Compressor Drive Allison 501-KB Gas Turbine

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

ALLISON 501-KB GAS TURBINE

COMPRESSOR DRIVE
APPLICATION CONTROL PACKAGE

INC.

Rotating Machinery Controls

PRODUCT BULLETIN: 06004

JULY 2006

PETROTECH HOME PAGE

BLEED
VALVES

NGP
1
NGP
2
NGP
3

CIT
THERMO
COUPLES

CDP

TIT
CAPACITY
CONTROL

BYPASS
VALVE

GAS
FUEL

LIQUID
FUEL
STOP
VALVE

4-20 mA
4-20 mA
4-20 mA
FREQUENCY
FREQUENCY
FREQUENCY

FCV

STOP
VALVE

FUEL
PUMP

FUEL VALVE OUTPUT

STOP
VALVE

LCV VALVE OUTPUT

CDP INPUT

THERMOCOUPLE INPUTS
TC01-TC18

CIT INPUT

4-20 mA
mV

GP SPEED INPUT 3
4-20 mA

GP SPEED INPUT 2

LOAD SETPOINT INPUT

GP SPEED INPUT 1
BLEED VALVES OUTPUT

NOTE: GP SPEED
INPUTS 2oo3 VOTE

APPLICATION CONTROL PACKAGE 9500-501-KB-COMP

OPTIONAL
MMI

COMM PORT
TO PLANT INFORMATION SYSTEM

DCS/SCADA

PLC INTEGRATED CONTROL SYSTEM

Simplified schematic showing a Petrotech ALLISON 501-KB gas turbine compressor drive
application control package integrated into an advanced PLC-based control system.

97038 PG. 2

APPLICATION

SCOPE OF SUPPLY

The Allison 501-KB COMP gas turbine application control package


replaces older mechanical/hydraulic/electronic/pneumatic fuel
regulators with a modern, reliable application control package
which runs on an advanced PLC-based system. The control
package for the gas turbine provides fuel control and bleed valve
control.

The application control package for the Allison 501-KB gas turbine
generator drive system, includes:
Analog inputs, 4 - 20 mA:
Watts (load control).
Compressor discharge pressure (CDP).
Ambient temperature (CIT).
Analog inputs, frequency:

ADVANTAGES
Hardware independent system:
Application control packages portability allows customer choice
of platform, reducing need for additional spare parts and
training expenses. Available PLCs include General Electric,
Siemens/TI, Allen-Bradley, and Modicon.
Fault tolerant:
Control package is available on fault tolerant controllers for
critical control applications.
Simplified interface to DCS or SCADA:
Communication tasks are handled with a separate, dedicated
module in the PLC, increasing data rate and simplifying network
installation.
Improved fuel regulation:
Fast loop sampling rate, combined with modern digital control
techniques improve steady-state setpoint control, and reduce
overshoot during transients.
Improved start-up reliability:
Special lean lightoff procedure ignites all combustors with
essentially 100% reliability, and with greatly reduced thermal
stress.
Improved engine temperature monitoring and control:
Advanced statistical algorithms detect turbine hot/cold spots
and automatically reject failed thermocouples.
Fail-safe features:
Redundant overspeeds; open/short monitoring of mA and
thermocouples; readback monitoring of outputs, and special
self-check features improve safety.
Non-proprietary interfaces:
Simple 4- 20 mA, RTD, thermocouple, and dry contact I/O allow
simple interface to existing sequence/protection logic unit,
making low-cost partial upgrades practical, and system
troubleshooting simple.
Improved operator information with optional MMI:
Optional Man-Machine Interface MS Windows-based graphic
operator interface displays system status, trending and data
logging, which can be used as part of a preventative maintenance program.

Three (3) redundant NGP.


Analog inputs, mV:
TIT (up to 18 thermocouples).
Analog outputs, 4-20 mA:
Fuel control valve position setpoint.
Bleed valve position setpoint.
Operating states:
Firing.
Warm-up.
Accelerate.
Load.
Status, alarms, and shutdowns:
Fault .
GP overspeed alarm.
GP underspeed shutdown.
GP overspeed shutdown.
Redundant GP overspeed shutdown.
UGP alarm.
High TIT alarm.
High TIT shutdown.
Low TIT shutdown.
Low TIT delayed alarm.
Rejected thermocouple.
Too few thermocouples shutdown.
UT alarm.
UT shutdown.
Thermocouple spread alarm.
Thermocouple spread shutdown.
Turbine maximum limit.

97038 PG. 3

Turbine minimum limit.


GP speed #1.
GP speed #2.

OPTIONS FOR COMPLETE


CONTROL SYSTEM UPGRADE

GP speed #3.

Gas turbine sequencing and protection discrete logic.

GP speed #4.

Compressor sequencing and protection discrete logic.

GP speed #5.

Communication interface to DCS or SCADA.

TIT switch #1.

PLC hardware.

Manual.

Man machine interface unit with WonderWare InTouch licensed


software package.

High firing fuel pressure shutdown.


Transmitter failure alarms.

Complete custom engineered control panel, factory tested and


ready to install.

Transmitter failure shutdowns.

Fuel control valve system upgrade.

Output failure shutdowns.

Bleed valve actuator system upgrade.

Control mode.

Thermocouple upgrade.

Controllers/special features:

Synchronizing and regulation equipment.

Start-up controller for fuel valve.

Vibration system upgrade.

NGP controller for fuel valve.

Installation and commissioning.

TIT controller for fuel valve.

Training

TIT rate of rise controller.


Fuel acceleration schedule.
Fuel deceleration schedule.
Deceleration rate limiter.
Corrected speed (CNGP) override.
Bleed valve controller.
Combustion monitoring system.
Stagnation detection system.
Ramps:
Firing (lean lightoff) ramp.
Start-up ramp.
Loading ramp.
Cooldown ramp.
Does not include:
PLC hardware.
Gas turbine sequencing and protection discrete logic.
Compressor sequencing and protection discrete logic.
Compressor anti-surge control application package.
End elements.

97038 PG. 4

THIS PAGE LEFT BLANK

Petrotech, Inc
141 James Drive West
St. Rose, Louisiana 70087
USA

Phone:
Fax:
Email:
Web Site:

(504) 620-6600
(504) 620-6601
[email protected]
www.petrotechinc.com

INC.

Rotating Machinery Controls

This document is a Petrotech, Inc. copyrighted intellectual property