Manual Varlogic NRC12
Manual Varlogic NRC12
Manual Varlogic NRC12
User manual
USERS MANUAL
Menu Structure
First Startup
Language selection
Main Menu
BANK PRECONF
AUTO SETUP
MANUAL SETUP
MEASUREMENTS
PARAMETERS
ALARMS
MAINTENANCE
E
K
E
K
Language selection
Main Menu
COMMISSIONING
AUTO SETUP
MANUAL SETUP
MEASUREMENTS
PARAMETERS
ALARMS
MAINTENANCE
BANK PRECONF
COMMISSIONING
AUTO SETUP
MANUAL SETUP
Language
Application
Input Voltage
Wiring
Target Cos
Delays
Step Program
Step Setup
Language
Transformers
Target Cos
Verify
Transformers
Input Voltage
Target Cos
Search
Application
Transformers
Input Voltage
Wiring
Target Cos
Resp Values
Delays
Step Program
Step Setup
Verify
Sequences
USERS MANUAL
MEASUREMENTS
Base Display
1 2
Alarm Status
2
Alarm Log
+
-
OVERVIEW
VOLTAGE
THD(U)
THD(I)
IRms/I1
CURRENT
POWER
TEMPERATURE
Step Usage
PARAMETERS
ALARMS
Application
Transformers
Input Voltage
Wiring
Target Cos
Resp Values
Auto Seek
Delays
Step Program
Step Setup
Fixed Steps
Verify
Step Test
Modbus Setup
Language
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Alarm
Menus
1 Params
2 Params
3 Params
4 Params
5 Params
6 Params
7 Params
8 Params
9 Params
10 Params
11 Params
12 Params
KK
MAINTENANCE
Controller Info
Temp Limits
Step Usage
Clear Stats
Alarm Log
Clr Alarm Log
Bank Test
Factory Config
OVERVIEW
For experts
USERS MANUAL
Table of Contents
1. General ........................................................................................................................................5
1.1 Safety .....................................................................................................................................5
1.2 Environmental conditions........................................................................................................5
1.3 Description..............................................................................................................................6
2. Installation ....................................................................................................................................9
3. Display .......................................................................................................................................12
4. Start-up Procedure .....................................................................................................................13
5. Menu Operations........................................................................................................................14
5.1 General .................................................................................................................................14
5.2 Main Menu ............................................................................................................................16
5.3 Bank Pre-Configuration ........................................................................................................18
5.4 Commissioning .....................................................................................................................19
5.4.1 Commissioning sequence ..............................................................................................19
5.4.2 List of errors ...................................................................................................................20
5.5 Auto Setup of Parameters ....................................................................................................21
5.6 Manual Setup of Parameters ................................................................................................22
5.7 Measurement Menu..............................................................................................................24
5.8 Parameters ...........................................................................................................................26
5.9 Alarms Menu.........................................................................................................................29
5.10 Maintenance menu .............................................................................................................31
6. Miscellaneous ............................................................................................................................33
6.1 Stepping programs ...............................................................................................................33
6.2 Manual calculation of response value...................................................................................36
6.3 High voltage application of NRC12.......................................................................................38
7. Options .......................................................................................................................................40
7.1 External Temperature Sensor...............................................................................................40
7.2 Controller Communication Adapter.......................................................................................40
8. Glossary .....................................................................................................................................41
9. Technical specifications .............................................................................................................44
USERS MANUAL
1. General
1.1 Safety
The following precautions must be taken into account when installing and operating the controller
x
x
x
x
x
For better understanding of the terminology used, please refer to the Glossary (chapter 8) at the
end of this manual.
USERS MANUAL
1.3 Description
Front view:
B
E
Legend
A
B
C
D
E
Display
Keys
Opening of door
Door
Mounting bracket for panel mounting installation
USERS MANUAL
Rear view:
M
L
K
J
Legend
F
G
H
I
J
K
L
M
USERS MANUAL
Side view:
Legend
N
O
USERS MANUAL
2. Installation
The controller is designed for either panel (cut-out 138 x 138 mm) or DIN-rail installation. It is
locked to a panel by a side fitting springs or to the rail by a screwdriver-operated fixing spring.
There are two ways of connecting the controller to the network.
Voltage LN (Line Neutral)
Separated inputs exist for measurement voltage ("U1" and " U2") and supply voltage ("0V" and
"110V"/"230V"/"400V"). The controller can automatically correct incorrect measurement
connection when Auto Setup is selected from the main menu.
External temperature sensor can be installed close to the devices to be watched and connected to
inputs "T1" and "T2". The cable used needs to be certified to national requirements relevant to
controller installation voltage.
Alternative target cos M can be controlled by using external relay contact connected between
inputs "M1" and "M2". The cable used needs to be certified to national requirements relevant to
controller installation voltage.
Caution:
Notes on installation:
A switch or circuit-breaker shall be included in the building installation. It shall be in close
proximity to the equipment and within easy reach of the operator. It shall be marked as the
disconnecting device for the equipment. An equipment switch or circuit-breaker employed as a
disconnecting device shall comply with relevant requirements of IEC 60947-1 and IEC 60947-3.
Overcurrent protection devices such as fuse or miniature circuit breaker with a rating of no more
than 10 A shall be connected in supply conductors. The overcurrent protection devices need to be
certified to national requirements.
10
400V 50/60 Hz
L1
L2
L3
N
PE
Bank
ON/OFFswitch
Fuses max. 10 A
U2
U1
R1
R2
R3
R4
R5
R6
C
S1
S2
T1
T2
400V
230V
110V
0V
Select switch
for
cos M2
M1
M2
Rear view
Alarm
circuit
A
B
F1
F2
C
R7
R8
R9
R10
R11
R12
Fan
Capacitor
step 1
External
temperature
probe
No connection
Capacitor
step 12
LOAD
11
400V 50/60 Hz
U1
R1
R2
R3
R4
R5
R6
C
S1
S2
T1
T2
Select switch
for
cos M2
400V
230V
110V
0V
L1
L2
L3
N
PE
Bank
ON/OFFswitch
Fuses max. 10 A
M1
M2
Rear view
Alarm
circuit
A
B
F1
F2
C
R7
R8
R9
R10
R11
R12
Fan
Capacitor
step 1
External
temperature
probe
No connection
Capacitor
step 12
LOAD
USERS MANUAL
3. Display
The controller is equipped with a backlighted dot matrix display with a resolution of 128 x 64
pixels.
Essential indicators:
12
USERS MANUAL
4. Start-up Procedure
Before connecting power, check the wiring of all controller terminals. Check carefully for correct
operating voltage. Selection of wrong voltage input can permanently damage the controller.
After the first power switch-on, the controller will automatically ask for the language setting of the
menu.
13
USERS MANUAL
5. Menu Operations
5.1 General
Navigation between different menu levels
As a precaution against accidental use, the access of certain menus has been protected by a
keylock, which is a special sequence of keystrokes enabling the use the particular menu item.
Code lock is automatically closed after the home delay (5 minutes from last keystroke).
14
USERS MANUAL
Adjusting a value
?-button provides information and browsing help for the current controller
screen.
15
USERS MANUAL
16
USERS MANUAL
(5) Measurement
The measurement menu contains the most common
measurements taken from the network and provides some
information about the bank. This is a read-only menu.
(6) Parameters
At any time, an experienced user can access the most
common operating parameters from this menu. Unlike the
configuration and setup sequences, this is a menu allowing
a free and unrestricted entry into all its items and should be
used when an occasional parameter access is needed.
(8) Maintenance
The maintenance menu provides useful information about
the usage of the bank, capacitors and contactors. Auxiliary
settings and action have also been provided. This menu is
basically intended for use by the manufacturers
maintenance team.
Figure 8: Main menu
17
USERS MANUAL
18
USERS MANUAL
5.4 Commissioning
19
USERS MANUAL
Code
Meaning
Action to do
1 Unstable network
Reserved
Wiring verify error: Controller wiring not
correct.
Disconnected bank disables Verify and Search functions and "Alarm with shutdown"-text
will be shown in the Verify / Search - result screen.
20
USERS MANUAL
21
USERS MANUAL
This menu item is a forced sequence, meaning that all items must be accessed before the
validation of the setup takes place. The sequence can be interrupted by pressing
key.
22
USERS MANUAL
23
USERS MANUAL
U1
THD(U)
IRMS/I1
Q
Temp
Description
List of detected alarms. A = Active alarm.
Log of 5 latest alarms. Alarm log can be cleared using
"Clear Alarm Log"-function in Maintenance menu.
Input voltage (VLL Line to Line or VLN Line to Neutral)
Total harmonic distortion of voltage
Capacitor overload factor
Reactive power
Internal temperature
24
USERS MANUAL
Screen
Item
Description
VOLTAGE
U1
THD(U)
THD(U)
THD(I)
IRMS/I1
CURRENT
POWER
TEMPERATURE
STEP USAGE
Active
Reactive
Apparent
Active
Reactive
Apparent
Internal
External
25
USERS MANUAL
5.8 Parameters
CAUTION:
In case of installation in a HV bank (with VT), you must adjust the default
factory settings. The reconnection delay must be changed to a larger value
(e.g. 600 secs) to prevent destruction of capacitors.
The most common operating parameters can be accessed from this menu.
Unlike the configuration and setup sequences presented earlier in this text, this is a menu allowing
a free and unrestricted entry into all of its items and should be used when occasional parameter
access is needed. Restart the controller after major changes in parameters.
To start the step size monitoring, set number of steps, step sequence and the size of the 1st step
(reactive power and voltage), initialize the measurement (asked when exiting the editor). If
wanted, set the alarm on from the alarm menu. If the step size is set to 0 the step size monitoring
is disabled.
Step size monitoring cannot be used when
loads change constantly and rapidly
if the 1st step is very small compared to total measurement scale
if HV application is selected (automatically disabled)
Fixed steps cannot be monitored or verified. Setting 1st step fixed disables also search and seek
functions.
See Glossary (chapter 8), for parameter definitions.
In case of error in verifying, refer to error table, page 20.
26
USERS MANUAL
Parameter Explanations:
Screen
Item
Description
Application
2 Quadrant
4 Quadrant
100-700V
0,5-50kV (VT)
10-400kV (VT)
27
USERS MANUAL
Screen
Item
Description
Transformers
CT
VT
Input Voltage
Wiring
Voltage Phase
CT Phase
CT Polarity
Target Cos
Cos 1
Cos 2
Resp Values
Inductive
Capacitive
Auto Seek
Delays
Reconnection
Step Program
Step Setup
Num of Steps
Step Seq
28
Screen
Item
Description
1st Step
Voltage
Fixed Steps
Verify
Step Test
Modbus Setup
Status
Mode
Address
Bits/s
Language
USERS MANUAL
29
USERS MANUAL
Alarm
Description
Out of Steps
2
3
4
5
Hunting
Abnormal Cos M
Low voltage
Over Compensation
Wrong frequency
7
8
9
Over Current
Over Voltage
Over Temperature
10
11
12
10 min
Ind. < 0.50, cap. < 0.80
80%
+- 2 Hz of nominal at startup
115% of nominal
110%( 30 min ) or 120%(1 min)
Temperature limit setting, default
50qC
THD(U) limit setting, default 7%.
IRMS/I1 limit setting, default 1.5.
Capacitor value < 75 % nominal
Alarm
Possible cause
Controller action
Out of Steps
Hunting
Abnormal cos M
4
5
Low voltage
Over Compensation
Wrong frequency
7
8
Over Current
Over Voltage
Over Temperature
10
Harmonic pollution
Resonance
11
Cap Overload
12
Defective capacitor
Wiring mistake
Over capacitive network (welded contactors)
Too low current
Disconnection till voltage returns
Wiring or LL/LN definition error
Improper use of fixed steps
Wrong or unstable network frequency detected
at startup
Undersized CT
In case of Alarm 12 user can set the defective capacitor Fixed OFF to clear the alarm situation.
30
USERS MANUAL
Description
Alarm Status
Mode
Disconnection
Limit
31
USERS MANUAL
Item
Description
Controller info
S/N
Program vers
Uptime
Alarm limit
Serial number
Software version
Power on hours
Display for temperature alarm limit
Fan offset
Fan limit
Limit Settings
Step Usage
Clear Stats
Alarm Log
Clr Alarm Log
Bank Test
Factory Config
32
USERS MANUAL
6. Miscellaneous
6.1 Stepping programs
The controller's algorithm will try to reach the target cos M inside a tolerance area dependant
upon the C/K value, figure 18. It reaches the value by switching on or off available relevant steps.
The regulation program choice follows the steps definition :
a) Stack Program (linear) :
All capacitor steps are of equal size (i.e :1.1.1.1). The operation sequence obeys to a last-in-firstout (LIFO) principle. The first step connected will be the last one to be disconnected and vice
versa. See Table 1.
b) Normal program (2+ linear)
Normal program can be used on bank whose step ratio is 1.2.4.4.. The linear sequence starts with
the 3rd step. The two first steps are used as fine-tuning. The controller always start by switching
the first step then the second. Other steps are used successively See Table 2.
c) Circular 1:1:1 program
All capacitor steps are of equal size (i.e :1.1.1.1). The operation sequence obeys the first-in-firstout (FIFO) principle. With this stepping program the amount of on- and off-connections at each
step will eventually be the same. The first step connected will be the first one to be disconnected
and vice versa. Then a circular sequence is followed. In order to operate correctly, the number of
steps programmed into the controller must strictly comply with the number of physical steps
See Table 3.
d) Circular 1:2:2 program (1+Circular)
Circular B program can be used on a bank whose step ratio is 1.2.2.2. The first step is used as
tuning after the activating limit is exceeded. The circular sequence starts with the 2nd step. See
Table 4.
e) Optimal Program :
The optimal program operates with many step configurations:
1.1.1.1.1
1.2.3.3.3
1.1.2.2.2
1.2.3.4.4
1.1.2.3.3
1.2.3.6.6
1.1.2.4.4
1.2.4.4.4
1.2.2.2.2
1.2.4.8.8
The target cos M power is reached using the fewest number of steps in minimal time. Like the
circular program, this algorithm equalizes the usage of largest steps.
This program uses optimally selected step sizes when approaching the target power and at the
same time the response delays are shortened, particularly if there is a large requirement for
compensation power or if the network suddenly becomes capacitive. As circular program, this
stepping program keeps the usage of steps even.
Optimal program is disabled with fixed steps and vice versa.
33
+
+
+
+
+
+
+
+
+
-
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Step number
2 3 4 5
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
USERS MANUAL
Step
demand
+
+
+
+
+
+
+
-
1
X
X
X
X
X
X
X
Step number
2 3 4 5
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Step
demand
+
+
+
+
+
+
+
+
-
1
X
X
X
X
X
X
X
Step number
2 3 4 5
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Step
demand
+
+
+
+
+
+
+
+
+
-
X
X
X
X
X
X
1
X
X
X
X
X
X
X
X
X
Step number
2 3 4 5
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
34
USERS MANUAL
35
USERS MANUAL
C/K
Q1
I1 5 A u U LL u 3
where Q1
ULL
I1/5A
=
=
=
Alternatively, the C/K value can be taken from the table below (valid for 400 V networks)
1st
step
(kvar)
5
7,5
10
12,5
15
18,5
20
25
30
37,5
40
50
60
75
90
100
120
150
200
50
0,72
1,08
1,44
1,80
20
100
0,36
0,54
0,72
0,90
1,08
1,34
1,44
1,80
30
150
0,24
0,36
0,48
0,60
0,72
0,89
0,96
1,20
1,44
1,80
1,92
40
200
0,18
0,27
0,36
0,45
0,54
0,67
0,72
0,90
1,08
1,35
1,44
1,80
60
300
0,12
0,18
0,24
0,30
0,36
0,45
0,48
0,60
0,72
0,90
0,96
1,20
1,44
1,80
CT n1/n2
80 100 120 160 200 300 400 500 600 /1
400 500 600 800 1000 1500 2000 2500 3000 /5
0,14
0,18
0,23
0,27
0,33
0,36
0,45
0,54
0,68
0,72
0,90
1,08
1,35
1,62
1,80
0,11
0,14
0,18
0,22
0,27
0,29
0,36
0,43
0,54
0,58
0,72
0,87
1,08
1,30
1,44
1,73
0,12
0,15
0,18
0,22
0,24
0,30
0,36
0,45
0,48
0,60
0,72
0,90
1,08
1,20
1,44
1,80
0,11
0,14
0,17
0,18
0,23
0,27
0,34
0,36
0,45
0,54
0,68
0,81
0,90
1,08
1,35
1,80
0,11
0,13
0,14
0,18
0,22
0,27
0,29
0,36
0,43
0,54
0,65
0,72
0,87
1,08
1,44
0,10
0,12
0,14
0,18
0,19
0,24
0,29
0,36
0,43
0,48
0,58
0,72
0,96
0,11
0,14
0,14
0,18
0,22
0,27
0,32
0,36
0,43
0,54
0,72
0,11
0,12
0,14
0,17
0,22
0,26
0,29
0,35
0,43
0,58
0,10
0,12
0,14
0,18
0,22
0,24
0,29
0,36
0,48
36
USERS MANUAL
37
USERS MANUAL
In case of installation in a HV bank (with VT), you must adjust the default
factory settings. The reconnection delay must be changed to a larger value
(e.g. 600 secs) to prevent destruction of capacitors.
The controller can be used in HV networks, if the following points are taken into account.
Connections must employ VT and CT with respect to the figure 19.
The application menu has two voltage ranges for HV applications: 0.5 - 50 kV and 10 - 400 kV.
The lower voltage range has finer VT ratio resolution and range than the higher voltage range.
Safety (or reconnection) delay must be adapted to the value of the discharge resistors of the
capacitors, the most usual value is 600 seconds (10 minutes). The controllers default
reconnection delay is adapted for LV use. Using too short a reconnection delay may damage the
capacitors.
Important:
the whole commissioning process must be performed using the Parameter menu
the commissioner should not use Bank Pre-Configuration, Manual Setup and Commissioning
menus
the use of Auto Setup menu is strictly forbidden to prevent capacitor destruction
do not use "Verify" or "Auto Seek" on HV network applications!
38
39
Example
20 kV 50/60 Hz
20 kV
100 V
U2
R1
R2
R3
R4
R5
R6
C
L1
L2
L3
PE
Fuses max. 10 A
L
Auxiliary voltage
230VAC
N
M1
M2
S1
S2
T1
T2
400V
230V
110V
0V
Rear view
Alarm
circuit
A
B
F1
F2
C
R7
R8
R9
R10
R11
R12
Capacitor
step 12
Aux. voltage
Aux. voltage
Capacitor
step 1
Aux. voltage
Aux. voltage
No connection
LOAD
USERS MANUAL
7. Options
7.1 External Temperature Sensor
The controller has terminals T1/T2 for external temperature sensor. With the external temperature
probe the temperature in a critical point in a capacitor bank can be monitored with the controller.
The external temperature measurement overrides the internal temperature in fan and alarm
monitoring. The External Temperature Sensor can be purchased as an option and installed into
the capacitor bank.
Do not touch the connectors when the controller is energized, make sure that the operating
voltage is disconnected before touching any parts located on the rear side of the controller
Always switch off the power from the controller before installation. Make
sure that the communication connector is always covered, either with
CCA-01 adapter or the original cover before switching on the power.
Touching an uncovered connector with the power applied may lead to an
electrical shock.
40
USERS MANUAL
8. Glossary
Display
information
Description
1st STEP
(Step Setup)
Max value
>1,10u
Inom
ADDRESS
(Modbus Setup)
ALARM LIST
List of detected active (A) and passive alarms. Reset
clears passive alarms.
ALARM LOG
Log of 5 latest alarms
ALARMS
Alarm Menu
ALARM STATUS ACT = Alarm active and triggered
PAS = Alarm passive.
APPLICATION
Power flow and network voltage level of the capacitor
bank. 2 quadrant = only power consumption (typical
situation). 4 quadrant = power generation possible.
Application is forced to 4 quadrant in Auto Setup.
AUTO SEEK
Automatic search of C/K response value
AUTO SETUP
Automatic Setup Sequence
BANK PRECONF Bank Pre-configuration Sequence
BANK TEST
Bank Test: each step is automatically connected and
disconnected in turn. This facilitates testing of the
operation of each capacitor step contactor. To be used
only for testing offline capacitors! Do not use in HV
network applications! See also Step Test.
BITS/S
Data transmission speed of the controller
(Modbus Setup)
CAPACITIVE
Response value for the capacitive side of the target
(Resp Values)
cos M. Normally set up automatically by the controller.
Detected in Auto Setup and Auto seek, or manually if
wanted. Checked with verify function.
CCA
The controller has a connector for CCA communication
module (option).
CIRCULAR 1.1.1
Circular stepping program for sequence 1.1.1.1.1.1
CIRCULAR 1.2.2 Circular stepping program for sequence 1.2.2.2.2.2
C/K
Response value. Can be manually set up or
automatically searched by the controller.
CLEAR STATS
Clear Statistics
CLR ALARM LOG Clear Alarm Log
COMMISSIONING Commissioning Sequence
COS 1
Target cos M value 1 (normally used)
(Target cos M)
COS 2
Target cos M value 2 (selected by control input)
(Target cos M)
CT
Current Transformer setting, xxx/5 or xxx/1
(Transformers)
CT PHASE
Example: CT phase L1. Current connected to phase 1.
(Wiring)
Detected in Auto Setup and Auto seek, checked with
verify function. See also Installation (chapter 2).
41
<0,025u
Inom
0 kvar
200V
0 kvar
400V
400 kvar
800V
247
1200
9600
38400
See
"C/K".
0,01
0,50
1,99
0,8ind
1.00
0,9cap
0,8ind
1.00
0,9cap
25/1
25/5
1000/5
6000/1
6000/5
L1
Display
information
CT POLARITY
(Wiring)
DISCONNECTION
(Alarm Paras)
EXT
USERS MANUAL
Description
Current polarity selections:
DIRECT = direct connection
REVERSE = inverted connection
AUTO = automatic polarity (controller identifies polarity
in 2 quadrant applications, disabled in 4 quadrant)
Disconnection of steps in case of alarm, ON/OFF
42
Max value
ON 9
OFF 2,10
0C
20C
50C
(automatic)
See
"C/K".
80V
400V
800V
20 qC
English
50 qC
60 qC
5%
7%
20%
1,0
1,5
1,5
NONE
12
12
Display
information
RECONNECTION
(Delays)
SEARCH
SECONDARY
(Input Voltage)
S/N
(Controller Info)
STACK
STATUS
(Modbus Setup)
STEP PROGRAM
STEP SEQ
(Step Setup)
STEP TEST
USERS MANUAL
Description
Max value
900s
150V
STEP USAGE
THD (I)
THD (U)
TRANSFORMERS
UPTIME
(Controller Info)
VERIFY
Automatic verification of parameters. Checks C/K
value, steps and wiring. In case of an error refer to
error table, page 20.
Do not use on HV network applications!
VT
0.5 50 kV 1.0
Voltage Transformer ratio setting.
(Transformers)
10 400 kV 60
VOLTAGE PHASE Connections of voltage inputs.
(Wiring)
Example : Voltage phase L2-L3
(Voltage connected between phase 2 and 3)
Detected in Auto Setup and Auto seek, checked with
verify function. See also Installation (chapter 2).
43
1.0
L2-L3
625.0
4000
USERS MANUAL
9. Technical specifications
Number of steps
Dimensions
Frequency
Measuring current
Measuring voltage
Displayed measuring power
Nominal power consumption
Supply voltages
Relay inputs/outputs
Display
Protection class
Target cos M -range
Response limits
Reconnection delay
Response delay
Displayed measurements
Installation method
Casing
Operating temperature range
Alarm log
Step counters
Fan control with dedicated relay
Alarm relay
Accuracy (of FS)
CT setting range
Power outage detection
Standards
Communication
12
155 x 158 x 80 mm
50 Hz nominal (range 48...52 Hz)
60 Hz nominal (range 58...62 Hz)
01 A or 0...5 A
80690 V (nominal, max. 115%)
100000 kVA
13 VA
110 V nominal, (range 88...130 V)
230 V nominal, (range 185...265 V)
400 V nominal, (range 320...460 V)
250 V, 2 A
Dot matrix display, resolution 64x128 pixels,
backlighted
IP41 front panel, IP20 rear part
0,85 ind 1,00 0,90 cap
0,01 1,99, symmetrical or asymmetrical
10900 s
20 % of reconnection delay, min. 10 s
cos M, Iact, Ireact, Iapp, IRMS/I1, P, Q, S, THD(U)
and voltage harmonics, THD(I) and current
harmonics, internal and external temperature.
Panel installation, DIN-rail installation
Impact resistant PC/ABS, UL94V-0
060qC
List of 5 last alarms
Yes
Yes. 250 V AC, 8A
Yes. 250 V AC, 8A
I : 2%
IQ : 2%
U/I-samples: 2%
Phase: 1q
Distortion: r3 dB (up to 15th)
Internal temperature: r3qC
External temperature: r2qC (option)
25/1 6000/1 or 25/5 6000/5
Reaction time > 15 ms
IEC 61010-1
IEC 61000-6-2
IEC 61000-6-4
UL 61010A-1
IEC 60529
Modbus protocol using CCA-01 (option)
44
N3653493EN-AA
07-2005