0% found this document useful (0 votes)
165 views2 pages

JHJJK

This document discusses proper routing of ground return conductors when using window-type current transformers (CTs) or fault current indicators (FCIs) for protective relaying of shielded power cables. It explains that the grounding conductor on cable shields must be routed back through the CT before grounding to allow detection of phase-to-ground faults. Similarly, the concentric neutral of a cable must be looped back through an FCI to cancel the magnetic field and allow fault detection. Proper placement is important for these devices to correctly sense fault currents.

Uploaded by

Thameemul Buhari
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
165 views2 pages

JHJJK

This document discusses proper routing of ground return conductors when using window-type current transformers (CTs) or fault current indicators (FCIs) for protective relaying of shielded power cables. It explains that the grounding conductor on cable shields must be routed back through the CT before grounding to allow detection of phase-to-ground faults. Similarly, the concentric neutral of a cable must be looped back through an FCI to cancel the magnetic field and allow fault detection. Proper placement is important for these devices to correctly sense fault currents.

Uploaded by

Thameemul Buhari
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

TECHNICAL NEWS

from

THE OKONITE COMPANY

Edition: 010

August 2001

g
Engineertinion
Informa
for the ional
Profess r
Enginee

SHIELDED POWER CABLE AND WINDOW CURRENT TRANSFORMERS


From time to time we get asked; what is the proper routing of the ground return conductor when a window (Adonut@)
type current transformer (CT) is used for protective relaying? Should the shield or concentric neutral be run through
the CT or routed outside the CT? The following sketches should help to illustrate that it is necessary to feed the
grounding conductor on the cable shields back through the CT before connecting it to ground.
Sketch A illustrates the case where a single phase-to-ground fault returns the fault current in the shield, and in a coaxial construction such as a medium voltage, shielded power cable, the magnetic fields produced by outgoing and return
current will tend to cancel one another. This cancellation thus renders the CT ineffectual in detecting a
phase-to-ground fault. This is particularly true for single point grounding at source end, or for multipoint grounding if
the fault occurs near source end.
CT
Conductor
Phase-toGround
Fault

V
Shield

Sketch B diagrams the connection with the shield doubled back on itself in the CT so that the magnetic field produced by the shield current is canceled, and allows the CT to detect excessive current in the phase conductor.
CT
Conductor
Phase-toGround
Fault

V
Shield

The following illustration depicts a typical utility installation with the proper routing of the ground return conductor.
BUS BAR
SHIELD GROUNDING STRAP
STRESS CONE
(SEE NOTE 1)

GROUNDING
CONDUCTOR

WINDOW CURRENT
TRANSFORMER (When Used)
MEDIUM VOLTAGE
SHIELDED CABLE

SWITCHGEAR
GROUND BUS
Note that shield ground is
pulled through donut CT prior
to attachment to ground bus.

Another type of fault detecting device, an FCI Sensor, can be used on concentric neutral cables. The proper placement
of this device is also important for correct operation in sensing a ground fault.
During a phase-to-ground fault, fault current flows through the conductor and a portion returns along the neutral. The
resulting magnetic field of the neutral tends to cancel the magnetic field of the conductor. If an FCI is installed directly over the concentric neutral, it may not detect the fault current because the magnetic field is canceled or reduced.
Correct placement can be done in one of two ways:
(1)
Train the concentric neutral wires back over themselves on the cable. The FCI is then installed over the
portion of the cable where the neutral wires are overlaid.
(2)
Train the neutral wires to the outside of the FCI. The FCI is placed on the cable above the concentric
neutral wires.
The following figure illustrates the proper placement as described above. This information comes from the Underground Systems Design and Installation Guide, published by the National Rural Electric Cooperative Association.

Concentric Neutral Must


Be Looped Back Through
Sensor Core to Cancel
Effect of Current in Neutral

You might also like