Manual Varlogic NRC12

Download as pdf or txt
Download as pdf or txt
You are on page 1of 44

Varlogic NRC12

Power factor controller

User manual

Power Factor Controller NRC12

USERS MANUAL

Menu Structure

First Startup

Startup after preconfiguration

Language selection
Main Menu

BANK PRECONF
AUTO SETUP
MANUAL SETUP
MEASUREMENTS
PARAMETERS
ALARMS
MAINTENANCE

E
K

E
K

Language selection
Main Menu

COMMISSIONING
AUTO SETUP
MANUAL SETUP
MEASUREMENTS
PARAMETERS
ALARMS
MAINTENANCE

BANK PRECONF

COMMISSIONING

AUTO SETUP

MANUAL SETUP

Language
Application
Input Voltage
Wiring
Target Cos
Delays
Step Program
Step Setup

Language
Transformers
Target Cos
Verify

Transformers
Input Voltage
Target Cos
Search

Application
Transformers
Input Voltage
Wiring
Target Cos
Resp Values
Delays
Step Program
Step Setup
Verify

For bank builders

Sequences

Power Factor Controller NRC12

USERS MANUAL

Startup after commissioning

MEASUREMENTS
Base Display

1 2

Alarm Status

2
Alarm Log

+
-

OVERVIEW
VOLTAGE
THD(U)
THD(I)
IRms/I1
CURRENT
POWER
TEMPERATURE
Step Usage

PARAMETERS

ALARMS

Application
Transformers
Input Voltage
Wiring
Target Cos
Resp Values
Auto Seek
Delays
Step Program
Step Setup
Fixed Steps
Verify
Step Test
Modbus Setup
Language

Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm

Menus

1 Params
2 Params
3 Params
4 Params
5 Params
6 Params
7 Params
8 Params
9 Params
10 Params
11 Params
12 Params

KK

MAINTENANCE

Controller Info
Temp Limits
Step Usage
Clear Stats
Alarm Log
Clr Alarm Log
Bank Test
Factory Config
OVERVIEW

For experts

Power Factor Controller NRC12

USERS MANUAL

Power Factor Controller NRC12


USERS MANUAL

Table of Contents
1. General ........................................................................................................................................5
1.1 Safety .....................................................................................................................................5
1.2 Environmental conditions........................................................................................................5
1.3 Description..............................................................................................................................6
2. Installation ....................................................................................................................................9
3. Display .......................................................................................................................................12
4. Start-up Procedure .....................................................................................................................13
5. Menu Operations........................................................................................................................14
5.1 General .................................................................................................................................14
5.2 Main Menu ............................................................................................................................16
5.3 Bank Pre-Configuration ........................................................................................................18
5.4 Commissioning .....................................................................................................................19
5.4.1 Commissioning sequence ..............................................................................................19
5.4.2 List of errors ...................................................................................................................20
5.5 Auto Setup of Parameters ....................................................................................................21
5.6 Manual Setup of Parameters ................................................................................................22
5.7 Measurement Menu..............................................................................................................24
5.8 Parameters ...........................................................................................................................26
5.9 Alarms Menu.........................................................................................................................29
5.10 Maintenance menu .............................................................................................................31
6. Miscellaneous ............................................................................................................................33
6.1 Stepping programs ...............................................................................................................33
6.2 Manual calculation of response value...................................................................................36
6.3 High voltage application of NRC12.......................................................................................38
7. Options .......................................................................................................................................40
7.1 External Temperature Sensor...............................................................................................40
7.2 Controller Communication Adapter.......................................................................................40
8. Glossary .....................................................................................................................................41
9. Technical specifications .............................................................................................................44

Power Factor Controller NRC12

USERS MANUAL

1. General
1.1 Safety
The following precautions must be taken into account when installing and operating the controller
x
x
x
x
x

The installation of the controller must be performed by a qualified electrician


Do not touch the connectors when the controller is energized, make sure that the operating
voltage is disconnected before touching any parts located on the rear side of the controller
Do not open a live current circuit, this may cause dangerous overvoltages. Always short circuit
the current transformer (CT) before replacing or removing the controller installed in a bank.
Do not open the controller casing, there are no user serviceable parts inside
External computing devices connected to the communication connector of Power Factor
Controller have to comply with the standard IEC 60950-1

For better understanding of the terminology used, please refer to the Glossary (chapter 8) at the
end of this manual.

1.2 Environmental conditions

The controller is designed for the following environmental conditions:


x Indoor use
x Altitude up to 2000 m
x Ambient temperatures within 0+60C
x Maximum relative humidity 80 percent for temperatures up to 31C decreasing linearly to 50
percent relative humidity at 40C
x Mains supply voltage fluctuations not to exceed 20/+15 percent of the nominal voltage
x Transient overvoltage for the Mains supply according to installation categories III
(IEC 61010-1)
x Pollution degree 2 (IEC 61010-1)

Power Factor Controller NRC12

USERS MANUAL

1.3 Description

Front view:

B
E

Legend
A
B
C
D
E

Display
Keys
Opening of door
Door
Mounting bracket for panel mounting installation

Power Factor Controller NRC12

USERS MANUAL

Rear view:

M
L
K
J

Legend
F
G
H
I
J
K
L
M

Step output connectors


Name plate
Mounting bracket for panel mounting installation
Fixing spring for DIN-rail mounting
Current, voltage, temperature sensor and target cos M connection inputs
Fan F and alarm A outputs
DIN-rail mounting installation area
Controller Communication Adapter (CCA-01) cover

Power Factor Controller NRC12

USERS MANUAL

Side view:

Legend
N
O

DIN-rail fixing spring


Air inlet for temperature measurement

See Chapter 9 for technical details.

Power Factor Controller NRC12

USERS MANUAL

2. Installation
The controller is designed for either panel (cut-out 138 x 138 mm) or DIN-rail installation. It is
locked to a panel by a side fitting springs or to the rail by a screwdriver-operated fixing spring.
There are two ways of connecting the controller to the network.
Voltage LN (Line Neutral)

Voltage LL (Line Line)

CT on the same line phase as voltage measurement.


For LN wiring Voltage setting should be L1-N and Current
setting should be L1.
CT normally on the remaining phase (normally phase L1).
For LL wiring Voltage setting should be L2-L3 and Current
setting should be L1.

Separated inputs exist for measurement voltage ("U1" and " U2") and supply voltage ("0V" and
"110V"/"230V"/"400V"). The controller can automatically correct incorrect measurement
connection when Auto Setup is selected from the main menu.
External temperature sensor can be installed close to the devices to be watched and connected to
inputs "T1" and "T2". The cable used needs to be certified to national requirements relevant to
controller installation voltage.
Alternative target cos M can be controlled by using external relay contact connected between
inputs "M1" and "M2". The cable used needs to be certified to national requirements relevant to
controller installation voltage.
Caution:

For application in HV network, look first at chapter 6.3

Control switch of capacitorbank switches the power to the controller.


In ambient temperature of 60qC the temperature class of connection wires must be at least 80qC.

Notes on installation:
A switch or circuit-breaker shall be included in the building installation. It shall be in close
proximity to the equipment and within easy reach of the operator. It shall be marked as the
disconnecting device for the equipment. An equipment switch or circuit-breaker employed as a
disconnecting device shall comply with relevant requirements of IEC 60947-1 and IEC 60947-3.
Overcurrent protection devices such as fuse or miniature circuit breaker with a rating of no more
than 10 A shall be connected in supply conductors. The overcurrent protection devices need to be
certified to national requirements.

10

400V 50/60 Hz

Figure 1-1: Controller connection example Line-to-Line (LL)

Power Factor Controller NRC12


Connection Example Line-to-Line

L1
L2
L3
N
PE

Bank
ON/OFFswitch
Fuses max. 10 A

U2

U1

R1
R2
R3
R4
R5
R6
C
S1
S2
T1
T2

400V
230V
110V
0V

Select switch
for
cos M2

M1
M2

Rear view

Alarm
circuit

A
B

Power Factor Controller


NRC12

F1
F2

C
R7
R8
R9
R10
R11
R12

Fan

Connection of steps 2...11 as with 1 and 12

Capacitor
step 1

External
temperature
probe

No connection

Capacitor
step 12

Power Factor Controller NRC12


USERS MANUAL

LOAD

11

400V 50/60 Hz

Figure 1-2: Controller connection example Line-to-Neutral (LN)


U2

U1

R1
R2
R3
R4
R5
R6
C
S1
S2
T1
T2

Select switch
for
cos M2

400V
230V
110V
0V

Power Factor Controller NRC12


Connection Example Line-to-Neutral

L1
L2
L3
N
PE

Bank
ON/OFFswitch
Fuses max. 10 A

M1
M2

Rear view

Alarm
circuit

A
B

Power Factor Controller


NRC12

F1
F2

C
R7
R8
R9
R10
R11
R12

Fan

Connection of steps 2...11 as with 1 and 12

Capacitor
step 1

External
temperature
probe

No connection

Capacitor
step 12

Power Factor Controller NRC12


USERS MANUAL

LOAD

Power Factor Controller NRC12

USERS MANUAL

3. Display
The controller is equipped with a backlighted dot matrix display with a resolution of 128 x 64
pixels.
Essential indicators:

Figure 2: Display layout and symbols

12

Power Factor Controller NRC12

USERS MANUAL

4. Start-up Procedure
Before connecting power, check the wiring of all controller terminals. Check carefully for correct
operating voltage. Selection of wrong voltage input can permanently damage the controller.
After the first power switch-on, the controller will automatically ask for the language setting of the
menu.

Figure 3: Language setting dialog

At any time press

?-button for help screen.

13

Power Factor Controller NRC12

USERS MANUAL

5. Menu Operations
5.1 General
Navigation between different menu levels
As a precaution against accidental use, the access of certain menus has been protected by a
keylock, which is a special sequence of keystrokes enabling the use the particular menu item.
Code lock is automatically closed after the home delay (5 minutes from last keystroke).

Figure 4: Entering a submenu with a keylock

14

Power Factor Controller NRC12

USERS MANUAL

Adjusting a value

Figure 5: Adjusting a value


For faster increasing/decreasing hold the button down.
Using controller help
At any time pressing

?-button provides information and browsing help for the current controller

screen.

Figure 6: Using controller help

15

Power Factor Controller NRC12

USERS MANUAL

5.2 Main Menu


The main menu contains all basic submenus required to set up and operate the controller.
Which menu to choose?

Figure 7: Required skills and menu selection


If bank preconfiguration is properly done, commissioning does not require any special skill.

16

Power Factor Controller NRC12

USERS MANUAL

(1) Bank pre-configuration


When factory settings have not been changed, this menu
provides the means of pre-configuring the bank at the
workshop. After pre-configuration, this menu topic is
replaced by (2) Commissioning, by which the controller is
taken into service.

(3) Automatic setup of parameters


In the event that the controller has not been preconfigured, an inexperienced user can automatically set up
all the characteristics of the bank and bring it into service.

(4) Manual setup of parameters


In the event that the controller has not been pre-configured,
an experienced user can manually set up all the
characteristics of the bank and bring it into service.

(5) Measurement
The measurement menu contains the most common
measurements taken from the network and provides some
information about the bank. This is a read-only menu.

(6) Parameters
At any time, an experienced user can access the most
common operating parameters from this menu. Unlike the
configuration and setup sequences, this is a menu allowing
a free and unrestricted entry into all its items and should be
used when an occasional parameter access is needed.

(7) Alarm settings


To show status and adjust the parameters of alarms.

(8) Maintenance
The maintenance menu provides useful information about
the usage of the bank, capacitors and contactors. Auxiliary
settings and action have also been provided. This menu is
basically intended for use by the manufacturers
maintenance team.
Figure 8: Main menu

17

Power Factor Controller NRC12

USERS MANUAL

5.3 Bank Pre-Configuration


This menu item is a forced sequence, meaning that all items must be accessed before the preconfiguration takes place.
NOTES:

1) Do not use the Bank Pre-Configuration menu for HV network applications


2) Select Cancel at the end of Bank Pre-Configuration menu if 1st step is fixed

The sequence can be interrupted by pressing

key. See Glossary (chapter 8) for definitions.

Figure 9: Bank pre-configuration

18

Power Factor Controller NRC12

USERS MANUAL

5.4 Commissioning

5.4.1 Commissioning sequence


A pre-configured controller is put into service by this menu. The sequence contains an automatic
C/K value detection and and automatic parameter verification to check that the manually entered
parameters comply with the network.
See Glossary (chapter 8) for parameter definitions.
NOTE:

The use of Commissioning menu is forbidden on HV network applications.

Figure 10: Commissioning

19

Power Factor Controller NRC12

USERS MANUAL

5.4.2 List of errors

What to do in case of error ?


Error codes can help you to identify a problem and make corrections.

Code

Meaning

Action to do

1 Unstable network

Unstable network: The controller is


unable to verify/search parameters due
to excessive load variations on the
network.
st
Step size too small: The effect of the 1
step cannot be measured. CT
oversized, wrong wiring, inoperative
steps.
Sequence not found: Step ratio does
not match available step sequences.

2 Step too small


3 Sequence not found

4 Step too large


5 Use manual setup
6 - 8
9 Wiring error

Step size too large: The ratio of


st
measured step compared with the 1
step is too large. Step sequence cannot
be resolved.
Non-relevant autosetup process with
this bank configuration.

Check the condition and sizes of


steps
Check the contactors and step
wiring.
Check the condition and sizes of
steps and contactors

Use manual setup to confirm or


correct the information obtained by
autosetup.

Check the wiring of voltage- and


current inputs
Check the Wiring setting from
Parameters menu
Check the Number of Steps setting
Check the number of steps in the
bank and the condition of steps
Check Step Sequence setting
Check step sizes used in the bank

Reserved
Wiring verify error: Controller wiring not
correct.

10 Step count error

Step count verify error: The Number of


Steps setting is incorrect.

11 Step sequence err

Step sequence verify error: The step


size ratios differ from the selected step
sequence.
C/K value verify error.

12 C/K value error

Enter the parameter settings


manually using Parameters menu.
Rerun the commissioning
sequence
Check wiring, CT, condition of
capacitor steps (1st step)

Check the response value used


Check the size of 1st step in the
bank

Disconnected bank disables Verify and Search functions and "Alarm with shutdown"-text
will be shown in the Verify / Search - result screen.

20

Power Factor Controller NRC12

USERS MANUAL

5.5 Auto Setup of Parameters


The auto setup sequence is intended for inexperienced users so they can commission the bank
with minimal prior knowledge. The user need only input three of the most common parameters
and then launch an automatic search for the other parameters.
Auto setup forces application setting to 4-quadrant, step program to optimal, and disables step
size monitoring. C/K-value, step setup and wiring are detected automatically. The automatic
detection is unavailable if fixed steps are set.
NOTE:

The use of Auto Setup of Parameters menu is forbidden on HV network


applications.

In the event of error, see the error table on previous page.

Figure 11: Auto setup of parameters

21

Power Factor Controller NRC12

USERS MANUAL

5.6 Manual Setup of Parameters


The manual setup sequence is intended for experienced users. There are nine important
parameters to input before the controller can be taken into service. This sequence is completed by
an automatic verification of the parameters entered in this sequence.

This menu item is a forced sequence, meaning that all items must be accessed before the
validation of the setup takes place. The sequence can be interrupted by pressing

key.

See Glossary (chapter 8), for parameter definitions.


In case of error in verification, refer to error table, page 20.
NOTE:

The use of verification in Manual Setup of Parameters is forbidden on HV network


applications.

22

Power Factor Controller NRC12

USERS MANUAL

Figure 12: Manual setup of parameters

23

Power Factor Controller NRC12

USERS MANUAL

5.7 Measurement Menu


The measurement menu contains the most common measurements taken from the network. This
is a read-only menu, only the selection on some displayed measurements is possible.

Figure 13: Measurement menu


Measurement Explanations:
Screen
Item
Alarm List
Alarm log
OVERVIEW

U1
THD(U)
IRMS/I1
Q
Temp

Description
List of detected alarms. A = Active alarm.
Log of 5 latest alarms. Alarm log can be cleared using
"Clear Alarm Log"-function in Maintenance menu.
Input voltage (VLL Line to Line or VLN Line to Neutral)
Total harmonic distortion of voltage
Capacitor overload factor
Reactive power
Internal temperature

24

Power Factor Controller NRC12

USERS MANUAL

Screen

Item

Description

VOLTAGE

U1

Input voltage (VLL Line to Line or VLN Line to Neutral) and


voltage limits. If nominal value is not standard, graphical
display is in % scale.
Total harmonic distortion of voltage and alarm limit for it.
Total harmonic distortion of voltage and harmonic
components.
Total harmonic distortion of current and harmonic
components.
Capacitor overload factor (measured current ratio to
nominal current at nominal voltage) and alarm limit for it.
Active current of CT primary (phase current)
Reactive current of CT primary
Apparent current of CT primary
Active power (3-phase total power)
Reactive power
Apparent power
Internal temperature, fan limit and alarm limit.
External temperature, only present if external
temperature sensor connected.
Number of step connections and usage hours

THD(U)
THD(U)
THD(I)
IRMS/I1
CURRENT

POWER

TEMPERATURE

STEP USAGE

Active
Reactive
Apparent
Active
Reactive
Apparent
Internal
External

Figure 13-2: Measured value and alarm limits

Figure 13-3: Graphs showing voltage harmonics

Figure 13-4: Temperature values and fan status

25

Power Factor Controller NRC12

USERS MANUAL

5.8 Parameters
CAUTION:

In case of installation in a HV bank (with VT), you must adjust the default
factory settings. The reconnection delay must be changed to a larger value
(e.g. 600 secs) to prevent destruction of capacitors.

The most common operating parameters can be accessed from this menu.
Unlike the configuration and setup sequences presented earlier in this text, this is a menu allowing
a free and unrestricted entry into all of its items and should be used when occasional parameter
access is needed. Restart the controller after major changes in parameters.
To start the step size monitoring, set number of steps, step sequence and the size of the 1st step
(reactive power and voltage), initialize the measurement (asked when exiting the editor). If
wanted, set the alarm on from the alarm menu. If the step size is set to 0 the step size monitoring
is disabled.
Step size monitoring cannot be used when
loads change constantly and rapidly
if the 1st step is very small compared to total measurement scale
if HV application is selected (automatically disabled)
Fixed steps cannot be monitored or verified. Setting 1st step fixed disables also search and seek
functions.
See Glossary (chapter 8), for parameter definitions.
In case of error in verifying, refer to error table, page 20.

26

Power Factor Controller NRC12

USERS MANUAL

Figure 14: Parameters

Parameter Explanations:
Screen

Item

Description

Application

2 Quadrant

2 quadrant application: Only use of power, the most


common situation.
4 quadrant application: Power generation possible.
Application is forced to 4-quadrant in Auto Setup.
Network voltage range of application.

4 Quadrant
100-700V
0,5-50kV (VT)
10-400kV (VT)

27

Power Factor Controller NRC12

USERS MANUAL

Screen

Item

Description

Transformers

CT
VT

Current transformer: primary and secondary current.


Voltage transformer ratio. Used if voltage range with
VT selected.
Nominal input voltage reference value at input
voltage terminals U1 and U2. For voltage alarms.
In VT application, the secondary voltage is entered
and the calculated primary voltage is displayed.
Location of voltage measurement: L2-L3, L3-L1, L1L2, L1-N, L2-N or L3-N. Detected in Auto Setup and
Auto seek, checked with verify function. See also
Installation (chapter 2).
Location of current measurement: L1, L2 or L3.
Detected in Auto Setup and Auto seek, checked with
verify function. See also Installation (chapter 2).
Detected in Auto Setup and Auto seek, checked with
verify function.
DIRECT = Normal polarity of current measurement
REVERSE = Inverted polarity of current
measurement
AUTO = Automatic current polarity detection,
disabled in 4 quadrant applications.
Primary Target Cos M (normally used when control
input is open), 0.80 ind - 0.90 cap
Secondary Target Cos M (selected by closing relay
input), 0.80 ind - 0.90 cap. Symbol in Base Display
shows the status of control relay.
C/K-value for inductive reactive power, 0.01 - 1.99.
Calculate using a formula or get from C/K value
table. Detected in Auto Setup and Auto seek, or
manually if wanted. Checked with verify function.
C/K-value for capacitive reactive power, 0.01 - 1.99.
Calculate using a formula or get from C/K value
table. Detected in Auto Setup and Auto seek, or
manually if wanted. Checked with verify function.
Automatic C/K-value seek, connects and disconnects
first step several times. Do not use on HV network
applications!
10s - 900s. Reconnection delay and response delay.
Reconnection delay is used to protect the step
capacitors (don't use too short values). Response
delay, the minimum time between changes in steps,
is defined as 20 % of reconnection delay, min 10 s.
The default value corresponds to capacitors with
internal discharge resistors 50V 1 min. Reconnection
is faster when using Optimal step program.
(Forced to Optimal in Auto Setup).
Normal, suitable for step sequence 1.2.4.4.4
Circular 1.1.1, suitable for step sequence 1.1.1.1.1
Circular 1.2.2, suitable for step sequence 1.2.2.2.2
Stack, suitable for step sequence 1.1.1.1.1
Optimal, suitable for several step sequences
Number of steps, 1 -12. Detected in Auto Setup,
checked with verify function.
Step sequence (needed for optimal stepping
program, step size monitoring function and alarm 12).
Detected in Auto Setup, checked with verify function.

Input Voltage

Wiring

Voltage Phase

CT Phase

CT Polarity

Target Cos

Cos 1
Cos 2

Resp Values

Inductive

Capacitive

Auto Seek

Delays

Reconnection

Step Program

Step Setup

Num of Steps
Step Seq

28

Power Factor Controller NRC12

Screen

Item

Description

1st Step

Size of first step at given voltage level (next


parameter) 1kvar - 400kvar, for step size monitoring.
0 = step size monitoring disabled.
See Alarms Menu (chapter 5.9) / Alarm 12
Nominal voltage of step (the line-to-line voltage)
A: Automatic (default)
0: Step fixed OFF
1: Step fixed ON
Steps set fixed are not included in any automatic
functions.
Fixed steps and Optimal Stepping Program cannot
be used together.
Automatic verification of C/K, steps and wiring. In
case of an error refer to error table, page 20.
Do not use in HV network applications!
Manual connection of steps for testing
2 digits containing correct message total counter +
2 digits containing faulty message counter +
2 digits containing replied message counter.
The use of controller's communication.
NONE = Communication disabled
READ = Communication reads information
READ/RESET = Communication reads information
and resets alarms.
READ/WRITE = Communication reads and writes
information
Modbus slave address of the controller
Bit rate used for data transmission
Language selection of user interface

Voltage
Fixed Steps

Verify

Step Test
Modbus Setup

Status

Mode

Address
Bits/s
Language

USERS MANUAL

5.9 Alarms Menu


In Alarms menu, each individual alarm can be enabled or disabled. Alarms 1-11 are enabled and
alarm 12 is disabled as default. Alarm screen also shows whether the alarm is active or passive.
Also, some alarm triggering levels can be adjusted. Disconnection of steps due to alarms 2, 9, 10
can be enabled or disabled from alarm settings.
Once an alarm condition is detected, the corresponding alarm number is shown at the upper part
of the display, and the alarm symbol becomes visible. The alarm relay is also activated.
Alarm indications can be reset in base display alarm dialog ( 1 ), this clears all passive
alarms. If alarm condition is still active, the alarm cannot be reset.

29

Power Factor Controller NRC12

USERS MANUAL

List of alarm descriptions and limits:


Alarm
No.

Alarm

Description

Limit, limit adjustment

Out of Steps

2
3
4
5

Hunting
Abnormal Cos M
Low voltage
Over Compensation

No steps left to connect. Network is still


inductive and request for more steps exist.
Continuing more/fewer step request detected.
Current flows, but cos M out of range.

Wrong frequency

7
8
9

Over Current
Over Voltage
Over Temperature

10
11

Too High THD(U)


Cap Overload

12

Cap Output Low

No steps left to disconnect, network is still


capacitive.
Frequency detected at startup neither 50 Hz
nor 60Hz.

If external temperature sensor is installed, only


external temperature is watched.
Harmonic distortion of voltage over limit.
Harmonic distortion or resonance polluted
current, overload factor IRMS/I1 over limit.
Capacitance is measured and watched during
connection and disconnection. Step sizes must
be configured for step size monitoring (see
Parameters/Step Setup).

10 min
Ind. < 0.50, cap. < 0.80
80%

+- 2 Hz of nominal at startup
115% of nominal
110%( 30 min ) or 120%(1 min)
Temperature limit setting, default
50qC
THD(U) limit setting, default 7%.
IRMS/I1 limit setting, default 1.5.
Capacitor value < 75 % nominal

List of alarm causes and actions:


Alarm
No.

Alarm

Possible cause

Controller action

Wiring or LL/LN definition error


Undersized bank
Too small C/K value
Wrong program choice
Defective capacitors

Out of Steps
Hunting

Abnormal cos M

4
5

Low voltage
Over Compensation

Wrong frequency

7
8

Over Current
Over Voltage

Over Temperature

Ambient temperature too high


Defective cooling system

10

Too High THD(U)

Harmonic pollution
Resonance

11

Cap Overload

Harmonic distortion, resonance

12

Cap Output Low

Defective capacitor

If disconnection in alarm setup is


ON disconnects bank for 10
minutes. No disconnection as
default.

Wiring mistake
Over capacitive network (welded contactors)
Too low current
Disconnection till voltage returns
Wiring or LL/LN definition error
Improper use of fixed steps
Wrong or unstable network frequency detected
at startup
Undersized CT

Stop regulation. No automatic


restart
Temporary disconnection of steps
during alarm and delay after that.
Temporary disconnection of steps
during alarm and delay after that,
if disconnection in alarm setup is
ON. Disconnection as default.
Temporary disconnection of steps
during alarm and delay after that,
if disconnection in alarm setup is
ON. No disconnection as default.
Temporary disconnection of steps
during alarm and delay after that.

b-marks in Base Display

In case of Alarm 12 user can set the defective capacitor Fixed OFF to clear the alarm situation.

30

Power Factor Controller NRC12

USERS MANUAL

Figure 15: Alarms menu


Alarm contacts are
x closed when the controller is not energized,
x opened when the controller is energized without alarm
x closed when the controller is energized with active alarm
Alarm parameter explanations:
Item

Description

Alarm Status

ACT = Alarm active and triggered


PAS = Alarm passive
ENABLED = Alarm ON
DISABLED = Cannot cause an alarm under any conditions. The other settings of the
alarm have no effect.
For alarms 2, 9 & 10.
ON = Bank shut down in case of alarm
OFF = No shutdown
Alarm detection limit for alarms 9, 10 & 11.

Mode

Disconnection

Limit

5.10 Maintenance menu


The maintenance menu provides useful information about the usage of the bank, capacitors and
contactors. Also, some auxiliary settings have been provided.
CAUTION:

This menu access is dedicated to specialists.

31

Power Factor Controller NRC12

USERS MANUAL

Figure 16: Maintenance menu


Maintenance explanations:
Screen

Item

Description

Controller info

S/N
Program vers
Uptime
Alarm limit

Serial number
Software version
Power on hours
Display for temperature alarm limit

Fan offset
Fan limit

Fan offset setting, fan limit = alarm limit - offset


Display for fan temperature limit. If external
temperature sensor is installed, fan is controlled by
external temperature.

Limit Settings

Step Usage
Clear Stats
Alarm Log
Clr Alarm Log
Bank Test

Factory Config

Connections of steps, usage hours display and possibility


of clearing.
Clear step statistics and alarm log.
Log of 5 latest alarms
Clear alarm log
Each step is automatically connected and disconnected in
turn. This facilitates testing of the operation of each
capacitor step contactor.
To be used only for testing offline capacitors! Do not use on
HV network applications!
Restore controller factory settings

32

Power Factor Controller NRC12

USERS MANUAL

6. Miscellaneous
6.1 Stepping programs
The controller's algorithm will try to reach the target cos M inside a tolerance area dependant
upon the C/K value, figure 18. It reaches the value by switching on or off available relevant steps.
The regulation program choice follows the steps definition :
a) Stack Program (linear) :
All capacitor steps are of equal size (i.e :1.1.1.1). The operation sequence obeys to a last-in-firstout (LIFO) principle. The first step connected will be the last one to be disconnected and vice
versa. See Table 1.
b) Normal program (2+ linear)
Normal program can be used on bank whose step ratio is 1.2.4.4.. The linear sequence starts with
the 3rd step. The two first steps are used as fine-tuning. The controller always start by switching
the first step then the second. Other steps are used successively See Table 2.
c) Circular 1:1:1 program
All capacitor steps are of equal size (i.e :1.1.1.1). The operation sequence obeys the first-in-firstout (FIFO) principle. With this stepping program the amount of on- and off-connections at each
step will eventually be the same. The first step connected will be the first one to be disconnected
and vice versa. Then a circular sequence is followed. In order to operate correctly, the number of
steps programmed into the controller must strictly comply with the number of physical steps
See Table 3.
d) Circular 1:2:2 program (1+Circular)
Circular B program can be used on a bank whose step ratio is 1.2.2.2. The first step is used as
tuning after the activating limit is exceeded. The circular sequence starts with the 2nd step. See
Table 4.
e) Optimal Program :
The optimal program operates with many step configurations:
1.1.1.1.1
1.2.3.3.3

1.1.2.2.2
1.2.3.4.4

1.1.2.3.3
1.2.3.6.6

1.1.2.4.4
1.2.4.4.4

1.2.2.2.2
1.2.4.8.8

The target cos M power is reached using the fewest number of steps in minimal time. Like the
circular program, this algorithm equalizes the usage of largest steps.
This program uses optimally selected step sizes when approaching the target power and at the
same time the response delays are shortened, particularly if there is a large requirement for
compensation power or if the network suddenly becomes capacitive. As circular program, this
stepping program keeps the usage of steps even.
Optimal program is disabled with fixed steps and vice versa.

33

Power Factor Controller NRC12


Step
demand

+
+
+
+
+
+
+
+
+
-

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

Step number
2 3 4 5

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X

X
X
X
X
X

X
X
X
X
X

X
X
X

X
X
X

USERS MANUAL
Step
demand

+
+
+
+
+
+
+
-

1
X
X
X
X

X
X
X

Step number
2 3 4 5

X
X
X
X

X
X
X

X
X
X
X
X
X
X
X
X
X
X

X
X
X
X
X
X
X
X
X

X
X
X

Table 2: Normal program - Operation


sequence 1:2:4:4

Table 1: Stack program - Operation


sequence 1:1:1:1

Step
demand
+
+
+
+
+
+
+
+
-

1
X
X
X
X

X
X
X

Step number
2 3 4 5

X
X
X
X

X
X

X
X
X
X
X
X

X
X
X
X
X
X

X
X
X
X
X
X

Step
demand

+
+
+
+
+
+
+
+
+
-

X
X
X
X
X
X

Table 3: Circular A program - Operation


sequence 1:1:1

1
X
X
X
X
X

X
X
X
X

Step number
2 3 4 5

X
X
X
X
X
X

X
X
X
X

X
X
X
X
X
X

X
X
X
X
X
X
X
X
X

X
X
X
X
X

X
X
X
X
X

Table 4: Circular B program - Operation


sequence 1:2:2

Comparison between normal and optimal program:


Normal program will reach the cos M target value by successive connection/disconnection of
capacitors corresponding to the smallest step value.
Optimal program will reach the target cos M value by successive connection/disconnection of
capacitors corresponding to the highest relevant and available step value.

34

Power Factor Controller NRC12

USERS MANUAL

Figure 17: Regulation example - Optimal vs. Normal

35

Power Factor Controller NRC12

USERS MANUAL

6.2 Manual calculation of response value


Normally the response value, more generally known as the C/K value, is set automatically as a
part of the Auto Setup sequence, but there are cases when these values must be entered
manually. The correct value can be calculated using an equation requiring the 1st step size (in
vars), line-to-line voltage of the network used (in volts) and the CT ratio as follows

C/K

Q1
I1 5 A u U LL u 3
where Q1
ULL
I1/5A

=
=
=

size of 1st step in vars


line-to-line voltage in volts
CT ratio ( alternative : I1/1A )

Alternatively, the C/K value can be taken from the table below (valid for 400 V networks)
1st
step
(kvar)
5
7,5
10
12,5
15
18,5
20
25
30
37,5
40
50
60
75
90
100
120
150
200

50
0,72
1,08
1,44
1,80

20
100
0,36
0,54
0,72
0,90
1,08
1,34
1,44
1,80

30
150
0,24
0,36
0,48
0,60
0,72
0,89
0,96
1,20
1,44
1,80
1,92

40
200
0,18
0,27
0,36
0,45
0,54
0,67
0,72
0,90
1,08
1,35
1,44
1,80

60
300
0,12
0,18
0,24
0,30
0,36
0,45
0,48
0,60
0,72
0,90
0,96
1,20
1,44
1,80

CT n1/n2
80 100 120 160 200 300 400 500 600 /1
400 500 600 800 1000 1500 2000 2500 3000 /5
0,14
0,18
0,23
0,27
0,33
0,36
0,45
0,54
0,68
0,72
0,90
1,08
1,35
1,62
1,80

0,11
0,14
0,18
0,22
0,27
0,29
0,36
0,43
0,54
0,58
0,72
0,87
1,08
1,30
1,44
1,73

0,12
0,15
0,18
0,22
0,24
0,30
0,36
0,45
0,48
0,60
0,72
0,90
1,08
1,20
1,44
1,80

0,11
0,14
0,17
0,18
0,23
0,27
0,34
0,36
0,45
0,54
0,68
0,81
0,90
1,08
1,35
1,80

0,11
0,13
0,14
0,18
0,22
0,27
0,29
0,36
0,43
0,54
0,65
0,72
0,87
1,08
1,44

0,10
0,12
0,14
0,18
0,19
0,24
0,29
0,36
0,43
0,48
0,58
0,72
0,96

0,11
0,14
0,14
0,18
0,22
0,27
0,32
0,36
0,43
0,54
0,72

0,11
0,12
0,14
0,17
0,22
0,26
0,29
0,35
0,43
0,58

0,10
0,12
0,14
0,18
0,22
0,24
0,29
0,36
0,48

Table 5: C/K-values for 400 V network


The reactive power between limits corresponding to response value is adjusted by successive
connections (or disconnections) of steps.

36

Power Factor Controller NRC12

USERS MANUAL

Figure 18: Compensation example and consequences

37

Power Factor Controller NRC12

USERS MANUAL

6.3 High voltage application of NRC12


CAUTION:

In case of installation in a HV bank (with VT), you must adjust the default
factory settings. The reconnection delay must be changed to a larger value
(e.g. 600 secs) to prevent destruction of capacitors.

The controller can be used in HV networks, if the following points are taken into account.
Connections must employ VT and CT with respect to the figure 19.
The application menu has two voltage ranges for HV applications: 0.5 - 50 kV and 10 - 400 kV.
The lower voltage range has finer VT ratio resolution and range than the higher voltage range.
Safety (or reconnection) delay must be adapted to the value of the discharge resistors of the
capacitors, the most usual value is 600 seconds (10 minutes). The controllers default
reconnection delay is adapted for LV use. Using too short a reconnection delay may damage the
capacitors.
Important:
the whole commissioning process must be performed using the Parameter menu
the commissioner should not use Bank Pre-Configuration, Manual Setup and Commissioning
menus
the use of Auto Setup menu is strictly forbidden to prevent capacitor destruction
do not use "Verify" or "Auto Seek" on HV network applications!

38

39

Example
20 kV 50/60 Hz

Figure 19: HV use of the controller


U1

20 kV

100 V

U2

R1
R2
R3
R4
R5
R6
C

Power Factor Controller NRC12


HV Connection Example

L1
L2
L3
PE

Fuses max. 10 A
L
Auxiliary voltage
230VAC
N

M1
M2

S1
S2
T1
T2

400V
230V
110V
0V

Rear view

Alarm
circuit

A
B

Power Factor Controller


NRC12

F1
F2

C
R7
R8
R9
R10
R11
R12

Connection of steps 2...11 as with 1 and 12

Capacitor
step 12

Aux. voltage

Aux. voltage

Capacitor
step 1

Aux. voltage

Aux. voltage

No connection

Power Factor Controller NRC12


USERS MANUAL

LOAD

Power Factor Controller NRC12

USERS MANUAL

7. Options
7.1 External Temperature Sensor
The controller has terminals T1/T2 for external temperature sensor. With the external temperature
probe the temperature in a critical point in a capacitor bank can be monitored with the controller.
The external temperature measurement overrides the internal temperature in fan and alarm
monitoring. The External Temperature Sensor can be purchased as an option and installed into
the capacitor bank.
Do not touch the connectors when the controller is energized, make sure that the operating
voltage is disconnected before touching any parts located on the rear side of the controller

7.2 Controller Communication Adapter


The controller is equipped with a communication port to connect the controller to a remote master.
The communication connector is covered to ensure electrical safety during the operation of the
controller. The Controller Communication Adapter (CCA-01) can be purchased as an option and is
installed into the controller according to installation instructions supplied with the CCA-01.

Always switch off the power from the controller before installation. Make
sure that the communication connector is always covered, either with
CCA-01 adapter or the original cover before switching on the power.
Touching an uncovered connector with the power applied may lead to an
electrical shock.

40

Power Factor Controller NRC12

USERS MANUAL

8. Glossary
Display
information

Description

Min value Default


value

Current too high

1st STEP
(Step Setup)

Max value
>1,10u
Inom

Current too low. All steps are disconnected in 2


quadrant application.
No Input Voltage.
Size and voltage of 1st step (the line-line voltage of
capacitor) for step size monitoring. 0 = step size
monitoring disabled.
See Alarms Menu (chapter 5.9) / Alarm 12
The Modbus slave address of the controller

ADDRESS
(Modbus Setup)
ALARM LIST
List of detected active (A) and passive alarms. Reset
clears passive alarms.
ALARM LOG
Log of 5 latest alarms
ALARMS
Alarm Menu
ALARM STATUS ACT = Alarm active and triggered
PAS = Alarm passive.
APPLICATION
Power flow and network voltage level of the capacitor
bank. 2 quadrant = only power consumption (typical
situation). 4 quadrant = power generation possible.
Application is forced to 4 quadrant in Auto Setup.
AUTO SEEK
Automatic search of C/K response value
AUTO SETUP
Automatic Setup Sequence
BANK PRECONF Bank Pre-configuration Sequence
BANK TEST
Bank Test: each step is automatically connected and
disconnected in turn. This facilitates testing of the
operation of each capacitor step contactor. To be used
only for testing offline capacitors! Do not use in HV
network applications! See also Step Test.
BITS/S
Data transmission speed of the controller
(Modbus Setup)
CAPACITIVE
Response value for the capacitive side of the target
(Resp Values)
cos M. Normally set up automatically by the controller.
Detected in Auto Setup and Auto seek, or manually if
wanted. Checked with verify function.
CCA
The controller has a connector for CCA communication
module (option).
CIRCULAR 1.1.1
Circular stepping program for sequence 1.1.1.1.1.1
CIRCULAR 1.2.2 Circular stepping program for sequence 1.2.2.2.2.2
C/K
Response value. Can be manually set up or
automatically searched by the controller.
CLEAR STATS
Clear Statistics
CLR ALARM LOG Clear Alarm Log
COMMISSIONING Commissioning Sequence
COS 1
Target cos M value 1 (normally used)
(Target cos M)
COS 2
Target cos M value 2 (selected by control input)
(Target cos M)
CT
Current Transformer setting, xxx/5 or xxx/1
(Transformers)
CT PHASE
Example: CT phase L1. Current connected to phase 1.
(Wiring)
Detected in Auto Setup and Auto seek, checked with
verify function. See also Installation (chapter 2).

41

<0,025u
Inom
0 kvar
200V

0 kvar
400V

400 kvar
800V

247

2 quadrant 2 quadrant 4 quadrant


100-700 V 100-700 V 10-400 kV
(VT)

1200

9600

38400

See
"C/K".

0,01

0,50

1,99

0,8ind

1.00

0,9cap

0,8ind

1.00

0,9cap

25/1
25/5

1000/5

6000/1
6000/5

L1

Power Factor Controller NRC12

Display
information
CT POLARITY
(Wiring)

DISCONNECTION
(Alarm Paras)
EXT

USERS MANUAL

Description
Current polarity selections:
DIRECT = direct connection
REVERSE = inverted connection
AUTO = automatic polarity (controller identifies polarity
in 2 quadrant applications, disabled in 4 quadrant)
Disconnection of steps in case of alarm, ON/OFF

External temperature. Present only if external


temperature sensor connected.
FACTORY CONFIG Restore Factory Settings
FAN OFFSET
Fan temperature offset (adjustable)
(Temp Limits)
Fan switch-on limit is offset degrees lower than
temperature limit.
FIXED STEPS
Fixed steps: each step can be manually fixed ON (1)or
OFF (0). In search, seek and verify functions a fixed
step is always skipped and considered OK. If 1st step is
fixed search, seek and verify functions are disabled.
INDUCTIVE
Response value for the inductive side of the target
(Resp Values)
cos M. Normally set up automatically by the controller.
Detected in Auto Setup and Auto seek, or manually if
wanted. Checked with verify function.
INPUT VOLTAGE Nominal input voltage reference value at input voltage
terminals U1 and U2. For voltage alarms.
INT
Internal temperature
IRMS/I1
Capacitor overload factor
LANGUAGE
Language Selection for menus
LIMIT
Adjustable over temperature alarm limit. Fan switches
(Alarm 9 Para) ON some degrees under this (adjustable offset).
LIMIT
Maximum harmonic distortion of voltage (adjustable)
(Alarm 10 Para)
LIMIT
Capacity overload alarm limit (maximum Irms/I1 - value)
(Alarm 11 Para)
LL
Line to Line connection
LN
Line to Neutral connection
MAINTENANCE
Maintenance Menu (for experts)
MANUAL SETUP Manual Setup Sequence
MEASUREMENTS Measurements Menu
MODE
Alarm setup (enable / disable)
(Alarm Paras)
MODE
The use of controller's communication.
(Modbus Setup) NONE = Communication disabled
READ = Communication reads information
READ/RESET = Communication reads information and
resets alarms.
READ/WRITE = Communication reads and writes
information
NUM OF STEPS Number of used steps. Detected in Auto Setup,
(Step Setup)
checked with verify function.
NORMAL
Normal stepping program for sequence 1.2.4.4.4.4
OPTIMAL
Optimal stepping program, for many step sequencies.
PARAMETERS
Parameters Menu
PRIMARY
Nominal network voltage in HV applications.
(Input Voltage) Calculated form secondary voltage and VT ratio.
PROGRAM VERS Software version
(Controller Info)

42

Min value Default


value
AUTO

Max value

ON 9
OFF 2,10

0C

20C

50C

(automatic)

See
"C/K".

80V

400V

800V

20 qC

English
50 qC

60 qC

5%

7%

20%

1,0

1,5

1,5

NONE

12

12

Power Factor Controller NRC12

Display
information
RECONNECTION
(Delays)

SEARCH
SECONDARY
(Input Voltage)
S/N
(Controller Info)
STACK
STATUS
(Modbus Setup)
STEP PROGRAM

STEP SEQ
(Step Setup)

STEP TEST

USERS MANUAL

Description

Min value Default


value
10s
50s

Reconnection delay and response delay.


Reconnection delay is used to protect the step
capacitors (don't use too short values). Response
delay, the minimum time between changes in steps, is
defined as 20% of reconnection delay, min 10 s. The
default value corresponds to capacitors with internal
discharge resistors 50V 1 min. Response to multi-step
changes is faster when using Optimal step program.
Search (response value, step sizes and wiring)
Controller input voltage in HV applications
80V

Max value
900s

150V

Serial Number of the product (for internal manufacturer


use)
Linear stepping program for sequence 1.1.1.1.1.1
2 digits containing correct message total counter +
2 digits containing faulty message counter +
2 digits containing replied message counter.
Selection of suitable stepping program between (see
Normal
6.1 Stepping programs).
Stack
Normal
Circular 1.1.1
Circular 1.2.2
Optimal
Forced to Optimal in Auto Setup.
Step Sequence setting defines step size ratios starting 1.1.1.1.1.1 1.1.1.1.1.1 1.2.4.8.8.8
from the smallest first step. Detected in Auto Setup,
checked with verify function. The alternatives are:
1.1.1.1.1.1 - 1.1.2.2.2.2 - 1.1.2.3.3.3 - 1.1.2.4.4.4 1.2.2.2.2.2 - 1.2.3.3.3.3 - 1.2.3.4.4.4 - 1.2.3.6.6.6 1.2.4.4.4.4 - 1.2.4.8.8.8
Step sequence setting is used with optimal stepping
program, or if the step size monitoring is on.
Step sequence is predefined with other programs and
modification request are not then taken into account
Step Test: each step can be manually connected and
disconnected. This facilitates testing of the operation of
each capacitor step contactor. See also Bank Test.
Number of step connections and usage hours
Total Harmonic Distortion of Current
Total Harmonic Distortion of Voltage
Contains CT setup, and VT setup in HV applications.
Uptime (Power On Hours)

STEP USAGE
THD (I)
THD (U)
TRANSFORMERS
UPTIME
(Controller Info)
VERIFY
Automatic verification of parameters. Checks C/K
value, steps and wiring. In case of an error refer to
error table, page 20.
Do not use on HV network applications!
VT
0.5 50 kV 1.0
Voltage Transformer ratio setting.
(Transformers)
10 400 kV 60
VOLTAGE PHASE Connections of voltage inputs.
(Wiring)
Example : Voltage phase L2-L3
(Voltage connected between phase 2 and 3)
Detected in Auto Setup and Auto seek, checked with
verify function. See also Installation (chapter 2).

43

1.0
L2-L3

625.0
4000

Power Factor Controller NRC12

USERS MANUAL

9. Technical specifications
Number of steps
Dimensions
Frequency
Measuring current
Measuring voltage
Displayed measuring power
Nominal power consumption
Supply voltages

Relay inputs/outputs
Display
Protection class
Target cos M -range
Response limits
Reconnection delay
Response delay
Displayed measurements

Installation method
Casing
Operating temperature range
Alarm log
Step counters
Fan control with dedicated relay
Alarm relay
Accuracy (of FS)

CT setting range
Power outage detection
Standards

Communication

Schneider Electric Industries SAS

12
155 x 158 x 80 mm
50 Hz nominal (range 48...52 Hz)
60 Hz nominal (range 58...62 Hz)
01 A or 0...5 A
80690 V (nominal, max. 115%)
100000 kVA
13 VA
110 V nominal, (range 88...130 V)
230 V nominal, (range 185...265 V)
400 V nominal, (range 320...460 V)
250 V, 2 A
Dot matrix display, resolution 64x128 pixels,
backlighted
IP41 front panel, IP20 rear part
0,85 ind 1,00 0,90 cap
0,01 1,99, symmetrical or asymmetrical
10900 s
20 % of reconnection delay, min. 10 s
cos M, Iact, Ireact, Iapp, IRMS/I1, P, Q, S, THD(U)
and voltage harmonics, THD(I) and current
harmonics, internal and external temperature.
Panel installation, DIN-rail installation
Impact resistant PC/ABS, UL94V-0
060qC
List of 5 last alarms
Yes
Yes. 250 V AC, 8A
Yes. 250 V AC, 8A
I : 2%
IQ : 2%
U/I-samples: 2%
Phase: 1q
Distortion: r3 dB (up to 15th)
Internal temperature: r3qC
External temperature: r2qC (option)
25/1 6000/1 or 25/5 6000/5
Reaction time > 15 ms
IEC 61010-1
IEC 61000-6-2
IEC 61000-6-4
UL 61010A-1
IEC 60529
Modbus protocol using CCA-01 (option)

As characteristics and dimensions of our products are constantly changing,


please contact our offices for confirmation.

44
N3653493EN-AA

07-2005

You might also like