Manual Programacion VARIADOR Aquavar
Manual Programacion VARIADOR Aquavar
Manual Programacion VARIADOR Aquavar
IM167R08
AQUAVAR CPC
Application
START-UP Wizards
APPLY power
CHECK installation
INSTALL wiring
Task
The installation of the AQUAVAR CPC adjustable speed drive follows the outline below.
Overview
AQUAVAR CPC
2 230 Volt
370 Amps
1 NEMA 1
2 NEMA 12
Options
CPC 4 370 1
4 460 Volt
Amps
Voltage
AQUAVAR (Series)
Tools Required
Screwdrivers, wire stripper, tape measure, mounting screws or bolts, and drill.
Use the following chart to interpret the type code
found on the drive label.
Check
Motor Compatibility Motor type, nominal current,
frequency and voltage range must match drive
specifications (3 phase motor only).
Suitable Environment Drive requires heated,
indoor controlled environment that is suitable for
the selected enclosure below 104 F.
Wiring Follow local codes for wiring and fusing
requirements. Refer to NEC, Local, State or Municipal codes.
Refer to the Installation Operation Manual and
confirm that all preparations are complete.
1
X0002
Wiring Power
1. Connect conduit runs to box.
2. Route input power and motor
wiring through conduits.
2. Attach a warning
sticker in the
appropriate language on the inside
plastic shell.
1. Position the
AQUAVAR and use
screws or bolts to
securely tighten all
four corners.
2. Loosen the
captive screw
at
the top.
WARNING!
For floating networks remove
screws at
F1 and F2
on Frame
Sizes R5 or R6.
Frame Size R6
Frame Size R5
3. Strip wires.
4. Connect power, motor and
ground wires to the drive terminals.
See Power Connections
in the instruction manual.
ON
Relay Outputs
AI1: 010 V
AI2: 0(4)20 mA (default)
ON
19 RO1C
20 RO1A
21 RO1B
22 RO2C
23 RO2A
24 RO2B
25 RO3C
26 RO3A
27 RO3B
J1
1. Route the
transducer
3
cable
through
5
the conduit.
2. Strip the
transducer
cable
sheathing
and twist
1
the screen
wire.
3. Connect the screen
wire of the
transducer to
terminal X1-1.
4. Connect the power supply wire of the
transducer (red or brown) to terminal
X1-10.
5. Connect analog output wire from the
transducer (white or black) to X1-5.
See chart in next column.
Control Wiring
and
12
X1
Trans-
1 SCR
ducer
Screen/
Shield
Analog I/O
Digital Inputs1
X1
Control Wiring
Check
Environment conforms to specifications.
The drive is mounted securely.
Proper cooling space around the drive.
Motor and driven equipment are ready for start.
Floating networks: Internal RFI filter disconnected.
Drive is properly grounded, with pump/motor.
Input power (mains) voltage matches the drive
nominal input voltage.
The input power (mains) terminals, U1, V1, W1,
are connected and tightened as specified.
The input power (mains) fuses / mains switch installed.
The motor terminals, U2, V2, W2, are connected
and tightened as specified.
Motor cable is routed away from other cables.
NO power factor compensation capacitors are
connected to the motor cable.
Control terminals are wired and tightened as specified.
NO tools or foreign objects (such as drill shavings) are
inside the drive.
NO alternate power source for the motor is connected
no input voltage is applied to the output of the drive.
Check Installation
(15
1
Digital input impedance 1.5 k. Maximum voltage
to 10
Jump- 2 for digital inputs is 30 V.
Default values depend on the macro used. Values
er)
Digital Inputs1
ON
ON
LOC
REM
DIR
REM
40.2 PSI sp
0.0 PSI ac
0.0 HZ
MENU
11.1%
Wizards
The Start-Up
Wizard steps through
typical start-up selections and runs
automatically upon the initial power
up. At other times, use the steps
below to run the Start-Up Wizard.
Start-Up
Apply Power
FEATURES
TABLE OF CONTENTS
Section 1 SAFETY
Section 3 INTRODUCTION
Section 5 START-UP
Section 7 PROGRAMMING
Section 8 FEATURES
TABLE OF CONTENTS
Section 9 FAULTS/ALARMS
Layout......................................................................................................................................................................... 125
Heatsink, Fan............................................................................................................................................................. 126
Replacing the Fan..................................................................................................................................................... 126
Capacitors................................................................................................................................................................. 128
LEDs........................................................................................................................................................................... 129
Control Panel............................................................................................................................................................. 129
Section 12 APPENDIX
Warranty..................................................................................................................................................................... 152
SAFETY
WARNING! The AQUAVAR adjustable speed AC drive should ONLY be installed by a qualified electrician.
WARNING! Even when the motor is stopped, dangerous voltage is present at the Power Circuit terminals U1, V1, W1 and U2, V2, W2 and, depending on the frame size, UDC+ and UDC-, or BRK+ and BRK-.
WARNING! Dangerous voltage is present when input power is connected. After disconnecting the
supply, wait at least 5 minutes (to let the intermediate circuit capacitors discharge) before removing the
cover.
WARNING! Even when power is removed from the input terminals of the AQUAVAR, there may be dangerous voltage (from external sources) on the terminals of the relay outputs R01R03.
WARNING! When the control terminals of two or more drive units are connected in parallel, the auxiliary
voltage for these control connections must be taken from a single source which can either be one of the
units or an external supply.
WARNING! The AQUAVAR CPC wall mount version is not a field repairable unit. Never attempt to repair
a malfunctioning unit; contact the factory or your local Authorized Service Center for replacement.
WARNING! The AQUAVAR will start up automatically after an input voltage interruption if the external
run command is on.
WARNING! The heat sink may reach a high temperature, in excess of 200 F. Severe burns are possible.
WARNING! If the drive will be used in a floating network, remove screws at EM1 and EM3 (Frame size
R1R4), or F1 and F2 (Frame size R5 or R6). See diagrams on pages 24 and 25 respectively.
NOTE! For more technical information, contact the factory or your local AQUAVAR representative.
WARNING! Always consult your local, state, municipal or NEC codes for proper wiring, electrical installation of inverter drives and AC motors.
USE OF WARNINGS AND NOTES
There are two types of safety instructions throughout this manual:
Notes draw attention to a particular condition or fact, or give information on a subject.
Warnings caution you about conditions which can result in serious injury or death and/or damage to
the equipment. They also tell you how to avoid the danger. The warning symbols are used as follows:
DANGEROUS VOLTAGE WARNING warns of high voltage which can cause physical injury and/or damage to the equipment.
GENERAL WARNING warns about conditions, other than those caused by
electricity, which can result in physical injury and/or damage to the equipment.
ACS550-U1-046A-2 ACS550-U1-046A-2
SW:
SW:
V.2.06B
V.2.06B
2053901277
2053901277
S/N2053901277
S/N2053901277
Input
Voltage (U1)
Current (11n)
3 PH 4863
208240 Vac
46.2 A
1 PH 4863 Hz
208240 Vac
46.2 A
Short Circuit
100 kAIC
100 kAIC
Output
Voltage (U2)
Current (12n)
Current (12hd)
3 PH 0500 Hz
0U1 Vac
46.2 A
30.8 A
3 PH 0500 Hz
0U1 Vac
22 A
Power (Pn)
Power (Phd)
15 HP
7.5 HP
ACS550-U1-046A-2
US
159339
206578
UL
US
S/N2053901277
This configuration is one of if not the most common. It provides rebalancing of unbalanced
voltage with a 30 degree phase shift. Depending on the output connections from the drive to
motor, the grounded neutral may be a path for common mode current caused by the drive
output.
Another common configuration providing voltage rebalancing with no phase shift between
input and output. Again, depending on the output connections from the drive to motor, the
grounded neutral may be a path for common mode current caused by the drive output.
Ungrounded secondary:
This type of configuration is common on 230 volt systems. From time to time it may be
encountered where only single phase power is available and three-phase power is required.
The technique uses two single phase transformers to derive a third phase. When used to
power a drive this configuration must be derated to about 70% of the single phase rating of
one transformer. This system provides poor regulation and it is possible that only the two line
connected phases will provide power. In this case the drive must be derated to 50% of its
rating. (Ex. A 20 HP 230 volt drive now becomes a 10 HP 230 volt drive.)
10
INTRODUCTION
Input Power and Line Transformer Requirements
The Aquavar CPC requires that the input line voltage and transformer power that meet
certain phase and balance requirements. If you or your installing electrical contractor is in
doubt of the requirements, the following provide guidelines for the Aquavar CPC. When
in doubt contact the local power utility or the factory.
Drive input isolation transformers are not generally required for the Aquavar CPC. The
Aquavar CPC utilizes as standard 3% line impedance, therefore unless additional filtering is
needed, an input line reactor is not required.
NOTE: 60 THROUGH 550 HP UNITS PROVIDE AN ACTUAL 3% IMPEDANCE LINE REACTOR
BUILT INTO THE DRIVE CABINET.
The internal power circuit of the drive is floating with respect to earth ground except for
transient protection (MOVs and EMI capacitors) therefore earth ground potential reference is
established only by the users power line grounding configuration. The drive can operate with
many different power grounding schemes. The drive requires only that the steady state RMS
voltage from any input line to ground be always less than 110% of the nominal power line to
line voltage. The use of optional RFI/EMC filters may require that the voltage from any input
line to ground be less than 110% of the nominal power line to neutral voltage.
Drive input isolation or dry type transformers may be required for the following:
1. Step up or down: An input transformer may be required to step the local input power
line voltage up or down to the level of the drive input rating.
2. Ground Isolation: An input isolation transformer with a direct or a high impedance wye
neutral secondary ground connection may be required to establish a local power source
with a ground relationship different from the utility power source.
A. If ground isolation is required to prevent a ground fault in one section from shutting
down equipment in another section.
B. To bring local line voltages within the line to ground limits (110% balance) stated in
the opening paragraph.
C. Some ground fault protection schemes and peripheral components require a
grounded neutral power source.
D. A symmetrical wye neutral grounded power source along with proper ground wiring
techniques according to NEC (good ac grounding from motor to drive and from
drive to earth ground) provides the best means to control the ground currents that
the drive switching frequency and dv/dt rate insert into the motor frame and shaft.
3. Phase shifting delta-wye or zig-zag isolation transformers are used to feed 12 or 18
pulse drive inputs to provide harmonic mitigation.
If an isolation transformer is used for 6 pulse input, the best choice is ONE three phase,
six winding transformer. A delta primary is best for third harmonic cancellation. A
wye secondary avoids circulating current problems and provides the very desirable option
of grounding the secondary neutral for minimum voltage stress and ripple to ground. The
transformer should have a KVA rating at least 1.1 times the maximum connected HP. A K
Factor of 6 is sufficient if transformer impedance is greater than 2%. A K Factor of 5 is sufficient
11
INTRODUCTION
if transformer impedance is greater than 3%. The transformer manufacturer may provide
derating for non K Factor rated transformers to operate at the drive produced K Factor levels.
Other transformer configurations are acceptable. Three single phase transformers can be
used if they are identical for phase to phase symmetry and balance. A wye connected
primary neutral should never be grounded. Great care should be taken with delta primary
delta secondary configurations. Any lack of phase to phase symmetry could result in
circulating currents and unacceptable transformer heating.
WARNING! Never use phase converters with drives as nuisance tripping and possible
damage may occur. Size the drive for single phase input using 50% derate factor.
WARNING! Use of Open Delta 230 volt power systems should be sized using the
50% derate factor. Consult factory.
Sometimes drive input isolation transformers are specified to deal with one or more of
the following issues:
1. Short Circuit Protection: Input transformers are sometimes used to provide impedance
to reduce the available short circuit current to levels that the input clearing devices,
such as fuses or circuit breakers, are rated to handle. Line reactors can perform this
impedance function much more cost effectively.
2. Transient Protection: Input transformers are sometimes used to provide transient
surge impedance. All the Aquavar CPC drives have capacitors and MOVs (Metal Oxide
Varistor transient protectors) providing 120 to 360 joules, line to line and line to ground
transient protection. Isolation transformers are not required for this protection within
those energy levels. Additional distribution transformer primary transient surge arrestors
may be required if the potential transient energy reflected to the drive exceed those
levels. MOVs are rated to handle high levels of one shot transient energy. MOVs are not
meant to handle continuously recurring transients. A problem of continuously recurring
transients should be corrected before connecting a drive.
3. Harmonic Mitigation: Input transformers are sometimes used to provide impedance to
reduce the harmonic currents generated in the drive. Line reactors can perform this
function much more cost effectively.
4. Power Factor Capacitor Isolation: Input transformers are sometimes used to provide
impedance to isolate drives from line connected power factor correction capacitors.
PWM drive inputs do not require power factor correction capacitors as drive power
factors are generally greater than 92% and cannot be significantly improved with
power factor correction capacitors which only correct for fundamental. However drives
should be isolated from power factor correction capacitors by about 3 to 6% additional
impedance with respect to the drives. Line reactors can perform this function much more
cost effectively than isolation transformers. ABB drives have either an internal 3% line
reactor or an equivalent 3 to 5% bus reactor.
5. RFI/EMI Mitigation: Neither input isolation transformers nor line or bus reactors provide
good high frequency filtering although an isolation transformer with a static shield will
provide some RFI mitigation. If RFI/EMI mitigation is required, an RFI/EMI filter mounted
inside the drive should be used together with all the proper wiring and grounding
techniques. Some RFI/EMI filters may operate only on a power source with a grounded
neutral. Establishing a local neutral ground may require the use of an input isolation
transformer.
12
INTRODUCTION
Study these installation instructions carefully before proceeding. Failure to observe the
warnings and instructions may cause a malfunction or personal hazard.
WARNING! Before you begin read Safety on page 7.
Task
See
Preparing for Installation on page 15.
Unpack the Drive on page 21.
Prepare the Mounting Location
on page 21.
Remove Front Cover on page 21.
Mount the Unit on page 22.
Install the Wiring on page 23.
Check Installation on page 32.
Reinstall Cover on page 33.
Apply Power on page 33.
Start-Up on page 33.
13
INTRODUCTION
AQUAVAR CPC Product Numbering
Voltage
Phase
Frame Size
Normal Duty
Horsepower
CPC20071
3.7
R1
1
CPC20171
8.5
R1
2
CPC20241
12
R2
3
CPC20311
15.5
R2
5
CPC20461
23
R3
7.5
CPC20591
29.5
R3
10
230
1
CPC20881
44.0
R4
15
CPC21141
57.0
R4
20
CPC21431
71.5
R6
25
CPC21781
89.0
R6
30
CPC22481
124.0
R6
40
CPC22481
124.0
R6
50
CPC20041
4.6
R1
1
CPC20071
7.5
R1
2
CPC20121
11.8
R1
3
CPC20171
16.7
R1
5
CPC20241
24.2
R2
7.5
CPC20311
30.8
R2
10
CPC20461
46.2
R3
15
230
3
CPC20591
59.4
R3
20
CPC20751
74.8
R4
25
CPC20881
88.0
R4
30
CPC21141
114.0
R4
40
CPC21431
143.0
R6
50
CPC21781
178.0
R6
60
CPC22211
221.0
R6
75
CPC22481
248.0
R6
100
CPC40061
6.9
R1
3
CPC40081
8.8
R1
5
CPC40121
11.9
R1
7.5
CPC40151
15.4
R2
10
CPC40231
23
R2
15
CPC40311
31
R3
20
CPC40381
38
R3
25
CPC40451
45
R3
30
CPC40591
59
R4
40
CPC40721
72
R4
50
CPC40781
78
R4
60
460
3
CPC40971
97
R4
75
CPC41251
125
R5
100
CPC41571
157
R6
125
CPC41801
180
R6
150
CPC42451
245
R7
200
CPC43161
316
R7
250
CPC43681
368
R8
300
CPC44141
414
R8
350
CPC44861
486
R8
400
CPC45261
526
R8
450
CPC46021
602
R8
500
CPC46451
645
R8
550
CPC50031
2.7
R2
2
CPC50041
3.9
R2
3
CPC50061
6.1
R2
5
CPC50091
9
R2
7.5
CPC50111
11
R2
10
CPC50171
17
R2
15
CPC50221
22
R2
20
CPC50271
27
R3
25
575
3
CPC50321
32
R4
30
CPC50411
41
R4
40
CPC50521
52
R4
50
CPC50621
62
R4
60
CPC50771
77
R6
75
CPC50991
99
R6
100
CPC51251
125
R6
125
CPC51441
144
R6
150
*** - HP classifications are for reference purposes only, always size the Aquavar according to the output amps and the service factor amps of the motor.
14
INTRODUCTION
Preparing for Installation
Drive Identification
Drive Labels
Serial number label attached on upper part of the chokeplate between the mounting
holes.
ACS550-01-08A8-4
U1
I2N / I2hd
PN / Phd
3~380480 V
8.8 A / 6.9 A
4 / 3 kW
Type code label attached on the heat sink on the right side of the unit cover.
Input U1
I1N
f1
3~380480 V
8.8 A
4863 Hz
Input U2 3~0U1 V
I2N / I2hd 8.8 A / 6.9 A
f2
0500 Hz
Input PN / Phd
4 / 3 kW
UL
US
LISTED
ACS550-01-08A8-4
Type Code
CPC 4 370 1 FD
AQUAVAR (Series)
Voltage
2 208-240 Volt
4 480 Volt
5 575 Volt
Amps
370 Amps
*See Technical Section
NEMA Enclosure Rating
1 NEMA 1
2 NEMA 12
** Fused Disconnect
Options
* Consult factory for other options, if available. Not all combinations may be available.
** Standard equipment on 200 HP and above 460 volt models.
15
INTRODUCTION
Ratings and Frame Size
The chart in Ratings on page 131 lists technical specifications, and identifies the drives
frame size significant, since some instructions in this document, vary, depending on the
drives frame size. To read the Ratings table, you need the Output current rating entry from
the type code. Also, when using the Ratings table, note that the table is broken into sections
based on the drives Voltage rating.
Motor Compatibility
The motor, drive and supply power must be compatible:
Motor
Specification
Motor type
Verify Reference
3-phase induction motor
NEMA MG1
Nominal current
Motor value is within this
range: 0.22.0 * I2hd
(I2hd = drive heavy duty)
50 70 Hz
Motor is compatible
with the AQUAVAR
voltage range.
Nominal frequency
Voltage range
Tools Required
To install the AQUAVAR you need the following:
True RMS multimeter
Screwdrivers (as appropriate for the mounting hardware used)
Wire stripper
Tape measure
Drill
Mounting hardware: screws or nuts and bolts, four each. The type of hardware depends on
the mounting surface and the frame size:
Frame Size
Mounting Hardware
R1R4
M5
#10
R5
M6
in.
5
R6 M8 16 in.
Suitable Environment and Enclosure
Confirm that the site meets the environmental requirements. To prevent damage prior to
installation, store and transport the drive according to the environmental requirements
specified for storage and transportation. See Ambient Conditions on page 145.
Confirm that the enclosure is appropriate, based on the site contamination level:
IP 21 / UL type 1 enclosure, indoor use only. The site must be free of airborne dust,
corrosive gases or liquids, and conductive contaminants such as condensation, carbon
dust and metallic particles.
16
INTRODUCTION
IP 54 / UL type 12 enclosure, indoor use only. This enclosure provides protection from
airborne dust and light sprays or splashing water from all directions.
UL Type 3R- Enclosures are intended for outdoor use to provide a degree of protection
from falling rain. Undamaged by the formation of ice on the enclosure. May be cooled by
forced air and louvers for vents.
IP 56 / UL type 4 enclosure. Constructed for outdoor use or hose down applications.
Provides a degree of protection against falling dirt, rain, sleet, snow, windblown dust and
splashing water. Not suitable for direct sun. A sun shield or canopy may be required.
Suitable Mounting Location
Confirm that the mounting location meets the following constraints:
The drive must be mounted vertically on a smooth, solid surface, and in a suitable
environment as defined above.
The minimum space requirements for the drive are the outside dimensions (see Outside
Dimensions on page 141 and 143), plus air flow space around the unit (see Cooling on
page 137).
The distance between the motor and the drive is limited by the maximum motor cable
length. See Motor Connection on page 136.
The mounting site must support the drives modest weight and noise output. See
Dimensions and Weights on page 141.
Wiring and EMC Considerations
Determine electromagnetic compliance (EMC) requirements per local codes. In general,
always follow the NEC in the absence of a local code.
Follow local codes for cable size, conduit, grounding and motors.
Keep these four classes of wiring separated: input power wiring, motor wiring, control/
communications wiring. Always use separate conduit for motor/control wires.
Refer to the specifications/recommendations in:
Cable Sizing/Rating on page 131, Cable Terminals on page 135, Input Power (Mains)
Connection on page 136 and Motor Connection on page 136.
Multiple motor wire should always be run in separate conduit. Shielded and grounded!
Control Cables
General Recommendations
Use shielded cables, temperature rated at 60 C (140 F) or above:
Control cables must be multi-core cables with a braided copper wire screen.
Double Shielded
Example: JAMAK by Draka NK Cables
Single Shielded
Example: NOMAK by Draka NK Cables
The screen must be twisted together into a bundle not longer than five times its width and
connected to terminal X1-1 (for digital and analog I/O cables) or to either X1-28 or X1-32
(for RS485 cables).
17
INTRODUCTION
Route control cables to minimize radiation to the cable:
Route as far away as possible from the input power and motor cables (at least 20 cm (8 in)).
Where control cables must cross power cables make sure they are at an angle as near 90
as possible.
Stay at least 20 cm (8 in) from the sides of the drive.
Use care in mixing signal types on the same cable:
Do not mix analog and digital input signals on the same cable.
Run relay-controlled signals as twisted pairs (especially if voltage > 48 V). Relay-controlled
signals using less than 48 V can be run in the same cables as digital input signals.
NOTE! Never mix 24 VDC and AC power signals in the same cable.
Analog Cables
Recommendations for analog signal runs:
Use double shielded, twisted pair cable
Use one individually shielded pair for each signal.
Do not use a common return for different analog signals.
Digital Cables
Recommendations for digital signal runs:
A double shielded cable is the best alternative, but single shielded twisted multi-pair cable
is also usable.
Control Panel Cable
If the control panel is connected to the drive with a cable, use only Category 5 Patch ethernet
cable.
18
Inner Insulation
Cable Core
Additional US Requirements
Type MC continuous corrugated aluminum armor cable with symmetrical grounds or shielded
power cable must be used for the motor cables if metallic conduit is not used. For the North
American market, 600 VAC cable is accepted for up to 500 VAC. For drives rated over 100
amperes, the power cables must be rated for 70C (158F).
20
1
X0002
NOTE! Frame sizes R3 and R4 have four holes along the top.
Use only two. If possible, use the two outside holes (to allow
room to remove the fan for maintenance).
Remove Front Cover
IP 21 / UL Type 1
1. Remove the control panel, if attached.
2. Loosen the captive screw at the top.
3. Pull near the top to remove the cover.
21
IP 54 / UL Type 12
For the IP54 / UL Type 12 enclosures, rubber plugs are required in
the holes provided for access to the drive mounting slots.
1. As required for access, remove the rubber plugs. Push plugs
out from the back of the drive.
2. Position the AQUAVAR onto the mounting screws or bolts and
securely tighten in all four corners.
NOTE! Lift the AQUAVAR by its metal chassis.
3. Reinstall the rubber plugs.
4. Non-English speaking locations: Add a warning sticker in the
appropriate language over the existing warning on the top of the module.
22
23
24
Not used
25
Not used
26
27
Description
Note
U1, V1, W1*
3-phase power supply input
PE
Protective Ground
U2, V2, W2
Power output to motor
Motor Connection on
page 136.
* NOTE: The AQUAVAR (208240V series) can be used with a single phase supply, if output current is derated by 50%.
For single phase supply voltage, connect power at U1 and W1. Refer to page 26.
Floating Networks
For floating networks (also known as IT, ungrounded or high impedance networks):
Disconnect the internal RFI filter by removing both the EM1 and EM3 screws (frame sizes
R1R4, see page 24), or F1 and F2 screws (frame sizes R5R6, see page 25).
Where EMC requirements exist, check for excessive emission propagated to neighboring
low voltage networks. In some cases, the natural suppression in transformers and cables is
sufficient. If in doubt, use a supply transformer with static screening between the primary
and secondary windings.
Do NOT install an external filter. Using an RFI filter grounds the input power through the
filter capacitors, which could be dangerous and could damage the unit.
Control Connections
To complete the control connections, use:
Following tables
Single/Multipump
Complete Parameter Descriptions
Cable recommendations in Control Cables
29
X1
Transducer
1
SCR
Screen/
Shield
Control Wiring
ON
Relay Outputs
Digital Inputs1
Analog I/O
ON
25 RO3C
26 RO3A
27 RO3B
10 +24V
11 GND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
10 +24V
11 GND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
Communications
Terminals 2832 are for RS485 or modbus communications. Use shielded cables. For lengths
of cable beyond 100 feet, use screen connections.
Do not directly ground the RS485 network at any point. Ground all devices on the network
using their corresponding earthing terminals.
As always, the grounding wires should not form any closed loops, and all the devices should
be earthed to a common ground.
Terminate the RS485 network using 120 resistors at both ends of the network. Use the DIP
switch to connect or disconnect the termination resistors. See following diagram and table.
Terminated
Station
Station
X1 Identification
28 Screen
29 B
RS485
Multipump
Connections
30 A
31 AGND
32 Screen
Terminated
Station
Station
Hardware Description1
RS485 Multidrop Application
Other Modbus Devices
SCR
B
A
GND
B
A
GND
SCR
28
29
30
31
32
SCR
B
A
AGND
SCR
RS485 Interface
J2 J5
J2 J5
ON ON
ON ON
31
Check
Installation environment conforms to the drives specifications for ambient
conditions.
Space around the drive meets the drives specifications for cooling.
The motor and driven equipment are ready for start (3 phase motor).
The drive is properly grounded, along with the pump, motor and control panel.
The input power (mains) voltage matches the drive nominal input voltage (watch
for open delta power).
The input power (mains) connections at U1, V1 and W1 are connected and
tightened as specified. Loose connections may cause arcing!
The motor cable is routed away from other cables and in separate conduit.
NO tools or foreign objects (such as drill shavings) are inside the drive.
32
IP 54 / UL Type 12
1. Align the cover and slide it on.
2. Tighten the captive screws around the edge of the cover.
3. Slide the hood down over the top of the cover.
4. Install the two screws that attach the hood.
5. Reinstall the control panel.
NOTE! The control panel window must be closed to
comply with IP 54/UL type 12.
6. Optional: Add a lock (not supplied) to secure the control
panel window.
Apply Power
Always reinstall the front cover before turning power on.
WARNING! The AQUAVAR will start up automatically at power up, if the
external run command is on.
1. Apply input power.
When power is applied to the AQUAVAR, the green LED comes on.
NOTE! Before increasing motor speed, check that the motor is running in
the desired direction.
Start-Up
The AQUAVAR has default parameter settings that are sufficient for many situations. However,
review the following situations. Perform the associated procedures as appropriate. Proceed to
Start-Up section of this manual.
33
34
Module
Drive
Module
WARNING! Only qualified electricians are allowed to carry out the work described
in this chapter. Follow requirements in Safety on the first pages of this manual.
Ignoring the safety instructions can cause injury or death.
Planning
When planning for cable/conduit routing, refer to the AQUAVAR Users Manual, but note that,
for the AQUAVAR, all connections are routed through the top of the extension module.
Mounting
Fastening the Unit
See the Dimensional Drawings on page 41 for the exact locations
of the mounting points.
1. Use at least four screws two at the front, two at the back to attach the unit base plate to
the floor.
2. Use at least two screws to attach the back of the enclosure to a wall.
There are two holes available at the top of each: the extension module and the drive module.
35
Extension Module
OMIO
3
Switch-fuse
Disconnect
Control
Panel
U1 V1 W1
U2
V2
W2
PE
Control
Wiring
L1
L2
L3 PE
Supply
U1
V1
W1
PE
3~
Motor
Temporarily remove the upper high voltage shield (clear plastic) to gain access to the
power connections in the extension module.
To avoid metal shavings inside the cabinet, temporarily remove the gland/conduit plate
at the top of the extension module. Then drill holes and mount conduit or cable fittings as
needed.
Route all power and control wiring through the top of the extension module.
36
37
38
R7
8. At the OTIF board, disconnect the two fiber optic cables. Make
note of the terminal colors for use when reconnecting.
8
9
R7
12
WARNING! These screws are an important step during reassembly the screws are required for grounding the drive.
11. R8: The front of the trolley includes support braces that fold
out. Lift each brace slightly and fold it out.
12. Remove screws that fasten the drive module to the extension
module.
CAUTION! The drive module is now separated and could
tip over. Use care when moving the drive module.
13. Pull on the handle to wheel the drive module out.
Drive Maintenance
See the AQUAVAR Users Manual for drive maintenance
procedures, page 34.
Re-Assembly
Re-attach the modules in reverse order to the above.
40
13
10
10
Pedestal
Trolley
200
[7.87]
200
[7.87]
0
[.00]
161.4
[6.35]
361.4
[14.23]
598.9
[23.58]
523
[20.59]
294
[11.57]
323
[12.72]
29
[1.14]
0
[.00]
BOTTOM PLATE HOLE 14 (6 pcs)
[.55]
81
[3.19]
12
81
[3.19]
520
[20]
381
[15.00]
29.55
[1.16]
33
[1.30]
286
[11.26]
A
LIFTING LUG (4 pcs)
(2 pcs.)
1501
[59.1]
1459
[57.44]
[.47]
352
[13.86]
190
[7.48]
DET. B
SEE SHEET 2
DET. A
SEE SHEET 2
465.5
[18]
MAIN
SWITCH
2.5
[.10]
12
[.47]
26.5
[1.04]
298.5
[11.75]
17
[.67]
45
[1.77]
734
[28.90]
193.7
[7.63]
27
[1.06]
A-A
C-C
425.1
[16.74]
598.4
[23.56]
41
520
[20.47]
0
[0.00]
133.9
[5.27]
0
[0.00]
U2, V2
V2
R, R+
52.1
[2.05]
223.3
[9.15]
278.3
[10.96]
201.5
[7.93]
0
[0.00]
132.5
[3.22]
125.3
[4.93]
102.5
[4.04]
155.5
[6.12]
78.8
[3.10]
24.8
[4.91]
<425.9 >
[16.77]
0
[0.00]
133.9
[5.27]
109.8
[4.32]
159.8
[6.29]
239.8
[10.23]
309.8
[12.19]
PE HOLE 2 (4 pcs.)
[.47]
488
[19.21]
U2
493.4
[19.43]
V2
R+
W2
540.5
[21.28]
578
[22.76]
U1
V1
W1
DET.B
2.5
42
250.5
[9.86]
256.8
[10.11]
285.5
[11.24]
300.5
[11.83]
186
[7.32]
151
[5.94]
2.5
87.5
[3.44]
DET.A
52.3
[2.07]
321.7
[12.67]
0
[0.00]
12 .5 (12 pcs.)
[.49]
11.1 (2 pcs.)
[0.43]
260
[10.24]
152.3
[6.00]
35.5
[1.40]
700
[27.56]
446
[17.56]
260
[10.24]
491.4
[19.35]
21.2
[0.83]
26
[1.02]
393.9
[15.51]
1882.5
[74.11]
2018
[79.45]
93
[3.66]
617
[24.3]
611.8
[24.09]
272.2
[10.72]
946.7
[37.27]
563.1
[22.2]
17
[0.67]
392.5
[15.45]
46
[7.81]
2.5
[0.10]
12
[0.47]
B
554.5
[21.83]
787
[30.98]
43
44
372
[14.65]
327
[12.87]
222.5
[8.76]
177.5
[6.99]
117
[4.61]
72
[2.83]
14 (6 pcs.)
[.55]
0
[0.00]
0
[0.00]
382.5
[15.06]
280.5
[11.04]
208.5
[8.21]
136.5
[5.37]
82
[3.23]
128
[5.04]
174
[6.85]
873.8
[34.40]
0
[0.00]
110.8
[4.36]
160.8
[6.33]
210.8
[8.30]
310.8
[12.24]
360.8
[14.20]
410.8
[16.17]
PE HOLE 11 (6 pcs.)
[.43]
0
[0.00]
0
[0.00]
47.5
[1.87]
115.5
[4.55]
379.3
[14.93]
Detail R8
Dimensions are listed in millimeters and [inches].
617
[24.3]
0
[0.00]
222.3
[8.75]
59.2
[2.33]
730.9
[28.77]
14 (6 pcs.)
[.55]
12.5 (2 pcs.)
[.49]
START-UP
Wizards
The Wizard configures the drive. This process sets parameters that define how the drive operates and communicates. Depending on the control and communication requirements, the
start-up process may require any or all of the following:
The Start-up Wizard steps you through the default configuration. The Start-up Wizard can
be activated at the first power up, or can be accessed at any time using the main menu.
Application macros can be selected to define common, alternate system configurations, using the default settings. See Single or Multipump Setup/Programming on page 73.
Additional refinements can be made using the control panel to manually select and set
individual parameters. See Complete Parameter Descriptions on page 50.
40.2 PSI sp
0.0 PSI ac
0.0 HZ
DIR
12:45
50%
Down Arrow
MENU
LOC
REM
45
START-UP
Output mode
Use the output mode to read information on the drives status and to operate the drive. To
reach the Output Mode, press EXIT until the LCD display shows status information as described below.
Status Information
Top The top line of the LCD display shows the basic status information of the drive.
LOC indicates that the drive control is local, that is, from the control panel.
REM indicates that the drive control is remote, which is required to operate the pump
and automatically control pressure. This mode is also used for fieldbus control. (e.g. Transducer or PLC control)
indicates the drive status as follows:
Significance
Drive is running
Stationary arrow
Drive is stopped
Upper right (50%) shows the percentage of full scale the transducer is operating.
Middle The middle of the LCD display will display:
For Single Pump
Reference or set point. Pressure SP
Actual set point. Pressure AC
Frequency in HZ.
REM
DIR
40.2 PSI sp
0.0 PSI ac
0.0 HZ
12:45
50%
MENU
NOTE! The AQUAVAR display will show (set pressure), (actual pressure) and Frequency
(Hz), in single pump mode.
Bottom The bottom of the LCD display shows:
Lower corners show the functions currently assigned to the two soft keys.
Lower middle (12:45) displays the current time (if configured to show the time).
Operating the Drive
LOC/REM The very first time the drive is powered up, it is in the remote control (REM) mode,
and is controlled from the Transducer and Control Panel.
To switch to local control (LOC) and control the drive using the Control Panel, press and hold
the
button. The drive must be stopped!
The Remote (REM) Mode uses the transducer and set point to control the speed output to
the pump.
The Local (LOC) Mode uses the control panel for manual control of the drive output. Speed
up or down.
LOC
REM
46
START-UP
Other Modes
Besides the Output Mode, the Control Panel has:
Other operating modes that are available through the main menu.
A fault mode that is triggered by faults. The fault mode includes a diagnostic assistant
mode.
REM
MAIN MENU
1
Access to Main Menu Modes
PARAMETERS
To reach the main menu:
1. Press EXIT, as necessary, to step back through the menus or WIZARDS
CHANGED PAR
lists associated with a particular mode. Continue until you
EXIT
ENTER
are back to the Output Mode.
2. Press MENU from the Output Mode. At this point, the middle of the display is a listing of
the other modes, and the top-right text says Main Menu.
3. Press UP/DOWN to scroll to the desired mode.
4. Press ENTER to enter the mode that is highlighted. The following sections describe each
of the other modes.
Parameters Mode
Use the Parameters Mode to view and edit parameter values:
1. Select PARAMETERS in the main menu.
REM
MAIN MENU
PARAMETERS
WIZARDS
CHANGED PAR
EXIT
REM
ENTER
PAR GROUPS
99 START-UP DATA
01 OPERATING DATA
04 FAULT HISTORY
10 START/STOP/DIR
11 REFERENCE SELECT
EXIT
REM
01
SEL
PARAMETERS
1101 LANGUAGE
1102 APPLIC MACRO
SINGLE PUMP
NOTE! The current parameter value appears below the high- 1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
lighted parameter.
EXIT
EDIT
4. Press EDIT.
5. Press UP/DOWN to step to the desired parameter value.
NOTE! To view the parameter default value: In the set mode, press UP/DOWN
simultaneously.
Press SAVE to store the modified value or press CANCEL
to leave the set mode. Any modifications not saved are
cancelled.
Press EXIT to return to the listing of parameter groups
and again to return to the main menu.
LOC
PAR EDIT
EXT1
CANCEL
SAVE
47
START-UP
Wizard Mode
When the drive is first powered up, the Start-Up Wizard guides you through the setup of a few
basic parameters. For example, at the first start, the drive automatically suggests entering the
first task, password.
The Start-Up Wizard is divided into tasks. You may activate the tasks one after the other, as the
Start-Up Wizard suggests, or independently. (You are not required to use the assistant, you
may use instead, the parameter mode to set the drive parameters.)
The order of the tasks presented by the Start-Up Wizard depends on your entries. The task list
in the following table (next page) is typical.
Start-Up Wizard
The start-up wizard is a tool that can be used to quickly program an Aquavar with the most
commonly used single / mult-pump parameters. The wizard will prompt the programmer to
enter the required parameters by automatically bringing them to the screen. To enable the
wizard following the steps below:
1. In the main screen select MENU. Then press enter.
2. Press the up / down arrow to select WIZARDS, then press SELECT.
3. Enter the values for the parameters as seen in the table below, and follow each entry by
pressing the SAVE key.
4. When complete, press the EXIT key until the main screen is displayed again.
5. Set the required system pressure using the up and down arrows, then start the pump
using the green START key.
Task Name
Description
48
START-UP
5. Press UP/DOWN to select a new value / edit the parameter value. (Pressing both keys at
the same time sets a parameter to its default value.)
6. Press SAVE to save the new parameter value. (If the new value is the default value, the parameter will no longer appear on the Changed Parameters listing.)
Par Backup Mode
The Control Panel can store a full set of drive parameters. If two sets of parameters are defined, both are copied and transferred when using this feature.
The Par Backup Mode has three functions:
Upload to Panel Copies all parameters from the drive to the Control Panel. The Control
Panel memory is nonvolatile and does not depend on the panels battery.
Restore All (Download To Drive All) Restores the full parameter set(s) from the Control
Panel to the drive. Use this option to restore a drive or to configure identical drives. Drive
must be in local mode.
NOTE! The Restore All function writes all parameters to the drive, including motor parameters. Only use this function to restore a drive or to transfer parameters to systems that are
identical to the original system.
Download Application Copies partial parameter set(s) from the Control Panel to a drive.
The partial set does not include internal motor parameters. Use this option to transfer parameters to systems that use similar configurations - the drive and motor sizes do not need
to be the same.
1. Select COPY in the Main Menu.
2. Press UP/DOWN to step to the desired option.
3. Press SAVE. The parameter set is transferred as directed. During the transfer, the
display shows the transfer status as a percent of completion.
4. Press EXIT to step back to the Output Mode.
Clock Set Mode
Use the Clock Set Mode to:
Enable/disable the clock function.
Set date and time.
Select display format.
1. Select CLOCK SET in the Main Menu.
2. Press UP/DOWN to step to the desired option.
3. Press EDIT.
4. Press UP/DOWN to select the desired setting.
5. Press SAVE to save setting.
49
PARAMETER LISTINGS
Aquavar CPC Parameter List
The Aquavar CPC parameter list contains all of the necessary pump, drive, fault and control
parameters needed for programming this unit. Each group indicates a certain function and
control for the Aquavar, in order to set up single or multipump control.
To view the available parameter list, on your keypad, press the MENU button to access the
parameter list. The parameters are write protected with a password. Please contact your
Aquavar representative for more information on this password (located in GROUP 10 LOCKS/
PASSWORDS).
Group 01, VFD SIGNALS (READ ONLY DATA) This set of parameters sets up the drive and
motor. These parameters can only be adjusted and changed when the motor has stopped.
Monitoring of motor output, and various analog and digital outputs.
Group 02, PUMP SIGNALS (Data output only) Provides output set points, energy savings
and wire to water power.
Group 03, STATUS WORDS Provides status of drive and alarm condition.
Group 10, LOCKS/PASSWORDS Provides password and parameter save information.
Keypad and set point locks.
Group 11, START UP DATA Provides parameters used for initial start up information (e.g
language, application, voltage, motor current, motor RPM, horsepower). Used for initial motor
setup.
Group 12, START/ STOP Determines method(s) of starting and stopping the Aquavar. i.e.
Keypad, external switch, Modbus, manual, test run and motor jog.
Group 13, RAMPS & WINDOWS Parameters used for the acceleration and deceleration
of the pump. Window and Hysterisis contains modulation of algorithm (pressure control
regulation).
Group 14, SPD LIM/START LVL Parameters that contain speed control, max and min
frequency, restart value, priming delay.
Group 15, TRANSDUCER VAR Parameters used for the setup and tuning of the pressure
transducer, flow meter and adjustment of transducer range.
Group 16, REFERENCE SELECT Parameters that control how the set point is maintained. i.e.
Modbus, keypad, analog input (transducer).
Group 18, RELAY OUTPUTS Parameters that define how the Aquavar output relays are
controlled and what delay time is actuated for each relay. Three total relays can be used (RO1,
RO2, RO3).
50
PARAMETER LISTINGS
Aquavar CPC Parameter List (continued)
Group 19, ANALOG OUTPUTS Defines the analog outputs available on the drive. Two
possible analog outputs that can be used to monitor various parameters (AO1, AO2).
Group 21, REGULATE Defines type of control regulation with analog input from transducer.
Normal, Inverse modes. Friction loss compensation.
Group 22, MULTIPUMP CONTROL Defines parameters for multi-pump control algorithm.
Addresses each drive. Required group for alternating each pump.
Group 24, FAULT FUNCTIONS Defines parameters for faults, pump protection and run
enable mode (e.g. keypad failure, pump protect, low water, error reset).
Group 25, AUTOMATIC RESET This group defines conditions for automatic reset. An
automatic reset occurs after a particular fault is detected. The Aquavar holds for a delay time,
then automatically restarts. You can limit the number of restarts in a specific period of time for
a variety of faults (e.g. overcurrent, over/ under voltage).
Group 26, ENERGY SAVINGS Defines parameters used for energy savings, and kW/hr
usage.
Group 27, CRITICAL SPEEDS This group defines up to three critical speeds or resonant
frequencies. This mechanical resonance may occur on certain loads at certain frequencies.
Group 30, OPTION MODULES Defines parameters used for fieldbus communication
networks and optional fieldbus adapter.
Group 31, FIELD BUS SETUP Parameters used for actual set up for the field bus
communication via the RS485 terminals.
Group 32, MODBUS SETUP Defines parameters used for the Modbus setup and protocol,
baud rate, parity, status functions.
Group 50, MOTOR CONTROL Provides adjustment of the switching frequency for the drive.
Group 51, MAINTENANCE TRIGGERS Defines the parameters for trigger points on the
cooling fan, motor revolutions, run time, used power in Megawatts. Provides actual time run
on each component.
Group 99, INFORMATION Provides firmware version, drive rating for the Aquavar.
51
PARAMETER LISTINGS
Defaults
Group VFD Signals
Range
Description
01
0101 Motor
0.0...500.0 Hz
Frequency
52
PARAMETER LISTINGS
Defaults
Group VFD Signals
Range
Description
01
0124 Current at Flt
- A
0125 Status at Flt
-
0126 DI 6-1 At Fault 000111
0127 Drive On Time Hi - Days
0128 Drive On Time Lo - Hrs : Min : Sec
FB CMD Word 1
FB CMD Word 2
FB STS Word 1
FB STS Word 2
Fault Word 1
Fault Word 2
Fault Word 3
Alarm Word 1
Alarm Word 2
53
PARAMETER LISTINGS
Defaults
Group Status Words
Range
Description
03
0310
0311
0312
0313
0314
Group
10
AV Alarm Word
AV Fault Word
Comm RO Word
Comm Value 1
Comm Value 2
Aquavar Alarm word
Aquavar Fault word
Locks/
Range Description
Passwords
54
Selects the state of the parameter Locked Locked Locked Locked Locked
lock. The lock prevents
parameters from being changed.
The lock is open. Parameter
values can be changed.
Parameter values cannot be
changed from the keypad. The
lock can be opened by entering
the valid password in parameter
10.02. When the keypad is
locked the AV keypad functionality is limited to starting,
stopping and changing the
reference (set point).
Password setting 66 opens the
0 0 0 0 0
lock and returns the value to
zero on the display. The password relocks when power is
disconnected. To relock the
keypad reset parameter 1001
to Locked.
Disables local control on the
Off Off Off Off Off
keypad. WARNING! Before
activating, ensure that the
control panel is not needed for
stopping the drive.
Local control allowed.
Local control disabled.
Saves the parameter values to Done Done Done
Done
Done
the permanent memory.
Parameters entered via the
keypad are automatically saved.
Parameters are not automatically
saved when altered through the
fieldbus connection.
PARAMETER LISTINGS
Defaults
Group
10
Start-Up
Range Description
Data
Done
Off
1101 Language
Selects the display language English English English English
English (AM) American English.
(Default)
Espaol
Spanish (full translation)
Francais
French (full translation)
1102 Application
Selects the application macro
Macro
Single Pump One AV regulating to a set point
(Default)
Synchronous Lag pumps start as needed and
all pumps regulate to the set
point at the same speed. Note:
it is recommended that all
pumps be identical.
Multicontrol
Lag pumps start as needed. The
last lag pump to start regulates
to the set point; the remaining
pumps operate at an enable
sequence speed (2203).
Constant Slave The master unit starts up to
three fixed speed slave units
when needed. See RO1, RO2
and RO3 settings (parameters
1801, 1804 and 1807).
Speed Control AV follows a speed reference
only. Pump protect fault
function is inactive.
1103 Application
No
Resets parameters to default
Restore
Yes
settings.
English
55
PARAMETER LISTINGS
Defaults
Group
11
Start-Up Range
Description
Data
56
PARAMETER LISTINGS
Defaults
Group Start/Stop Range
Description
12
1203 Test Run
Automatic
(continued)
Manual
1204 Test Speed % (FL) 0...100%
1205 Test Run Delay
0...3600 Hr
1206 Motor Jog
1209 Manual
Disabled
Override
(Default)
1210 Override
0-60 Hz
Freq
Group
13
Group
14
Ramps/
Range Description
Windows
Spd Lim/
Range Description
Strt Lvl
1401 Maximum
Minimum
Frequency/Speed Frequency
60 Hz
5
5
60
60
80
5
5
60
60
80
5
5
60
60
80
5
5
60
60
80
60
60
60
60
57
PARAMETER LISTINGS
Defaults
Group
14
1402 Minimum
0Max
Frequency/Speed Frequency
1403 Config Speed
Min
0 (Default)
Min Freq
1404 Stp Delay
01800 s
Min Spd
1405 Restart Value
0150 %
1406 Restart Delay
01800 s
58
PARAMETER LISTINGS
Defaults
Group
14
Transducer
Range Description
Var
Psig
60
59
PARAMETER LISTINGS
Defaults
Group
15
Transducer Range
Description
Var
60
4 mA
PARAMETER LISTINGS
Defaults
Group
16
Reference Range
Description
Select
61
PARAMETER LISTINGS
Defaults
Group
16
Reference Range
Description
Select
1604 AI 1 Minimum
Tune
(continued)
Group
18
62
Relay
Range Description
Outputs
Ready
0
0
PARAMETER LISTINGS
Defaults
Group
18
63
PARAMETER LISTINGS
Defaults
Group
18
Low Water
Pump Protect
Start Slave
Stand by
1808 RO3 ON Delay 03600 s
1809 RO3 OFF Delay 0 3600 s
Group
19
64
Analog
Range Description
Outputs
0
0
Not
Used
PARAMETER LISTINGS
Defaults
Group
19
Analog Range
Description
Outputs
Group
Regulate Range
Description
21
2101 Regulation Mode
Normal
(Default)
Inverse
4
20
Selects the type of AV control with Normal Normal Normal Normal Normal
falling process variable signal.
Increases the output speed with
falling process variable signal.
For level control applications the
tank is on the discharge side.
Decreases the output speed with
falling process variable signal.
For level control applications the
tank is on the suction side.
65
PARAMETER LISTINGS
Defaults
Group
Regulate Range
Description
21
2102 Press Incr Speed 060 Hz
2103 Press Incr
0.10000
Group
22
Multipump
Range Description
Control
66
0 0 0 0 0
59
59
59
59
59
48
48
48
48
48
PARAMETER LISTINGS
Defaults
Group
22
Multipump Range
Description
Control
Fault
Range Description
Functions
45
45
45
Off
Off
Off
Off
Disabled
67
PARAMETER LISTINGS
Defaults
Group
24
68
Disabled
60
PARAMETER LISTINGS
Defaults
Group
24
Group
26
Automatic
Range Description
Reset
2501 NR of Trials
05
2502 Trial Time
1.0600.0 s
2503 Delay Time
0.0120.0 s
2504 AR Overcurrent
Disable
2505 AR Overvoltage
Disable
2506 AR Undervoltage
Disable
2507 AR AI<Min
Disable
Energy
Range Description
Savings
69
PARAMETER LISTINGS
Defaults
Group
26
Energy Range
Description
Savings
Option
Range Description
Modules
Fieldbus
Range Description
Setup
70
No
PARAMETER LISTINGS
Defaults
Group
32
Modbus Range
Description
Setup
3201 Protocol ID
00xFFFF
This parameter configures the
module type automatically by
the fieldbus adapter. No action
is required by the user unless
changes to default settings are
desired. Refer to the fieldbus
manual.
3202 Station ID
0...247
1
1
1
1
1
3203 Baud Rate
1.257.6
9.6
9.6
9.6
9.6
9.6
kbits/s
kbits/s kbits/s kbits/s kbits/s kbits/s
3204 Parity
Defines the data length, parity 8N2
8N2
8N2
8N2
8N2
and stop bits.
8N1
8 data bits, no parity and one
stop bit
8N2
8 data bits, no parity and two
stop bits
8E1
8 data bits, even parity and one
stop bit.
8O1
3205 Control
Profile
ABB Drives
AV
3206 OK Messages
065535
3207 CRC Errors
3208 EFBUART Errors
3209 EFB Status
Idle
Exec. Init
Time Out
Config Error
Off-line
On-Line
Reset
Listen Only
ABB
Drives
71
PARAMETER LISTINGS
Defaults
Group
32
Modbus Range
Description
Setup
Motor
Range Description
Control
Group Maintenance
Range Description
51
Triggers
5101 Cooling Fan Trig 0.06553.5
kh
5102 Cooling Fan Act 0.06553.5
kh
5103 Revolution Trig
065535
MRev
5104 Revolution Act
065535
MRev
5105 Run Time Trig
0.06553.5
kh
5106 Run Time Act
72
Group Information
Range Description
99
9901 FW Version
AXXX hex
9902 Drive Rating
XXXY
20
32000
40
PROGRAMMING
Single Pump Programming (Pressure transducer)
REM
0.0%
40.2 PSI sp
0.0 PSI ac
0.0 HZ
DIR
MENU
SUPPLY POWER
U1
V1
W1
ND
5
AIR
6
U2
V2
W
3 PHASE OUTPUT
ND
TO MOTOR
9
SUCTION
FLOW
3
1
2
3
4
5
AQUAVAR CPC
FUSIBLE DISCONNECT
CENTRIFUGAL PUMP
CHECK VALVE (NON-SLAM TYPE)
PRESSURE TRANSDUCER (CABLE ASSEMBLY)
6
7
8
9
NOTES: A. Use of load filter (reactor) should be used between the Aquavar and motor, if motor leads exceed
60 wire feet.
B. If single phase power is supplied on 200 - 240 volt three phase units, use U1 and W1 as input terminals
from single phase supply, and de-rate unit by 50% of three phase rating.
C. Tank size should be 10-20% (total volume) of flow in system. Pre-charge tank 10-15 PSI below system
pressure.
73
PROGRAMMING
Single Pump Programming (Pressure transducer)
Programming Step(s)
1. Access the main menu on the keypad. Press the MENU key
once and the display will show (PARAMETERS, WIZARDS,
CHANGED PAR). Using the arrow keys, highlight the
parameters option, then press the ENTER key .
REM
MAIN MENU
PARAMETERS
WIZARDS
CHANGED PAR
EXIT
REM
ENTER
PAR GROUPS
01 VFD SIGNALS
02 PUMP SIGNALS
03 FB ACTUAL SIGNALS
10 LOCKS/PASSWORDS
11 START-UP DATA
EXIT
REM
10
SEL
PARAMETERS
REM
REM
REM
EDIT
PARAMETERS
EDIT
PARAMETERS
1101 LANGUAGE
1102 APPLIC MACRO
SINGLE PUMP
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
EXIT
EDIT
PARAMETERS
1101 LANGUAGE
1102 APPLIC MACRO
1104 MOTOR NOM VOLT
230V
1105 MOTOR NOM CURR
EXIT
74
EDIT
PROGRAMMING
Single Pump Programming (Pressure transducer)
7. Use the down arrow until group parameter 1105 MOTOR
NOM CURRENT is highlighted, then press EDIT. Using
arrows, enter your motors maximum allowed amp draw at
speed, or Service Factor Amps. NOTE: Enter motors service
factor from nameplate or motor manual. Once you have
entered the amps, press the SAVE key.
REM
REM
PARAMETERS
the
1101 LANGUAGE
1102 APPLIC MACRO
full
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
3.4A
EXIT
EDIT
PARAMETERS
REM
EDIT
PARAMETERS
10. Once you have saved parameter 1108, use the down
arrow until you highlight group parameter 1201 START/
STOP, then press EDIT. Default is KEYPAD. This parameter
determines how the operator will control the Aquavar; via
the keypad or via MODBUS communication. If no changes
are required, press the CANCEL key then EXIT and go to the
next step.
REM
EDIT
PARAMETERS
EDIT
11. From group 12, press the down arrow until group 14 SPD
REM
PARAMETERS
LIM/STRT LVL is highlighted, then press EDIT. Use down
1401 MAXIMUM FREQ
1402 MINIMUM FREQ
arrows to highlight group 1402 MINIMUM FREQ, then
30.0 HZ
press EDIT. Using the arrow keys select the appropriate
1403 CONFIG SPEED MIN
minimum speed in HZ. Default is 10% of the parameter
1404 STP DELY MIN SPD
EXIT
EDIT
1106 MOTOR NOM FREQ which is 6 HZ. For a submersible
motor or suction lift situation, this would be set to at least
30 HZ. For a positive suction booster system, leave at the default setting. Once changed,
press the SAVE key to store the setting.
75
PROGRAMMING
Single Pump Programming (Pressure transducer)
12. From group 1402, press the down arrow until group 1502
TRANSDUCER MAX is highlighted, then press EDIT. Default
pressure transducer setting is 300 psi. Adjust this based on
your maximum rating for a new transducer. NOTE: CentriPro
provides a 0 -300 psi transducer as standard. Select the
appropriate range, then press SAVE. If no changes are
necessary, press CANCEL.
REM
PARAMETERS
EDIT
REM
15
16
18
19
21
XDUCER VARIABLES
REFERENCE SELECT
RELAY OUTPUTS
ANALOG OUTPUTS
REGULATE
REM
PARAMETERS
REM
4 mA
15
SEL
1504 SENSOR
1505 K-DP FLOW METER
1506 SENSOR MIN
4 mA
EXIT
EDIT
PAR EDIT
EXIT
REM
PAR EDIT
PAR GROUPS
TUNED VALUE
SAVE
CANCEL
SAVE
Status
LED
REM
UP
SOFT
KEY 1
DIR
40.2 PSI sp
0.0 PSI ac
0.0 HZ
11.1%
MENU
SOFT
KEY 2
DOWN
LOC
REM
76
LOC/REM
HELP
STOP
START
PROGRAMMING
Single Pump Programming (Pressure transducer)
16. Optional Step: To lock out access to the control panel (keypad), refer to page 109. This
will prevent unauthorized users from changing programming.
NOTE: If an error or fault occurs, refer to the troubleshooting/faults section of this
manual, page 116. When troubleshooting an Aquavar system, always break down into the
following components:
1. Aquavar programming check default settings recommended for single pump, multipump, slave pump etc.
2. Electrical supply/ motor/ wiring/grounding check your supply voltage, motor
wiring, transducer wiring, and grounding.
3. Mechanical/Pump/ Rotation check your pump rotation, rubbing or other mechanical
problems. Pump run out.
4. Hydraulic System/ Piping check to ensure proper suction and discharge piping
layout, proper NPSHa, air entrainment, vortex, friction loss, system curve compensation
etc.
5. Environment protect from high temperatures, direct sun, freezing temperatures, high
altitude, dust, vibration, lack of air flow.
77
PROGRAMMING
Single Pump Submersible Pump Constant Pressure
6
U1
V1
W1
GND
U2
V2
W2
GND
U2
V2
W2
GND
4
5
8
FLOW
1
2
3
4
5
6
7
8
9
10
78
AQUAVAR CPC
FUSIBLE DISCONNECT
LOAD REACTOR
AIR DIAPHRAGM TANK
PRESSURE TRANSDUCER
3 PHASE OUTPUT (ALWAYS)
DISCHARGE CHECK VALVE
GATE VALVE (HIGHLY RECOMMENDED)
SUBMERSIBLE PUMP END
SUBMERSIBLE MOTOR (3 PHASE)
10
PROGRAMMING
Single Pump Submersible Pump Constant Pressure
It is possible to utilize the Aquavar Centrifugal Pump Controller on commercial/industrial
well and submersible turbine applications. Submersible pumps and motors require specific
installation, programming and pipe layout compared to above ground booster pump
systems. However, specific programming must be followed to meet minimum requirements
set forth by the motor manufacturer (i.e. Franklin Electric). Always consult with the appropriate
motor technical manual for motor compatibility and requirements when using a Variable
Frequency type drives.
NOTE: THE AQUAVAR IS NOT RECOMMENDED FOR RESIDENTIAL WELL APPLICATIONS.
CONSULT CENTRIPRO FOR SUITABLE VARIABLE SPEED CONTROLLERS DESIGNED FOR
RESIDENTIAL WELL PUMPS (e.g. BF15 series).
Service Factor Amps
The submersible pump will sometimes utilize the motor service factor or MAX AMPS.
Therefore, during peak use times, it is recommended to select the appropriate Aquavar based
on the MOTOR MAXIMUM AMPS or service factor amps. Normally, this can be found on
the motor nameplate or the AIM (application, installation manual). This will avoid nuisance
tripping or current overload by the Aquavar. The Aquavar is designed to protect the motor on
overcurrent! Compare the motor max amps with the list of Aquavar models.
NOTE: ALL MOTORS MUST BE THREE PHASE.
Minimum Frequency
Submersible pump motors require a minimum speed or frequency to operate properly.
Because submersible motors use the water to lubricate and cool, they require this minimum
frequency when controlled by a Variable Speed Drive. Franklin has suggested that the
Minimum Frequency is set to at least 30 HZ in the Aquavar. Therefore, it is recommended
to set the Aquavar Minimum Frequency to 30 to 35 HZ (depending on static head) in
programming group 1402. See programming section.
WARNING: FAILURE TO SET THE MINIMUM FREQUENCY FOR SUBMERSIBLE
TURBINE INSTALLATION COULD RESULT IN DAMAGE TO THE PUMP AND/OR
MOTOR.
Tank Sizing
An appropriate size diaphragm tank must be sized for smooth operation. The tank will also
provide a needed compressability at zero flow. A tank with approximately 20% of total system
volume in GPM would be recommended.
79
PROGRAMMING
Single Pump Submersible Pump Constant Pressure
Load Reactor (Filter)
A Load reactor or load filter is an electrical device that provides protection to the motor
windings from a specific variable speed drive. Motors are more susceptible to voltage
spikes and switching frequencies found in IGBT type drives, especially when the motor leads
exceed 50 ft. Therefore, a load reactor is required when all of the following conditions are met
for ANY type of AC induction motor (above ground or submersible type):
1. Motor cable length from the Aquavar to the motor is more than 50 wire feet.
2. Drive uses IGBT type of switching (which is industry standard and is used by the Aquavar).
If all of the conditions are present above, then it is recommended to wire a LOAD REACTOR
between the Aquavar output (U2, V2, W2) and the motor. Keep the load reactor as close to
the output of the Aquavar for best results. NOTE: See suggested layout drawing and always
refer to your specific motor manufacturers recommendation for VFDs.
Grounding
NOTE: Always follow local codes for wiring and grounding or refer to the National
Electrical Codes.
Submersible installations are susceptible to stray voltage or grounding problems. It is
recommended to ground the transducer shield to the chassis of the Aquavar cabinet and to
check with a meter for any stray voltage from the three phase motor. Each component of the
electrical Aquavar system should have the same grounding point or reference. Always follow
the submersible motor manufacturers recommended installation procedures.
NOTES:
Motors used must be three phase, equal to input voltage.
Standard enclosure is rated for NEMA 1 INDOOR USE ONLY. Consult Factory/ Price
pages for outdoor rated enclosures.
Aquavar CPC not for use on RESIDENTIAL WELL PUMP applications. Consult with factory
for appropriate variable speed controller like the BF15.
Input voltage for the Aquavar can be single phase. Use the U1 , W1 and Ground
connections, and derate the drive by 50% from the three phase rating. Example: 230 volt,
three phase 10 HP Aquavar becomes a 5 HP, 230 volt, single phase rated drive.
80
PROGRAMMING
Single Pump Submersible Pump Constant Pressure
Each component of the electrical Aquavar system should have the same grounding point or
reference.
Programming Step(s)
Standard view of the display in REM (remote) mode. You will see
the reference pressure (REF PRESSURE), actual pressure (ACT
PRESSURE) and motor frequency in HZ.
1. Access the main menu on the keypad. Press the MENU key
once and the display will show (PARAMETERS, WIZARDS,
CHANGED PAR). Using the arrow keys, highlight the
parameters option, then press the ENTER key.
REM
0.0%
40.2 PSI sp
0.0 PSI ac
0.0 HZ
DIR
REM
MENU
MAIN MENU
PARAMETERS
WIZARDS
CHANGED PAR
EXIT
REM
REM
ENTER
PAR GROUPS
01 VFD SIGNALS
02 PUMP SIGNALS
03 FB ACTUAL SIGNALS
10 LOCKS/PASSWORDS
11 START-UP DATA
EXIT
10
SEL
PARAMETERS
REM
5. After the SAVE key is pressed in the above group, press the
EXIT key, then the down arrow to highlight the group 11
START UP DATA, then Press the SEL key once. Using the
arrows, highlight 1102 APPLIC MACRO, then press the
EDIT key. Default is set for SINGLE PUMP. Change this group
whether your system is Single Pump, Multi-Pump, Slave
Pump etc. To exit press CANCEL, to save this parameter,
press the SAVE key once.
REM
EDIT
PARAMETERS
EDIT
PARAMETERS
1101 LANGUAGE
1102 APPLIC MACRO
SINGLE PUMP
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
EXIT
EDIT
81
PROGRAMMING
Single Pump Submersible Pump Constant Pressure
6. Use down arrow until group parameter 1104 MOTOR NOM REM
PARAMETERS
VOLTAGE is highlighted, then press EDIT. Use the arrows to 1101 LANGUAGE
1102 APPLIC MACRO
enter your motors nameplate voltage, then press the SAVE
1104 MOTOR NOM VOLT
key.
230V
1105 MOTOR NOM CURR
EXIT
EDIT
REM
PARAMETERS
REM
EDIT
PARAMETERS
EDIT
10. Once you have saved parameter 1108, use the down
REM
PARAMETERS
arrow until you highlight group parameter 1201 START/
1111 MOTOR ID RUN
STOP, then press EDIT. Default is KEYPAD. This parameter 1201 START/STOP KEYPAD
1202 AUTO RESTART
determines how the operator will control the Aquavar; via
1203 TEST RUN
the keypad or via MODBUS communication. If no changes
EXIT
EDIT
are required, press the CANCEL key then EXIT and go to the
next step.
11. From group 12, press the down arrow until group 14 SPD
REM
PARAMETERS
LIM/STRT LVL is highlighted, and then press SEL. Use down 1401 MAXIMUM FREQ
1402 MINIMUM FREQ
arrows to highlight group 1402 MINIMUM FREQ, then
30.0 HZ
press EDIT. Using the arrow keys select the appropriate
1403 CONFIG SPEED MIN
minimum speed in HZ. Default is 10% of the parameter 1106 1404 STP DELY MIN SPD
EXIT
EDIT
MOTOR NOM FREQ which is 6 HZ. For a submersible motor
or suction lift situation, this would be set to at least 30 HZ.
Depending upon the static water level, and pipe distance to the transducer, you may have
to increase this setting up to 40HZ. Once changed, press the SAVE key to store the setting.
82
PROGRAMMING
Single Pump Submersible Pump Constant Pressure
12. Next step will set the appropriate time delay in seconds at
the MINIMUM FREQUENCY. Use the down arrow until you
highlight parameter 1404 STP DELY MIN SPD, and then
press the EDIT key. Use the UP ARROW to select a time in
seconds. A suggested delay time is 5 seconds. When the
pump reaches the minimum frequency, it will have a delay
of 5 seconds before shutting down. Once entered, then
press the SAVE key.
REM
PARAMETERS
EDIT
13. From group 1404, press the down arrow until group 1502
REM
PARAMETERS
TRANSDUCER MAX is highlighted, then press EDIT. Default
1410 UNDERVOLT CTRL
1411 PRIMING DELAY
pressure transducer setting is 300 psi. Adjust this based on
1501 TRANSDUCER UNIT
your maximum rating for a new transducer. NOTE: CentriPro 1502 TRANSDUCER MAX
300.0
provides a 0 -300 psi transducer as standard. Select the
E
X
I
T
EDIT
appropriate range, then press SAVE. If no changes are
necessary, press CANCEL.
14. Use the down arrow to highlight 1503 TRANSDUCER MIN
0.0 , then press EDIT. Default should be 0 psi. Press CANCEL
to advance to the next step. If this group needs to be
changed based on another type of transducer valve, press
SAVE to store.
REM
REM
15
16
18
19
21
PAR GROUPS
XDUCER VARIABLES
REFERENCE SELECT
RELAY OUTPUTS
ANALOG OUTPUTS
REGULATE
EXIT
SEL
PARAMETERS
1504 SENSOR
1505 K-DP FLOW METER
1506 SENSOR MIN
4 mA
EXIT
15
REM
EDIT
PAR EDIT
TUNED VALUE
CANCEL
SAVE
83
PROGRAMMING
Single Pump Submersible Pump Constant Pressure
16. Final step is to enter your required pressure in
the system. After above programming has been
completed, press the EXIT key three (3) times, until
you arrive back to the first control display screen.
Then press the UP or DOWN arrow to select the
required system pressure. Once pressure has been
selected, press the green START key on the keypad.
Status
LED
REM
UP
SOFT
KEY 1
DIR
40.2 PSI sp
0.0 PSI ac
0.0 HZ
11.1%
MENU
SOFT
KEY 2
DOWN
LOC
REM
LOC/REM
HELP
STOP
START
17. Optional Step: To lock out access to the control panel (keypad), refer to page 109. This
will prevent unauthorized users from changing programming.
NOTE: If an error or fault occurs, refer to the troubleshooting/faults section of this
manual, page 116. When troubleshooting an Aquavar system, always break down into the
following components:
1. Aquavar programming check default settings recommended for single pump, multipump, slave pump etc.
2. Electrical supply/ motor/ wiring/grounding check your supply voltage, motor
wiring, transducer wiring, and grounding.
3. Mechanical/Pump/ Rotation check your pump rotation, rubbing or other mechanical
problems. Pump run out.
4. Hydraulic System/ Piping check to ensure proper suction and discharge piping
layout, proper NPSHa, air entrainment, vortex, friction loss, system curve compensation
etc.
5. Environment protect from high temperatures, direct sun, freezing temperatures, high
altitude, dust, vibration, lack of air flow.
84
PROGRAMMING
SINGLE-PUMP LEVEL CONTROL
Submersible Transducer Setup
PARAMETER SETTINGS QUICK LIST
1002 Pass Code = 66
1001 Parameter Lock = OPEN
1102 Application Macro = SINGLE PUMP
1104 Motor Nom. Volt.
1105 Motor Nom. Current
1106 Motor Nom. Freq.
1107 Motor Nom. RPM
1108 Motor Nom. Pow.
2101 Regulation Mode = INVERSE
1501 Transducer Unit = FT
SYSTEM TUNING
Group 13 Ramps allow for tuning of the system response. Ramps 1 and 2 provide control
of start and stop ramps and can be used to produce smooth operation throughout pumping
level. Ramps 3 and 4 work within the regulation window to provide a final adjustment of
system operation when needed (reference pages 107-111).
NOTE: Level control application performance is dependant on sump size, maximum flow
rate and pump selection. An oversized pump may produce on/off type system operation,
similar to a level switch. This condition might not be fully correctable with ramp control.
85
PROGRAMMING
MULTI-PUMP LEVEL CONTROL
Submersible Transducer Setup
PARAMETER SETTINGS QUICK LIST
1002 Pass Code = 66
1001 Parameter Lock = OPEN
1102 Application Macro = MULTIPUMP
1104 Motor Nom. Volt.
1105 Motor Nom. Current
1106 Motor Nom. Freq.
1107 Motor Nom. RPM
1108 Motor Nom. Pow.
2101 Regulation Mode = INVERSE
1501 Transducer Unit = FT
2207 Pump Address = 1, 2, 3 or 4
SYSTEM TUNING
Group 13 Ramps allow for tuning of the system response. Ramps 1 and 2 provide control
of start and stop ramps and can be used to produce smooth operation throughout pumping
level. Ramps 3 and 4 work within the regulation window to provide a final adjustment of
system operation when needed (reference pages 112-114).
NOTE: Level control application performance is dependant on sump size, maximum flow
rate and pump selection. An oversized pump may produce on/off type system operation,
similar to a level switch. This condition might not be fully correctable with ramp control.
86
PROGRAMMING
MultiPump Constant Pressure Control
Overview
The Aquavar CPC has the ability to connect and control up to four centrifugal pumps, to
form a Multi-Pump, lead-lag and alternating pumping system. This will allow the operator to
maintain a constant pressure through a larger system flow range, and provides equal wear for
the pumps and motors. The Aquavar units will be hard wired together via the RS485 terminals
(29,30,31), and provide communication to maintain a constant pressure to the system. Once
the lead pump cannot maintain a certain pressure and allows a slight pressure drop, the next
(lag) pump will turn on and vary the speed according to the flow demand. This sequencing
can be programmed according to the specific system requirements, and is field adjustable. If
a pump or controller fails, the next pump will automatically turn on in its place. Each Aquavar
controlled pump will provide a fully functional lead/lag and automatic alternation system, with
automatic back up control when required.
System Curve - Friction Compensation
It is possible to program the Aquavar to maintain a constant pressure, and compensate for
increasing friction loss according to a system curve. As the flow rate increases in the system,
the friction loss will increase as well. The Aquavar can compensate for this friction loss with
the simple adjustment of the parameter 2202 VALUE INCREASE. When each Aquavar unit
enables the pump, it will increase the system pressure by the programmed amount. This
pressure is additive with each additional pump. Therefore, if you set this parameter for 3 psi,
and you initial constant pressure is 50 psi, and you have 4 pumps total: (50 psi + 3 psi + 3
psi + 3 psi) = 59 psi when all 4 pumps are operating at full speed. This final system pressure
should be enough to overcome your calculated head and friction loss, and to provide constant
pressure at the end of the pipe run. NOTE: This program function is not intended for
substitution of proper pipe layout and sizing according to Hydraulic Institute Standards.
This feature may not work for excessive friction losses!
Pump Sequencing
The Aquavar CPC has the ability to operate in a multiple pump with lead and lag pumps.
Each Aquavar will be given an address then operate as Pump 1, Pump 2, Pump 3 or Pump 4.
When Pump 1 cannot maintain the required system pressure and the speed reaches 60 Hz,
then that will trigger the lag pump to come on and help maintain the set pressure. In order
for the lag pump to turn on, the lead pump must be at full speed (Maximum Frequency)
and programmed system pressure drop must be met (VALUE DECREASE). Each Aquavar
controlled pump will vary its speed according to the demand on the entire system. In a
Duplex System, you could have Pump 1 running at full speed 60 Hz, and Pump 2 running at 50
Hz in order to maintain the system pressure at the flow demand. Each pump will operate in a
sequential mode, when called.
87
PROGRAMMING
MultiPump Constant Pressure Control
Wiring/Connection RS485
Each Aquavar unit must be connected via terminals
29, 30 and 31. Using a three wire shielded cable
between each Aquavar terminal. Suggested wire
specifications would be 3 or 4 wire, 22AWG, one
pair shielded, TYPE CM or CL3, 75 degree C(UL).
Remember to keep the color coded wires the same
to each terminal connection, and inspect for loose or
bad connections.
When using all the same Aquavar CPC units, you must
provide a BUS TERMINATION for the last drives in the
multi-pump system. The RS485 has two yellow DIP
SWITCHES that must be in the ON position when that Aquavar CPC unit is the last or first in
the system. Therefore, if you have 4 pumps in multi-pump configuration, Aquavar address 1
and Aquavar address 4 would have their DIP SWITCHES in the ON position (see diagram). If
you have a DUPLEX system, then Aquavar address 1 and Aquavar address 2 would have the
switches in the ON position.
Always follow your local codes or National codes and have a certified electrician perform the
necessary wiring.
NOTE: Fieldbus cannot be used with RS485 multipump (Modbus, Devicenet,
Profibus). Single pump only!
Terminated
Station
Station
X1 Identification
28 Screen
Multipump
Connections
for each
Aquavar
29 B
30 A
31 AGND
32 Screen
88
Terminated
Station
Station
Hardware Description1
RS485 Multidrop Application
Other Modbus Devices
SCR
B
A
GND
B
A
GND
SCR
28
29
30
31
32
SCR
B
A
AGND
SCR
RS485 Interface
J2 J5
J2 J5
ON ON
ON ON
PROGRAMMING
MultiPump Constant Pressure Control
Pump Sizing
It is recommend to use the same size pump for a multi-pump configuration. This is to
ensure even distribution of flow rates especially when small flow demands are put on the
system. If the operator requires a flow range of 10 500 GPM for the system, it would be
recommended to select a TRIPLEX system, with each pump capable of a maximum of 167
GPM at the required TDH. (167 GPM x 3 pumps = 501 GPM ) A smaller sized pump is more
capable of providing the low flow rates, rather than a larger pump that may oscillate more
at the low flows. One of the immediate benefits is to have all the same pumps for parts and
spares. No smaller jockey pumps. Each pump is evenly distributing the required flow and
pressure. Remember to allow system friction losses at maximum flow!
Tank Sizing
Similar to the single pump constant pressure system, the multi-pump system should have
a diaphragm or bladder type tank for system cushion. The tank should be rated for the
maximum system pressure, and be sized for 10-25% of the single pump capacity. This is total
tank volume, not drawdown. If you have a triplex system of 167 GPM per pump capacity,
then your tank size should be a minimum of 17 Gallon capacity. Go to the next higher
tank volume if you have a suction lift or flooded suction. The tank provides small
drawdown capacities on drive start up and provides a cushion for the entire system at
normal operation and will provide compressibility at shut-down. The tank pressure will greatly
improve system operation. A larger tank is acceptable and sometimes required, just do not
exceed 50% volume of the flow for one pump, this may cause system problems.
Programming
The following steps are for multi-pump, constant pressure systems, with up to four (4) Aquavar
CPC. Each Aquavar CPC will have to be programmed according to this parameter guide. The
parameters will not transfer over to each unit. There are two options for downloading the
parameters into each Aquavar:
A) Manually entering each parameter into the Aquava
control panel/display with the following steps.
B) Using the first Aquavar control panel, you can
download the software to each additional Aquavar
via the control panel. Take the programmed control
panel from Aquavar #1, then insert and replace each
additional control panel for Aquavar #2, #3, #4. This will
automatically download saved parameters into the other
Aquavar units. See diagram to the left.
89
PROGRAMMING
MultiPump Constant Pressure Control
Programming Step(s)
Standard view of the display in REM (remote) mode. You will see REM
the reference pressure (REF PRESSURE), actual pressure (ACT
PRESSURE) and motor frequency in HZ.
0.0%
40.2 PSI sp
0.0 PSI ac
0.0 HZ
DIR
1. Access the main menu on the keypad. Press the MENU key
once and the display will show (PARAMETERS, WIZARDS,
CHANGED PAR). Using the arrow keys, highlight the
parameters option, then press the ENTER key.
REM
MENU
MAIN MENU
PARAMETERS
WIZARDS
CHANGED PAR
EXIT
REM
REM
ENTER
PAR GROUPS
10
02 PUMP SIGNALS
03 FB ACTUAL SIGNALS
10 LOCKS/PASSWORDS
11 START-UP DATA
12 START/STOP
EXIT
SEL
PARAMETERS
REM
5. After the SAVE key is pressed in the above group, press the
EXIT key, then the down arrow to highlight the group 11
START UP DATA, then Press the SEL key once. Using the
arrows, highlight 1102 APPLIC MACRO, then press the
EDIT key. Using the UP arrow, highlight MULTICONTROL
option, then press the SAVE key.
REM
90
EDIT
PARAMETERS
EDIT
PAR GROUPS
02 PUMP SIGNALS
03 FB ACTUAL SIGNALS
10 LOCKS/PASSWORDS
11 START-UP DATA
12 START/STOP
EXIT
11
SEL
PROGRAMMING
MultiPump Constant Pressure Control
6. Use down arrow until group parameter 1104 MOTOR
NOM VOLTAGE is highlighted, then press EDIT. Use the
arrows to enter your motors nameplate voltage, then press
the SAVE key.
REM
PARAMETERS
1101 LANGUAGE
1102 APPLIC MACRO
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
EXIT
REM
REM
EDIT
PARAMETERS
1101 LANGUAGE
1102 APPLIC MACRO
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
3.5A
EXIT
EDIT
PARAMETERS
REM
EDIT
PARAMETERS
EDIT
10. After saving your motor horsepower, press the EXIT key. Use REM
PAR GROUPS
15
11
START-UP
DATA
the down arrow until you highlight the Group 15 XDUCER
12 START/STOP
VARIABLES, then press SEL.
13 RAMPS/WINDOWS
14 SPD LIM/STRT LEVL
15 XDUCER VARIABLES
EXIT
REM
SEL
PARAMETERS
EDIT
91
PROGRAMMING
MultiPump Constant Pressure Control
12. Use the down arrow to highlight 1503 TRANSDUCER MIN 0.0 , then press EDIT. Default
should be 0 psi. Press CANCEL to advance to the next step. If this group needs to be
changed based on another type of transducer value, press SAVE to store.
13. Use the down arrow to highlight 1506 SENSOR MIN,
then press EDIT. Use the up arrow until the TUNE value is
displayed, press the SAVE key. This provides the transducer
a tuned value of 0 (ZERO) psi. NOTE: Make sure that your
transducer is wired to the Aquavar but free from any
pressure in the system. The transducer must be exposed
to 0 psi when this step is performed. Press the SAVE key to
tune your transducer.
14. Once you have saved the parameter 1506, press the EXIT
key. Use down arrow until you highlight parameter Group 22
MULTIPUMP CTRL Then press the SEL key.
REM
PARAMETERS
1504 SENSOR
1505 K-DP FLOW METER
1506 SENSOR MIN
4mA
EXIT
REM
EDIT
PAR GROUPS
16 REFERENCE SELECT
18 RELAY OUTPUTS
19 ANALOG OUTPUTS
21 REGULATE
22 MULTIPUMP CTRL
EXIT
15. After above step, you should have parameter 2201 VALUE
DECREASE highlighted. Press the EDIT once. Uses the
up or down arrow to select the allowable pressure drop
before the next lag pump comes on. (Example: If the first
pump reaches maximum frequency, and the pressure drop
allowed before the lag pump turns on is 3 psi, you would
set this parameter for 3.0 psi). Once a pressure is set in
2201, then press the SAVE key.
REM
REM
22
SEL
PARAMETERS
EDIT
PARAMETERS
EDIT
REM
PARAMETERS
17. Once parameter 2202 has been saved, use the DOWN
2201
VALUE
DECREASE
arrow to highlight parameter 2203 ENABLE SEQUENCE
2202 VALUE INCREASE
then press the EDIT key. Using the up or down arrows
2203 ENABLE SEQUENCE
59.00 HZ
select the frequency in HZ that will turn the next lag pump
2204 SWITCH LEAD/LAG
on, when the lead pump has reached this frequency.
EXIT
EDIT
Normal setting is 59 HZ, which allows the lag pump to start
when the frequency has reached 59HZ on the lead pump, plus value decrease has been
met). NOTE: Always set this parameter at or BELOW the MAXIMUM FREQUENCY). If
no changes from default are required, press the CANCEL key.
92
PROGRAMMING
MultiPump Constant Pressure Control
18. After 2203 has been selected, press the down arrow to
highlight parameter 2204 SWITCH LEAD LAG. Press
the EDIT key once. Using the up or down arrows, select
the alternating time between lead and lag pumps. Once
selected, press the SAVE key.
REM
19. Once 2204 has been saved, press the down arrow to
highlight 2207 PUMP ADDRESS. Press the EDIT key once.
Use the up arrow to select your appropriate address for
each pump. Always start with address one. Once each
pump has a different address, press the SAVE key.
REM
PARAMETERS
EDIT
PARAMETERS
EDIT
Status
LED
REM
UP
SOFT
KEY 1
DIR
40.2 PSI sp
0.0 PSI ac
0.0 HZ
11.1%
MENU
SOFT
KEY 2
DOWN
LOC
REM
LOC/REM
HELP
STOP
START
94
27 R03B
26 R03A
25 R03C
24 R02B
23 R02A
22 R02C
21 R01B
20 R01A
19 R01C
NOTE:
AQUAVAR ISSUES RUN COMMANDS TO
CONSTANT SPEED (SLAVE PUMP) VIA RELAY
OUTPUTS (R01, R02, R03)
CONTROL LOOP MUST BE POWERED (EG. 120 AC) BY
SEPARATE SOURCE OR CONTROL PANEL.
NOTE:
RELAY STATE
R01C = NC
R01A = CC
R01B = NO
RELAY OUTPUT SPECS
250 VAC MAX, 2 AMP
RELAY OUTPUTS
CONTROL LOOP
POWER SOURCE
RELAY OUTPUTS
CAN BE ASSIGNED
IN GROUP 18.
SET TO
START SLV
X1 TERMINAL BOARD
AQUAVAR
POWER
SUPPLY
AC
SLAVE PUMP
MOTOR
T1 T2 T3
START/STOP
SLAVE PUMP
STARTER
CUSTOMER SUPPLIED
CONTROL PANEL
PROGRAMMING
PROGRAMMING
MultiPump Slave Pump Control
Overview
The Aquavar CPC has the ability to use up to three dry relay contacts for constant speed
SLAVE or lag pump control. This is useful if the operator requires a wide range of flow rates
in certain situations (i.e. emergency flow), and does not require all variable speed controlled
pumps. When the required demand increases beyond capacity of the variable speed
controlled lead pump, then the FULL SPEED lag pump will turn on. Each relay will be wired
to your constant speed pump starter, sized for the appropriate horsepower and voltage. The
relay outputs located on the terminal control board X1 (SEE DIAGRAM FROM PREVIOUS
PAGE) will actuate when programmed according to the operators desired output. The lag
pumps will turn on when the Aquavar controlled pump cannot keep up to the required
demand. The lag pumps will be operated by across the line starters, and signaled to start
via the Aquavar relays located on terminals 19 through 27 of the X1 terminal block. The lag
pumps are referred to as SLAVE pumps, because they operate with commands from the
Aquavar controlled LEAD pump. The Aquavar controller will actuate the relays, and provide
a time delay for ON/ OFF on each relay.
Head
Lag Pump
Starts
Lag Pump
Starts
Value Decrease
Pump 1
Pump
1+2
Pump
1+2+3
Capacity (GPM)
The figure shows Pump 1 when it cannot maintain the system pressure (value decrease). Next,
Pump 1 + lag pump 2 will operate as a lead and lag system. If Pump 1 + 2 cannot maintain
system flow, then lag # 2 pump will turn on, then you will have all three pumps ( 1 + 2 + 3 )
operating in the system. You can operate up to 3 slave pumps, with 1 Aquavar controlled
pump.
NOTE: Each lag pump is controlled by the speed of the lead Aquavar pump, system
pressure drop (value decrease), and a delay time in seconds. Do not set the pressure drop
too close to operating system pressure, or pump cycling will occur!
95
PROGRAMMING
MultiPump Slave Pump Control
Lead vs. Lag
The Aquavar controlled pump will always be considered the LEAD pump, and start first in
the system sequence. The constant speed pumps will always be the SLAVE or LAG pumps
in the system. When the Aquavar controlled pump, starts to run out or cannot meet the
system demand, then the first relay output will actuate based on a programmed pressure and
time delay. The Aquavar CPC has up to three contacts that can be used for SLAVE operation.
Wiring/ Connection
The relays used for the SLAVE pump control are dry relay contacts, rated for a MAXIMUM
250 VAC or 30VDC, 2 Amps free from inductivity. Minimum is 500 mW (12V, 10mA). Refer to
diagram below, or in APPENDIX section.
Each relay will be wired to a voltage starter DO NOT EXCEED 250 VOLTS AC through each
relay. Each relay is designed for control power only. It is up to the operator to provide
necessary starters, overloads or fuses for each SLAVE pump motor control. Always follow your
local codes or National codes and have a certified electrician perform the necessary wiring.
= Run power to drive
= not used
96
PROGRAMMING
MultiPump Slave Pump Control
Programming Steps
Default settings for each relay are set for NOT USED. Therefore, REM
27.0%
the operator will have to access the programming, and go to
40.2 PSI sp
GROUP 18 RELAY OUTPUTS and set each relay to START
0.0 PSI ac
SLAVE. (SEE BELOW FOR DETAILED PROGRAMMING
0.0 HZ
STEPS.) Each relay is labeled (R01, R02, R03) and can be
DIR
MENU
programmed to respond based on a drop in system pressure
and delay time in seconds. Therefore, you can control the relay
when the system pressure starts to drop, and you allow a certain time delay in seconds to
respond. When the demand stops, each LAG pump will stop after a time delay, and operation
will return solely to the Aquavar controlled pump.
1. Access the main menu on the keypad. Press the MENU key
once and the display will show (PARAMETERS, WIZARDS,
CHANGED PAR). Using the arrow keys, highlight the
parameters option, then press the ENTER key.
REM
MAIN MENU
PARAMETERS
WIZARDS
CHANGED PAR
EXIT
REM
ENTER
PAR GROUPS
01 VFD SIGNALS
02 PUMP SIGNALS
03 FB ACTUAL SIGNALS
10 LOCKS/PASSWORDS
11 START-UP DATA
EXIT
10
SEL
REM
EDIT
PARAMETERS
EDIT
97
PROGRAMMING
MultiPump Slave Pump Control
5. After the SAVE key is pressed in the above group, press the
EXIT key, then the down arrow to highlight the group 11
START UP DATA, then Press the SEL key once. Using the
arrows, highlight 1102 APPLIC MACRO, then press the
EDIT key. Using the UP arrow, highlight CONSTANT SLV
option, then press SAVE key.
REM
PAR GROUPS
01 VFD SIGNALS
02 PUMP SIGNALS
03 FB ACTUAL SIGNALS
10 LOCKS/PASSWORDS
11 START-UP DATA
EXIT
REM
11
SEL
PARAMETERS
1101 LANGUAGE
1102 APPLIC MACRO
CONSTANT SLV
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
EXIT
EDIT
6. Use down arrow until group parameter 1104 MOTOR NOM REM
PARAMETERS
VOLTAGE is highlighted, then press EDIT. Use the arrows to 1101 LANGUAGE
1102 APPLIC MACRO
enter your motors nameplate voltage, then press the SAVE
1104 MOTOR NOM VOLT
key.
230V
1105 MOTOR NOM CURR
EXIT
REM
REM
EDIT
PARAMETERS
1101 LANGUAGE
1102 APPLIC MACRO
full
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
1.8A
EXIT
EDIT
PARAMETERS
REM
PARAMETERS
98
EDIT
EDIT
PROGRAMMING
MultiPump Slave Pump Control
10. After saving your motor horsepower, press the EXIT key. Use REM
PAR GROUPS
15
the down arrow until you highlight the group 15 XDUCER
15 XDUCER VARIABLES
16 REFERENCE SELECT
VARIABLES, then press EDIT.
18 RELAY OUTPUTS
19 ANALOG OUTPUTS
21 REGULATE
EXIT
REM
REM
REM
SEL
PARAMETERS
EDIT
PARAMETERS
EDIT
PARAMETERS
1504 SENSOR
1505 K-DP FLOW METER
1506 SENSOR MIN
TUNE
EXIT
REM
EDIT
PAR EDIT
4 mA
CANCEL
REM
SAVE
PAR EDIT
TUNED VALUE
CANCEL
SAVE
99
PROGRAMMING
MultiPump Slave Pump Control
14. Once you have saved the parameter 1506, press the EXIT
REM
PAR GROUPS
18
key. Use down arrow until you highlight parameter group 18 14 SPD LIM/STRT LEVL
15 XDUCER VARIABLES
RELAY OUTPUTS. Then press the SEL key.
16 REFERENCE SELECT
18 RELAY OUTPUTS
19 ANALOG OUTPUTS
EXIT
15. After above step, you should have parameter 1801 RELAY
OUTPUT 1 highlighted. Press the EDIT once. Uses the up
arrow to highlight START SLV, then press SAVE.
REM
SEL
PARAMETERS
EDIT
17. Once parameter 1802 has been saved, use the DOWN
arrow to highlight parameter 1803 RO 1 OFF DELAY, then
press the EDIT key. Use the UP arrow to select the OFF
DELAY for relay 1 in seconds. Press the SAVE key. This will
allow a timed delay when relay 1 turns off the first slave
pump.
REM
EDIT
PARAMETERS
EDIT
18. If you do not require other SLAVE relays, then proceed to the next step MULTIPUMP
CONTROL. If more relays are required, repeat steps above for RELAY 2 and RELAY 3,
parameters 1804, 1805, 1806, 1807, 1808.
REM
19. Once you have saved your last relay output, press the EXIT
key once. Use the down arrow until you highlight parameter
group 22 MULTIPUMP CTRL, then press SEL key.
PAR GROUPS
16 REFERENCE SELECT
18 RELAY OUTPUTS
19 ANALOG OUTPUTS
21 REGULATE
22 MULTIPUMP CTRL
EXIT
REM
22
SEL
PARAMETERS
EDIT
PROGRAMMING
MultiPump Slave Pump Control
21. Once previous step has been saved, use the Down Arrow
and highlight parameter 2203 ENABLE SEQUENCE, then
press EDIT. Using the up or down arrow, enter the frequency
in Hertz (HZ) that you wish the SLAVE pump will turn on once
the lead pump reaches this speed. Default is set for 59 HZ
and is typical for 60HZ systems. If you change this setting,
press the SAVE key. If no changes are required, then press
the EXIT key.
REM
PARAMETERS
EDIT
22. Group 2205 Enter frequency for slave pump to be turned off.
23. Final step is to enter your required pressure in
the system. After above programming has been
completed, press the EXIT key two (2) or three
(3) times, until you arrive back to the first control
display screen. (SEE DIAGRAM) Then press the
UP or DOWN arrow to select the required system
pressure for your Aquavar controlled pump. Once
pressure has been selected, press the green
START key on the keypad.
Status
LED
REM
UP
SOFT
KEY 1
DIR
40.2 PSI sp
0.0 PSI ac
0.0 HZ
27.8%
MENU
SOFT
KEY 2
DOWN
LOC
REM
LOC/REM
HELP
STOP
START
NOTE: If an error or fault occurs, refer to the faults/alarms section of this manual, page
115. When troubleshooting an Aquavar system, always break down into the following
components:
1. Aquavar programming check default settings recommended for single pump, multipump, slave pump etc.
2. Electrical supply/ motor/ wiring/grounding check your supply voltage, motor
wiring, transducer wiring, and grounding.
3. Mechanical/Pump/ Rotation check your pump rotation, rubbing or other mechanical
problems. Pump run out.
4. Hydraulic System/ Piping check to ensure proper suction and ischarge piping layout,
proper NPSHa, air entrainment, vortex, friction loss, system curve compensation etc.
5. Environment protect from high temperatures, direct sun, freezing temperatures, high
altitude, dust, vibration, lack of air flow.
101
FEATURES
Analog Outputs
The Aquavar CPC has two 4-20 mA analog outputs as standard. These outputs may be
configured by the user to output from a selection of nine actual pump signals. Parameter
group 19 is used to configure these outputs. Analog Outputs are found on X1 Terminal Block,
# 2 and # 5 pins. Reference the terminal block diagram on pages 24-31 for detailed wiring
connections.
Parameter
Name
Value/Range
Note(s)
19.01
AO 1
Content Sel
19.06
AO 2
Content Sel
21.01
REGULATION NORMAL (DEFAULT)
MODE
INVERSE
26.03
SAVINGS
0-65535
SCALE
Default 10,000
Auto Restart
The Aquavar drive can be configured to start automatically following a power failure.
Changing the value to ON will enable auto-restart. Selecting OFF disables the auto-restart.
AUTO RESTART is also used with ERROR RESET for automatic restarts following a shutdown
due to a pump fault. AUTO RESTART will also restart the pump once a secondary protection
fault is reset.
Parameter
Name
Value/Range
12.02
AUTO
OFF
RESTART
ON (DEFAULT)
25.04
AR OVER-
ENABLE
CURRENT
25.05
AR OVER-
ENABLE
VOLTAGE
25.06
AR UNDER-
ENABLE
VOLTAGE
25.07
AR AI <
ENABLE
MIN
102
Note(s)
When this is set to ON , the Aquavar
will automatically re-start after a power
failure or fault reset.
Allows the drive to restart after a motor
overcurrent error.
Allows the drive to restart after an
INPUT OVERVOLTAGE error.
Allows the drive to restart after an
INPUT UNDERVOLTAGE error.
Allows the drive to restart after a
transducer or analog signal loss.
FEATURES
Energy Savings Information [Group 26]
Aquavar can calculate the energy savings as compared to a constant speed pump application.
To enable this function to perform properly, local energy costs and comparative application
information must be entered.
Enter the local energy cost in $ (local currency) per kWh into parameter 26.01($/KWhr) and
then enter the nominal power rating of a comparable fixed speed unit into parameter 26.02
(baseline power). To find this, look at the fixed speed pump performance curve and enter the
power for the rated operating point or maximum Brake Horsepower for the specific pump/
impeller combination.
Example - If your power cost is $0.06 per kWh, enter a value of .06 into parameter 26.01.
Parameter
Name
Value/Range
26.01
$/kWh
0-1.00
26.02
BASELINE
0-1000 HP
POWER
26.03
SAVINGS
065535
SCALE
26.04
ENERGY
SAVINGS OP 1
SAVE
METHOD
SAVINGS OP 2
26.05
ENERGY
DISABLED (Default)
SAVE RESET
RESET
Note(s)
Default is zero.
Default is zero.
Scales the analog output when energy
savings is selected.
Calculates energy savings with the Aquavar
based on a fixed speed pump that turns
ON and OFF when not required.
Calculates energy savings with the
Aquavar based on a fixed speed pump
that operates 24 hrs a day. Does not
turn off.
Allows resetting of savings to zero.
One of the benefits of using Aquavar is its ability to automatically shut off the pump when not
required. Parameter 26.04 SAVINGS OPTION #2 allows the savings of using Aquavar to be
tracked during automatic shutdown. The OPTION # 2 will calculate according to a fixed speed
unit that is designed to run continuously 24 hrs a day, 7 days a week.
NOTE: This is an estimated comparative data used for ideal situations, CentriPro cannot
guarantee savings will be exactly as stated. Many system variables
may increase or decrease estimated savings.
Fieldbus Control
The Aquavar CPC may be integrated into BMS (Building Management Systems) or existing
Distributive Control Systems (DCS) via optional Fieldbus control modules. The use of Fieldbus
control modules allows selected Aquavar parameters and operating signals to be accessed
and modified.
Fieldbus control modules are available in numerous communication protocols, including:
DeviceNet, Modbus, Profibus.
Modbus is the DEFAULT protocol for the Aquavar CPC.
With the control module installed (See INSTALLATION manual), set parameter 30.01
FIELDBUS to YES. This will open up parameter groups 90 D SET REC ADDR and 92 D SET
TR ADDR. These parameter groups define the addresses and data sets that are exchanged
between Aquavar and the DCS.
103
FEATURES
Parameter
Name
Value/Range
30.01
COMM
NOT SELECTED
PROTOCOL
(Default)
SELECT
STD MODBUS
EXT FBA
Note(s)
No fieldbus communication
Drive uses MODBUS protocol on the
standard RS485 port. Protocol settings
are in group 32.
The drive communicates with a fieldbus
adapter module in option slot 2 of the
drive. NOTE: When EXT. FBA is selected
parameter group 31 is unlocked.
Any parameter changes that are made using a Fieldbus control system must be saved to the
drive.
Parameter
Name
Value/Range
10.04
PARAMETER
DONE (Default)
SAVE
SAVE
Note(s)
Parameters that are manually entered through
the keypad are automatically saved, only
parameters entered through a Fieldbus
connection must be saved. To save, select SAVE
and press the ENTER key.
Language
The Aquavar CPC system fully supports 3 languages; English(AM), French, and Spanish.
English(AM) refers to American English and is the default language. Units of power are in HP.
Parameter
Name
11.01
LANGUAGE
Value/Range
ENGLISH (AM)
ESPANOL
FRANCAIS
Note(s)
ENGLISH (AM) is the default setting.
Locking
The AQUAVAR CPC has three levels of control panel (keypad) locking; LOCAL LOCK,
PARAMETER LOCK and SET POINT LOCK.
PARAMETER LOCK - In parameter lock, parameters may be viewed, however they cannot
be changed. Starting, Stopping, set point changes and drive fault resets may still be
performed using the keypad. A valid password must be entered in parameter group 10.02.
LOCAL LOCK - In local lock, starting and stopping, and setpoint changes are prevented.
Resetting of drive faults is still possible and ON and OFF control.
SET POINT LOCK When in the ON position, the set-point cannot be changed from the
control panel. This prevents unwanted changes to Aquavar settings.
To change the drive parameters, including 10.03 LOCAL LOCK, the parameter lock must be
opened. To open the parameter lock, go to parameter 10.02 PASS CODE and scroll to the
number 66 and press ENTER. Parameter 10.01 PARAMETER LOCK will read OPEN.
NOTE: If power to the drive is lost [power failure, disconnect, etc] parameter 10.01
PARAMETER LOCK will automatically reset to LOCKED.
104
FEATURES
Parameter
Name
Value/Range
10.01
PARAMETER
LOCKED (Default)
OPEN
10.02
PASS CODE
-Not Displayed-
10.03
LOCAL LOCK OFF (Default)
ON
10.06
SET POINT
OFF (Default)
LOCK
ON
Note(s)
This parameter displays the status of the
parameter lock and can be used to lock
the parameters when necessary. To OPEN
the parameter lock, use parameter 10.02.
Using the arrow keys, scroll to the
number 66 and press enter. This will
open the parameter lock. Note - The
number entry will disappear once
ENTER has been pressed.
This parameter disables local control of
the drive (Start/Stop/setpoint changes).
This lock prevents the set point from
being changed on the control panel.
Must enter password first.
WARNING! It is not possible to stop the drive through the keypad with LOCAL LOCK
set to ON.
Use LOCAL LOCK only with a remote (external) stop/start method.
Keypad must be set in REMOTE before enabling LOCAL LOCK.
Minimum Speed Options
When the Aquavar CPC reaches the minimum speed that is set in parameter 14.02, it can be
programmed to stay at that minimum speed indefinitely, or to shut-down after a time delay.
This reaction applies to conditions where Aquavar is trying to regulate to a setpoint, when it
faults due to a secondary protect condition, or there is little or no process demand.
If the parameter 14.03 CONFIG SPEED MIN is set to MINIMUM FREQ the drive will stay at
minimum speed indefinitely, until the system demand increases, it is shutdown manually, or
a fault occurs forcing it to shutdown. If it is operating at minimum speed due to a Secondary
Protect fault, it will stay at minimum speed until the fault is reset.
If a Pump Protect condition exists and CONFIG SPEED MIN is set to MINIMUM FREQ, Aquavar
will try to reset the fault while at minimum speed if parameter 12.02 AUTO RESTART is set to
ON and parameter 24.06 ERROR RESET is set for the desired number of attempts. If the fault
has not cleared after the selected number of resets has been attempted, the pump will be
shut down. If parameter 24.06 ERROR RESET = 0, the pump will be shut down upon a Pump
Protect fault.
If parameter 14.03 CONFIG SPEED MIN is set to ZERO 0 (DEFAULT), the drive will stop the
pump for Pump Protect and Secondary Protect faults. The reaction to stop the pump when at
minimum speed can be delayed for up to 1800 seconds by programming parameter 14.04
(Stp Delay Min Spd).
For example, if the MINIMUM FREQ. is set for 35 HZ, and the Stp. Delay Min Spd is
set for 5 seconds, the pump will ramp down to 35HZ and remain at that speed for 5
seconds, then turn off. This is dependent upon the demand decreasing in the system.
Leaks will keep the pump running at slow speeds. Also check for properly seated check
valves and bladder tank pressure.
WARNING! It is not possible to manually set speed or frequency below the
MINIMUM SPEED setting in parameter 14.02
105
FEATURES
Minimum Speed Options (continued)
Parameter
Name
Value/Range
14.03
CONFIG
SPD=MINSPD
SPEED MIN
SPD=0 [default]
14.04
STP DELAY
0-1800 sec
MIN SPD
0 (default)
14.05
RESTART
0.0-150%
VALUE
0 (default)
14.06
RESTART
0-3600 Sec
DELAY
0 (default)
12.02
AUTO
OFF (default)
RESTART
ON
24.06
ERROR
0 (Default)
RESET
1-9999
24.07
RESET
0-250 seconds
DELAY
60 seconds (Default)
Note(s)
Selecting SPD=MINSPD will result in the drive
staying at minimum speed until it is manually
shut-off, process demand increases, a secondary
protection fault is cleared, or a pump protection
fault forces it to shutdown.If SPD=0 is selected,
the drive will stop.
This parameter enables the drive to remain at
minimum speed for a period (up to 1800
seconds) before shutting down.
If the drive is shutdown by CONFIG SPEED MIN
(14.03) due to no system demand (pressure
control and level control modes only) the drive
will sleep until the process actual value drops
below a set restart value (14.05) for longer than
the restart delay (14.06). If operating in inverse
mode (21.01) the drive will sleep until the
process variable rises above the restart value.
Wake-up level in % of setpoint value = 0 150%.
Default is 0%. To disable the Restart Value
function enter 0%.
This is the length of time the drive waits
between starting the pump according to
1405 value.
This enables the drive to restart on its own
following a power failure or ERROR RESET.
If the Aquavar unit faults on Pump Protection,
this parameter will reset the fault up to the
selected number of times before completely
shutting off the drive.
The automatic reset of protection faults can be
delayed. Default value is 60 seconds.
Restart Value
Allows a pressure or value drop before the Aquavar starts to maintain system pressure. Units
are in % of set value. (e.g. If set pressure is 100 PSI and 14.05 is set for 90%, then the Aquavar
will wait until system pressure drops to 90 PSI before starting.)
Priming Delay
This feature will override the PUMP PROTECT feature and is designed to allow self-priming
pumps sufficient time to prime before the Aquavar Pump Protection logic becomes active.
The delay period is applied only if the pump is being started from a zero-speed condition.
Once the priming delay is complete, the PROTECTION DELAY (24.06) becomes active, if set.
Parameter
14.07
Name
PRIMING
DELAY
Value/Range
0-6000 Seconds
0 (Default)
Note(s)
The priming delay time is added to the
pump protection delay time.
NOTE: Do not set beyond normal priming time for specific pumps or damage may occur.
Refer to pump manufacturer for maximum allowed priming times before shutdown.
106
FEATURES
Pump Protect Ctrl
This feature is designed to protect the pump from lack of available NPSH, loss of or low
suction, pump run-out. This pump protection feature is exclusive to the Aquavar and
measures the discharge pressure of the pump via the transducer, and compares it with the
minimum allowed system pressure as entered into parameter (2403) PROTECTION LIMIT. If
this parameter is set, then a time delay will need to be set in number of seconds allowed to
run at or below this limit, before shutting down on a fault.
Parameter
24.02
24.03
24.04
Name
PUMP
PROTECT
CTRL
PROTECTION
LIMIT
PROTECTION
DELAY
Value/Range
Note(s)
Disabled (Default)
WARN
WARN & CTRL.
0 6553.5
0 -200 seconds
Name
REGULATION
MODE
Value/Range
NORMAL (Default)
INVERSE
Note(s)
Inverse is normally used for control of
suction side systems.
EXAMPLE If an Aquavar unit is trying to control the level in a suction-side tank or sump, the regulation mode
would be set to INVERSE. As the level in the sump increased, Aquavar would respond by increasing pump speed
to maintain a constant level.
Relay Outputs
The AQUAVAR CPC has three relay outputs that are configurable for different operating
and fault conditions. Relays will revert to original states once warnings or faults are reset or
cleared.
Comment(s)
2 A RMS
107
FEATURES
Parameter
Name
18.01
RELAY R0
OUTPUT
18.04
RELAY R02
OUTPUT
18.07
RELAY R03
Value/Range
Note(s)
NOT USED
RUNNING
READY
Default for RO3
OUTPUT
VFD FAULT
SECND PRTECT A
Secondary Protect A activation.
PUMP PROTECT
Pump protection activation.
START SLAVE
Used with multi-pump macro only.
STAND BY
NOTE: When using relay outputs to activate constant speed pumps in a multi-pump
application, the slave pumps 1, 2 and 3 should utilize relay outputs RO1, RO2, and RO3
accordingly (Slave 1 RO1). Sequence logic is affected by these selections.
Restart Options
Parameter 14.05 See MINIMUM SPEED OPTIONS
Low Water (Suction) Protection
The Aquavar provides protection from dry-run conditons in pressure, level, temperature and
speed control modes. This feature may also be used to provide inter-lock capabilities. In these
cases, additional system condition inputs (e.g. level switch, pressure switch, flow switch, etc)
are used to alert Aquavar of conditions that require protection of the pump.
Discharge Header
Flow Switch
Speed Signal
Once wired, parameter 24.05 LOW WATER must be set to WARNING or WARN AND
CONTROL. Digital Input 2 (DI 2), terminal # 14 on the X1 terminal board. If this contact is
OPEN, the response being:
1. WARN & CONTROL In this response, Aquavar will issue a warning and then either shut
down or reduce speed depending on your settings. At this point the pump will behave
similar to the description in MINIMUM SPEED. Alarm & Control is the recommended
setting.
108
FEATURES
2. WARNING ONLY In this response, Aquavar will simply issue an alarm/warning displayed
on the keypad screen, but continues to operate.
NOTE: The WARNING ONLY mode may result in damage to the pump if a low water
condition occurs. It is recommended to set this for WARN & CONTROL.
Keypad Failure
In the event of a keypad failure, Aquavar has been configured to fault and shut down the
controller. This functionality can be disabled, or configured to result in a drive fault.
Parameter
24.01
Name
KEYPAD
FAILURE
Value/Range
DISABLED (default)
FAULT
Note(s)
Fault message - PANEL LOSS
Name
Value/Range
16.01
SP1/SP2
SETP 1 [Default]
SELECT
DI4
FIELDBUS
16.02
SET POINT 1 KEYPAD (Default)
SEL
AI 1
FIELDBUS
16.03
SET POINT 2 KEYPAD (Default)
SEL
ANALOG INPUT
FIELDBUS
22.08
SET POINT 2
OFF, 14
SOURCE
Note(s)
This parameter defines the source that
toggles the Aquavar unit between
Set Point 1 or Set Point 2.
SET POINT 1 (Default) indicates that
only set point 1 is being used.
DI4 is a digital input where 0
(Open) selects Set Point 1 and 1
(Closed) selects Set Point 2.
This selects where the value for
Set Point-1or 2 is coming from.
KEYPAD - a number [e.g. 100] will
be manually entered via the keypad.
Selecting ANALOG INPUT will require
entry of parameters 16.03-16.04.
This selects where the value for
Set Point-1or 2 is coming from.
KEYPAD - a number [e.g. 100] will
be manually entered via the keypad.
Selecting ANALOG INPUT will require
entry of parameters 16.03-16.04.
Must select source.
EXAMPLE for 16.02 and 16.03 An irrigation system requires 110 psi for watering all zones, then
during the daytime normal water pressure is set for 60 psi.
109
FEATURES
Parameter
Value
Notes
16.01
DI4
16.02
KEYPAD
16.03
KEYPAD
A switch would be wired into DI4 and the DCOM on the X1 terminal to
toggle between set point 1 and set point 2.
The setpoint would be manually entered using the Aquavar keypad.
When the switch [DI4] is set to 0 (Open), the set point would be entered
as 110 psi using the keypad REF button.
The set point would be manually entered using the Aquavar keypad.
When the switch [DI4] is set to 1 (Closed), the set point would be entered
as 60 psi using the keypad REF button.
WARNING! Parameter 16.01, 16.02 and 16.05 can only be changed when the motor
is not running. Most parameters require you to stop the pump, before programming.
System Curve Compensation
The AQUAVAR CPC system can automatically compensate for system friction losses due to
increased flow in single pump operation or multi-pump backup modes. Tables are available in
most pump catalogs to assist in determining the amount of friction loss that can be expected
for various pipe sizes and flow rates on simple systems. As flow increases, velocity increases
causing friction loss through piping and various fixtures. Normally this would provide a loss in
flow or overall pressure to the system. With the Aquavar you can compensate for this friction
loss!
The diagram below illustrates a typical system curve in relation to pump speed.
Head /
Pressure
N=100%
%N
System Curve
on
sati
%N
ys
gS
ltin
u
Res
Set
Pressure
o
eC
urv
C
tem
en
mp
Pressure Increase
%N
%N
Flow
In this case the system pressure set point is shown at shutoff ( 0 flow) and the increase in
setpoint pressure is shown for increasing flow. EXAMPLE - If the set point is 150 Ft [65 PSIG
@ 1.0 SG] and the system resistance increase 10 Ft at the maximum flow rate, or roughly 7%
of the set point, parameter 21.08 would be set as 7.
110
FEATURES
Parameter
Name
Value/Range
21.02
PRESS INCR
0- 60 HZ
SPEED
20 HZ (Default)
21.03
PRESS INCR
0-100%
0.0 %
0% (Default)
Note(s)
This is the frequency at which system curve
compensation begins. At speeds below this, no
compensation for increased resistance is made.
This is the amount that Aquavar will have
increased the set point at maximum speed.
Test Run
The TEST RUN capability allows the Aquavar system to run periodically if it has been inactive.
The most common circumstance for which Test Run would be applied is when a standby
pump is infrequently used; the test run would allow lubrication of bearings and help verify if
the unit is ready for operation. The TEST RUN DELAY sets the interval that automatic test runs
will occur at.
Test runs are factory programmed for 20 seconds. This duration cannot be changed. If
Automatic test run is selected, the test run is at 50% of maximum speed.
NOTE: Once manual test is selected and the test is complete, parameter 12.03 will return
to NOT SEL.
Parameter
Name
Value/Range
12.02
AUTO
OFF (Default)
RESTART
ON
12.03
TEST RUN
NOT SEL (default)
AUTOMATIC
MANUAL
12.04
TEST SPEED
0-100%
% (FL)
50% (Default)
12.05
TEST RUN
0-3600 hours
DELAY
1000 Hrs (Default)
Note(s)
Must be set to ON for test run function to
operate.
111
FEATURES
Set Point
Hysteresis
Window
R3
R4
Set Point
R1
R2
10s
50s
Time
Parameter
13.06
Name
Value/Range
REG
0-100%
WINDOW
Note(s)
Constant Pressure = 8%
Flow [Direct] = 30%
Suggested settings are above in the notes. Sometimes the REGULATION WINDOW will have to be adjusted to
smooth out the system pressure. Default setting is 8%.
NOTE: If the system pressure drops below or goes above the hysteresis limits (DASHED
lines), then the Aquavar control software will adjust the speed with the fast ramps. This
would occur if you have a rapid demand of water in your system. Normally it takes a few
seconds to level off.
112
R3
R3
R4
R4
Hysteresis -%
Hysteresis -%
Window Setting
% of Set Point
Set Point
Set Point
Hysteresis
Window
FEATURES
R1
Time
RAMP HYSTERESIS
Ramp hysteresis is the point at which the Aquavar controller changes over from the fast
ramp to the slow ramp. Default values of Ramp Hysteresis are in % of the regulation window.
The values for RAMP HYSTERESIS are automatically selected based upon the control mode
selection made during programming.
EXAMPLE: Using the same example above, the Regulation Window was 8 psig. An 80% ramp hysteresis would
be 3.2 PSIG. Note from the graph, this is 1.6 PSIG on the upper half of the regulation window, and 1.6 PSIG on
the lower half of the regulation window.
Parameter
13.05
Name
Value/Range
RAMP
0-100%
HYSTERESIS
Note(s)
Pressure = 80%
Flow [Direct] = 5%
As the figure shows, Aquavar attempts to keep the actual process reading within the Setpoint
Hysteresis Window using the slow acceleration and deceleration ramp rates. When the
process reading exceeds this window, it will compensate using the fast acceleration or
deceleration ramp rates.
Adjusting Ramp Rates
Ramp 1 - Fast Acceleration: This ramp is the fast run up time used when the pump first
starts and is trying to reach the setpoint. A setting too fast may overshoot the set-point, while
a setting too slow may cause the drive to respond too slowly to set point changes. NOTE:
FOR AQUAVAR UNITS ABOVE 10 HP, SET RAMP 1 AND RAMP 2 TO AT LEAST 8 10
SECONDS.
Parameter
13.01
Name
Value/Range
RAMP 1
0-1800s
FAST ACCEL
Note(s)
Pressure default = 5 seconds
Level, Temperature default = 20 seconds
113
FEATURES
Ramp 2 - Fast Deceleration: This ramp is the fast run down time used when the pump is
shutting down. If the setting R2 setting is too fast, the pump may oscillate, or hunt while it
tries to attain the set point. If it is too slow, the actual process value may rise well above the
set point. NOTE: AQUAVAR UNITS ABOVE 10 HP, RAMP 1 AND RAMP 2 SHOULD BE SET
FOR AT LEAST 8 10 SECONDS.
NOTE: Air in the pump system may cause a condition that looks like oscillation or hunting.
Make sure all the air is purged from the system before trying to change the Ramp 2 setting.
Parameter
13.02
Name
Value/Range
RAMP 2
0-1800s
FAST DECEL
Note(s)
Pressure default = 5 sec
Level, Temperature default = 20 seconds
Ramp 3, Slow Acceleration: This ramp is the slow run up time used when the pump is
operating within its setpoint window. If the R3 setting is too slow, pressure or flow may be
slow to respond to the set point as demand varies. A setting too fast may lead to oscillation.
Parameter
Name
Value/Range
13.03
RAMP 3
0-1800s
SLOW ACCEL
Note(s)
Pressure default = 60 seconds
Flow [magnetic flow meter] default = 50 sec
Level, Temperature default = 200 seconds
Ramp 4, Slow Deceleration: This ramp is the slow run down time used when the pump is
operating within its set point window. If the R4 setting is too slow, it will lead to oscillation. A
setting too fast may delay the motor shut-down when demand is reduced.
Parameter
Name
Value/Range
13.04
RAMP 4
0-1800s
SLOW DECEL
114
Note(s)
Pressure default = 60 seconds
Flow [magnetic flow meter] default = 50 sec
Level, Temperature default = 200 seconds
FAULTS/ALARMS
Warning! Do not attempt any measurement, parts replacement or other service
procedure not described in this manual. Such action will void the warranty, may
endanger correct operation, and increase downtime and expense.
Warning! All electrical installation and maintenance work described in this chapter
should only be undertaken by qualified service personnel. The Safety instructions on
the first pages of this manual must be followed.
Diagnostic Displays
The drive detects error situations and reports them using:
The green and red LED on the body of the drive.
The status LED on the control panel (if a control panel is attached to the drive).
The control panel display (if a control panel is attached to the drive).
The Fault Word and Alarm Word parameter bits (parameters 0310 to 0311).
See Group 03: FB Status Words on page 50 for the bit definitions.
The form of the display depends on the severity of the error. You can specify the severity for
many errors by directing the drive to:
Ignore the error situation.
Report the situation as an alarm.
Report the situation as a fault.
Red Faults
The drive signals that it has detected a severe error, or fault, by:
Enabling the red LED on the drive (LED is either steady on or blinking).
Setting an appropriate bit in a Fault Word parameter (0305 to 0307).
Overriding the control panel display with the display of a fault code.
Stopping the motor (if it was on).
The fault code on the control panel display is temporary. Pressing any of the following buttons
removes the fault message: MENU, ENTER, UP button or DOWN button. The message reappears after a few seconds if the control panel is not touched and the fault is still active.
Flashing Green Alarms
For less severe errors, called alarms, the diagnostic display is advisory. For these situations,
the drive is simply reporting that it had detected something unusual.
The drive signals that it has detected an alarm, by:
Flashing the green LED on the drive does not apply to alarms that arise from control
panel operation errors (Alarms 1 to 7).
Setting an appropriate bit in an Alarm Word parameter (0308 or 0309).
See Group 03: FB Status Words on page 50 for the bit definitions.
Overriding the control panel display with the display of an alarm code and/or name.
The alarm messages disappears from the control panel display if/when any of the following
are pressed on the control panel: MENU, ENTER, UP button, or DOWN button.
115
FAULTS/ALARMS
Correcting Faults
The recommended corrective action for faults is:
Use the Fault Listing table below to find and address the root cause of the problem.
Reset the drive. See Fault Resetting on page 119.
* Drive not ready fault. Check supply voltage / DC Bus = 1.35 x input voltage.
* Comm fault drive not responding. Internal communication lost.
Cycle Power Remove and reinstall panel Replace panel
Fault Listing
Fault Fault Name
Code In Panel
1 OVERCURRENT
2 DC OVERVOLT
3 DEV OVERTEMP
4 SHORT CIRC
5 OVERLOAD
6 DC UNDERVOLT
7 AI1 LOSS
Analog input 1 loss. Analog input value is less than AI1 MIN (1604).
Check for and correct:
Source and connection for analog input.
Parameter settings for AI1 MIN (1604).
8 AI2 LOSS
Analog input 2 loss. Analog input value is less than SENSOR MIN (1506).
Check for and correct:
Source and connection for analog input.
Parameter settings for SENSOR MIN (1506) and (1503) TRANSDUCER MIN.
9 MOT OVERTEMP
116
FAULTS/ALARMS
Fault Fault Name
Code In Panel
10 PANEL LOSS
11 ID RUN FAIL
12 MOTOR STALL
13 RESERVED
14 PUMP PROTECT
15 LOW WATER
16 EARTH FAULT
17 UNDERLOAD
18 THERM FAIL
19 OPEX LINK
20 OPEX PWR
21 CURR MEAS
22 SUPPLY PHASE
23 RESERVED
24 OVERSPEED
25 RESERVED
26 DRIVE ID
117
FAULTS/ALARMS
Fault Fault Name
Code In Panel
27 CONFIG FILE
Internal configuration file has an error. Contact your local factory
representative.
Cycle power
Check Group 9902 / Drive Size Type
28 SERIAL 1 ERR
Fieldbus communication has timed out. Check for and correct:
Fault setup (2409 COMM FAULT FUNC and 2410 COMM FAULT TIME).
Communication settings (Group 31 or 32 as appropriate).
Poor connections and/or noise on line.
29 EFB CON FILE
Error in reading the configuration file for the fieldbus adapter.
30 FORCE TRIP
Fault trip forced by the fieldbus. See the fieldbus Users Manual.
31 EFB 1
Fault code reserved for the EFB protocol application.
The meaning is protocol dependent.
32 EFB 2
33 EFB 3
34 MOTOR PHASE
Fault in the motor circuit. One of the motor phases is lost.
Check for and correct:
Motor fault
Motor wiring, connections
Motor cable fault
Internal fault
35 OUTP WIRING
Error in power wiring suspected. Check for and correct:
Input power wired to drive output
Ground faults
101 SERF CORRUPT
Error internal to the drive. Contact your local factory
representative and report the error number.
102 SERF IITFILE
103 SERF MACRO
104 SERF EFBPROT
105 SERF BPFILE
201 DSP T1 OVERLOAD
Error internal to the drive. Contact your local factory
representative and report the error number.
202 DSP T2 OVERLOAD
203
204
205
206
DSP T3 OVERLOAD
DSP STACK ERROR
DSP REV ERROR
OMIO ID ERROR
Faults that indicate conflicts in the parameter settings are listed below.
1000 PAR HZRPM
1001 PAR PFCREFNG
1003 PAR AI SCALE
1004 PAR AO SCALE
118
FAULTS/ALARMS
Fault Fault Name
Code In Panel
1005 PAR PCU 2
1007 PAR FBUS
Fault Resetting
The AQUAVAR can be configured to automatically reset certain faults. Refer to parameter
Group 24: Fault Functions and Group 25: Automatic Reset.
Warning! If an external source for start command is selected and it is active, the
AQUAVAR may start immediately after fault reset.
Flashing Red LED
To reset the drive for faults indicated by a flashing red LED:
Turn the power off for 5 minutes.
Red LED
To reset the drive for faults indicated by a red LED (on, not flashing), correct the problem and
do one of the following:
From the control panel: Press RESET
Turn the power off for 5 minutes.
NOTE: In some cases a fault reset soft key will appear on the display. Press this button to
reset, then press the start key.
When the fault has been removed, the motor can be started.
Fault History
For reference, the last three fault codes are stored in Group 01: VFD Signals. Specifically parameters 01160118. The Aquavar CPC stores additional fault data, which helps the operator
identify operating conditions at the time of fault. (Parameters 01190126).
To clear the fault history, go to PAR GROUPS 01, VFD SIGNALS. Press the SEL key. Down arrow
to 0116 LAST FAULT, then press the EDIT key. Next press the UP and DOWN arrow at the
same time until NO RECORD shows on the display. This clears all the faults in the history.
119
FAULTS/ALARMS
Correcting Alarms
The recommended corrective action for alarms is:
Determine if the Alarm requires any corrective action (action is not always required).
Use Alarm Listing below to find and address the root cause of the problem.
Press the reset key (when available) or turn the power off for at least 5 minutes.
Alarm Listing
The following table lists the alarms by code number and describes each.
Alarm
Code
Display Description
2001 Reserved
2002
2003
2004 DIR LOCK
2005
I/O COMM
Fieldbus communication has timed out. Check for and correct:
Fault setup (2411 COMM FAULT FUNC and 2412 COMM FAULT TIME).
Communication settings (Group 31 or 32 as appropriate).
Poor connections and/or noise on the line.
2006
AI1 LOSS
Analog Input 1 is lost, or value is less than the minimum setting.
Check:
Input source and connections
Parameter that sets the minimum (1604)
2007 TRANSDUCER Analog Input 2 is lost, or value is less than the minimum setting.
LOSS Check:
Transducer, connection and wiring
Input source and connections
Parameter that sets the minimum (1506)
2008 PANEL LOSS
Panel communication is lost and either:
Drive is in local control mode (the control panel displays LOC), or
Drive is in remote control mode (REM) and is parameterized to accept
start/stop, direction or reference from the control panel.
To correct check:
Communication lines and connections
Parameter 2401 KEYPAD FAILURE
2009
RESERVED
120
FAULTS/ALARMS
Alarm
Code
Display Description
2010 MOT
OVERTEMP
2011 UNDERLOAD
2012 MOTOR STALL
2013
AUTORESET
(note 1)
2015
ALARM 2015
PUMP
PROTECT
2016
LOW WATER
2017
NOT USED
2023
E-STOP
FAULT
This alarm warns that the drive is about to perform an automatic fault reset,
which may start the motor.
To control automatic reset, use parameter Group 12 AUTOMATIC RESET.
Pump protection has been triggered via parameter 2403 (protection limit)
and 2404 (protection delay). This protection is enabled when the pump
reaches maximum frequency and cannot maintain system set point for the
specific delay time. Check for air entrainment, plugged impeller, blocked
suction, lack of NPSHa, pump run-out.
Check DI2 contact or suction switch continuity.
Check jumper / connection, between Terminal 10 and 15 (DI3).
121
Maintenance Intervals
If installed in an appropriate environment, the drive requires very little maintenance. This table
lists the routine maintenance intervals recommended by CentriPro.
Maintenance
Interval
Instruction
Heatsink Temperature
Check and Cleaning
Main Cooling
Every five years
Fan Replacement
Internal Enclosure
Every three years
Cooling Fan Replacement
(IP 54/UL Type 12 units)
Capacitor Change
Every ten years
(Frame size R5 and R6)
Heatsink
The heatsink fins accumulate dust from the cooling air. Since a dusty heatsink is less efficient
at cooling the drive, overtemperature faults become more likely. In a normal environment
(not dusty, clean) check the heatsink annually, in a dusty environment check more often.
Clean the heatsink as follows (when necessary):
1. Remove power from drive
2. Remove the cooling fan (see section Main Fan Replacement below)
3. Blow clean compressed air (not humid) from bottom to top and simultaneously use a
vacuum cleaner at the air outlet to trap the dust.
Note: If there is a risk of the dust entering adjoining equipment, perform the cleaning in
another room.
4. Replace the cooling fan
5. Restore power
Capacitors
The drive intermediate circuit employs several electrolytic capacitors. Their life span is from
35,00090,000 hours depending on drive loading and ambient temperature. Capacitor life
can be prolonged by lowering the ambient temperature.
It is not possible to predict a capacitor failure. Capacitor failure is usually followed by a input
power fuse failure or a fault trip. Contact factory if capacitor failure is suspected. Replacements for frame size R5 and R6 are available from the factory. Do not use other than factory
specified spare parts.
Control Panel
Cleaning
Use a soft damp cloth to clean the control panel. Avoid harsh cleaners which could scratch the
display window.
Battery
A battery is only used in control panels that have the clock function available and enabled.
The battery keeps the clock operating in memory during power interruptions. To remove the
battery, use a coin to rotate the battery holder on the back of the control panel. Replace the
battery with type CR2032.
124
Designation
Component
A49
Control Panel
A41
Motor Control and I/O Board (OMIO)
Y41
Cooling Fan
_
C Capacitors
125
Fan
The life span of the cooling fan of the drive is about 50,000 (R7) and 60,000 (R8) hours. The
actual life span depends on the running time of the fan, ambient temperature and dust concentration. See the appropriate Aquavar CPC User Manual for the actual signal which indicates the running time of the cooling fan.
Replacement fans are available from CentriPro. Do not use other than factory specified spare
parts.
3
3
DCDC+
2
7
3
8
5
3
3
3
126
DC+
DC-
127
128
Where
OMIO Board
LED
Red (blinking)
Green
Control Panel
Red
Mounting Platform
Green
OITF Board
V204 (green)
V309 (red)
V310 (green)
Control Panel
Cleaning
Use a soft damp cloth to clean the control panel. Avoid harsh cleaners which could scratch the
display window.
Battery
A battery is only used in Assistant Control Panels that have the clock function available and
enabled. The battery keeps the clock operating in memory during power interruptions.
The expected life for the battery is greater than ten years. To remove the battery, use a coin
to rotate the battery holder on the back of the control panel. Replace the battery with type
CR2032.
129
TECHNICAL DATA
Sizing
The current ratings are the same regardless of the supply voltage within one voltage range.
To achieve the rated motor power given in the table, the rated current of the drive must be
higher than or equal to the rated motor current.
Note 1: The maximum allowed motor shaft power is limited to 1.5 ATimes Rated HP. If
the limit is exceeded, motor torque and current are automatically restricted. The function
protects the input bridge of the drive against overload.
Note 2: The ratings apply in ambient temperature of 40 C (104 F).
Derating
The load capacity (current and power) decreases if the installation site altitude exceeds 1000
meters (3300 ft), or if the ambient temperature exceeds 40 C (104 F) or if 8 kHz switching
frequency (parameter 5001) is used.
Temperature Derating
In the temperature range +40 C50 C (+104 F122 F) the rated output current is decreased 1% for every 1 C (1.8 F) above +40 C (+104 F). The output current is calculated by
multiplying the current given in the rating table by the derating factor.
Example: If the ambient temperature is 50 C (+122 F) the derating factor is
100% - 1%/C x 10 C = 90% or 0.90.
The output current is then 0.90 x I2N or 0.90 x I2hd.
Altitude Derating
The derating is 1% for every 100 m (330 feet) above 3300 feet. If the installation site is higher
than 2000 m (6600 feet) above sea level, please contact the factory for assistance.
Single Phase Supply Derating
For 208240 Volt series drives, a single phase supply can be used. In that case, the derating
is 50%, for the maximum amps and corresponding power rating of the three phase drive at
208-230 Volt input.
Switching Frequency Derating
If the 8 kHz switching frequency (parameter 5001) is used, derate HP and current output to
80%.
130
TECHNICAL DATA
Cable Sizing/Ratings
208240 Volt Drives
The following tables provide current, horsepower, frame size and recommended cable sizes
for the Aquavar CPC.
CENTRIPRO AQUAVAR CPC
NEMA 1
Full
NORMAL
Output
Frame
Voltage Phase
Base
Load
DUTY
Cable
Size
Size2 Min. AWG1
Model
Amps HORSEPOWER
CPC20171 8.5
2
R1
14
CPC20241 12
3
R2
12
CPC20311 15.5
5
R2
12
CPC20461 23
7.5
R3
10
CPC20591 29.5
10
R3
8
230
1 CPC20881 44.0
15
R4
6
CPC21141 57.0
20
R4
4
CPC21431 71.5
25
R6
3
CPC21781 89.0
30
R6
2
CPC22211 110.5
40
R6
1/0
CPC22481 124.0
50
R6
2/0
CPC20121 11.8
3
R1
14
CPC20171 16.7
5
R1
10
CPC20241 24.2
7.5
R2
8
CPC20311 30.8
10
R2
8
CPC20461 46.2
15
R3
6
CPC20591 59.4
20
R3
4
230
3 CPC20751 74.8
25
R4
3
CPC20881 88.0
30
R4
2
CPC21141 114.0
40
R4
1/0
CPC21431 143.0
50
R6
3/0
CPC21781 178.0
60
R6
4/0
CPC22211 221.0
75
R6 300MCM
CPC22481 248.0
100
R6 350MCM
Input
Cable Size
Min. AWG1
10
8
8
6
4
2
1/0
3/0
4/0
300MCM
350MCM
14
10
8
8
6
4
3
2
1/0
3/0
4/0
300MCM
350MCM
(1) Recommended AWG Size based on NEC table 310.16, 40 C ambient, 90 C, UL type copper wire. For other
wire sizes or types, consult local, state or NEC codes.
(2) Frame sizes R7 and R8, the Aquavar CPC will have multiple conductor terminals for each phase. Consult
technical section (CABLE TERMINALS).
131
TECHNICAL DATA
Cable Sizing/Ratings
380480 Volt Drives
The following table provides Aquavar CPC rating information and
recommended wire sizing for the input and output cables.
CENTRIPRO AQUAVAR CPC
NEMA 1
Full
NORMAL
Output
Input
Frame
Voltage Phase
Base
Load
DUTY
Cable
Size
Cable
Size
Size2 Min. AWG1 Min. AWG1
Model
Amps HORSEPOWER
CPC40061 6.9
3
R1
14
14
CPC40081 8.8
5
R1
14
14
CPC40121 11.9
7.5
R1
14
14
CPC40151 15.4
10
R2
12
12
CPC40231 23
15
R2
12
12
CPC40311 31
20
R3
10
8
CPC40381 38
25
R3
8
8
CPC40451 45
30
R3
8
6
CPC40591 59
40
R4
6
4
CPC40721 72
50
R4
4
3
CPC40771 77
60
R4
4
3
460
3 CPC40971 97
75
R4
3
1
CPC41251 125
100
R5
1
2/0
CPC41571 157
125
R6
2/0
3/0
CPC41801 180
150
R6
3/0
4/0
CPC42451 245
200
R7 350MCM 350MCM
CPC43161
316
250
R7
2 X 250MCM 2 X 250MCM
CPC43681
368
300
R8
2 X 300MCM 2 X 300MCM
CPC44141
414
350
R8
2 X 400MCM 2 X 400MCM
CPC44861
486
400
R8
2 X 500MCM 2 X 500MCM
CPC45261
526
450
R8
2 X 350MCM 2 X 350MCM
CPC46021
602
500
R8
2 X 500MCM 2 X 500MCM
CPC46451
645
550
R8
2 X 500MCM 2 X 500MCM
(1) Recommended AWG Size based on NEC table 310.16, 40 C ambient, 90 C, UL type copper wire. For other
wire sizes or types, consult local, state or NEC codes.
(2) Frame sizes R7 and R8, the Aquavar CPC will have multiple conductor terminals for each phase. Consult
technical section (CABLE TERMINALS) for maximum wire diameter and torque values.
132
TECHNICAL DATA
Fuse Sizing/Ratings
208240 Volt Drives
Branch circuit protection must be provided by the end user, electrical contractor or distributor, sized per local, state or local National Electrical Codes. Recommendations for fused
circuit protection are in the following tables.
CENTRIPRO AQUAVAR CPC
NEMA 1
Full
NORMAL
Input
Frame
Fuse Type3
Voltage Phase
Base
Load
DUTY
Current
Size
JJN
Model
Amps HORSEPOWER
Amps
CPC20171 8.5
2
R1 17.3
20
CPC20241 12
3
R2 24.5
30
CPC20311 15.5
5
R2
31.6
40
CPC20461 23
7.5
R3 46.9
60
CPC20591
29.5 10 R3
60.2 70
230
1 CPC20881 44.0
15
R4
89.8
110
CPC21141 57.0
20
R4 116.3
150
CPC21431 71.5
25
R6 145.9
175
CPC21781 89.0
30
R6 181.6
225
CPC22211 110.5
40
R6
225.4
300
CPC22481 124.0
50
R6
252.9
300
CPC20121 11.8
3
R1
12.0
15
CPC20171 16.7
5
R1
17.0
25
CPC20241 24.2
7.5
R2
24.7
30
CPC20311
30.8 10 R2
31.4 40
CPC20461
46.2 15 R3
47.1 60
CPC20591
59.4 20 R3
60.6 70
230
3
CPC20751
74.8 25 R4
76.3 90
CPC20881 88.0
30
R4
89.8
110
CPC21141 114.0
40
R4
116.3
150
CPC21431 143.0
50
R6
145.9
175
CPC21781 178.0
60
R6
181.6
225
CPC22211 221.0
75
R6
225.4
300
CPC22481
248.0 100 R6
252.9 300
(3) UL Class T fuses are recommended for short circuit protection. Very fast acting Bussmann* T-tron type
JJN and JJS are shown in the Aquavar CPC tables. Other manufaturers are acceptable if they meet fuse
requirements.
* Bussmann is a registered trademark of Cooper Industries Inc.
133
TECHNICAL DATA
Fuse Sizing/Ratings
380480 Volt Drives
The following table provides Aquavar CPC rating information and recommended fuse sizing
for the input short circuit protection. Branch circuit protection must be provided by the end
user, contractor or distributor. Sized according to local or applicable NEC codes.
CENTRIPRO AQUAVAR CPC
NEMA 1
Full
NORMAL
Input
Frame
Fuse Type3
Voltage Phase
Base
Load
DUTY
Current
Size
JJN
Model
Amps HORSEPOWER
Amps
CPC40061 6.9
3
R1
7.0
10
CPC40081 8.8
5
R1
9.0
15
CPC40121 11.9
7.5
R1
12.1
15
CPC40151
15.4 10 R2
15.7 20
CPC40231 23
15
R2 23.5
30
CPC40311 31
20
R3 31.6
40
CPC40381 38
25
R3 38.8
45
CPC40451 45
30
R3 44.9
60
CPC40591 59
40
R4 60.2
70
CPC40721 72
50
R4 73.4
90
CPC40771 77
60
R4 78.5
90
460
3 CPC40971 97
75
R4
98.0
125
CPC41251 125
100
R5 126.5
150
CPC41571 157
125
R6 160.1
200
CPC41801 180
150
R6 183.6
225
CPC42451 245
200
R7 250.0
300
CPC43161 316
250
R7 322.3
400
CPC43681 368
300
R8 375.4
450
CPC44141 414
350
R8 422.3
500
CPC44861 486
400
R8 495.8
600
CPC45261 526
450
R8 536.5
800
CPC46021 602
500
R8 614.0
800
CPC46451 645
550
R8 658.0
800
(3) UL Class T fuses are recommended for short circuit protection. Very fast acting Bussmann* T-tron type
JJN and JJS are shown in the Aquavar CPC tables. Other manufaturers are acceptable if they meet fuse
requirements.
134
TECHNICAL DATA
Cable Terminals (Frames R1-R6)
Mains and motor cable maximum sizes (per phase) accepted at the cable
terminals and the tightening torques are listed below.
U1, V1, W1
Earthing PE
Control Wire
U2, V2, W2
Ground
Frame
Maximum Torque Maximum Torque Maximum Torque
Size
Wire Size
Wire Size
Wire Size
mm2 AWG Nm lb-ft mm2 AWG Nm lb-ft mm2 AWG Nm lb-ft
R1
6
8 1.4 1.0 4 10 1.4 1.0
R2 10
6
1.4
1.0
10
8
1.4
1.0
R3 25
3
1.8
1.3
16
6
1.8
1.3
2
R4
R5
2
3
58
58
2.28
2.28
M8
M8
1522 1016
1522 1016
135
TECHNICAL DATA
Input Power (Mains) Connection
Voltage (U1)
Prospective Short-Circuit
Current (IEC 629)
Frequency
4863 Hz
Imbalance
Fundamental Power
Factor (cos phi1)
Cable Temperature
Rating
Motor Connection
Voltage (U2) 0U1, 3-phase symmetrical, Umax at the field weakening point.
Frequency
0500 Hz
Frequency Resolution
0.01 Hz
Current
See Ratings on pages 131-134
Power Limit
1.5 x Rated HP
Field Weakening Point
1060 Hz
Switching Frequency
Selectable: 1, 4 or 8 kHz
Cable Temperature
90 C (194 F) rating minimum
Rating
Maximum Motor Cable Length
Frame Size
fsw = 1 or 4 kHz
fsw = 8 kHz
Maximum Motor
R1
100 m
50 m
Cable Length
R2 - R4
200 m
100 m
R5 - R6
300 m
150 m
R7 - R8
300 m
NA
WARNING! Using a motor cable longer than specified in the chart above may cause
permanent damage to the drive or motor.
WARNING! Use of an output load filter or reactor is required when motor leads
exceed the above recommendations. Consult motor manufacturer on required use
of inverter drives.
136
TECHNICAL DATA
Control Connection
Analog Inputs
and Outputs
Digital Inputs
Relays
(Digital Outputs)
Cable Specifications
Cooling Specifications
Internal fan, flow direction from bottom to top.
Free space around the unit:
200 mm (8 in) above and below the unit.
25 mm (1 in) along each side of the unit.
137
TECHNICAL DATA
Cooling (Frames R7-R8)
Installation Procedure
Choose the mounting orientation (a, b, c or d).
a)
b)
c)
Lifted from above
Symbols:
required free space
air inlet surface
wall fixing point (recommended)
control panel mounting slot
Required Free Space Around the Unit for
Frame Mounting
Mounting, Maintenance, Service and Cooling*
Size Orientation
Front
Side
Above
mm in mm in mm in
a,d
500
20
200
7.9
b
500
20
200
7.9
R7
lifting lifting
c
200**
7.9**
space space
a,d
600
24
300
12
b
600
24
300
12
R8
lifting lifting
c
300**
12**
space space
* Space for the installer not included.
** Space for the fan and capacitor replacement not included.
138
TECHNICAL DATA
Air Flow, 380480 Volt Drives
The following table lists heat loss and air flow data for 380480 Volt drives.
CENTRIPRO AQUAVAR CPC
NEMA 1
Full
NORMAL
Heat Loss Air
Frame
Voltage Phase
Base
Load
DUTY
Flow
Size
Model
Amps HORSEPOWER
Watts BTU/HR CFM
CPC40061 6.9
3
R1 97 331 26
CPC40081 8.8
5
R1 127 433 26
CPC40121 11.9
7.5
R1 172 587 26
CPC40151 15.4
10
R2 232 792 52
CPC40231 23
15
R2 337 1150 52
CPC40311 31
20
R3 457 1560 79
CPC40381 38
25
R3 562 1918 79
CPC40451 45
30
R3 667 2276 165
CPC40591 59
40
R4 907 3096 165
CPC40721 72
50
R4 1120 3820 165
CPC40771 77
60
R4 1295 4420 168
460
3 CPC40971 97
75
R4 1440 4915 168
CPC41251 125
100
R5 1940 6621 239
CPC41571 157
125
R6 2310 7884 239
CPC41801 180
150
R6 2810 9590 239
CPC42451 245
200
R7 3850 13144 319
CPC43161 316
250
R7 6850 23386 319
CPC43681 368
300
R8 6850 23386 721
CPC44141 414
350
R8 7850 26800 721
CPC44861 486
400
R8 7850 26800 721
CPC45261 526
450
R8 7600 25946 721
CPC46021 602
500
R8 8100 27653 721
CPC46451 645
550
R8 9100 31067 721
139
TECHNICAL DATA
Air Flow, 208240 Volt Drives
The following table lists heat loss and air flow data for 208240 Volt drives.
CENTRIPRO AQUAVAR CPC
NEMA 1
Full
NORMAL
Heat Loss Air
Frame
Voltage Phase
Base
Load
DUTY
Flow
Size
Model
Amps HORSEPOWER
Watts BTU/HR CFM
CPC20171 8.5
2
R1 161 551 26
CPC20241 12
3
R2 227 776 52
CPC20311 15.5
5
R2 285 373 52
CPC20461 23
7.5
R3 420 1434 79
CPC20591 29.5
10
R3 536 1829 79
230
1 CPC20881 44.0
15
R4 786 2685 165
CPC21141 57.0
20
R4 1014 3463 165
CPC21431 71.5
25
R6 1268 4431 238
CPC21781 89.0
30
R6 1575 5379 238
CPC22211 110.5
40
R6 1952 6666 238
CPC22481 124.0
50
R6 2189 7474 238
CPC20121 11.8
3
R1 116 404 26
CPC20171 16.7
5
R1 161 551 26
CPC20241 24.2
7.5
R2 227 776 52
CPC20311 30.8
10
R2 285 373 52
CPC20461 46.2
15
R3 420 1434 79
CPC20591 59.4
20
R3 536 1829 79
230
3 CPC20751 74.8
25
R4 671 2290 165
CPC20881 88.0
30
R4 786 2685 165
CPC21141 114.0
40
R4 1014 3463 165
CPC21431 143.0
50
R6 1268 4431 238
CPC21781 178.0
60
R6 1575 5379 238
CPC22211 221.0
75
R6 1952 6666 238
CPC22481 248.0
100
R6 2189 7474 238
140
TECHNICAL DATA
Dimensions and Weights
Frames R1-R6
The dimensions and mass for the AQUAVAR depend on the frame size and enclosure type.
If unsure of frame size, first, find the Type code on the drive labels. Then look up that type
code in the Technical Data on page 142, to determine the frame size. A complete set of dimensional drawings for AQUAVAR drives is located in the Technical Data section.
Units with UL Type 1 Enclosures
Outside Dimensions
R1 R2 R3 R4 R5 R6
Ref.
mm in mm in mm in mm in mm in mm in
W
H
H2
H3
D
125 4.9 125 4.9 203 8.0 203 8.0 265 10.4 300 11.8
330 13.0 430 16.9 490 19.3 596 23.4 602 23.7 700 27.6
315 12.4 415 16.3 478 18.8 583 23.0 578 22.8 698 27.5
369 14.5 469 18.5 583 23.0 689 27.1 739 29.1 880 34.6
212 8.3 222 8.7 231 9.1 262 10.3 286 11.3 400 15.8
141
TECHNICAL DATA
Frames R1-R6
Mounting Dimensions
R1 R2 R3 R4 R5 R6
Ref.
mm in mm in mm in mm in mm in mm in
W1* 98.0 3.9 98.0 3.9 160 6.3 160 6.3 238 9.4 263 10.4
W2*
98.0 3.9 98.0 3.9
H1* 318 12.5 418 16.4 473 18.6 578 22.8 588 23.2 675 26.6
a
5.5 0.2 5.5 0.2 6.5 0.25 6.5 0.25 6.5 0.25 9.0 0.35
b 10.0 0.4 10.0 0.4 13.0 0.5 13.0 0.5 14.0 0.55 14.0 0.55
c 5.5 0.2 5.5 0.2 8.0 0.3 8.0 0.3 8.5 0.3 8.5 0.3
d 5.5 0.2 5.5 0.2 6.5 0.25 6.5 0.25 6.5 0.25 9.0 0.35
* Center to center dimension.
Weight
R1 R2 R3 R4 R5 R6
kg lb. kg lb. kg lb. kg lb. kg lb. kg lb.
6.1 13.4 8.9 19.5 14.7 32.4 22.8 50.2 37 82 78 176
142
TECHNICAL DATA
Units with IP 54 / UL Type 12 Enclosures
Outside Dimensions
R1 R2 R3 R4 R5 R6
Ref.
mm in mm in mm in mm in mm in mm in
W
W2
H3
D
215 8.5 215 8.5 257 10.1 257 10.1 369 14.5 410 16.1
225 8.9 225 8.9 267 10.5 267 10.5 369 14.5 410 16.1
441 17.4 541 21.3 604 23.8 723 28.5 776 30.5 924 36.4
238 9.37 245 9.6 276 10.9 306 12.0 309 12.2 423 16.6
Mounting Dimensions
Mounting dimensions are the same as for the IP 21 / UL Type 1 Enclosure. See Mounting
Dimensions on page 144.
Weight
R1 R2 R3 R4 R5 R6
kg lb. kg lb. kg lb. kg lb. kg lb. kg lb.
8.4 18.6 11.5 25.4 18.1 40.0 26.6 58.7 42 93 86 190
143
E1
Top View
E1
TECHNICAL DATA
E2
X2
W2
Frames R7-R8
E1
Top View
E1
E2
X2
H1
D
W2
H1
NEMA 1 Enclosure
H1
W2 Depth Weight E1
E2
Frame
mm in mm in mm in kg lb. mm in mm in
R7
R8 2130 83.86 800 31.5 585 23.03 375 827 92 3.62 250 9.84
1503 59.17 609 23.98 495 19.49 195 430 92 3.62 250 9.84
Degrees of Protection
Available enclosures:
IP 21 / UL Type 1 Enclosure. The site must be free of airborne dust, corrosive gases or
liquids, and conductive contaminants such as condensation, carbon dust and metallic particles. Indoor use only.
IP 54 / UL Type 12 Enclosure. This enclosure provides protection from airborne dust and
light sprays or splashing water from all directions. Indoor use only.
UL Type 3R- Enclosures are intended for outdoor use to provide a degree of protection
from falling rain. Undamaged by the formation of ice on the enclosure. May be cooled
by forced air and louvers for vents. This rating is met by placing the drive into a NEMA 3R
Enclosure.
Compared to the IP 21 / UL Type 1 Enclosure, the IP 54 / UL Type 12 Enclosure has:
The same internal plastic shell as the IP 21 Enclosure.
A different outer plastic cover.
An additional internal fan to improve cooling.
Larger dimensions.
The same rating (does not require a derating).
Plastic gasketed cover for keypad.
144
TECHNICAL DATA
Ambient Conditions
The following table lists the AQUAVAR environmental requirements.
Ambient Environment Requirements
Storage and Transportation
Installation Site
in the protective package
Altitude1
Ambient
Temperature2
-1540 C (5104 F)
Max. 50 C (122 F) if PN and I2
derated to 90%.
Relative humidity
Contamination
levels
Storage
No conductive dust allowed.
Chemical gases: Class 1C2
Solid particles: Class 1S2
(IEC 721-3-3)
Transportation
No conductive dust allowed.
Chemical gases: Class 2C2
Solid particles: Class 2S2
Sinusoidal
Vibration
-4070 C (-40158 F)
Shock
Not allowed
(IEC 68-2-29)
Free Fall3
Not allowed
145
TECHNICAL DATA
Materials
Materials Specifications
Drive
Enclosure
Package
Disposal
PC/ABS 2.5 mm, color NCS 1502-Y (RAL 90021 / PMS 420 C and 425 C)
Hot-dip zinc coated steel sheet 1.52 mm, thickness of coating 100 micrometers.
Cast aluminium AlSi
Extruded aluminium AlSi
Corrugated board (drives and option modules), expanded polystyrene.
Plastic covering of the package: PE-LD, bands PP or steel.
The drive contains raw materials that should be recycled to preserve energy and natural
resources. The package materials are environmentally compatible and recyclable. All
metal parts can be recycled. The plastic parts can either be recycled or burned under
controlled circumstances, according to local regulations. Most recyclable parts are
marked with recycling marks.
If recycling is not feasible, all parts excluding electrolytic capacitors and printed circuit
boards can be landfilled. The DC capacitors contain electrolyte and the printed circuit
boards contain lead, both of which will be classified as hazardous waste within the EU.
They must be removed and handled according to local regulations.
For further information on environmental aspects and more detailed recycling
instructions, please contact your local recycler.
Applicable Standards
The drive complies with the following standards. The compliance with the European Low Voltage Directive is verified according to standards EN 50178 and EN 60204-1.
Applicable Standards
EN 50178 (1997)
EN 60204-1
(1997)
EN 60529: 1991
(IEC 529), IEC
60664-1 (1992)
EN 61800-3
(1996) +
Amendment
A11 (2000)
UL 508C
146
TECHNICAL DATA
UL Markings
The AQUAVAR is suitable for use on a circuit capable of delivering not more than 65,000 RMS
symmetrical amperes, 480 V maximum. The AQUAVAR has an electronic motor protection
feature that complies with the requirements of UL 508C. When this feature is selected and
properly adjusted, additional overload protection is not required unless more than one motor
is connected to the drive or unless additional protection is required by applicable safety
regulations.
The drives are to be used in a controlled environment. See section Ambient Conditions on
page 145 for specific limits.
Liability Limits
The manufacturer is not responsible for:
Any costs resulting from a failure if the installation, commissioning, repair, alteration
or ambient conditions of the drive do not fultill the requirements specified in the
documentation delivered with the unit and other relevant documentation.
Units subjected to mususe, negligence or accident.
Units comprised of materials provided or designs stipulated by the purchaser.
In no event shall the manufacturer, its suppliers or subcontractors be liable for special,
indirect, incidental or consequential damages, losses or penalties.
If you have any questions concerning your product, please contact the local distributor or
CentriPro. The technical data, information and specifications are valid at the time of printing.
The manufacturer reserves the right to modifications without prior notice.
147
APPENDIX
PRESSURE TRANSDUCER
300 PSI 4-20 mA
P/N 9K515
(To order sensor with 200 inch (16 ft.) cable, use P/N 9K391)
Packard 3-pin
Metri-Pack
Series 150
Output
White
3/16 Dia
sphere of
silicon
grease at
base of
terminals
3.25
Snubber
added
+Supply
Brown
3
1
No
Connection
1/4 MNPT
0.875 HEX
LABEL
CentriPro
www.centripro.com
UL
US
0300SB
PART#: 9K515
LISTED
79BN
PRESSURE: 0-300PSI
INPUT: 10-28VDC
MADE IN USA
OUTPUT: 4-20mA
SERIAL #: AXXXXXX
YYMMDD
SPECIFICATIONS
Parameter
Value
Pressure Range
300 PSI
Output (0 - 100%)
4-20 mA
Supply Voltage
10-28 VDC
Burst Pressure Minimum
5x rated
Pressure Overload Maximum
2x rated
Supply Current Maximum
<22mA
Pressure Cycles Minimum
100 million
Accuracy (combined lin/hyst/rep)
< 0.5% BFSL
Zero Offset Maximum
< 1% of FS / C
Span Tolerance Maximum
< 2% of FS / C
148
Parameter
Value
Operating Temp. Range
-40 to 85C
Compensation Temp. Range
0 to 55C
Zero Thermal Error Maximum
< .035% of FS
Span Thermal Error Maximum
< .035% of FS
Pressure Port Material
17-4 PH
Housing Material
304 stainless steel
Isolation Voltage Minimum
500VDC
Seal Material
N/A
UL cUL 508
Listings
CE ENG/326
K No.
9K514
9K515
9K516
9K517
Part No.
A00462C 1
A00462C 2
A00462C 3
A00462C 4
A00439C 4
A00439C 3
A00439C 2
A00439C 1
0-1000 PSI
0-500 PSI
0-300 PSI
0-150 PSI
Transducer Part
Pressure Range
No.
A00436C 360
Cable Part
No.
APPENDIX
Transducer Data/Specifications
149
150
A00436C 100
A00436C 50
A00436C 30
A00436C 16
100
50
30
16
(standard)
Drawing
Number
A (ft)
9K400
9K399
9K398
9K397
K No.
APPENDIX
APPENDIX
Spare Parts List
Part Number
Description
64732048
CPCCPA
OCAT01
CPCB01
OFAN KIT R1
OFAN KIT R2
OFAN KIT R3
OFAN KIT R4
OFAN KIT R5
OFAN KIT R6
64391615
64391658
CPCEXTKIT
151
Xylem Inc.
2881 East Bayard Street Ext., Suite A
Seneca Falls, NY 13148
Phone: (800) 453-6777
Fax: (888) 322-5877
www.centripro.com
CentriPro and Aquavar are trademarks of Xylem Inc. or one of its subsidiaries.
2012 Xylem Inc.
IM167 Revision 8
December 2013