AI-518/AI-518P Artificial Intelligence Industrial Controller

Download as pdf or txt
Download as pdf or txt
You are on page 1of 58

Yudian (H.K.) Automation Technology Co. Ltd.

Website: http://www.yudian.us http://www.yudian.com.hk


Email: [email protected]
Tel: +852-2770 8785 Fax: +852-2770 8796

AI-518/AI-518P
ARTIFICIAL INTELLIGENCE INDUSTRIAL CONTROLLER
Operation Instruction
Ver. 8.0

(Applicable for accurate controls of


Temperature, Pressure, Flow, Level and Humidity etc.)

CONTENTS

1.

SUMMARY .............................................................................................................................................................. 1
1.1

MAIN FEATURES

1.2

ORDERING CODE DEFINITION

1.3

MODULES

1.4
1.5
2.

1.3.1
Slots of modules
1.3.2
Commonly used modules:
1.3.3
Installation and replacement of modules
1.3.4
Electric isolation of the modules
1.3.5
Further descriptions about module applications
TECHNICAL SPECIFICATION
REAR TERMINAL LAYOUT AND WIRING

4
6
7
7
8
9
12

DISPLAYS AND OPERATIONS .......................................................................................................................... 16

3.

2.1

FRONT PANEL DESCRIPTION

16

2.2

PARAMETER SETTING FLOW CHART

18

2.3

OPERATION DESCRIPTION

19

2.3.1
2.3.2
2.3.3

19
19
21

Parameter Setting
Set Value Setting
Auto Tuning

PARAMETERS AND SETTINGS........................................................................................................................ 23


3.1

PARAMETER LOCK (LOC) AND FIELD PARAMETERS

23

3.2

THE PARAMETER TABLE

24

3.3

ADDITIONAL REMARKS OF SPECIAL FUNCTIONS

42

3.3.1
3.3.2
3.3.3

42
42
43

Single-phase phase-shift trigger output


Alarm blocking at the beginning of power on
Setpoints switch

3.3.4
3.3.5

Communication function
Temperature re-transmitter / Program generator / Manual current output

43
44

4. FURTHER DESCRIPTION FOR THE OPERATION OF AI-518P SERIES INSTRUMENT .......................... 45


4.1 CONCEPTS AND FUNCTIONS PROGRAM

StEP:
StEP time:
Running time:
Jump:
Run/Hold:
Stop:
Power cut/resume event handling:
PV startup and PV preparation function (rdy function) :
Curve fitting:

45

45
45
45
46
46
46
46
47
47

5. PROGRAMMING AND OPERATION (FOR AI-518P ONLY) ........................................................................ 48


5.1 RAMP MODE(PAF : B=0)

48

5.2 SOAK MODE(PAF : B=1)

51

Time setting
Program arrangement of multi-curve operation

51
52

1. SUMMARY
1.1 Main Features
z
z
z
z
z
z

Adopt digital calibration technology for input measurement with input measurement accuracy 0.3% F.S., Support
standard thermocouples and RTDs, maximum resolution is 0.01
Adopt advanced artificial intelligence control algorithm, no overshoot and with the function of auto tuning (AT)
and self-adaptation.
Adopt advanced modular structure, conveniently providing plentiful output options, able to satisfy the
requirements of various applications, make quick delivery and convenience the maintenance of the instrument.
Friendly and customized operating interface leads to easy learning and simple operation. Parameter can be
promoted to immediate operator access in Field Parameter Table or password protected in Full Parameter
Table.
With worldwide power supply of 100-240VAC or 24VDC and various installation dimensions for users to choose.
ISO9001 and CE certified, achieving world class level of quality, anti-interference ability and safety.
POINTS FOR ATTENTION
This manual introduces AI-518/AI-518P ARTIFICIAL INTELLIGENCE INDUSTRIAL CONTROLLER of
Version 8.0. Certain functions introduced by this manual are probably not applicable for the instrument of
other version. When power on, instruments model and software version will be displayed. User should
1

pay attention to the difference between different versions when using the instrument. Please read this
manual carefully in or der to use the instrument correctl y and make it to its full use.
Please correctly set parameters according to input / output type and function. Only correctly wired
instruments with parameters correctly set can be put into use.

1.2 Ordering Code Definition


Advanced modularized hardware design is utilized for AI series instruments. There are maximum five module slots:
multi-function input/output (MIO), main output (OUTP), alarm (ALM), auxiliary output (AUX) and communication
(COMM). The modules can be purchased together with or separately from the instrument, and can be assembled
freely. The input type can be freely set to thermocouple, RTD, or linear current/voltage.
The ordering code of AI-518/AI-518P (V8.0) series instrument is made up of 9 parts. For example:
AI518

X3

L5

S4

24VDC (F2)

It shows that the model of this instrument is AI-518, front panel dimension is 9696mm, no module is installed in MIO
slot, X3 linear current output module is installed in OUTP (main output), ALM (alarm) is L5 (dual relay contact output
module), no module is installed in AUX (auxiliary output), S4 (RS485 communication interface module) was installed
at COMM , and the power supply of the instrument is 24VDC, an extended input type (F2 radiation type pyrometer) is
available
The following is the meanings of the 9 parts:
Shows the model of the instrument
2

AI-518 : Economical type instrument with measurement accuracy 0.3%F.S. It adopts artificial intelligent control
technology, and has the functions of control, alarm, retransmission and communication.
AI-518P: Base on AI-518 added 30 segments programmable functions.

Shows the front panel dimension


A(A2)
Front panel 9696mm(widthheight), cut out 9292mm, depth behind mounting surface 100mm.
A2 has a light bar with 25 segments and 4 levels of luminosity.
B
Front panel 16080mm(widthheight), cut out 15276mm, depth behind mounting surface 100mm.
C(C3)
Front panel 80160mm(widthheight), cut out 76152mm, depth behind mounting surface 100mm.
C3 has an additional light bar with 50 segments and 2 levels of luminosity.
D
Front panel 7272mm(widthheight), cut out 6868mm, depth behind mounting surface 95mm
D4
Front panel 4848mm(widthheight), cut out 4545mm, depth behind mounting surface 95mm`
E
Front panel 4896mm(widthheight), cut out 4592mm, depth behind mounting surface 100mm
F
Front panel 9648mm(widthheight), cut out 9245mm, depth behind mounting surface 100mm
Shows the module type of multiple functions I/O (MIO). Selectable modules are I2, I4, K3 and V. N means none,
no module installed.
Shows the module type of main output (OUTP). Selectable modules are L1,L2,L4,W1,W2,G,K1,K3,K5,K6,X3,X5
etc.
Shows the module type of alarm (ALM). Selectable modules are L1, L2, L4, L5, W1, W2, G, etc.
3

Shows the module type of auxiliary output (AUX). Selectable modules are L1, L2, L4, L5, W1, W2, G, K1, X3
X5, etc.
Shows the module type of communication (COMM). Selectable modules are S, S4, V, etc.
Shows the power supply of the instrument. If left blank, the power of the instrument is 100~240VAC. Added
"24VDC" means the power supply of 20~32V DC or AC power
Shows the optional extended graduation spec (If none, leave it blank). AI-518 series instruments support many
input types including popular thermocouples, RTDs, linear voltage, current and resistance inputs. If needed, an
additional specification not mentioned in input type selection (InP) table can be extended.

Note 1: The instrument applies the technology of automatic zero and digital calibration, and is free of maintenance.
If the error exceeds certain range, generally, cleaning and drying the inside of the instrument can fix it. If not, send the
instrument back to the factory to examine and repair.

1.3 Modules
1.3.1 Slots of modules
AI-518/518P series instruments have five slots for modules to be installed (D dimension instruments have 3
slots: OUTP, AUX and COMM/AL1; D4 dimension instruments have 2 slots: OUTP and COMM/AUX). By
4

z
z

installing different modules, the controller can meet the requirements of different functions and output types.
Multiple function Input / Output (MIO):
Can input signal from 2-wire transmitter or 4-20mA signal by installing I4 (current input) module and I4 module
can provide VDC to transmitter. If a I2 (on-off signal input) module is installed, the instrument can switch between
set points SV1 and SV2 by an external switch. Cooperating with OUTP and installing a K3 module can realize
three-phase thyristor zero cross triggering output.
Main output (OUTP):
Commonly used as control output such as on-off control, standard PID control, and AI PID control. It can be
used as retransmission output of process value (PV) or set point (SV). Installing L1 or L4 modular can realize
relay contact output; installing X3 or X5 module can realize 0-20mA/4-20mA/0-10mA linear current output;
installing G module can realize SSR voltage output; installing W1 or W2 module can implement TRIAC no
contact switch output.
Alarm (ALM):
Commonly used as alarm output. Support 1 normally open + normally close relay output (AL1) by installing L1 or
L2 module or 2 normally open relay outputs (AL1+AL2) by installing L5 module.
Auxiliary output (AUX): In a heating/refrigerating dual output system, module X3, X5, L1, L4, G, W1, W2 can be
installed for the second control output. It can also output alarm by installing L1, L2 or L5 module, or be used for
communicating with computer by installing R module (RS232C interface).
Communication Interface (COMM): Module S or S4 can be installed in for communicating with computer
(RS485 communication interface), and it can also be used as power supply for external sensor when equipped
5

with a voltage output module.

1.3.2 Commonly used modules:


N
L2
L4
L5
W1/W2
G
G5
K1
K3
K5/K6
X3/X5

No module installed (or null)


Normally open + normally close relay output module (small volume, capacity: 30VDC/1A, 250VAC/1A,
suitable for alarm)
Large capacity normally open relay output module (large volume, Capacity: 30VDC/2A, 250VAC/2A)
Dual normally open relay output module (Capacity: 30VDC/2A, 250VAC/2A)
TRIAC no contact normally open (W2 is normally close) discrete output module (Capacity:
100-240VAC/0.2A)
SSR voltage output module (DC12V/30mA)
Dual SSR voltage driver (DC12V/30mA
Single-phase thyristor zero crossing trigger output module (can trigger one loop of a TRIAC or a pair of
inverse parallel SCR with current of 5-500A)
Three-phase thyristor zero crossing trigger output module (can trigger 3-phase circuit; each loop can trigger
TRIAC or a pair of inverse parallel SCR with current of 5-500A)
Single-phase 220VAC/380VAC thyristor phase-shift trigger output module (can trigger one loop of TRIAC or
a pair of inverse parallel SCR with current of 5-500A), only 50Hz power
Linear current output module (continuous 0-22mA output, selectable in the range of 0-10mA, 4-20mA etc.).
X5 is equipped with photoelectric isolated power supply.
6

S/S4
R
I2

RS485 communication interface module. S4 is equipped with photoelectric isolated power supply.
RS232 communication interface module.
Switch / frequency signal input interface for inputting external switch or frequency signal, has a 12VDC
power supply for external transducer.
I4
4-20mA/0-20mA analogue input interface, has a 24VDC/24mA power supply for a transmitter.
V24/V12/V10/V5
Isolated 24V/12V/10V/5V DC voltage output with maximum current of 50mA, can supply power for transmitter.

1.3.3 Installation and replacement of modules


Before the instrument delivery, module installation is done on request, with corresponding parameter set correctly.
Users can replace or install modules by themselves when needed. When replacing a module, you should pull the
controller out of the housing at first, insert a small flat-tip screwdriver into the opening between the original module
and the slot on motherboard to remove the old module, and then install a new module. Changing module type needs
to modify the corresponding parameters.

1.3.4 Electric isolation of the modules


There are a group of 24V and a group 12V power supply built in the instrument and isolated to the main circuit. The
24V power commonly supplies voltage output module, such as V24/V12/V10/V5, I2 and I4. The 12V power is
commonly supplies output or communication module. Generally, the relay contact output and TRIAC no contact
discrete output are self insulated from the other circuit, no matter whether other modules are installed or not. SSR
7

voltage output do not need to be insulated from input circuit, because SSR itself has isolation function. Therefore,
only the electric isolation between the communication interface and the current output should be considered. Those
modules, for example, S (RS485 communication interface), R (RS232 communication interface) and X3 (linear current
output), all need the 12V power supply. If more than one of the above modules are installed, in order to be electric
isolated, only one of them can be module without electric isolation, the other modules should be S4 or X5, which has
its own isolated power supply. For example, if an X3 module is installed in OUTP (main output) slot, for isolate
purpose, COMM slot should be install S4 or X5.

1.3.5 Further descriptions about module applications


z

Voltage output module: The voltage output modules like V24, V12, \/10 or V5 are often used for supplying
power for external transducer or feedback resistance of transmitter. These modules can be installed in any slot.
To standardize the wiring, it is recommended to be installed in the first idle slot in the order of MIO, AUX, and
COMM.
No contact switch module: W1 and W2 are new types of no contact switch module which apply the advanced
technology of burn proof and zero crossing conduction. It can replace the relay contact switch. Compared to
the relay contact output module, W1 and W2 have longer life and lower interference. They can largely lower the
interference spark of the equipment, and greatly improve the stability and reliability of the system. Protection
elements are series wound to the output terminals, so it can control continuous current up to 0.2A with maximum
allowed instantaneous current 2A. Since the driver element is TRIAC, it is suitable for controlling 100-240VAC
(not for DC power) with contactor which current below 80A. For the current larger than 80A, an intermediate
8

relay is needed.
Relay switch module: The relay modules are widely used in industrial control. However, they are the only
modules with life time limit and volume limit and have much electromagnetic interference. It is important to
choose a suitable relay module. To control equipments with 100~220VAC supply, such as contactor and
electromagnetic valve, W1 module is recommended. To control DC or AC above 50VAC, users can only use
relay module. L2 module is small, and both its normal open and normal close terminals have the function of
spark absorption, but the capacity is small. It is suitable for alarm output. L1 and L5 have bigger volume and
capacity. In the 48mm dimension instrument (for example, D4, E, F and E5), only one of L1or L5 can be installed.
L5 has dual output, can be used to support two loops of alarm, for example, AL1+AL2. If you dont like
mechanical switch, you can choose G5 (dual SSR voltage driver) and connect with external SSR instead.

1.4 TECHNICAL SPECIFICATION


z

Input type: (Either of below specifications can be used selectively in the one instrument)
Thermocouple: K, S, R, E, J, N, T, B, WRe3-WRe25, WRe5-WRe26.
Resistance temperature detector: Cu50, Pt100
Linear voltage: 05V, 15V, 01V, 0100mV, 020mV, 0~500mV etc.
Linear current (external precise shunt resist needed): 010mA,020mA, 420mA, etc.
Extended input (install I4 module in MIO) : 020mA, 420mA or two line transmitter.
Optional: apart from the above-mentioned Input type, an additional type can be provided upon request.
9

z
z
z
z
z
z
z
z

(Graduation index is needed)


Instrument Input range
K(-501300), S(-501700), R(-501700), E(0800), J(01000), N(01300), T(-200~+350),
B(200~1800)
Cu50(-50+150), Pt100(-200+800)
Linear Input: -999030000 defined by user
Measurement accuracy : 0.3%FS 0.1
Resolution : 0.1 for K, E, T, N, J, Cu50, Pt100; 1 for S,R
Temperature shift : 0.015%FS / (typical value is 80ppm/)
Sampling period : read A/D converter 8 times per second
Response time : 0.5s ( when digital filter parameter FILt=0)
Alarm function : High limit, low limit, deviation high limit and deviation low limit; providing the function of alarm
blocking at the beginning of power on.
Control period : 0.24300.0 seconds selectable, and it should be integer times of 0.5 second.
Control mode:
On-off control mode (dead band adjustable)
Standard PID with auto tuning
AI PID with auto tuning, adopting artificial intelligence algorithm.
Output mode (modularized)
10

z
z
z
z
z
z
z
z

Relay output (NO+NC): 250VAC/1A or 30VDC/1A


TRIAC no contact discrete output (NO or NC): 100240VAC/0.2A (continuous), 2A (20mS instantaneous,
repeat period5s)
SSR Voltage output: 12VDC/30mA (used to drive SSR).
Thyristor zero crossing trigger output: Can trigger TRIAC of 5500A, a pair of inverse paralleled SCRs or
SCR power module.
Linear current output: 020mA, 420mA can scaling by user. (Output voltage : X310.5V; X57V
maximum load resistor 500ohm, output precision 0.2%FS)
Electromagnetic compatibility (EMC): 4KV/5KHz according to IEC61000-4-4; 4KV according to
IEC61000-4-5.
Isolation withstanding voltage : Between power, relay contact or signal terminals 2300VDC; between
isolated electroweak terminals 600V
Power supply : 100240VAC, -15%, +10% / 50-60Hz; 120240VDC; or 24VDC/AC, -15%, +10%.
Power consumption: 5W
Operating Ambient : Temperature 060; humidity 90%RH
Front panel dimension: 9696mm, 16080mm, 80160mm, 4896mm, 9648mm, 4848mm, 7272mm
Panel cutout dimension: 9292mm, 15276mm, 76152mm, 4592mm, 9245mm, 4545mm, 6868mm
Depth behind mounting surface: 100mm
11

11

C O M C OM

100-240VAC ~

2
3

1.5 Rear Terminal Layout and Wiring

A
B

OP2
OP1

N/C

N /O

N/O

N/O

OUT P

G1
Thyristor trigger output K1/K 3

12

G2

13

G1
T hyristor trigger output K3

14

G2

CO M +
CO MM
Wiring graph of instruments
+ N /C
5
15
G1
N/O
N/O
A
L1
Note 1: For linear voltage input, if the range is below
+
Thyristor trigger outuput K3
+ N /O V+
G2
6 + N /C N/O A L2
16
500mV, connect to terminals 19 and 18. 05V or 15V
T he graph suits for upright instrum ents
M2 /MIO
w ith dim ension A or E
COM CO M
signal can be inputted from terminals 17 and 18.
0-5V
17
7
1-5V
+
AL M
Note 2: 420mA linear current signal can change to 1
18
8
5V voltage signal by connecting a 250 ohm resistor, and
+ N /O N/O AU 1
F or instrum ents w ith dim ension F or B,
then be inputted from terminals 17 and 18. If I4 module
19
just clockw ise rotate the graph 90
9 + N /C N /O A U 2
+
degree, and the num bers of the
term inals keep the sam e.
is installed in MIO slot, 420mA signal can be inputted
CO M C O M
10
20
AUX
from terminals 14+ and 15-, and 2-wire transmitter can be
inputted from terminals 16+ and 14-.
Note 3: The compensation wires for different kinds of thermocouple are different, and should be directly connect to
the terminals. When the internal auto compensation mode is used, connecting the common wire between the
compensation wire and the terminals will cause measurement error.
Note 4: When main output selected linear current or SSR voltage, output form terminal 13+, 11-,

12

Wiring graph of D dimension instruments (7272mm)


Note 1: Linear voltage signal of range below 500mV should
be inputted from terminals 13 and 12, and signal of 05V
and 15V should be inputted from terminals 11 and 12.
Note 2: 420mA linear current signal can be converted to
15V voltage signal by connecting a 250 ohm resistor and
inputted from terminals 11 and 12.
Note 3: S or S4 module can be installed in COMM slot for
communication. If relay, TRIAC no contact switch, or SSR
drive voltage output module is installed in COMM, it can be
used as alarm output.
If I2 module is
installed in COMM and parameter bAud is
set to 1, SV1 and SV2 can be switching by
connecting a switch between terminals 3 and
4.
Wiring graph of instruments with D4
dimension as below:
Note 1: D4 dimension instruments dont
13

COM COM

100-240VAC~

2
3
4
5
6
7

OP2

N/C N/O

OP1

N/O N/O

N/O

B COM

COMM/AL1

+
+

N/O N/O AU1


N/C

N/O AU2

COM COM

AUX

OUTP

G1

Thyristor trigger output


G2

9
10
11

0-5V

+ 1-5V

12
13
14

support 05V or 15V linear voltage input. However, 05V or 15V signal can be converted to 0500mV or
100500mV by connecting external precise resistors, 420mA can be converted to 100500mV by connecting a
25ohm resistor, then be inputted from terminals 9 and 8.
Note 2: For COMM/AUX slot, if S or S4 communication module is installed, it can be used for communication; if L2
module is installed in, parameter set bAud = 0, it can be used for AU1 or AU2 alarm output; if set parameter bAud = 2,
it can be used for AU1 or AL1 alarm output. If L1, L2, L4, G, K1, W1 or W2 is installed, it can be the auxiliary output in
bidirectional (heating/refrigerating) control (Auxiliary output doesnt support analog current output); if I2 is installed and
bAud = 1, then it can input on-off signal to switch SV1 and SV2 (AI-518) or switching the program status RUN / Stop
(AI-518P) by connecting a switch between terminals number 3 and 5.

14

SCR

Power Module
1N4001

Capacitor Resistor
Varistor
Absorber Circuit

BX

G1
SCR X2
5~500A

Thyristor trigger output G2

ZNR

100~380VAC

Load

IN4001
Capacitor Resistor
Varistor
Absorber Circuit

BX

G1

Thyristor trigger output

G2

TRIAC
5~500A

ZNR

100~380VAC

Load

Note 1: According to the voltage and current of load, choose suitable varistor to protect the thyristor. A
resistor-capacitor circuit (RC circuit) is needed for inductance load or phase-shift trigger output.
Note 2: SCR power module is recommended. A power module includes two SCRs, is similar to the above dashed
square.
Note 3: K5 and K6 TRAIC trigger module only support 220380VAC and 50Hz power.
15

2. DISPLAYS AND OPERATIONS


2.1 Front Panel Description
Upper display window: Displays PV, parameter code, etc.
PV
Lower display window: Displays SV, parameter value, or
alarm message

Setup key: For accessing parameter table and conforming


parameter modification.
Data shift key, start auto tuning
SV

Data decrease key, and also run switch


Data increase key, and also stop key
MAN RUN MIO COM OP1 OP2 AL1 AL2 AU1 AU2
LED indicator: MAN led is non-applicable for AI-518 series.

RUN led on, it mean AI-518P running program. MIO, OP1,


OP2, AL1, AL2, AU1 and AU2 indicate I/O operation of the

corresponding module. For example, when COMM led is


RUN/HOLD
STOP
A/M
lighting means that the instrument is communicating with

AI A
computer.
Basic display status : When power on, the upper display
window of the instrument shows the process value (PV), and the lower window shows the set point (SV). This status
16

is called basic display status. Symbol description was shown as following table:
Symbol

orAL

HIAL
LoAL
HdAL
LdAL
EErr
8888

Description
Input specification setting is incorrect
Or
Input wiring is disconnected/ thermocouple problem
Or
Short circuited
High limit alarm
Low limit alarm
Deviation high alarm
Deviation low alarm
IC Software error
IC Software error

Note 1: The alarm message can turn off by setting parameter AdIS to oFF.
Note 2: When occur orAL alarm, instrument will cut the output in short period.
Note 3: For AI-518P, StoP,HoLd and rdy which mean the status in stop, hold and ready.

17

2.2

Parameter Setting Flow Chart

18

2.3 Operation Description


2.3.1 Parameter Setting
In basic display status, press

and hold for about 2 seconds can access Field Parameter Table. Pressing

can go to the next parameter; pressing

or

can modify a parameter.

Press and hold

(don't release) and then press


key simultaneously can
can return to the preceding parameter. Press
escape from the parameter table. The instrument will escape auomatically from the parameter table if no key is
pressed within 25 seconds, and the change of the last parameter will not be saved.
till the last field parameter Loc appears. Setting Loc=808 and then press
In Field Parameter Table,
can access System Parameter Table.

2.3.2 Set Value Setting


In basal display status, if the parameter lock Loc isn't locked, we can set setpoint (SV) by pressing
first
then can press
,
or
to adjust value. Press
key to decrease the value,
key to increase
key to move to the digit expected to modify. Keep pressing
or
, the speed of
the value, and
19

decreasing or inscreasing value get quick.


default range is 0~400.

The range of setpoint is between the parameter SPL and SPH. The

Program segment setting:


Press the
key once and release in the display status, the instrument will be in the setup program status.
The set point of the current program StEP will be displayed.

or
can modify the value.
Pressing
can go to next parameter. The program parameters will be displayed in the sequence of
Pressing
setpoint1, time1, setpoint2, time2.
Pressing and holding
for about 2 seconds will return to the previous parameter. Program step can modify
anytime even the program still in running.
Run / Hold
In basic display status, if the program is in stoP status (StoP is alternately displayed on the lower window),
press and hold the
key for about 2 seconds until the lower display window displays the "Run" symbol, the
instrument then will start the program.
Hold status only can activate by parameter setting (Srun), once hold function selected, lower display window
displays the "HoLd" symbol, and the instrument changes to hold status.
At Hold status, the program is still executing, and the process value is controlled same as setpoint, but the timer
20

stop working, and the running time and setpoint remains. At Hold status, press and hold the
key for about 2
seconds until the lower display window displays the "Run" symbol, the instrument will back to run program
Stop
key for about 2 seconds in the basic display status, until the lower display window
Press and hold the
displays the "stoP" symbol, means the stoP operation is executed now, when program stopped, timer will be
reset and stop. This operation forces the instrument to stop running, meanwhile, the StEP number will reset to 1,
and control output is also stopped

2.3.3 Auto Tuning


When AI control method is chosen (CtrL=APId / nPId), the PID parameters can be obtained by running
auto-tuning.
In basal display status, press
for 2 seconds, the At parameter will appear. Press
to change the
value of At from oFF to on, then press
to active the auto-tuning process. During auto tuning, the
instrument executes on-off control. After 2-3 times of on-off action, the instrument will obtain the optimal control
parameter value.
21

key for about 2 seconds until the "At"


If you want to escape from auto tuning status, press and hold the
parameter appear again. Change At from on to oFF, press
to confirm, then the auto tuning
process will be cancelled. (P.S. If parameter SPr activate and the heating was running, then will stop the At
until completed the heat up process. ) If the controller was applied on heat/cooling duel output system, PID
parameter need separate two group to process auto tuning. When the controller was cooling control from AUX,
this time can enable auto tuning to obtain P2, I2, d2.
Note 1: At AI-518P, when auto tuning was running, the program timer will stop until tuning finish.
Note 2: If the setpoint is different, the parameters obtained from auto-tuning are possible different. So youd better
set setpoint to an often-used value or middle value first, and then start auto-tuning. For the ovens with good
heat preservation, the setpoint can be set at the highest applicable temperature. Depending on the system,
the auto-tuning time can be from several seconds to several hours.
Note 3: Parameter CHYS (on-off differential, control hysteresis) has influence on the accuracy of auto-tuning.
Generally, smaller value of CHYS, will get higher precision of auto tuning result. Too large value of CHYS,
will made the controller out of control, so, CHYS is recommended to be 2.0.
Note 4: AI series instrument has the function of self-adaptation. It is able to learn the process while working.
he control effect at the first run after auto tuning is probably not perfect, but excellent control result
will be obtained after a period of time because of self-adaptation.
22

3. PARAMETERS AND SETTINGS


3.1

Parameter Lock (Loc) and Field Parameters

Parameter was protected by LOC (Parameter LOCK) to prevent setting error. The function was shown as below:
: allow to modify data or execute
X : not allow to modify data or execute
Run, Stop, Hold. and Program Time & Temp. function just for AI-518P only
Primary
Secondary Can changing status to Run,
Loc
SV
AT
Program Step Time & Temp.
Parameter
Parameter Stop
0

X
X

2
X
X

X
3
X
X

X
X
X
4~255
X
X
X
X
X
X
808

Loc 808 is the master password, this valve can be change by parameter PASd. Please set PASd cautiously, if the password lost,
you cant access the parameter table again.
1 to 8 field parameters can be defined by parameters EP1 to EP8. If the number of the field parameters is less than 8, the first idle
EP parameter should be set to nonE. The initial values of EPs and Loc are EP1=HIAL, EP2=LoAL, EP3=HdAL, EP4=LdAL,
EP5=nonE, EP6=nonE, EP7=nonE, EP8=nonE and Loc=0.
You can redefine field parameters and Loc to change operation style. For example, you can execute auto tuning from field parameter
in basic display status, and only take HIAL and HdAL as field parameter.
instead of by pressing
The EP paramters and Loc should be set as follows: EP1=HIAL, EP2=HdAL, EP3=At, EP4=nonE, Loc=1

23

3.2 The Parameter Table


The parameters can be divided to 8 groups including alarm, control, input, output, communication,
system, setpoint and field parameter definition. They are listed as below in sequence:
Setting
Code
Name
Description
Range
Alarm on when PV>HIAL
Alarm off when PV<HIAL-AHYS,
HIAL
High limit alarm
When the value set to Max. will disable this function
Alarm output action can be defined by parameter AOP.
Alarm on when PV<LoAL;
LoAL
Low limit alarm Alarm off when PV>LoAL+AHYS
-9990
When the value set to Min. will disable this function
+30000
Alarm on when PV-SV>HdAL;
Deviation high
units
HdAL
Alarm off when PV-SV<HdAL-AHYS
alarm
When the value set to Max. will disable this function
Alarm on when PV-SV<LdAL; Alarm off when PV-SV>LdAL+AHYS
Deviation low
When the value set to Min. will disable this function HdAL and LdAL can also be used
LdAL
alarm
as high limit and low limit alarms when needed. (Refer to the description of
parameter AF)
24

AHYS

Alarm
hysteresis

AdIS

Alarm display

Avoid frequent alarm on-off action because of the fluctuation of PV

02000
units

oFF : Will not display alarm message in the lower display window when alarming;
on : Alternately display alarm message in the lower display window when alarming.

oFF / on

25

AOP

Alarm output
allocation

Alarm
LdAL
HdAL
LoAL
HIAL
Output to
(x 1000)
(x100)
(x10)
(x1)
0
0
0
0
None
1
1
1
1
AL1
2
2
2
2
AL2
3
3
3
3
AU1
4
4
4
4
AU2
Example:
AOP =
3
3
0
1
LdAL
HdAL
LoAL
HIAL
It shows that HdAL and LdAL are sent to AU1, LoAL has no output, HIAL is sent to
AL1.
Note 1: When AUX is used as auxiliary output in bidirectional (heating/refrigerating)
control, alarm to AU1 and Au2 wont work.
Note 2: Installing L5 dual relay output module in ALM or AUX can implement AL2 or
AU2 alarm.

26

04444

CtrL

Srun

Control mode

onoF: on-off control. For situation not requiring high precision


APId: advanced artificial intelligence PID control. (Recommended)
nPId: standard PID algorithm with anti integral-saturation function (no integral when
PV-SV > proportional band)
POP: Transmit PV. The instrument works as a temperature re-transmitter.
SOP: Transmit SV. The instrument works program generator.

onoF
APId
nPId
POP
SOP

Running Status

run: Control or program was running, RUN led light on


StoP : Control or program was stopped. Lower display keep flashing StoP and
RUN led light off.
HoLd: This only functioned on AI-518P, this will keeping temperature when this HoLd
was appeared. If the parameter Pno=0(Non timing limitation mode), controller will
functioning same at AI-518, if Pno>0 (in program mode),and Srun was set as HoLd,
means the timer stops and the temperature remains; user can resume the timer by
pressing the Hold from panel.

StoP /
run /
HoLd

27

Act

Acting method

At

Auto tuning

Proportional
band

rE: Reverse acting. Increase in measured variable causes a decrease in the output,
such as heating control.
dr: Direct acting. Increase in measured variable causes an increase in the output,
such as refrigerating control.
rEbA: Reverse acting with low limit alarm and deviation low alarm blocking at the
beginning of power on.
drbA: Direct acting with high limit alarm and deviation high alarm blocking at the
beginning of power on.
oFF: Auto tuning function was off.
on: Active auto turning function to calculate the values
FoFF : Auto tuning function was off, cannot activate again by pressing key from
panel .
Proportional band in PID and APID control.
Instead of percentage of the
measurement range, the unit is the same as PV.
Generally, optimal P, I, D and CtI can obtained by auto tuning. They can also be
manually inputted if you already know the correct values.

28

rE
dr
rEbA
drbA

oFF / On /
FoFF

1~32000
units

Time of Integral

Time of
Derivative

CtI

Control period

No integral effect when I=0

09999
seconds

No derivative effect when d=0

0999.9
seconds

Small value can improve control accuracy.


For SSR, thyristor or linear current output, it is generally 0.5 to 3 seconds.
For Relay output or in a heating/refrigerating dual output control system, generally 15
to 40 seconds, because small value will cause the frequent on-off action of
mechanical switch or frequent heating/refrigerating switch, and shorten its service life.
CtI is recommended to be 1/5 1/10 of derivative time. (It should be integer times of
0.5 second.)
When the parameter OPt or Aut = rELy, CtI will be limited to more than 3 seconds.
Auto tuning will automatically set CtI to suitable value considering both control
precision and mechanical switch longevity.
When the parameter CtrL = onoF, CtI will used as timer to make delay time to avoid
the power restart in short period. It suit for compressor protection.
29

0.2
300.0
Sec

nd

P2

2
Proportional
band
nd

I2
d2
CtI2

CHYS

Time of
Integral
nd
2 Time of
Derivative

nd
The 2 proportional band in PID and APID control. Instead of percentage of the
measurement range, the unit is the same as PV.
Generally, optimal P, I, D and CtI can obtained by auto tuning. They can also be
manually inputted if you already know the correct values.

No integral effect when I=0


No derivative effect when d=0

2nd Control
period

Same description and function as parameter as Ctl

Control
Hysteresis

CHYS is used for on-off control to avoid frequent on-off action of relay.
For a reverse acting (heating) system, when PV > SV, output turns off; when
PV<SV-CHYS, output turns on.
For a direct acting (cooling) system, when PV<SV, output turns off; when
PV>SV+CHYS, output turns on.

30

1~32000
units
09999
seconds
0999.9
seconds
0.2
300.0
Sec

02000

InP

Input
specification
Code

InP
0
1
2
3
4
5
6
7
8
9
10
12
15

Input spec.
K
S
R
T
E
J
B*
N
WRe3-WRe25
WRe3-Wre26
Extended
input
specification
F2 radiation type pyromter
4 20mA (installed I4
module in MIO)

31

InP
20
21
22
25
26
27
28
29
30
31

Input spec.
Cu50
Pt100
Pt100 (-80+300.00) *
0~75mV voltage input
080ohm resistor input
0400ohm resistor input
020mV voltage input
0100mV voltage input
060mV voltage input
0500mV voltage input

32

100500mV voltage input

33

15V voltage input

34

05V voltage input

037

dPt
ScL
ScH

Scb

Display
Resolution
Signal scale
low limit
Signal scale
high limit
Input Shift
Adjustment

16

0 20mA (installed I4
module in MIO)

35

010V

17

K (0300.00) *

36

210V

18

J (0300.00) *

37

020V

Four formats (0, 0.0, 0.00, 0.000) are selectable


Note 1: For thermocouples or RTD input, only 0 or 0.0 is selectable, and the internal
resolution is 0.1. When S type thermocouple is used, dPt is recommended to be 0. If
Inp= 17,18 or 22, resolution will support display 0.0 or 0.00
Define scale low limit of input. It is also the low limit of transmitter output (CtrL=POP
or SOP) and light bar display.
Define scale high limit of input. It is also the high limit of retransmission output
(CtrL=POP or SOP) and light bar display.
Scb is used to shift input to compensate the error caused by transducer, input signal,
or auto cold junction compensation of thermocouple.
PV after compensation=PV before compensation + Scb
It is generally set to 0. The incorrect setting will cause measurement mistake.
32

0 / 0.0 /
0.00 /
0.000
-9990
+32000
units
-1999
+4000
units

FILt

PV input filter

Fru

Selection of
power
frequency and
temperature
scale

OPt

Main output
type

The value of FILt will determine the ability of filtering noise.


When a large value is set, the measurement input is stabilized but the response
speed is slow. Generally, it can be set to 1 to 3.
If great interference exists, then you can increase parameter FILt gradually to make
momentary fluctuation of measured value less than 2 to 5.
When the instrument is being metrological verified, FILt s can be set to 0 or 1 to
shorten the response time.

040

50C: 50Hz,display . , 50F: 50Hz, display


60C: 60Hz,display . , 60F: 60Hz, display .
Input has max. anti-interference ability to 50Hz or 60Hz frequency when parameter
set;
SSr: Output SSr drive voltage or thyristor zero crossing trigger signal. G, K1 or K3
module should be installed. The output power can be adjusted by the on-off time
proportion. The period (CtI) is generally 0.54 seconds.
rELy: for relay contact output or for execution system with mechanical contact switch.
To protect the mechanical switch, the output period (CtI) is limited to 3120 seconds,
and generally is 1/5 to 1/10 of derivative time.
0-20: 020mA linear current output. X3 or X5 module should be installed in OUTP
33

50C, 50F,
60C, 60F

SSr
rELy
0-20
4-20
PHA

slot.
4-20: 420mA linear current output. X3 or X5 module should be installed in OUTP
slot.
PHA: Single-phase phase-shift output. K5 module should be installed in OUTP slot.
PHA is only for 50Hz power supply, and dont support bidirectional control system.

34

Aut

OPL

Auxiliary output
type

Define AUX only when AUX is worked as the auxiliary output of a heating/refrigerating
bidirectional systerm.
SSr: to output SSr driver voltage or thyristor zero crossing trigger signal. G, K1 or K3
module should be installed. The output power can be adjusted by adjusting the
on-off time proportion. The period (CtI) is generally 0.54 seconds.
rELy: for relay contact output or for execution system with mechanical contact switch.
To protect the mechanical switch, the output period (CtI) is limited to 3120 seconds,
and generally is 1/5 to 1/10 of derivative time.
0-20: 020mA linear current output. X3 or X5 module should be installed in AUX
slot.
4-20: 420mA linear current output. X3 or X5 module should be installed in AUX
slot.
Note: In a heating/refrigerating bidirectional control system, if any of OPt or Aut is set
to rELy, then CtI is limited to 3120.

SSr
rELy
0-20
4-20

Output low limit

0100%: OPL is the minimum output of OUTP in single directional control system.
-1-110%: The instrument works for a bidirectional system, and has
heating/refrigerating dual output. When ACt=rE or rEbA, OUTP (main output) works
for heating, and AUX (Auxiliary output) works for refrigerating. When Act=dr or drbA,

-110
+110%

35

OUTP works for refrigerating, and AUX works for heating.


In a bidirectional system, OPL for define the limitation of maximum cooling output. So,
when the OPL= -100%, means no limitation on cooling output. If set OPL=-110%, it
can made current output excess 10% on maximum output. When the output type is
SSR output or relay output, maximum of cooling output should not set more than
100%
OPH

Output upper
limit

OPL limits the maximum of OUTP (main output) when PV<OEF. OPH should be
greater than OPL.

0110%

OEF

Work range of
OPH

When PV<OEF, the upper limit of OUTP is OPH; when PV>OEF, the upper limit of
OUTP is 100%.
For example, to avoid that the temperature raises too quickly, under 150, a heater
can work only under 30% of power, then we can set OEF=150.0 (), OPH=30 (%)

-999
+3200

Addr

Communication
address

bAud

Baud rate

In the same communication line, different instrument should be set to different


address.
The range of baud rate is 120019200bit/s. When COMM/AUX slot is used as AUX,
bAud should be set to 0.
36

080
019.2K

Et

Event input
type

If set parameter bAud = 2, it can be used for AU1 or AL1 alarm output.
For D4 dimension instrument, if I2 is installed and bAud = 1, then it can input on-off
signal to switch SV1 and SV2 (AI-518) or switching the program status RUN/Stop
(AI-518P) by connecting a switch between terminals number 3 and 5.
When I2 module was installed, the meter have following functions,
nonE : Disable event input function
reSt : Run / Stop switching function. Connected in short time, start to running
program, keep connect more than 2 sec, program switch to stop.
SP1.2 : Switching between setpoint 1 and setpoint 2 when use AI-518 or Pno=0 at
AI-518P. MIO in open status, SV=SP1, when MIO in close status, SV=SP2
st
nd
PId2 : Switching 1 PID and 2 PID. When use as single direction control, MIO in
open status, P, I, d and Ctl was active, when MIO in close status, P2, I2, d2 and Ctl2
was active

37

nonE /
rest /
SP1.2 /
PId2

AF is used to select advanced function. The value of AF is calculated as below:


AF=Ax1 + Bx2 + Cx4 + Dx8 + Ex16 + Fx32 + Gx64

AF

Advanced
function

A=0, HdAL and LdAL work as deviation high and low limit alarms;
A=1, HdAL and LdAL work as high and low limit alarms, and the instrument can have
two groups of high and low limit alarms.
B=0, Alarm and control hysteresis work as unilateral hysteresis;
B=1, As bilateral hysteresis.
C=0, The light bar indicates the output value;
C=1, The light bar indicates the process value (for instruments with light bar only).
D=0, Loc=808 can access the whole parameter table;
D=1, Loc=PASd can access the parameter table.
E=0, Normal application on HIAL and LoAL;
E=1, HIAL AND LoAL will become to deviation high alarm and Deviation low alarm
F=0, Fine control mode, internal control resolution was demonstrations 10 times.
When on linear input mode, biggest display value is 3200 units
F=1, Wide range display mode, when the value is bigger than 3200 ,chooses this
option
38

0255

G=0, When the thermocouple or RTD input is burnt out, PV value will increase and
trigger the high limit alarm.
G=1, When the thermocouple or RTD input is burnt out, PV value will increase and
NOT trigger the high limit alarm. After it was sets, High Limit alarm will have 30 sec.
delay for trigger in normal usage.
Note: AF=0 is recommended.

PASd

Password

SPL

SP1

Low limit of SV
Upper limit of
SV
Setpoint 1

SP2

Setpoint 2

SPH

When PASd=0255 or AF.D=0, set Loc=808 can enter the whole parameter table.
When PASd=256 9999 and AF.D=1, only Loc=PASd can access the whole
parameter table.
Please setting PASd cautiously, if the password is lost, you cant access the
parameter table again.
Minimum value that SV is allowed to be.
Maximum value that SV is allowed to be.
When Pno=0 or 1, then SV=SP1
When I2 module installed in MIO slot, SP1 and SP2 can be switched by an external
switch. If the switch is off, SV=SP1; if the switch is on, SV=SP2.
39

09999

-999
+3000
unit
SPL
SPH

SPr

Ramp Slope
limit (Only for
AI-518P)

Pno

No. of Program
step (Only for
AI-518P)

PonP

Program run
mode after
power restart
(Only for
AI-518P)

Once SPr was set, if PV<SV when program start, the first step of ramp slope will
limited by SPr value until the temperature reach the first SV , under this limitation, the
RUN lamp will keep flashing.
For Ramp mode. SPr had effect on first step only.
For Soak mode, SPr had effect on each step.
To define the number of program in use.
Pno= 0, disable the program running mode, then AI-518P will same as AI-518,
meanwhile, can set the parameter SPr to limit the ramp time.
Pno=1~30, AI-518P working as normal programmable controller
Cont : Continue to run the program from the original break point. If STOP STATUS
was activated before power cut, then it (the program) will keep stop status after power
restart.
StoP : Stop the program after power restart
run1 : Start to run the program from step 1 unless the instrument was in stop state
before power cut.
dASt : If these have deviation alarm after power resume, then stop the program,
otherwise, continue run the program from the original break point.
HoLd : Go into HOLD state after power on. If it is in StoP state before power cut, then
keep in StoP State after power on.
40

0~3200

/Min

0~30

Cont /
StoP /
run1 /
dASt /
HoLd

PAF

Program
Running mode
(Only for
AI-518P)

EP1
EP8

Field
parameter
definition

PAF = Ax1 + Bx2 + Cx4 + Dx8


When
A=0, Enable ready (rdy) function
A=1, Disenable ready (rdy) function
B=0, Ramp mode.
B=1, Soak mode,
C=0, Time unit in Minute, the range is 0.1~3200.
C=1, Time unit in Hour, the range is 0.1~3200
D=0, Disable PV start up function.
D=1, Enable PV start up function.
Please refer to Page XX for more detail of Ramp mode, Soak mode and PV start up
function.
Define 08 of the parameters as field parameters.

41

nonE and
all
parameter
codes

3.3 Additional Remarks of Special Functions


3.3.1 Single-phase phase-shift trigger output
When OPt is set to PHA, installing a K5 or K6 module in OUTP slot can single-phase phase-shift trigger a TRIAC or 2
inverse parallel SCRs. It can continuously adjust heating power by control the conduction angle of thyristor. With
non-linear power adjustment according to the characters of sine wave, it can get ideal control. The trigger adopts
self-synchronizing technology, so it can also work even when the power supplies of the instrument and the heater are
different. Phase-shift trigger has high interference to the electric power, so user should pay attention to the
anti-interference ability of other machines in the system. Now the K5 or K6 module can be only used in 50Hz power
supply.

3.3.2 Alarm blocking at the beginning of power on


Some unnecessary alarms often occur at the beginning of power on. In a heating system, at the beginning of power
on, its temperature is much lower than the setpoint. If low limit and deviation low limit are set and the alarm
conditions are satisfied, the instrument should alarm, but there is no problem in the system. Contrarily, in an
refrigerating system, the unnecessary high limit or deviation high limit alarm may occur at the beginning of power on.
Therefore, AI instruments offer the function of alarm blocking at the beginning of power on. When Act is set to rEbA
or drbA, the corresponding low or high alarms are blocked until the alarm condition first clears. If the alarm condition
is satisfied again, the alarm will work.
42

3.3.3 Setpoints switch


If an I2 module is installed in MIO slot (or bAud=1 and I2 installed in COMM slot). User can connect external on off
switch to realize some control function. Set Et = rest, can switching program run and stop. For AI-518, or AI518P when
its Pno=0, set Et = SP1.2, can switching between setpoint 1 and setpoint 2.

3.3.4 Communication function


S or S4 module can be installed at COMM slot to communicate with a computer. The instrument can be controlled
by computer. A RS232C/RS485 or USB/RS485 converter can enable a computer connect to AI instruments through
RS232 or USB communication port. Every communication port of a computer can connect up to 60 AI instruments,
or 80 AI instruments if a repeater is installed. A computer with 2 communication ports can connect to up to 160
instruments. Please note that every instrument connecting to the same communication line should be set to a unique
communication address. When number of the instruments is big enough, 2 or more computers can be used and built
into a local network.
AIDCS application software, a distributed control system software developed by Yudian, can control and manage 1
160 AI instruments, record the data, generate and print reports. If users want to develop their own distributed control
system by themselves, the communication protocol of AI instruments can be free offered. There are already many
famous distributed control system software support AI instruments.
43

3.3.5 Temperature re-transmitter / Program generator / Manual current output


Besides AI PID, stand PID control and on-off control, if the output is defined as current output, the instrument can also
retransmit PV (process value) or SV (setpoint) into linear current and output from OUTP. The precision of current
output is 0.2%FS. Base on that ability, AI-518 can become temperature re-transmitter and AI-518P can become
program generator
The corresponding parameters are set as below:
When CtrL=POP, PV is retransmitted to linear current, the instrument works as temperature re-transmitter.
When CtrL=SOP, SV is transmitted and outputted, and the instrument works as manual current output
controller(AI-518) or prodram generator(AI-518) .
OPt is used to choose output type, generally 420mA or 020mA output.
Parameter InP, SCL, SCH, and Scb are used for selecting input specification, setting low limit or high limit of PV and
adjusting input.
For example, in order to retransmit temperature read from K thermocouple, range 0400, to current 420mA, the
parameters are set as below: InP=0, ScL=0.0, ScH=400.0, OPt=4~20, and X3 or X5 linear current module is installed
in OUTP slot. When the temperature is less than or equal to 0, the output is 4mA. When the temperature equals
to 400, the output is 20mA.

44

4. Further description for the operation of AI-518P series instrument


AI-518P v8.0 program type temperature controller is used in the application where the setpoint should be changed
automatically with the time. It provides 30 segments program control which can be set in any slope and the function of
jump, run, hold and stop can also be set in the program. Measurement startup function, preparation function and
power-cut/power-resume event handling modes also provided.

4.1 Concepts and functions Program


StEP:
The No. of the program Step can be defined from 1 to 30, and the current Step is the program Step being executing.

StEP time:
Total run time of the program step. The unit is minute and the available value range from 1 to 9999.

Running time:
The Time of current Step has run. As the running time reaches the Step time, the program will jump to the next Step
automatically.
45

Jump:
The program can jump to any other steps in the range of 1 to 30 automatically as you programmed in the program
Step, and realize cycle control.

Run/Hold:
When program is in the running status, timer works, and set point value changes according to the preset curve. When
program is in the holding status, timer stops, and set point remains to make temperature hold also. The holding
operation can be programmed into the program step.

Stop:
When the stop operation is activated, the program will stop, running time will be clear, event output switch will reset
and the output control will stop output. If run operation is activated when instrument is in the stop status, the program
will start-up and run again from the set step no. The stop function can be programmed into the program Step. The stop
operation can also be performed manually at any time. (After stop operation is done, the step no. will be set to 1, but
user can modify it again). If the program ran the last step of Pno, program will stop automatically.

Power cut/resume event handling:


There are 5 events handling method selectable for power resume after power cut. Please refer to parameter PonP.

46

PV startup and PV preparation function (rdy function) :


At the beginning of starting a program, resuming a program after power cut or continuing to run a program after it is
just modified, the PV (process value) are often quite different from the set point. PV startup function and PV
preparation function can make PV and set point consistent, and avoid unexpected result. When PV startup function
enabled, the instrument will adjust the running time automatically to make the expected set point is the same as the
current PV.
For example, the program is set that the temperature will be raised form 25 to 625 in 600 minutes. But the current
PV is 100, then the instrument will automatically to run this program start from 75 minutes, that mean changed the
temperature raised from 100 to 625 in 525 minutes (600-75) min.
At the above situation(PV=100, SV=25, first step SV), when PV preparation function is enable, the alarm function will
be blocked at that time, and PV will be adjusted to approach SV until the deviation alarm condition is released (PV is
between SV-LdAL and SV+HdAL). After deviation alarm was off, the controller start the program again. Preparation
function (rdy Function) is helpful to keep the integrity of the program, but it will prolong the program time because the
start of the program is postponed.
PV startup function is prior to PV preparation function. If both function are enabled, the system apply PV startup first, if
PV startup function works, PV preparation function will not be activated.

Curve fitting:
Curve fitting is adopted as a kind of control technology for AI-518P series instrument. As controlled process often has
lag time in system response, by the way of curve fitting the instrument will smooth the turning point of the linear
47

heating-up, cooling-down and constant temperature curves automatically. The degree of the smooth is relevant with
the systems lag time t (t=d+CtI) ; the longer of the lag time, the curve will more smooth. On the opposite the smooth
function will be weaker. Generally the shorter of the process lag time (such as temperature inertia), the better of the
program control on effect. By the way of the curve fitting to deal with the program curves, will avoid overshoot. Note:
The characteristic of the curve fitting will force the program control to generate fixed negative deviation during the
linear heating-up and fixed positive deviation during the linear cooling-down, the deviation is direct proportional to the
lag time and the speed of heating-up (cooling-down). This phenomenon is normal.

5. Programming and operation

(For AI-518P only)

5.1 Ramp Mode(PAF : B=0)


Programming of instrument has uniform format of temperature-time-temperature, which means temperature A(SP 1),
passed Time A(t01), then reached Temperature B(SP 2). The unit of temperature set is and the unit of time set
is minute. The following example includes 5 steps, which is linear temperature heating up, constant temperature,
linear temperature cooling down, jump cycling, ready, Hold..
StEP1: SP 1=100 , t 1=30.0 Start linear temperature heating up from 100, and the time needed 30 minutes to reach
SP 2(400 degree).
48

StEP2: SP 2=400 , t 2=60.0 Temperature raised to 400, slope of raising curve is 10/minute, The program take 60
minutes to raise temperature to SP3 (400 degree). It means keep the same temperature in 60 minutes.
StEP3: SP 3=400 , t 3=120.0 This is the step for temperature cooling down, slope of cooling curve is 2/minute, and
the time needed is 120 minutes to reach SP4 (160degree).
StEP4: SP 4=160 , t 4=0.0 When temperature reached 160 degree, the program get in Hold state. If need go to next
step, it needed operator to executed the run for next step.
StEP5: SP 5=160 , t05=-1.0 Jump to StEP1 to start from beginning.
In this example, it is assumed that the deviation high alarm is set to 5. Because the temperature of StEP 5 is 160,
and the temperature of StEP1 is 100, when program jumps from StEP 5 to StEP 1, the program will change to
preparation state at first(if preparation mode rdy was enabled), i.e., Control the temperature until the deviation
between setpoint and PV is less than deviation high alarm value. After temperature is controlled to 105, the program
will be started from StEP 1, and run the above steps again. The temperature control drawing was shown below.

49

50

5.2 Soak mode(PAF : B=1)


Suitable for the process which does not need to establish the temperature slope, can simplify the programming and
more effective. Each step also can set parameter SPr to define temperature raise slope, if SPr=0 raising speed will
set to maximum. Because cannot know the actual time which spend on temperature raising, user can enable rdy
function to ensure the correct soak time.

Time setting
Set t-xx = 13200 (min)
Set the time of xx StEP. (Time units can be change to Hour by parameter PAF.)
Set t-xx = 0.0
The program hold on StEP xx, program will hold running and hold counting time.
Set t-xx = -121.0
The program stops, and switches to stop status.
Set t-xx = -0.1-122.0
Negative value of this range represents a jump operation which will jump to step xx and event output. Range -1~-120
is for step jumping application. The step jumping cannot greater than Pno(No. of Program step).
Decimal point use for control the event output from AL1 and AL2. (Modular), Note, if parameter AOP was assigned
alarm action will trigger from AL1 and AL2, the event output also will cause alarm from AL1 and AL2.
51

When set
-XXX.1, AL1 activate, AL2 release
-XXX.2, AL1 release, AL2 activate
-XXX.3, AL1 and AL2 activate
-XXX.4, AL1 and AL2 release
Example:
Example 1 : t -5 = -1.1 ; means when the program arrived step 5, AL1 activate, AL2 release and
will jump to step 1 continues running
Example 2 : t-6 = -0.3 ; means when the program arrived step 6, AL1 and AL2 activate and
continuous next step.
Note: The program will be held if it jump from a control segment to another control segment (an Hold action will be
inserted between two control sections), external run/Hold operation is needed to release the Hold status. It is not
allowed that the jump section jump to itself (for example: t 06= -6), otherwise, the Hold status cannot be released.

Program arrangement of multi-curve operation


AI-518P has the advanced function of flexible program arrangement. Normally, when the program stops, the StEP will
be automatically set to1. Thus if StEP is not change to other value, a program will start from step1. If multiple curves
are defined, the control can jump to different curve by setting step 1 as jump segment.
For example: There are three curves with the length of 3 steps represent three groups of process parameter, they are
52

separately arranged on StEP2-StEP4, StEP5-StEP7, StEP8-StEP10. Settings are as follows:


t- 1=-2.0 Execute the program of curve 1 (StEP2-StEP4)
t- 1=-5.0 Execute the program of curve 2 (StEP5-StEP7)
t- 1=-8.0 Execute the program of curve 3 (StEP8-StEP10)
Note: Can choose the curves by setting the value of StEP t-1 set to -2.0, -5.0 or -8.0 before the program startup.