11IPST060
11IPST060
Travelling Waves
F. V. Lopes, Student Member, IEEE, D. Fernandes Jr., Member, IEEE, W. L. A. Neves, Member, IEEE
I. INTRODUCTION
(a)
Where:
t11 is the initial transient instant at Bus 1;
t21 is the initial transient instant at Bus 2;
t12 is the arrival instant of the reflected wave at Bus 1;
t22, t23 are the arrival instants of reflected waves at Bus 2;
t22r is the arrival instant of the refracted wave at Bus 1;
l is the line length;
d is the distance to the fault point.
The t21r instant was left off in Fig. 1 to simplify the diagram.
It is important to know that fault location algorithms consist on
two main steps the transient detection and the fault point
location. For the first step, considering double ended methods,
(b)
Fig. 2. Parks Transformation (Tdq0) application: (a) Electrical machine
researches; (b) Transient detection and fault location.
V d (i ) V d (i 1) .
t
(2)
Where:
Vd is the direct axis component;
i is the sample number;
t is the time step.
In the literature, difference quantities are widely used in
protective relaying algorithms [10]. In this work, [cdif]2 will be
used to detect de initial transient instants in monitored
terminals. [cdif]2 makes the transient detection more robust
because coefficient related to transient signals are amplified
and coefficients related to normal conditions of the system are
kept with low magnitude. An example of transient detection
using Tdq0 is shown in Fig. 3.
x 10
(a)
Three-phase
Voltage Signal (V)
2
PhaseA
1
PhaseB
PhaseC
-1
(b)
Direct Axis Componente - V d (p.u.)
-2
0.8
0.9
1.1
1.2
1.3
1.4
Sample Number
1.5
1.6
1.7
1.8
4
x 10
0.5
-0.5
0.8
0.9
1.1
1.2
1.3
1.4
Sample Number
1.5
1.2
1.3
1.4
Sample Number
1.5
1.6
1.7
1.8
4
x 10
(c)
Difference Coefficients
c dif (p.u.)
x 10
3
2
1
0
-1
(d)
Square of the Difference Coefficients
[c dif ]2
0.8
0.9
1.1
1.6
1.7
1.8
10
0
0.9
1.1
1.2
1.3
1.4
Sample Number
1
2
2
1
3
0
1
1
3
2 V A
.
1 V B
2
3 V C
2
1
2
2
(3)
x 10
x 10
0.8
V 0
V =
V
1.5
1.6
1.7
1.8
4
x 10
Fig. 3. Transient detection from a double phase to ground fault using Tdq0:
(a) Three-phase voltage signal; (b) Direct axis component Vd; (c) Difference
coefficients cdif; (d) Square of the difference coefficients [cdif]2.
(4)
Where:
is the angular power frequency;
t is the DFRs clock synchronized by GPS;
is the angle between Vd and the voltage phasor at phase A
(see Fig. 2b).
(a)
Three-phase
Voltage Signal - Bus 1 (V)
x 10
2
PhaseA
PhaseB
PhaseC
-1
-2
0.9
0.95
1.05
1.1
1.15
1.2
Sample Number
1.25
1.3
1.35
1.4
4
x 10
(b)
Three-phase
Voltage Signal - Bus 2 (V)
x 10
2
PhaseA
PhaseB
PhaseC
-1
-2
0.9
0.95
1.05
1.1
1.15
1.2
Sample Number
1.25
1.3
1.35
1.4
4
x 10
(c)
[cdif ] 2 coefficients - Bus 1
x 10
t11
Initial transient
instants detection
4
2
0
0.9
0.95
7
(d)
[cdif ] 2 coefficients - Bus 2
x 10
1.05
1.1
1.15
1.2
Sample Number
1.25
1.1
1.15
1.2
Sample Number
1.25
1.3
1.35
1.4
4
x 10
t21
8
6
4
2
0
0.9
0.95
1.05
1.3
1.35
1.4
4
x 10
V. SIMULATION STUDIES
A. Simulation Model
Fig. 4. Detection of the initial transient instants through the [cdif]2 analysis.
If [c dif ( i ) ]2 = 0 t transient = {} ;
If c dif (i )
> 0 t transient = (i 1) F s ;
Where:
ttransient is the initial transient instant in seconds;
cdif is the difference coefficients calculated from Vd;
i is the sample number.
(5a)
(5b)
TABLE II
FAULT LOCATION SIMULATIONS FOR TRANSPOSED TRANSMISSION LINE
No of simulated
cases
960
Fault
type
AG
R0 = 1,445
G1
G2
= 1,445
G2
= 13,996 mH
G2
= 1,963
Z + = 0,054 + j0,527 km
= 14,982 mH
Y+
R0
G1
= 13,996 mH
L0
R+
G1
= 1,963
R+
L+
G1
= 14,982 mH
L0
L+
TRANSMISSION LINE
l = 500 km
Z0 = 0,236 + j1,035 km
G2
Y0
shunt
shunt
= 2,49 mho / km
960
960
960
960
960
960
960
960
960
9600
Reliable
simulations (%)
98.85%
949
949
960
960
960
960
960
960
960
9567
98.85%
98.85%
100.00%
100.00%
100.00%
100.00%
100.00%
100.00%
100.00%
99.66%
= 3,144 mho / km
B. Applied Disturbances
For validation purposes, situations where the transmission
line is transposed and untransposed were analyzed. For each
type of transposition scheme, 9600 different cases were run,
totaling 19200 different cases in which fault parameters were
changed: the fault resistance (5 to 95 with steps of 30 ),
the fault inception angle (0 to 180 with steps of 20) and the
distance from fault point to Bus 1 (20 km to 480 km with steps
of 20 km). Digital simulations were performed for phase to
ground, double phase, double phase to ground and three-phase
faults. The most adverse cases were considered, as high fault
resistance cases, fault inception angle near to zero (or at zero
crossing) and faults very close to the substations.
To perform such a high quantity of simulations, batch files
were created with Matlab to allow the automatic run of the
ATP files.
C. Simulation Results and Analysis
As shown in Table II and Table III, all results show the
reliability of the fault location method. It is important to point
out that the maximum expected error is a function of the
sampling rates, i.e., it is a hardware limitation. The travel time
of waves is not interpolated and, thus, the initial transient
instants are approximated to the nearly multiple of the time
step t used by DFRs. In this way, errors in the order of a half
time step can be introduced in the calculated initial transient
instants and are considered to be admissible errors. So, the
module of such admissible errors is calculated using (6).
e ( t c ) 2
BG
CG
AB
BC
CA
ABG
BCG
CAG
ABC
Total:
No of reliable
simulations
949
TABLE III
FAULT LOCATION SIMULATIONS FOR UNTRANSPOSED TRANSMISSION LINE
BG
CG
AB
BC
CA
ABG
BCG
CAG
ABC
Total:
960
960
960
960
960
960
960
960
960
9600
No of reliable
simulations
944
Reliable
simulations (%)
98.33%
947
950
954
960
954
955
960
959
960
9543
98.65%
98.96%
99.38%
100.00%
99.38%
99.48%
100.00%
99.90%
100.00%
99.41%
(6)
Where:
c is the speed of light ( 3.105 km/s).
No of simulated
cases
960
Fault
type
AG
TABLE IV
GENERAL RESULTS OF FAULT LOCATION SIMULATIONS
Considered
system
Transposed
Untransposed
Total:
No of
simulated
cases
9600
No of
unreliable
simulations
33
No of
reliable
simulations
9567
Reliable
simulations
(%)
99.66%
9600
57
9543
99.41%
19200
90
19110
99.53%
TABLE V
ANALYSIS OF UNRELIABLE SIMULATION RESULTS
Considered system
Case analysis
No of unreliable
simulations
No of cases related to
high impedance fault
(>60 )
No of cases related to fault
inception angle nearly to
zero crossing (< 10)
No of cases related to
unknown reasons
Transp.
Untransp.
Total:
33
(100.00%)
22
(66.67%)
57
(100.00%)
41
(71.93%)
90
(100.00%)
63
(70.00%)
0
(0.00%)
6
(10.53%)
6
(6.67%)
11
(33.33%)
10
(17.54%)
21
(23.33%)
FP
(km)
Fs=20 kHz
FL
(km)
Fs=100 kHz
(km)
FL
(km)
(km)
[2]
[3]
[4]
Fs=500 kHz
FL
(km)
(km)
AG
28
23.30
-4.70
27.69
-0.31
28.27
0.27
BG
78
81.80
3.80
77.41
-0.59
78.29
0.29
CG
129
125.68
-3.32
130.07
1.07
129.19
0.19
AB
166
169.56
3.56
165.17
-0.83
166.05
0.05
BC
205
198.81
-6.19
204.66
-0.34
204.95
-0.05
CA
244
242.69
-1.31
244.15
0.15
243.86
-0.14
ABG
311
315.82
4.82
311.43
0.43
310.84
-0.16
BCG
393
388.95
-4.05
393.33
0.33
392.75
-0.25
CAG
432
432.82
0.82
431.36
-0.64
431.65
-0.35
ABC
472
476.70
4.70
472.31
0.31
471.73
-0.27
[5]
[6]
[7]
[8]
VI. CONCLUSIONS
In this paper an approach for fault location on transmission
lines monitored in two terminals was presented. Only the
current voltage samples are used to detect transients and all
three phases are monitored by the direct axis voltage signal Vd
obtained through Parks transformation (Tdq0). The method
automatically determines the fault location point immediately
after the fault occurrence.
[10]
[11]
[12]
[13]