Boiler
Boiler
Boiler
Boilermate Deaerator
750-183
Cleaver-Brooks
Operation, Maintenance, and Parts Manual
Spraymaster Deaerator
Boilermate Deaerator
Deaerator and Surge Controls
Printed in U.S.A.
Notes
Table of Contents
Section 1 Deaerators
1.1 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 DESCRIPTION AND PRINCIPLES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2 Spraymaster Deaerator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.3 Boilermate Deaerator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 SYSTEM LAY-OUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.2 Plan A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3.3 Plan B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4.1 Installation 1-11
1.4.2 Water Pumps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4.3 Flexible Coupling Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4.4 Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4.5 Operation and Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.5 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1
1-2
1-3
1-3
1-8
1-8
1-8
1-8
1-11
1-11
1-12
1-13
1-13
1-16
Section 3- Parts
2-1
2-1
2-1
2-1
2-1
2-2
Notes
Section 1
Deaerators
1.1 GENERAL
The Spraymaster and Boilermate Deaerators (Figures 1-1 and
1-2) are designed to operate with steam generation plants, or
wherever oxygen-free water is required.
Boiler feedwater usually contains two harmful dissolved
gases; oxygen and carbon dioxide. The purpose of deaeration
is to remove these gases before they are liberated in the boiler.
This reduces corrosion in the boiler, steam lines, condensate
lines, and heat transfer equipment.
The deaerator conditions feedwater so that it has less than
0.005 CC oxygen per liter. This is termed zero oxygen and
is the practical limitation of current chemical testing
equipment. Carbon dioxide is, for all practical purposes,
eliminated. Water delivered to the boiler is pre-heated.
Deaerators are designed to operate on steam from the boiler,
exhaust steam, or both. If exhaust steam is currently going to
1-1
Deaerators
1. Water Inlet
2. Steam Inlet
3. Gas Vent
4. Spray Nozzle
5. Water Collector
6. Deflecting Baffle
4
7. Water Free of Gases
5
Drops to Storage Tank
8. Storage Tank
9. Atomizing Tank
In the Spraymaster, water is collected in a conical water collector. From there, it fl ws to an atomizing valve where high-velocity
steam strikes it, breaks it down into a fine mist, and heats it to full
steam saturation temperature. The mixture strikes a deflecting
baffl , which separates water and steam. Hot, gas-free water
then drops to the storage compartment to complete the cycle.
11
6
1. Water Inlet
2. Gas Vent
3. Spray Nozzle
4. Vent Condensing Area
5. Exchange Packing (Counterflow of
Steam and Water)
10
6. Water Free of Gases Drops to
Storage Tank
7. Storage Tank
8. Steam Inlet
9. Pump Supply
10. Overflow
11. Relief Valve
1-2
750-183
Deaerators
to oper ation. The manhole co ver m ust be
opened for this removal.
Single Tank
Spraymaster or Boilermate
750-183
Deaerator Column
2.
Storage Tank
3.
Accessories
Single -Tank
Vertical Spraymaster
1-3
1-4
750-183
750-183
1-5
Deaerators
750-183
Deaerators
Figure 1-8. Shipping Configuration for Units Equipped with a Counterbalance System
750-183
1-7
Deaerators
Accessories generally provided with the assembly are relief
valve(s) for the tank, overflow drainer, steam pressure
reducing valve, and float-operated make-up water control
valve.
1.3.1 General
Two typical system lay-outs are described in plan A (Figure
1-10) and plan B (Figure 1-11).
Note that in either case the minimum water pressure
requirement is 10-12 lbs, and that the recommended steam
pressure within the deaerator storage tank is 5 psig.
If water exceeds 1 part per million of hardness, a water
softener is recommended.
All supply water to the deaerator, with the exception of
uncontrolled condensate return, must be limited to the
maximum capacity of the deaerator, whether the source is a
condensate pump, a transfer pump, or a city water supply.
This is usually accomplished by manual adjustment of a
control valve in the transfer pump discharge line. This
adjustment is of extreme importance to proper operation.
Some of the larger Spraymaster deaerators contain two (2)
spray units in a single tank. To assure proper flow of water to
each spray nozzle, balancing cocks with pressure gauges
should be installed in the symetrically branched supply lines.
1-8
If high pressure (high temperature) returns are less than 2530% of the deaerator rating, they may be returned directly to
the deaerator storage tank. High pressure trap returns are
defined as being at a temperature greater than the normal
operating temperature of the deaerator.
750-183
Deaerators
SURGE TANK
WITH PROTECTIVE
LINING
4 . C O N T RO L L I N E M U S T B E AT L E A S T 1 0 P I P E D I A M E T E R S
DOWNSTREAM OF LAST FITTING.
1-9
Deaerators
4 . C O N T RO L L I N E M U S T B E AT L E A S T 1 0 P I P E D I A M E T E R S
DOWNSTREAM OF LAST FITTING.
4 . C O N T RO L L I N E M U S T B E AT L E A S T 1 0 P I P E D I A M E T E R S
DOWNSTREAM OF LAST FITTING.
750-183
Deaerators
4 . C O N T RO L L I N E M U S T B E AT L E A S T 1 0 P I P E D I A M E T E R S
DOWNSTREAM OF LAST FITTING.
Figure 1-15. Steam Piping for Spraymaster Model SM-7 Deaerator Only
must at least be the same size as the valve. See Table 1-1 for
valve and orifice sizes.
1.4.1 Installation
This manual contains information on typical accessory
equipment such as water controls and steam reducing valves.
Some installations may use specialized controls not covered
in this manual. In such cases, refer to the Manufacturers
literature. Familiarize yourself with the instructions for the
particular items furnished.
Installation should conform to the manufacturers prints
supplied for the system. Check all piping for proper
connections. Check all valves and controls to be sure they are
installed with proper direction of flow.
Refer to Figures at the end of this section for appropriate
piping arrangements of controls.
IMPORTANT: The steam pressure reducing
valve should be installed as near as practical to
the deaerator tank. Installation should be made
in accordance with instr uctions of the v alve
manufacturer. The downstream piping MUST
be the same size as the tapping in the tank.The
external control line MUST be installed to agree
with the man ufacturers recommendation.
These recommendations will ensure the correct
volume of steam supplied to the deaerator.
The manual vent valve supplied with the deaerator has an
orifice of a predetermined size drilled in its gate; since it is
used for continuous venting, the discharge should be piped to
atmosphere with no obstructions or resistance. The piping
750-183
! CAUTION
DANGER
Do not substitute or replace the man ual vent
valve. If there is any doubt, verify that the valve
has a dr illed gate pr ior to placing the unit into
operation.
The automatic vent valve may be piped to the outside,
although it does not necessarily have to be. This valve
provides a faster means of venting at startup, or should there
be a sudden build up of gases.
NOTE: In the Boiler mate Deaer ator, the
packing (stainless steel r ings) should be
carefully dumped onto the suppor t grid, being
careful to prevent damaging the grid. Be sure to
achieve a unif orm distr ibution to maximiz e
efficiency and thoroughness of deae ation.
! CAUTION
DANGER
Wear suitable gloves when handling the rings to
prevent cuts from sharp edges.
Deaerators
If a deaerator storage tank only was supplied by CleaverBrooks and the pumps by others, the tank must be mounted at
a proper height above the pumps to avoid flashing and
cavitation. The pump manufacturers recommendations must
be followed.
Continuously operating centrifugal pumps must have a bypass orifice in the discharge line ahead of the check valve.
This orifice is shipped loose with all centrifugal pumps and
should be installed in the manner shown in Figure 1-17.
Turbine pumps should be protected by a relief valve in the
discharge line when they operate against a feed water valve
on the boiler.
Because of the various makes and models of pumps utilized
with a deaerator, it is not practical to provide specific
instructions in this manual. The manufacturers literature
provided with the pump should be referred to. It provides
instructions for proper mounting, piping, and alignment;
these recommendations should be followed.
When pumps are provided by Cleaver-Brooks as a part of the
deaerator, care is taken to assure proper installation and
alignment. It is extremely important, however, that alignment
be rechecked prior to operation. A flexible coupling does not
correct or compensate for any misalignment between the
pump and the motor. Paragraph 1.4.3 deals with coupling
alignment.
There are general instructions applicable to all pumps. Most
of these are listed in the various manufacturers literature, but
they are worth repeating.
Do not run the pump unless it is filled with liquid.
Protect the pump from foreign particles, chips, scale, etc.,
using a suitable strainer installed in the suction line as near
as possible to the pump.
Suction and discharge piping must aline and not be forced
into position when assembling to a pump. All piping must
1-12
Spraymaster
Deaerator
Size
Boilermate
Column
SIze
Valve Size
Orifice Size
SM7
8 & 12
1/2
1/8
SM15
16
3/4
3/16
SM30-45
20 & 24
3/4
1/4
SM70
30
3/8
SM100
36
1-1/2
3/8
SM140
42
7/16
Deaerators
The coupling must be checked for both parallel (offset)
a l i g n m e n t a n d a n g u l a r ( g a p ) a l i g n m e n t . Pa r a l l e l
misalignment occurs when shaft axes are parallel but not
concentric (see Figure 1-16). Angular misalignment is the
reverse situation - shaft axes concentric but not parallel.
If the boiler is empty and will be filled from this tank, close
the pump discharge shut-off valve. Be sure that the pump is
turned off.
! CAUTION
DANGER
Be sure that the orifice ent valve supplied with
the unit is installed. Damage to the equipment
could result.
750-183
1-13
Deaerators
with steam pressures ranging from 2 to 15 psig,
5 psig is the recommended operating pressure.
CV
30
40
50
60
70
100
13
15
17
11
7.7
27
33
43
52
58
64
80
10.1
32
39
50
60
67
75
93
1-1/4
19.3
63
77
100
118
134
148
184
1-1/2
25
80
97
125
149
168
186
232
40
126
155
200
238
269
298
370
78
250
305
390
460
530
575
710
110
350
425
555
650
740
220
710
850
Notes:
1. McDonnel Miller #51-S maximum body rating is 35 psi. Deaerator relief valve to be set at 35 psi. Use same selection as 50
psi setting. Make up side Temperature Rating 70F maximum (do not use on Deaerator of two tank system).
2. Capacities are based on 15 psi back pressure from water spray nozzle including deaerator operating pressure of 5 psi.
Valves used for make-up on atmospheric tanks will fl w slightly more water.
3. Specific GPM and PSI when orde ing.
4. Same sizing chart applies for emergency make-up valves. The difference is the external float controllers p ysical location.
5. Valves are suitable for temperatures up to 300F.
6. Valves 1 thru 2 Warren No. 326L, bronze body with balanced piston, stainless steel seating surfaces and screwed ends.
7. Valves 2-1/2 thru 4 are Warren No. 322L, Q.O. port with cast iron bodies and 125# flanged connection .
8. External float controller used is Warren No. 377 with 8 S.S. float
1-14
750-183
Deaerators
CV
ACTUATOR
USED NO.
SHIPPING WEIGHT
WITH CONTROLLER
LBS
30
35
40
45
50
60
1/2
4.1
30
13
16
18
20
22
24
28
195
3/4
8.2
30
26
32
37
42
46
49
56
195
12.7
30
41
50
58
65
71
77
87
200
1-1/2
22.2
30
72
88
101
113
124
134
152
230
50.0
40
161
198
228
255
280
302
342
275
2-1/2
77.7
40
251
307
355
397
434
467
533
290
104.0
45
336
411
475
531
581
628
712
315
Notes:
1. Capacities are based on 15 PSI back pressure from spray nozzle including a Deaerator operating pressure of 5 PSI. Valves used for
make-up on atmospheric tanks will fl w slightly more water.
2. Specify GPM and PSI when ordering.
3. Same sizing chart applies to emergency make-up valves. The difference is the physical location of the level controller.
4. Control valve is globe type with proportional control and with spring-opposed diaphram actuator arranged for 3-15 PSIG operating pressure. Controller is proportional type sensing the level of the liquid in the tank using a 14 inch diplacer and produces a standard pneumatic
output signal. (Valve normally open on loss of air.)
5. All make-up valves 2 and smaller have screwed NPT connections.
6. All make-up valves 2-1/2 and larger are ANS1 125 lb. flange connection .
7. Valves are suitable for water temperatures up to 410F.
8. All valves are Fisher model 657EZ except for the 2-1/2 size which is 657ES.
9. Valves are cast iron body with hardened stainless steel trim and TFE packing.
10. Controller is a Fisher model 2500-249.
Always observe the water level in the gauge glass and make
any necessary re-adjustment to maintain the desired level.
Deaerators
Depending upon conditions, ambient temperature, length of
shut down, etc. the water temperature in the deaerator tank
may have cooled considerably. Because of the advantage of
feeding hot deaerated water to the boiler as soon as possible,
it may be desirable to speed up heating of the water more
quickly than normal operation will accomplish. This can be
done as soon as steam is available by manually operating the
drain valve to dump water so that make-up water and steam
will enter. Care must be taken not to overload the system or to
starve the pump. When the desired operating temperature and
pressure are obtained be sure to tightly shut the drain valve.
During shut downs, especially seasonal or extended periods,
chemical treatment of the water in the deaerator is
required.Your feedwater consultants recommendations
regarding the use of an oxygen scavenger should be followed.
1.5 MAINTENANCE
Cleaver-Brooks equipment is designed, engineered, and built
to provide long life and excellent service on the job. Good
operating practices and conscientious maintenance and care
will obtain efficiency and economy from their operation and
contribute to long years of performance.
A well planned maintenance program avoids unnecessary
down time or costly repairs, promotes safety, and aids boiler
code and local inspectors. An inspection schedule with a
listing of procedures should be established. It is
recommended that a boiler room log, or record, be
maintained. Recording of daily, weekly, monthly and yearly
maintenance activities provides a valuable guide and aids in
obtaining economies and length of service from CleaverBrooks equipment.
Even though the deaerator has electrical and mechanical
devices that make it operate automatically, these devices
require systematic and periodic maintenance. Any
automatic features do not relieve the operator from
responsibility, but rather free him of some repetitive chores,
providing time to devote to maintenance.
1-16
750-183
Deaerators
6" 1/8"
7-5/8" 1/8"
TEMPERATURE
F
212.
215.5
218.7
221.7
Capacity in
lb/hr
224.5
227.3
10,000
229.9
45,000
232.4
234.9
78,500
138,000
293,000
750-183
237.2
10
239.5
11
241.7
12
243.8
13
245.9
14
247.9
15
249.8
1-17
Deaerators
Model No.
Rating
lb/hr
Gallons to
Overflow 10
Minute
Storage
Tank Size
Gallons to
Overflow 5
Minute
Storage
SM7
7,000
230
36" x 6"0"
SM15
15,000
300
48" x 8"0"
SM30
30,000
600
54" x 10"0"
300
48" x 80"
SM45
45,000
900
60" x 111"
450
48" x 108"
SM70
70,000
1,400
66" x 14"10"
700
54" x 116"
SM100
100,000
2,000
72" x 167"
1,000
60" x 120"
SM140
140,000
2,800
84" x 154"
1,400
66 x 1410"
SM200
200,000
4,000
96" x 159"
2,000
72 x 167"
SM280
280,000
5,600
108" x 16"8"
2,800
84" x 154""
Tank Size
Gallons to Overflow 10
Minute Storage
SM7 D
7,000
230/160
36" x 90"
SM15 D
15,000
300
48 x 116"
Model No.
Tank Size
SM30 D
30,000
600
54" x 150"
SM45 D
45,000
900
60" x 173"
SM70 D
70,000
1,400
66" x 228"
SM100 D
100,000
2,000
72" x 260"
SM140 D
140,000
2,800
84 x 250"
SM200 D
200,000
4,000
96 x 263"
SM280 D
280,000
5,600
108 x 284"
NOTES:
Duo-Tank Deaerators have a 10 minute storage capacity in each section.
200 and 280 Models use two internal sprays.
1-18
750-183
Deaerators
Table 1-8a. Steam Pressure Reducing Valve Capacity (Spence With Pilot Operator)
AVERAGE INLET MIX TEMPERATURE
STEAM REQUIRED AS % OF
TOTAL OUTPUTCAPACITY (2)
200F
4%
150F
8%
100F
12%
50F
16%
Note:
High pressure steam must be reduced to less than 15 PSIG for a standard deaerator to function properly. The steam pressure reducing valve
(PRV) regulates the fl w of steam according to the deaerator load, and holds a constant operating pressure (5 PSIG recommended) on the system. The successful operation of the deaerator requires that the capacity of the PRV be carefully matched to the load required. The following
steps will enable you to select a PRV of appropriate size:
STEP 1: Determine the peak output capacity of the deaerator, i.e. maximum pumping rate out of the deaerator during normal operation, and the
steam supply pressure from the boiler.
STEP 2: Estimate the average inlet mix temperature of all input streams, i.e. cold make-up, low temperature returns and high temperature
returns (Mix temp = (fl w 1 x temp + fl w 2 x temp + fl w 3 x temp) / total fl w). NOTE: Consult the local Cleaver-Brooks Representative if average mix temperature is greater than 210F.
STEP 3: Refer to Table 1-8 to determine Percentage Steam Required to heat the inlet water to 227F (5 PSIG). Interpolate if necessary.
STEP 4: Multiply the Percentage Steam Required obtained above times the peak output capacity from Step 1. The result is the required capacity for the PRV. Refer to the selection chart.
EXAMPLE:
40,000 lb/hr peak total capacity
125 PSIG Operating Pressure
50% returns @ 180F = 90F
50% make-up @ 60F = 30F
Mix temperature is 120F, from Table 1 approximately 10% steam required
40,000 lb/hr x 10% = 4,000 lb/hr steam
From the selection chart choose a 1-1/2 valve with inlet pressure of 125 PSIG and capacity of 4,730 lb/hr
INLET PRESSURE
PSIG
1/2
3/4
1-1/4
1-1/2
2-1/2
250
1,265
2,435
3,970
6,360
8,930
13,985
19,845
33,380
49,165
200
1,030
1,980
3,230
5,175
7,265
11,380
16,150
27,160
40,005
150
790
1,520
2,480
3,970
5,575
8,730
12,390
20,840
30,700
125
670
1,290
2,100
3,370
4,730
7,405
10,510
17,680
26,040
100
550
1,060
1,725
2,765
3,885
6,080
8,630
14,515
21,380
75
420
805
1,315
2,105
2,955
4,630
6,570
11,050
16,275
50
310
600
975
1,560
2,190
3,430
4,870
8,185
12,060
25
190
365
595
955
1,345
2,105
2,985
5,025
7,400
12**
280
430
690
1,005
1,610
2,490
3,515
5,235
Shipping Weight
Spence ED
21
25
30
40
50
69
107
137
242
Shipping Weight
Spence E2D
28
29
40
46
60
80
108
145
750-183
1-19
Deaerators
Table 1-8b. Safety Valve(s) Required (Spence with Pilot Operator)
1/2
3/4
1-1/4
1-1/2
2-1/2
250
1@1-1/2
1@2
1@1-1/4
1@2
2@1-1/2
1@2
3@2
2@2-1/2
1@2-1/2
1@3
3@3
1@4N
2@4P
200
1@1-1/4
1@2
2@1-1/2
2@2
1@1-1/2
2@2
1@3
2@2-1/2
3@2-1/2
1@2-1/2
3@3
150
1@1-1/4
1@1-1/2
1@2
1@1-1/4
1@2
2@2
3@2
2@2-1/2
2@3
1@2-1/2
2@3
125
1@1
1@1-1/2
1@2
2@1-1/2
1@1-1/2
1@2
1@1-1/2
2@2
1@3
1@2-1/2
1@3
3@2-1/2
100
1@1
1@1-1/4
1@1-1/2
1@2
1@1-1/2
1@2
2@2
3@2
2@2-1/2
2@3
75
1@3/4
1@1-1/4
1@1-1/2
1@2
1@2
1@1-1/2
1@2
2@2-1/2
1@2
2@2-1/2
2@2-1/2
50
1@3/4
1@1
1@1-1/4
1@1-1/2
1@2
2@1-1/2
1@1-1/2
1@2
3@2
2@2-1/2
Example: Having selected a 1-1/2 PRV at 200 PSIG max. inlet pressure, relief valve(s) required from the table are:
One (1) 1-1/2 inch valve and Two (2) 2 inch valves.
Notes:
1. All relief valves are selected for vessel design maximum pressure of 50 psig. Consult with consult the local Cleaver-Brooks Represenatative if different settings are required.
2. These safety valve selections are based on standared catalogued pressure reducing valves indicated. Contact the local CleaverBrooks Representative if non-standard PRVs are used.
3. Consult the local Cleaver-Brooks Representative for safety valve size in the presence of significant high tempe ature returns.
4. Bypass valves installed in PRV piping must be sized to not exceed relief valve capacity.
1-20
750-183
Deaerators
Table 1-9. Steam Pressure Reducing Valve Capacity (Fisher With Pilot Operator)
AVERAGE INLET MIX TEMPERATURE
200F
4%
150F
8%
100F
12%
50F
16%
Note:
High pressure steam must be reduced to less than 15 PSIG for a standard deaerator to function properly. The steam pressure reducing valve
(PRV) regulates the fl w of steam according to the deaerator load, and holds a constant operating pressure (5 PSIG recommended) on the system. The successful operation of the deaerator requires that the capacity of the PRV be carefully matched to the load required. The following
steps will enable you to select a PRV of appropriate size:
STEP 1: Determine the peak output capacity of the deaerator, i.e. maximum pumping rate out of the deaerator during normal operation, and the
steam supply pressure from the boiler.
STEP 2: Estimate the average inlet mix temperature of all input streams, i.e. cold make-up, low temperature returns and high temperature returns
(Mix temp = (fl w 1 x temp + fl w 2 x temp + fl w 3 x temp) / total fl w). NOTE: Consult the local Cleaver-Brooks Representative if average mix
temperature is greater than 210F.
STEP 3: Refer to Table 1-9 to determine Percentage Steam Required to heat the inlet water to 227F (5 PSIG). Interpolate if necessary.
STEP 4: Multiply the Percentage Steam Required obtained above times the peak output capacity from Step 1. The result is the required capacity for the PRV. Refer to the selection chart.
EXAMPLE:
40,000 lb/hr peak total capacity.
125 PSIG Operating Pressure
65% returns @ 180F = 117 F
35% make-up @ 60F = 21 F
Mix temperature is 138F, from Table 1 approximately 9% steam required
40,000 lb/hr x 9% = 3,600 lb/hr steam
From the selection chart choose a 1-1/2 valve with inlet pressure of 125 PSIG and capacity of 4,140 lb/hr
INLET
PRESSURE
PSIG
VALVE
SIZE
1/2
92C
3/4
92C
1
92B
1-1/2
92B
2
92B
250
4,460
7,820
200
3,610
2-1/2
92S
3
92B
4
92B
13,000
27,200
37,300
6,480
10,700
21,900
29,500
150
400
740
2,770
5,000
8,220
11,900
16,700
23,600
125
390
730
2,310
4,140
6,950
10,000
13,900
19,600
100
370
710
1,900
3,400
5,710
8,500
11,500
16,100
75
370
590
1,500
2,510
4,610
6,000
9,080
10,900
50
250
440
1,080
1,830
3,300
4,180
6,500
8,960
25
200
280
660
1,060
2,060
1,000
3,800
4,940
Notes:
1. Steam Capacities are based on pressure reduction to 5 PSIG. Consult the local Cleaver-Brooks Representative if higher deaerator operating
pressure are required.
2. Percentage Steam Required in Table 1-9 includes the contribution of deaerating steam condensate to the total load.
3. For inlet pressure above 250 PSIG, cast steel valves are available. Consult the local Cleaver-Brooks Representative for details. For inlet pressure below 25 PSIG consult the local Cleaver-Brooks Representative for details.
750-183
1-21
Deaerators
Table 1-9b. Safety Valve Requirements (Fisher with Pilot Operated)
1/2
3/4
1-1/2
2-1/2
250
1@1-1/4
1@1-1/2
1@2
1@1/2
2@2
3@2
2@3
1@2
1@4P
1@2
1@1-1/2
2@4P
200
1@1
1@1-1/4
2@2
1@2
1@1-1/2
2@2
1@1-1/2
2@3
2@3
1@4P
2@2
150
1@3/4
1@1
2@2
1@2
1@3/4
2@2
3@2
1@2-1/2
2@2
2@3
1@1/2
125
1@3/4
1@1
1@1-1/2
2@2
1@2
1@1-1/2
2@2
1@1-1/4
1@3
1@1-1/2
1@3
2@2
100
1@3/4
1@1
1@1-1/2
2@2
1@2
1@1-1/4
2@2
2@2
1@1-1/2
1@2-1/2
1@2
1@1-1/2
75
1@1/2
1@3/4
1@1-1/4
1@1-1/2
1@2
1@1/2
1@2
1@1-1/4
2@2
1@1/2
2@2
1@1-1/2
Example: Having selected a 2 inch PRV at 200 PSIG max. inlet pressure, relief valve(s) required from the table are: Two (2) 2 inch
valves and One (1) 1-1/2 inch valve.
Notes:
1. All relief valves are selected for vessel design maximum pressure of 50 psig. Consult with the local Cleaver-Brooks Representative if
different settings are required.
2. These safety valve selections are based on standared catalogued pressure reducing valves indicated. Contact the local CleaverBrooks Representative if non-standard PRVs are used.
3. Consult the local Cleaver-Brooks Representative for safety valve size in the presence of significant high tempe ature returns.
4. Bypass valves installed in PRV piping must be sized to not exceed relief valve capacity.
1-22
750-183
Deaerators
Table 1-10a. Steam Pressure Reducing Valve Capacity (Fisher With Pneumatic Type)
AVERAGE INLET MIX TEMPERATURE
200F
4%
150F
8%
100F
12%
50F
16%
Note:
High pressure steam must be reduced to less than 15 PSIG for a standard deaerator to function properly. The steam pressure reducing valve
(PRV) regulates the fl w of steam according to the deaerator load, and holds a constant operating pressure (5 PSIG recommended) on the system. The successful operation of the deaerator requires that the capacity of the PRV be carefully matched to the load required. The following
steps will enable you to select a PRV of appropriate size:
STEP 1: Determine the peak output capacity of the deaerator, i.e. maximum pumping rate out of the deaerator during normal operation, and the
steam supply pressure from the boiler.
STEP 2: Estimate the average inlet mix temperature of all input streams, i.e. cold make-up, low temperature returns and high temperature returns
(Mix temp = (fl w 1 x temp + fl w 2 x temp + fl w 3 x temp) / total fl w). NOTE: Consult PWS Sales if average mix temperature is greater than
210F.
STEP 3: Refer to Table 10a to determine Percentage Steam Required to heat the inlet water to 227F (5 PSIG). Interpolate if necessary.
STEP 4: Multiply the Percentage Steam Required obtained above times the peak output capacity from Step 1. The result is the required capacity for the PRV. Refer to the selection chart.
EXAMPLE:
40,000 lb/hr peak total capacity
150 PSIG Operating Pressure
65% returns @ 180F= 117 F
35% make-up @ 60F = 21 F
Mix temperature is 138F, from Table 1 approximately 9% steam required
40,000 lb/hr x 9% = 3,600 lb/hr steam
From the selection chart choose a 1 valve with inlet pressure of 150 PSIG and capacity of 3,740 lb/hr
Valve
Body Size
Inlet
Press
PSIG
Orifice Si e
1"
1/2"
3/4"
1-1/2"
2"
2-1/2"
3"
4"
1-1/2
1-1/2
2-7/8"
6 30
300
2100
Size 30
4500
Size 30
7000
Size 30
12500
Size 34
30000
Size 45
45000
Size 70
275
1900
Size 30
4000
Size 30
6500
Size 30
11000
Size 34
28000
Size 45
42000
Size 70
250
1750
Size 30
3750
Size 30
5900
Size 30
10000
Size 34
25000
Size 45
38000
Size 70
225
1600
Size 30
3400
Size 30
5300
Size 30
9300
Size 34
23000
Size 45
35000
Size 70
44000
Size 70
200
1400
Size 30
3100
Size 30
4800
Size 30
8500
Size 34
20500
Size 45
27000
Size 70
44000
Size 70
175
1250
Size 30
2700
Size 30
4200
Size 30
7400
Size 34
18000
Size 45
27000
Size 70
35000
Size 70
150
1100
Size 30
2350
Size 30
3700
Side 30
6500
Size 34
15500
Size 45
23500
Size 45
30000
Size 70
100
940
Size 30
1950
Size 30
3000
Size 30
5500
Size 34
13000
Size 45
20000
Size 45
26000
Side 45
42500
Size 70
75
740
Size 30
1600
Size 30
2500
Size 30
4500
Size 34
11000
Size 40
16500
Size 45
21000
Size 45
35000
Size 70
55
580
Size 30
1200
Size 30
1900
Size 30
3400
Size 34
8400
Size 40
12500
Size 45
16000
Size 45
27000
Size 70
50
420
Size 30
900
Size 30
1400
Size 30
2300
Size 34
6000
Size 40
9000
Size 45
11500
Size 45
19000
Size 70
NOTES:
1. Steam capacities are based on pressure reduction to 5 PSIG. Consult the local Cleaver-Brooks Representative of higher deaerator operating pressures are
required.
2. Percentage steam required in Table 10a includes the contribution of deaerating steam condensate to the total load.
3.Consult the local Cleaver-Brooks Representative if inlet pressures exceeds 300 PSIG or is lower than 50 PSIG.
750-183
1-23
Deaerators
Table 1-10b. Safety Valve Selection Requirements
(For FISHER pneumatically operated PRVs).
1
1/2
1
3/4
1
1
1-1/2
1-1/2
2
1-1/2
2-1/2
2-7/8
3
3
4
4
300
1@1-/12
1@2
1@1/2
1@2
1@1-1/2
3@2
2@4(N)
1@1-1/4
2@4(P)
1@2
250
1@1-1/2
1@2
1@2
1@1-1/4
2@2
1@1-1/4
2@3
1@1-1/4
2@4(P)
200
1@1-1/4
1@2
1@2
1@3/4
2@2
1@4(N)
2@2
2@3
1@2
2@4(P)
150
1@1-1/4
1@1-1/2
1@2
1@2
1@1-1/2
1@2-1/2
1@2
1@1-1/2
2@3
2@4(N)
1@1-1/4
125
1@1-1/4
1@1-1/2
1@2
1@2
1@1-1/2
1@2-1/2
1@2
1@1-1/2
2@3
2@4(N)
1@1-1/4
100
1@1
1@1-1/2
1@2
1@2
1@1-1/4
3@2
1@3
2@2
3@3
1@1-1/2
2@4(P)
1@1
75
1@1
1@1-1/4
1@1-1/2
1@2
1@1/2
2@2
1@1-1/2
1@2-1/2
2@2
2@2-1/2
1@1-1/2
1@4(P)
2@2-1/2
Example: Having selected a 1 PRV at 200 PSIG max. inlet pressure, relief valve(s) required from the table are: One (1) 2 inch
valve and One (1) 3/4 inch valve.
Notes:
1. All relief valves are selected for vessel design maximum pressure of 50 psig. Consult with the local Cleaver-Brooks Representative if
different settings are required.
2. These safety valve selections are based on standared catalogued pressure reducing valves indicated. Contact the local Cleaver-Brooks
Representative if non-standard PRVs are used.
3. Consult the local Cleaver-Brooks Representative for safety valve size in the presence of significant high tempe ature returns.
4. Bypass valves installed in PRV piping must be sized to not exceed relief valve capacity.
5. After selecting the pressure reducing valve, locate the quantity and size of relief valves required opposite the maximum inlet pressure.
6. Maximum inlet pressure is the safety valve set pressure on the boiler or header, not the operating pressure.
1/2 through 2 inch valves are Kunkle Fig. 6010 or equal.
2- 1/2 through 4 inch valve is Kunkle Fig. 252 with N-orifice or P-o ific .
1-24
750-183
Deaerators
1-25
1-26
Figure 1-18. Make-Up Valve Arrangement for Spraymaster or Boilermate Storage Tanks (McDonnell & Miller No. 51)
SPRAYMASTER
BOILERMATE
Deaerators
750-183
Figure 1-19. Make-Up Valve Arrangement for Spraymaster Storage Tanks (McDonnell & Miller No. 51)
Deaerators
750-183
1-27
1-28
SPRAYMASTER
Figure 1-20. Make-Up Valve Arrangement for Spraymaster or Boilermate Storage Tanks (Warren 326L & 322L Valve with No. 377 Controller)
BOILERMATE
Deaerators
750-183
Figure 1-21. Make-Up Valve Arrangement for Spraymaster Storage Tanks (Warren 326L & 322L Valve with No. 377 controller)
Deaerators
750-183
1-29
1-30
SPRAYMASTER
Figure 1-22. High and Low Alarm Control Arrangement for Spraymaster or Boilermate Storage Tanks (Mercoid or McDonnell Miller 64)
BOILERMATE
Deaerators
750-183
Section 2
Pressure Reducing Valves
START-UP AND SETTING
On pressure reducing valves such as the type ED, use a by-pass
to fill the delivery system and raise pressure to slightly below
normal required. Close the pilot by releasing compression on
the adjusting spring. See Figure 2-1. Open the 1/4" control pipe
valve, crack the outlet stop valve, the crack inlet stop valve, and
blow down the strainer.
! CAUTION
DANGER
Never open a reducing valve without positive indication that the high side is clear of condensate.
Open the inlet stop valve and gradually compress the adjusting
spring until the valve opens and takes control at the desired
pressure. Alternately choke down on the by-pass and open the
outlet stop valve until the regulator is on the line, See individual
instructions for other pilots.
ADJUSTING NUTS
BLEEDPORT BEND
NO. 4A BLEEDPORT
ADJUSTING SPRING
NO. 88 TEE
2.
3.
4.
5.
1/4"
CONTROL
PIPE
2.
3.
4.
DO NOT INSULATE
BELOW THIS LINE
750-183
2-1
After the first few days of operation and twice a year, the
following should be checked.
1.
2.
Inspect all joints for leakage. Keep bolts tight. Never allow
a leak to persist.
MAINTENANCE
Inspection
Under normal conditions, complete dismantling at regular
intervals is not recommended. A valve kept relatively free of
dirt will function for years with minimum attention.
Notes:
2-2
750-183
Section 3
Parts
Table 3-1. Standard Spraymaster Parts
PART NO.
DESCRIPTION
USAGE
851-284
108" Dia
853-115
2 per Glass
853-618
825-281
850-50
850-583
937-669
937-660
937-662
934-322
817-161
817-187
750-183
DESCRIPTION
853-115
853-618
825-281
853-913
853-914
853-915
853-916
853-917
853-918
850-50
850-583
937-669
937-660
934-322
817-161
914-238
USAGE
2 per Glass
Qty
Column Size
cu-ft
0.7
12
1.6
16
3.0
20
5.0
24
8.0
30
12.0
36
18.0
42
29.0
3-1
Parts
MODEL SM 15-P
SPRAYMASTER
MODEL BM 30 800
PACKAGED UNIT
BOILERMATE
SIZE OF TANK
IN GALLONS
QTY.
PART NO.
DESCRIPTION
934-322
194-42
869-61
13-174
Cap, Spring
82-77
Spring
939-65
869-61
67-553
Hook, Spring
82-76
10
903-164
Spring
11
853-710
12
194-74
Valve, Atomizing
13
194-71
Pin, Roll
14
952-122
15
869-35
16
194-90
17
853-543
18
63-68
Stationary Baffl
TANK
ITEM 1
ITEM 2
ITEM 3
SIZE
656-6203
141-777
853-1003
28"
SM100
656-6202
141-810
853-1002
32"
SM140
656-5923
141-743
853-1004
36"
2
3
3-2
750-183
Parts
COVER
PART NO.
YOKE
REQ.
PART NO.
BOLT
REQ.
PART NO.
NUT
REQ.
PART NO.
WASHER
REQ.
PART NO.
REQ.
821-191
953-40
868-778
869-320
952-132
821-188
821-187
953-50
868-366
869-65
952-124
869-65
952-288
821-207
953-50
868-366
FISHER #92
PART NO.
CURRENT FISHER
REPLACEMENT
PART NO.
APPROXIMATE WEIGHT
940-1448
918-505
12 lbs
940-1329
918-507
23 lbs
940-1449
918-512
23 lbs
940-1355
940-1427
918-513
42 lbs
940-1447
918-514
55 lbs
940-1611
918-516
67 lbs
940-1612
918-517
115 lbs
940-1618
918-518
165 lbs
940-1617
NOTE: The above chart is only for standard Cleaver-Brooks specified deae ator pressure reducing valves.
PART NO.
APPROXIMATE WEIGHT
940-4904
24 lbs
940-4339
28 lbs
940-4905
33 lbs
940-4722
43 lbs
940-4077
53 lbs
2 Spence PRV
940-3298
77 lbs
940-4906
92 lbs
940-4907
120 lbs
940-3976
210 lbs
940-4450
290 lbs
NOTE: The above chart is only for standard Cleaver-Brooks specified deae ator pressure reducing valves.
750-183
3-3
Parts
PART NO.
APPROXIMATE WEIGHT
940-4919
28 lbs
940-3321
29 lbs
940-4358
40 lbs
940-2740
46 lbs
940-2885
67 lbs
940-2859
80 lbs
940-3390
108 lbs
940-3357
145 lbs
940-4069
195 lbs
940-3303
260 lbs
NOTE:
The above chart is only for standard Cleaver-Brooks specified deae ator pressure reducing valves.
PART NO.
825-216
825-281
941-55
825-317
PART NO.
APPROXIMATE WEIGHT
817-2040
60 lbs
817-2041
75 lbs
817-1910
125 lbs
817-1554
150 lbs
817-1663
200 lbs
817-673
65 lbs
817-769
110 lbs
817-666
120 lbs
817-671*
No Longer Mfg.
*Replace with 3" Warren #313 (Part No. 817-1910), but note that piping will have to be modified to fi
3-4
750-183
Parts
PART NO.
817-672
817-2012
817-205
817-1523
817-1815
Note: These float cages are used with ma e-up valves. The float cage detects
water level and the make-up valves lets water in.
PART NO.
940-05724
940-05725
940-05726
940-05727
940-05728
940-05729
APPROXIMATE
WEIGHT
940-3539
8 lbs
797-04052
940-3540
8 lbs
797-04052
940-3541
8 lbs
797-04053
940-3542
19 lbs
797-04054
940-3543
25 lbs
797-04054
940-3544
30 lbs
797-04055
DESCRIPTION
DESCRIPTION*
PART NO.
* Kits include O-ring, seat ring, pilot valve assembly, packing, piston rinr, and expander.
750-183
3-5
Parts
Table 3-14. Make-Up Controls (Lever Operated Make-Up Valves) (Fisher 670EK)
DESCRIPTION
PART NO.
940-4894
940-4474
940-5193
940-4278
940-4320
Table 3-15. Make-Up Controls (Lever Operated Make-Up Valves) (Fisher 608EK)
DESCRIPTION
PART NO.
940-4697
940-4781
940-4580
Table 3-16. Make-Up Controls (Diaphragm Operated Make-Up Valves) (Fisher 657ES)
DESCRIPTION
PART NO.
940-4520
940-4632
940-4081
940-3849
940-4660
940-4555
940-4684
3-6
750-183
Parts
MODEL USED
DESCRIPTION
194-72
SM7
277-116
SM15
277-117
SM30 - SM45
277-118
SM70
277-119
277-120
295-109
295-111
97-221
Cone Assembly
97-222
Cone Assembly
97-239
Cone Assembly
656-6203
656-6202
656-5923
141-777
141-810
141-743
797-4039
All Models
Engineering Calculations
When retrofiting the deae ator to a davited manway, please use these part numbers related to the model.
Table 3-18. Spray Nozzle Assembly or Water Inlet Assembly (SM-15 thru SM280)
MODEL NUMBER
SM-15
277-116
SM-30
277-117
SM-45
277-117
SM-70
277-118
SM-100
277-119
SM-140
277-120
SM-200
277-119 (2 Required)
SM-280
277-120 (2 Required)
NOTE: The water inlet assembly does not change from old style to new style.
Only the steam inlet assembly changed from spring loaded to counter balanced. The next fi e pages shows a parts break down of the water inlet assemblies.
750-183
3-7
Parts
530-256
530-257
12
530-258
16
530-259
20
530-260
24
530-261
30
530-262
36
530-263
42
NOTE: The reason a support grid comes in pieces instead of a complete circle is for installation purposes.
LENGTH OF LINER
102-47
25-9/16"
102-50
12
28"
102-51
16
29-1/4"
102-52
20
30-1/4"
102-53
24
32-1/4"
102-54
30
34-1/4"
102-55
36
36-1/4"
102-56
42
38-1/4"
3-8
12
16
20
24
30
36
42
750-183
Parts
NOMINAL DIMENSIONS
172-388
172-387
12
172-3885
16
172-386
20
172-387
24
172-388
30
172-389
36
172-390
42
NOTE: Bare column only is the shell with grid support and liner. This does not include water inlet assembly, gaskets, packing, plug or
data nameplate.91-121
Table 3-23. Boilermate Column Type Deaerator Water Inlet Valve Parts
COLUMN
MODEL
WATER INLET
ASSEMBLY
MANUAL
VENT VALVE
SPRING
DISC
SPRING
CAP
2 REG.
NUT (JAM)
2 REQ.
AUTO VENT
VALVE
277-139
194-42
82-50
91-122
13-167
869-370
934-322
12
277-146
194-42
82-24
91-121
13-86
869-370
934-322
16
277-116
194-44
82-107
91-109
13-86
869-370
934-322
20
277-117
194-43
82-52
91-110
13-160
869-209
934-322
24
277-117
194-43
82-52
91-110
13-160
869-209
934-322
30
277-118
194-46
82-20
91-111
13-160
869-209
934-322
36
277-119
194-45
82-21
91-112
13-160
869-209
934-322
42
277-120
194-49
82-21
91-113
13-160
869-209
934-322
SM-15
SM-30
SM-45
SM-70
SM-100
SM-140
SM-200*
SM-280*
750-183
3-9
e-mail: [email protected]
Web address: http://www.cleaverbrooks.com