Power System Protection
Power System Protection
Relay function
Causes fast disconnection of equipment
from power system during abnormal
conditions
Minimizes damage
Minimizes effects on the system operation
Maximizes power transfer
Relay function
Power transfer (from C.R. Mason page 13)
I CT
I SYS
=
N CT
Current
50:5
100:5
200:5
400:5
600:5
1000:5
20005
Turns
10
20
40
80
120
200
400
10
VPT = VSYS
N2
N1
11
Relaying Diagram
Jan 20/2006
12
13
Relay Contacts
a Contact
Open when relay that controls it is
not picked up, or when CB that
controls it is open
Closed when relay that controls it is
picked up, or when CB that controls
it is closed
b Contact
Closed when relay that controls it is
not picked up, or when CB that
controls it is open
Open when relay that controls it is
picked up, or when CB that controls
it closed
Copyright L.R. Orama 2006
14
Contacts
A relay is said to be picked up
when its:
Its a contacts are closed
or
Its b contacts are open
15
16
17
18
Security
Relay should not cause CB to open during
normal conditions
Dependability (reliability)
Relay should cause CB to open during
abnormal operation
Copyright L.R. Orama 2006
19
Selectivity
Ability to discriminate between faults internal and
external to its intended zone of protection
20
21
Protection system
Primary and backup
Jan 23/2006
22
Primary Protection
Primary
To do it, zones are drawn on the systems
one-line diagram
Zones are defined by CT location and include
equipment & CBs that isolate equipment
23
Primary Protection
24
Primary Protection
Primary
protective zones
Zones defined
by the CTs
located in the
bushings of the
CBs
Zones overlap to
avoid uncovered
areas and CB
failure
Copyright L.R. Orama 2006
25
Relay failure
Copyright L.R. Orama 2006
26
27
Backup Protection
Provided in case of:
Primary relay failure
Circuit breaker failure
28
Backup Protection
Types of backup protection
Remote backup
Clears fault one substation away from where the
failure has occured
Local backup
Clears fault in the same substation where the
fault has occured
29
Remote Backup
30
Remote Backup
Trips more system than necessary to clear
the fault
Long backup times from 50-60 cycles (0.81.0 sec)
Difficult to set remote relays
Initially, more economical
In the long run is more expensive
Copyright L.R. Orama 2006
31
Local Backup
Primary relay op.
& energizes timer
If CB relays
remain picked up
& timer times out
Opens all CBs on
the bus (trips all
CBs)
32
Local Backup
J opens
H closed
G and I opens
Load is operating
Copyright L.R. Orama 2006
33
Local Backup
P and O open
M closed
G and I opens
L trips locally
I tripped by
communicated signal
(Transfer Trip)
A special kind of
backup keeps Z
closed
Copyright L.R. Orama 2006
34
Local Backup
When a CB does not work
Trips least amount of system in clearing a
fault
Fastest backup times are 9-20 cycles
(0.15-0.33 sec)
Simple relay settings
Initially has a higher cost
Copyright L.R. Orama 2006
35
Local
36
Local
37