HV Project
HV Project
HV Project
GROUP MEMBERS:
M. Faizan Mughal
M. Imran Sattar Mughal
Arslan Ali
Ata ur Rehman
MS Electrical Engineering
1st Semester
APCOMS
2014
SUBMITTED TO
Dr. M. Ejaz Hassan
1
OUTLINE
TARBELA HYDEL POWER GENERATION
HIGH VOLTAGE TRANSMISSION LINE DESIGN
Mechanical Design
Calculation Of Insulator Discs
Power Conductor Selection
Earth Wire / Ground Conductor
Sag Calculation
Height Calculation
Electrical Design
Inductance of each conductor
Capacitance of each Conductor
A, B, C, D parameters calculation (Nominal pi method)
Sending end line Voltage
Voltage Regulation
Line Losses
Transmission Efficiency
MATLAB SIMULATION OF DESIGNED TRANSMISSION LINE
RLC Line Parameters
Simulation Model without Statcom
Simulation Model with Statcom
Analysis
REFERENCES
6, 50,000 cusecs
Earth and Rock fill
485 ft (above river bed)
9000 ft
3478 MW
TURBINE (FRANCIS-VERTICAL)
UNITS
1-4
5-6
Output (BHP) 23900
23900
7-8
23900
9-10
23900
11-14
596000
7-8
184.210
0.95
175
13.8
9-10
184.210
0.95
175
13.8
11-14
480
0.90
432
18.2
CGE Canada
Hitachi Japan
SiemensABB
Germany
GENERATOR (UMBRELLA)
UNITS
1-4
5-6
Output(MVA) 205.882
184.210
Output( P.F ) 0.85
0.95
Output(MW) 175
175
Rated
13.8
13.8
Voltage(KV)
Manufacturer Hitachi Japan CGE Canada
TRANSFORMER
UNITS
Capability(MVA/Phase)
Voltage Ratio
Manufacturer
1-4
79
13.2/220
JeumountScheider
SWITCH YARD
No. of 500 KV feeder/breaker
No. of 220 KV feeder/breaker
Scheme Layout
Annual Generation (2012-13)
Plant Factor (2012-13)
5-6
71
13.2/500
ASEA
Canada
Hitachi
Japan
7-8
71
13.2/500
Hitachi
Japan
9-10
71
13.2/500
JeumountScheider
11-14
160
25.0/500
Ansaldo
Italy
= 4 / 24
= 6 / 24
= Double Bus bar/ One and half breaker system
= 14,788.22 GWh
= 48.41 %
Mechanical Design
R ATED S YS TEM
VO LTAGE
33KV
66KV
132KV
220KV
NUMBER O F D IS C
INS U LA TOR US ED IN
S TR A IN TYP E
TENS ION INS U LA TOR
S TR ING
3
5
9
15
NUMBER O F D IS C
INS U LA TOR US ED IN
S US P ENS ION
INS U LA TOR S TR ING
3
4
8
14
Conductor Selection
We supposed the load of Islamabad = Receiving End Power = 130MW
Wolf Conductor
Current capacity= 430 Amp
Resistance = R = 0.1844 ohm/km
Number of Wires Strands (Al/St) = 30/7
Diameter of Conductor = 18.13mm
Weight of Conductor = 727 kg/Km
T = 6880 kg
Code name
Area (sq mm)
No. of wire
Diameter (mm)
Linear mass (kg/km)
Rated strength (kN)
=
=
=
=
=
=
55
55
7
9.45
430
70
Sag Calculation
Length of Span = L= 320m
Neglected the Wind and ice loading
Weight of wolf conductor = w
Tension of wolf conductor = T
Sag = wL2/8T
Sag = [(727/1000)* (320)2] / (8*6880)
Sag = 1.35m
Height Calculation
Height of tower is determine byH=h1+h2+h3+h4+h5
h1=Minimum permissible ground clearance
h2=Maximum sag
h3=Vertical spacing between conductors
h4= Vertical spacing between conductors
h5=Vertical clearance between earth wire and top conductor
Voltage level
33 KV
66 KV
132KV
220 KV
400 KV
Ground clearance(m)
5.20
5.49
6.10
7.01
8.84
E= line voltage(kV)
Electrical Design
Resistance of wolf conductor = R = 0.1844 ohm/km
Resistance for 112km length = R = 0.1844 *112= 20.65 ohm
Diameter of wolf conductor =18.13mm
L =1.2*10 H
Inductance of 112 km transmission line
L = 1.2*10-6*112*10-3 = 0.134H
XL = 2fL = 2*3.14*50*0.134 = 42.1ohm
Is =C Vr+ D Ir
Is = (-5.934*10-7+j3.38*10-4) (1270170) + (0.993+j3.5*10-3) (426.5 -36.86)
Is =340.05-j212.01
Is = 400.73 -31.94 A
Voltage receiving under No-Load = Vr = [Vs (-2j/C)]/[R+jX-(2j/C)]
= [(144260.5 3.79) (-2j/3.3912*10-4)] / [20.656+j42.1 (2j/3.3912 *10-4)]
Vr
= 145296.83.59
Voltage Regulation
V-Reg = [(Vr Vr) / Vr]*100
= [(145296.8 127017)/127017] *100
= 20022.4/127017 * 100
Voltage Regulation = 14.4 %
Line Losses
= 3 I2 R
= 3 (492)2*20.65
Line Losses =14.99MW
Transmission Efficiency
= Pout/Pin *100
=
Transmission Efficiency =
89.6%
10
Wolf Conductor
Resistance = R = 0.1844 ohm/km
Diameter of Conductor = 18.13mm
ID = Inner diameter of a tubular conductor (m)
ID = 2.59 mm
T/D = Ratio of the thickness of the aluminum layers to the conductor diameter in an ACSR
Conductor = (D ID)/ (2*D)
T /D ratio= (18.13 2.59)/ (2*18.13) = 0.429
Earth Wire / Ground Conductor
Galvanised standered steel utilized for Earth wire, Guy wire, and Stay wire.
Diameter (mm)
=
9.45
T /D ratio = (9.45-0)/ (2*9.45) = 0.5
11
12
13
Analysis
14
REFERENCES
Http://www.electrical4u.com/types-of-electrical-insulator-overhead-insulator/
Http://nptel.ac.in/courses/105106113/7_transmission_towers/2_material_properties.pdf
Design of steel structures ; prof. S.r.satish kumar and prof. A.r.santha kumar
Haryana vidyut prasaran nigam limited
Technical specification for power conductor accessories, ground wire accessories and ground
wire hardware for 220kv transmission lines( chief engineer/d&p transmission design directorate
hvpnl, power colony, indl. Area phase-ii. Panchkula haryana india)
Transmission line ppt by ravi shankar singh
Https://www.scribd.com/doc/44731675/current-carrying-capacity-acsr-conductors#scribd
Pakistan water and power development authority
Brief specification of all dams
https://www.powerlink.com.au/Network/Documents/TNSP_Operational_Line_Ratings.aspx
International Journal of Electronics and Computer Science Engineering 198
Available Online at www.ijecse.org ISSN: 2277-1956
ISSN-2277-1956/V1N2-198-208
Voltage Stability in Power system Using STATCOM
Mr. D.K. Sharma , Prof. Aziz Ahmad , Ms. Richa Saluja Reena Parmar
AP Electrical Engineering HOD Electrical Engineering, M.Tech Student
RIET Faridabad, A.F.S.E.T
15