Lets calculate voltage drop in transformer 1000KVA, 11/0.480 kV, impedance 5.75% due to
starting of 300 kW, 460V, 0.8 power factor, motor code D (kva/hp). Motor starts 2 times
per hour and the allowable voltage drop at transformer secondary terminal is 10%.
Calculation can be checked by using this MS Excel Spreadsheet dedicated especially to this kind
of problem.
Ok, lets get into the calculations
http://electrical-engineering-portal.com/calculating-transformer-size-voltage-drop-due-to... 5/1/2558
An example of calculating transformer size and voltage drop due to starting of large m... Page 2 of 5
http://electrical-engineering-portal.com/calculating-transformer-size-voltage-drop-due-to... 5/1/2558
An example of calculating transformer size and voltage drop due to starting of large m... Page 3 of 5
Min
Max
3.15
3.16
3.55
3.56
4.1
4.5
4.6
5.1
5.6
5.7
6.3
6.4
7.1
7.2
8.1
9.1
10
10.1
11.2
11.3
12.5
12.6
14
14.1
16
16.1
18
18.1
20
20.1
22.4
22.5
Min. motor locked rotor current (L1) = 4.10 471 = 1930 Amp
Max. motor locked rotor current (L2) = 4.50 471 = 2118 Amp
Motor inrush Kva at Starting (Irsm) = Volt x locked rotor current x Full load
current x 1.732 / 1000
Motor inrush Kva at Starting (Irsm) = 460 x 2118 x 471 x 1.732 / 1000 = 1688 kVA
Transformer
Transformer full load current = kVA / (1.732 x Volt)
Transformer full load current = 1000 / (1.73 2 480) = 1203 Amp.
http://electrical-engineering-portal.com/calculating-transformer-size-voltage-drop-due-to... 5/1/2558
An example of calculating transformer size and voltage drop due to starting of large m... Page 4 of 5
Recommended EE articles
About Author //
Jignesh Parmar
jiguparmar - Jignesh Parmar has completed his B.E(Electrical) from
Gujarat University. He is member of Institution of Engineers
(MIE),India. Membership No:M-1473586.He has more than 12 years
experience in Transmission -Distribution-Electrical Energy theft
detection-Electrical Maintenance-Electrical Projects (Planning-DesigningTechnical Review-coordination -Execution). He is Presently associate
with one of the leading business group as a Assistant Manager at
Ahmedabad,India. He has published numbers of Technical Articles in "Electrical Mirror",
"Electrical India", "Lighting India", "Industrial Electrix"(Australian Power Publications)
Magazines. He is Freelancer Programmer of Advance Excel and design useful Excel base
Electrical Programs as per IS, NEC, IEC,IEEE codes. He is Technical Blogger and Familiar with
English, Hindi, Gujarati, French languages. He wants to Share his experience & Knowledge and
help technical enthusiasts to find suitable solutions and updating themselves on various
Engineering Topics.
http://electrical-engineering-portal.com/calculating-transformer-size-voltage-drop-due-to... 5/1/2558
An example of calculating transformer size and voltage drop due to starting of large m... Page 5 of 5