Army Public College of Management Science

HIGH VOLTAGE ENGINEERING


Project:
POWER TRANSMISSION DESIGN AND SIMULATION FROM
TARBELLA TO ISLAMABAD

GROUP MEMBERS:
M. Faizan Mughal
M. Imran Sattar Mughal
Arslan Ali
Ata ur Rehman
MS Electrical Engineering
1st Semester
APCOMS
2014
SUBMITTED TO
Dr. M. Ejaz Hassan
1

OUTLINE
TARBELA HYDEL POWER GENERATION
HIGH VOLTAGE TRANSMISSION LINE DESIGN
Mechanical Design
Calculation Of Insulator Discs
Power Conductor Selection
Earth Wire / Ground Conductor
Sag Calculation
Height Calculation
Electrical Design
Inductance of each conductor
Capacitance of each Conductor
A, B, C, D parameters calculation (Nominal pi method)
Sending end line Voltage
Voltage Regulation
Line Losses
Transmission Efficiency
MATLAB SIMULATION OF DESIGNED TRANSMISSION LINE
RLC Line Parameters
Simulation Model without Statcom
Simulation Model with Statcom
Analysis
REFERENCES

TARBELA HYDEL POWER STATION


Tarbela Dam is one of the worlds largest earth and rock filled Dam and greatest water
resources development project which was completed in 1976 as a component part of Indus Basin
Project. The Dam is built on one of the Worlds largest rivers the Indus known as the
Abbasin or the father of rivers.
Main Spillway Capacity
Type
Height
Length
Total Capacity

6, 50,000 cusecs
Earth and Rock fill
485 ft (above river bed)
9000 ft
3478 MW

TURBINE (FRANCIS-VERTICAL)
UNITS
1-4
5-6
Output (BHP) 23900
23900

7-8
23900

9-10
23900

11-14
596000

7-8
184.210
0.95
175
13.8

9-10
184.210
0.95
175
13.8

11-14
480
0.90
432
18.2

CGE Canada

Hitachi Japan

SiemensABB
Germany

GENERATOR (UMBRELLA)
UNITS
1-4
5-6
Output(MVA) 205.882
184.210
Output( P.F ) 0.85
0.95
Output(MW) 175
175
Rated
13.8
13.8
Voltage(KV)
Manufacturer Hitachi Japan CGE Canada

TRANSFORMER
UNITS
Capability(MVA/Phase)
Voltage Ratio
Manufacturer

1-4
79
13.2/220
JeumountScheider

SWITCH YARD
No. of 500 KV feeder/breaker
No. of 220 KV feeder/breaker
Scheme Layout
Annual Generation (2012-13)
Plant Factor (2012-13)

5-6
71
13.2/500
ASEA
Canada
Hitachi
Japan

7-8
71
13.2/500
Hitachi
Japan

9-10
71
13.2/500
JeumountScheider

11-14
160
25.0/500
Ansaldo
Italy

= 4 / 24
= 6 / 24
= Double Bus bar/ One and half breaker system
= 14,788.22 GWh
= 48.41 %

HIGH VOLTAGE TRANSMISSION LINE DESIGN


For our project we take output of first unit of tarbella power generation plant i.e.
Generator with apparent power of 205MVA, real power of 175MW with power factor 0.85 and
generator voltage are 13.8kV. Generator voltage is further stepped up by power transformer of
voltage ratio 13/220kV.
The distance between tarbella station and Islamabad station is 112 km. We use Steel
Tower due to its capability to withstand longer spans. We have considered single circuit coming
from tarbella. We are using 220kV as power transmission voltage. Span of tower is 320 meter so
total no. of towers used in transmission are 350.

Mechanical Design

Calculation Of Insulator Discs

R ATED S YS TEM
VO LTAGE

33KV
66KV
132KV
220KV

NUMBER O F D IS C
INS U LA TOR US ED IN
S TR A IN TYP E
TENS ION INS U LA TOR
S TR ING
3
5
9
15

NUMBER O F D IS C
INS U LA TOR US ED IN
S US P ENS ION
INS U LA TOR S TR ING
3
4
8
14

Conductor Selection
We supposed the load of Islamabad = Receiving End Power = 130MW

Power Factor = cos r = 0.8


Pr = 3 Vr Ir cos
Ir=Pr/ (3 Vr cos r)
Ir = 130*106/ (3 * 220*103*0.8)
I r= 426.5 Amp

Wolf Conductor
Current capacity= 430 Amp
Resistance = R = 0.1844 ohm/km
Number of Wires Strands (Al/St) = 30/7
Diameter of Conductor = 18.13mm
Weight of Conductor = 727 kg/Km
T = 6880 kg

Earth Wire / Ground Conductor


Galvanised standered steel utilized for Earth wire, Guy wire, and Stay wire.

Code name
Area (sq mm)
No. of wire
Diameter (mm)
Linear mass (kg/km)
Rated strength (kN)

=
=
=
=
=
=

55
55
7
9.45
430
70

Sag Calculation
Length of Span = L= 320m
Neglected the Wind and ice loading
Weight of wolf conductor = w
Tension of wolf conductor = T
Sag = wL2/8T
Sag = [(727/1000)* (320)2] / (8*6880)
Sag = 1.35m

Height Calculation
Height of tower is determine byH=h1+h2+h3+h4+h5
h1=Minimum permissible ground clearance
h2=Maximum sag
h3=Vertical spacing between conductors
h4= Vertical spacing between conductors
h5=Vertical clearance between earth wire and top conductor

Ground Clearances (Cl)


Cl =5.182+0.305*K
Where K= (v-33)/33
Minimum permissible ground clearances
S.No.
1.
2.
3.
4.
5.

Voltage level
33 KV
66 KV
132KV
220 KV
400 KV

Ground clearance(m)
5.20
5.49
6.10
7.01
8.84

Swedish Formula to find Spacing (cm) between the conductors


Spacing = 6.5 S + 0.7 *E
Where S=sag (cm),
Spacing =
=

E= line voltage(kV)

6.5 * 135 +0.7 *220


229 cm =2.29m

Total Height of Tower


H = h1 + h2 +h3+h4 +h5
H= 7+1.35+2.29+2.29+2.29
H = 15.22m

Electrical Design
Resistance of wolf conductor = R = 0.1844 ohm/km
Resistance for 112km length = R = 0.1844 *112= 20.65 ohm
Diameter of wolf conductor =18.13mm

Inductance of Each Conductor (Per Phase)


L = 2*10-7 ln [Deq/Ds]
Deq = 3 (D12 * D23*D31)
Deq = 3 (2.29*2.29*4.58)
Deq =2.89m=289cm
Radius = r = diameter/2= (18.13*10-3)/2=9.065*10-3m = 0.9065cm
Ds = 0.7788* r
Ds = 0.7788*9.065*10-3
Ds = 0.7cm
L = 2*10-7 ln [Deq/Ds]
L = 2*10-7*ln [289/0.7]
-6

L =1.2*10 H
Inductance of 112 km transmission line
L = 1.2*10-6*112*10-3 = 0.134H
XL = 2fL = 2*3.14*50*0.134 = 42.1ohm

Capacitance of each Conductor (Per Phase)


C= 10-9/ [18*ln (Dm/r)]
C = 10-9/ [18*ln (289/0.9065)]
C = 9.63*10-12F/m
C for 112 km = 9.63*10-12 * 112*103 = 1.08*10-6

Susceptance per phase = Y = j2fC


Y = j 2 *3.14*50*1.08*10-6
Y=3.3912*10-4 siemens
Receiving Power = 130MW
Power Factor = 0.8
Receiving Current = Ir = 426.5 Amp
Susceptance per phase = Y= 3.3912*10-4 mho
Impedance = Z = R + j XL= 20.65 + j42.1

A, B, C, D Parameters Calculation (Nominal Pi Method)


A = D = [1+YZ/2]
A = [1+ {(j3.3912*10-4)* (20.65+j42.1)/2}]
A= 1+ (-0.0143+j7*10-3 /2)
A = 0.993+j3.5*10-3
B =Z= 20.65 +j42.1
C = Y [1+ (YZ/4)]
C = j3.3912*10-4 [1+ (-0.0143+j7*10-3 /4)]
C = -5.934*10-7+j3.38*10-4
Vs = A Vr+ B Ir
Vs = (1270170) (0.993+j3.5*10-3) + (426.5 -36.86) (20.65 +j42.1)
Vs = 143945.5+j9527.8
Vs = 144260.5 3.79

Sending end line Voltage


Vs= 3 * 144260.5
= 249866.5 V

Is =C Vr+ D Ir
Is = (-5.934*10-7+j3.38*10-4) (1270170) + (0.993+j3.5*10-3) (426.5 -36.86)
Is =340.05-j212.01
Is = 400.73 -31.94 A
Voltage receiving under No-Load = Vr = [Vs (-2j/C)]/[R+jX-(2j/C)]
= [(144260.5 3.79) (-2j/3.3912*10-4)] / [20.656+j42.1 (2j/3.3912 *10-4)]
Vr

= 145296.83.59

Voltage Regulation
V-Reg = [(Vr Vr) / Vr]*100
= [(145296.8 127017)/127017] *100
= 20022.4/127017 * 100
Voltage Regulation = 14.4 %

Line Losses
= 3 I2 R
= 3 (492)2*20.65
Line Losses =14.99MW

Transmission Efficiency
= Pout/Pin *100
=

130 * 106 / (130*106 + 14.99*106)

Transmission Efficiency =

89.6%

10

MATLAB SIMULATION OF DESIGNED TRANSMISSION


LINE
RLC Line Parameters

Wolf Conductor
Resistance = R = 0.1844 ohm/km
Diameter of Conductor = 18.13mm
ID = Inner diameter of a tubular conductor (m)
ID = 2.59 mm
T/D = Ratio of the thickness of the aluminum layers to the conductor diameter in an ACSR
Conductor = (D ID)/ (2*D)
T /D ratio= (18.13 2.59)/ (2*18.13) = 0.429
Earth Wire / Ground Conductor
Galvanised standered steel utilized for Earth wire, Guy wire, and Stay wire.
Diameter (mm)
=
9.45
T /D ratio = (9.45-0)/ (2*9.45) = 0.5
11

12

Simulation Model without STATCOM

Simulation Model with STATCOM

13

Analysis

STATCOM provides excellent voltage regulation,


power factor and active power regulation
capabilities. The STATCOM is one of the
important shunt connected Flexible AC
Transmission system controllers to control the
power flow and make better transient stability. A
statcom is a controlled reactive power source. It
provides voltage support by generating or
absorbing capacitors banks. From graphs It can be
seen that it regulates the voltage at its terminals by
compensating the amount of reactive power in or
out from the power system.

14

REFERENCES
Http://www.electrical4u.com/types-of-electrical-insulator-overhead-insulator/
Http://nptel.ac.in/courses/105106113/7_transmission_towers/2_material_properties.pdf
Design of steel structures ; prof. S.r.satish kumar and prof. A.r.santha kumar
Haryana vidyut prasaran nigam limited
Technical specification for power conductor accessories, ground wire accessories and ground
wire hardware for 220kv transmission lines( chief engineer/d&p transmission design directorate
hvpnl, power colony, indl. Area phase-ii. Panchkula haryana india)
Transmission line ppt by ravi shankar singh
Https://www.scribd.com/doc/44731675/current-carrying-capacity-acsr-conductors#scribd
Pakistan water and power development authority
Brief specification of all dams
https://www.powerlink.com.au/Network/Documents/TNSP_Operational_Line_Ratings.aspx
International Journal of Electronics and Computer Science Engineering 198
Available Online at www.ijecse.org ISSN: 2277-1956
ISSN-2277-1956/V1N2-198-208
Voltage Stability in Power system Using STATCOM
Mr. D.K. Sharma , Prof. Aziz Ahmad , Ms. Richa Saluja Reena Parmar
AP Electrical Engineering HOD Electrical Engineering, M.Tech Student
RIET Faridabad, A.F.S.E.T

15

You might also like