIO

SBCS-Net networking concept


SBCS-Net is the name of the new, flexible networking concept for innovative and
economical automation systems with Saia PCDs.
Based on the Ethernet-TCP/IP (Ether-S-Net) and Profibus (Profi S-Net) open
standards: use of existing network infrastructure no duplicate cabling required
Supports multi-vendor and multi-protocol operation:
Reduced costs for project planning, programming, commissioning and
maintenance by general use of Ethernet TCP/IP and Profibus with S-Net, the
Private Control Network (PCN) for SaiaPCDs
General use of web technologies via Ethernet TCP/IP and Profibus for
commissioning, operation, monitoring and diagnostics
General programming and commissioning via Ethernet TCP/IP and Profibus
Network connections integrated into the base unit; Profibus interface integrated
into the operating system of the new PCD3 controllers and PCD3 RIOs (included
in the base unit, at no extra charge)
Profi S-Net with optimized protocols and services for efficient operation of PCD3
RIOs and PCD3 controllers on the Profibus
Multi-protocol operation:
The new PCD3 controllers and PCD3 RIOs support Profibus-DP and S-Net on the
same socket
Continuity and security of investment:
All Saia PCD systems can be integrated into the design using existing Profibus
and Ethernet TCP/IP connections

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-1

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


System overview

Saia PCD web server


All PCD3 controllers and PCD3 RIOs come with an integrated web server as
standard:
Web browser as a tool for commissioning, support and visualization:
Access to the SBC web server is via standard web browsers such as Internet
Explorer and Netscape Navigator This makes the web browser, which can be
operated intuitively by anyone, the standard tool for commissioning, service,
support and visualization of machines, units and installations. The user can
retrieve pre-defined device and system-specific HTML pages, giving access to all
data on controllers and RIOs. Graphical elements (images, diagrams etc.) as well
as text documents (operating and repair manuals) can also be integrated into the
HTML pages, to provide a personalized user interface

General access to any desired interfaces and networks:


Access to the web server is available not only via Ethernet TCP/IP, but also via
cost-effective standard serial interfaces (RS-232, RS-485, modem etc.) and via
Profibus networks, throughout the system and at different levels in the network.
This makes it economical to use web technology to operate and monitor even the
smallest applications.
The SaiaPCD web server is integrated into all products:
Having a web server integrated as standard eliminates the cost of run-time
licenses or additional modules. In all new PCD3 controllers and the PCD3 RIOs,
the web server is already included in the base units, at no extra cost.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-2

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

General technical details


3.2

General technical details


Supply (external and internal)
Supply voltage
24VDC +25% smoothed or 19VAC 15% full-wave rectified
(18VDC)
1)
Power consumption
typically 15W for 64I/Os
Capacity of internal
5 V bus2)
Capacity of internal
+V bus (1624 V)2)

600mA
The capacity of the +V bus depends on the capacity of the 5V
bus, as follows (the more precisely the 24 V are maintained, the
higher the possible capacity):
24 V

- 25 %
+30 %:

100 [mA]

I 5 V Bus
[mA]
15
24 V - 10 %: 260 - I 5 V Bus [mA]
+10 %
4.8
24 V

- 20 %
+25 % :

150 -

1) The loads handled by the outputs and other consumers are generally more important for sizing the supply than
the internal power leakage of the control
2) When planning PCD3 systems, it is essential to check that the two internal supplies are not overloaded. This
check is especially important when using analogue, counter and positioning modules, as these may have a very
large power consumption.
It is advisable to use the Device Configurator from PG% V2.0,
for calculation the power consumption of the moduls.

Atmospheric conditions
Ambient temperature
When mounted on vertical surface with vertically aligned
terminals: 0+55 C
In all other mounting positions, a reduced temperature range of
0..+40 C applies
Storage temperature
-25+85 C
Relative humidity
1095% without condensation
Vibration resistance
Vibration
according to EN/IEC61131-2:
513.2 Hz constant amplitude (1.42 mm)
13.2150 Hz, constant acceleration (1 G)
Electrical safety
Protection type
Air/leakage paths
Test voltage

IP 20 according to EN60529
according to EN61131-2 and EN50178: between circuits and
bodies and between electrically isolated circuits: surge category
II, fouling level 2
350V / 50Hz AC for nominal unit voltage 24 VDC

Electromagnetic compatibility
Electrostatic discharge
according to EN61000-4-2: 8 KV: contact discharge
Electromagnetic fields
according to EN61000-4-3: field intensity 10 V/m, 801000 MHz
Bursts
according to EN61000-4-4: 4 KV on DC supply lines, 4 kV on I/O
signal lines, 1 kV on interface lines
Noise emission
according to EN 61,000-4-6: Class A (for industrial areas)
Guidance on the correct use of these controls in residential areas
can be found at www.sbc-support.com (additional measures).
Noise immunity
acc. to EN61000-6-4

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-3

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

General technical details


Mechanism and mounting
Housing material
Module holder:
PC/ABS, light grey, RAL7035
I/O modules:
PC, transparent blue
Clips:
PAM, orange, RAL2003
Fibre optics:
PC, crystal-clear
Mounting rail
Top-hat rail according to DIN EN60715 TH35
(formerly DIN EN50022) (1 35mm)
Connections
Terminal Spring
blocks
terminals
10-pole,
4-pole

3
Screw
terminals
10-pole

Spring
terminals
14-pole,
12-pole,
8-pole

Spring
terminals
24-pole,
6-pole

Earth
terminal

Terminal
2-pole
supply

Section
stranded 0.52.5mm 0.52.5mm 0.51.5mm 0.51.0 mm 0.08
0.5
single wire 0.52.5mm 0.52.5mm 0.51.5mm 0.51.0mm 2.5mm 1.5mm
The terminal blocks may only be plugged onto 20 times. They must then be replaced, to
guarantee a reliable contact
Length of 7 mm
7 mm
7 mm
7 mm
56 mm 7 mm
insulation
Standards / approvals
EN/IEC
Shipbuilding

cULus-listed

EN/IEC61131-2 Programmable controllers


ABS, BV, DNV, GL, LRS, PRS.
Please verify if your chosen product is mentioned in the
list of corresponding Type-Approval-Company under
www.sbc-support.com.
Please verify if your chosen product is listed in the corresponding
Certificate under www.sbc-support.com. The condition for cULus
Compliance are mentioned on the sheet annexed to the product
or can be required under www.sbc-support.com.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-4

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

System resources
3.3

System resources

3.3.1

Program blocks
Type
Quantity
Cyclic organization blocks
32* (16)
(COB)
Exception/system-dependent
32
organization blocks (XOB)
Program blocks (PB)
1000* (300)
Function blocks (FB)
2000*
(1000)
Sequential blocks (SB)
total 6000 steps and
transitions each (with PG5
1.3 and firmware version
xxx)

96

Addresses
0...31* (015)

Remarks
Main program elements

031

called from the system

0...999* (0299) Sub-programs


0...1999*
Sub-programs with
(0999)
parameters
for Graftec programming of
sequential processes
095

* This information is valid for firmware 1.10.16 and newer versions. Before this version 16 COBs, 300 PBs and 1000
FBs were supported.

3.3.2

Computation ranges for count types


Type
Integers
Floating point numbers

2,147,483,648 to
+ 2,147,483,647
9.223,37 1018 to
5.421,01 10-20
+ 9.223,37 1018 to
+ 5.421,01 10-20

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

Remarks
Format: decimal, binary, BCD or
hexadecimal
Instructions are provided to
convert values held in SBC
format (Motorola Fast Floating
Point, FFP) to IEEE 754 format
and vice versa.

3-5

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

System resources
3.3.3 Media
Type
Flags (1 bit)

Quantity
14336
(8192)

Addresses
F014335
(F08191)

Registers (32 bit)

16383

R 016383

Text/data blocks

Timers/counters (31 bit)

X or DB
8191

08191

16001)

T/C 01599

Constants with media code K any


Constants with no media
code

any

Remarks
By default, flags are not volatile,
but a volatile range can be
configured, beginning with
address 0
For integer or floating point
values
The texts 0..3999 are always
written to the same memory area
as the user program.
Where the user memory has
been extended, the base
memory can be configured to
hold RAM texts and DBs. The
texts and DBs held in this way
have addresses 4000
The breakdown of timers and
counters is configurable. Timers
are periodically decremented by
the operating system; the basic
time unit can be set between 10
ms and 10 seconds
Values 016383; may be used
in instructions instead of registers
Values 2,147,483,648 to
+2,147,483,647. Can only be
loaded into a register with an LD
command, and cannot be used in
instructions instead of registers.

1) The number of timers configured should be only as many as required, to prevent unnecessary CPU loading
** Since firmware 1.14.23 14336 flags are supported, before it was 8192. In order to use flags > 8191 PG5 2.0.150 is
required.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-6

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

PCD3 CPUs
3.4

PCD3 CPUs

3.4.1

PCD3.M3xx0 and PCD3.M5xx0/PCD3.M6xx0

Differentiation of PCD3
base units PCD3.M
General features
I/O bus extension
Number of inputs/outputs or
I/O module sockets
Processor (Motorola)
Processing time
Bit instruction
Word instruction
Firmware, firmware update
(firmware memory soldered
on)
Programmable with PG5
Main memory for user
program, text, DB (RAM)
Backup memory onboard
(Flash)
Hardware clock
Accuracy
Data backup
Interrupt inputs
Max. input frequency
Interfaces
Programming
interface
Optional serial port
Port 1

Basic

5440

6240

Profibus
DP
Master
6440

5540

6340

6540

Extended

3020

3230

3120

3330

5340

no
up to
641)
4

CAN

yes
up to 10231) 2)
64
CF 5272 / 66 MHz
0.31.5 s3)
0.9 s3)
Downloadable from the PG5 environment

from 1.3.1002
M3120 from
1.4.100
128
512
KByte KByte 4)
128
512
KByte KByte 4)

from
1.4.120

from
1.3.1002

from
1.4.100

from
1.4.120

1 MByte 4)
1 MByte 4)
1 MByte flash card (optional)

Yes, better than 1 min/month


4 hours with
Super Cap
(after 10 mins)

CR 2032 lithium battery


1-3 years5)
2
1 kHz6)
USB 7)

1x
RS-232, RS-422/485 or TTY current loop 20mA
pluggable (PCD3.F1xx modules)

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-7

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

PCD3 CPUs

Differentiation of PCD3
base units PCD3.M

Basic

5440

6240

Profibus
DP
Master
6440

5540

6340

6540

Extended

3020

3230

3120

3330

CAN

5340

Port 0 (PGU) also available


as RS-232 interface, up to
115 kbps

Serial data port RS-485, up


to 115 kBit/s
Profi-S-Net interface
Ether-S-Net interface
Field bus connections
Serial-S-Net
Profi-S-Net
Ether-S-Net (TCP/IP)

Port 2
Port 2 up to 187.5 kbps
M3120
only

M3330
only

Port 10 up Port 2 up to 187.5


to 1.5 Mbps
kbps
M6340 M6540
M5540 only
only
only

M3120
only

M3330
only

M5540 only

M6340
only

M6540
only

1) Using digital I/O modules PCD3.E16x or A46x with 16 I/Os each


2) On all PCD3 units, address 255 is reserved for the watchdog. The I/Os reserved for the watchdog cannot be used,
and no analogue and H modules can be used on the sockets with base address 240
3) Typical values; the processing time is dependent on the load on the communication ports
4) From hardware version D and matching firmware, see detailed notes in section 3.13.1
5) The period given is a buffer time; it is dependent on the ambient temperature (a higher temperature means a
shorter buffer time)
6) The 1kHz applies with a pulse/pause ratio of 1:1 and refers to the total frequencies of the two inputs
7) The USB port is type USB 1.1 Slave Device 12 Mbps and can only be used for programming and as an S-Bus
Slave, together with certain software products (Webconnect, ViSi-PLUS with S-Driver).
With a USB 2.0 hub, the download runs twice as fast
Can also be used as a serial data port, e.g. to connect a terminal; but this hampers commissioning and troubleshooting with the debugger

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-8

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


PCD3 CPUs

3.4.2 PCD3.Mxx60

Differentiation of PCD3 base


units PCD3.

Extended
M5560

M6360

General features
I/O bus extension
Number of inputs/outputs or
I/O module sockets
Processor (Motorola)
Processing time
Bit instruction
Word instruction
Firmware, firmware update (firmware memory soldered on)

Profibus DP
Master

CAN

yes
up to 10231) 2)
64
MCF 5373
0.10.8 s3)
0.3 s3)
Downloadable from the PG5 environment

Programmable with PG5


Main memory for user program
(FLASH)

from version SP2 2.0.200

Main memory for text (FLASH)

1 MByte

Backup memory onboard (Flash)

16 MByte

Hardware clock
Accuracy

2 MByte

Yes, better than 1 min/month


CR 2032 lithium battery
1-3 years5)
2
1 kHz6)

Data backup
Interrupt inputs
Max. input frequency
Interfaces
Programming interface
Optional serial port
Port 1

M6560

USB 7)
1
RS-232, RS-422/485 or TTY current loop 20mA
pluggable (PCD3.F1xx modules)

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-9

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


PCD3 CPUs

Differentiation of PCD3 base


units PCD3.

Extended
M5560

Port 0 (PGU) also available as RS232 interface, up to 115 kbps

Ether-S-Net interface
Field bus connections
Serial-S-Net
Profi-S-Net
Ether-S-Net (TCP/IP)

M6360

M6560

Serial data port RS-485,


up to 115 kBit/s
Profi-S-Net interface

Profibus DP
Master

CAN

Port 2
Port 10 up to
1.5Mbps

Port 2 up to 187.5kbps

1) Using digital I/O modules PCD3.E16x or A46x with 16 I/Os each


2) On all PCD3 units, address 255 is reserved for the watchdog. The I/Os reserved for the watchdog cannot be used,
and no analogue and H modules can be used on the sockets with base address 240
3) Typical values; the processing time is dependent on the load on the communication ports
5) The period given is a buffer time; it is dependent on the ambient temperature (a higher temperature means a
shorter buffer time)
6) The 1kHz applies with a pulse/pause ratio of 1:1 and refers to the total frequencies of the two inputs
7) The USB port is type "USB 1.1 Slave Device 12 Mbps" and can only be used for programming and as an S-Bus
Slave, together with certain software products (Webconnect, ViSi-PLUS with S-Driver).
With a USB 2.0 hub, the download runs twice as fast
Can also be used as a serial data port, e.g. to connect a terminal; but this hampers commissioning and troubleshooting with the debugger

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-10

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

PCD3 CPUs
3.4.3

Block diagram for PCD3.Mxx0


2)

F1xx moduls
communication
slot#0...3

Supply

I/O in Base
unit
Addresses 0...63

Serial data interfaces/


connections of fieldbus

I/O in Extensions
PCD3.C100/.C110/.C200
Addresses 64...1023

3
I/O Bus

CPU and I/O Bus


3)

RUN
STOP

Interruptinputs

CPU

R
nvol

T
vol

F
vol

F
C
nvol nvol

M
E
M
O
R
Y

E
E
P
R
O
M

M
A
P

user media

Date-Time
nvol

DB
TX
P

4)

3)

3)

user
memory

user memory

Watch-Dog

3)

Backup

1)

R
T
C
F
vol
nvol
P
TX
DB

register
timer
counter
flag
volatile
non volatile
program
text
data block

USB for the programing


RS-485
COM/PGU
unit
S-Net/
EthernetModem RS-232
MPI
TCP/IP
full handshaking

1) Connection for the programming unit


2) Except PCD3.M3020/3120
3) PCD3.M5xx0/M6xx0 only
4) With PCD3.M3330 or PCD3.M5540

I/O modules and I/O terminal blocks may only be plugged in and removed when the
Saia PCD and the external +24V are disconnected from the power supply.

To prevent loss of data, batteries should be changed with the power switched on.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-11

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


PCD3 CPUs

3.4.4

Hardware and firmware versions for the PCD3.Mxxx0

The firmware versions for the PCD3.Mxxx0 are generally upwardly compatible in
terms of hardware, so old CPUs can be fitted with new firmware, in order to take
advantage of new functions. This feature is highly valued, and we will try to retain it
for as long as possible; however, we cannot guarantee this.
The firmware for the PCD2.Mxxx0 is stored in a Flash EPROM, soldered to the
motherboard. A firmware update can be applied by downloading a new version with
the PG5. The procedure is as follows:

Go to www.sbc-support.com and download the latest firmware version


Establish a connection between PG5 and the CPU, as when downloading an
application (according to the facilities available, serial with PGU cable, modem1),
USB, Ethernet)
Open the Online Configurator and go offline
From the Tools menu, select Download Firmware, then use the Browse function
to select a path to the file for the new firmware version. Ensure that only one file is
selected for download
Start the download
After the download, the power supply to the Saia PCD must not be interrupted for
2 minutes (CPLD programming sequence). Otherwise, the CPU may be blocked in
such a way that it has to be returned to the factory.
While the Run/Halt LED is flashing slowly, the download is not yet complete. Only
when it starts flashing fast is the programming finished.
1) A modem connection is not always reliable. A modem may become blocked in such a way that remote access is
no longer possible. In such cases, an on-site visit will be necessary. Other connection options are preferable.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-12

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Expansion with PCD3 components


3.5

Expansion with PCD3 components

The PCD3.Mxxxx controllers can be expanded with PCD3.Cxxx components, making


additional module sockets available. On the PCD3.Mxxx0, up to 15 PCD3.Cxxx
module holders can be attached (PCD3.M3020/3120 cannot be expanded). This
allows the user to attach a maximum of 64 I/O modules, or 1023 digital inputs/
outputs.
Type

M3020
M3120
641)
4

Maximum number of inputs/outputs or I/O


module sockets for the system:

M3230
M3330
10231) 2)
64

M5xx0
M6xx0
10231) 2)
64

1) Using digital I/O modules PCD3.E16x or PCD3.A46x with 16 I/Os each


2) On all PCD3 units, address 255 is reserved for the watchdog. The I/Os reserved for the watchdog cannot be used,
and no analogue and H modules can be used on the sockets with base address 240

PCD3.M5540

PCD3.C100

PCD3.C110

Addressing
32

48

64

128

Frontview

16

Frontview
Frontview

176

Frontview

Frontview

Frontview

192

368

Frontview

Frontview

Frontview
Frontview

Frontview

Frontview

next row up to
max. 1023

For local expansion, the PCD3 LIO (local I/O) modules can be used.
For decentralized expansion using Profibus, the PCD3 RIO (remote I/O) modules can
be used:
The maximum number of I/Os is dependent on the controller being used:
When selecting I/O cassettes, ensure that the internal 5V and +V supply is not
overloaded.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-13

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


Mounting CPUs and module holders

3.6

Mounting CPUs and module holders

The PCD3 CPUs and module holders can be snapped onto a 35mm Top-hat rail
according to DIN EN60715 TH35 (formerly DIN EN50022). (Remember: the PCD2
needs two top-hat rails).

Mounting the PCD3 on the top-hat rail

Press bottom of housing onto the

mounting surface
Press upwards against the top-hat rail
Press top of housing against the
mounting surface and snap into place
Push the housing down onto the top-hat
rail to ensure that it is secure

Removal

To remove the housing, push upwards


and pull out.

Insertion of I/O modules

PCD3.C100 basic unit


with four slots

Locks

Location slots

For additional
screw fixing

Label holders

Insert the module into the appropriate module location and press down to the

bottom of the CPU or module holder housing; ensure that the orange clip is
engaged
For security, a guideway is provided to prevent the module being inserted

the wrong way round. In awkward positions, the modules can also be secured

with a screw.

Screw type: self-tapping 3x8mm, standard type obtainable from hardware
stores
Number of module slots in the module holder:


4 positions (labelled 0, 1, 2 and 3) PCD3.Mxxx0,C100/C200/T760


2 positions (labelled 0 and 1). The PCD3.C110 can only be used as the

last module holder in the bus

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-14

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Dimensions
3.6.1

Mounting position and ambient temperature

A vertical surface is normally used to mount the module carrier; the I/O connections
to the modules then also run vertically. In this mounting position, the ambient
temperature may be from 0C to 55C. In all other positions, air convection works
less well, and an ambient temperature of 40C should not be exceeded.

3.7 Dimensions

PCD3.M5xx0/M6xx0

PCD3.M3xx0

180

130

35
32.7

100.5

32.8

67.3

28.5
63.8
125.8
139

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-15

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


Dimensions

PCD3.C100/C200/T76x

130

PCD3.C110

66

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-16

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Power supply and connection plan


3.8

Power supply and connection plan

3.8.1

External power supply


Simple, small installations
+18V

19VAC
15%
0V
L N

GND
Trafo min. 50VA

Sensors:
Actuators:
Suitable for
modules:

Electro-mechanical switches
Relays, lamps, small valves with < 0.5A switching current
PCD3.Mxxxx
PCD3.E1xx, E5xx, E6xx, A2xx, A4xx, B1xx
PCD3.W1xx, W2xx, W3xx, W4xx, W5xx, W6xx

Small to medium installations


Trafo min. 50VA
+18V
19VAC
15%
0V
GND

L
N

Controller

24VDC
20%

+24V =

0V
L N


Sensors:
Electro-mechanical and proximity switches, photoelectric
barriers

Actuators:
Relays, lamps, displays, small valves with < 0.5A switching
current

Suitable for PCD3.Mxxxx

modules:
PCD3. E1xx, E5xx, E6xx, A2xx, A4xx, B1xx

PCD3.W1xx, W2xx, W3xx, W4xx, W5xx, W6xx
PCD3. H1xx*), H2xx*), H3xx*)
PCD7.D2xx*)
*) These modules must be connected to a smoothed 24 VDC supply

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-17

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Power supply and connection plan


3.8.2

Earthing and connection plan


0V +24VDC

O...

I...

W...

2.5 mm2

2.5 mm2

Earthing bar

In the bottom part of the PCD3 module housing there is a shielding and earthing
plate. Together with the shielding and earthing plate in the module holder, this
constitutes the common, large-area ground for all I/O modules and for the external
power supply.
When a module is plugged into the module holder, a metal tab on the module housing
creates a reliable multi-point contact to the module carrier concerned.
The zero-potential (Minus pole) of the 24 V supply is connected to the Minus
terminal of the supply. This should be connected to the earthing bar with the shortest
possible wire (< 25 cm) of 1.5mm2. The same applies to the Minus connection to the
PCD3.F1xx or the interrupt terminal.
Any shielding of analogue signals or communication cables should also be brought to
the same earth potential, either via a Minus terminal or via the earthing bar.
All Minus connections are linked internally. For problem-free operation, these
connections should be reinforced externally with short wires of 1.5mm2.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-18

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Operating states
3.8.3

Internal power supply

Supply 24 VDC

PCD3
+24 V

PCD-Bus

LED
24V

PTC

DC

+5V

DC

Voltagemonitor
5V

39V

CLR
0V

GND
DC
DC

+V
(16...24V)

Capacity of internal power supply


From the base units, the following currents are available for the plug-in modules:
+5 V :

600 mA

+V (1624 V) : 100 mA (the exact loads should be taken or calculated from the
technical details in section 3.2, or you are advised to use the
calculation table at www.sbc-support.com).
3.9

Operating states

The CPU can assume the following operating states:


Run, Run conditional, Run with error, Run cond. with error, Stop, Stop with error, Halt
and System Diagnostics
The display uses the LEDs shown below:

Battery
Batt
modul
Run
Halt
Error

Run/Halt

Link

Power
User

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-19

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Operating states

CPU type
LED

Batt

Battery module
Run
Halt

Colour
Run

Red

Green

Run cond.
Run with
error
Run cond.
with error
Stop

LED off

Stop with
error
Halt
System
diagnostics
Batt./Super
Cap voltage
absent
Communication

Red

PCD3.Mxxxx
For PCD3.M3xx0, these LEDs only
Error
Run/
Link
User
Power
Halt
Yellow bi-colour Yellow
Yellow Yellow

LED on

LED flashing

Start
Run

Self-diagnosis for approx. 1 sec. after switching on or after a Restart


Normal processing of the user program after Start. Where a programming
unit is connected via a PCD8.K11x in PGU mode (e.g. PG5 in PGU mode),
the CPU automatically goes into the Stop state and not the Run state; this
is for safety reasons
Run conditional Conditional Run state. A condition has been set in the debugger (Run
until), which has not yet been met
Run with error Same as Run, but with an error message
Run cond. with Same as conditional Run, but with an error message
error
Stop
The Stop state occurs in the following cases:
Programming unit in PGU mode connected when the CPU was switched
on
PGU stopped by programming unit
Condition for a COND.RUN has been met
Stop with error Same as Stop, but with an error message
Halt
The Halt state occurs in the following cases:
Halt instruction processed
Serious error in user program
Hardware fault
No program loaded
no communication module on an S-Bus PGU or
Gateway Master port
System
If the PLC doesnt go to RUN after 2 minutes, you have to send it for repair
diagnostics
Reset
The RESET state has the following causes:
Supply voltage too low
Firmware not starting up

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-20

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Connections to the PCD3.Mxxx0


3.10

Connections to the PCD3.Mxxx0


Slot 0 (Port 1)

PCD3.M5540

PCD3.M3330

USB
Ethernet (Port 9)
RS-485 (Port 2)

S-Net/MPI
(Port 10)
PGU/RS-232 (Port 0)

PCD3.M5xx0 and
PCD3.M6xx0
RS-232/PGU
Port 0
D-Sub
Signal
pin
1
DCD
2
RXD
3
TXD
4
DTR

Port 0

Port 10

PCD3.M5xx0 (except PCD3.M5340)


S-Net / MPI / RS-485
Port 10
Signal
Explanation

D-Sub
pin
1
GND
2
M24
3
RxD/TxD-P1)
4
CNTR-P

GND

DGND1)

DSR

VP2)

7
8
9

RTS
CTS
not used

7
8
9

P24
RxD/TxD-N1)
n.c.

1)
2)

GND
0V of 24V supply
Receive/transmit data positive.
Control signal for repeater
(direction control)
Data communication potential
(earth to 5V)
Supply voltage to P line
termination resistors
Output voltage plus 24V
Receive/send data negative
not connected

Mandatory signals (must be provided by the user).


The signal is provided by the control system.

PCD3.M5xx0 (except PCD3.M5340)


PGND

10
5
4
3
2
1

9
8
7
6

5
4
3
2
1

9
8
7
6
11

PGND
Port 0
*)

Port 3

RS-485
Port 3
D-Sub
Signal
pin
1
2
3
/RxD /TxD
4
5
PGND
6
7
8
RxD TxD
9
10/11
PGND

Explanation
RS-485

Receive/send +
Data ground

Receive/send Protective ground *)

Fixing screws on the D-Sub socket housing

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-21

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Connections to the PCD3.Mxxx0


PCD3.M5340
PGND

10
5
4
3
2
1

9
8
7
6

5
4
3
2
1

9
8
7
6
11

PGND
Port 0
*)

Port 3

RS-422
Port 3
D-Sub
Signal
pin
1
/RXD
2
/CTS
3
/TXD
4
/RTS
5
PGND
6
RXD
7
CTS
8
TXD
9
RTS
10/11
PGND

Explanation
RS-422
Receive data Ready to send.Send data +
Send request -

Data ground
Receive data+
Ready to send.+
Send data Send request +
Protective ground *)

Fixing screws on the D-Sub socket housing


PCD3.M6240, PCD3.M6340 und PCD3.M6360

1
2
3
4
5

6
7
8
9

Port 0
1)

Port 10

CAN
Port 10
D-Sub
Signal
pin
1
2
CAN_L1)
3
GND
4
5
6
7
CAN_H1)
8
9

Explanation
CAN
Receive/send neg.
Data transfer potential ground

Receive/send pos.
.

Electrically isolated
PCD3.M6440, PCD3.M6540 und PCD3.M6560
Profibus DP Master
Port 10
D-Sub
Signal
pin
Profibus DP

9
8
7
6

Port 0
2)

5
4
3
2
1

Port 10

1
2
3
4
5
6
7
8
9

GND2)
B red
En
GND_BUS
+5V_BUS
24V2)
A green

Explanation
Profibus DP
Protective ground
Receive/send pos.

For terminal resistors


For terminal resistors
Receive/send neg.

Not electrically isolated

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-22

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Connections to the PCD3.Mxxx0


For all types
Terminal block for supply, watchdog, interrupt inputs and Port 2
Pin Signal
Explanation
1

/D

3
Int0
4
Int1
5
WD
6
WD
7
+24V
8
GND
RS-485 terminator switch
Switch
Designation
position
left
O
right
C

Port#2; RS-485 up to 115.2kbit/s usable as


free user interface or (except PCD3.M5440
and PCD3.M5540) Profi-S-Bus up to 187.5
kbits/s
2 interrupt inputs 24 VDC or
1 rapid counter 24 VDC

Profibus
signal

Profibus
wiring

RxD/TxD-N

A
green

RxD/TxD-P

B
red

Watchdog
Voltage supply

Explanation
without termination resistors
with termination resistors

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-23

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


Partitioning options for user memory

3.11

Partitioning options for user memory

In the PG5 hardware configuration, the user memory is partitioned by default into
lines of code and texts/DBs, in a way that suits most applications.
In the case of a large program with few texts/DBs or a very small program with
many texts/DBs, the user can partition the memory manually. In order to choose an
appropriate breakdown, the following should be noted:
the partitioning is into "kBytes lines of code" and "kBytes text/DBs", where the
"kBytes lines of code" can only be changed in 4 kByte steps, as every line of code
occupies 4 bytes

the result of the formula (4 "kBytes program cells") + "kBytes texts/DBs" must
equal the effectively available user memory,
e.g. 4 24 kBytes + 32 kBytes = 128 kBytes
each character of a text occupies 1 byte
each 32-bit element of a DB occupies eight bytes in the address range 0..3999,
and the header of the DB takes up a further three bytes
We recommend always using DBs with addresses 4000. These can hold more
elements (16384 instead of 384), take up less space (only 4 bytes instead of 8
bytes per element, but NB, 8 bytes instead of 3 for the header) and the access
time is substantially shorter.
Example of manual partitioning:

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-23

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Data storage in case of power failure


3.12

Data storage in case of power failure

The resources (registers, flags, timers, counters etc), and possibly the user program
and the text strings/DBs, are stored in RAM. To ensure that they are not lost and that
the hardware clock (where present) continues to run when there is a power failure,
the PCD3s are equipped with a buffer capacitor (SuperCap) or a buffer battery.
CPU type

Buffer

Buffer time

PCD3.M3xx0

Super Cap (soldered, maintenancefree)

4 hours1)

PCD3.M5xx0/M6xx0

Renata CR2032 lithium battery

1-3 years2)

1) The total charging time is approx. 10 minutes


2) Depending on the ambient temperature; the higher the temperature, the shorter the buffer time

With new controllers, the batteries are packaged with the units, and have to be
inserted on commissioning. Observe the polarity of the batteries:

Insert CR2032 coin cells in such a way that the Plus pole is visible

CPUs with lithium batteries are not maintenance-free. The battery voltage is
monitored by the CPU. The BATT LED lights up and XOB 2 is called if


the battery voltage is less than 2.4 V


the battery is flat or shows an interrupt
the battery is missing

We recommend changing the batteries with the Saia PCD attached to the power
supply, to avoid any loss of data.
3.12.1 Battery module PCD3.R010 for PCD3.M3xxx

As the PCD3.M3xxx is only buffered by the Super Cap (max. 4 hours.), and
optional battery module is available with the same buffer time as the batteries in the
PCD3.M5xxx/M6xxx. The battery module may only be plugged into Slot#3 on the
PCD3.M3xxx. The other slots do not support RAM (program/data memory) or the
clock. This may cause damage to the Saia PCD.
Unpacking and mounting


Do not hold the circuit board by the LED holder


Do not touch the electronic side of the circuit board
Switch the Saia PCD off before inserting the circuit board

Technical details:
Internal current consumption: 10 mA at +5 V

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-24

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


Data storage in case of power failure

Installation rules:

1.
2.

3.

4.

Position circuit board over Slot#3 (battery holder upwards)


Insert circuit board horizontally. Ensure that the pins are correctly inserted into
the right positions in the Slot
Push the circuit board in as far as it will go (1 cm clearance between the circuit
board and the bottom of the grey Saia PCD housing)
Insert battery and place battery I/O cover on Slot#3.

Battery monitoring:
A red LED on the module indicates a weak battery that needs to be replaced. It does
have capacity left for a few more days. A weak battery also generates an entry in the
history list and calls XOB 2 (where this is programmed).
When the base address of the PCD3.R010 is read (=48 for Slot#3), the battery status
is read off:

0 for a weak battery (or module error, or module not present, etc.)
1 for battery OK

Inserting or changing a battery:


The battery (but not the module) can be replaced with the power on1) (XOB 2 called)
Pull the locking clip gently in the direction of the arrow
Remove old battery
Insert the Renata CR 2032 coin cell in such a way that the
positive pole is in contact with the locking clip
CPU type
Buffer
PCD3.M3xxx Renata CR2032 lithium battery
1)

Buffer time
1-3 years 2)

Changing the battery with the Saia PCD switched off will not cause any program or data loss
provided

that the Supercap for the Saia PCD CPU is not flat.
2)

Depending on the ambient temperature; the higher the temperature, the shorter the buffer time

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-25

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


Memory space on the PCD3

3.13

Memory space on the PCD3

3.13.1 General

The PCD3 controllers are fitted with a user program memory and a matching user
backup memory as standard. On the PCD3, both types are referred to as user
memory.
User Program Memory (RAM)

The user program memory consists of a RAM (Random Access Memory) and
contains the program code and a text and DB memory area. It also contains the
extension memory, which also holds DBs and texts (addresses 4000). On a PCD3,
all DBs and texts are always in RAM. The main difference between the texts and
DBs in the text/DB memory segment and those in extension memory is the greater
maximum size of DBs and texts.
To run an application on the PCD3, it is sufficient to load only the user program
memory. As this is a RAM, the program and the contents of the texts and DBs (and
the other media, registers, flags etc.) may be lost if there is no power and the battery
is flat or not connected. On a PCD3.M3xxx with no battery module, this kind of data
loss can also occur where the Supercap is exhausted.
Backup memory (Flash)
In order to prevent the loss of the program, every PCD3 CPU has onboard flash
memory fitted as standard to back up the user program memory.
It is also possible to save DBs on this flash during runtime. This allows key values of
registers and flags to be saved to the flash at runtime and reloaded later.
Along with the installed onboard flash memory, a flash card can also be used for the
user backup program, e.g. PCD7.R500 or PCD3.R500. The use of this card allows
the user program and the configuration to be transferred from one controller to
another.
Even with backup to the flash card, the source files for the project must be retained,
as the application is only stored in the Saia PCD as machine code.
If it transpires when the PCD3 is started up that the RAM memory has been
corrupted (e.g. after a power failure with a flat or missing battery), the application is
automatically reloaded from the flash backup memory. The LIST command "Test" and
operand "400" can be used to test this.
All hardware settings are also saved to the flash backup memory (onboard or on an
equivalent flash card).
Partition of user backup memory
The user backup memory is split into two parts. The first is available for the user
program backup and is always present. In the PG5 hardware configurator, this
memory is referred to accordingly as "user program backup".

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-26

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Memory space on the PCD3


The second, optionally configurable part is referred to in PG5 as "extension memory
backup" (data backup) and can be used to back up DBs and texts to the flash during
runtime.
If part of the backup memory is used as "extension memory backup", the available
"user backup memory" is reduced by twice the amount of "extension memory backup"
used. In parallel with the reduction of the "user program memory backup", the user
program memory is also adjusted, so the total user program memory can be copied
to the backup flash.

Available user backup memory on the onboard memory


The various versions of the PCD3 CPUs have different sizes of user program
memory (and hence of user backup memory). The effectively usable memory sizes
are basically dependent on the PCD3 type. As the available memory size on the
PCD3 has increased over time, there is a dependency on hardware and firmware
versions (the larger memory is configurable from version 030 upwards).
Available user memory with firmware version < 030
System H/w rev.
M3020
M3120
M3230
M3330
M5340
M5440
M5540
M6340
M6540

RAM user program Flash user


Default memory
memory
backup (prg +
configuration
data)
128 Kb
Only flash onboard 12 k prg lines,
16 k txt, 64 k ext.
256 Kb
Only flash onboard 24 k prg lines,
32 k txt, 128 k ext.
256 Kb
Flash onboard
24 k prg lines,
32 k txt, 128 k ext.
512 Kb
Flash card
48 k prg lines,
required
64 k txt, 256 k ext.

Available user memory with firmware version 030 and 1.xx.yy


System H/w rev.
M3020
M3120
M3230
M3330
M5340
M5440
M5540
M6340
M6540

RAM user program Flash user


memory
backup (prg +
data)
128 Kb
256 Kb

512 Kb

512 Kb

H/w < D

512 Kb

HW D
M5440 3)

1024 Kb 2)

512k onboard
1024k flash card1)
1024 Kb2)

Default memory
configuration
12 k prg lines,
16 k txt, 64 k ext.
48 k prg lines,
64 k txt, 256 k ext.
48 k prg lines,
64 k txt, 256 k ext.
96 k prg lines,
128 k txt, 384 k ext.

1)

If a flash card is used for flash user backup on a PCD3.M5xx0 or M6xx0 with hardware version < D,
the 512 kB user program backup can be saved to the flash and a further 256 kB will be available to back
up DBs at runtime.
2)

In order for a PCD3.M5xx0 with hardware version D and firmware version 030 to be configured,
PG5 SP1.4.120 or higher is needed.
3)

The PCD3.M5440 from hardware version D with modification 2 8 has 1024 Kb of user backup memory.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-27

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


Memory space on the PCD3

Note that in the default memory configuration, each program line requires 4 bytes.
Any flash memory module suitable for user program backup (e.g. a PCD7.R500) can
be used as a flash card. Where multiple compatible modules are connected, the first
module from the left will be used (socket M1, M2, I/O Slot 0, 1, 2, 3).
Flash memory modules (optional)
For the PCD3, there are various flash memory modules for different applications.
Some of these modules are explicitly designed for a particular use (e.g. the PCD7.
R500 for user program backup). However, there are other modules available for
various types of storage (e.g. the PCD7.R551M04, which contains 1 MB of memory
space for the user program backup and 3 MB the file system).

Most flash memory modules are simple cards (PCD7.Rxxx), which can be plugged
into a PCD3.M5xx0 or PCD3.M6xx0 on the communications extension in socket M1
or M2.
For use on a PCD3.M3xx0, there are the PCD3.Rxxx memory modules which contain
a PCD7.Rxxx and can be inserted into an I/O slot (03) on a PCD3 CPU.
Flash memory modules for the file system (optional)
Apart from the flash memories mentioned above for backing up the user program
memory and DBs, there is another type of flash memory available for files. These
memory modules can be used to save "PC-readable" files such as web pages,
images or log files. The content of these flash memory modules can be accessed via
the web server, the FTP server (for PCD3 with Ethernet interface only) and the user
program.
Flash memory modules for BACnet (optional)
When the PCD3.M5540, PCD3.M3330 and PCD3.M3120 controls are fitted with a
flash memory module for BACnet, the controls also have a BACnet stack. These
modules have the firmware extension for BACnet. The configuration of the BACnet
server and client is also stored on these modules.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-28

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


Memory space on the PCD3

PCD3.R560

Flash card modules with BACnet firmware. The module


contains both the firmware extension for BACnet and the
configuration files for the BACnet application.

Flash memory modules with BACnet firmware. The module


contains both the firmware extension for BACnet and the
configuration files for the BACnet application.
The module contains a PCD7.R560.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

I/O slot 03
I/O slot 03
M1 / M2
I/O slot 03

3 MB
3 MB

1 MB

M5xx0
M6xx0
1 MB

4 MB

Mxxx0

4 MB

M1 / M2

1 MB

M5xx0
M6xx0

Mxxx0
PCD7.R560

Mxxx0

PCD7.R551M04 Flash card modules with file system and as backup for the
user program.
The files can be accessed by the PCD3 via FTP or web
servers. The Saia PCD can also write PC-readable files
(*.csv) directly to the module.
PCD3.R551M04 Flash memory modules with file system and as backup for
the user program.
The files can be accessed by the PCD3 via FTP or web
servers. The Saia PCD can also write PC-readable files
(*.csv) directly to the module.
The module contains a PCD7.R551M04.

Mxxx0 with TCP/IP M5xx0 ,M6xxx0


with TCP/IP

PCD7.R550M04 Flash card modules with file system. To save files e.g. for the
web server. The files can be accessed by the PCD3 via FTP
or HTTP direct servers. The Saia PCD can also write PCreadable files (*.csv) directly to the module.
PCD3.R550M04 Flash memory modules with file system. To save files e.g. for
the web server. The files can be accessed by the PCD3 via
FTP or HTTP direct servers. The Saia PCD can also write
PC-readable files (*.csv) directly to the module.
The module contains a PCD7.R550M04.

Socket
M1 / M2

Flash memory modules as backup for the user program.


The module contains a PCD7.R500.

M1 / M2

PCD3.R500

I/O slot 03

Flash card modules as backup for the user program.


M5xx0
M6xx0
1 MB

PCD7.R500

BACnet

Description

File system

Module

for PCD3
system
User backup

Memory module summary for PCD3.Mxxx0 CPUs

3-29

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings

Socket
M1 / M2
I/O slot 03

I/O slot 03

BACnet

1 MB

PCD3.R600

PCD7.R-SD256 SBC SD flash memory card with 256 or 512 MB file system
PCD7.R-SD512 for PCD3.R600.
This card can be read with a card reader and the appropriate
software (SBCFile System Explorer) installed on a PC.

1 MB

for PCD3
system
User backup

Base module for the SD flash memory card. The card


contains a file system and is used to back up the user
program. The files can be accessed by the PCD3 via FTP
or web servers. The Saia PCD can also write PC-readable
files (*.csv) directly to the module.
In this module, PCD7.R-SD256 or R-SD512 flash memory
cards can be used.

up to 1 GB

PCD3.R600

Flash memory modules with BACnet firmware. The module


contains both the firmware extension for BACnet and the
configuration files for the BACnet application, plus a file
system, and is used to back up the user program.
The module contains a PCD7.R561.

1 MB

PCD3.R561

Flash memory modules with BACnet firmware. The module


contains both the firmware extension for BACnet and the
configuration files for the BACnet application, plus a file
system, and is used to back up the user program.

Mxxx0 with TCP/IP M5xx0 ,M6xxx0


with TCP/IP
1 MB
1 MB

PCD7.R561

Description

Mxxx0

Module

File system

Memory space on the PCD3

Sockets for memory modules


The sockets/slots shown below are provided, among other things, to take the memory
cards and memory modules.

Socket M1
Socket M2

Slot 0...3

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-30

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


Memory space on the PCD3

3.13.2 Program backup and restore on backup flash

The user program memory (user program, text/DB memory and extension memory),
including the hardware settings, can be copied from a PCD3 either to the onboard
flash or to an appropriate memory module (e.g. PCD3.R500). The procedure for
backup/restore to/from a flash card is identical to that for backup/restore using the
onboard flash.
If a flash card is plugged into the PCD3 and a backup is run, this module is
automatically written to and the backup is also created on the onboard flash (provided
sufficient memory space is available).

With a restore with a memory module plugged in, the content of the flash module is
restored and then (where possible) copied to the onboard flash.
Where multiple flash modules suitable for backing up the user program memory are
installed on the PCD3, the first from the left will be read/written to (sequence: M1, M2,
I/O slot 0..3).
In order to copy to the backup flash, the control must be in a STOP state. Where
necessary, a reminder message will appear. The copying process may take up to 30
seconds.
Program backup to backup flash
The user program memory can be loaded into flash using PG5. The relevant function
can be found on the "Online" menu within the PG5 project manager or the online
configurator.

Configuration for onboard backup of user program memory


The available memory space for the system memory backup to the flash memory can
be configured in the hardware settings for the PCD3. This allows a configuration for
backing up DBs and text contents (extension / data memory) to flash to be entered.
By default, a setting with no memory space for extension memory backup (for
"backup DB to flash") is configured.
Depending on the memory space available and required for the "backup DB to flash"
functionality, the following fields should be set:

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-31

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


Memory space on the PCD3

Saia PCD tab

Code/Text/Extension Memory Size: The available user program memory (RAM). As


the memory on a PCD3.M5xxx or PCD3.M6xxx is dependent on the hardware and
firmware versions, several possibilities are displayed here. The following options are
available:

256 kB RAM: For a PCD3.M5xxx or PCD3.M6xxx with hardware version

< D, where 128 kB is required for DB backup and no memory

card is installed.

512 kB RAM:



For a PCD3.M5xxx or PCD3.M6xxx with hardware version


< D, where no DB backup is being used and no memory card is
installed, or for a PCD3.M5xxx/PCD3.M6xxx with hardware
version < D, where 128 kB are required for DB backup and a
memory card is installed


1024 kB RAM: For a PCD3.M5xxx/PCD3.M6xxx with hardware version >= D



and firmware version >= 030 (or 1.xx.yy), whether a memory

card is installed or not
For all other types of control, the memory should be configured according to the table
on page xxx.
Memory tab

On the Memory tab, the Extension Memory Backup Size can be set. This memory
size represents the memory space for the "backup DB to flash" function. On the lefthand side, the currently available memory space for the user program is displayed.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-32

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


Memory space on the PCD3

If the "extension memory backup size" is increased, the "user program backup size"
will be automatically reduced (by twice the configured "extension memory backup
size")
Program restore from backup flash

Automatic restore

If no valid user program is loaded when the CPU is switched on, the CPU

operating system checks whether there is a valid program in the onboard flash;

if so, it is automatically loaded and executed.

An automatic restore is also run when an empty SuperCap is detected on a

PCD3.M3xxx or no battery or a flat battery is found on a PCD3.M5xxx/
PCD3.M6xxx

Manual restore with Saia PG5

PG5 can be used to write a valid program including configuration to the CPU

from the onboard flash. This function can be found on the "Online" menu within

the PG5 project manager or the online configurator:

Manual restore without PG5

If the "run/halt" switch is pressed for more than 3 seconds (while the PCD3 is in a
"Run" state), the user program will be loaded from the onboard flash.
During the "backup to flash" or "backup from flash" procedure, the run/halt LED on
the PCD3 flashes alternately red and green. On a PCD3.M5xxx or PCD3.M6xxx, the
"Run" and "Halt" LEDs also flash alternately.
3.13.3 Transferring an application with flash card

With the flash card, it is possible to transfer an application from a PCD3.M5xx0 to


another controller of the same type:








On the source controller, copy the application to the flash card as described in
the preceding sections
Remove the supply to the source controller, and unplug the flash card
Send off the flash card where applicable
Insert the flash card into the target controller (which should be switched off)
Switch on controller.
Press "Run/Halt" switch for more than 3 seconds; the LEDs will flash while the
program is being copied from the flash card (control switches to "Halt" state)
Restart the control with the "Run/Halt" switch

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-33

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


Memory space on the PCD3

If the configuration does not match the options available on the controller (e.g. IP
configuration on a controller without IP), the controller will switch to "Halt" state and
an entry will be written to history.
Loading the user program from the flash card will overwrite the user program backup
on the onboard flash, provided there is sufficient space for the program on the backup
flash.
3.13.4 Backup program after download option

In PG5, there is an option which copies the whole user program (HW configuration,
code, Text/DB and extension memory) to flash after the program download. This can
be found on the "Download Program" screen:

It is also possible to activate this option by default. To do this, the corresponding


option should be enabled in the PG5 project manager in the "Tools" menu
"Options":

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-34

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Memory space on the PCD3


3.13.5 Backup/restore of RAM texts/DBs at run-time

As described above, the application can be copied to the flash card after
downloading. In order to store process data gathered during operation, there is a
facility to copy texts or DBs from extension memory (address 4000) to the flash
card, or conversely, to copy the last state written to the flash card back in the text/DB
in extension memory.
The memory space required to back up the DBs (extension memory backup) must be
configured in the "Memory" tab in hardware settings. See section 3.13.3.

For storing texts/DBs on the flash card, restoring, deleting and running diagnostics,
there are four SYSRD/SYSWR instructions provided, as described in detail below;
these can be invoked at a suitable place in the user program. These instructions
must be used with great care, to prevent any damage to the unit or the flash card.
Storing a text/DB on the flash card with SYSWR K 3000
Storing a text/DB on the onboard flash with SYSWR K 3100
Instruction:

SYSWR

K 3x001)
K number

; address of the texts/DBs as


; K constant or in a register, existing
; text/DB addresses in the range >= 4000
; may be used

1) Alternatively, the value 3x00 can be passed in a register.

Battery status after execution:


low:
the text/DB has been saved, and the flash card is ready
for new SYSWR instructions
high:
the last instruction was not processed to completion;
before further SYSWR K 3x0x instructions, a SYSRD
K 3x0x must be executed to check the readiness of the
flash card
When using the instruction SYSWR K 3x00, note the following:
After any change of memory configuration, a "backup user program to flash" must
be run, to ensure that the "backup DB to flash" will work (partitioning the flash).
See section 3.13.4.
The flash card can be written to a maximum of 100,000 times, so it is not
permissible to invoke the instruction in a cyclical manner or at short intervals.
It is strongly recommended to execute a SYSRD K 3x00 before this instruction, to
test whether the flash card is available and ready.
The processing time for the instruction may be up to 100 ms. At that point, there is
no guarantee that all of the text/DB has been written (the process will continue in
background). For this reason, the instruction must not be invoked in XOB 0 (XOB
for a power failure) or during time-critical processes.
If errors occur during processing, XOB 13 will be called where it is present, or the
error LED will be set

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-35

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Memory space on the PCD3


When starting the Saia PCD after a loss of RAM memory, the state of the texts/
DBs after the last download is restored, even where the SYSWR K 3x00
instruction has been used to store newer versions.
Within the maximum number of write cycles, a text/DB can be stored any number
of times, without the flash card becoming over-full.
Restoring a text/DB from the flash card with SYSWR K 3001
Restoring a text/DB from the onboard flash with SYSWR K 3101
Instruction:

SYSWR

K 3x01
K number

1)

; address of the texts/DBs as


; K constant or in a register, existing
; text/DB addresses in the range >= 4000
; may be used

1) Alternatively, the value 3x01 can be passed in a register.

Battery status after execution:


low:
the text/DB has been restored and the process is
complete, so further SYSWR K 3x0x instructions can be
executed immediately
high:
the last instruction was not processed to completion;
before further SYSWR K 300x instructions, a SYSRD
K 3x00 must be executed to check the readiness of the
flash card
When using the instruction SYSWR K 3x01, note the following:
It is strongly recommended to execute a SYSRD K 3x00 before this instruction, to
test whether the flash card is available and ready.
If errors occur during processing, e.g. because no flash card is plugged in, XOB 13
will be called where it is present, or the error LED will be set
Deleting stored texts/DBs from the flash card with SYSWR K 3002
Deleting stored texts/DBs from the onboard flash with SYSWR K 3102
SYSWR K 3x021)
Instruction:
K0
; Dummy parameter, required to
; maintain the structure of the SYSWR
; instruction
1) Alternatively, the value 3x02 can be passed in a register.

Battery status after execution:


low:
the text/DB has been deleted and the process is
complete, so further SYSWR K 3x0x instructions can be
executed immediately
high:
the last instruction was not processed to completion;
before further SYSWR K 3x0x instructions, a SYSRD
K 3x00 must be executed to check the readiness of the
flash card

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-36

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Memory space on the PCD3


When using the instruction SYSWR K 3x02, note the following:
The deletion only affects text/DBs previously stored with SYSWR K 3x00. The
contents of the extension memory stored after a
download are retained
It is strongly recommended to execute a SYSRD K 3x00 before this instruction, to
test whether the flash card is available and ready.
The processing time for the instruction may be several 100 ms. For this reason,
it must not be invoked in XOB 0 (XOB for a power failure) or during time-critical
processes.

If errors occur during processing, e.g. because no flash card is plugged in, XOB 13
will be called where it is present, or the error LED will be set
Diagnostics of flash card with SYSRD K 3000
Diagnostics of onboard flash with SYSRD K 3100
SYSRD

Instruction:

K 3x001)
R_Diag

; Diagnostics register

1) Alternatively, the value 3x00 can be passed in a register.

Battery status after execution (only where memory space available for "backup DB to flash"
function):
low:
The flash card is ready, and SYSWR 3x0x instructions can be
executed
high:
The Flash card is not available or not ready; the diagnostic
register must be retrieved and the process retried later

When using the instruction SYSRD K 3x00, note the following:


The battery is only set as described above where there is memory space available
for the "backup DB to flash" function (i.e is correctly configured). For this reason,
the diagnostics register should also be checked. A decimal value of 0 means that
the flash can be used.
Specification of diagnostic register
Bit-no.

Description

Cause, where bit high

0 (LSB)

No backup possible

Header not configured

No application on the flash card

No SYSWR access to flash


card

DB/text not present

DB/text format invalid

The corresponding option has not been activated


in the hardware configuration (reserved for text/DB
etc.)
In the last instruction, an incorrect DB/text number
was used as a parameter
The length of the DB or the text has been changed

Restored

Memory full

Already in progress

831

Spare

Text/DB on the flash card has been restored, as an


error occurred
Too many texts/DBs, no more free memory space
available
The last SYSWR 3x0x instruction was not yet
completed when the next was started

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-37

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


Memory module PCD3.R600 for flash cards (FCs)

3.14

Memory module PCD3.R600 for flash cards (FCs)

3.14.1 System overview

The PCD3.R600 is an I/O module for industrial Secure Digital (SD) flash card
applications, for which it can be inserted into I/O slots 03 on a PCD3.Mxxxx. The
SD cards can be removed with the power on.

The SD cards can be accessed in 3 different ways:




Via Ethernet TCP/IP with FTP server


With a browser via Saia PCD web server
With the Saia PCD program, using a file system library
BCD switch

se

User

r
D

ag
W

ri

te

t
ro

us

LEDs

Diag
y
A

ct

iv

ity

Write Prot

Busy
Activity

Flashcard
slot
Switch

3.14.2 Technical data


PCD3.R600 module
Power consumption without SD flash card
15 mA
Max. power consumption incl. SD flash card
100 mA
Display
5 LEDs
Operating mode setting
BCD switch
Card holder and detection switch
With label clip
Required properties of SD flashcard (as tested by SBC)
Capacity supported
128, 256, 512 MB, 1 GB
Technology
Single-level cell
Service life
600,000 or more programming/deletion
cycles
Data retention
5 years or more
Operating temperature
-25C+85C or better
MTBF
1,000,000 hours or better

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-38

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Memory module PCD3.R600 for flash cards (FCs)


3.14.3 Operation

The PCD3.R600 can only be inserted into I/O slot 03 on a PCD3.Mxxxx.


The module cannot be plugged into the extension modules (PCD3.C1xx, PCD3.C2xx
or PCD3.Txxx). Up to 4 PCD3.R600 units can be used in a PCD3 system.

Slots
1

Data access
PG5

Browser

Explorer
FTP-Client
Ethernet-TCP/IP

Web-Server

User program,
Web pages
Onboard memory,
and PCD7.R500
for backup
(512 kByte max.)

PCD3.Mxxxx

FTP-Server

Web
pages

Any
data/files

Flash memory with file system


PCDx.R55xM04, PCD3.R600
(4 Mbyte - 1 GByte max.)

User program
with new CSF,
SFB instructions

PCD data
memory
DB/X, R, F, ...

FTP server and file system access can only be achieved with the plug-in flash
memory module. Access via FTP server is only possible via the Ethernet TCP/IP
interface.
Due to predetermined requirements SBC uses its own file system.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-39

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


Memory module PCD3.R600 for flash cards (FCs)

Based on the predefined requirements, SBC uses its own file system. The SBC file
system is embedded in a FAT (PC compatible file system) framework, to make the
restricted processes when used in a commercial SD card reader/writer visible with
standard PC tools. The SBC file system is called SBCNTFS.FFS.
Individual files within SBCNTFS.FFS can be accessed with a software tool for PCs
provided by SBC.
As 10% of the SD card capacity is reserved for the FAT, this extraction PC tool can be
copied there. This allows data stored in the SBC file system to be accessed quickly
on any PC with a standard SD card reader. The SBC PC tool can also make copies of
SBCNTFS.FFS on any drive. Any remaining FAT storage space can be used to save
documentation or for other purposes.

The PCD3.R600 can be used for PCD3 program backup in the same way as the
PCD7.R500. The PCD3 program backup is written to the file backup.sei in a specified
area and identified as a hidden read-only file in the FAT.
Apart from the SBCNTFS.FFS and backup.sei files, files in the FAT area cannot be
accessed when the SD card is inserted into the PCD3. During formatting, a file is
written to the FAT area containing the properties of the SD card. Data access is faster
with a commercial SD card reader/writer than with a PCD3.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-40

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


Memory module PCD3.R600 for flash cards (FCs)

3.14.4 Displays and switches

The memory module is fitted with 5 LEDs:


LED
User
Diag

Write Prot
Busy
Activity

Meaning
User LED, set by the user program with the base address of the module
(SET = off; RES = on)
The diagnostic LED is turned on when the SD card is not visible (eg SD
card is not formatted with FT16, poor boot sector, or poorly plugged in).
Once the SD card is inserted properly, it can take 5 seconds until the LED
goes out
Active when a "write-protected" condition is detected (read-only SD switch,
BCD switch or software)
Do not remove module when this LED is on.
Works as with a hard disk drive; flashes when data being processed

Setting of operating modes with the BCD switch:


Behind the label clip is a 10-position BCD switch which can be turned with a #0
screwdriver.
BCD position
0
1
2
3
4
5
6
7
8
9
*
**

Meaning
normal read/write**
Spare
Spare
Spare
Spare
format*/**
Spare
Spare
Spare
normal read only

Starts after insertion; remove, then plug in again


If the card itself is not write-protected (switch or software)

There must be a PC FAT file system (FAT16) on the card in order for the SD
card to be formatted with the SBC file system
First, all FAT files are deleted, then the SBC file system is installed when the
card is inserted and the BCD switch set to 5
If the BCD switch is set to 0, the SBC file system (SBCNTFS.FFS) is installed
if it is not already present and the card is empty, i.e. if a new card is installed, it
does not have to be formatted with position 5.
Not all flash cards have a "write-protect" switch
The card is inserted into a so-called push-push socket (push to insert and
remove)
All operations apart from formatting are blocked when the label clip is removed
Do not remove card when the "Busy" LED is on.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-41

Saia-Burgess Controls AG

PCD3.Mxxx0 Classic CPUs and expansion housings


Memory module PCD3.R600 for flash cards (FCs)

3.14.5 Flash card

The SD flash card is not part of the PCD3.R60x and has to be ordered
separately.
The SD card must be of good quality (industry-standard, as tested
by SBC). Other flash cards can also be used, but they will not be
supported and are excluded from any warranty.

To increase service life, the flash cards should not be more than 80% filled for pure
read applications. For read/write applications, no more than 50% of the memory
space should be used.
On the PCD3, a non-standard file system (SBC FS) is used. This means that the
flash cards have to be formatted before being used for the first time. This happens
automatically when a new FAT 16 flash card is inserted into the PCD3.R60x.
Flash card handling
The card is inserted into a so-called push-push socket (push to insert and remove),
located under the label clip.
It can be removed without switching off the PCD3.
To remove the label clip, first pull out the bottom end.
U
se
r
D
ia
g
W
ri
te

B
us
y
A
ct
iv
ity

A mechanism detects when the label clip is removed. Where


necessary, any unsaved data will be saved to the flash card.
The "Busy" LED will flash while this is happening.
Inserting the flash card
When inserting the flash card, press until you feel some
resistance; you may hear a soft click. Ease off the pressure
until the card is at the same height as the slot.
Removing the flash card
If the "Busy" LED is off, push the card into the module housing
until you feel some resistance. Ease off the pressure until the
card slides out.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-42

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Memory module PCD3.R600 for flash cards (FCs)


3.14.6 User program backup to the flash card

It is possible to back up the user program (see section 3.13.1) to the flash card in the
PCD3.R60x.
The memory locations for the user program (to back up and restore) are queried in
the following order:



1. M1 Slot
2. M2 Slot
3. I/O Slot 03
4. Onboard flash memory (where present)

I/O bus functions


Some states are detected by the user program.
I/O bus
offset
+0
+1
+2
+3
+4
+5
+6
+7

Write

Read

Meaning

User LED
do not use
do not use
do not use
do not use
do not use
do not use
do not use

BCD switch setting Bit 0 (lsb)


BCD switch setting Bit 1
BCD switch setting Bit 2
BCD switch setting Bit 3 (msb)
/label clip present

Position (non-inverted) of BCD


switch

/flash card present


SD write-protect switch

1 = removed
1 = card removed
1 = SD blocked/removed
0 = MMC or SD released

3.14.7 Order details


Order code
PCD3.R60x
PCD7.R-SD256
PCD7.R-SD512
PCD7.R-SD1024

Description
Base module for SD flash memory cards, for I/O
slot 03 (flash card not included)
SD flash memory card 256 MB
SD flash memory card 512 MB
SD flash memory card 1,024 MB

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

Weight
60 g
2g
2g
2g

3-43

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Hardware clock / hardware watchdog


3.15

Hardware clock (Real Time Clock)

The PCD3 CPUs are fitted with a hardware clock on the motherboard:
The presence of a hardware clock is an absolute requirement where the HeaVAC
library clock timers are used.
3.16

Hardware watchdog

PCD3 CPUs are fitted with a hardware watchdog as standard. A relay at I/O address
255 can be triggered; this remains activated as long as the status of O 255 changes
periodically at least every 200 ms. Within PG5, FBoxes are provided for this purpose.
If for any reason the program component with the watchdog FBox is no longer being
processed at sufficiently short intervals, the watchdog relay will drop out. Please read
the online help for these FBoxes for more details.
The same function can also be implemented with IL (AWL) instructions. This variant
works independently of the cycle time of the user program.
Example:

COB 0
0

STL WD_Flag

OUT WD_Flag

OUT O 255
: :
: :

ECOB

; or 115
;Invert help flag
;Set output 255 to flashing

With the code shown in the example, the watchdog also drops out in the case of
loops caused by the programmer. With regard to the cycle time of the user program,
please note:
With cycle times over 200 ms, the code sequence must be repeated several times
in the user program, to prevent the watchdog dropping out in normal operation.
As address 255 is in the normal I/O range, there are restrictions on the permissible
I/O modules in certain sockets:
CPU type

Restrictions

PCD3.Mxxx0

1) No analogue, counter and motion control modules on the


socket with base address 240 (apart from PCD3.W3x5 and
PCD3.W6x5, which are not affected by the watchdog)
2) Output 255 cannot be used for digital I/O modules

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-44

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Hardware clock / hardware watchdog


Watchdog - connection diagram
WD 1)

Supply

8
7
5
6
WD WD +24V GND

+24V

1)

A-module
Main switch

0V

Start

Bridging switch
for
CPU-Start

Process

Switching capacity of the watchdog contact: 1A, 48VAC/DC

The status of the watchdog relay can be read via I 8107


1 = Watchdog relay on.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-45

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Software watchdog
3.17

Software watchdog

The hardware watchdog provides maximum security. However, for non-critical


applications, a software watchdog may be sufficient, whereby the processor monitors
itself and the CPU is restarted in the event of a malfunction or a loop.
The core of the software watchdog is the instruction SYSWR K 1000. When this is
first issued, the software watchdog function is activated. This instruction must then be
issued at least every 200 ms, or the watchdog will trigger and restart the controller.
Instruction:

SYSWR

K 1000

; Software watchdog instruction

R/K x
x=0
x=1
x=2

; Parameters as per table below


; K constant or value in register
The software watchdog is deactivated
The software watchdog is activated; if the instruction is not
repeated within 200 ms, there will be a cold start
The software watchdog is activated; if the instruction is not
repeated within 200 ms, XOB 0 will be called and then there
will be a cold start
XOB 0 calls are entered in the Saia PCD history as follows:
"XOB 0 WDOG START"
where XOB 0 has been invoked
by the software watchdog
"XOB 0 START EXEC"
where XOB 0 has been invoked
because of a supply fault

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-46

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Interrupt inputs
3.18

Interrupt inputs

3.18.1 Basics

Because of the input filters and the effect of the cycle time, the digital input modules
are not suitable for immediate reaction to events or for rapid counting processes.
Some CPUs have interrupt inputs for this purpose.
When a positive edge is detected at the interrupt input, an associated XOB is called
(e.g. XOB 20). The code in this XOB defines how the unit should react to the event,
e.g. by incrementing a counter.

The code in XOBs called from interrupt inputs must be kept as brief as possible to
allow enough time between the interrupts to process the rest of the user program.

Many FBoxes are intended for cyclic invocation and so not suitable for use in XOBs,
or only in a limited way.
Exception: the FBoxes in the Graftec family (standard library) are well suited

3.18.2 PCD3.Mxxx0 interrupt inputs 24VDC

The two interrupt inputs are located on the motherboard and can be connected via
the 8-pole, plug-in terminal block (terminals 1 to 8). Source operation is always used.
Interrupt
input

XOB called in case of a posi- Direct input query


tive edge

INT0

XOB 20

I 8100

INT1

XOB 21

I 8101

Operation:
When there is a positive edge at input INT0, XOB 20 is called. The reaction time
up to the XOB 20 call is a maximum of 1 ms. The code in these XOBs determines
how the system should react to the events, e.g. by incrementing a counter (max.
input frequency 1kHz where pulse/pause ratio 1:1, total of the two frequencies max.
1kHz). Regardless of whether the XOB is programmed, input 8100 is set (the same
applies to INT1; see table above).
D
/D
INT0
INT1
WD
WD
7 +24V
8 GND

10k

C
CF 5272
4k7

4.7 nF

10k

2
3
4
5
6

Source operation

Input signals:
H = 15...30 V
L = -30...+ 5 V or not connected

Do not connect to D and /D. The RS-485 interface runs at 5VDC and may be destroyed.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-47

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Operating mode switch


3.19

Operating mode switch (Run/Halt)

3.19.1 Run/halt push button

The operating mode can be changed while in use or at start-up:


At start-up:
If the Run/Halt push button is pressed during start-up and then released
again during one of the sequences described below, the following actions
may be triggered:
LED sequence
Action
Orange

none

Green, flashing
(1 Hz)
Red, flashing fast
(4 Hz);
from FW >
V01.08.45

Goes into "boot" state and waits for f/w download

Red, flashing
slowly (2 Hz)
Red/green flashing (2 Hz)

The system starts in the same way as with a flat Super


CAP or missing battery, i.e. media (flags, registers etc.),
user program and hardware settings are erased. The
clock is set to 00:00:00 01.01.1990. The backup on the
onboard flash is not deleted. If a backup is present the
program will be restored.
The PLC does not start up and goes into "Stop" mode.
Stored data deleted, i.e. media (flags, registers etc.), user
program, hardware settings and the backup on the onboard flash are erased. However, if an external flash card
with a backup is present, the backup is not erased but the
program is restored and copied on the onboard flash.

In operation:
If the button is pressed in run mode for more than second and less
than 3 seconds, the controller changes to halt mode and vice versa.
If the push button is pressed for longer than 3 seconds, the last user
program saved will be loaded from flash memory.

3.19.2 Run/halt switch


Run

On the PCD3.M5xx0, it is also possible to influence the operating state


with the switch accessible on the front of the unit under the blue cover.

Stop

If the controller is switched to stop mode, this will cause a change from
run to stop; when it is switched to run, a cold start will be executed.

To release the switch, check the options in the hardware settings in PG5 (see also
hardware settings in section 7.1).

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-48

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Manual and emergency operation


3.20

Manual and emergency operation

The manual and emergency operation required in building automation can be


provided with a PCD3.C200 module holder1) and the manual control modules PCD3.
A810 (digital) and PCD3.W800 (analogue). These manual control modules are based
on digital and analogue output modules, which can be activated either via the user
program or by a manual switch.



For emergency operation, the manual control modules must be used in a


PCD3.C200 module holder with an external power supply. The external power
supply is needed to continue to use the manual control module in emergency
mode in case of a cable break or during maintenance work on the CPU.

In this PCD3.C200 module holder (from hardware version C), and possibly
others, manual control modules may be used in combination with other data
point modules.

When planning a PCD3 system, it is essential to consider the current


requirements of the data point modules in the PCD3.C200 and of the
subsequent module holders.

It is advisable to use the calculation table at www.sbc-support.com.

Manual control modules:


PCD3.A810, Digital manual control module with 4 relays, 2 with changeover contacts,
2 with make contacts (for detailed description, see Section 6.6)
PCD3.W800, Analogue manual control module with 4 output channels, 0+10 V,
10 bit resolution (for detailed description, see Section 6.14)
Installation:

CPU
Frontview

Frontview
Frontview

Frontview

connection cable

Frontview

C200 (last modul holder)

manual- and emergency


modules

pot.
further

Frontview

Frontview

Frontview
Frontview

or
installation of
further
rows

Frontview

Frontview

24 V
1

from hardware version C: no restrictions


Hardware versions A and B:
- see restrictions on current output, section 3.21.1
- PCD3.C200 at the end of the I/O bus only
- PCD3.C200 for emergency operation, and any other module holders, may
only be used with manual control modules

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-49

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Expansion housings
3.21

Module holder

Supply 24 VDC

3.21.1 Internal supply to PCD3.C200 module holders


PCD-Bus

LED
24V

PTC

DC

+5V

DC

39V

Voltagemonitor 5V

2200u F

CLR

0V
DC

V+
(16...24V)

DC

The PCD3.C200 module holders provide the following internal supply currents to the
modules plugged in or connected to them:
Type

+5V

V+
The capacity of the +V bus depends on the capacity of
the 5V bus, as follows (the more precisely the 24 VDC are
maintained, the higher the possible capacity):
1,000 mA
100 mA

PCD3.C200
Hardware versions A
and B
PCD3.C200
1,500 mA
Hardware version C


- 25 %

24 V +30 %: 200 [mA]


- 20 %

I 5 V bus
[mA]
15

- 10 %

I 5 V bus
[mA]
3.8

24 V +25 %: 310 -

24 V +10 %: 630 -

When planning PCD3 systems, it is essential to check that the two internal supplies
are not overloaded. This check is especially important when using analogue, counter
and positioning modules, as these may have a very large power consumption.
It is advisable to use the calculation table at www.sbc-support.com.
3.21.2 LIO module holders

PCD3.LIOs (local I/Os) are used to capture central I/O signals. The compact
PCD3.LIOs are snapped onto a 35-mm DIN rail and fitted with PCD3 I/O modules.
PCD3.LIOs can be connected as an I/O extension to a PCD2 CPU, PCD3 CPU or a
PCD3.RIO. Three different module holders are available to take the I/O modules:

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-50

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Expansion housings
LIO module
holder
PCD3.C100
PCD3.C110
PCD3.C200

Module Description
slots
4
2
4

for 4 I/O modules


for 2 I/O modules
for 4 I/O modules; acts as I/O bus repeater
and provides internal +5V and V+ for a
segment of I/O modules (for calculation of
possible capacity, see 3.20.1).

Ext. supply

24 VDC

Int. supply
I at +5 V
10 mA
10 mA

PCD3.C100/C110

4 or 2 plug-in PCD3 I/O modules (selectable)

May be connected to PCD2.Mxxx, PCD3.Mxxx0, PCD3.RIO and PCD3.LIO

PCD3.C100 expandable with PCD3.LIO (C110, C200); PCD3.C110 not
expandable

PCD3.C200

4 plug-in PCD3 I/O modules (selectable)

May be connected to PCD2.Mxxx, PCD3.Mxxx0, PCD3.RIO and PCD3.LIO

May be expanded with PCD3.LIO (C100, C110, C200)

Serves as a bus repeater and provides + 5 V and V+ internally for a segment of

I/O modules

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-51

PCD3.Mxxx0 Classic CPUs and expansion housings

Saia-Burgess Controls AG

Expansion housings
3.21.3 Connections to PCD3.Cxxx LIO module holders

PCD3.C200 for 4 modules


Bus connection
from PCD2 or PCD3

Bus connection
to PCD3

F rontview
F rontview

0V +24V
Power

PCD3.C200

Supply 24VDC

Power ok
Ground

PCD3.C100 for 4 modules


Bus connection
from PCD3

Bus connection
to PCD3

F rontview
F rontview

Power

PCD3.C100

Power ok
Ground

PCD3.C110 for 2 modules


Bus connection
from PCD3

F rontview

Power

PCD3.C110

Power ok
Ground

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

3-52

RIO (remote input/output) head stations

Saia-Burgess Controls AG

Internal supply to PCD3.T76x head stations

RIO (remote input/output) head stations

4.1

Internal supply to PCD3.T76x head stations

Supply 24 VDC

PCD-Bus

LED
24V

PTC

DC

+5V

DC

39V

Voltagemonitor 5V

2200u F

CLR
0V

DC

V+
(16...24V)

DC

The PCD3.T76x head stations provide the following internal supply currents to the
modules plugged in or connected to them:
Type

PCD3.T76x

+5V

650 mA

V+
The capacity of the +V bus depends on the capacity of
the 5V bus, as follows (the more precisely the 24 VDC are
maintained, the higher the possible capacity):

24 V

24 V

- 25 %
+30 %:

100 [mA]

I 5 V bus
[mA]
15
- 10 %
I 5 V bus
[mA]
24 V +10 % : 275 - 4
- 20 %
+25 % :

150 -

When planning PCD3 systems, it is essential to check that the two internal supplies
are not overloaded. This check is especially important when using analogue, counter
and positioning modules, as these may have a very large power consumption.
It is advisable to use the calculation table at www.sbc-support.com.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

4-1

RIO (remote input/output) head stations

Saia-Burgess Controls AG

RIO head station module holders


4.2

RIO head station module holders

PCD3.RIOs (remote I/Os) are used to capture decentralized I/O signals. PCD3.RIOs
communicate with Profibus-DP or any SPS Master; the .gsd file is included in Saia
PG5 (version 1.2 or above), or it can be retrieved from www.sbc-support.com.
The web server integrated into PCD3.RIOs offers the user great benefits in
commissioning, diagnostics and service. Access is via familiar easy-to-use standard
web browsers. This makes it easy to check the states of all I/O signals (digital/
analogue/counters), and to modify specific output states.
RIO head
stations
PCD3.T760

Module
slots
4

Description
For 4 I/O modules with Profibus DP and
S-Net connection
Supply to integrated +5V and V+ Bus
for a segment of I/O modules (for
calculation of possible load, see 4.1)

Ext.
supply
24 VDC

PCD3.T760

Integrated Profibus DP and S-Net connection up to 1.5 Mbps

4 plug-in PCD3 I/O modules (selectable)

May be expanded with PCD3.LIO

Integrated web server for diagnostics, service and commissioning

Provides internal +5V and V+ for the I/O modules on the PCD3.T760 and the

attached PCD3.C1x0 units

Option to expand a RIO head station with up to 3 LIOs


Number of inputs/outputs or I/O
module sockets:

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

256
16

4-2

RIO (remote input/output) head stations

Saia-Burgess Controls AG

Connections to PCD3.T76x RIO head station for 4 modules


4.3

Connections to PCD3.T76x RIO head station for 4 modules


Supply 24VDC

DIP Switch for PROFIBUS address


RS-232

Ground
Bus connection
to PCD3.LIO's

PROFIBUS

4
1 3 5
2 4 6

Frontview

Power

PCD3.T76_

0V +24V
Run

BF

Diag

Power ok
Status LED's

Meaning of connections
Profibus-DP or Profi-S-Net network connection

The bus is set up for


baud rates up to 1.5
Mbps. More detailed
specifications can be
found in manual 26/765

1
2
3
4
5
6
7
8
9

"Profibus-DP.

On a PCD3.M3 or PCD3.
M6 (orange terminal block)
corresponds /D to the pin3
(RxD / TxD-P, red) and D
to the pin 8 (RxD / TxD-N,
green).

PGND
GND
B = RxD/TxD-P | Red = /D
CNTR-P
SGND
+5V-Ext
24VDC
A = RxD/TxD-N | Green = D
NC

Serial interface RS-232


This connection supports
configuration with a browser
such as Internet Explorer or
Netscape Navigator (with PCD3.
K225 connecting cable).

1 3 5
2 4 6

Expansion connection
This connection allows the RIO
to be expanded with up to 3 LIO
module holders (with PCD3.
K010 connector). This means
that up to 256 I/Os can be set up
per RIO.

1
2
3
4
5
6

TXD
RTS
RXD
CTS
PGND
DSR

Frontview

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

4-3

RIO (remote input/output) head stations

Saia-Burgess Controls AG

Connections to PCD3.T76x RIO head station for 4 modules


Setting the Profibus address
The Profibus address on the PCD3.T760 is set as a binary value using a DIP switch.
The numbers on the DIP switch have the following values assigned:
MSB

LSB

1=1
Address
2=2
set to 73
3=4
1
2
3
4
5
6
7
8
4=8
5 = 16
6 = 32
OP E N
7 = 64
8 = not used
Example for address 73: DIP switch nos. 1 + 4 + 7 ON.

Meaning of LEDs
Power yellow
Run green
BF red
Diag yellow

Supply on
RIO processor running
Bus error
Diagnostics running: permanently on: - more than 4 I/O modules


configured, but no PCD3.Cxxx


- Profibus address is 0

2 x flashing:
Load EPROM with configuration

5 x flashing:
Min. one I/O is locked

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

4-4

RIO (remote input/output) head stations

Saia-Burgess Controls AG

Diagnostic information on RIOs


4.4

Diagnostic information on RIOs

LEDs
These three LEDs on the PCD3.T76x head station display the operating
states - error, alert, diagnostics etc. The LEDs are used as described in
the table below.

Run green
BF red
Diag yellow

RUN
OFF
ON
ON
OFF

BF
ON
OFF
OFF
ON

DIAG
OFF
OFF
ON
ON

OFF

ON

ON

OFF

flashing
5x
flashing
2x
flashing
2x

Explanation
Bus error, Slave not assigned to any Master
Slave working correctly
Diagnostic / alert from Slave
Bus error, Slave not assigned to any Master, but
configured and in a diagnostic state
At least one Lock active

Current configuration comes from EEPROM or web server


Current configuration comes from EEPROM; Master has
the same configuration and is connected

DP diagnostics
The PCD3.T76x provides Profibus-DP with standard diagnostics in octets*) 16. See
also DIN 19245 part 3
*) In DIN 19245 a byte is called an octet, so the same term is used here.
Standard diagnostics:
Byte
1

4
5, 6

Bit
0
1
2

Abbreviation
non_exist
station_not_ready
cfg_fault

3
4
5
6
7
0
1
2
3
4
5
6
7
06
7

ext_diag
invalid_slave_response
prm_fault
master_lock
prm_req
stat_diag
wd_on
freeze_mode
sync_mode
slave_deactivated
ext_diag_overflow
Master address
ID (0xCD32)

Explanation
Slave does not exist (Master set)
Slave not ready to exchange data
Configuration data for Master and Slave
differ
Extended diagnostic bytes
Always set to "0" by Slave
Incorrect parameter
Slave parameterized via a master
Slave must be re-parameterized
Static diagnosis
Always 1
Watchdog monitoring on
Freeze instruction on
Sync instruction on
Spare
1 when Slave deactivated by Master
Spare
Diagnostic data overflow in Master or
Slave

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

4-5

RIO (remote input/output) head stations

Saia-Burgess Controls AG

Diagnostic information on RIOs


Extended diagnostics:
1) Power failure on a PCD3.C200 or defective cable to a PCD3.C1x0
Byte
7
8

Bit
0x02
0xFF

Explanation
Device-related diagnostics, 2 bytes (incl. header byte)
External power failure, defective cable to a PCD3.C1x0 or power
failure in a PCD3.C200

2) Error accessing an I/O module


Byte Bit
7 (9) 0x43
8 (10) 0
.
.
7
9 (11) 0
.
.
7

Explanation
Identification-related diagnostics, 3 bytes (incl. header byte)
Error accessing module 0
.
.
Error accessing module 7
Error accessing module 8
.
.
Error accessing module 15

Both diagnostic messages may be sent in the same telegram. In this case, the entries
described above will be packed together in one frame, i.e. the identification-related
diagnostic message will start with Octet 9 and end with Octet 11.
4.4.1

Diagnostic module

In addition to DP-compliant diagnostic information, the PCD3.RIO also supports


a Diagnostic module integrated into the DP configuration. This Slave diagnostic
informationen is stored in the Master resources. The use of a Diagnostic module is
not mandatory. This Diagnostic module must however be configured after the last
I/O module (exception: plug-ins must be configured after the Diagnostic module). It
requires 4 input bytes and 4 output bytes. The precise defintion of query and reply is
as follows:
MasterRIO
Byte 0

Byte 1

Byte 2

Byte3
Query

RIOMaster
Byte 0

Byte 1

Byte 2

Byte3
Reply

The content of bytes 0 to 2 is dependent on the query instruction. The Master always
checks that the reply instruction matches the query instruction and so ensures that
the details are correct and belong to the information requested.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

4-6

RIO (remote input/output) head stations

Saia-Burgess Controls AG

Diagnostic information on RIOs


Instruction 0: NOP instruction
This instruction is used for synchronization. The RIO returns the data bytes
unchanged.
MasterRIO
Byte 0

Byte 1

Byte 2

Byte3

Byte 0

Byte 1

Byte 2

Byte3

RIOMaster

Instruction 1: Query firmware version


This function is used to obtain the current firmware version for the RIO.
MasterRIO
Byte 0

Byte 1

Byte 2

Byte3

irrelevant

irrelevant

irrelevant

Byte 0

Byte 1

Byte 2

Byte3

highest version

lowest version MSB

lowest version LSB

RIOMaster

Instruction 2: Query RIO status


This function is used to obtain the current status of the RIO.
MasterRIO
Byte 0

Byte 1

Byte 2

Byte3

irrelevant

irrelevant

irrelevant

Byte 0

Byte 1

Byte 2

Byte3

Status 0

Status 1

Status 2

RIOMaster

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

4-7

RIO (remote input/output) head stations

Saia-Burgess Controls AG

Diagnostic information on RIOs


Coding of bits in Status 0:
Bit
7
6
5
4
3
2
1
0

Explanation
DIAG LED: Set when diagnostic information is present
Set in case of power failure on the external I/O Bus
Set when valid configuration present in EEPROM
Set when Clear instruction received from Slave
Set when a Lock is on
Spare
Spare
Spare

Coding of bits in Status 1 and 2 not yet defined.


Instruction 3: State of outputs in case of bus error
MasterRIO
Byte 0

Byte 1

Byte 2

Byte3

Value of MSB

Value of LSB

Module position

Byte 0

Byte 1

Byte 2

Byte3

Status

Module position

RIOMaster

Function 3 defines the preferred state of the outputs. This preferred state is selected
when

the connection to the bus is broken


the Master is in a STOP/HALT state

The status is 0 when the selection has been accepted; otherwise it is set to 0xFF.
The coding of the module position field is as follows:
Bits 03: Module position (015)
Bits 46: Channel number (07). On analogue outputs, this is the analogue
channel
Bit 7:
If set (continue), the last state of the outputs is retained. In this case,

bytes 0 and 1 are irrelevant.
Example: Module position = 0x82Retain the outputs (if 16 digital outputs, then the 8
LSBs) for module position 2 (3rd position).
In case of a bus error, or in STOP mode, the default switch-off status sets all outputs
to 0.
For analogue outputs, this does not mean that the value of all outputs is "0".

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

4-8

RIO (remote input/output) head stations

Saia-Burgess Controls AG

Diagnostic information on RIOs


Instruction 4: Resetting the preferred switch-off state of the outputs
MasterRIO
Byte 0

Byte 1

Byte 2

Byte3

irrelevant

irrelevant

irrelevant

RIOMaster
Byte 0

Byte 1

Byte 2

Byte3

irrelevant

irrelevant

irrelevant

Function 4 sets the preferred switch-off state for all outputs to a pre-defined value,
e.g. 0

Instruction 5: Store I/O configuration in EEPROM


MasterRIO
Byte 0

Byte 1

Byte 2

Byte3

irrelevant

irrelevant

irrelevant

Byte 0

Byte 1

Byte 2

Byte3

irrelevant

irrelevant

irrelevant

0x85/0x05

RIOMaster

Function 5 stores the configuration in EEPROM, so that the user can use the web
browser to go online without a Master after switching on the power, and test his/her
configuration without redefining it.
This asynchronous function takes a few milliseconds, depending on the scope of
the configuration. While writing to the EEPROM, the value 0x85 is displayed in the
Diagnostic module. While the instruction is being processed, no new instruction will
be accepted.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

4-9

RIO (remote input/output) head stations

Saia-Burgess Controls AG

Profibus-DP or Profi-S-Net network line termination resistors


4.5

Profibus-DP or Profi-S-Net network line termination resistors

To prevent reflections at the line-ends, every segment must be terminated at the


physical extremity of its line.
This means that the lines are biased at the equilibrium rest potential.
According to the Profibus standard, this must not be done directly on Profibus
devices, but must be achieved by means of external components.
Both the PCD7.T160 termination box and commercially available 9-pole Profibus
D-Sub connectors are suitable for this purpose; for more details, see manual 26/740
"Installation components for RS-485 networks" and 26/765 "Profibus-DP.

Network termination should therefore be as follows:


9

R390

R390

Frontview

R220

1
3
4
5
6
8
9

Shield
RxD/TxD-P
CNTR-P
DP GND
DP +5V
RxD/TxD-N
CNTR-N

Supplier for 9-pole Profibus D-Sub connectors to connect Saia PCD controllers to
Profibus networks:
ERNI Elektrotechnik AG, Brttisellen, Switzerland:


ERbic junction, horizontal grey:


(junction fitted with series inductance
of 110 nH)

ERbic junction, horizontal grey:


with PG connector:
(junction fitted with series inductance
of 110 nH)

ERbic termination, horizontal yellow:


(junction fitted with series inductance
of 110 nH plus termination resistors
of 390 and 220 )

Erni Ref. 103648

Erni Ref. 103663

Erni Ref. 103649

ERNI ERbic connector

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

4-10

Communication interfaces

Saia-Burgess Controls AG

Summary of onboard interfaces and plug-in interface modules

Communication interfaces
SBCS-Net, the networking concept from Saia Burgess Controls, is based on the
Profibus and Ethernet open standards. Ethernet covers layers 1 and 2 of the ISO
layer model. Based on layer 2, a variety of different protocols and applications can be
run in parallel on the same network.
Layer 2 (Field Data Link-FDL) from Profibus also allows parallel running of different
application protocols such as DP, FMS and others. The use of this facility allows
Profi S-Net to be used to create a "Private Control Network (PCN)". This makes all
SBC units into active network components.
Profibus Layer 2 (FDL) is integrated into the operating system of the PCD3.Mxxx0
CPUs and the PCD3.T76x RIOs, giving these units a Profi S-Net connection with
transmission speeds up to 1.5 Mbps.

These units support Profibus DP and S-Net on the same port. In this way, Profibus
can be used to construct networks cheaply and flexibly (detailed notes can be found
in TI 26/381).
Since summer 2010 the PCD3 family (PCD3.M2xxx, PCD3.M3xxx, PCD3.M5xxx and
PCD3.M6xxx) do support the full-duplex mode and Auto-MDIX on the Ethernet port.
The easiest way to detect whether a PCD3 features the full duplex mode as well as
Auto-MDIX is checking whether the RJ-45 plug is equipped with LEDs. If it is, the
Saia PCD supports the full duplex mode as well as the Auto-MDIX feature (autocrossing the signals).
In detail the following hardware version or later are required in order to support full
duplex and Auto-MDIX:

The PCD3.M3xxx, PCD3.M5xxx and PCD3.M6xxx since hardware F.

The PCD3.M2x30A4T1 and PCD3.M2x30A4T3 since hardware B.

The PCD3.M2x30A4T5 since hardware C.

Using the SBC S-Bus

The proprietary SBC S-Bus has been designed essentially for communication with
the engineering and debugging tools, and for connecting the management
level/process control systems.
It is neither suitable nor approved for the connection of field devices from
diverse manufacturers. An open, vendor-neutral fieldbus will be more effective in
achieving this end.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-1

Communication interfaces

Saia-Burgess Controls AG

Summary of onboard interfaces and plug-in interface modules


5.1

Summary of onboard interfaces and plug-in interface modules


PCD3.M5540

S-Net/MPI
(Port 10)
RS-232/PGU (Port 0)

Slot 0 (Port 1)

PCD3.M3330

USB
Ethernet (Port 9)
RS-485 (Port 2)

The easiest way to determine whether the device supports full-duplex mode or not, is
to control if the RJ-45 connector is equipped with LEDs (left side in the picture).

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-2

Communication interfaces

Saia-Burgess Controls AG

Summary of onboard interfaces and plug-in interface modules

115.2kBit/s
187.5kBit/s

10/100MBit/s

Ethernet
USB 1.1 Slave (PGU)

12 MBit/s

Plug-in communication interfaces


Port 10
Port 0

Port130&131

Port120&121

Slot

Port110&111

PCD3.F110
PCD3.F121
PCD3.F130
PCD3.F150
PCD3.F180
PCD3.F210
PCD3.F221
PCD3.F281

Port 1

USB

Port 3 (M5340)

Slot

Port 2
Port 9

Port1

I/O
communication
modules

Port100&101

5.1.2

PCD3.M6540

2
2

PCD3.M6440

Terminal block
RS-485
Profi-S-Net/DP Slave

PCD3.M6340

PCD3.M6240

115.2kBit/s
115.2kBit/s
1.5 MBit/s

PCD3.M5540

3
3
10
10
10

PCD3.M5440

D-Sub #2
RS-485 (serial)
RS-422 (serial)
Profi-S-Net/DP Slave
CAN
Profibus DP Master

PCD3.M5340

PCD3.M3330

115.2kBit/s

PCD3.M3230

PCD3.M3120

D-Sub #1 (PGU)
RS-232

Onboard interfaces

PCD3.M3020

max. baud
rate

Onboard interfaces
Port (in PG5)

5.1.1

Port
100
-----Port
101

Port
110
-----Port
111

Port
120
-----Port
121

Port
130
-----Port
131

Slot 0...3

Applies to all PCD3.CPUs

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-3

Communication interfaces

Saia-Burgess Controls AG

Protocols on serial ports


5.2

Protocols on serial ports

5.2.1

Protocols supported by the firmware

PCD3.M5440 /
M6440

PCD3.M5340 /
M5540 / M6540

Supported by
PCD3.M3330/
M3120

Purpose

PCD3.M3020 /
M3230

Protocol overview and


firmware support for
the different CPUs

S-Bus PGU on USB


Programming, debugging, visualization. Also
connector with USB or PGU allows access via gateway to stations within a
port
different S-Bus network

S-Bus PGU on the PGU


RS-232 connector (with
Pin 6 (DSR) of the PGU
connector set to logical 0
(Data, Full Protocol)) 1)
Serial S-Bus protocol
(Data, Parity) 3) 6)

Programming, debugging, visualization. Also


allows access via gateway to stations within a
different S-Bus network

Supports the S-Bus protocol on serial


interfaces (RS-232, RS-485/422, USB, modem)
in Master/Slave operation.

Character mode (MC0 to


MC5) 4)

Transmission of characters or text over serial


ports; basis for creating own protocols in the
user program

Profi S-Bus protocol

2)

2)

Exchange of data with multi-master


communication between controllers. Also
allows access from PG5 programming unit,
SBCOPC server or web browser

Profi S-IO protocol

For PCD3.RIO operation. Enables configuration


and diagnostics, and management of C plugins

Ether S-Bus protocol

Exchange of data with multi-master


communication between controllers. Also
allows access from PG5 programming unit,
SBCOPC server or web browser

Ether-S-IO protocol5)

For PCD3.RIO operation. Enables configuration


and diagnostics, and management of C plugins

MPI

Multi-point protocol for exchange of data with


other devices (SBC xx7 controllers, HMI,
SCADA systems)

1) Requires the use of programming cable PCD8.K111


2) Requires a corresponding configuration in hardware settings
3) Requires an assignment of the port in the user program (SASI). For new applications, Data mode should always be
selected.
4) RS-485 with immediate releae of data line after transmission of last character
5) In preparation
6) S-Bus Parity Master Mode (SM1) not supported on Port 0 and 3 (from FW 010)

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-4

Communication interfaces

Saia-Burgess Controls AG

Protocols on serial ports


5.2.2

Serial-S-Net

Supports the S-Bus protocol on serial interfaces (RS-232, RS-485/422, USB, modem)
in Master/Slave operation. The SBCS-Bus with its simple and secure protocol is part
of the basic set up of all Saia PCDs.
Technical data
Transmission rates:

Number of stations:

Up to 115 kbps on S-Bus protocol, high net data rates


because of low protocol overhead
Up to 254 stations in segments of 32 stations each

Port in PG5:

0, 1, 2, 3,100, 101, 110, 111, 120, 121, 130, 131

5
5.2.3

Profi-S-Net

The Private Control Network" (PCN) includes all protocols and services for operating
SBC units (SPS, RIO, HMI, PG) on the Profibus. Supports multi-protocol operation on
the same connector and cable.
Technical data

5.2.4

Transmission rates:
Number of stations:
Protocols:

Up to 1.5 Mbps
Up to 124 stations in segments of 32 stations each
Profi-S-Bus, Profi-S-I/O, DP Slave, HTTP

Port in PG5:

2 and 10

Ether S-Net

The Private Control Network" (PCN) includes all protocols and services for operating
SBC units (SPS, RIO, HMI, PG) on the Ethernet. Supports multi-protocol operation
(S-Bus, S-IO, HTTP, SMTP) on the same connector and cable.
Technical data
Terminals:

Speed:

Protocols:

Port in PG5:
5.2.5

10 Base-T/100 Base TX (RJ-45)


10/100 Mbps (auto-sensing)
TCP/IP or UDP/IP, Ether-S-Bus, Ether-S-I/O, HTTP,
SMTP
9

Protocols implemented in the user program

Based on Character mode (and a very good knowledge of LI programming), any


desired protocols can be implemented.
Our system partners have already done this for a large number of protocols, enabling
our controllers to communicate with components from a variety of manufacturers, e.g.
via Modbus, M-Bus etc.
Please refer to the Links page at www.sbc-support.com for links to system partners.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-5

Saia-Burgess Controls AG

Communication interfaces
USB PGU interface

5.3

USB PGU interface for connecting programming units

In order to use the USB interface (type B) on the PCD3.Mxxx0, PG5 version 1.3.100
or later must be installed.
When the PCD3.Mxxxx is first connected to a PC via the USB interface, the PC
operating system automatically installs the appropriate USB driver
To establish a connection with a Saia PCD via USB, the following settings must be
entered in the online settings for the PG5 project:

Activating the PGU option ensures that the PCD3.Mxxxx connected directly to the PC
can be reached, regardless of the S-Bus address that has been configured.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-6

Communication interfaces

Saia-Burgess Controls AG

RS232 connector (Port 0) as communication interface


5.4

RS-232 connector (Port 0) as communication interface and as


connection for programming unit (PCD3.M5xx0/M6xx0 only)

This interface is via a 9-pole D-Sub connector (female). The interface is of type RS232.
The pin configuration and associated signals are:
Pin
1
2
3
4
5

Designation
DCD
RXD
TXD
DTR
GND

Meaning
Data carrier detect
Receive data
Transmit data

[Empfangsdaten]
[Sendedaten]

Signal ground

[Signalerde]

6
7
8
9

DSR
RTS
CTS
n.c.

PGU connected
Request to send
Clear to send
Not connected

[Erkennung PGU]
[Sender einschalten]
[Sendebereitschaft]
[Not used]

The interface can be used for the following purposes:


Option 1:

Configuration with desired protocol


(S-Bus PGU configuration)

Option 2:

Assignment (SASI) in the user program


(the port must not be configured as an S-Bus PGU port)
If another programming device is connected during operation
instead of the peripheral device, the unit will switch over
automatically to PGU mode (pin 6 logical 1 (DSR); in PGU
mode: DSR PING = 1)
Before using the port to connect another peripheral device, Port
0 must be reconfigured by means of an SASI instruction.

PGU-Plug
D-SUB 9 pol.
(female)
DCD
1
RXD
2
TXD
3
4
5
6
7
8
9

Cable

GND

Peripheral
PGD
RX
TX
SGN

RTS

RTS

1)

CTS

CTS

1)

+5V (just for PGU)

) When communicating with terminals, check whether some connections are


provided with bridges or need to be set to "1" or "0" with the "SOCL" instruction. It is
generally recommended to use a handshake (RTS/CTS) (see also manual 26/795
"PCD7.D23x Series graphic terminals").
1

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-7

Communication interfaces

Saia-Burgess Controls AG

RS232 connector (Port 0) as communication interface


Option 3:


Port 0 can also be used as a modem port with a 1-to-1 cable. For this,
the Full RS-232 handshaking on Port 0 should be ticked, as described
in section 7.1.2 "Hardware options".

Option 4:

With the PCD8.K111 connecting cable, this interface can be used to


connect a programming unit.

PCD8.K111 connecting cable


D-SUB 9 pol.
(female)
1
2
3
4

PC

5
6
7
8

D-SUB 9 pol.
(male)

RX

RX

TX

TX

DTR
SGN

SGN
DSR

RTS

RTS

CTS

CTS

1
2
3
4
5
6

PCD

7
8
9

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-8

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module Slot 0


5.5

Serial interfaces on I/O module Slot 0 (Port 1)

5.5.1

General remarks on the PCD3.F1xx

System properties of PCD3.F1xx modules:


The following points must be observed when using the PCD3.F2xx interface modules:

For each Saia PCD system, 1 PCD3.F1xx module can be used on Slot 0.

The PCD3 system has a powerful processor which handles the application as
well as the serial interfaces. Processing of the interface modules requires the
appropriate CPU capacity. To determine the maximum communication capacity
per PCD3 system, note the following:

The communication volume is determined by the peripheral devices connected.


This will be the case, for example, where a PCD3 is used as an S-Bus slave
station. If a PCD3 controller is bombarded with heavy telegram traffic at high
baud rates, less CPU capacity will be left to handle the actual application.

If the PCD3 is the initiator of the communication, the communication volume,


and hence the communication capacity, will be determined by the user program
in the PCD3 (PCD3 used as master station). Theoretically, all interfaces can be
run at the maximum baud rate of 115kbps.
However, the effective data throughput will be governed by the user program
and the number of interfaces, and may be quite low. The crucial factor is that
the peripheral devices connected can be run with the selected configuration
and communication capacity.

Current
consumption
Module
PCD7.F110
PCD7.F121
PCD7.F130
PCD7.F150
PCD7.F180

+5 V bus
[I in mA]
40
15
5
130
15

The PCD3.F1xx base module consumes < 10 mA.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-9

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module Slot 0


5.5.2

RS-422/485 with PCD3.F110

PCD7.F110:
RS-422 with RTS/CTS or RS-485 electrically connected,
with line termination resistors capable of activation, for
I/O modiule Slot A To move the jumper (activate line
termination resistors), the module housing has to be
opened, as described in section 6.1.5 Open the module
housing, to reach the PCD7.F110 circuit board.

RXD

Yellow

n.r.

Yellow

n.r.

Yellow

n.r.

Yellow

n.r.

Yellow

n.r.

Module
Green
inserted
n.r. = not relevant

Example for RS-485

RS-422

0
1
2
3
4
5
6
7
8
9

1
1
0

PGND
TX
/TX
RX
/RX
PGND
RTS
/RTS
CTS
/CTS

RS-485

GND
RX-TX
/RX-/TX

PCD3.F110 A
RS-422 / RS-485

TXD

Yellow

Bus RS-485

Only pluggable
on slot #0

Signal

Yellow

PGND
RX - TX
/RX - /TX

Bus RS-485

PCD7.F110

Descriptionlabel

LEDColour

GND

PGND
RX - TX
/RX - /TX

PCD7.F110
Backside

Addresslabel

Terminal 0

LED 0...7

J1 (=RT)

CLOSED OPEN

Connections and LEDs for RS-422/485

Terminals

Terminal 9

Choice of termination resistors


+5 V

+5 V
n

Pull up
330 Ohm

/n

/n
/RX-/TX

Termination
Resistor
150 Ohm
Pull down
330 Ohm

RX-TX

/n

Segment lenght max. 1200 m


max. 32 stations

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-10

Saia-Burgess Controls AG

Communication interfaces
Serial interfaces on I/O module Slot 0

Not all manufacturers use the same connection configuration, so the data lines may
need to be crossed

At the first and last stations, jumper J1 must be set to the "CLOSED position.
At all other stations, jumper J1 must be set to "OPEN" (factory setting). The jumper is
on the connection side of the module.

For RS-422, each pair of receive lines is terminated with a 150 line termination
resistor. Jumper J1 must be left in the OPEN position (factory setting). The jumper is
on the connection side of the module.

For details, see manual 26/740 "Installation components for RS-485 networks" and
manual 26/795, "PCD7.D23x series graphics terminals".

If the PCD7.F110 is used on Port x.1 of a PCD3.F2xx, the pin allocation is as follows:
RS-422 mode
RS-422
0 PGND
Tx
1
2
/Tx
Rx
3
4
/Rx
PGND 5
6 RTS
/RTS 7
8 CTS
/CTS 9

10-pole spring terminal on PCD3.F2xx


Connection:
In RS-422 mode, the input signal lines on the PCD3.F210 must be terminated with
150 resistors.
RS-485 mode
(Electrically connected RS-485 interface)
RS-485
0 PGND Rx-Tx 1
2 /Rx3
/Tx
4
PGND 5
6
7
8 (SGD)
9

10-pole spring terminal on PCD3.F2xx


The network termination for Port x.0 can be enabled with a switch on the PCD3.F210.
The switch is marked 'O' for OPEN and 'C' for CLOSED.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-11

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module Slot 0


5.5.3

RS-232 with PCD3.F121 (suitable for modem)

PCD3.F121:
RS-232 with RTS/CTS, DTR/DSR, DCD, suitable for
modem connection, for I/O module Slot 0.

Connections and LEDs


RS-232 interface for ...

D-Sub w D-Sub m
25 pol.
9 pol.
(z.B. PC) (z.B. PC)

RXD

Yellow

RTS

Yellow

CTS

Yellow

DTR

Yellow

DSR

Yellow

DCD

Green

Module
inserted

n.r. = not relevant

F
1
2
1

0
1
2
3
4
5
6
7
8
9

2
3
4
5
7
20
6

DCD

PGND
TXD
RXD
RTS
CTS
PGND
DTR
DSR
COM
DCD

RS-232

TXD

Yellow

3
2
7
8
5
4
6

PCD3.F121

Yellow

PGND
TX
RX
RTS
CTS
SGND
DTR
DSR

Only pluggable
on slot #0

Signal

Descriptionlabel

Colour

PGND
TXD
RXD
RTS
CTS
PGND
DTR
DSR
COM
DCD

PCD7.F121

Addresslabel

LED 0...7

Terminal 0

cabel

Terminals RS-232 interface for externel modem

Terminal 9

cabel

Modem
(ETCD) DCE

PGND
TXD
RXD
RTS
CTS
PGND
DTR
DSR
COM
DCD

PGND
TX
RX
RTS
CTS
SGND
DTR
DSR

DCD

D-Sub m
25 pol.
(z.B. Zyxel)
2
3
4
5
7
20
6
8

See also manual 26/795, PCD7.D23x Series graphic terminals


If the PCD7.F121 is used on Port x.1 of a PCD3.F2xx, the pin allocation is as
follows (10-pole spring terminal on PCD3.F2xx):
RS-232
0 PGND TxD 1
2 RxD
RTS 3
4 CTS PGND 5
6 DTR
DSR 7
8 COM
DCD 9

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-12

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module Slot 0


5.5.4

Current loop with PCD3.F130

PCD3.F130:
TTY/current loop 20 mA (active or passive), for I/O module
slot 0.

TXD

Yellow

RXD

Yellow

n.r.

Yellow

n.r.

Yellow

n.r.

Yellow

n.r.

Yellow

n.r.

Module
Green
inserted
n.r. = not relevant

F
1
1
0

0
1
2
3
4
5
6
7
8
9

PGND
TS
RS
TA
RA
PGND
TC
RC
TG
RG

+
+

Only pluggable
on slot #0

Signal

Yellow

Descriptionlabel

LEDColour

PCD7.F130

Addresslabel

LED 0...7

Terminal 0

Connections and LEDs

Terminals
Terminal 9

Saia PCD active


PCD7.F130
(active)

Cable

Peripherie
(passive)

Pin-Nr.
1
Transmitter

Receiver

6
8
2

Receiver

4
7

Transmitter

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-13

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module Slot 0


Saia PCD passive
PCD7.F130
(passive)

Cable
Pin-Nr.

Receiver

1
Transmitter

Peripherie
(active)

3
6
8
2
4

Receiver

7
9

Transmitter

Saia PCD and peripheral active


PCD7.F130
(active)

Transmitter

Cable
Pin-Nr.
1
3
6

Peripherie
(active)

Receiver

8
2
Receiver

4
7
9

Transmitter

If the PCD7.F130 is used on Port x.1 of a PCD3.F2xx, the pin allocation is as


follows (10-pole spring terminal on PCD3.F2xx):
TTY (CL)
0 PGND
TS
1
2
RS
TA
3
4
RA
PGND 5
6
TC
RC 7
8
TG
RG 9

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-14

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module Slot 0


5.5.5

RS-485 with PCD3.F150

PCD3.F150:
RS-485, electrically isolated, with line termination resistors capable of activation, for I/O module Slot 0. To change
the jumper (activate line termination resistors), the module
housing has to be opened, as described in section. 6.1.5
Open the module housing, to reach the PCD7.F150 circuit board.

The electrical isolation is achieved with 3 optocouplers and a DC/DC transducer.


The data signals are protected against surges by a suppressor diode (10V). The line
termination resistors can be connected/disconnected with a jumper.

Yellow

n.r.

Yellow

n.r.

Yellow

n.r.

Yellow

n.r.

Yellow

n.r.

Module
inserted
n.r. = not relevant
Green

7
Terminal 9

F
1
5
0

0
1
2
3
4
5
6
7
8
9

Terminals

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

PGND
RX-TX
/RX-/TX

PGND

SGND

PCD3.F150

RXD

RS-485 opto-isol.

Yellow

Only pluggable
on slot #0

OFF
ON

TXD

D
/RX - /TX /D

Bus RS-485

PCD7.F150

RT

Signal

Yellow

RX - TX

PCD7.F110
Backside

Descriptionlabel

LEDColour

SBUS

RX - TX
/RX - /TX

Addresslabel

LED 0...7

Terminal 0

J1 (=RT)

CLOSED OPEN

Connections and LEDs

SGND (galv. sep.)


has to be connected with
the shield of the cable

5-15

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module Slot 0


Block diagram:
OPTO-0601

+5VE
Transmit

TXD

Receive

RXD

75176

330 Ohm

Driver
RS-485

/D
150 Ohm

RTS

EN
330 Ohm
SGND
+5V
PGND

DC
DC

+5VE
SGND

SGND

Not all manufacturers use the same connection configuration, so the data lines may
need to be crossed
The potential difference between PGND and the data lines Rx-Tx, /Rx-/Tx (and
SGND) is limited to 50V by a suppressor capacitor.
For installation details, see manual 26/740 Installation components for RS-485
networks
If the PCD7.F150 is used on Port x.1 of a PCD3.F2xx, the pin allocation is as
follows (10-pole spring terminal on PCD3.F2xx):
RS-485
0 PGND Rx-Tx 1
2 /Rx-/Tx
3
4
PGND 5
6
7
8 (SGD)
9

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-16

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module Slot 0


5.5.6

MP-Bus with PCD3.F180

PCD3.F180:
Switching module for MP bus, for I/O module slot 0.
The module has a facility to connect an MP-Bus line with 8
drives and sensors.

RXD

Yellow

n.r.

Yellow

n.r.

Yellow

n.r.

Yellow

n.r.

Yellow

n.r.
Module
inserted

Green

n.r. = not relevant

Terminal 9

F
1
8
0

0
1
2
3
4
5
6
7
8
9

PGND
MP
,MFT
,IN
,GND
PGND

MP Bus, Bellimo

TXD

Yellow

GND (A-)
MP-Bus signal line (18V in/out)
MFT-Parametrie device (MP-Bus intern)
MFT-Parametrie device detection (Input 10 kOhm, Z5V1)

PCD3.F180

Yellow

PGND
MP
,MFT
,IN

Only pluggable
on slot #0

Signal

Descriptionlabel

LEDColour

PCD7.F180

Addresslabel

LED 0...7

Terminal 0

Connections and LEDs

Terminals

If the PCD7.F180 is used on Port x.1 of a PCD3.F2xx, the pin allocation is as


follows: (10-pole spring terminal on PCD3.F2xx):
Belimo MP bus
MP
0 PGND
,MFT
,IN
2
PGND
4
6
8

1
3
5
7
9

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-17

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module Slot 0

MFT Parametrie device

Supply option
Common supply for control and drive

0
1
2
3
4
5
6

Slot

3330

LN

Controller

24 VDC
20%

drives

When using the PCD3.F180 connection module, the supply voltage to the PC control
unit must be at least 24VDC, 5 % (not the default tolerance of 20%)..
With a separate DC or AC supply to the drives, it is especially important to ensure
that the Saia PCD control unit is connected to the earth (Minus pole) of the drive
supply. The earth serves as a common base for communication.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-18

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module slots 0 - 3


5.6

Serial interfaces on I/O module slots 0 - 3

5.6.1

General remarks on the PCD3.F2xx

System properties of PCD3.F2xx modules:


The following points must be observed when using the PCD3.F2xx interface modules:
For each Saia PCD system, up to 4 PCD3.F2xx modules (8 interfaces) can be
used on slots 03.
The PCD3 system has a powerful processor which handles the application as
well as the serial interfaces. Processing of the interface modules requires the
appropriate CPU capacity. To determine the maximum communication capacity per
PCD3 system, note the following:

The communication volume is determined by the peripheral devices connected.


This will be the case, for example, where a PCD3 is used as an S-Bus slave
station. If a PCD3 controller is bombarded with heavy telegram traffic at high baud
rates, less CPU capacity will be left to handle the actual application. The following
rules apply here: the use of 8 interfaces at 9.6 kbps takes approx. 50% of CPU
capacity. Two interfaces at 57.6 kbps also take up approx. 50% of CPU capacity.
Two interfaces at 115 kbps require approx. 60% of CPU capacity.
If the PCD3 is the initiator of the communication, the communication volume, and
hence the communication capacity, will be determined by the user program in the
PCD3 (PCD3 used as master station). Theoretically, all interfaces can be run at
the maximum baud rate of 115kbps. However, the effective data throughput will
be governed by the user program and the number of interfaces, and may be quite
low. The crucial factor is that the peripheral devices connected can be run with the
selected configuration and communication capacity.
5.6.2

Communication ports on the PCD3.Mxxxx

The PCD3.F2xx modules are designed to be mounted in I/O slots 03 on a


PCD3.Mxxxx. As shown in the figure below, the I/O slots are designated as follows:
I/O slot 0: Port 100 for the x.0 port on the PCD3.F2xx module
Port 101 for the x.1 port on the PCD3.F2xx module
I/O slot 1: Port 110 for the x.0 port on the PCD3.F2xx module
Port 111 for the x.1 port on the PCD3.F2xx module
I/O slot 2: Port 120 for the x.0 port on the PCD3.F2xx module
Port 121 for the x.1 port on the PCD3.F2xx module
I/O slot 3: Port 130 for the x.0 port on the PCD3.F2xx module
Port 131 for the x.1 port on the PCD3.F2xx module

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-19

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module slots 0 - 3

Port
100
-----Port
101

Port
110
-----Port
111

Port
120
-----Port
121

Port
130
-----Port
131

PCD3.M5540

Port
100
-----Port
101
Slot 0 (Port 1)

Port
110
-----Port
111

Port
120
-----Port
121

Port
130
-----Port
131

PCD3.M3330

5
USB
Ethernet (Port 9)

S-Net/MPI
(Port 10)
RS-232/PGU (Port 0)

RS-485 (Port 2)

If a PCD3.F2xx module is inserted in I/O slot 0, port 1 cannot be used. Instead, the
PCD3.F2xx occupies ports 100 and 101.
5.6.3

Module overview

The PCD3.F2xx communication modules are designed for the PCD3.Mxxxx systems.
Each module has two serial ports, one fixed interface and a second that can be
established by the use of a PCD7.F1xx module.
PCD3.F210
Serial communication module with two
serial interfaces
Port x.0: RS-422 / RS-485

(fixed on PCD3.F210 module)
Port x.1: Slot for PCD7.F1xx module

I/O Bus
Connect
I/O Bus
Interface

Microcontroller

Port x.0
Port x.1
PCD7.F1xx
RS-232
RS-485/422
TTY
Belimo

Port x.1
2x5 Pol

C
O

Port x.0
2x5 Pol

Switch for
line termination
(only PCD3.F210)

PCD3.F221
Serial communication module with two
serial interfaces
Port x.0: RS-232

(fixed on PCD3.F221 module)
Port x.1: Slot for PCD7.F1xx module
PCD3.F281
Serial communication module with two
serial interfaces
Port x.0: Belimo MP-Bus

(fixed on PCD3.F281 module)
Port x.1: Slot for PCD7.F1xx module

PCD7.F1xx modules (for connection to Port x.1 on the PCD3.F210/221/281)


PCD7.F110 Serial interface module RS-422 / RS-485
PCD7.F121 Serial interface module RS-232, for modem connection
PCD7.F130 Serial interface module, current loop 20 mA
PCD7.F150 Serial interface module, RS-485, electrically isolated
PCD7.F180 Serial interface module for Belimo MP bus,

for max. 8 actuators and sensors

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-20

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module slots 0 - 3


Connections and LEDs
LED TxD x.0
LED RxD x.0

x.0

LED State x.0

LED TxD x.1


LED RxD x.1

x.1

LED State x.1

F
2
x
x

cage clamp x.0


10 pole (2x5)

cage clamp x.1


10 pole (2x5)

Switch for network termination


port x.0 (RS-485)
inside

Summary of connections
0
2
4
6
8

RS-232
PGND
TxD 1
RxD
RTS 3
CTS PGND 5
DTR
DSR 7
COM
DCD 9

0
2
4
6
8

RS-422
PGND
Tx
1
/Tx
Rx
3
/Rx
PGND 5
RTS
/RTS 7
CTS
/CTS 9

0
2
4
6
8

TTY (CL)
PGND
TS
RS
TA
RA
PGND
TC
RC
TG
RG

0
2
4
6
8

Belimo MP bus
PGND
MP
1
,MFT
,IN
3
PGND 5
7
9

1
3
5
7
9

RS-485
0 PGND Rx-Tx 1
2 /Rx-/Tx
3
4
PGND 5
6
7
8 (SGD)
9

Spring terminal block (supplied)


Each serial port has its own individual 10-pole spring terminal block. The F2xx
module is fitted with two spring terminal blocks, the upper one for Port x.0 and the
lower for Port x.1.
Maximum wire gauge:

1.0 mm2

AWG 18

LEDs
LED TxD:
LED RxD:
LED status:

Send data detection


Receive data detection
The "Status" LED displays the status of the serial port,
green means that the port is working properly


Both LEDs permanently red:
F2xx not running

Both LEDs green 25% / red 75%: F2xx start-up procedure

Both LEDs green 50% / red 50%: F2xx running, but no communication with
PCD3.Mxxxx

Status LED green 75% / red 25%: F2xxx running, Interface still not
assigned by the program

Status LED green 100%:

F2xxx running, Interface assigned

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-21

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module slots 0 - 3


Technical data
Communication modes supported:
MC0 Character mode, no automatic handshake
MC1 Character mode with RTS/CTS handshake
MC2 Character mode with Xon/Xoff protocol
MC4 Character mode for RS-485 interface
MC5 As MC4 with rapid switching between sending and receiving
SM1 S-Bus master, parity mode
SM2 S-Bus master, data mode
SS1 S-Bus slave, parity mode
SS2 S-Bus slave, data mode

GS1 S-Bus Gateway slave, parity mode


GS2 S-Bus Gateway slave, data mode
GM S-Bus gateway master
Gateway always via PCD3.
Baud rates supported (bits/sec):
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Current consumption:

Base module Port x.1 config.


none
PCD7.F110
PCD7.F121
PCD3.F210
PCD7.F130
PCD7.F150
PCD7.F180
none
PCD7.F110
PCD7.F121
PCD3.F221
PCD7.F130
PCD7.F150
PCD7.F180
none
PCD7.F110
PCD7.F121
PCD3.F281
PCD7.F130
PCD7.F150
PCD7.F180

+5 V bus
[I in mA]
110
150
125
190
240
125
90
130
105
120
225
105
90
130
105
115
225
105

V+
[I in mA]
0
0
0
22
0
15
0
0
0
22
0
15
15
15
15
15
15
30

Restrictions:
The PCD3.F2xx modules for the PCD3 systems offer the possibility of implementing
up to 8 additional serial interfaces. It should be noted that each additional interface
adds to the load on the PCD3.Mxxxx CPU.
The use of these 8 ports is dependent on the type of communication, the baud rate
required and the volume of data transferred. Other key factors are:



Communication on the PCD3.Mxxxx, such as Profi-S-Net, Ether-S-Net, USB


Use of the web server
Data transfer from CPU to memory
User program in the PCD3.Mxxxx

The exact system limits have still to be confirmed.


Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-22

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module slots 0 - 3

I/O Bus
Interface
(CPLD)

Power supply
3.3V

RS-232 or
RS-422/485
equipped

I/O Port
Microcontroller
ARM7
SPI
Bus
Interrupt
Input

5.6.4

SPI (Slave)
Interface
Interrupt
Output

Port x.0
serial line
driver /
receiver

UART 1

UART 2

Port x.1
serial line
interface
Slot for one
module
PCD7.F1xx

Clamp connector
Port x.1

PCD3
I/O Bus

Clamp connector
Port x.0

Block diagram

Port x.0: RS-422/485 auf Modul PCD3.F210

The PCD3.F210 module contains two different interface types on Port x.0: RS-422
with RTS/CTS and RS-485 (electrically connected). The line termination is integrated
into the module and can be enabled by means of a switch on the module. To switch
it on (activate line termination resistors), the module casing must be opened as
described in section 6.1.5 Open the module housing.
RS-422 mode
0
2
4
6
8

RS-422
PGND
Tx
1
/Tx
Rx
3
/Rx
PGND 5
RTS
/RTS 7
CTS
/CTS 9

10-pole spring terminal block


Line termination in RS-422 mode always uses 150 resistor on the PCD3.F210.
RS-485 mode
(Electrically connected RS-485 interface)
RS-485
0 PGND Rx-Tx 1
2 /Rx-/Tx
3
4
PGND 5
6
7
8 (SGD)
9

10-pole spring terminal block

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-23

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module slots 0 - 3


Connection:
+5 V

+5 V
n

Pull up
330 Ohm

/n

/n
/RX-/TX

Termination
Resistor
150 Ohm

RX-TX

Pull down
330 Ohm

/n

Segment lenght max. 1200 m


max. 32 stations

The line termination for Port x.0 is integrated into the module and can be enabled by
means of a switch on the module. On the base plate next to the switch are the codes
'O' for OPEN and 'C' for CLOSED.
5.6.5

Port x.0: RS-232 on PCD3.F221 module (for modem)

The PCD3.F221 module offers a complete RS-232 interface on Port x.0. This port is
intended mainly for modem connections such as RTS/CTS, DTR/DSR and DCD.
RS-232 connection
0
2
4
6
8

RS-232
PGND
TxD 1
RxD
RTS 3
CTS PGND 5
DTR
DSR 7
COM
DCD 9

10-pole spring terminal block


RS-232 connection to DTE:
cable
PGND
TXD
RXD
RTS
CTS
PGND
DTR
DSR
Reserve
DCD

Peripherie
device (DTE)
PGND
TX
RX
RTS
CTS
SGND
DTR
DSR
DCD

RS-232 connection to DCE:


cable
PGND
TXD
RXD
RTS
CTS
PGND
DTR
DSR
Reserve
DCD

Modem
(ETCD) DCE
PGND
TX
RX
RTS
CTS
SGND
DTR
DSR
DCD

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-24

Communication interfaces

Saia-Burgess Controls AG

Serial interfaces on I/O module slots 0 - 3


5.6.6

Port x.0: Belimo MP-Bus on module PCD3.F281

The PCD3.F281 module offers a complete Belimo MP-Bus interface on Port x.0. An
MP-Bus with up to 8 drives and sensors can then be connected to Port x.0.
Belimo connection
0
2
4
6
8

Belimo MP bus
PGND
MP
1
,MFT
,IN
3
PGND 5
7
9

10-pole spring terminal block

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-25

Saia-Burgess Controls AG

Communication interfaces
LIOs and RIOs

5.7

LIOs and RIOs

The description of the interfaces for the PCD3.Cxxx and Txxx can be found in the
sections on chaptre 3. "PCD3.Mxxxx Classic CPUs and extension housings" and
chapter 4."RIO (remote input/output) head stations".

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

5-26

Saia-Burgess Controls AG

Input/output (I/O) modules


Overview

Input/output (I/O) modules

All I/O-modules for the series PCD1 | PCD2 and PCD3 are described in the manual
27-600.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

6-1

Saia-Burgess Controls AG

Configuration
CPUs

Configuration

7.1 CPUs

This section assumes that the user is familiar with the PG5 software. If not, please
refer to Manual 26/733 PG5.
7.1.1

Configuring the Saia PCD with Saia PG5

Connecting the Saia PCD to the configuration with PG5:

Start up PG5 1.3


Create new project:

Click on New

The New Project dialogue is displayed

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-1

Saia-Burgess Controls AG

Configuration
CPUs

Creating and opening a new project.


The dialogue box is brought up via File/New Project. The size of the dialogue box can be
changed by dragging the bottom right corner or by dragging the frame.
Project Name
Name of the project to be
created. This is used as the
directory name for the project. It
must not include any path or file
extension.
Project Directory
Directory containing the new
project. The specified project
directory is set up via Options,
Directories page. The >
button can be used to browse
for a directory.
Description
May contain up to 2000
characters of free text. The first
line of text is displayed in the
"Description" window in the
"Open Project" dialogue box.
Create CPU box
If this box is ticked, a CPU
with the same name is created
automatically (the name can
be changed later in CPU
properties). This is useful for
single CPU projects. If it is not
ticked, a project will be created
without any CPU. The New
CPU command can be used to
add a CPU.

Enter project name, e.g. First Project


Check Create CPU option
Click OK

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-2

Saia-Burgess Controls AG

Configuration
CPUs

Go to "Online Settings" and select the following options:



Channel name: S-Bus USB

Tick PGU option

Click OK

Now connect the Saia PCD to the PC via the USB cable. Ensure that the PCD is
connected to the 24 VDC supply.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-3

Saia-Burgess Controls AG

Configuration
CPUs

Go to Hardware Settings:

Click on Upload, to copy the settings from the CPU.

Click on Upload

Click OK

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-4

Saia-Burgess Controls AG

Configuration
CPUs

7
The connection of the Saia PCD to the configuration with PG5 via the PC is complete.
The hardware settings can now be changed and programming the application can
begin.
7.1.2

"Hardware settings" option

The PCD3.Mxxxx CPUs do not have any "jumpers to be set. As with earlier
SaiaPCD systems, the settings are entered in PG5 on the Hardware Settings
screen. After you have selected the desired settings, they will be loaded into the
PCD3.Mxxxx when you click Download.
If "Upload" is pressed, the current sttings for the CPU will be displayed.
Example: PCD3.M5540 settings

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-5

Saia-Burgess Controls AG

Configuration
CPUs

Reset Output Enable


If the CPU goes into Halt or Stop mode, all outputs are set to 0.
XOB 1 Enable
Where PCD3.Cxxxx module holders are used, a cable break or power outage is
displayed by calling XOB 1.
Run/Halt Switch Enable


Run
Stop

The Run/Halt switch is activated. On the PCD3.M5xx0, it is thus


possible to manipulate the operating mode with the switch that is
accessible on the front of the CPU

Full RS-232 handshaking on Port 0


This allows Port 0 to be used as a normal serial port or as a modem interface.
If this option is enabled, it will no longer be possible to communicate with the CPU
via the PGU port. This seting should only be used when the USB port or the Ethernet
connection are being used for programming.

All these options are written to the flash card when the settings are backed up.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-6

Saia-Burgess Controls AG

Configuration
RIOs

7.2 RIOs

The following description assumes that the user is familiar with the PG5 software. If
not, you are advised to read manual 26/733 "PG5".
7.2.1

Example project with Saia PG5 and Profibus-S-IO

Launch the PG5 software

Open a new project with the name NETWORK

Select CPU with the name Master

Hardware and software settings are dependent on the Saia PCD selected.

Definition of the "Master" PCD


First, the network structure has to be defined. Under Program files, open a new
file for the CPU concerned, with the name NET_Topo.sio. The file extension *.sio
identifies a Profibus-S-IO network file. After entering the file name and pressing
"Enter", the "Network Configurator" window is displayed, with the relevant file name.

Here, a PCD3 has already been selected as "Master". By pressing


Enter key, move the Saia PCD into the right half of the screen.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

or the

7-7

Saia-Burgess Controls AG

Configuration
RIOs

Set parameters

Double-clicking on the PCD3.M5xxx Profi-S-IO Master 1 icon opens a configuration


window with four tabs. The figure 1 above the name of the icon indicates the
network address of the Saia PCD.
Station tab
The Associated CPU File field is used to enter the desired CPU name. By pressing
the Existing CPU button, a specific CPU can be selected from the list. This tells
the Configurator which CPU should be mapped to the icon.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-8

Saia-Burgess Controls AG

Configuration
RIOs

Resources tab
Every communication application in the Saia PCD requires flags, registers and an
initialization text. These elements can be specified here. The Configurator normally
takes dynamic elements. Remember: Project ManagerCPUSettings
SoftwareDynamic Space.

These are the entries for this CPU; click "OK" to finish.
Confirmation:

Definition of PCD3.RIO
One PCD3.RIO has already been positioned in this window.

Double-click on the PCD3.RIO DP Slave icon.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-9

Saia-Burgess Controls AG

Configuration
RIOs

Station tab
Enter a meaningful name for the RIO node in the "Name" field. The Address field
must contain the station address set on the RIO with the DIP switch.

Parameters tab

Option to swap the Low byte with the High byte for a 16-channel I/O module.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-10

Saia-Burgess Controls AG

Configuration
RIOs

Modules tab
This window is used to define the I/O modules. At present, no module is defined; the
"Define Modules" button has to be selected.

Select a suitable module, e.g. a PCD3.A400, from the Supported modules field and
copy to the right-hand field within the window.

The bottom part of the window shows information on the copied modules under
Installed Module Configuration.
Select next module.
As the exchange of data between Master (PCD3.CPU) and Slave (PCD3.RIO) is
controlled by flags and registers, these must be mapped to the I/O modules.
The "diagnostic module" can be used to exchange diagnostic information between
Master and RIO. The use of a Diagnostic module is not mandatory. This "diagnostic
module" must be configured after the last I/O module:
detailed description in section 3.19.6.
Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-11

Saia-Burgess Controls AG

Configuration
RIOs

Clicking on the Media Map button opens a window with this name, where Saia
PCD elements and symbol names can be specified.

The user either enters the Base Address for the number of elements defined in
the Number of Media field, or enters the symbol names in the fields under Media
Name (PG5 then takes the dynamic resources from the Software Settings).
More convenient: first define the symbol name for Media Number 0, and then press
the Set Defaults button; the elements will be automatically numbered from 0 to 7.

Further RIO I/O modules can be configured in the same way.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-12

Saia-Burgess Controls AG

Configuration
RIOs

Some I/O modules can be parameterized. An example, with parameters for the
PCD3.W340:

The result is a list of all the modules required in this example.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-13

Saia-Burgess Controls AG

Configuration
RIOs

Device tab
Information on current RIO nodes

Bus tab
Information on possible transmission rates

Complete the configuration of the RIO node by pressing "OK".

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-14

Saia-Burgess Controls AG

Configuration
RIOs

The next step is to compile the configuration with the DP Configurator.

7
Acknowledge the message below with "Yes".

If an error message is returned during the compilation, all details entered for this
example should be checked from the beginning.
If everything is OK:

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-15

Saia-Burgess Controls AG

Configuration
RIOs

The Consistency check function can be used to check for possible conflicts with
other elements of the user program.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-16

Saia-Burgess Controls AG

Configuration
RIOs

7.2.2

Web server

The PCD3.T76x has an integrated web server. This can be accessed via any
standard web browser such as Internet Explorer or Netscape Navigator, and used
for commissioning and diagnostics. The connection between web server and web
browser is via RS-232 (connecting cable PC PCD3.T76x: PCD3.K225).
The web server can also be accessed via Profibus.
The web server contains predefined device-specific web pages. These pages can be
used to check and manipulate the status of digital and analogue inputs and outputs.
The web server can also be used to configure the PCD3.T76x and the modules
connected to it. Further information on the web server can be found in manual 26/790
"Web server".
Special requirements for the web server on the PCD3.T76x
The device-specific web pages for the PCD3.T76x require some special Java
functions covered by Java Machine V1.4. These Java functions are not supported by
MicrosoftInternet Explorer. The Java Machine should therefore be installed on the
PC running the Web Connect software.

Java Machine
The software can be downloaded free of charge from Sun Microsystems, Inc at:
http://java.sun.com/getjava/index.html; this also contains the whole installation
procedure. The version must be V1.4 or higher; the file size is 8 MBytes. After
installation, you will be asked whether the Java Machine is to be used with an Internet
browser; reply "Yes".
To ensure that the installation has been executed correctly, launch Explorer, go to the
"Tools" menu and select "Internet Options".

The window below will appear; select the Advanced" tab and check that the JavaSun
option is ticked:

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-17

Saia-Burgess Controls AG

Configuration
RIOs

The Java Machine installation was successful, and the Java applet can be used.
7.2.3

Device-specific web pages

Launch device-specific web pages


Connect the RS-232 interface on the PCD3.T76x to the PC with cable PCD3.K225.
To access the web server on the PCD3.T76x, first launch the Web Connect software.
For more detailed information, refer to the "Web Connect" section in manual 26/790
"Web server.

Once Web Connect is running, the device-specific web pages for the PCD3.T76x can
be retrieved by starting up the web browser. Enter the correct URL in the address
field within the web browser: http://localhost/
The screen will display a standard web page, similar to the page shown overleaf.
Now click on the link pointing to the PCD3.T76x.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-18

Saia-Burgess Controls AG

Configuration
RIOs

If no connection to the PD3.T76x has been defined, this can be rectified now, using
the Setup page: http://localhost/setup

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-19

Saia-Burgess Controls AG

Configuration
RIOs

Add new stations with the following parameters:

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-20

Configuration

Saia-Burgess Controls AG

RIOs
Clicking on the PCD3.RIO causes the device-specific web page for the PCD3.T76x to
be loaded into the web browser. Depending on the performance of the PC, this may
take between 2 and 10 seconds.
Once the Applet is running, the screen displays a window like that below. Other I/O
modules may be used, or there may be none installed as yet:
1
3
2
4
6

URL to launch the device-specific web pages for the PCD3.T76x


Command buttons
Tab selection
Directory tree
Control field
List of configured modules

URL path from the browser to launch the device-specific web pages for the
PCD3.T76x

Command button field, with buttons for configuration upload and download,
Start/Stop monitoring and EEPROM functionality.

Tab selection for communication or configuration.

Directory tree with all possible modules that can be plugged into the
PCD3.T76x

Control field with status LEDs for the PCD3.T76x.

List of possible and already configured module positions on the PCD3.T76x


(0-15)

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-21

Configuration

Saia-Burgess Controls AG

RIOs
Command buttons

Loads the current configuration of the PCD3.T76x


Loads the configuration displayed into the device-specific

web pages for the PCD3.T76x

Saves the current configuration of the PCD3.T76x to the


PCD3.T76x EEPROM

Clears the PCD3.T76x EEPROM


Clears all "locks" configured in the PCD3.T76x
Starts or stops Monitoring mode
Upload function

This function loads the PCD3.T76x configuration and displays it in the configuration
list within the device-specific web pages for the PCD3.T76x. This function is not
available in Monitoring mode.

Download function
This function loads the configuration from the configuration list into the PCD3.T76x.
This function is not available in Monitoring mode.
Where a DP-Master is connected to the PCD3.T76x, the DP-Master configuration has
priority. This applies when downloading or attempting to load a configuration into the
PCD3.T76x. In this case, it is impossible to download without losing the connection
to the Master. If the PCD3.T76x is disconnected from the network, the download can
continue.

When attempting to download a configuration while still connected to the Master, the
system displays a warning message offering the option either to disconnect from the
Master and continue with the download, or to cancel the download.

Saving to EEPROM
This function is not available in Monitoring mode. The two configurations, in the
PCD3.T76x itself and in the device-specific web pages for the PCD3.T76x, must be
identical. This function saves the configuration from the PCD3.T76x to its EEPROM.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-22

Saia-Burgess Controls AG

Configuration
RIOs

During the save, a pop-up window is displayed, allowing the user to specify which
configuration has priority.
Selecting Configuration from EEPROM has priority means:
The PCD3.T76x will only start up if the configuration from the Master matches the
configuration stored in EEPROM. This function allows a desired I/O configuration to
be pre-defined and saved to the PCD3.T76x. The Master will only start up if it has the
same I/O configuration as the PCD3.T76x.

Selecting Configuration from Master has priority means:


The PCD3.T76x will always start up with the configuration received from the Master.
This function is normally used during commissioning, where no Master is yet
connected to the PCD3.T76x. Saving the configuration (set up in the web server) to
EEPROM allows more rapid commissioning.
The configuration stored in this way is taken as the default configuration when the
unit is connected to the Master.

Clear EEPROM
This function is not available in Monitoring mode. This function clears the whole
EEPROM, the PCD3.T76x configuration, the "lock" list and the EEPROM priority.

Clear all "locks


This function is not available in Monitoring mode. This function clears all "locks in the
PCD3.T76x RAM; the "lock in EEPROM is retained.

Start/Stop monitoring
This button enables the user to switch to Monitoring or Configuration mode. Start/
Stop monitoring is only available where the configuration in the device-specific webpages for the PCD3.T76x matches that in the PCD3.T76x itself.
Synchronizing the configuration
This tool is based on a complicated mechanism that monitors whether the
configuration in the PCD3.T76x matches that in the device-specific web pages for
the PCD3.T76x. If the two configurations are not the same, some functions, such
as Start Monitoring and Save to EEPROM", will not be available. In this case, the
buttons for these functions will be blocked, as shown on the next page.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-23

Saia-Burgess Controls AG

Configuration
RIOs

Tab selection (Configuration/Communication/Events History)


Tab selection allows the user to select within the main screen between the windows
for "RIO Configuration", "Communication" (shown below) and "Events History".

This tab displays information on the communication status of the PCD3.T76x. Most
of the information relates to Profibus-DP/Profi-S-Net communication. Device type
shows the PCD3.T76x and its firmware version. The Update button is used to update this information.
The last field allows the user to switch the PCD3.T76x into "Firmware download
mode. Typing "firmware" into this field and pressing Enter takes the PCD3.T76x into
"Firmware update mode". To return to Operating mode, it is necessary to switch the
power off and on again (POWER OFF and ON).

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-24

Saia-Burgess Controls AG

Configuration
RIOs

Events History tab


This tab displays possible disconnections between web server and web browser.

Control field
LEDs
The control field is mainly used to display the PCD3.T76x status LEDs. These show
the current status of the PCD3.T76x; see also section 4.4 "Diagnostic information on
RIOs".
Master connect/disconnect
This button to connect or disconnect the Master is mainly used to remove the PCD3.
T76x from the network, so that it does not "see" either the Master or any other device.
This is used where a different configuration from the Master is required. To prevent
conflicts, the Master must be disconnected.
The Reconnect Master button can be used to reconnect the PCD3.T76x to
the network (where the PCD3.T76x is disconnected from the network, it is not
automatically reconnected).
Two ways of reconnecting the PCD3.T76x to the network:

Reconnect Master button

Switching the supply to the PCD3.T76x off and on again. On POWER ON, the
PCD3.T76x is reconnected to the Master (default setting).

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-25

Saia-Burgess Controls AG

Configuration
RIOs

Configuring the PCD3.T76x with the web server


The I/Os on the PCD3.T76x are normally configured in the Profibus Configurator for
the Master PCD. The configuration details for the PCD3.T76x in the Master PCD are
loaded into the PCD3.T76x when communication is started up.
However, it is also possible to configure the I/Os for the PCD3.T76x directly with the
web server. This function is mainly used when commissioning an installation, where
the Master PCD is not yet connected.
This configuration is not possible in Monitoring mode.

This is the Configuration tab. On the left-hand side is the directory tree, and on the
right a list showing all the module positions on the PCD3.T76x. This can be used to
insert, remove and parameterize the modules. The configuration can then be loaded
into the PCD3.T76x; see section on "Command buttons". A configuration can also be
uploaded, modified and then downloaded again.
Add module
Select module and hold down the left mouse button to drag it to the desired module
position.
Remove module
Select module from the list and press "Delete" on the keyboard.
Set parameters for a module
Some modules have more functionality than others and need to be configured
accordingly. This applies especially to analogue modules that are able to read in
values in different formats, e.g. temperature for Pt1000, Ni1000, Pt100, Ni100, S7
format, etc.
To enter parameters, double-click on the module, or select the module and press
"Enter" on the keyboard. This is the screen to parameterize a PCD3.W500 module.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-26

Saia-Burgess Controls AG

Configuration
RIOs

When all the required parameters are set, click on "OK" to confirm or "Cancel to
undo a change.

Monitoring mode
In order to enter Monitoring mode, a configuration must first be synchronized, to
activate the Start Monitoring button; if it is not, synchronize the configuration via
Download or Upload.
In Monitoring mode, all configuration functionality is blocked: directory tree,
parameterization, upload and download of the configuration.
It is only possible to monitor the status of the I/Os. This is done by double-clicking
on the relevant module position. Depending on the module type, the modules are
displayed in different ways.
Examples of digital and analogue output modules:

To switch off monitoring, press STOP or click on the cross in the top right corner of
the window.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-27

Saia-Burgess Controls AG

Configuration
RIOs

Write values to outputs


In Monitoring mode, values can be written to the outputs. This allows an application
to be tested, provided the DP-Master is not yet connected. If the DP-Master is
connected to the PCD3.T76x, this function is useless, as the Master will immediately
overwrite all the values, and any changes made cannot be seen.
Write value:
Position the mouse over the output to be modified. Press the right mouse button to
display a context menu. The menu is different for analogue and digital I/Os.
When the function and value have been selected, the operation is executed
immediately and the value written to the output. The image is updated. There is no
record of these commands.
Analogue module:
Context menu: select Write a value.

A new window opens, to enter the desired value.

Digital module:
The context menu can be used to switch the output on or off directly.

Set 1 or Set 0 option to write directly to the output


"Locking" inputs and outputs
The "Lock I/Os" function can be used to manipulate values at PCD3.T76x input or
output, where the PCD3.T76x DP-Master is connected and sending values to the
outputs. The locked value has the highest priority. The locks are stored in the PCD3.
T76x RAM and/or EEPROM. If they are in EEPROM, they will be activated after every
POWER OFF and ON.
Lock inputs or outputs:
Position the mouse over the input or output to be locked. Press the right mouse
button to display a context menu. The menu is different for analogue and digital I/Os.
Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-28

Saia-Burgess Controls AG

Configuration
RIOs

When the function and value have been selected, the operation is executed
immediately and the value written to the input or output, regardless of what is
transmitted from the Master. The locks are held in a list within the PCD3.T76x.
Analogue module:
Context menu: select Lock a value.

A new window opens, to enter the desired value to lock the input/output.

Digital module:
The context menu can be used to lock the input or output directly.

If an I/O is locked, its status can be viewed in the


Monitoring window:
Output 1 locked ON,
Output 4 locked OFF,
Both have a lock icon to the left of the LED. For
analogue I/Os, the same icon is used.
Unlock:
Position the mouse over the locked input or output.
Press the right mouse button and select "Unlock"
from the context menu. The lock is cleared from the
PCD3.T76x lock list, and the "lock" icon disappears
from the Monitoring window.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-29

Saia-Burgess Controls AG

Configuration
RIOs

7.2.4

Application-specific web pages

The PCD3.T76x web server also allows application-specific web pages to be stored.
The description of the procedure for this is in preparation.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

7-30

Maintenance

Saia-Burgess Controls AG

Changing the battery on the PCD3.Mxxx

8 Maintenance
PCD3 components are maintenance-free, apart from some CPUs (PCD3.Mxxx0),
where the battery needs to be changed occasionally.
PCD3 components do not contain any parts that can be swapped out by the user.
If hardware problems arise, the components should be returned to Saia Burgess
Controls.
8.1

Changing the battery on the PCD3.M5xx0/M6xx0

The resources (registers, flags, timers, counters etc), and possibly the user program
and the text strings/DBs, are stored in RAM. To ensure that they are not lost and that
the hardware clock (where present) continues to run when there is a power failure,
the PCD3s are equipped with a buffer capacitor (SuperCap) or a buffer battery.
CPU type

Buffer

Buffer time

PCD3.M3xx0

Super Cap (soldered, maintenancefree)

4 hours1)

PCD3.M5xx0/M6xx0

Renata CR2032 lithium battery


+ Super Cap (soldered)

1-3 years2)

1) The total charging time is approx. 10 minutes


2) Depending on the ambient temperature; the higher the temperature, the shorter the buffer time

With new controllers, the batteries are packaged with the units, and have to be
inserted on commissioning. Observe the polarity of the batteries:

Insert CR2032 coin cells in such a way that the Plus pole is visible

CPUs with lithium batteries are not maintenance-free. The battery voltage is
monitored by the CPU. The BATT LED lights up and XOB 2 is called if


the battery voltage is less than 2.4 V


the battery is flat or shows an interrupt
the battery is missing

We recommend changing the batteries with the Saia PCD attached to the power
supply, to avoid any loss of data.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

8-1

Saia-Burgess Controls AG

Appendix
Icons

A Annex
A.1 Icons
In manuals, this symbol refers the reader to further information in this manual or
other manuals or technical information documents.
As a rule there is no direct link to such documents.
This symbol warns the reader of the risk to components from electrostatic
discharges caused by touch.
Recommendation: Before coming into contact with electrical components, you
should at least touch the Minus of the system (cabinet of PGU connector). It is
better to use a grounding wrist strap with its cable permanently attached to the
Minus of the system.

Explanations beside this sign are valid only for the Saia PCD Classic series.

la

ss
ic

This sign accompanies instructions that must always be followed.

xx

Explanations beside this sign are valid only for the Saia PCD xx7 series.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

A-1

Appendix

Saia-Burgess Controls AG

Definitions of serial interfaces


A.2

Definitions of serial interfaces

A.2.1 RS-232

Designation of signal lines:


Data lines

Signal and
response circuits

TXD

Transmit data

RXD

Receive data

RTS

Request to send

CTS

Clear to send

DTR

Data terminal ready

DSR

Data set ready

RI

Ring indicator

DCD Data carrier detect

Signals to RS-232
Signal type

Logical state

Set-point

Nominal value

Data signal

0 (space)
1 (mark)

+3 V to +15 V
-15 V to -3 V

-7 V
+7 V

Control/
message signal

0 (off)
1 (on)

-15 V to -3 V
+3 V to +15 V

-7 V
+7 V

The idle state


of the data signals = "mark"


of the control and message signals = off

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

A-2

Appendix

Saia-Burgess Controls AG

Definitions of serial interfaces


A.2.2 RS-485/422

Signals to RS-485 (RS-422)

not active
= mark

TX

2V
1V

VOL

3V /TX

e.g. Startbit

VOH

4V

space

VOZ

5V

2.5V

mark

0V
VOZ =
VOH =
VOL =

0.9 V min 1.7 V


2 V min (with load) 5 V max (without load)
-2 V -5 V

In the idle state, RS-422 is in the mark position


RS-422:
Signal type

Logical state

Polarity

Data signal

0 (space)
1(mark)

TX positive to /TX
/TX positive to TX

Control/
message signal

0 (off)
1 (on)

/RTS positive to RTS


RTS positive to /RTS

Signal type

Logical state

Polarity

Data signal

0 (space)
1(mark)

RX-TX positive to /RX-/TX


/RX-/TX positive to RX-TX

RS-485:

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

A-3

Appendix

Saia-Burgess Controls AG

Definitions of serial interfaces


RS-485 Wiring information
There are confusing screw terminal identifier terminologies around. Depending on the
manufacturer the identifiers used are in conflict to the identifiers you can find in SBC
manuals.
Converters
Some products form other manufacturers (p.e. RS-232 - RS-485 converters) are
often inversly indicated. Therefore it is sometimes necessary to cross the wires.
Converter

PCD

Rx- Tx

/Rx- /Tx/

/Rx- /Tx/

Rx- Tx

Profibus and Profi-S-I/O


Profibus

color

A=RxD /TxD-N

green

PCD7.T160
D

D-Sub 9pin on PCD Port 2 on PCD3.M3 and M6


pin 8

B=RxD /TxD-P

red

D/

pin 3

/D

Not all manufacturers use the same connection configuration, so the data lines may
need to be crossed
To guarantee error-free operation of an RS-485 network, the network should be
terminated at both ends. Cable and line termination resistors should be selected in
accordance with manual 26/740 "Installation components for RS-485 networks".

The drivers operate at 5VDC. If a higher voltage is attached, the drivers may be
destroyed.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

A-4

Appendix

Saia-Burgess Controls AG

Definitions of serial interfaces


A.2.3 TTY/current loop

Signals to TTY/current loop


Terminal 1

TS

Transmitter Source

Terminal 3

TA

Transmitter Anode

Terminal 6

TC

Transmitter Cathode

Terminal 8

TG

Transmitter Ground

Terminal 2

RS

Receiver Source

Terminal 4

RA

Receiver Anode

Terminal 7

RC

Receiver Cathode

Terminal 9

RG

Receiver Ground

Sender

Recipient

Signal type

Set-point

Nominal value

Power for logic L (space)

-20 mA to +2 mA

0 mA

Power for logic H (mark)

+12 mA to +24 mA

+20 mA

Neutral voltage to TS, RS

+16 V to +24 V

+24 V

Short circuit power on TS, RS

+18 mA to +29.6 mA

+23.2 mA

The idle state of the data signals = "mark"


By wiring to the cable connector, the user selects either an "active" or "passive"
circuit.

The max. transmission rate for TTY/current loops at 20 mA is 9600 bps.

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

A-5

Appendix

Saia-Burgess Controls AG

Order details
A.3

Order details

Type

Description

Weight


Base units for 4 I/O modules
PCD3.M3020
CPU with 128 KByte user program memory

Backup with internal flash memory, USB port for PG5

max. 64 digital I/Os (not expandable), 2 interrupts, web server
RS-485 for Profi-S-Net or S-Bus
PCD3.M3120
asPCD3.M3020 plus Ethernet TCP/IP
PCD3.M3230
CPU with 256 KBytes user program memory

Backup with internal flash memory, USB port for PG5

max. 1,023 digital I/Os, 2 interrupts, web server
RS-485 for Profi-S-Net or S-Bus
PCD3.M3330
asPCD3.M3020 plus Ethernet TCP/IP
PCD3.M5340
CPU with 1 MByte user program memory, 1 MByte onboard Flash memory

for backup, up to 1,023 digital I/Os (with PCD3.Cxxx), 2 interrupts, web server

USB port for PG5, RS-232, RS-485 for Profi-S-Net and RS-485 for S-Bus,

Ethernet TCP/IP, Run/Stop switch, 2 sockets for PCD7.Rxxx, data backup

13 years with lithium battery
PCD3.M5440
CPU with 512 KBytes user program memory, with Run/Stop switch

Backup option with PCD7.R500 flash card, USB port for PG5

max. 1,023 digital I/Os, 2 interrupts, web server

RS-232, RS-485 for Profi-S-Net and RS-485 for S-Bus

Data backup 13 years with lithium battery
PCD3.M5540
asPCD3.M5440 plus Ethernet TCP/IP
PCD3.M6240
CPU with 1 MByte user program memory, 1 MByte onboard Flash memory

for backup, up to 1,023 digital I/Os (with PCD3.Cxxx), 2 interrupts, web server, USB port

for PG5, RS-232, RS-485 for Profi-S-Net/MPI/S-Bus, CAN interface, Run/Stop

switch, 2 sockets for PCD7.Rxxx, data backup 13 years with lithium battery
PCD3.M6340 asPCD3.M6240 plus Ethernet TCP/IP
PCD3.M6440
CPU with 1 MByte user program memory, 1 MByte onboard Flash memory

for backup, up to 1,023 digital I/Os (with PCD3.Cxxx), 2 interrupts, web server, USB port

for PG5, RS-232, RS-485 for Profi-S-Net/MPI/S-Bus, Profibus DP Master, Run/Stop

switch, 2 sockets for PCD7.Rxxx, data backup 13 years with lithium battery
PCD3.M6540 asPCD3.M6440 plus Ethernet TCP/IP

400 g
400 g

400 g
400 g

560 g

560 g
560 g

560 g
560 g

A
560 g
560 g


Additional memory
PCD3.R500
Flash module holder, 1 MByte program backup for PCD3.Mxxx0, I/O Slot 0,
PCD7.R500
Flash module, 1 MByte program backup for PCD3.M5xx0/.M6xx0, Slot M1,
PCD3.R550M04 Flash module holder, 4 MByte with file system for PCD3.M3xx0, I/O Slots 03
PCD7.R550M04 Flash module, 4 MByte with file system for PCD3.M5xx0/.M6xx0, Slot M1 or M2
PCD3.R551M04 Flash module holder, 1 MByte program backup + 3 MByte file system for PCD3.Mxx0,

I/O Slots 03,
PCD7.R551M04 Flash module, 1 MByte program backup + 3 MByte file system for PCD3.M5xx0/.M6xx0,,

Slot M1/M2
PCD3.R560
Bacnet Flash module holder, for PCD3.Mxxx0, I/O Slots 03
PCD7.R560
Bacnet Flash module for PCD3.M5xx0/.M6xx0, Slot M1/M2
PCD3.R561
Flash module holder, 1 MByte program backup + 1 MByte file system

for PCD3.M3xx0, I/O Slots 03
PCD7.R561
Bacnet Flash module, 1 MB program backup + 1 MB file system

for PCD3.M5xx0/.M6xx0, Slot M1/M2
PCD7.R600
PCD3 module holder to take SD Flash memory cards,

plugs into I/O Slots 03,
PCD7.R-SD256 SaiaPG5 SD Flash card, 256 MByte with file system
PCD7.R-SD512 SaiaPG5 SD Flash card, 512 MByte with file system

4 104 7502 0
4 104 7493 0
4 405 4995 0
PCD3.R010
4 639 4898 0
4 507 4817 0

Spares
I/O slot cover
PCD3.M5xxx covering cap
1 for CPUs: Pluggable cage clamp terminal, 8-pole (up to 2.5 mm)
Battery module for PCD3.M3xxx
Battery module for PCD3.M5xxx/M6xxx
Lithium battery

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

6g
12 g
12 g
30 g
12 g
3g

A-6

Appendix

Saia-Burgess Controls AG

Order details
Type

Description


PCD3.F110
PCD3.F121
PCD3.F130
PCD3.F150
PCD3.F180

Communication modules on I/O module Slot#0


with RS422/RS-485 interface (electrically connected)
with RS-232 interface (suitable for modem)
with interface for 20 mA current loop
with RS-485 interface (electrically isolated)
Belimo MP-Bus (based on RS-232))

80 g
80 g
80 g
80 g
80 g



PCD3.F221
PCD3.F210

Communication modules on I/O module Slot#03


(optional with PCD3.F1xx module)
serial interface module, RS-232
serial interface module, RS-422/RS-485

80 g
80 g


PCD3.C100
PCD3.C110
PCD3.C200

Module holders for expansion units


Module holder for for 4 I/O modules
Module holder for for 2 I/O modules
Module holder for 4 I/O modules, with 24V supply

350 g
180 g
350 g


PCD3.T760

PCD3.T765
(on request)

PCD3 RIO head station


Profibus RIO head station with 4 I/O module sockets
Profibus DP/Profi-S-Net connection
Profibus RIO head station with 4 I/O module sockets
Profibus DP/Profi-S-Net connection
+ facility to implement user-specific software modules
(plug-Ins)




PCD3.E110
PCD3.E111
PCD3.E112
PCD3.E116

Input/output modules
Digital input modules
with 8 inputs 24 VDC
Input delay typically 8 ms (pulsed voltage possible)
Input delay typically 0.2 ms (smoothed voltage required)
Input delay typically 9 ms, 12 VDC (smoothed voltage required)
Input delay typically 0.2 ms, 5 VDC (smoothed voltage required)


PCD3.E160

PCD3.E161

PCD3.E165

PCD3.E166

with 16 inputs 24 VDC


Input delay typically 8 ms (pulsed voltage possible,
connection via 34-pole system cable)
Input delay typically 0.2 ms (smoothed voltage required,
connection via 34-pole system cable)
Input delay typically 8 ms (pulsed voltage possible,
connection via 24-pole spring terminal block)
Input delay typically 0.2 ms (smoothed voltage required,
connection via 24-pole spring terminal block)


PCD3.E500

with 6 inputs 250 VAC, electrically isolated


Input delay typically 20 ms (pulsed voltage possible)


with 8 inputs 24 VDC, electrically isolated
PCD3.E610
Input delay typically 10 ms (pulsed voltage possible)
PCD3.E613
Input delay typically 10 ms, 48 VDC (pulsed voltage possible)

Weight

370 g
370 g

60 g
60 g
60 g
60 g

65 g
65 g
65 g
65 g
65 g
65 g
65 g


PCD3.A200
PCD3.A210
PCD3.A220
PCD3.A251
PCD3.A300

relay output modules


with 4 make contacts 2 A/250VAC or 2 A/50 VDC
with 4 break contacts 2 A/250VAC or 2 A/50 VDC
with 6 make contacts 2 A/250VAC or 2 A/50 VDC
with 6 changeover contacts and 2 make contacts 2 A/48 VAC or 2 A/50 VDC
with 6 outputs, 24VDC/2 A

85 g
90 g
90 g
90 g
70 g


PCD3.A400
PCD3.A410
PCD3.A460
PCD3.A465

withTransistor outputs, 0.5 A/24 VDC


8 outputs, 24VDC/0.5 A
8 outputs 24 VDC/0.5 A, electrically isolated
16 outputs, connection via 34-pole system cable
16 outputs, connection via 24-pole spring terminal block

65 g
65 g
65 g
70 g

Manual control modules


PCD3.A810
Manual control module, 2 changeover contacts + 2 make contacts, 2 A, 5(6) A
PCD3.A860
Light and shade module, 2 outputs 12 A/250 VAC, 2 inputs 24 VDC

75 g
75 g

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

A-7

Appendix

Saia-Burgess Controls AG

Order details
Type

Description

Combined digital input and output module


PCD3.B100
with 2 inputs and 2 transistor outputs, plus 4 selectable as inputs or outputs

Analogue input modules

with 8 input channels, 10 bit resolution
PCD3.W200
8 input channels 0..0.10 V
PCD3.W210
8 input channels 020 mA
PCD3.W220
8 input channels for resistive temperature sensors Pt/Ni 1000

(2-wire), 50+400 C or +200 C
PCD2.W220Z02 Analogue input module, 8 inputs, 10 bits, NTC10 temperature sensors
PCD2.W220Z12 Analogue input module, 10 bits, 4 inputs 010 V and 4 inputs Pt/Ni 1000

Weight
70 g

60 g
60 g
65 g
40 g
40 g


PCD3.W300
PCD3.W310
PCD3.W340

PCD3.W350

PCD3.W360

with 8 input channels, 12 bit resolution


8 input channels 0..0.10 V
8 input channels 020 mA
8 input channels, jumper selectable: 010 V, 020 mA
or for resistive temperature sensor Pt/Ni 1000 (2-wire)
8 input channels for 2-wire resistive temperature sensor Pt 100
for 50+600 C or Ni 100 for 50+250 C
8 input channels for 2-wire resistive temperature sensor Pt 1000
for 50+150 C, resolution < 0.1 C


65 g
65 g


PCD3.W305
PCD3.W315
PCD3.W325

with 7 input channels, 12 bit resolution


7 input channels 0..0.10 V
7 input channels 020 mA
7 input channels -10 V+10 V


80 g
80 g
80 g


Analogue output modules
with 4 output channels, 8 bit resolution
PCD3.W400
Single modules: 4 channels 010 V ( 3k)
PCD3.W410
General purpose modules: 4 channels 010 V ( 3k)

020 mA ( 500 k) oder 420 mA ( 500 k)

65 g
65 g
65 g

60 g
45 g


PCD3.W605
PCD3.W615
PCD3.W625

with 6 (4) output channels, 10 bit resolution


Single modules: 6 channels 010 V ( 3k)
Single modules: 4 channels 020 V ( 500k)
Single modules: 6 channels -10+10 V ( 3k)


80 g
80 g
80 g


PCD3.W600
PCD3.W610

with 4 output channels, 12 bit resolution


Single modules: 4 channels 010 V ( 3k)
General purpose modules: 4 channels, jumper selectable, 010 V
and 10+10 V ( 3 k) 020 mA ( 500 )


45 g


PCD3.W500
PCD3.W510
PCD3.W525

Combinedanalogue input and output module


2 input and 2 output channels for voltage signals
2 input and 2 output channels for current/voltage signals
4 analogue inputs, 14Bit + 2analogue outputs, 12Bit

80 g
80 g
80 g


PCD3.W720
PCD3.W745

Weighing and thermocouple modules


2-channel weighing module for 4/6-wire weighing cells
4-channel thermocouple module for J, K thermocouples

80 g
80 g

45 g

Manual control module


PCD3.W800
3 outputs 010 V with manual control, 1 output 010 V without 75 g

PCD3.H100
PCD3.H110
PCD3.H150
PCD3.H210
PCD3.H310
PCD3.H311

Counting, measuring and motion control modules


Counter module up to 20 kHz
General purpose counting and measuring module up to 100 kHz
SSI interface module
Motion control module for one stepper motor axis
Motion control module up to 100 kHz for servo-drives, 1 axis for 24 VDC encoder
Motion control module up to 100 kHz for servo-drives, 1 axis for 422 VDC encoder

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

80 g
80 g
80 g
80 g
80 g
80 g

A-8

Appendix

Saia-Burgess Controls AG

Order details
Type

Description


PCD3.E009
PCD3.K010
PCD3.K106
PCD3.K116
PCD2.K106
4 405 4954 0
4 405 4955 0

Accessories
Empty cassette
Connector PCD3 PCD3
Connecting cable 0.7 m PCD3 PCD3
Connecting cable 1.2 m PCD3 PCD3
Connecting cable 0.7 m PCD2 PCD3 (supplied with numeric labelling)
1: Pluggable I/O spring terminal block, 10-pole (Type A)
1: Pluggable I/O spring terminal block, 10-pole (Type B)

PCD2.K2xx
PCD2.K3xx

For connecting "ribbon cable to screw terminal" adapters


with PCD2.K23x or PCD2.K22x cables (type D)

4 405 4956 0
4 405 4998 0
4 405 4936 0
PCD3.K810

4 405 5027 0
PCD3.K860

4 405 5028 0
PCD3.K861

4 405 4934 0
PCD3.K800

4 329 4819 0
4 310 8686 0
PCD3.K225

1: Pluggable I/O spring terminal block, 24-pole (Type C)


1: Pluggable I/O spring terminal block, 14-pole (Type E)
1 for A810: Pluggable spring terminals, 12-pole (up to 1.5 mm), (Type F)
1 for A810: Pluggable spring terminals, 12-pole (as 4 405 4936 0, Type F
with 12 grouped strands, numbered, 2.5 m long
1 for A860: Pluggable spring terminals, 4-pole (up to 2.5 mm), (Type G)
1 for A860: Pluggable spring terminals, 4-pole (as 4 405 5027 0, Type G),
with 4 grouped strands, numbered, 2.5 m long
1 for A860: Pluggable spring terminals, 6-pole (up to 1.0 mm), (Type H)
1 for A860: Pluggable spring terminals, 6-pole (as 4 405 5028 0, Type H),
with 6 grouped strands, numbered, 2.5 m long
1 for A800: Pluggable spring terminals, 8-pole (up to 1.5 mm), (Type J)
1 for A800: Pluggable spring terminals, 8-pole (as 4 405 4934 0, Type J),
with 8 grouped strands, numbered, 2.5 m long
Label plates, set of 10
Preprinted tapes
Connecting cable 2.5 m PCD3 web serverPC

Weight
35 g
40 g
70 g
70 g
70 g
12 g
12 g

12 g
12 g
12 g
25 g
6g
15 g
10 g
20 g
12 g
25 g
2g
2g
70 g

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

A-9

Saia-Burgess Controls AG

Appendix
Addresses

A.4 Contact

Saia-Burgess Controls AG
Bahnhofstrasse 18
3280 Murten
Switzerland
Phone........................................... +41266727272
Fax................................................ +41266727499

Email support: .............................. [email protected]


Supportsite: ................................. www.sbc-support.com
SBC site: ...................................... www.saia-pcd.com
International Represetatives &
SBC Sales Companies: ............... www.saia-pcd.com/contact

Postal address for returns from customers of the Swiss Sales office
Saia-Burgess Controls AG
Service Aprs-Vente
Bahnhofstrasse 18
3280 Murten
Switzerland

Hardware Manual for the PCD3 Series Document 26-789 EN172014-09-16

A-10

You might also like