E550 Seri 2
E550 Seri 2
E550 Seri 2
ZMG310AR/CR
E550 Series 2
Technical Data
Date: 20.01.2012
File name: D000029744 E550 ZMG310xR Series 2 Technical Data en.docx
Landis+Gyr
D000029744 en h
2/10
Revision history
Version
Date
Comments
17.02.2010
First edition
be
23.07.2010
Continuous improvement
01.12.2011
02.12.2011
20.01.2012
New extension boards 060 with 6 output contacts and 240 with 2 control inputs and
4 output contacts.
Nothing in this document shall be construed as a representation or guarantee in respect of the performance, quality or durability of the
specified product. Landis+Gyr accepts no liability whatsoever in respect of the specified product under or in relation to this document.
Subject to change without notice.
Landis+Gyr
3/10
The E550 direct connected I&C meters record
active and reactive energy consumption in 1-phase
2-wire, 2-phase 3-wire, 3-phase 4-wire and 3-phase
3-wire (no neutral) networks.
Basic Version
The basic version provides energy registers for
tariffication, red test diodes for active and reactive
energy, an optical interface for meter reading and
an electrical interface.
Interfaces
The Series 2 now supports two independent electrical interfaces.
The meter supports RS232, RS485, RS422, CS
and a specially powered RS232 to supply external
modems.
Installation support
The monitoring of voltage, current, demand and
power factor supports the installation.
Measurement Behaviour
Voltage
Nominal voltage Un ZMG310xR
3 x 220/380 V to 240/415 V
3 x 110/190 V to 133/230 V
3 x 110/190 V to 277/480 V
Voltage range
80% to 115% Un
Frequency
Starting current
According to IEC
0.4% Ib
Typical
0.3% Ib
The startup of the meter is controlled by the starting
power and not by the starting current.
Starting power in M-circuit
Nominal voltage x starting current
MID-specific Data
Nominal frequency fn
Tolerance
50 or 60 Hz
2%
Application
1 phase 2 wire; 2 phase 3 wire; 3 phase 4 wire, 3phase 3-wire (without neutral)
IEC-specific Data
selectable: 5, 10, 20 or 40 A
0.1 x Iref
125 A
80 A
Short circuit 10 ms
10,000 A
to EN 50470-3
class B
Measurement Behaviour
Starting current Ist
0.004 x Iref
General
Operating Behaviour
Measurement Accuracy
ZMG310xR
Active energy, to IEC 62053-21
Reactive energy, to IEC 62053-23
Measurement Accuracy
ZMG310xR
0.05 x Iref
Current
Base current Ib
single phase
class 1
class 2
0.5 s
after another 0.2 s
after approx. 10 s
Landis+Gyr
4/10
Insulation Strength
Insulation strength
Power Consumption
Environmental Influences
Temperature range
Operation
Storage
to IEC 62052-11
40 C to +70 C
40 C to +85 C
Temperature coefficient
Range
25 C to +70 C
Average value (typical)
0.012% per K
At cos=1
(from 0.05 Ib to Imax) 0.02% per K
0.03% per K
At cos=0.5 (from 0.1 Ib to Imax)
Impermeability to IEC 60529
IP 53
Electromagnetic Compatibility
Electrostatic discharges
Contact discharge
Air discharge
to IEC 61000-4-2
8 kV
15 kV
Electromagnetic RF fields
80 MHz to 2 GHz
to IEC 61000-4-3
10 and 30 V/m
Landis+Gyr
4 kV at 50 Hz during 1 min.
to IEC 62052-11
10 kV
6 kV
2
Calendar Clock
Calendar Type
Gregorian or Persian (Jalaali)
Accuracy
< 5 ppm
Display
Characteristics
Type
LCD liquid crystal display
Digit size in value field
9 mm
Number of digits in value field
up to 8
Digit size in index field
8 mm
Number of digits in index field
up to 7
5/10
Communication Interface
Optical interface
to IEC 62056-21
Type
serial, asynchronous, half-duplex
Max. transmission rate
19,200 bps
Protocols
IEC 62056-21 and dlms
RS232 Interface (powered and not powered)
to DIN 61393 / DIN 66259
Type
serial, asymmetric, asynchr., bidirectional
Operating mode
intelligent or transparent
Nominal voltage
9 VDC
Maximum voltage
15 VDC
Minimum voltage
5 VDC
Max. transmission rate
38,400 bps
Protocols
IEC 62056-21 and dlms
Max. conductor length depending on
environment and connecting cable
30 m
Insulation resistance to meter 4 kVAC/50 Hz, 1 min
Creep distance
6.3 mm
RS485 Interface
to ISO-8482
Type
serial, symmetrical, half duplex
Nominal input voltage common mode range
7 to +12 VDC
Binary 1 state
difference voltage < 0.2 V
Binary 0 state
difference voltage > 0.2 V
Max. transmission rate
38,400 bps
Max. number of slaves
31
Protocols
IEC 62056-21 and dlms
Max. conductor length depending on
environment and connecting cable
1000 m
Insulation resistance to meter 4 kVAC/50 Hz, 1 min
Creep distance
6.3 mm
CS Interface
to IEC 62056-21 / DIN 66258
Type
serial, bidirectional, current interface
Nominal voltage without load
24 VDC
Max. voltage without load
30 VDC
Binary 1 state
1030 mA
Binary 0 state
2 mA
Max. transmission rate
9600 bps
Protocols
IEC 62056-21 and dlms
Insulation resistance to meter 4 kVAC/50 Hz, 1 min
Creep distance
6.3 mm
RS422-Interface
to ISO-8482
Type serial, symmetric, asynchronous, bidirectional
Nominal input voltage common mode range
3 to +3 VDC
Binary 1 state
difference voltage < 0.2 V
Binary 0 state
difference voltage > 0.2 V
Max. transmission rate
38,400 bps
Max. number of slaves
10
Protocols
IEC 62056-21 and dlms
Max. conductor length depending on
environment and connecting cable
1000 m
Insulation resistance to meter 4 kVAC/50 Hz, 1 min
Creep distance
6.3 mm
approx. 1.5 kg
External dimensions
Width
Height (with short terminal cover)
Height (with standard terminal cover)
Height (with extended hook)
Depth
177 mm
244 mm
281.5 mm
305.5 mm
75 mm
Suspension triangle
Height (with extended hook)
Height (suspension eyelet open)
Height (suspension eyelet covered)
Width
Terminal cover
Short
Standard
Long (opaque, transparent)
Standard
Standard
GSM
RCR/FTY adapter
ADP1 adapter
230 mm
206 mm
190 mm
150 mm
no free space
40 mm free space
60 mm free space
80 mm free space
110 mm free space
60 mm free space
Material
Housing
Polycarbonate, partly glass-fibre reinforced
Connections
Phase connections
Type
cage type terminals
Cross section
9 x 9 mm
Min. conductor cross section
2.5 mm2
2
Max. cross section cable
35 mm (up to 125 A)
Max. cross section strand
25 mm2 (up to 80 A)
Screw head
Pozidrive Combi No. 2
Screw dimension
M6 x 14
Screw head diameter
6.6 mm
Tightening torque
3 to 5 Nm
Landis+Gyr
6/10
RS422-Interface
Type designation
Type
Pin assignment
Connections (cont.)
RS232 Interface
Type designation
Type
Pin assignment
.02/.42/.62
RJ 12
1
RS485 Interface
Type designation
Type
Pin assignment
6
1
1
2
3
4
5
6
1
2
3
4
5
6
RS422
RS422
1
2
3
4
5
6
GND
U P (Data a)
U N (Data b)
U N (Data z)
UP (Data y)
GND
.03/.43/.63/.37
RJ 12
RS232 powered
Type designation
Type
Pin assignment
c (common ground)
a (data a)
b (data b)
b
a
c
CS Interface
Type designation
Type
CTS
TxD
GND
DTR
RxD
DSR
.60/.62/.63
RJ 12
.40/.42/.43
screw type terminals
.07/.37
RJ 45
8
1
2
3
4
5
6
7
8
NC
CTS
TxD
GND
NC
RxD
NC
V+ (10 ... 14 V)
281.5
206
40
26
190
75
150
177
75
The height of the suspension triangle with extended hook is 230 mm. See also User Manual.
Landis+Gyr
7/10
Terminal Dimensions
5
13.5
Terminal Layout
Communication
interfaces
Voltage
outputs
U2
U1
U3
optical
separation
of phases
L1
L2
L3
Phase connections
Communication
interfaces
Voltage
outputs
U1
U2
U3
optical
separation
of phases
L1
L2
L3
Phase connections
Landis+Gyr
8/10
Type designation
ZMG
10
CR
4.
260
b.
43 S2
Network type
ZMG
Connection type
3
Direct connection
Accuracy class
10
Measured quantities
CR
AR
Tariff functions
1
2
3
4
Additional functions
0
3
4
7
a
b
None
With software events
With hardware and software events
With load profile
With load profile and software events
With load profile, hardware and software events
40 CS*
42 CS and RS232*
43 CS and RS485*
60 RS422**
62 RS422 and RS232**
63 RS422 and RS485**
07 Powered RS232***
37 RS485 and
Powered RS232***
Landis+Gyr
9/10
Landis+Gyr
Contact:
Landis+Gyr (Europe) AG
Theilerstrasse 1
CH-6301 Zug
Switzerland
Phone: +41 41 935 6000
www.landisgyr.com