MS Maneurop Refigeration Compressors Spec Sheets
MS Maneurop Refigeration Compressors Spec Sheets
MS Maneurop Refigeration Compressors Spec Sheets
REFRIGERATION &
AIR CONDITIONING DIVISION
Selection &
Application guidelines
Application guidelines
Contents
FRCC.PC.004.A4.02
Application guidelines
The positive benets of internal motor protection, high eciency circular valve design and high
torque motors provide for a quality installation.
The MT series is designed for use with the traditional R22 refrigerant, using Danfoss mineral oil
160P as lubricant.
The MT series can also be applied with several R22
based refrigerant blends (substitute refrigerants),
using 160 ABM alkylbenzene as lubricant. The
MTZ series is specically designed for use with
FRCC.PC.004.A4.02
MT and MTZ compressors are available in 22 different models with displacement ranging from
30 to 271 cm3/rev. Seven dierent motor voltage
ranges are available for single and three phase
power supplies at 50 and 60 Hz. Most compressors exist in two versions:
standard version
VE version (oil equalisation + oil sight glass).
Application guidelines
Code numbers
(for ordering)
Compressor
type
Packaging type
I: single pack
M: industrial pack
(see ordering section)
Polyolester
oil
Motor power
(divide by 12 to convert to HP)
Compressor reference
(indicated on the
compressor nameplate)
Compressor
type
Option code
Oil equalisation port
and sight glass
Polyolester oil
Generation index
Motor power
(divide by 12 to convert to HP)
Displacement code
(see page 5)
Versions
S version
Models
Oil sight glass
VE version
Oil equalisation
connection
Oil equalisation
connection
MT/MTZ018-040 (1 cyl.)
threaded
3/8are
MT/MTZ044-081 (2 cyl.)
threaded
3/8are
MT/MTZ100-160 (4 cyl.)
welded
threaded
3/8are
FRCC.PC.004.A4.02
Application guidelines
Specications
Technical specications
Compressor
model
Displacement
Cyl.
number
Oil
charge
dm3
Net
weight
kg
0.95
21
MT/MTZ018
JA
30.23
m3/h at
2900 rpm
5.26
MT/MTZ022
JC
38.12
6.63
0.95
21
Code
cm3/rev
MT/MTZ028
JE
48.06
8.36
0.95
23
MT/MTZ032
JF
53.86
9.37
0.95
24
MT/MTZ036
JG
60.47
10.52
0.95
25
MT/MTZ040
JH
67.89
11.81
0.95
26
MT/MTZ044
HJ
76.22
13.26
1.8
35
MT/MTZ045
HJ
76.22
13.26
1.8
37
MT/MTZ050
HK
85.64
14.90
1.8
35
MT/MTZ051
HK
85.64
14.90
1.8
37
MT/MTZ056
HL
96.13
16.73
1.8
37
MT/MTZ057
HL
96.13
16.73
1.8
39
MT/MTZ064
HM
107.71
18.74
1.8
37
MT/MTZ065
HM
107.71
18.74
1.8
39
MT/MTZ072
HN
120.94
21.04
1.8
40
MT/MTZ073
HN
120.94
21.04
1.8
41
MT/MTZ080
HP
135.78
23.63
1.8
40
MT/MTZ081
HP
135.78
23.63
1.8
41
MT/MTZ100
HS
171.26
29.80
3.9
60
MT/MTZ125
HU
215.44
37.49
3.9
64
MT/MTZ144
HV
241.87
42.09
3.9
67
MT/MTZ160
HW
271.55
47.25
3.9
69
Pressure equipment
directive 97/23/EC
CE 0062 or CE 0038
(European Directive)
All models
UL
(Underwriters Laboratories)
All 60 Hz models
CCC
(China Compulsory Product Certication)
Gost
certicate (for Russia)
Products
Refrigerating uids
Category PED
Evaluation module
Service temperature - Ts
MT - Service pressure - Ps
MTZ - Service pressure - Ps
MT/ MTZ 18 to 40
Group 2
I
no scope
50c < Ts > -35c
18,4 bar(g)
22,6 bar(g)
Products
MT/ MTZ 18 to 40
PED005C
PED005C
Products
1 cyl. with height = 333 mm (see page 10)
FRCC.PC.004.A4.02
Volume (litre)
7.2
7.7
2 cyl.
16.5
30.7
32
Application guidelines
Specications
R404A
Compressor
model
MTZ018-4*
MTZ022-4*
MTZ028-4*
MTZ032-4*
MTZ036-4*
MTZ040-4*
MTZ044-4
MTZ045-4*
MTZ050-4
MTZ051-4*
MTZ056-4
MTZ057-4*
MTZ064-4
MTZ065-4*
MTZ072-4
MTZ073-4*
MTZ080-4
MTZ081-4*
MTZ100-4*
MTZ125-4*
MTZ144-4*
MTZ160-4*
Refrigeration
50 Hz, EN12900 ratings
To = -10 C, Tc = 45C, SC = 0 K, SH = 10 K
Cooling
capacity
W
Power
input
kW
Current
input
A
C.O.P.
W/W
Cooling
capacity
W
Power
input
kW
Current
input
A
1 900
2 620
3 430
3 980
4 670
5 330
1.21
1.48
1.96
2.16
2.58
2.95
2.73
3.06
4.04
4.25
4.95
5.87
1.58
1.77
1.75
1.84
1.81
1.81
2 070
2 830
3 690
4 260
4 990
5 680
1.31
1.62
2.14
2.37
2.83
3.24
2.86
3.24
4.30
4.56
5.33
6.29
5.40
5.96
5.88
6.15
6.02
5.97
5 150
5 370
6 150
6 260
7 000
6 710
8 130
7 980
9 150
8 920
10 520
10 470
3.16
2.77
3.61
3.22
4.00
3.51
4.54
4.20
4.99
4.69
5.84
5.61
6.37
5.35
6.53
5.95
7.07
6.83
8.30
7.82
8.64
8.95
10.12
10.20
1.63
1.93
1.70
1.94
1.75
1.91
1.79
1.90
1.84
1.90
1.80
1.87
5 530
5 780
6 580
6 700
7 500
7 250
8 700
8 590
9 760
9 570
11 200
11 180
3.43
3.02
3.92
3.50
4.38
3.85
4.96
4.60
5.45
5.11
6.38
6.14
6.66
5.67
6.92
6.33
7.57
7.25
8.84
8.35
9.28
9.50
10.87
10.94
12 280
15 710
18 490
20 310
6.76
8.44
9.78
11.08
12.21
13.79
16.29
18.26
1.82
1.86
1.89
1.83
13 170
16 800
19 690
21 660
7.35
9.21
10.65
12.09
12.94
14.86
17.47
19.64
R22
Compressor
model
MT018-4
MT022-4
MT028-4
MT032-4
MT036-4
MT040-4
MT044-4
MT045-4
MT050-4
MT051-4
MT056-4
MT057-4
MT064-4
MT065-4
MT072-4
MT073-4
MT080-4
MT081-4
MT100-4
MT125-4
MT144-4
MT160-4
Power
input
kW
Current
input
A
E.E.R.
Btu.h/W
2 630
3 600
4 680
5 110
5 900
6 730
1.76
2.05
2.68
2.98
3.33
3.76
2.86
3.27
4.23
4.56
5.09
5.88
5.09
6.00
5.95
5.85
6.04
6.11
5.51
6.53
5.73
6.54
5.85
6.43
5.99
6.37
6.11
6.39
5.99
6.22
7 100
7 110
8 290
8 360
9 310
9 490
10 580
10 540
11 850
11 960
13 400
13 600
4.18
3.85
4.82
4.42
5.44
4.98
6.11
5.67
6.91
6.53
8.03
7.81
6.58
5.85
7.04
6.53
7.80
7.52
8.98
8.31
9.76
9.73
11.35
11.35
5.79
6.30
5.87
6.46
5.84
6.50
5.91
6.35
5.85
6.25
5.70
5.94
6.11
6.22
6.31
6.11
15 480
19 970
23 530
25 570
8.72
11.37
12.99
14.73
12.79
15.41
17.93
20.17
6.06
6.00
6.18
5.92
Refrigeration
Air Conditioning
To = -10 C, Tc = 45 C, SC = 0 K, SH = 10 K
Cooling
capacity
W
Power
input
kW
Current
input
A
C.O.P.
W/W
Cooling
capacity
W
Power
input
kW
Current
input
A
1 690
2 490
3 730
3 950
4 810
5 220
1.00
1.29
1.81
2.11
2.35
2.67
2.27
2.55
3.59
3.73
4.30
4.86
1.69
1.94
2.06
1.87
2.04
1.95
3 880
5 360
7 380
8 060
9 270
10 480
1.45
1.89
2.55
2.98
3.37
3.86
2.73
3.31
4.56
4.97
5.77
6.47
9.16
9.69
9.87
9.22
9.38
9.27
5 300
4 860
5 810
5 870
6 830
6 440
7 640
7 750
8 520
8 710
9 720
10 360
2.72
2.46
2.95
2.94
3.44
3.18
3.89
3.64
4.29
4.19
4.84
4.89
6.03
5.02
5.22
5.53
6.21
6.39
7.06
7.03
7.58
8.48
8.24
9.52
1.95
1.98
1.97
2.00
1.99
2.03
1.96
2.13
1.99
2.08
2.01
2.12
11 040
10 520
12 320
12 230
13 770
13 750
15 820
15 730
17 120
18 190
19 530
20 730
3.89
3.53
4.32
4.19
5.04
4.58
5.66
5.27
6.31
6.12
7.13
7.08
7.37
6.37
8.46
7.20
10.27
8.19
9.54
9.16
10.54
10.98
11.58
12.48
11 330
15 260
17 270
19 190
5.79
7.55
8.47
9.49
11.82
12.28
17.06
16.81
1.96
2.02
2.04
2.02
23 400
30 430
34 340
38 270
7.98
10.66
11.95
13.40
14.59
17.37
22.75
22.16
Cooling
E.E.R.
capacity
Btu.h/W
W
Cooling
E.E.R.
capacity
Btu.h/W
W
Power
input
kW
Current
input
A
E.E.R.
Btu.h/W
4 660
6 440
8 850
9 680
11 130
12 570
1.74
2.27
3.06
3.58
4.05
4.63
2.73
3.31
4.56
4.97
5.77
6.47
9.16
9.69
9.87
9.22
9.38
9.27
9.69
10.17
9.74
9.97
9.32
10.24
9.53
10.18
9.26
10.15
9.36
9.99
13 240
12 890
14 790
14 690
16 530
16 520
18 980
18 850
20 550
21 840
23 440
24 880
4.66
4.32
5.18
5.04
6.05
5.58
6.80
6.32
7.57
7.33
8.55
8.50
7.37
6.42
8.46
7.26
10.27
8.23
9.54
9.33
10.54
10.77
11.58
12.34
9.69
10.18
9.74
9.95
9.32
10.10
9.53
10.18
9.26
10.16
9.36
10.00
10.00
9.74
9.80
9.75
28 080
36 510
41 210
45 930
9.58
12.80
14.35
16.08
14.59
17.37
22.75
22.16
10.00
9.74
9.80
9.75
FRCC.PC.004.A4.02
Application guidelines
Specications
Air Conditioning
50 Hz, EN12900 ratings
To = +5 C, Tc = 50 C, SC = 0 K, SH = 10 K
Cooling
capacity
W
Power
input
kW
Current
input
A
C.O.P.
W/W
Cooling
capacity
W
Power
input
kW
Current
input
A
Cooling
E.E.R.
capacity
Btu.h/W
W
Power
input
kW
Current
input
A
E.E.R.
Btu.h/W
3 470
4 550
5 880
6 650
7 510
8 660
1.27
1.71
2.17
2.43
2.93
3.40
2.73
3.27
4.30
4.57
5.58
6.46
2.73
2.67
2.72
2.74
2.56
2.55
3 850
5 020
6 540
7 330
8 280
9 580
1.38
1.86
2.36
2.65
3.21
3.71
2.86
3.47
4.57
4.90
5.99
6.92
9.53
9.23
9.45
9.43
8.82
8.81
5 050
6 280
8 220
8 990
9 990
11 720
1.73
2.26
2.82
3.20
3.90
4.46
2.82
3.45
4.41
4.80
5.78
6.69
9.98
9.48
9.93
9.61
8.74
8.98
8 940
9 130
10 190
10 420
11 700
11 680
13 180
13 360
14 800
15 320
16 750
17 380
3.34
3.12
3.79
3.69
4.32
4.02
4.84
4.61
5.50
5.42
6.29
6.29
6.10
5.84
6.90
6.51
7.85
7.45
8.79
8.35
9.81
9.85
11.02
11.31
2.67
2.93
2.69
2.83
2.71
2.90
2.72
2.90
2.69
2.83
2.66
2.76
9 870
10 100
11 270
11 530
12 940
13 000
14 590
14 850
16 380
17 050
18 530
19 330
3.63
3.38
4.11
4.01
4.69
4.37
5.26
5.02
5.97
5.87
6.83
6.83
6.49
6.18
7.34
6.95
8.36
7.91
9.35
8.91
10.48
10.48
11.83
12.08
9.27
10.21
9.34
9.82
9.42
10.16
9.47
10.10
9.36
9.91
9.25
9.67
12 600
12 730
14 100
14 110
15 920
16 050
17 700
18 080
19 890
20 780
22 520
22 870
4.36
4.25
4.95
4.87
5.66
5.40
6.35
6.14
7.21
7.30
8.24
8.24
6.84
6.34
7.33
7.06
8.41
8.03
9.47
9.01
10.78
10.61
12.35
11.99
9.85
10.23
9.72
9.89
9.60
10.15
9.50
10.05
9.41
9.72
9.33
9.47
20 480
26 880
29 770
34 090
7.38
9.48
10.68
12.40
13.05
15.14
17.55
20.08
2.78
2.84
2.79
2.75
22 700
29 790
33 070
37 820
8.00
10.32
11.59
13.46
13.83
16.28
18.80
21.50
9.69
9.85
9.74
9.59
28 220
35 620
40 900
45 220
9.86
12.83
14.42
16.64
14.22
18.07
19.81
22.46
9.77
9.47
9.68
9.27
R134a
Compressor
model
MTZ018-4
MTZ022-4
MTZ028-4
MTZ032-4
MTZ036-4
MTZ040-4
MTZ044-4
MTZ045-4
MTZ050-4
MTZ051-4
MTZ056-4
MTZ057-4
MTZ064-4
MTZ065-4
MTZ072-4
MTZ073-4
MTZ080-4
MTZ081-4
MTZ100-4
MTZ125-4
MTZ144-4
MTZ160-4
Air Conditioning
50 Hz, EN12900 ratings
To = +5 C, Tc = 50 C, SC = 0 K, SH = 10 K
Cooling
capacity
W
Power
input
kW
Current
input
A
C.O.P.
W/W
Cooling
capacity
W
Power
input
kW
Current
input
A
2 310
3 000
3 730
4 390
5 340
5 700
0.92
1.11
1.41
1.74
1.97
2.15
2.12
2.42
3.18
3.80
3.88
4.58
2.51
2.70
2.65
2.52
2.71
2.66
2 550
3 350
4 210
4 950
6 000
6 400
0.99
1.20
1.53
1.87
2.13
2.33
2.19
2.51
3.30
3.94
4.09
4.89
8.81
9.56
9.40
9.03
9.60
9.36
6 120
6 090
7 170
7 110
8 040
7 680
9 160
8 960
10 540
10 230
12 080
11 750
2.36
2.06
2.68
2.44
2.99
2.62
3.36
3.02
3.74
3.50
4.31
4.02
5.51
4.56
5.33
5.02
5.61
5.93
6.66
6.53
6.83
7.66
8.03
8.44
2.60
2.96
2.67
2.91
2.69
2.93
2.73
2.96
2.82
2.92
2.80
2.92
6 870
6 850
8 070
8 010
9 070
8 720
10 350
10 160
11 850
11 650
13 580
13 320
2.52
2.22
2.88
2.63
3.21
2.84
3.62
3.26
4.01
3.78
4.64
4.35
5.65
4.73
5.50
5.20
5.83
6.17
6.96
6.81
7.20
7.99
8.45
8.83
13 770
16 980
21 030
23 080
4.89
5.84
7.27
7.98
9.84
10.24
13.11
13.90
2.81
2.91
2.89
2.89
15 530
19 070
23 620
25 860
5.28
6.29
7.83
8.57
10.24
10.80
13.78
14.67
FRCC.PC.004.A4.02
Cooling
E.E.R.
capacity
Btu.h/W
W
Power
input
kW
Current
input
A
E.E.R.
Btu.h/W
3 280
4 350
5 640
6 130
7 170
8 160
1.22
1.54
2.04
2.39
2.75
3.08
2.09
2.56
3.37
3.89
4.20
4.72
9.20
9.63
9.43
8.76
8.91
9.03
9.29
10.53
9.57
10.39
9.63
10.47
9.77
10.63
10.09
10.52
10.00
10.44
8 740
8 820
10 090
10 110
11 130
11 380
13 260
13 000
14 640
14 640
16 550
16 490
3.14
2.84
3.60
3.29
3.95
3.82
4.68
4.20
5.19
4.81
5.99
5.47
5.47
4.70
5.36
5.33
5.92
6.37
7.11
6.77
7.59
7.88
8.79
8.68
9.51
10.59
9.57
10.48
9.62
10.16
9.67
10.56
9.64
10.39
9.42
10.29
10.04
10.35
10.30
10.29
18 730
23 110
28 390
31 520
6.50
7.71
9.81
10.91
10.11
11.09
14.28
15.54
9.84
10.23
9.87
9.86
Application guidelines
Operating envelopes
MT - R22
70
65
60
S.H. = 11.1 K
55
S.H. = 30 K
50
45
40
35
30
-30
-25
-20
-5
-10
0
Evaporating temperature (C)
-15
10
15
20
MTZ - R134a
Condensing temperature (C)
80
75
70
S.H. = 11.1 K
65
60
S.H. = 30 K
55
50
45
40
35
-20
-15
-10
-5
0
5
10
Evaporating temperature (C)
15
20
25
FRCC.PC.004.A4.02
Application guidelines
Operating envelopes
Zeotropic refrigerant
mixtures
Phase shift
Temperature glide
During the evaporating process and the condensing process at constant pressure, the refrigerant
temperature will decrease in the condenser and
rise in the evaporator. Therefore when speaking
about evaporating and condensing temperatures, it is important to indicate whether this is a
dew point temperature or a mean point value. In
the gure below, the dotted lines are lines of constant temperature.
To obtain exact capacity data at mean point temperatures, the mean point temperatures must be
converted to dew point temperatures with help
of refrigerant data tables from the refrigerant
manufacturer.
FRCC.PC.004.A4.02
Application guidelines
Outline drawings
1 cylinder
224
Suction rotolock
11/4
LP gauge
port 1/4
(schrader)
333 (1) (3)
356 (2)
263
oil equalisation
(VE models only)
Discharge rotolock
1
98
68
68
25
82
109
33
35
Silent bloc
Threaded oil
sight glass
Bolt HM8-40
39
68
15
23
141
123
31.75
17
159
17
Terminal box
Spade connectors
1/4" AMP-AWE
21 mm
Earth M4-12
Knock-out 21 mm
10
Pipe sizing
Suction
Discharge
Rotolock valve
Suction
Discharge
1/2
3/8
V06
V01
11/4
5/8
1/2
V09
V06
FRCC.PC.004.A4.02
Application guidelines
Outline drawings
2 cylinders
288
Suction rotolock
1"3/4
Schrader 1/4"
413
Discharge rotolock
1"1/4
252
Oil equalisation
3/8"
265
117(1)
98(2)
74
68
20
156
60
Suction 179
Discharge 176
98 (1) / 82(2)
Silent bloc
Bolt HM8-40
171
145
21
38
15
23
125
31.75
8
1) MT/MTZ 44-6, 5 0 - 56/64-1/6, 72-6, 80-3/6, 81-3
2) MT/MTZ 44-1/3/4/7/9, 45/51/57/ 65/73 -3/4, 50-3/4/5/7/9,
56-3/4/7/9, 64/72-3/4/9, 80-4/9,81-4
96
196 (1) / 188 (2)
Screw
10-32 UNF x 9.5
Spade connectors
1/4" AMP-AWE
Knock-out
25.5 mm
21 mm
Earth M4-12
Earth M4-12
Knock-out 21 mm
Knock-out 29 mm
FRCC.PC.004.A4.02
Pipe sizing
Suction
Discharge
Rotolock valve
Suction
Discharge
MT/MTZ044 - 045 - 050 - 051 056 - 057 - 064 - 065 - 072 - 073
13/4
11/4
7/8
3/4
V07
V04
MT/MTZ080 - 081
13/4
11/4
11/8
3/4
V02
V04
11
Application guidelines
Outline drawings
4 cylinders
352
210
518 (1)
538 (2)
Suction rotolock
1"3/4
Discharge rotolock
1"1/4
117
Oil equalisation
3/8"
Threaded oil
sight glass
209
233
155
125
95
99
98
232
Mounting hole for
PTC crankcase heater
15
246
Silent bloc
15
205
155
15
246
Terminal box
Screw
10-32 UNF x 9.5
Knock-out
25.5 mm
Earth M4-12
Knock-out 29 mm
12
13/4
11/4
Pipe sizing
Suction
Discharge
11/8
3/4
Rotolock valve
Suction
Discharge
V02
V04
FRCC.PC.004.A4.02
Application guidelines
Winding
run
start
40
13
10
1.36
4.82
1.80
4.70
MT/MTZ022
49.3
41
17
15
1.25
2.49
1.78
4.74
MT/MTZ028
81
51
25
20
0.74
1.85
1.16
3.24
MT/MTZ032
84
70
26.5
20
0.64
2.85
0.90
4.30
MT/MTZ036
84
60
30
22
0.64
2.85
0.89
4.35
MT/MTZ040
99
34
0.53
2.00
MT/MTZ044
97
31
0.45
1.90
MT/MTZ050
114
92
36
29
0.37
1.79
0.52
2.65
MT/MTZ056
136
42.5
0.32
1.61
MT/MTZ064
143
46
0.32
2.10
PSC/CSR*
Models
50 Hz
60 Hz
Trickle circuit
start
51
CSR only
run
MT/MTZ018
Winding resistance ()
( 7 % at 20 C)
(C) F
(B) F
MT/MTZ018 JA-5
20
10
100
MT/MTZ022 JC-5
20
10
100
MT/MTZ028 JE-5
20
10
100
MT/MTZ032 JF-5
25
10
135
MT/MTZ036 JG-5
25
10
135
MT/MTZ050 HK-5
30
15
135
MT/MTZ018 JA-1
15
10
100
MT/MTZ022 JC-1
30
15
100
MT/MTZ028 JE-1
25
25
135
MT/MTZ032 JF-1
25
20
100
MT/MTZ036 JG-1
25
20
100
MT/MTZ040 JH-1
35
20
100
MT/MTZ044 HJ-1
30
15
135
MT/MTZ050 HK-1
30
15
135
MT/MTZ056 HL-1
35
20
200
MT/MTZ064 HM-1
30
25
235
Start relay
3ARR3J4A4
/RVA6AMKL
3ARR3J4A4
/RVA6AMKL
PSC wiring
CSR wiring
The single phase compressor motors are internally protected by a temperature/current sensing
FRCC.PC.004.A4.02
13
Application guidelines
IOL
A&C
C
S
R
220 k - 1 W
Motor protector
Run capacitors
Common
Start winding (auxiliary)
Run winding (main)
A F
C F
Thermostat
IOL
230 V
Start relay
5
IOL
A&C
B
C
S
R
220 k - 1 W
Motor protector
Run capacitors
Start capacitor
Common
Start winding (auxiliary)
Run winding (main)
IOL
2
A F
B F
C F
Thermostat
15 k - 1 W
230 V
Start Relay
C
IOL
Motor protector
A+C
Run capacitors
B
Start capacitor
C
Common
S
Start winding (auxiliary)
R
Run winding (main)
Capacitors A and C can be replaced by
a single capacitor of size A + C
Thermostat
IOL
CF
Run capacitor
AF
Run capacitor
BF
Start capacitor
14
15 k -1 w
FRCC.PC.004.A4.02
Application guidelines
MCC - Maximum
Continuous Current (A)
Winding resistance ()
( 7 % at 20 C)
Motor Code
MT/MTZ018
38
20
2.49
10.24
MT/MTZ022
38
16
30
22.5
11
8.5
2.49
10.24
3.38
6.58
MT/MTZ028
57
23
41
32
16
7.5
11.5
8.5
1.37
7.11
3.38
4.80
MT/MTZ032
60
25
44
22
35
18
13
5.5
1.27
6.15
1.27
8.90
4.20
MT/MTZ036
74
30
74
26
35
17
17
9.5
1.16
5.57
1.16
8.60
4.10
MT/MTZ040
98
38
74
22
10
18
0.95
4.56
0.95
MT/MTZ044
115
42
77
44
78
22
9.5
16
8.5
13
0.74
3.80
1.13
5.83
1.68
MT/MTZ045
115
48.5
17
9.5
0.69
3.22
MT/MTZ050
115
42
77
44
78
25
12
19
10
13.5
0.72
3.80
1.39
5.83
1.68
MT/MTZ051
120
48.5
22
11.5
0.69
3.60
MT/MTZ056
130
60
105
50
72
26
12
23
11
15
0.57
2.41
0.76
3.86
1.64
MT/MTZ057
130
64
24
12
0.55
2.39
MT/MTZ064
137
67
124
72
29
15
25
17.5
0.57
2.41
0.76
1.64
MT/MTZ065
135
64
28
14
0.55
2.39
MT/MTZ072
135
80
143
100
30
15.5
27
18.5
0.55
1.90
0.56
1.32
MT/MTZ073
155
80
32
17
0.48
1.90
MT/MTZ080
140
80
132
102
36
18
29
22.5
0.48
1.90
0.56
1.30
MT/MTZ081
140
80
36
19
0.48
1.90
MT/MTZ100
157
90
126
62
110
43
22
35
17
26
0.50
1.85
0.67
3.10
1.26
MT/MTZ 125
210
105
170
75
150
54
27
43
22
30
0.38
1.57
0.43
2.51
0.84
MT/MTZ 144
259
115
208
90
165
64
30
51
25
40
0.27
1.19
0.37
2.00
0.72
MT/MTZ 160
259
140
208
99
165
70
36
51
29
46
0.27
1.10
0.37
1.76
1.10
The 3-phase compressors are protected by an internal motor protector, connected to the neutral
point of the star connected stator windings, the
protector cuts out all 3-phases simultaneously.
CONTROL CIRCUIT
L1
L3
L2
Q1
F1
F1
KM
KA
KM
KA
KS
KA
A1
T1
T2
A3
KS
180 s
HP
T3
A2
TH
LP
KS
M
DGT
KM
FRCC.PC.004.A4.02
KA
LLSV
KS
15
Application guidelines
Wiring diagram without
pump-down cycle
CONTROL CIRCUIT
L1
L3
L2
Q1
F1
F1
KM
KA
KA
KS
KA
A1
T2
T1
A3
HP
180 s
A2
T3
LP
KS
TH
M
DGT
KM
Soft starters
KS
KA
Starting current of Maneurop 3-phase compressors can be reduced by using a soft starter. Two
dierent versions are available: CI-tronicTM soft
starters type MCI (recommended) and soft start
kits with statoric resistors type SCR. The starting
current can be reduced by up to 50% depending on the compressor model and the type of
soft starter. Also mechanical stresses that occur
at starting are reduced which increases the life of
the internal components.
IP rating
Nominal voltage
208-230 V / 1 ph / 60 Hz
187 - 253 V
200-230 V / 3 ph / 60 Hz
180 - 253 V
380-400 V / 3 ph / 50 Hz
340 - 440 V
460 V / 3 ph / 60 Hz
414 - 506 V
230 V / 1 ph / 50 Hz
207 - 253 V
230 V / 3 ph / 50 Hz
207 - 253 V
500 V / 3 ph / 50 Hz
450 - 550 V
575 V / 3 ph / 60 Hz
517 - 632 V
380 V / 3 ph / 60 Hz
342 - 418 V
The compressor terminal boxes IP rating according to CEI 529 are shown on the outline drawings
section.
IP
16
FRCC.PC.004.A4.02
Application guidelines
General information
Refrigerant
Type
Lubricant
type
Compressor
type
Danfoss lubricant
Application
R22
HCFC
Mineral
MT
R407C
HFC
Polyolester
MTZ
R134a
HFC
Polyolester
MTZ
R404A
HFC
Polyolester
MTZ
Medium temperature
R507A
HFC
Polyolester
MTZ
Medium temperature
Alkylbenzene
(ABM)
MT
Transitional
refrigerants,
R22 based
Hydrocarbons
Danfoss does not authorise the use of hydrocarbons in Maneurop MT/MTZ compressors
R22
R407C
Refrigerant R407C is an HFC refrigerant with similar thermodynamic properties to those of R22.
FRCC.PC.004.A4.02
17
Application guidelines
R134a
ture. For more information refer to section zeotropic refrigerant mixtures. For low evaporating
temperature applications down to -45C, Maneurop NTZ compressors should be used. Refer to
the NTZ selection and application guidelines. For
medium temperature R404A applications, always
use the Maneurop MTZ compressor with 160PZ
polyolester oil which is supplied with the MTZ
compressor.
A wide variety of R22 based transitional refrigerants exist (also called service refrigerants or dropin blends). These were developed as temporary
R12 or R502 alternatives. Some examples are
R401A, R401B, R409A and R409B as R12 alternatives and R402A, R402B, R403A and R403B as R502
Hydrocarbons
R404A
R507A
18
FRCC.PC.004.A4.02
Application guidelines
Piping design
Oil in a refrigeration circuit is required to lubricate moving parts in the compressor. During
normal system operation small oil quantities
will continuously leave the compressor, with the
discharge gas. With good system piping design
this oil will return to the compressor. As long as
the amount of oil circulating through the system
is small it will contribute to good system operation and improved heat transfer eciency. However, too large amounts of oil in the system will
have a negative eect on condenser and evaporator eciency. If, in a poorly designed system,
Suction lines
For compressors mounted in parallel, the common suction riser should be designed as a double
riser. Also refer to the News bulletin "Mounting
instructions for installation of Maneurop compressors in parallel " and " Parallel application
guidelines".
Gas velocities higher than 12 m/s will not contribute to signicantly better oil return. However they
Note that the suction rotolock valves, which can
be ordered from Danfoss as accessories, are designed for average pipe sizes, selected for systems running at nominal conditions.
Discharge line
FRCC.PC.004.A4.02
When the condenser is mounted above the compressor, a loop above the condenser and a U-trap
close to the compressor are required to prevent
liquid draining from the condenser into the discharge line during standstill.
19
Application guidelines
Filter driers
The drier is to be oversized rather than undersized. When selecting a drier, always take into
account its capacity (water content capacity), the
system refrigerating capacity and the system refrigerant charge.
Operating limits
High pressure
Low pressure
20
MT
R22
MTZ
R407C
MTZ
R134a
MTZ
R404A / R507A
bar (g)
25
25
25
25
bar (g)
10.9 - 27.7
12.5 - 29.4
7.9 - 22.6
13.2 - 27.7
bar (g)
1.0 - 7.0
1.4 - 6.6
0.6 - 4.7
1.0 - 7.2
bar (g)
30
30
30
30
bar (g)
At low ambient temperatures, the condensing temperature and condensing pressure in air
cooled condensers will decrease.
Other problems can also occur when the compressor is operating at low ambient temperature.
During shut down periods, liquid refrigerant can
migrate to a cold compressor.
For such conditions a belt-type crankcase heater
is strongly recommended.
Note that with 100% suction gas cooled motors,
Maneurop compressors can be externally insulated.
Refer to section "Liquid refrigerant migration &
charge limits" for more details.
FRCC.PC.004.A4.02
Application guidelines
The operating voltage limits are shown in the table on page 4. The voltage applied to the motor
terminals must always be within these table limits. The maximum allowable voltage unbalance
for 3-phase compressors is 2%. Voltage unbalance
% voltage unbalance:
x 100
O-cycle migration
21
Application guidelines
in extreme situations with high system refrigerant charge and large amounts of oodback, liquid
slugging could occur.
In heat pumps, change over from cooling to heating cycles, defrost and low load short cycles may
lead to liquid refrigerant oodback or saturated
refrigerant return conditions.
Crankcase heater
Under extreme conditions such as very low ambient temperature a belt type crankcase heater
could be used in addition to the PTC heater, although this is not a preferred solution for 1 and 2
cylinder compressors. The belt crankcase heater
must be positioned on the compressor shell as
close as possible to the oil sump to ensure good
heat transfer to the oil.
Liquid line solenoid valve &
pump-down
Suction accumulator
In refrigeration applications, the Liquid Line Solenoid Valve (LLSV) is highly recommended. During
the o-cycle, the LLSV isolates the liquid charge
in the condenser side, thus preventing against
refrigerant transfer or excessive migration of refrigerant into the compressor. Furthermore, when
using a LLSV in conjunction with a pump-down
cycle, the quantity of refrigerant in the low-pressure side of the system will be reduced.
A suction accumulator shall not be used in systems with zeotropic refrigerant mixtures.
22
FRCC.PC.004.A4.02
Application guidelines
Sound
Because Maneurop compressors are 100% suction gas cooled, and require no body cooling,
they can be insulated. Values for the sound reduction achieved with acoustic hoods are shown
also in the table on the right. For inside mounted
compressors, sound insulation of the plantroom
is an alternative to sound insulation of the compressor.
Sound transmitted by mounting feet, pipework
and refrigerant should be treated the same way
as for vibration. Please refer to the next section.
Sound power level at 60 Hz
dB(A)
without hood
with hood*
without hood
with hood*
MTZ018
73
65
73
66
MTZ022
74
68
77
71
MTZ028
71
64
73
66
MTZ032
71
64
73
66
MTZ036
70
64
76
69
MTZ040
70
65
72
67
MTZ044
80
74
82
76
MTZ045
80
74
82
76
MTZ050
83
76
84
78
MTZ051
83
76
84
78
MTZ056
81
74
81
74
MTZ057
81
74
81
74
MTZ064
80
74
84
78
MTZ065
80
74
84
78
MTZ072
79
72
82
75
MTZ073
79
72
82
75
MTZ080
79
73
84
78
MTZ081
79
73
84
78
MTZ100
85
79
87
81
MTZ125
84
78
86
80
MTZ144
83
77
86
80
MTZ160
83
77
86
80
Acoustic hood
accessory
7755001
7755002
7755003
Vibration
The mounting grommets delivered with the compressor should always be used. They reduce the
vibration transmitted by the compressor mounting feet to the base frame.
The base on which the compressor is mounted
should be suciently rigid and of adequate mass
to ensure the full eectiveness of the mounting
grommets.
The compressor should never be directly mounted to the base frame without the grommets, otherwise high vibration transmission would occur
and the compressor service life reduced. Suction
and discharge lines must have adequate exibility in 3 planes. Eventually vibration absorbers may
be required.
FRCC.PC.004.A4.02
Care must be taken to avoid tubing having resonant frequencies close to those of the compressor
frequency.
Vibration is also transmitted by the refrigerant
gas. Maneurop compressors have built in mufers to reduce this vibration.
To further reduce vibration an extra muer can
be installed.
Note: Maneurop MT & MTZ compressors have
been designed and qualied for stationary equipment used in A/C and Refrigeration applications.
Danfoss doesnt warrant these compressors for
use in mobile applications, such as trucks, railways, subways, etc...
23
Application guidelines
System cleanliness
Compressor handling,
mounting and connection to
the system
Compressor handling
Compressor mounting
Maneurop MT and MTZ compressors are provided with a lifting lug. This lug should always be
used to lift the compressor. Once the compressor
is installed, the compressor lifting lug should nev-
These grommets largely attenuate the compressor vibration transmitted to the base frame. The
compressor must always be mounted with these
grommets. Refer to the table below for torque
values.
Designation
Cable screw of T connector in electrical box
1"
80
1"1/4
90
24
1"3/4
110
1 - 2 - 4 cylinder
15
50
1 - 2 - 4 cylinder
30
FRCC.PC.004.A4.02
Application guidelines
It is recommended that an inert gas such as nitrogen be used for pressure testing. Dry air may
also be used but care should be taken since it can
form an inammable mixture with the compressor oil. When performing a system pressure test,
the maximum allowed pressure for the dierent
components should not be exceeded.
For MT/MTZ compressors the maximum test pressures are shown in the table beside.
Leak detection
FRCC.PC.004.A4.02
1-2-4 cylinder
compressors
Maximum compressor test pressure,
low side
25 bar(g)
30 bar(g)
Do not exceed 30 bar pressure dierence between high pressure side and low pressure side of
the compressor because this will open the internal compressor relief valve.
25
Application guidelines
Start-up
Refrigerant charging
The oil charge must be checked before commissioning (1/4 to 3/4 of the oil sight glass). Check the
oil level again after a minimum of 2 hours operation at nominal conditions. In most installations
the initial compressor oil charge will be sucient.
In installations with line runs exceeding 20 m or
with many oil traps or an oil separator, additional
oil may be required. Normally the quantity of oil
added should be no more than 2% of the total
refrigerant charge (this percentage does not take
into account oil contained in accessories such
26
FRCC.PC.004.A4.02
Application guidelines
Packaging
Single pack
4 cylinders
2 cylinders
1 cylinder
Model
Dimensions
(mm)
Gross
weight
(kg)
Multipack
Nbr
Dimensions
(mm)
Gross
weight
(kg)
Industrial pack
Static
stacking
Nbr
Dimensions
(mm)
Gross
weight
(kg)
MT/MTZ 018
23
197
278
MT/MTZ 022
23
197
278
l: 330
w: 295
h: 385
MT/MTZ 028
MT/MTZ 032
25
8
26
l: 1150
w: 800
h: 510
213
4
12
221
l: 1150
w: 800
h: 500
302
4
314
MT/MTZ 036
27
229
326
MT/MTZ 040
27
229
326
MT/MTZ 044-050
37
232
224
MT/MTZ 045-051
39
244
236
MT/MTZ 056-064
MT/MTZ 057-065
l: 395
w: 365
h: 455
39
6
41
l: 1150
w: 800
h: 600
244
4
256
l: 1150
w: 800
h: 600
236
4
248
MT/MTZ 072-080
42
262
254
MT/MTZ 073-081
43
268
260
MT/MTZ 100
70
291
381
MT/MTZ 125
MT/MTZ 144
MT/MTZ 160
l: 570
w: 400
h: 670
73
4
76
78
l: 1150
w: 800
h: 820
303
4
315
323
l: 1150
w: 800
h: 710
399
4
417
429
Single pack:
Multipack:
A full pallet of compressors, each individually packed in a cardboard box. Mainly dedicated to wholesalers and Danfoss
distribution centers.
Industrial pack:
Nbr:
FRCC.PC.004.A4.02
Static
stacking
27
Application guidelines
R22
Compressor
model
Design1)
1
208-230/1/60
3
200-230/3/60
S
MT18-3M
VE
MT18-1VM
MT18-3VM
S
MT22-1M
MT22-3M
MT022
VE
MT22-1VM
MT22-3VM
S
MT28-1M
MT28-3M
MT028
VE
MT28-1VM
MT28-3VM
S
MT32-3M
MT032
VE
MT32-1VM
MT32-3VM
S
MT36-3M
MT036
VE
MT36-1VM
MT36-3VM
S
MT40-1M
MT40-3M
MT040
VE
MT40-1VM
MT40-3VM
S
MT44-1M
MT44-3M
MT044
VE
MT44-1VM
MT44-3VM
S
MT045
VE
MT45-3VM
S
MT50-3M
MT050
VE
MT50-1VM
MT50-3VM
S
MT51-3M
MT051
VE
MT51-3VM
S
MT56-3M
MT056
VE
MT56-1VM
MT56-3VM
S
MT057
VE
MT57-3VM
S
MT64-3M
MT064
VE
MT64-1VM
MT64-3VM
S
MT65-3M
MT065
VE
MT65-3VM
S
MT72-3M
MT072
VE
MT72-3VM
S
MT73-3M
MT073
VE
MT73-3VM
S
MT080
VE
MT80-3VM
S
MT081
VE
MT81-3VM
Sv
MT100-3M
MT100
VE
MT100-3VM
Sv
MT125-3M
MT125
VE
MT125-3VM
Sv
MT144-3M
MT144
VE
MT144-3VM
Sv
MT160-3M
MT160
VE
MT160-3VM
1
) S = Single compressor, no oil sight glass, no oil equalisation connection
SV = Single compressor, welded oil sight glass, no oil equalisation connection
VE = Single compressor, threaded oil sight glass, 3/8" oil equalisation connection
MT018
28
Code no.
4
460/3/60
400/3/50
230/1/50
380/3/60
MT18-4M
MT18-4VM
MT22-4M
MT22-4VM
MT28-4M
MT28-4VM
MT32-4M
MT32-4VM
MT36-4M
MT36-4VM
MT40-4M
MT40-4VM
MT44-4M
MT44-4VM
MT45-4M
MT45-4VM
MT50-4M
MT50-4VM
MT51-4M
MT51-4VM
MT56-4M
MT56-4VM
MT57-4M
MT57-4VM
MT64-4M
MT64-4VM
MT65-4M
MT65-4VM
MT72-4M
MT72-4VM
MT73-4M
MT73-4VM
MT80-4M
MT80-4VM
MT81-4M
MT81-4VM
MT100-4M
MT100-4VM
MT125-4M
MT125-4VM
MT144-4M
MT144-4VM
MT160-4M
MT160-4VM
MT18-5M
MT18-5VM
MT22-5M
MT22-5VM
MT28-5M
MT28-5VM
MT32-5M
MT32-5VM
MT36-5M
MT36-5VM
MT50-5VM
-
MT22-9VM
MT28-9VM
MT32-9VM
MT36-9VM
MT44-9M
MT44-9VM
MT50-9M
MT50-9VM
MT56-9M
MT56-9VM
MT64-9M
MT64-9VM
MT72-9M
MT72-9VM
MT80-9M
MT80-9VM
MT100-9M
MT100-9VM
MT125-9VM
MT125-9VM
MT144-9M
MT144-9VM
MT160-9M
MT160-9VM
FRCC.PC.004.A4.02
Application guidelines
R22
Compressor
model
MT018
MT022
MT028
MT032
MT036
MT040
MT044
MT045
MT050
MT051
MT056
MT057
MT064
MT065
MT072
MT073
MT080
MT081
MT100
MT125
MT144
MT160
Design1)
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
208-230/1/60
200-230/3/60
460/3/60
400/3/50
MT18-1VI
MT22-1VI
MT28-1VI
MT32-1VI
MT36-1VI
MT40-1VI
MT44-1VI
MT50-1VI
MT56-1VI
MT64-1VI
-
MT18-3VI
MT22-3VI
MT28-3VI
MT32-3VI
MT36-3VI
MT40-3VI
MT44-3VI
MT45-3VI
MT50-3VI
MT51-3VI
MT56-3VI
MT57-3VI
MT64-3VI
MT65-3VI
MT72-3VI
MT73-3VI
MT80-3VI
MT81-3VI
MT100-3VI
MT125-3VI
MT144-3VI
MT160-3VI
MT18-4VI
MT22-4VI
MT28-4VI
MT32-4VI
MT36-4VI
MT40-4VI
MT44-4VI
MT45-4VI
MT50-4VI
MT51-4VI
MT56-4VI
MT57-4VI
MT64-4VI
MT65-4VI
MT72-4VI
MT73-4VI
MT80-4VI
MT81-4VI
MT100-4VI
MT125-4VI
MT144-4VI
MT160-4VI
Code no.
5
230/1/50
230/3/50
575/3/60
500/3/50
380/3/60
MT18-5VI
MT22-5VI
MT28-5VI
MT32-5VI
MT36-5VI
MT50-5VI
-
MT22-6VI
MT28-6VI
MT32-6VI
MT36-6VI
MT40-6VI
MT44-6VI
MT50-6VI
MT56-6VI
MT64-6VI
MT72-6VI
MT80-6VI
MT100-6VI
MT125-6VI
MT144-6VI
MT160-6VI
MT44-7VI
MT50-7VI
MT56-7VI
MT100-7VI
MT125-7VI
MT144-7VI
MT160-7VI
MT22-9VI
MT28-9VI
MT32-9VI
MT36-9VI
MT44-9VI
MT50-9VI
MT56-9VI
MT64-9VI
MT72-9VI
MT80-9VI
MT100-9VI
MT125-9VI
MT144-9VI
MT160-9VI
) VE = Single compressor, threaded oil sight glass, 3/8" oil equalisation connection
FRCC.PC.004.A4.02
29
Application guidelines
Compressor
model
Design1)
1
208-230/1/60
3
200-230/3/60
MTZ18-1M
MTZ18-3M
MTZ18-1VM
MTZ18-3VM
MTZ22-1M
MTZ22-3M
MTZ022
MTZ22-1VM
MTZ22-3VM
MTZ28-1M
MTZ28-3M
MTZ028
MTZ28-1VM
MTZ28-3VM
MTZ32-1M
MTZ32-3M
MTZ032
MTZ32-1VM
MTZ32-3VM
MTZ36-1M
MTZ36-3M
MTZ036
MTZ36-1VM
MTZ36-3VM
MTZ40-1M
MTZ40-3M
MTZ040
MTZ40-1VM
MTZ40-3VM
MTZ44-3M
MTZ044
MTZ44-1VM
MTZ44-3VM
MTZ045
MTZ45-3VM
MTZ50-3M
MTZ050
MTZ50-1VM
MTZ50-3VM
MTZ051
MTZ51-3VM
MTZ56-3M
MTZ056
MTZ56-1VM
MTZ56-3VM
MTZ057
MTZ57-3VM
MTZ64-3M
MTZ064
MTZ64-1VM
MTZ64-3VM
MTZ065
MTZ65-3VM
MTZ72-3M
MTZ072
MTZ72-3VM
MTZ073
MTZ73-3VM
MTZ080
MTZ80-3VM
MTZ081
MTZ81-3VM
MTZ100-3M
MTZ100
MTZ100-3VM
MTZ125-3M
MTZ125
MTZ125-3VM
MTZ144-3M
MTZ144
MTZ144-3VM
MTZ160-3M
MTZ160
VE
MTZ160-3VM
1
) S = Single compressor, no oil sight glass, no oil equalisation connection
Sv = Single compressor, welded oil sight glass, no oil equalisation connection
VE = Single compressor, threaded oil sight glass, 3/8" oil equalisation connection
MTZ018
30
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
S
VE
Sv
VE
Sv
VE
Sv
VE
Sv
460/3/60
400/3/50
230/1/50
380/3/60
MTZ18-4M
MTZ18-4VM
MTZ22-4M
MTZ22-4VM
MTZ28-4M
MTZ28-4VM
MTZ32-4M
MTZ32-4VM
MTZ36-4M
MTZ36-4VM
MTZ40-4M
MTZ40-4VM
MTZ44-4M
MTZ44-4VM
MTZ45-4M
MTZ45-4VM
MTZ50-4M
MTZ50-4VM
MTZ51-4M
MTZ51-4VM
MTZ56-4M
MTZ56-4VM
MTZ57-4M
MTZ57-4VM
MTZ64-4M
MTZ64-4VM
MTZ65-4M
MTZ65-4VM
MTZ72-4M
MTZ72-4VM
MTZ73-4M
MTZ73-4VM
MTZ80-4M
MTZ80-4VM
MTZ81-4M
MTZ81-4VM
MTZ100-4M
MTZ100-4VM
MTZ125-4M
MTZ125-4VM
MTZ144-4M
MTZ144-4VM
MTZ160-4M
MTZ160-4VM
MTZ18-5M
MTZ18-5VM
MTZ22-5M
MTZ22-5VM
MTZ28-5M
MTZ28-5VM
MTZ32-5M
MTZ32-5VM
MTZ36-5M
MTZ36-5VM
MTZ50-5VM
-
MTZ22-9VM
MTZ28-9VM
MTZ32-9VM
MTZ36-9VM
MTZ44-9M
MTZ44-9VM
MTZ50-9M
MTZ50-9VM
MTZ56-9M
MTZ56-9VM
MTZ64-9M
MTZ64-9VM
MTZ72-9M
MTZ72-9VM
MTZ80-9M
MTZ80-9VM
MTZ100-9M
MTZ100-9VM
MTZ125-9M
MTZ125-9VM
MTZ144-9M
MTZ144-9VM
MTZ160-9M
MTZ160-9VM
FRCC.PC.004.A4.02
Application guidelines
Compressor
model
MTZ018
MTZ022
MTZ028
MTZ032
MTZ036
MTZ040
MTZ044
MTZ045
MTZ050
MTZ051
MTZ056
MTZ057
MTZ064
MTZ065
MTZ072
MTZ073
MTZ080
MTZ081
MTZ100
MTZ125
MTZ144
MTZ160
Design1)
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
VE
208-230/1/60
200-230/3/60
460/3/60
400/3/50
MTZ18-1VI
MTZ22-1VI
MTZ28-1VI
MTZ32-1VI
MTZ36-1VI
MTZ40-1VI
MTZ44-1VI
MTZ50-1VI
MTZ56-1VI
MTZ64-1VI
-
MTZ18-3VI
MTZ22-3VI
MTZ28-3VI
MTZ32-3VI
MTZ36-3VI
MTZ40-3VI
MTZ44-3VI
MTZ45-3VI
MTZ50-3VI
MTZ51-3VI
MTZ56-3VI
MTZ57-3VI
MTZ64-3VI
MTZ65-3VI
MTZ72-3VI
MTZ73-3VI
MTZ80-3VI
MTZ81-3VI
MTZ100-3VI
MTZ125-3VI
MTZ144-3VI
MTZ160-3VI
MTZ18-4VI
MTZ22-4VI
MTZ28-4VI
MTZ32-4VI
MTZ36-4VI
MTZ40-4VI
MTZ44-4VI
MTZ45-4VI
MTZ50-4VI
MTZ51-4VI
MTZ56-4VI
MTZ57-4VI
MTZ64-4VI
MTZ65-4VI
MTZ72-4VI
MTZ73-4VI
MTZ80-4VI
MTZ81-4VI
MTZ100-4VI
MTZ125-4VI
MTZ144-4VI
MTZ160-4VI
Code no.
5
230/1/50
230/3/50
575/3/60
500/3/50
380/3/60
MTZ18-5VI
MTZ22-5VI
MTZ28-5VI
MTZ32-5VI
MTZ36-5VI
MTZ50-5VI
-
MTZ22-6VI
MTZ28-6VI
MTZ32-6VI
MTZ36-6VI
MTZ40-6VI
MTZ44-6VI
MTZ50-6VI
MTZ56-6VI
MTZ64-6VI
MTZ72-6VI
MTZ80-6VI
MTZ100-6VI
MTZ125-6VI
MTZ144-6VI
MTZ160-6VI
MTZ32-7VI
MTZ36-7VI
MTZ44-7VI
MTZ50-7VI
MTZ56-7VI
MTZ100-7VI
MTZ125-7VI
MTZ144-7VI
MTZ160-7VI
MTZ22-9VI
MTZ28-9VI
MTZ32-9VI
MTZ36-9VI
MTZ44-9VI
MTZ50-9VI
MTZ56-9VI
MTZ64-9VI
MTZ72-9VI
MTZ80-9VI
MTZ100-9VI
MTZ125-9VI
MTZ144-9VI
MTZ160-9VI
) VE = Single compressor, threaded oil sight glass, 3/8" oil equalisation connection
FRCC.PC.004.A4.02
31
Controls for
Commercial Refrigeration
Controls for
Industrial Refrigeration
Industrial Automation
Household Compressors
Commercial Compressors
Sub-Assemblies
Thermostats
Brazed plate
heat exchanger
We are oering a single source for one of the widest ranges of innovative refrigeration and air
conditioning components and systems in the world. And, we back technical
solutions with business solution to help your company reduce costs,
streamline processes and achieve your business goals.
Danfoss A/S www.danfoss.com