Escalator Load Test On Initial Inspection
Escalator Load Test On Initial Inspection
Safety Division
Ref. No.:
59/88
Date:
DIRECTORS RULING
Rev. No.:
Date:
March 31/88
Subject:
Sent to:
INTRODUCTION
With Ruling #49/87/REV.A of June 24, 1987, you were informed that starting October 1, 1987, no initial
inspection of a new escalator shall start unless that escalator type was subject to the testing and certification
process, in accordance with clause 8.5 of CAN3-B44-M85, Elevator Safety Code.
We have recently been approached by an escalator manufacturer asking if a number of escalators could be
inspected and licensed before the certification by a testing laboratory is completed.
Whilst the code requires type testing of several elevator components because their performance (e.g. free
fail) or reliability (e.g. 100,000 cycles) cannot be tested during an initial inspection, we understand that the
type testing requirement for escalator braking systems is introduced in the code for a different reason. The
intent, as we understand, was to avoid inconvenience of performing full load tests on the initial inspection
of every escalator, even though such tests could prove safety performance of escalator brakes.
PROCEDURE FOR TESTING ESCALATOR BRAKES (Where No Type Test Certificate Is Available)
3.1
3.2
Further information may be obtained by contacting: Director - ED/AD Division, Technical Standards and Safety Authority,
4th Floor West Tower, 3300 Bloor St. West, Etobicoke ON., M8X 2X4 Ph:416 325 2000 Fx:416 326 8248
ED-059-88.doc 1/2
3.3
Testing equipment
a) Provide calibrated test weights necessary for loading in accordance with item 32. of spec sheet.
b) Install an auxiliary device (connected in the stop button circuit), which will automatically interrupt the
power to the machine and brake when an index (M) marked on a step reaches a predetermined
reference point (P), marked on the skirt, while the escalator is travelling down.
c) The stopping distances (between M and P) shall be measured by the movement of a step along its path
of travel after the auxiliary device has initiated the stop.
3.4
Tests
a) No-load running tests
Run empty escalator in down direction and arrange that the auxiliary device initiates
stopping when index M reaches point P. Carry out at least 3 tests and measure stopping distance
(DN). Installing contractor shall specify minimum "cooling-down" interval between tests. The
shortest of the recorded distance (DN min.) must be equal to or greater than that shown in item
49.3 of the spec sheet (also see 3.1.b above). The longest recorded distance (DN max.) must not
exceed DN min. for more than 10%.
b) Static load test
Load escalator steps (steps on incline only) with "stopped brake rated load" specified in item 32 of
spec sheet (clause 8.3.9.3(a) of B44). Check that there is no movement of steps.
c) Rated-load running test
Load escalator with "Running brake rated load" specified in item 32 of spec sheet (clause 8.3.9.3(b)
of B44).
The load must be placed on the incline portion of escalator steps (equally distributed or
concentrated on the upper steps).
Run the loaded escalator in down direction and arrange that the auxiliary device initiates stopping
when index M reaches reference point P.
Carry out at least 3 tests and measure stopping distance (DR). The installing contractor shall
specify the minimum "cooling down" interval between tests.
The longest recorded distance (DR max.) must not exceed the shortest distance (DR min.) by more
than 10%, and must be equal to or less than entry in item 49.4.
3.5
Readjustments
If any test results prove non-conformance with the above requirements, the escalator will not be licensed.
If any readjustment is carried out during the test, e.g. the initial torque setting (see 3.2(b) above) tests shall
be repeated and a revised specification sheet shall be submitted for registration.
3.6
Data plate
A plate must be affixed in conformance with clause 8.5.3.1 of B44, containing data corresponding to items
49.1 to 3 of spec sheet, as verified by the tests.
3.7
Further information may be obtained by contacting: Director - ED/AD Division, Technical Standards and Safety Authority,
4th Floor West Tower, 3300 Bloor St. West, Etobicoke ON., M8X 2X4 Ph:416 325 2000 Fx:416 326 8248
ED-059-88.doc 2/2