Generator Protection Class Defined
Generator Protection Class Defined
Module 7
GENERATOR PROTECTION
OBJECTIVES:
After completing this module you will be able to:
Pag.2
7.1
7.2
Pag.s2-4~
a)
Pag.sU ~
b)
Pag.7~
c)
Pag.7~
d)
Generatorlossoffiel~
Pag.9~
e)
Overexcitation.
Pag.9~
f)
Generator underfrequency,
Pag.10~
Pag.s 10-11
Pag.. I1-12~
Pag.. 4-11~
i)
7.3
Motoring.
INSTRUCTIONAL TEXT
INTRODUCTION
This module concentrates on the protection schemes used for the protection
of generators and the consequences of their failure to operate. A brief
discussion will also be given on the operation of the various types of
protective relays, but you will not be required to memorize this
information.
-1-
Approvellssue
There are different classes of protecove nips for generators. -each with
different actions, depending on the cause and potential for damage. Each of
the four Classes of nip (A, B, C, &D) are discussed below.
Class A trips will completely separate the generator from tbe grid, and
sbut down tbe turbine generator (ie. it will nip the turbine and the field
breaker). Typical causes could be generator electrical protection, main
transformer electrical protection, ground faults or,any other cause which may
directly affect the unit's safe electrical output.
Class B trips will disconnect the generator from the grid, but will leave
tbe turbine generator supplying the unit load. Typical initiation of this
event is a grid problem, thus resulting in this loss of load.
Class C trips are generator overexcitation trips, and are activated only if
the generat9I' is not connected to the grid (it may still be supplying the unit
loads). Typical causes of this overexcitation are manually applying too much
excitation, or applying excitation current below synchronous speed (this will
be discussed later in this module).
Class D trips the turbine and then trips the generator after motoring
(motoring is discussedin the 234Turbine and-Auxiliaries course). The causes
of this type of nip are associated with mechanical problems with the turbine
generator set
Each of these trips, along with their causes and exact effects, will be
discussed further in your station specific training.
-2-
... ,
Approval Issue
Generator Tel111lnals
.o
o
o
------
-.
o
o
Protection :
Zones ,
o
o
o
o
o
o
o
o
,o
,,"
,,
,,
,
Neutral
Connection
To Ground
aj Heahhy
Phase
bl
Fau~ed
c) Open Circuit in
Phase
the Phase
In Figure 7.1 bJ, a ground fault is shown on one of the windings. In this case
the faultcutTent direction is shown, and it will be unbalanced. This will result
in unbalanced secondary currents in the protection circuit, causing the
differential relay to operate. Similarly, a"short circuit" within a winding will
cause the two winding currents to be unmatched, causing the differential
relay to operate.
In Figure 7.1 c), an optn circuit is shown, resulting in no current in the one
winding. Again, the unbalanced currents will cause the differential relay to
operate.
'd~
-3-
""I
Approvsllssue
This latter type of differential protection scheme could be used to protect the
windings of the generator and the main transfonner, by optimum placement
of the current transformers. Figure 7.2 shows the differential scheme with the
current transformers located at the output side of the main transformer, the
connection for the unit service transfonner and on the generator winding at
the center of the star connection. This puts the generator winding and main
transformer windings within the zone of protection for this differential
scheme. Note that the current transformers will require a different ratio, since
Transformer
,..........,.\A-(G}--""'---<:
>--.+Ir..-{
Differential
Relay
~>---
Unit Service
Transformer
Connection
Unit Service
Transformer
Figure 7.2:
If the faults listed earlier are not cleared, then the risk ofinsulation damage
will occur due to overheating. as well as damage from arcing if the
insulation has already been damaged.
In the pre0.olls section, we have seen how differential protection can be used
to protect against a ground fault in the windings of the generator itself.
-4-
"'1
ApprovalisSUB
Generator Terminals
Neutral
Connection
Transformer
GrInding
Resistor
=!>
=!>
The windings on the rotor of an ac generator produce the magnetic field at the
poles. In four pole generators (typical of 60 Hz, 1800 rpm units). the
-5-
.."
Approvellssue
A means of detecting the first ground fault provides protection against the
effects of a second fault to ground on the rotor. Figure 7.4 shows a simplified
excitation system with a ground fault detection (GFD) circuit'. The GFD is
connected to the positive side of the exciter source.
r---------;:::l.,Reid
Winding
L----r----=:r+
Current Umitlng Resistor
Auxmary
IIC
A.C. Supply
Rotor grolllfdfau1l protection was tkaltwith in your 335.05-1 Electrit:D1 Systems COUTS#!.
-6-
Approve/issue
Obi. 7.2 c)
:>
:>
Relays that sense conditions resulting from a loss of field, such as reactive
power flow to the machine, internal impedance changes as a result of field
changes or voltage decreases, may be used fur the detection of the loss of
field. A field breaker limit switch indicating that the breaker is open also
gives an indication that there is no field to the generator.
.. Trips of the whine-generator initiated by high vibration signals an discussed in the 234
-7-
... ,
Approvallssua
Cl&Ss A trips will completely separate the Unit from the grid, and shut
Class B trips will disconnect the generator from the grid, but will leave
the turbine generator supplying the unit loads.
Cl&Ss D trips will trip the turbine and then trip the generator after
motoring.
The flow of fault currents can arise from insulation damaged due to
aging, overheating, moisture or mechanical damage.
Loss of field protection will prevent the generator from pole slipping.
which can result in mechanical shocks to the turbine generator. This can
be caused by an exciter failure, automatic voltage regulator failure,
accidental tripping of the field breaker, shorl circuits in the field
currents, poor brush contact on the sliprings, or ac power loss to the
exciters.
Loss of field can be detected by special relays that sense reactive power
flow to the machine or internal impedance changes.
-8-
,,",I
Approvellssue
This problem may occur on generators that are connected to the grid if they
experience generator voltage regulation problems. It may also occur for
units during start-up or ,.....ynchroniZing following a trip (the field breaker
should open when the turbine is tripped. At low frequencies, the field
discharge resistor should prevent tenninal voltage from reaching dangerous
levels**). Overexcitation in these instances may be a result of equipment
problems or operator error in applying excessive excitation prematurely
(excitation should not be applied to the generator until it reaches ncar
synchronous speed).
7.2f)~
Obi. 7.3
Obi.
oil.
oil. .
-9-
"'1
Approvellssue
7.3~
This protects the generator from continuing operation when the generator is
pole slipping. Pole slipping will result in mechanical rotational impacts to
the turbine, as the generator slips in and out of synchronism. This can be
the result of running in an under excited condition (see the section on loss
of field), or a grid fault that has not cleared.
Obj. 7.2 g)
As the amount of current through the rectifiers increases. the generator field
increases. This current must be limited to prevent damage due to
overheating. Complete loss ofthe rectifier can occur if the protective device
for the circuit operates, if the rectifier has a component fault, or if the unit has
tripped on overload or high temperature (these units require cooling to
dissipate heat produced). Causes ofrectifier overcurrent could be overexcitation due to some voltage regulation fault, or a grid fault requiring higher
than nonnal excitation.
Obj.
*.
-10-
Approvsllssue
and these rectifiers will also be lost Some stations will allow continued
operation with minced number of rectifiers in service, but generator
excitation (hence load) will be limited by remaining field current
capacity. By not having the field. CUITent available to "stiffen" the
generator's connection to the grid. the system stability is at risk.
The rectifiers have an overload capacity, but the duration that they can
sustain this overload is limited. This overload capacity is requiml when grid
faults result in mluced voltage, power or frequency changes. A power
stabilizing system, upon "seeing a grid problem", will call foran increase in
excitation to maintain grid stability. This is known as field forcing. If the
number of rectifiers is limited, and field forcing is required, it can/will
overload the remaining rectifiers. resulting in a total loss ofexcitation (hence
production). To prevent this, the ability to rreld force is reduced to a value
dependent upon the number ofrectifier sections in service. This will result in
a less secure electrical supply.
MOTORING
Obj. 7.3 =>
TM stabilizing $JIfDn will detect vollage. spud tJNi powt!T c1IlJ1ages llwt CtDI btt indicalwe ofQ,
grid ftuJI. TIw. ~i:ilIg S'J#I!III willlM disc~ in JOfU station spifU: training.
.. FIITtIwr infonNJlion on turbiM genuator motoring can lMfound in 1M TlU'bine & Auxiliaries
cOline 234.0-13.
-11-
'""
ApprovsllSSUB
r--
AA
.,.
.J:.
AA
'--
/'
'-
"
./
-.b
-
V.T.
Reverse
Power
Relay
Figure 7.5:
CI.... ofTrip
Differential Protection
Phase Unbalance
Loss of Field
Overexcitation
A,B,C
Underfrequency
Out nfStep
A*
Motoring
This does not lead to a trip directly, though once excitation collapses, a loss
of excitation trip will result.
-12-
""'I
Apptovallssue
Pages 13-18
<=}
A-reverse power relay detects the flow of power into a generator. It can
provide an alann. as occurs before turbine generator motoring. or
initiate a protective trip. as is the case with standby generators.
-13-
... ,
Approvsllssue
ASSIGNMENT
1.
Class B:
Class C:
Class D:
2.
3.
b)
c)
-14-
... ,
Approval Issue
4.
5.
c)
6.
Explain how ground fault protection is provided for a generator rotor (in
your explanation include consequences to station equipment if this
protection fails to operate):
7.
Explain how phase unbalance protection is used. for a generator (in your
explanation include conseque,nces to station equipment if this protection
fails to operate):
-15-
Rod
Approvellssue
8.
b)
9.
Explain how loss of field protection is used for a generator (in your
explanation include consequences to station equipment if this protection
fail' to operate):
b)
c)
d)
11. Explain how overexcitation protection is used for a genemtor (in your
explanation include consequences to station equipment if this protection
fail' to operate):
-16-
... ,
Approvsllssue
NOTES' REFERENCES
13. Explain how underfrequency protection is used for a generator (in your
explanation include consequences to station equipment if this protection
fails to operate):
b)
15. Explain how out of step protection is used for a generator (in your
explanation include consequences to station equipment if this protection
fails to operate):
16. Three possible reasons that of out of step operation could occur are:
a)
b)
c)
-17-
... ,
ApprovallssUB
(in your
b)
Before you move on to the next module. review the objectives and make
sure that you can meet their requirements.
Prepared by:
Revised by:
Revision date:
-18-
MYl