AI-518/AI-518P Artificial Intelligence Industrial Controller
AI-518/AI-518P Artificial Intelligence Industrial Controller
AI-518/AI-518P Artificial Intelligence Industrial Controller
AI-518/AI-518P
ARTIFICIAL INTELLIGENCE INDUSTRIAL CONTROLLER
Operation Instruction
Ver. 8.0
CONTENTS
1.
SUMMARY .............................................................................................................................................................. 1
1.1
MAIN FEATURES
1.2
1.3
MODULES
1.4
1.5
2.
1.3.1
Slots of modules
1.3.2
Commonly used modules:
1.3.3
Installation and replacement of modules
1.3.4
Electric isolation of the modules
1.3.5
Further descriptions about module applications
TECHNICAL SPECIFICATION
REAR TERMINAL LAYOUT AND WIRING
4
6
7
7
8
9
12
3.
2.1
16
2.2
18
2.3
OPERATION DESCRIPTION
19
2.3.1
2.3.2
2.3.3
19
19
21
Parameter Setting
Set Value Setting
Auto Tuning
23
3.2
24
3.3
42
3.3.1
3.3.2
3.3.3
42
42
43
3.3.4
3.3.5
Communication function
Temperature re-transmitter / Program generator / Manual current output
43
44
StEP:
StEP time:
Running time:
Jump:
Run/Hold:
Stop:
Power cut/resume event handling:
PV startup and PV preparation function (rdy function) :
Curve fitting:
45
45
45
45
46
46
46
46
47
47
48
51
Time setting
Program arrangement of multi-curve operation
51
52
1. SUMMARY
1.1 Main Features
z
z
z
z
z
z
Adopt digital calibration technology for input measurement with input measurement accuracy 0.3% F.S., Support
standard thermocouples and RTDs, maximum resolution is 0.01
Adopt advanced artificial intelligence control algorithm, no overshoot and with the function of auto tuning (AT)
and self-adaptation.
Adopt advanced modular structure, conveniently providing plentiful output options, able to satisfy the
requirements of various applications, make quick delivery and convenience the maintenance of the instrument.
Friendly and customized operating interface leads to easy learning and simple operation. Parameter can be
promoted to immediate operator access in Field Parameter Table or password protected in Full Parameter
Table.
With worldwide power supply of 100-240VAC or 24VDC and various installation dimensions for users to choose.
ISO9001 and CE certified, achieving world class level of quality, anti-interference ability and safety.
POINTS FOR ATTENTION
This manual introduces AI-518/AI-518P ARTIFICIAL INTELLIGENCE INDUSTRIAL CONTROLLER of
Version 8.0. Certain functions introduced by this manual are probably not applicable for the instrument of
other version. When power on, instruments model and software version will be displayed. User should
1
pay attention to the difference between different versions when using the instrument. Please read this
manual carefully in or der to use the instrument correctl y and make it to its full use.
Please correctly set parameters according to input / output type and function. Only correctly wired
instruments with parameters correctly set can be put into use.
X3
L5
S4
24VDC (F2)
It shows that the model of this instrument is AI-518, front panel dimension is 9696mm, no module is installed in MIO
slot, X3 linear current output module is installed in OUTP (main output), ALM (alarm) is L5 (dual relay contact output
module), no module is installed in AUX (auxiliary output), S4 (RS485 communication interface module) was installed
at COMM , and the power supply of the instrument is 24VDC, an extended input type (F2 radiation type pyrometer) is
available
The following is the meanings of the 9 parts:
Shows the model of the instrument
2
AI-518 : Economical type instrument with measurement accuracy 0.3%F.S. It adopts artificial intelligent control
technology, and has the functions of control, alarm, retransmission and communication.
AI-518P: Base on AI-518 added 30 segments programmable functions.
Shows the module type of auxiliary output (AUX). Selectable modules are L1, L2, L4, L5, W1, W2, G, K1, X3
X5, etc.
Shows the module type of communication (COMM). Selectable modules are S, S4, V, etc.
Shows the power supply of the instrument. If left blank, the power of the instrument is 100~240VAC. Added
"24VDC" means the power supply of 20~32V DC or AC power
Shows the optional extended graduation spec (If none, leave it blank). AI-518 series instruments support many
input types including popular thermocouples, RTDs, linear voltage, current and resistance inputs. If needed, an
additional specification not mentioned in input type selection (InP) table can be extended.
Note 1: The instrument applies the technology of automatic zero and digital calibration, and is free of maintenance.
If the error exceeds certain range, generally, cleaning and drying the inside of the instrument can fix it. If not, send the
instrument back to the factory to examine and repair.
1.3 Modules
1.3.1 Slots of modules
AI-518/518P series instruments have five slots for modules to be installed (D dimension instruments have 3
slots: OUTP, AUX and COMM/AL1; D4 dimension instruments have 2 slots: OUTP and COMM/AUX). By
4
z
z
installing different modules, the controller can meet the requirements of different functions and output types.
Multiple function Input / Output (MIO):
Can input signal from 2-wire transmitter or 4-20mA signal by installing I4 (current input) module and I4 module
can provide VDC to transmitter. If a I2 (on-off signal input) module is installed, the instrument can switch between
set points SV1 and SV2 by an external switch. Cooperating with OUTP and installing a K3 module can realize
three-phase thyristor zero cross triggering output.
Main output (OUTP):
Commonly used as control output such as on-off control, standard PID control, and AI PID control. It can be
used as retransmission output of process value (PV) or set point (SV). Installing L1 or L4 modular can realize
relay contact output; installing X3 or X5 module can realize 0-20mA/4-20mA/0-10mA linear current output;
installing G module can realize SSR voltage output; installing W1 or W2 module can implement TRIAC no
contact switch output.
Alarm (ALM):
Commonly used as alarm output. Support 1 normally open + normally close relay output (AL1) by installing L1 or
L2 module or 2 normally open relay outputs (AL1+AL2) by installing L5 module.
Auxiliary output (AUX): In a heating/refrigerating dual output system, module X3, X5, L1, L4, G, W1, W2 can be
installed for the second control output. It can also output alarm by installing L1, L2 or L5 module, or be used for
communicating with computer by installing R module (RS232C interface).
Communication Interface (COMM): Module S or S4 can be installed in for communicating with computer
(RS485 communication interface), and it can also be used as power supply for external sensor when equipped
5
S/S4
R
I2
RS485 communication interface module. S4 is equipped with photoelectric isolated power supply.
RS232 communication interface module.
Switch / frequency signal input interface for inputting external switch or frequency signal, has a 12VDC
power supply for external transducer.
I4
4-20mA/0-20mA analogue input interface, has a 24VDC/24mA power supply for a transmitter.
V24/V12/V10/V5
Isolated 24V/12V/10V/5V DC voltage output with maximum current of 50mA, can supply power for transmitter.
voltage output do not need to be insulated from input circuit, because SSR itself has isolation function. Therefore,
only the electric isolation between the communication interface and the current output should be considered. Those
modules, for example, S (RS485 communication interface), R (RS232 communication interface) and X3 (linear current
output), all need the 12V power supply. If more than one of the above modules are installed, in order to be electric
isolated, only one of them can be module without electric isolation, the other modules should be S4 or X5, which has
its own isolated power supply. For example, if an X3 module is installed in OUTP (main output) slot, for isolate
purpose, COMM slot should be install S4 or X5.
Voltage output module: The voltage output modules like V24, V12, \/10 or V5 are often used for supplying
power for external transducer or feedback resistance of transmitter. These modules can be installed in any slot.
To standardize the wiring, it is recommended to be installed in the first idle slot in the order of MIO, AUX, and
COMM.
No contact switch module: W1 and W2 are new types of no contact switch module which apply the advanced
technology of burn proof and zero crossing conduction. It can replace the relay contact switch. Compared to
the relay contact output module, W1 and W2 have longer life and lower interference. They can largely lower the
interference spark of the equipment, and greatly improve the stability and reliability of the system. Protection
elements are series wound to the output terminals, so it can control continuous current up to 0.2A with maximum
allowed instantaneous current 2A. Since the driver element is TRIAC, it is suitable for controlling 100-240VAC
(not for DC power) with contactor which current below 80A. For the current larger than 80A, an intermediate
8
relay is needed.
Relay switch module: The relay modules are widely used in industrial control. However, they are the only
modules with life time limit and volume limit and have much electromagnetic interference. It is important to
choose a suitable relay module. To control equipments with 100~220VAC supply, such as contactor and
electromagnetic valve, W1 module is recommended. To control DC or AC above 50VAC, users can only use
relay module. L2 module is small, and both its normal open and normal close terminals have the function of
spark absorption, but the capacity is small. It is suitable for alarm output. L1 and L5 have bigger volume and
capacity. In the 48mm dimension instrument (for example, D4, E, F and E5), only one of L1or L5 can be installed.
L5 has dual output, can be used to support two loops of alarm, for example, AL1+AL2. If you dont like
mechanical switch, you can choose G5 (dual SSR voltage driver) and connect with external SSR instead.
Input type: (Either of below specifications can be used selectively in the one instrument)
Thermocouple: K, S, R, E, J, N, T, B, WRe3-WRe25, WRe5-WRe26.
Resistance temperature detector: Cu50, Pt100
Linear voltage: 05V, 15V, 01V, 0100mV, 020mV, 0~500mV etc.
Linear current (external precise shunt resist needed): 010mA,020mA, 420mA, etc.
Extended input (install I4 module in MIO) : 020mA, 420mA or two line transmitter.
Optional: apart from the above-mentioned Input type, an additional type can be provided upon request.
9
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
z
11
C O M C OM
100-240VAC ~
2
3
A
B
OP2
OP1
N/C
N /O
N/O
N/O
OUT P
G1
Thyristor trigger output K1/K 3
12
G2
13
G1
T hyristor trigger output K3
14
G2
CO M +
CO MM
Wiring graph of instruments
+ N /C
5
15
G1
N/O
N/O
A
L1
Note 1: For linear voltage input, if the range is below
+
Thyristor trigger outuput K3
+ N /O V+
G2
6 + N /C N/O A L2
16
500mV, connect to terminals 19 and 18. 05V or 15V
T he graph suits for upright instrum ents
M2 /MIO
w ith dim ension A or E
COM CO M
signal can be inputted from terminals 17 and 18.
0-5V
17
7
1-5V
+
AL M
Note 2: 420mA linear current signal can change to 1
18
8
5V voltage signal by connecting a 250 ohm resistor, and
+ N /O N/O AU 1
F or instrum ents w ith dim ension F or B,
then be inputted from terminals 17 and 18. If I4 module
19
just clockw ise rotate the graph 90
9 + N /C N /O A U 2
+
degree, and the num bers of the
term inals keep the sam e.
is installed in MIO slot, 420mA signal can be inputted
CO M C O M
10
20
AUX
from terminals 14+ and 15-, and 2-wire transmitter can be
inputted from terminals 16+ and 14-.
Note 3: The compensation wires for different kinds of thermocouple are different, and should be directly connect to
the terminals. When the internal auto compensation mode is used, connecting the common wire between the
compensation wire and the terminals will cause measurement error.
Note 4: When main output selected linear current or SSR voltage, output form terminal 13+, 11-,
12
COM COM
100-240VAC~
2
3
4
5
6
7
OP2
N/C N/O
OP1
N/O N/O
N/O
B COM
COMM/AL1
+
+
N/O AU2
COM COM
AUX
OUTP
G1
9
10
11
0-5V
+ 1-5V
12
13
14
support 05V or 15V linear voltage input. However, 05V or 15V signal can be converted to 0500mV or
100500mV by connecting external precise resistors, 420mA can be converted to 100500mV by connecting a
25ohm resistor, then be inputted from terminals 9 and 8.
Note 2: For COMM/AUX slot, if S or S4 communication module is installed, it can be used for communication; if L2
module is installed in, parameter set bAud = 0, it can be used for AU1 or AU2 alarm output; if set parameter bAud = 2,
it can be used for AU1 or AL1 alarm output. If L1, L2, L4, G, K1, W1 or W2 is installed, it can be the auxiliary output in
bidirectional (heating/refrigerating) control (Auxiliary output doesnt support analog current output); if I2 is installed and
bAud = 1, then it can input on-off signal to switch SV1 and SV2 (AI-518) or switching the program status RUN / Stop
(AI-518P) by connecting a switch between terminals number 3 and 5.
14
SCR
Power Module
1N4001
Capacitor Resistor
Varistor
Absorber Circuit
BX
G1
SCR X2
5~500A
ZNR
100~380VAC
Load
IN4001
Capacitor Resistor
Varistor
Absorber Circuit
BX
G1
G2
TRIAC
5~500A
ZNR
100~380VAC
Load
Note 1: According to the voltage and current of load, choose suitable varistor to protect the thyristor. A
resistor-capacitor circuit (RC circuit) is needed for inductance load or phase-shift trigger output.
Note 2: SCR power module is recommended. A power module includes two SCRs, is similar to the above dashed
square.
Note 3: K5 and K6 TRAIC trigger module only support 220380VAC and 50Hz power.
15
AI A
computer.
Basic display status : When power on, the upper display
window of the instrument shows the process value (PV), and the lower window shows the set point (SV). This status
16
is called basic display status. Symbol description was shown as following table:
Symbol
orAL
HIAL
LoAL
HdAL
LdAL
EErr
8888
Description
Input specification setting is incorrect
Or
Input wiring is disconnected/ thermocouple problem
Or
Short circuited
High limit alarm
Low limit alarm
Deviation high alarm
Deviation low alarm
IC Software error
IC Software error
Note 1: The alarm message can turn off by setting parameter AdIS to oFF.
Note 2: When occur orAL alarm, instrument will cut the output in short period.
Note 3: For AI-518P, StoP,HoLd and rdy which mean the status in stop, hold and ready.
17
2.2
18
and hold for about 2 seconds can access Field Parameter Table. Pressing
or
The range of setpoint is between the parameter SPL and SPH. The
or
can modify the value.
Pressing
can go to next parameter. The program parameters will be displayed in the sequence of
Pressing
setpoint1, time1, setpoint2, time2.
Pressing and holding
for about 2 seconds will return to the previous parameter. Program step can modify
anytime even the program still in running.
Run / Hold
In basic display status, if the program is in stoP status (StoP is alternately displayed on the lower window),
press and hold the
key for about 2 seconds until the lower display window displays the "Run" symbol, the
instrument then will start the program.
Hold status only can activate by parameter setting (Srun), once hold function selected, lower display window
displays the "HoLd" symbol, and the instrument changes to hold status.
At Hold status, the program is still executing, and the process value is controlled same as setpoint, but the timer
20
stop working, and the running time and setpoint remains. At Hold status, press and hold the
key for about 2
seconds until the lower display window displays the "Run" symbol, the instrument will back to run program
Stop
key for about 2 seconds in the basic display status, until the lower display window
Press and hold the
displays the "stoP" symbol, means the stoP operation is executed now, when program stopped, timer will be
reset and stop. This operation forces the instrument to stop running, meanwhile, the StEP number will reset to 1,
and control output is also stopped
Parameter was protected by LOC (Parameter LOCK) to prevent setting error. The function was shown as below:
: allow to modify data or execute
X : not allow to modify data or execute
Run, Stop, Hold. and Program Time & Temp. function just for AI-518P only
Primary
Secondary Can changing status to Run,
Loc
SV
AT
Program Step Time & Temp.
Parameter
Parameter Stop
0
X
X
2
X
X
X
3
X
X
X
X
X
4~255
X
X
X
X
X
X
808
Loc 808 is the master password, this valve can be change by parameter PASd. Please set PASd cautiously, if the password lost,
you cant access the parameter table again.
1 to 8 field parameters can be defined by parameters EP1 to EP8. If the number of the field parameters is less than 8, the first idle
EP parameter should be set to nonE. The initial values of EPs and Loc are EP1=HIAL, EP2=LoAL, EP3=HdAL, EP4=LdAL,
EP5=nonE, EP6=nonE, EP7=nonE, EP8=nonE and Loc=0.
You can redefine field parameters and Loc to change operation style. For example, you can execute auto tuning from field parameter
in basic display status, and only take HIAL and HdAL as field parameter.
instead of by pressing
The EP paramters and Loc should be set as follows: EP1=HIAL, EP2=HdAL, EP3=At, EP4=nonE, Loc=1
23
AHYS
Alarm
hysteresis
AdIS
Alarm display
02000
units
oFF : Will not display alarm message in the lower display window when alarming;
on : Alternately display alarm message in the lower display window when alarming.
oFF / on
25
AOP
Alarm output
allocation
Alarm
LdAL
HdAL
LoAL
HIAL
Output to
(x 1000)
(x100)
(x10)
(x1)
0
0
0
0
None
1
1
1
1
AL1
2
2
2
2
AL2
3
3
3
3
AU1
4
4
4
4
AU2
Example:
AOP =
3
3
0
1
LdAL
HdAL
LoAL
HIAL
It shows that HdAL and LdAL are sent to AU1, LoAL has no output, HIAL is sent to
AL1.
Note 1: When AUX is used as auxiliary output in bidirectional (heating/refrigerating)
control, alarm to AU1 and Au2 wont work.
Note 2: Installing L5 dual relay output module in ALM or AUX can implement AL2 or
AU2 alarm.
26
04444
CtrL
Srun
Control mode
onoF
APId
nPId
POP
SOP
Running Status
StoP /
run /
HoLd
27
Act
Acting method
At
Auto tuning
Proportional
band
rE: Reverse acting. Increase in measured variable causes a decrease in the output,
such as heating control.
dr: Direct acting. Increase in measured variable causes an increase in the output,
such as refrigerating control.
rEbA: Reverse acting with low limit alarm and deviation low alarm blocking at the
beginning of power on.
drbA: Direct acting with high limit alarm and deviation high alarm blocking at the
beginning of power on.
oFF: Auto tuning function was off.
on: Active auto turning function to calculate the values
FoFF : Auto tuning function was off, cannot activate again by pressing key from
panel .
Proportional band in PID and APID control.
Instead of percentage of the
measurement range, the unit is the same as PV.
Generally, optimal P, I, D and CtI can obtained by auto tuning. They can also be
manually inputted if you already know the correct values.
28
rE
dr
rEbA
drbA
oFF / On /
FoFF
1~32000
units
Time of Integral
Time of
Derivative
CtI
Control period
09999
seconds
0999.9
seconds
0.2
300.0
Sec
nd
P2
2
Proportional
band
nd
I2
d2
CtI2
CHYS
Time of
Integral
nd
2 Time of
Derivative
nd
The 2 proportional band in PID and APID control. Instead of percentage of the
measurement range, the unit is the same as PV.
Generally, optimal P, I, D and CtI can obtained by auto tuning. They can also be
manually inputted if you already know the correct values.
2nd Control
period
Control
Hysteresis
CHYS is used for on-off control to avoid frequent on-off action of relay.
For a reverse acting (heating) system, when PV > SV, output turns off; when
PV<SV-CHYS, output turns on.
For a direct acting (cooling) system, when PV<SV, output turns off; when
PV>SV+CHYS, output turns on.
30
1~32000
units
09999
seconds
0999.9
seconds
0.2
300.0
Sec
02000
InP
Input
specification
Code
InP
0
1
2
3
4
5
6
7
8
9
10
12
15
Input spec.
K
S
R
T
E
J
B*
N
WRe3-WRe25
WRe3-Wre26
Extended
input
specification
F2 radiation type pyromter
4 20mA (installed I4
module in MIO)
31
InP
20
21
22
25
26
27
28
29
30
31
Input spec.
Cu50
Pt100
Pt100 (-80+300.00) *
0~75mV voltage input
080ohm resistor input
0400ohm resistor input
020mV voltage input
0100mV voltage input
060mV voltage input
0500mV voltage input
32
33
34
037
dPt
ScL
ScH
Scb
Display
Resolution
Signal scale
low limit
Signal scale
high limit
Input Shift
Adjustment
16
0 20mA (installed I4
module in MIO)
35
010V
17
K (0300.00) *
36
210V
18
J (0300.00) *
37
020V
0 / 0.0 /
0.00 /
0.000
-9990
+32000
units
-1999
+4000
units
FILt
PV input filter
Fru
Selection of
power
frequency and
temperature
scale
OPt
Main output
type
040
50C, 50F,
60C, 60F
SSr
rELy
0-20
4-20
PHA
slot.
4-20: 420mA linear current output. X3 or X5 module should be installed in OUTP
slot.
PHA: Single-phase phase-shift output. K5 module should be installed in OUTP slot.
PHA is only for 50Hz power supply, and dont support bidirectional control system.
34
Aut
OPL
Auxiliary output
type
Define AUX only when AUX is worked as the auxiliary output of a heating/refrigerating
bidirectional systerm.
SSr: to output SSr driver voltage or thyristor zero crossing trigger signal. G, K1 or K3
module should be installed. The output power can be adjusted by adjusting the
on-off time proportion. The period (CtI) is generally 0.54 seconds.
rELy: for relay contact output or for execution system with mechanical contact switch.
To protect the mechanical switch, the output period (CtI) is limited to 3120 seconds,
and generally is 1/5 to 1/10 of derivative time.
0-20: 020mA linear current output. X3 or X5 module should be installed in AUX
slot.
4-20: 420mA linear current output. X3 or X5 module should be installed in AUX
slot.
Note: In a heating/refrigerating bidirectional control system, if any of OPt or Aut is set
to rELy, then CtI is limited to 3120.
SSr
rELy
0-20
4-20
0100%: OPL is the minimum output of OUTP in single directional control system.
-1-110%: The instrument works for a bidirectional system, and has
heating/refrigerating dual output. When ACt=rE or rEbA, OUTP (main output) works
for heating, and AUX (Auxiliary output) works for refrigerating. When Act=dr or drbA,
-110
+110%
35
Output upper
limit
OPL limits the maximum of OUTP (main output) when PV<OEF. OPH should be
greater than OPL.
0110%
OEF
Work range of
OPH
When PV<OEF, the upper limit of OUTP is OPH; when PV>OEF, the upper limit of
OUTP is 100%.
For example, to avoid that the temperature raises too quickly, under 150, a heater
can work only under 30% of power, then we can set OEF=150.0 (), OPH=30 (%)
-999
+3200
Addr
Communication
address
bAud
Baud rate
080
019.2K
Et
Event input
type
If set parameter bAud = 2, it can be used for AU1 or AL1 alarm output.
For D4 dimension instrument, if I2 is installed and bAud = 1, then it can input on-off
signal to switch SV1 and SV2 (AI-518) or switching the program status RUN/Stop
(AI-518P) by connecting a switch between terminals number 3 and 5.
When I2 module was installed, the meter have following functions,
nonE : Disable event input function
reSt : Run / Stop switching function. Connected in short time, start to running
program, keep connect more than 2 sec, program switch to stop.
SP1.2 : Switching between setpoint 1 and setpoint 2 when use AI-518 or Pno=0 at
AI-518P. MIO in open status, SV=SP1, when MIO in close status, SV=SP2
st
nd
PId2 : Switching 1 PID and 2 PID. When use as single direction control, MIO in
open status, P, I, d and Ctl was active, when MIO in close status, P2, I2, d2 and Ctl2
was active
37
nonE /
rest /
SP1.2 /
PId2
AF
Advanced
function
A=0, HdAL and LdAL work as deviation high and low limit alarms;
A=1, HdAL and LdAL work as high and low limit alarms, and the instrument can have
two groups of high and low limit alarms.
B=0, Alarm and control hysteresis work as unilateral hysteresis;
B=1, As bilateral hysteresis.
C=0, The light bar indicates the output value;
C=1, The light bar indicates the process value (for instruments with light bar only).
D=0, Loc=808 can access the whole parameter table;
D=1, Loc=PASd can access the parameter table.
E=0, Normal application on HIAL and LoAL;
E=1, HIAL AND LoAL will become to deviation high alarm and Deviation low alarm
F=0, Fine control mode, internal control resolution was demonstrations 10 times.
When on linear input mode, biggest display value is 3200 units
F=1, Wide range display mode, when the value is bigger than 3200 ,chooses this
option
38
0255
G=0, When the thermocouple or RTD input is burnt out, PV value will increase and
trigger the high limit alarm.
G=1, When the thermocouple or RTD input is burnt out, PV value will increase and
NOT trigger the high limit alarm. After it was sets, High Limit alarm will have 30 sec.
delay for trigger in normal usage.
Note: AF=0 is recommended.
PASd
Password
SPL
SP1
Low limit of SV
Upper limit of
SV
Setpoint 1
SP2
Setpoint 2
SPH
When PASd=0255 or AF.D=0, set Loc=808 can enter the whole parameter table.
When PASd=256 9999 and AF.D=1, only Loc=PASd can access the whole
parameter table.
Please setting PASd cautiously, if the password is lost, you cant access the
parameter table again.
Minimum value that SV is allowed to be.
Maximum value that SV is allowed to be.
When Pno=0 or 1, then SV=SP1
When I2 module installed in MIO slot, SP1 and SP2 can be switched by an external
switch. If the switch is off, SV=SP1; if the switch is on, SV=SP2.
39
09999
-999
+3000
unit
SPL
SPH
SPr
Ramp Slope
limit (Only for
AI-518P)
Pno
No. of Program
step (Only for
AI-518P)
PonP
Program run
mode after
power restart
(Only for
AI-518P)
Once SPr was set, if PV<SV when program start, the first step of ramp slope will
limited by SPr value until the temperature reach the first SV , under this limitation, the
RUN lamp will keep flashing.
For Ramp mode. SPr had effect on first step only.
For Soak mode, SPr had effect on each step.
To define the number of program in use.
Pno= 0, disable the program running mode, then AI-518P will same as AI-518,
meanwhile, can set the parameter SPr to limit the ramp time.
Pno=1~30, AI-518P working as normal programmable controller
Cont : Continue to run the program from the original break point. If STOP STATUS
was activated before power cut, then it (the program) will keep stop status after power
restart.
StoP : Stop the program after power restart
run1 : Start to run the program from step 1 unless the instrument was in stop state
before power cut.
dASt : If these have deviation alarm after power resume, then stop the program,
otherwise, continue run the program from the original break point.
HoLd : Go into HOLD state after power on. If it is in StoP state before power cut, then
keep in StoP State after power on.
40
0~3200
/Min
0~30
Cont /
StoP /
run1 /
dASt /
HoLd
PAF
Program
Running mode
(Only for
AI-518P)
EP1
EP8
Field
parameter
definition
41
nonE and
all
parameter
codes
44
StEP time:
Total run time of the program step. The unit is minute and the available value range from 1 to 9999.
Running time:
The Time of current Step has run. As the running time reaches the Step time, the program will jump to the next Step
automatically.
45
Jump:
The program can jump to any other steps in the range of 1 to 30 automatically as you programmed in the program
Step, and realize cycle control.
Run/Hold:
When program is in the running status, timer works, and set point value changes according to the preset curve. When
program is in the holding status, timer stops, and set point remains to make temperature hold also. The holding
operation can be programmed into the program step.
Stop:
When the stop operation is activated, the program will stop, running time will be clear, event output switch will reset
and the output control will stop output. If run operation is activated when instrument is in the stop status, the program
will start-up and run again from the set step no. The stop function can be programmed into the program Step. The stop
operation can also be performed manually at any time. (After stop operation is done, the step no. will be set to 1, but
user can modify it again). If the program ran the last step of Pno, program will stop automatically.
46
Curve fitting:
Curve fitting is adopted as a kind of control technology for AI-518P series instrument. As controlled process often has
lag time in system response, by the way of curve fitting the instrument will smooth the turning point of the linear
47
heating-up, cooling-down and constant temperature curves automatically. The degree of the smooth is relevant with
the systems lag time t (t=d+CtI) ; the longer of the lag time, the curve will more smooth. On the opposite the smooth
function will be weaker. Generally the shorter of the process lag time (such as temperature inertia), the better of the
program control on effect. By the way of the curve fitting to deal with the program curves, will avoid overshoot. Note:
The characteristic of the curve fitting will force the program control to generate fixed negative deviation during the
linear heating-up and fixed positive deviation during the linear cooling-down, the deviation is direct proportional to the
lag time and the speed of heating-up (cooling-down). This phenomenon is normal.
StEP2: SP 2=400 , t 2=60.0 Temperature raised to 400, slope of raising curve is 10/minute, The program take 60
minutes to raise temperature to SP3 (400 degree). It means keep the same temperature in 60 minutes.
StEP3: SP 3=400 , t 3=120.0 This is the step for temperature cooling down, slope of cooling curve is 2/minute, and
the time needed is 120 minutes to reach SP4 (160degree).
StEP4: SP 4=160 , t 4=0.0 When temperature reached 160 degree, the program get in Hold state. If need go to next
step, it needed operator to executed the run for next step.
StEP5: SP 5=160 , t05=-1.0 Jump to StEP1 to start from beginning.
In this example, it is assumed that the deviation high alarm is set to 5. Because the temperature of StEP 5 is 160,
and the temperature of StEP1 is 100, when program jumps from StEP 5 to StEP 1, the program will change to
preparation state at first(if preparation mode rdy was enabled), i.e., Control the temperature until the deviation
between setpoint and PV is less than deviation high alarm value. After temperature is controlled to 105, the program
will be started from StEP 1, and run the above steps again. The temperature control drawing was shown below.
49
50
Time setting
Set t-xx = 13200 (min)
Set the time of xx StEP. (Time units can be change to Hour by parameter PAF.)
Set t-xx = 0.0
The program hold on StEP xx, program will hold running and hold counting time.
Set t-xx = -121.0
The program stops, and switches to stop status.
Set t-xx = -0.1-122.0
Negative value of this range represents a jump operation which will jump to step xx and event output. Range -1~-120
is for step jumping application. The step jumping cannot greater than Pno(No. of Program step).
Decimal point use for control the event output from AL1 and AL2. (Modular), Note, if parameter AOP was assigned
alarm action will trigger from AL1 and AL2, the event output also will cause alarm from AL1 and AL2.
51
When set
-XXX.1, AL1 activate, AL2 release
-XXX.2, AL1 release, AL2 activate
-XXX.3, AL1 and AL2 activate
-XXX.4, AL1 and AL2 release
Example:
Example 1 : t -5 = -1.1 ; means when the program arrived step 5, AL1 activate, AL2 release and
will jump to step 1 continues running
Example 2 : t-6 = -0.3 ; means when the program arrived step 6, AL1 and AL2 activate and
continuous next step.
Note: The program will be held if it jump from a control segment to another control segment (an Hold action will be
inserted between two control sections), external run/Hold operation is needed to release the Hold status. It is not
allowed that the jump section jump to itself (for example: t 06= -6), otherwise, the Hold status cannot be released.
53