Installation Instructions
MicroLogix 1762-OB16 Solid State
24V dc Source Output Module
Inside
Description ................................................................................................3
Installation ................................................................................................4
Mounting...................................................................................................5
System Assembly......................................................................................7
Field Wiring Connections..........................................................................7
I/O Memory Mapping .............................................................................10
Specifications .........................................................................................11
Hazardous Location Considerations .......................................................13
Environnements dangereux ....................................................................14
Publication 1762-IN011A-EN-P
MicroLogix 1762-OB16 Solid State 24V dc Source Output Module
For More Information
For
Refer to this Document
Information on installing, wiring, and
operating a MicroLogix 1200
Programmable Controller
MicroLogix 1200 Programmable 1762-UM001A-US-P
Controllers User Manual
(Bulletin 1762 Controllers and
Expansion I/O)
Installation guide for the MicroLogix
1200 Programmable Controller.
MicroLogix 1200 Programmable 1762-IN006B-ML-P
Controllers Installation
Instructions
More information on proper wiring and Industrial Automation Wiring
grounding techniques.
and Grounding Guidelines
Pub. No.
1770-4.1
If you would like a manual, you can:
download a free electronic version from the internet:
www.ab.com/micrologix or www.theautomationbookstore.com
purchase a printed manual by:
contacting your local distributor or Rockwell Automation representative
visiting www.theautomationbookstore.com and placing your order
calling 1.800.963.9548 (USA/Canada)
or 001.330.725.1574 (Outside USA/Canada)
Publication 1762-IN011A-EN-P
MicroLogix 1762-OB16 Solid State 24V dc Source Output Module
Description
9
1a
Item Description
7
1a
upper panel mounting tab
1b
lower panel mounting tab
I/O diagnostic LEDs
module door with terminal
identification label
bus connector
with male pins
bus connector cover
flat ribbon cable with bus
connector (female pins)
terminal block
DIN rail latch
pull loop
1b
4
1a
6
2
1b
Publication 1762-IN011A-EN-P
MicroLogix 1762-OB16 Solid State 24V dc Source Output Module
Installation
1762 I/O is suitable for use in an industrial environment when installed in
accordance with these instructions. Specifically, this equipment is intended for use in
clean, dry environments (Pollution degree 2 (1)) and to circuits not exceeding Over
Voltage Category II(2) (IEC 60664-1).(3)
Prevent Electrostatic Discharge
ATTENTION Electrostatic discharge can damage integrated circuits or
semiconductors if you touch bus connector pins. Follow these
guidelines when you handle the module:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch the bus connector or connector pins.
Do not touch circuit components inside the module.
If available, use a static-safe work station.
When not in use, keep the module in its static-shield box.
Remove Power
ATTENTION Remove power before removing or installing this module. When
you remove or install a module with power applied, an electrical
arc may occur. An electrical arc can cause personal injury or
property damage by:
sending an erroneous signal to your systems field devices,
causing unintended machine motion
causing an explosion in a hazardous environment
causing permanent damage to the modules circuitry
Electrical arcing causes excessive wear to contacts on both the
module and its mating connector. Worn contacts may create
electrical resistance.
(1) Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that
occasionally a temporary conductivity caused by condensation shall be expected.
(2) Over Voltage Category II is the load level section of the electrical distribution system. At this level transient
voltages are controlled and do not exceed the impulse voltage capability of the products insulation.
(3) Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC)
designations.
Publication 1762-IN011A-EN-P
MicroLogix 1762-OB16 Solid State 24V dc Source Output Module
Mounting
Minimum Spacing
Top
Side
MicroLogix
1200
1762 I/O
Maintain spacing from
enclosure walls, wireways,
adjacent equipment, etc.
Allow 50.8 mm (2 in.) of
space on all sides for
adequate ventilation, as
shown:
1762 I/O
Do not remove protective debris strip until after the module and
all other equipment near the module is mounted and wiring is
complete. Once wiring is complete and the module is free of
debris, carefully remove protective debris strip. Failure to remove
strip before operating can cause overheating.
1762 I/O
ATTENTION
Side
Bottom
NOTE
ATTENTION
1762 expansion I/O may be mounted horizontally only.
During panel or DIN rail mounting of all devices, be sure that all
debris (metal chips, wire strands, etc.) is kept from falling into
the module. Debris that falls into the module could cause
damage when power is applied to the module.
Publication 1762-IN011A-EN-P
MicroLogix 1762-OB16 Solid State 24V dc Source Output Module
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 mm
(EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latch. Press the DIN
rail mounting area of the module against the DIN rail. The latch will momentarily
open and lock into place.
Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or
1492-EAH35) for vibration or shock environments.
End Anchor
End Anchor
NOTE
For environments with greater vibration and shock concerns, use
the panel mounting method described below, instead of DIN rail
mounting.
Panel Mounting
Use the dimensional template shown below to mount the module. The preferred
mounting method is to use two M4 or #8 panhead screws per module. M3.5 or #6
panhead screws may also be used, but a washer may be needed to ensure a good
mechanical contact. Mounting screws are required on every module.
For more than 2 modules: (number of modules - 1) x 40 mm (1.58 in.)
14.5
(0.57)
40.4
(1.59)
NOTE: All
dimensions are in
mm (inches). Hole
spacing tolerance:
0.4 mm
(0.016 in.).
100 90
(3.94) (3.54)
40.4
(1.59)
Publication 1762-IN011A-EN-P
MicroLogix 1762-OB16 Solid State 24V dc Source Output Module
System Assembly
The expansion I/O module is attached to the controller or another I/O module by
means of a flat ribbon cable after mounting as shown below.
NOTE
ATTENTION
Use the pull loop on the connector to disconnect modules. Do
not pull on the ribbon cable.
EXPLOSION HAZARD
In Class I, Division 2 applications, the bus connector must be
fully seated and the bus connector cover must be snapped in
place.
In Class I, Division 2 applications, all modules must be
mounted in direct contact with each other as shown on
Page 6. If DIN rail mounting is used, an end stop must be
installed ahead of the controller and after the last 1762 I/O
module.
Field Wiring Connections
Grounding the Module
This product is intended to be mounted to a well-grounded mounting surface such
as a metal panel. Refer to Industrial Automation Wiring and Grounding Guidelines,
Allen-Bradley publication 1770-4.1, for additional information.
Publication 1762-IN011A-EN-P
MicroLogix 1762-OB16 Solid State 24V dc Source Output Module
Output Wiring
Basic wiring(1) of the 1762-OB16 is shown below.
+DC
VDC+
CR
CR
OUT 0
OUT 1
CR
OUT 3
CR
OUT 2
OUT 4
OUT 5
CR
OUT 6
CR
OUT 7
CR
OUT 8
CR
OUT 9
CR
OUT 11
24V dc (source)
OUT 10
OUT 12
CR
OUT 13
OUT 14
OUT 15
DC COM
-DC
A write-on label is provided with the module. Mark the identification of each
terminal with permanent ink, and slide the label back into the door.
ATTENTION
Be careful when stripping wires. Wire fragments that fall into a
module could cause damage when power is applied. Once wiring
is complete, ensure the module is free of all metal fragments.
ATTENTION
Miswiring of the module to an AC power source will damage the
module.
(1) Surge Suppression Connecting surge suppressors across your external inductive load will extend the
life of the relay contacts. For additional details, refer to Industrial Automation Wiring and Grounding
Guidelines, Allen-Bradley publication 1770-4.1.
Publication 1762-IN011A-EN-P
MicroLogix 1762-OB16 Solid State 24V dc Source Output Module
NOTE
Finger-safe cover not shown for clarity.
Wiring the Finger-Safe Terminal Block
When wiring the terminal block, keep the finger-safe cover in place.
1. Route the wire under the terminal pressure plate. You can use the stripped end of
the wire or a spade lug. The terminals will accept a 6.35 mm (0.25 in.) spade lug.
2. Tighten the terminal screw making sure the pressure plate secures the wire.
Recommended torque when tightening terminal screws is 0.90 Nm
(8 in-lbs).
NOTE
If you need to remove the finger-safe cover, insert a screw driver
into one of the square wiring holes and gently pry the cover off.
If you wire the terminal block with the finger-safe cover removed,
you will not be able to put it back on the terminal block because
the wires will be in the way.
Wire Size and Terminal Screw Torque
Each terminal accepts up to two wires with the following restrictions:
Wire Type
Wire Size
Terminal Screw Torque
Solid
Cu-90C (194F)
#14 to #22 AWG
0.90 Nm (8 in-lbs)
Stranded
Cu-90C (194F)
#16 to #22 AWG
0.90 Nm (8 in-lbs)
Publication 1762-IN011A-EN-P
10
MicroLogix 1762-OB16 Solid State 24V dc Source Output Module
I/O Memory Mapping
Output Data File
Word
For each output module, the output data file contains the controller-directed state of
the discrete output points. Bit positions 0 through 15 correspond to output
terminals 0 through 15.
Bit Position
15
14
13
12
11
10
w = write only
Addressing
The addressing scheme for 1762 Expansion I/O is shown below.
Slot Number(1)
Data File
Output
Word (always zero for this module)
O0:x.0/0
Slot Delimiter
Bit (0 to 15)
Bit Delimiter
Word Delimiter
(1) I/O located on the controller (embedded I/O) is slot 0. I/O added to the controller (expansion I/O) begins with
slot 1.
Publication 1762-IN011A-EN-P
MicroLogix 1762-OB16 Solid State 24V dc Source Output Module
11
Specifications
General Specifications
Specification
Value
Dimensions
90 mm (height) x 87 mm (depth) x 40.4 mm (width)
height including mounting tabs is 110 mm
3.54 in. (height) x 3.43 in. (depth) x 1.59 in. (width)
height including mounting tabs is 4.33 in.
Approximate Shipping Weight
(with carton)
235g (0.52 lbs.)
Storage Temperature
-40C to +85C (-40F to +185F)
Operating Temperature
0C to +55C (+32F to +131F)
Operating Humidity
5% to 95% non-condensing
Operating Altitude
2000 meters (6561 feet)
Vibration
Operating: 10 to 500 Hz, 5G, 0.030 in. max. peak-to-peak,
2 hours per axis
Shock
Operating: 30G panel mounted, 3 pulses per axis
Non-Operating: 50G panel mounted, 3 pulses per axis
(40G DIN Rail mounted)
Agency Certification
C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
Hazardous Environment Class
Class I, Division 2, Hazardous Location, Groups A, B, C, D
(UL 1604, C-UL under CSA C22.2 No. 213)
Radiated and Conducted Emissions
EN50081-2 Class A
Electrical /EMC:
ESD Immunity (IEC1000-4-2)
The module has passed testing at the following levels:
4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity (IEC1000-4-3)
10 V/m, 80 to 1000 MHz, 80% amplitude modulation, +900
MHz keyed carrier
Fast Transient Burst (IEC1000-4-4)
2 kV, 5 kHz
Surge Immunity (IEC1000-4-5)
2 kV common mode, 1 kV differential mode
Conducted Immunity (IEC1000-4-6)
10V, 0.15 to 80 MHz(1)
(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is
30 MHz to 1000 MHz.
Publication 1762-IN011A-EN-P
12
MicroLogix 1762-OB16 Solid State 24V dc Source Output Module
Output Specifications
Specification
1762-OB16
Voltage Category
24V dc
Operating Voltage Range
20.4V dc to 26.4V dc
Number of Outputs
16
Bus Current Draw (max.)
175 mA at 5V dc (0.88W)
Heat Dissipation (max.)
2.9 total Watts at 30C (86F)
2.1 total Watts at 55C (131F)
Signal Delay (max.) resistive
load
turn-on = 0.1 ms
Off-State Leakage (max.)
1.0 mA
turn-off = 1.0 ms
On-State Current (min.)
1.0 mA
On-State Voltage Drop (max.)
1.0V dc
Continuous Current per Point
(max.)
0.5A at 55C (131F)
Continuous Current per Module
(max.)
4.0A at 55C (131F)
Surge Current (max.)
2.0A (Repeatability is once every 2 seconds at 55C (131F),
once every second at 30C (86F) for a duration of 10 msec.)
Power Supply Distance Rating
6 (The module may not be more than 6 modules away from the
power supply.)
Isolated Groups
Group 1: Outputs 0 to 15
Output Group to Backplane
Isolation
Verified by one of the following dielectric tests: 1200V ac for 1
sec. or 1697V dc for 1 sec.
Vendor I.D. Code
Product Type Code
Product Code
103
1.0A at 30C (86F)
8.0A at 30C (86F)
75V dc working voltage (IEC Class 2 reinforced insulation)
Publication 1762-IN011A-EN-P
MicroLogix 1762-OB16 Solid State 24V dc Source Output Module
13
Sourcing Output - Source describes the current flow between the I/O module and
the field device. Sourcing output circuits supply (source) current to sinking field
devices. Field devices connected to the negative side (DC Common) of the field
power supply are sinking field devices. Field devices connected to the positive side
(+V) of the field supply are sourcing field devices.
Typical Loading Resistor - To limit the effects of leakage current through
solid-state outputs, a loading resistor can be connected in parallel with your load.
Use a 5.6k ohm, 1/4W resistor for transistor outputs, 24V dc operation.
Recommended Surge Suppression - Use a 1N4004 diode reverse-wired across the
load for transistor outputs switching 24V dc inductive loads. For additional
information, refer to Industrial Automation Wiring and Grounding Guidelines,
Allen-Bradley publication 1770-4.1.
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or
non-hazardous locations only. The following WARNING statement applies to use
in hazardous locations.
WARNING
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I,
Division 2.
Do not replace components or disconnect equipment unless
power has been switched off.
Do not connect or disconnect components unless power has
been switched off.
This product must be installed in an enclosure.
In Class I, Division 2 applications, the bus connector must be
fully seated and the bus connector cover must be snapped in
place.
In Class I, Division 2 applications, all modules must be
mounted in direct contact with each other as shown on
Page 6. If DIN rail mounting is used, an end stop must be
installed ahead of the controller and after the last 1762 I/O
module.
Publication 1762-IN011A-EN-P
14
MicroLogix 1762-OB16 Solid State 24V dc Source Output Module
Environnements dangereux
Cet quipement est conu pour tre utilis dans des environnements de Classe I,
Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante
sapplique une utilisation dans des environnements dangereux.
MIS EN GARDE
DANGER DEXPLOSION
La substitution de composants peut rendre cet quipement
impropre une utilisation en environnement de Classe I,
Division 2.
Ne pas remplacer de composants ou dconnecter
l'quipement sans s'tre assur que l'alimentation est coupe.
Ne pas connecter ou dconnecter des composants sans s'tre
assur que l'alimentation est coupe.
Ce produit doit tre install dans une armoire.
Pour les applications de Classe I, Division 2, le connecteur de
bus doit tre correctement install et son couvercle enclench.
Pour les applications de Classe I, Division 2, tous les modules
doivent tre installs en contact direct les uns avec les autres,
comme indiqu Page 6. Si on utilise le montage sur rail DIN,
une bute doit tre place l'avant de l'automate et aprs la
dernire unit d'E/S 1762.
Publication 1762-IN011A-EN-P
MicroLogix 1762-OB16 Solid State 24V dc Source Output Module
15
Publication 1762-IN011A-EN-P
MicroLogix is a trademark of Rockwell Automation.
Publication 1762-IN011A-EN-P - July 2000
PN 40071-115-01(A)
2000 Rockwell International Corporation. Printed in MALAYSIA.