WinCC To Customer Computer
WinCC To Customer Computer
No. Procedure
1
Once you have done the data backup, no more configuring should be performed on the customer
computer, because any changes in the configuration will be overwritten when the configuration
data is loaded from the configuration computer.
2
You can create new tags, pictures, messages and archives and/or change existing ones.
However, make sure that you never delete existing archive tags to create them anew
possibly with different parameters. When you create new tags, archives or messages, the
system gives them an internally unique number (ID). These IDs change when the tags,
archives or messages are created anew. If the ID of an archive tag changes, or the ID no
longer exists, because the archive has been deleted, then the old data of that archive tag
can no longer be displayed.
You can also test newly created measuring points without a real controller by using the "S7PLCSIM" software. The "S7-PLCSIM" software permits you to control/monitor the external
WinCC tags. The requirement is that the software products STEP 7, S7-PLCSIM and WinCC
The repeated data backup saves the actual status of the Runtime data. The last backup
might have been made some time ago.
If you have made changes to the configuration since the last backup of the project on the
customer computer, then this data backup saves these changes.
Move the Runtime database from the renamed project path to the
current project path
In the current project directory you delete the following files and
directories:
ArchiveManager
<Project>RT.mdf
<Project>RT.ldf
<Project>Tlg.mdf
<Project>Tlg.ldf
<Project>Alg.mdf
<Project>Alg.ldf
Fig. 01
Copy the following files and directories from the renamed WinCC
project path into the current project path:
ArchivManager
<Project>RT.mdf
<Project>RT.ldf
Do not copy the following files, because if not available, they are regenerated
automatically the next time the Runtime starts:
<Project>Tlg.mdf
<Project>Tlg.ldf
<Project>Alg.mdf
<Project>Alg.ldf
If one of the backup paths (destination paths) configured is located in the
WinCC project path, you must also replace this path with the identically
Fig. 02
Fig. 03
8
Start Runtime
Start the WinCC Runtime on the customer computer. Test the functionality.