MSC.1/Circ.1318
ANNEX
GUIDELINES FOR THE MAINTENANCE AND INSPECTIONS
OF FIXED CARBON DIOXIDE FIRE-EXTINGUISHING SYSTEMS
1
General
These Guidelines provide the minimum recommended level of maintenance and inspections for
fixed carbon dioxide fire-extinguishing systems on all ships, and are intended to demonstrate that
the system is kept in good working order as specified in SOLAS regulation II-2/14.2.1.2. These
Guidelines are intended to supplement the fire-extinguishing system manufacturers approved
maintenance instructions. Certain maintenance procedures and inspections may be performed by
competent crewmembers, while others should be performed by persons specially trained in the
maintenance of such systems. The onboard maintenance plan should indicate which parts of the
recommended inspections and maintenance should be completed by trained personnel.
2
Safety
Fixed carbon dioxide fire-extinguishing systems should be kept in good working order and
readily available for immediate use. Maintenance and inspections should be carried out in
accordance with the ships maintenance plan having due regard to ensuring the reliability of the
system. The onboard maintenance plan should be included in the ships safety management
system and should be based on the system manufacturers recommendations including:
.1
.2
.3
.4
I:\CIRC\MSC\01\1318.doc
MSC.1/Circ.1318
ANNEX
Page 2
4
Monthly inspections
4.1
At least every 30 days a general visual inspection should be made of the overall system
condition for obvious signs of damage, and should include verification that:
4.2
.1
.2
all releasing controls are in the proper position and readily accessible for
immediate use;
.3
all discharge piping and pneumatic tubing is intact and has not been damaged;
.4
all high pressure cylinders are in place and properly secured; and
.5
.2
.3
the manually operated storage tank main service valve is secured in the open
position; and
.4
Annual inspections
The following minimum level of maintenance and inspections should be carried out in
accordance with the system manufacturers instructions and safety precautions:
.1
the boundaries of the protected space should be visually inspected to confirm that
no modifications have been made to the enclosure that have created uncloseable
openings that would render the system ineffective;
.2
all storage containers should be visually inspected for any signs of damage, rust or
loose mounting hardware. Cylinders that are leaking, corroded, dented or bulging
should be hydrostatically retested or replaced;
.3
system piping should be visually inspected to check for damage, loose supports
and corrosion. Nozzles should be inspected to ensure they have not been
obstructed by the storage of spare parts or a new installation of structure or
machinery;
.4
the manifold should be inspected to verify that all flexible discharge hoses and
fittings are properly tightened; and
I:\CIRC\MSC\01\1318.doc
MSC.1/Circ.1318
ANNEX
Page 3
.5
all entrance doors to the protected space should close properly and should have
warning signs, which indicate that the space is protected by a fixed carbon dioxide
system and that personnel should evacuate immediately if the alarms sound. All
remote releasing controls should be checked for clear operating instructions and
indication as to the space served.
6.1
At least biennially (intervals of 2 years 3 months) in passenger ships or at each
intermediate, periodical or renewal survey* in cargo ships, the following maintenance should be
carried out (to assist in carrying out the recommended maintenance, examples of service charts
are set out in the appendix):
.1
all high pressure cylinders and pilot cylinders should be weighed or have their
contents verified by other reliable means to confirm that the available charge in
each is above 90% of the nominal charge. Cylinders containing less than 90% of
the nominal charge should be refilled. The liquid level of low pressure storage
tanks should be checked to verify that the required amount of carbon dioxide to
protect the largest hazard is available;
.2
the hydrostatic test date of all storage containers should be checked. High
pressure cylinders should be subjected to periodical tests at intervals not
exceeding 10 years. At the 10-year inspection, at least 10% of the total number
provided should be subjected to an internal inspection and hydrostatic test**.
If one or more cylinders fail, a total of 50% of the onboard cylinders should be
tested. If further cylinders fail, all cylinders should be tested. Flexible hoses
should be replaced at the intervals recommended by the manufacturer and not
exceeding every 10 years; and
.3
the discharge piping and nozzles should be tested to verify that they are not
blocked. The test should be performed by isolating the discharge piping from the
system and flowing dry air or nitrogen from test cylinders or suitable means
through the piping.
6.2
At least biennially (intervals of 2 years 3 months) in passenger ships or at each renewal
survey* in cargo ships, the following maintenance should be carried out by service
technicians/specialists trained to standards accepted by the Administration:
.1
where possible, all activating heads should be removed from the cylinder valves
and tested for correct functioning by applying full working pressure through the
pilot lines.
In cases where this is not possible, pilot lines should be disconnected from the
cylinder valves and blanked off or connected together and tested with full working
pressure from the release station and checked for leakage.
In both cases this should be carried out from one or more release stations when
installed.
*
**
Refer to Survey guidelines under the Harmonized System of Survey and Certification, 2007 (resolution A.997(25)).
Refer to standard ISO 6406 Periodic inspection and testing of seamless steel gas cylinders.
I:\CIRC\MSC\01\1318.doc
MSC.1/Circ.1318
ANNEX
Page 4
If manual pull cables operate the remote release controls, they should be checked
to verify the cables and corner pulleys are in good condition and freely move and
do not require an excessive amount of travel to activate the system;
.2
all cable components should be cleaned and adjusted as necessary, and the cable
connectors should be properly tightened. If the remote release controls are
operated by pneumatic pressure, the tubing should be checked for leakage, and the
proper charge of the remote releasing station pilot gas cylinders should be
verified. All controls and warning devices should function normally, and the time
delay, if fitted should prevent the discharge of gas for the required time period;
and
.3
after completion of the work, the system should be returned to service. All
releasing controls should be verified in the proper position and connected to the
correct control valves. All pressure switch interlocks should be reset and returned
to service. All stop valves should be in the closed position.
I:\CIRC\MSC\01\1318.doc
MSC.1/Circ.1318
ANNEX
Page 5
APPENDIX
EXAMPLE SERVICE CHARTS
HIGH PRESSURE CO2 SYSTEM
Date:
Name of ship/unit:
IMO No.:
Technical description
No.
1
2
3
4
5
6
7
8
9
Text
Manufacturer
Number of main cylinders
Main cylinders capacity (each)
Number of pilot cylinders
Pilot cylinder capacity (each)
Number of distribution lines
Oldest cylinder pressure test date
Protected space(s)
Date flexible hoses fitted/renewed
Value
Description of inspection/Tests
No.
Description
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
*
I:\CIRC\MSC\01\1318.doc
Carried
out
Not carried
Not
Comment
out
applicable
MSC.1/Circ.1318
ANNEX
Page 6
LOW PRESSURE CO2 SYSTEM
Date:
Name of ship/unit:
IMO No.:
Technical description
No.
1
2
3
4
5
6
7
Text
Manufacturer
No. of tanks
Tanks capacity (tonnes)
Number of pilot cylinders
Pilot cylinder capacity (each)
Number of distribution lines
Protected space(s)
Value
Description of inspection/Tests
No. Description
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
*
Carried
out
___________
I:\CIRC\MSC\01\1318.doc
Not carried
Not
Comment
out
applicable