Electricity Meters IEC/MID

Industrial and Commercial

ZMD405AT/CT, ZFD405AT/CT,
ZMD410AT/CT, ZFD410AT/CT

E650 Series 3 (ZMD400AT/CT,


ZFD400AT/CT)
Technical Data

Date: 27.01.2011
Filename: D000030106 E650 ZxD400xT series 3 Technical Data EN e.docx
Landis+Gyr Investments AG

D000030106 EN e

2/8

Revision history
Version

Date

Comments

27.01.2011

Updated document template and Chapter 1.3 table entry 045x 4


outputs, additional power supply 100-240 VAC/VDC

Copyright 2010-2011 Landis+Gyr Investments AG. Subject to change without notice.

All Landis+Gyr products and solutions have been designed and developed for the best possible performance. Performance of this product
may vary depending on the system environment. You are strongly advised to only use solutions and products recommended by Landis+Gyr.
It is strictly forbidden to make any changes, alterations or modifications whatsoever to the product without the prior written permission of
Landis+Gyr.
If you use solutions or products not recommended by Landis+Gyr, or if the product is changed, altered or modified in any way, you agree to
assume all responsibility and risk for the use of such system, and all possible warranties from Landis+Gyr are immediately voided.
Landis+Gyr will not be liable for any loss or damage, including without limitation any direct, indirect, consequential, special or incidental
damages arising out of, based on, or resulting from the use of non-recommended solutions or any such changed, altered or modified
products or product solutions.
No part of this document may be reproduced, stored in retrieval system, or transmitted in any form or by any means without the prior written
permission of Landis+Gyr.
Landis+Gyr assumes no responsibility for any errors in this document or for any damages, incidental or consequential, caused by use of this
document.
Landis+Gyr and Gridstream are trademarks of Landis+Gyr Investments AG.
Landis+Gyr system products include software developed by the following trademark owners: Oracle is a registered trademark of Oracle
Corporation. Java and J2EE are registered trademarks of Sun Microsystems, Inc. Microsoft and Windows are registered trademarks of
Microsoft Corporation. Adobe is a registered trademark of Adobe Systems. InstallShield is a registered trademark of InstallShield Software
Corporation. Ant software is developed by the Apache Software Foundation (http://www.apache.org/). Echelon, LON, LonWorks, LonTalk
and Neuron are registered trademarks of Echelon Corporation.
Other brand or product names mentioned in this manual may also be trademarks or registered trademarks of their respective owners and
are used here for identification only.
Landis+Gyr Investments AG

D000030106 EN e E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) Technical Data

3/8
The E650 transformer connected I&C meters
record active and reactive energy consumption in
all three-phase four-wire and three-phase threewire networks.
Range
E650 meters are the answer to a wide range of
specific needs: from the reliable commercial meter
to the complex measuring device with comprehensive additional functionality for sophisticated data
acquisition and flexible tariff control of large industrial customers.

Modular communication
AT/CT-type meters are equipped with modular
communication units which provide the right choice
for the best data channel at all times. Plug+Play
modules also offer you full freedom of choice for
deployment of new communication technologies.

E650 Series 3 ZxD400AT/CT

Technical specifications
Measurement Accuracy

General

Voltage
Nominal voltage Un ZMD400xT
3 x 58/100 V to 69/120 V
3 x 110/190 V to 133/230 V
3 x 220/380 V to 240/415 V
extended operating voltage range
3 x 58/100 to 240/415 V

3 x 100 to 120 V
3 x 220 to 240 V
extended operating voltage range 3 x 100 to 415 V
80 to 115%

Frequency
Nominal frequency fn
tolerance

ZxD405xT
active energy, to IEC 62053-22
reactive energy, to IEC 62053-23

class 0.5 S
accuracy 1%

ZxD410xT
active energy, to IEC 62053-21
reactive energy, to IEC 62053-23

class 1
accuracy 1%

Measurement Behaviour

Nominal Voltage Un ZFD400xT

Voltage range

Installation support
An indication of phase voltages, phase angles,
rotating field and energy direction supports the
installation.

50 or 60 Hz
2%

Starting current ZxD405xT


according to IEC
typical
5||1 A

0.1% In
0.07% In
as 1 A meter

Starting current ZxD410xT


according to IEC
typical
5||1 A

0.2% In
0.14% In
as 1 A meter

The startup of the meter is controlled by the starting power


and not by the starting current.

Starting power in M-circuit


nominal voltage x starting current

IEC-specific Data

single phase

Current
Nominal Current In

1 A, 2 A, 5 A, 5||1 A

Maximal Current Imax


metrological 1 A
metrological 2 A
metrological 5||1 A
metrological 5 A
thermal 1 A, 2 A,5||1 A
thermal 5 A
Short Circuit Current

2 A, 10 A
4A
6A
200% In or 400% In
12 A
12 A or 24 A
0.5 s with 20 x Imax

Starting power in F-circuit


nominal voltage x starting current x 3

all phases

MID-specific Data

Current (for classes B and C)


Rated current In
Minimum current Imin

1.0 A, 2.0 A, 5.0 A


0.01 A, 0.02 A, 0.05 A

Transitional current Itr

0.05, 0.1 A, 0.25 A

Maximum current Imax

2.0 A, 4 A, 10.0 A or 20 A

D000030106 EN e E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) Technical Data

Landis+Gyr Investments AG

4/8

Measurement Accuracy

to EN 50470-3

ZxD400xT

classes B and C

Measurement Behaviour
Starting current Ist
class B: Ist
class C: Ist

0.002, 0.01 A
0.001, 0.005 A

General

Insulation strength
0.5 s
after another 0.2 s
after approx. 2.5 s

Voltage restoration (Power Up)


function standby 3 phases
after 2 s
function standby 1 phase
after 5 s
detection of energy direction and phase voltage
after 2 to 3 s

Power Consumption
Power consumption per phase in voltage circuit
phase voltage
58 V 100 V 240 V
active power (typical)
0.4 W 0.5 W 0.7 W
apparent power (typical)
0.8 VA 1.0 VA 1.7 VA
Power consumption per phase in current circuit
phase current
1A
5 A 10 A
active power (typical)
5 mW 0.125 W 0.5 W
apparent power (typical) 5 mVA 0.125 VA 0.5 VA

Environmental Influences
Temperature range
operation
storage

to IEC 62052-11
25 C to +70 C
40 C to +85 C

Temperature coefficient
range
25 C to +70 C
average value (typical)
0.012% per K
at cos=1
(from 0.05 Ib to Imax) 0.02% per K
at cos=0.5 (from 0.1 Ib to Imax)
0.03% per K
Impermeability to IEC 60529

IP51

Electromagnetic Compatibility
Electrostatic discharges
contact discharge

to IEC 61000-4-2
15 kV

Electromagnetic RF fields
80 MHz to 2 GHz

to IEC 61000-4-3
10 and 30 V/m

Radio interference suppression


according to IEC/CISPR 22
Landis+Gyr Investments AG

Fast transient surge test


current and voltage circuits
auxiliary circuits > 40 V

to IEC 61000-4-5
4 kV
1 kV

Insulation Strength

Operating Behaviour
Voltage failure (Power Down)
bridging time
data storage
switch off

Fast transient burst test


to IEC 61000-4-4
current and voltage circuits under load
according to IEC 62053-21/23
4 kV
auxiliary circuits > 40 V
2 kV

4 kV at 50 Hz during 1 min.

Impulse voltage 1.2/50 s


current and voltage circuits
auxiliary circuits

to IEC 62052-11
8 kV
6 kV

Protection class ll to IEC 62052-11

Calendar Clock
Calendar type

Gregorian or Persian (Jalaali)

Accuracy

< 5 ppm

Backup time (power reserve)


with supercap
charging time for max. backup time
with battery (optional)
battery type

> 20 days
300 h
10 years
CR-P2

Display
Characteristics
type
LCD liquid crystal display
digit size in value field
8 mm
number of digits in value field
up to 8
digit size in index field
6 mm
number of digits in index field
up to 8

Inputs and Outputs


Control inputs
control voltage US
input current

100 to 240 VAC


< 2 mA ohmic at 230 VAC

Output contacts
type
solid state relay
voltage
12 to 240 VAC/DC
max. current
100 mA
max. switching frequency (pulse length 20 ms) 25 Hz
Optical test outputs
type
number
meter constant

active and reactive energy


red LED
2
selectable

class B
D000030106 EN e E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) Technical Data

5/8

Communication Interface
Optical interface
to IEC 62056-21
type
serial, asynchronous, half-duplex
max. transmission rate
9600 bps
protocols
IEC 62056-21 and dlms
Communication Units
Exchangeable communciation units for various
applications.

Additional Power Supply (optional)


On Extension Board 045x
nominal voltage range
tolerance
frequency
max. power consumption

100 to 240 VAC/DC


80 to 115% Un
50 or 60 Hz
6.8 W

On Extension Board 046x


nominal voltage range
tolerance
max. power consumption

External dimensions
width
height (with short terminal cover)
height (with standard terminal cover)
height (with extended hook)
depth

Terminal cover
short
standard
long (opaque, transparent)
GSM
ZxB-type 80 mm
ZxB-type 110 mm
ADP1 adapter
RCR/FTY adapter

230 mm
206 mm
190 mm
150 mm

no free space
40 mm free space
60 mm free space
60 mm free space
80 mm free space
110 mm free space

Material housing
Polycarbonate, partly glass-fibre reinforced

12 to 24 VDC
80 to 115% Un
3.5 W

Weight and Dimensions


Weight

Suspension triangle
height (with extended hook)
height (suspension eyelet open)
height (suspension eyelet covered)
width

approx. 1.5 kg

177 mm
244 mm
281.5 mm
305.5 mm
75 mm

Connections
Phase connections
type
screw type terminals
diameter
5.2 mm
recommended conductor cross section 4 to 6 mm2
screw head
Pozidrive Combi No. 2
screw dimensions
M4 x 8
screw head diameter
5.8 mm
tightening torque
< 1.7 Nm
Other connections
type
screwless spring-type terminal
max. current of voltage outputs
1A
max. voltage of inputs
250 V

D000030106 EN e E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) Technical Data

Landis+Gyr Investments AG

6/8
Meter Dimensions (standard terminal cover)

extended hook: 230

190

40

26

standard hook: 206

75

150
177

12.5

Terminal Dimensions

5.2
16

10 10 10 10 10 10 10 10 10
150
168

Landis+Gyr Investments AG

D000030106 EN e E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) Technical Data

7/8
Terminal Layout according to DIN
Control inputs and/or
output contacts of
extension board

U2 U3

U1

I1

U1

I1 I2

U2

I2 I3

Pulse
inputs

Communication
interfaces
Communication unit

Control inputs
and/or
output contacts
Voltage outputs

U3

I3

N
Voltage connections
Current connections

Symmetrical Terminal Layout (optional, ZMD400 only)


Control inputs and/or
output contacts of
extension board

U2 U3

U1

I1

U1

I2

U2

I3

U3 N

Pulse
inputs

Communication
interfaces
Communication unit

Control inputs
and/or
output contacts
Voltage outputs

I3 I2 I1
Voltage connections
Current connections

D000030106 EN e E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) Technical Data

Landis+Gyr Investments AG

8/8
Type designation

ZMD

10

44

4207

S3

Network Type
ZFD
ZMD

3-phase 3 wire network (F-circuit)


3-phase 4 wire network (M-circuit)

Connection Type
4

Transformer operated

Accuracy Class
10
05

Active energy class 1 (IEC), B (MID)


Active energy class 0.5s (IEC), C (MID)

Measured Quantities
C
A

Active and reactive energy


Active energy

Construction
T

With exchangeable communication units

Tariffication
21
24
41
44

Energy rates, external rate control via control inputs


Energy rates, internal rate control via time switch
(additionally possible via control inputs)
Energy and demand rates, external rate control via control inputs
Energy and demand rates, internal rate control via time switch
(additionally possible via control inputs)
All versions with 3 control inputs and 2 output contacts

Additional functions
060x
240x
420x
045x
046x

6 outputs
2 control inputs, 4 outputs
4 control inputs, 2 outputs
4 outputs, auxiliary power supply 100 to 240 VAC/VDC
4 outputs, auxiliary power supply 12 to 24 VDC

xxx0
xxx2
xxx7
xxx9

no additional functions
DC-magnet-detection
load profile
DC-magnet-detection and load profile

Series 3

Contact:
Landis+Gyr (Europe) AG
Theilerstrasse 1
CH-6301 Zug
Switzerland
Phone: +41 41 935 6000
www.landisgyr.com

Landis+Gyr Investments AG

D000030106 EN e E650 Series 3 (ZMD400AT/CT, ZFD400AT/CT) Technical Data