Manual Programacion VARIADOR Aquavar

Download as pdf or txt
Download as pdf or txt
You are on page 1of 152

INSTRUCTION MANUAL

IM167R08

AQUAVAR CPC

(Centrifugal Pump Control)


INSTALLATION AND OPERATION MANUAL

NOTE: This guide does not provide detailed


installation, safety or operational instructions. See the Installation Operation Manual
for complete information.

This guide provides a quick reference for


installing Aquavar CPC drives having a standard enclosure (NEMA 1).

Application

START-UP Wizards

APPLY power

REINSTALL the cover

CHECK installation

INSTALL wiring

MOUNT the drive

REMOVE the front cover

PREPARE mounting location

UNPACK the drive

PREPARE for installation

Task

The installation of the AQUAVAR CPC adjustable speed drive follows the outline below.

Overview

Centrifugal Pump Controller


Quick Start Guide

AQUAVAR CPC

2 230 Volt
370 Amps
1 NEMA 1
2 NEMA 12

*See Technical Section

NOTE: Lift the Aquavar by its chassis and not by


its cover.
1. Unpack the drive.
2. Check for any damage and notify the
shipper immediately if damaged components are found.

Unpack the Drive

Collect Motor Data


Collect the following data from the motor nameplate
plate for later use in the Aquavar startup:
Voltage_______________________________
Nominal Motor Current________________
Nominal Frequency____________________
Nominal Speed_______________________
Nominal Power________________________

* Consult factory for other options, if available.


Not all combinations may be available.

Options

CPC 4 370 1

4 460 Volt

NEMA Enclosure Rating

Amps

Voltage

AQUAVAR (Series)

Tools Required
Screwdrivers, wire stripper, tape measure, mounting screws or bolts, and drill.
Use the following chart to interpret the type code
found on the drive label.

Check
Motor Compatibility Motor type, nominal current,
frequency and voltage range must match drive
specifications (3 phase motor only).
Suitable Environment Drive requires heated,
indoor controlled environment that is suitable for
the selected enclosure below 104 F.
Wiring Follow local codes for wiring and fusing
requirements. Refer to NEC, Local, State or Municipal codes.
Refer to the Installation Operation Manual and
confirm that all preparations are complete.

WARNING! The Aquavar should ONLY


be installed by a qualified electrician.

Prepare for Installation

1
X0002

Wiring Power
1. Connect conduit runs to box.
2. Route input power and motor
wiring through conduits.

1. Install thin-wall conduit clamps (not


supplied) in the conduit/gland box.
2. Install conduit/gland box.

Install the Wiring (copper only)

2. Attach a warning
sticker in the
appropriate language on the inside
plastic shell.

1. Position the
AQUAVAR and use
screws or bolts to
securely tighten all
four corners.

Mount the Drive

3. Pull near the


top to remove
the cover.

2. Loosen the
captive screw
at
the top.

1. Remove the control panel


(display), if attached.

Remove the Front Cover

1. Mark the mounting


points.
2. Drill the mounting holes.

The drive requires a smooth,


vertical, solid surface, free from
heat and moisture, with free
space for air flow 200 mm (8
in.) above and below, and 25
mm (1 in.) around the sides of
the drive.

Prepare the Mounting Location

3. Check the contents against the order


and the shipping label to verify that all
parts have been received.

WARNING!
For floating networks remove
screws at
F1 and F2
on Frame
Sizes R5 or R6.

Frame Size R6

Frame Size R5

WARNING! For floating networks


remove screws at EM1 and EM3 on
Frame Sizes R1R4.

* Single phase input power must use U1, W1


and PE for wiring.

Frame Sizes R1R4

3. Strip wires.
4. Connect power, motor and
ground wires to the drive terminals.
See Power Connections
in the instruction manual.

ON

Relay Outputs

Relay output 1, programmable. Default2


= run power to drive
Maximum: 250 VAC/
30 VDC, 2 A
Minimum: 500 mW
(12 V, 10 mA)
Relay output 2, programmable. Default2
= ready, pump is
running
Maximum: 250 VAC/
30 VDC, 2 A
Minimum: 500 mW
(12 V, 10 mA)
Relay output 3, programmable. Default2
= not used
Maximum: 250 VAC/
30 VDC, 2 A
Minimum: 500 mW
(12 V, 10 mA)

AI1: 010 V
AI2: 0(4)20 mA (default)

ON

6. Install the conduit/gland box cover (1


screw).



19 RO1C



20 RO1A



21 RO1B




22 RO2C




23 RO2A



24 RO2B



25 RO3C



26 RO3A



27 RO3B



J1

Note 1. Jumper Setting: (Analog Input)

1. Route the
transducer
3
cable
through
5
the conduit.
2. Strip the
transducer
cable
sheathing
and twist
1
the screen
wire.
3. Connect the screen
wire of the
transducer to
terminal X1-1.
4. Connect the power supply wire of the
transducer (red or brown) to terminal
X1-10.
5. Connect analog output wire from the
transducer (white or black) to X1-5.
See chart in next column.

Control Wiring

and
12

Terminal for transducer


shield. (Connected internally to chassis ground.)
Analog input channel 1,
2nd transducer. Default2
= frequency reference.
Resolution 0.1%,

2 AI1 accuracy 1%.
J1:AI1 OFF: 010 V (Ri =
312 k)
J1:AI1 ON: 020 mA (Ri
= 100 )
Analog input circuit com mon. (Connected interJumper
Wire 3
AGND nally to chassis gnd.
through 1 MW. Jumper
wire to X1-11.)
()
10 V/10 mA reference

Trans-
voltage output for analog
4 +10V input potentiometer,
ducer
(4 -20
accuracy 2%. (Not used.)
mA)
Analog input channel 2.
Conn-
Resolution 0.1%,
ection
5 AI2 accuracy 1%.
(White
Transducer input
or
420 mA
Black)

Analog input circuit com

mon. (Connected inter6 AGND nally to chassis gnd.

through 1 M)

Analog output, program

mable. Default2 = Not
7 AO1 used. Current 020 mA

()
(load < 500 )
Trans
Analog output, programducer

mable. Default2 = Not
Power
8 AO2 used. 020 mA
Supply
(load < 500 )
(Brown

Analog output circuit
or Red)


common (Connected
9 AGND internally to chassis gnd.

through 1 M)
Auxiliary voltage output
1015
24 VDC / 250 mA
E-stop
(reference to GND).
or
10 +24V Short circuit protected.
Jump-

Transducer/digital input
er
power supply.
Jump-
Auxiliary voltage output
er
11 GND common. (Connected
Wire
internally as floating.)
11

X1

Trans-

1 SCR
ducer

Screen/

Shield

Analog I/O

Digital Inputs1

X1

Control Wiring

may be provided by the


AQUAVAR (X1-10) or by
an external 1224V
source of either polarity.

Digital input 1, selectable.
13 DI1 Default2 = run enable


Digital input 2, selectable.
14 DI2 Default2 = low water
1015
E-stop
Digital input 3,
or
15 DI3 selectable. Default2
Jump-
= E-stop or jumper
er
Digital input 4,
16 DI4 selectable. Default2
E-stop

= set point selection
/start
Jump
Digital input 5, selectable.
17 DI5 Default2 = not used
to
+24V
Digital input 6, selectable.
for en-
18 DI6 Default2 = not used
able

JumpDigital input common.


er
To activate a digital input,
Wire
11
there must be +10V
and (or -10V) between that
12 12
DCOM input and DCOM. The 24V

Check
Environment conforms to specifications.
The drive is mounted securely.
Proper cooling space around the drive.
Motor and driven equipment are ready for start.
Floating networks: Internal RFI filter disconnected.
Drive is properly grounded, with pump/motor.
Input power (mains) voltage matches the drive
nominal input voltage.
The input power (mains) terminals, U1, V1, W1,
are connected and tightened as specified.
The input power (mains) fuses / mains switch installed.
The motor terminals, U2, V2, W2, are connected
and tightened as specified.
Motor cable is routed away from other cables.
NO power factor compensation capacitors are
connected to the motor cable.
Control terminals are wired and tightened as specified.
NO tools or foreign objects (such as drill shavings) are
inside the drive.
NO alternate power source for the motor is connected
no input voltage is applied to the output of the drive.

Before applying power, perform the following checks.

Check Installation

specified are for the default macro, single/multipump.


NOTE: Jumper Wires between 3 and 11, 10 and 15,
11 and 12.

(15
1
Digital input impedance 1.5 k. Maximum voltage
to 10
Jump- 2 for digital inputs is 30 V.
Default values depend on the macro used. Values
er)

Digital Inputs1

Wiring the Transducer

ON

ON

LOC
REM

DIR

REM

40.2 PSI sp
0.0 PSI ac
0.0 HZ

MENU

11.1%

NOTE! For common parameters and


menu items, use the Help Key
to
display descriptions. If you encounter
Alarms or Faults, use the Help Key or
refer to the Diagnostic section of the
instruction manual.

1. Use the MENU key to access the


Menu list.
2. Select Wizards.
3. Select Start-Up Wizards.
4. Follow the screen instructions to
configure the system.
DEFAULT PASSWORD IS 66.

Wizards
The Start-Up
Wizard steps through
typical start-up selections and runs
automatically upon the initial power
up. At other times, use the steps
below to run the Start-Up Wizard.

In Start-Up, enter motor


data (collected earlier)
and, if needed, edit parameters that define how
the drive operates and
communicates.

Start-Up

NOTE! Before increasing motor


speed, check that the motor is running in the desired direction.

1. Apply input power.


When power is applied to the AQUAVAR, the green LED comes on.

WARNING! The AQUAVAR


will start up automatically at
power up, if the external run
command is on.

Always reinstall the front cover before


turning power on.

Apply Power

1. Align the cover


and slide
it on.
2. Tighten
the
captive screw.
3. Reinstall the
control panel.

Reinstall the Cover

FEATURES

Quick Reference Guide


Analog Output, 102
Auto Restart, 102
Energy Savings Information, 103
Fieldbus Control, 103
Keypad (Control Panel), 104
Language, 104
Locking,104
Low Water Protection, 108
Manual Override, 104
Minimum Speed Options, 105
Priming Delay, 106
Pump Protect Control, 107
Ramp Hysteresis, 113
Ramp Settings, 113
Regulation Mode, 107
Relay Outputs, 107
Restart Value, 106
Secondary Protection, 108
Setpoints, Dual, 109
System Curve Compensation, 110
Test Run, 111
Tuning, 111
Window (Regulation), 112

TABLE OF CONTENTS
Section 1 SAFETY

Use of Warnings and Notes.........................................................................................................................................7

Section 2 POWER DISTRIBUTION SYSTEMS












Delta / Wye with grounded Wye neutral....................................................................................................................9


Delta / Delta with grounded leg..................................................................................................................................9
Ungrounded secondary...............................................................................................................................................9
Resistance grounding and ground fault protection................................................................................................10
Open Delta...................................................................................................................................................................10
Single Phase Connection............................................................................................................................................10

Section 3 INTRODUCTION

Input Power and Line Transformer Requirements...................................................................................................11


Issues for Drive Input Isolation Transformers...........................................................................................................11
Installation Flow Chart................................................................................................................................................13
Aquavar CPC Product Numbering............................................................................................................................14
Preparing for Installation; Drive Identification.........................................................................................................15
Section 4 INSTALLATION (Frames R1-R6)

Supply Connection......................................................................................................................................................19

Thermal Overload and Short-Circuit Protection......................................................................................................19

Ground Fault Protection.............................................................................................................................................19

Emergency Off Devices..............................................................................................................................................19

Selecting the Power Cables........................................................................................................................................20

Motor Cable Shield.....................................................................................................................................................20

Additional US Requirements......................................................................................................................................20

Installing the Drive.......................................................................................................................................................21

Wiring Connection Diagrams....................................................................................................................................24

Single Phase Wiring / Connection Diagram............................................................................................................26

Wiring IP 21 / UL Type 1 Enclosure with Conduit....................................................................................................27

Wiring IP 54 / UL Type 12 Enclosure with Conduit..................................................................................................28

Power Connections.....................................................................................................................................................29

Control Wiring.............................................................................................................................................................30

Communications..........................................................................................................................................................31

Installation Check Sheet.............................................................................................................................................32

Reinstall Cover.............................................................................................................................................................33
Section 4 INSTALLATION (Frames R7-R8)

Aquavar Drive Manuals Descriptions........................................................................................................................34

Introduction, Planning , Moving the Unit and Mounting........................................................................................35

Connecting Power and Control Cables....................................................................................................................36

R7 Frame Size...............................................................................................................................................................37

R8 Frame Size...............................................................................................................................................................38

Maintenance.................................................................................................................................................................39

Technical Data - Extension Module R7......................................................................................................................41

Detail R7.......................................................................................................................................................................42

Technical Data - Extension Module R8......................................................................................................................43

Detail R8.......................................................................................................................................................................44

Section 5 START-UP


Wizards and Assistant Control Panel (Display).........................................................................................................45


Controls / Display Overview.......................................................................................................................................45
Start-Up Wizard............................................................................................................................................................48

Section 6 PARAMETER LISTINGS


Aquavar CPC Parameter List......................................................................................................................................50

Section 7 PROGRAMMING



Single Pump Programming (Pressure Transducer)..................................................................................................73


Single Pump Submersible Pump Constant Pressure............................................................................................78
MultiPump Constant Pressure Control...................................................................................................................87
MultiPump Slave Pump Control..............................................................................................................................94

Section 8 FEATURES

Analog Outputs........................................................................................................................................................ 102


Auto Restart, Energy Saving Information (Group 26)........................................................................................... 102
5

TABLE OF CONTENTS











Fieldbus Control....................................................................................................................................................... 103


Language, Locking................................................................................................................................................... 104
Minimum Speed Options........................................................................................................................................ 105
Priming Delay, Pump Protect Ctrl, Regulation Mode................................................................................... 106-107
Relay Outputs; Restart Options; Low Water (Suction) Protection............................................................... 107-108
Keypad Failure.......................................................................................................................................................... 109
Set Points, Dual with example................................................................................................................................. 109
System Curve Compensation.................................................................................................................................. 110
Test Run; Tuning, System Pressure.......................................................................................................................... 111
Window Setting (Reg Window)............................................................................................................................... 112
Ramp Hysteresis....................................................................................................................................................... 113
Adjusting Ramp Rates.............................................................................................................................................. 113

Section 9 FAULTS/ALARMS



Diagnostic Displays.................................................................................................................................................. 115


Correcting Faults...................................................................................................................................................... 116
Fault Resetting.......................................................................................................................................................... 119
Correcting Alarms.................................................................................................................................................... 120

Section 10 MAINTENANCE (Frame Sizes R1-R6)







Maintenance Intervals.............................................................................................................................................. 122


Heatsink..................................................................................................................................................................... 122
Main Fan Replacement............................................................................................................................................ 122
Internal Enclosure Fan Replacement...................................................................................................................... 123
Capacitors................................................................................................................................................................. 124
Control Panel............................................................................................................................................................. 124

Section 10 MAINTENANCE (Frame Sizes R7-R8)







Layout......................................................................................................................................................................... 125
Heatsink, Fan............................................................................................................................................................. 126
Replacing the Fan..................................................................................................................................................... 126
Capacitors................................................................................................................................................................. 128
LEDs........................................................................................................................................................................... 129
Control Panel............................................................................................................................................................. 129

Section 11 TECHNICAL DATA





















Sizing; Derating........................................................................................................................................................ 130


Cable Sizing / Ratings 208-240 Volt Drives........................................................................................................... 131
Cable Sizing / Ratings 380-480 Volt Drives........................................................................................................... 132
Fuse Sizing / Ratings 208-240 Volt Drives............................................................................................................. 133
Fuse Sizing / Ratings 380-480 Volt Drives............................................................................................................. 134
Cable Terminals (frames R1-R6 and frames R7-R8).............................................................................................. 135
Input Power (Mains) Connection............................................................................................................................ 136
Motor Connection.................................................................................................................................................... 136
Control Connection.................................................................................................................................................. 137
Efficiency (frames R1-R8); Cooling (frames R1-R6)............................................................................................... 137
Cooling (frames R7-R8); Mounting Orientations a & b........................................................................................ 138
Air Flow 380-480 Volt Drives................................................................................................................................... 139
Air Flow 208-240 Volt Drives................................................................................................................................... 140
Dimensions and Weights (Frames R1-R6)............................................................................................................. 141
Units with IP 54 / UL Type 12 Enclosures............................................................................................................... 143
Weights and Dimensions (Frames R7-R8) 460 Volt.............................................................................................. 144
Degrees of Protection.............................................................................................................................................. 144
Ambient Conditions................................................................................................................................................. 145
Materials; Applicable Standards............................................................................................................................. 146
UL Markings; Liability Limits.................................................................................................................................... 147

Section 12 APPENDIX

Pressure Transducer................................................................................................................................................. 148



Transducer Data / Specifications Drawing #A00462C........................................................................................ 149

Transducer Data / Specifications Drawing #A00436C........................................................................................ 150

Spare Parts List.......................................................................................................................................................... 151

6

Warranty..................................................................................................................................................................... 152

SAFETY
WARNING! The AQUAVAR adjustable speed AC drive should ONLY be installed by a qualified electrician.
WARNING! Even when the motor is stopped, dangerous voltage is present at the Power Circuit terminals U1, V1, W1 and U2, V2, W2 and, depending on the frame size, UDC+ and UDC-, or BRK+ and BRK-.
WARNING! Dangerous voltage is present when input power is connected. After disconnecting the
supply, wait at least 5 minutes (to let the intermediate circuit capacitors discharge) before removing the
cover.
WARNING! Even when power is removed from the input terminals of the AQUAVAR, there may be dangerous voltage (from external sources) on the terminals of the relay outputs R01R03.
WARNING! When the control terminals of two or more drive units are connected in parallel, the auxiliary
voltage for these control connections must be taken from a single source which can either be one of the
units or an external supply.
WARNING! The AQUAVAR CPC wall mount version is not a field repairable unit. Never attempt to repair
a malfunctioning unit; contact the factory or your local Authorized Service Center for replacement.
WARNING! The AQUAVAR will start up automatically after an input voltage interruption if the external
run command is on.
WARNING! The heat sink may reach a high temperature, in excess of 200 F. Severe burns are possible.
WARNING! If the drive will be used in a floating network, remove screws at EM1 and EM3 (Frame size
R1R4), or F1 and F2 (Frame size R5 or R6). See diagrams on pages 24 and 25 respectively.
NOTE! For more technical information, contact the factory or your local AQUAVAR representative.
WARNING! Always consult your local, state, municipal or NEC codes for proper wiring, electrical installation of inverter drives and AC motors.
USE OF WARNINGS AND NOTES
There are two types of safety instructions throughout this manual:
Notes draw attention to a particular condition or fact, or give information on a subject.
Warnings caution you about conditions which can result in serious injury or death and/or damage to
the equipment. They also tell you how to avoid the danger. The warning symbols are used as follows:
DANGEROUS VOLTAGE WARNING warns of high voltage which can cause physical injury and/or damage to the equipment.
GENERAL WARNING warns about conditions, other than those caused by
electricity, which can result in physical injury and/or damage to the equipment.

TYPICAL DRIVE LABEL


ACS550-U1-046A-2 ACS550-U1-046A-2

SW:

SW:

V.2.06B

V.2.06B

2053901277

2053901277
S/N2053901277

S/N2053901277

Input
Voltage (U1)
Current (11n)

3 PH 4863
208240 Vac
46.2 A

1 PH 4863 Hz
208240 Vac
46.2 A

Short Circuit

100 kAIC

100 kAIC

Output
Voltage (U2)
Current (12n)
Current (12hd)

3 PH 0500 Hz
0U1 Vac
46.2 A
30.8 A

3 PH 0500 Hz
0U1 Vac
22 A

Power (Pn)
Power (Phd)

15 HP

7.5 HP

ACS550-U1-046A-2

Made in USA of foreign parts


LISTED 45Y1

US

159339
206578

UL

US

IND. CONT. EQ.

Mfg. Date: 31-October-2005

Orig. Firmware: V.2.06B

S/N2053901277

POWER DISTRIBUTION SYSTEMS


The type of transformer and the connection configuration feeding a drive plays an important
role in its performance and safety. The following is a brief description of some of the more
common configurations and a discussion of their virtues and shortcomings. Always ask what
type of power system the site has before sizing the drive.

Delta / Wye with grounded Wye neutral:

This configuration is one of if not the most common. It provides rebalancing of unbalanced
voltage with a 30 degree phase shift. Depending on the output connections from the drive to
motor, the grounded neutral may be a path for common mode current caused by the drive
output.

Delta / Delta with grounded leg:

Another common configuration providing voltage rebalancing with no phase shift between
input and output. Again, depending on the output connections from the drive to motor, the
grounded neutral may be a path for common mode current caused by the drive output.

Ungrounded secondary:

Grounding of the transformer secondary is essential to the safety of personnel as well as


the safe operation of the drive. Leaving the secondary floating can permit dangerously high
voltages between the chassis of the drive and the internal power structure components.
In many cases this voltage could exceed the rating of the input MOV protection devices of
the drive causing a catastrophic failure. In all cases, the input power to the drive should be
referenced to ground. If the transformer can not be grounded, then an isolation transformer
must be installed with the secondary of the transformer grounded.

POWER DISTRIBUTION SYSTEMS


Resistance grounding and ground fault protection:

Connecting the Wye secondary neutral to ground through a resistor is an acceptable


method of grounding. Under a short circuit secondary condition, any of the output phases
to ground will not exceed the normal line to line voltage. This is within the rating of the MOV
input protection devices on the drive. The resistor is often used to detect ground current
by monitoring the associated voltage drop. Since high frequency ground current can flow
through this resistor, care should be taken to properly connect the drive motor leads using
the recommended cables and methods. In some cases, multiple drives on one transformer
can produce a cumulative ground current that can trigger the ground fault interrupt circuit.

Open Delta (consult factory):

This type of configuration is common on 230 volt systems. From time to time it may be
encountered where only single phase power is available and three-phase power is required.
The technique uses two single phase transformers to derive a third phase. When used to
power a drive this configuration must be derated to about 70% of the single phase rating of
one transformer. This system provides poor regulation and it is possible that only the two line
connected phases will provide power. In this case the drive must be derated to 50% of its
rating. (Ex. A 20 HP 230 volt drive now becomes a 10 HP 230 volt drive.)

Single Phase Connection:


For small drive with a diode rectifier front end it is possible to run a three phase output with a
single phase input. Only part of the three phase input bridge is used. Ripple current becomes
120 Hz rather than 360. This places a greater demand on the DC filter components (capacitor
bank and DC choke). The result is that the drive must be derated to 50% current. Single phase
will not work with an SCR front end drive.

10

INTRODUCTION
Input Power and Line Transformer Requirements
The Aquavar CPC requires that the input line voltage and transformer power that meet
certain phase and balance requirements. If you or your installing electrical contractor is in
doubt of the requirements, the following provide guidelines for the Aquavar CPC. When
in doubt contact the local power utility or the factory.
Drive input isolation transformers are not generally required for the Aquavar CPC. The
Aquavar CPC utilizes as standard 3% line impedance, therefore unless additional filtering is
needed, an input line reactor is not required.
NOTE: 60 THROUGH 550 HP UNITS PROVIDE AN ACTUAL 3% IMPEDANCE LINE REACTOR
BUILT INTO THE DRIVE CABINET.
The internal power circuit of the drive is floating with respect to earth ground except for
transient protection (MOVs and EMI capacitors) therefore earth ground potential reference is
established only by the users power line grounding configuration. The drive can operate with
many different power grounding schemes. The drive requires only that the steady state RMS
voltage from any input line to ground be always less than 110% of the nominal power line to
line voltage. The use of optional RFI/EMC filters may require that the voltage from any input
line to ground be less than 110% of the nominal power line to neutral voltage.
Drive input isolation or dry type transformers may be required for the following:
1. Step up or down: An input transformer may be required to step the local input power
line voltage up or down to the level of the drive input rating.
2. Ground Isolation: An input isolation transformer with a direct or a high impedance wye
neutral secondary ground connection may be required to establish a local power source
with a ground relationship different from the utility power source.
A. If ground isolation is required to prevent a ground fault in one section from shutting
down equipment in another section.
B. To bring local line voltages within the line to ground limits (110% balance) stated in
the opening paragraph.
C. Some ground fault protection schemes and peripheral components require a
grounded neutral power source.
D. A symmetrical wye neutral grounded power source along with proper ground wiring
techniques according to NEC (good ac grounding from motor to drive and from
drive to earth ground) provides the best means to control the ground currents that
the drive switching frequency and dv/dt rate insert into the motor frame and shaft.
3. Phase shifting delta-wye or zig-zag isolation transformers are used to feed 12 or 18
pulse drive inputs to provide harmonic mitigation.
If an isolation transformer is used for 6 pulse input, the best choice is ONE three phase,
six winding transformer. A delta primary is best for third harmonic cancellation. A
wye secondary avoids circulating current problems and provides the very desirable option
of grounding the secondary neutral for minimum voltage stress and ripple to ground. The
transformer should have a KVA rating at least 1.1 times the maximum connected HP. A K
Factor of 6 is sufficient if transformer impedance is greater than 2%. A K Factor of 5 is sufficient
11

INTRODUCTION
if transformer impedance is greater than 3%. The transformer manufacturer may provide
derating for non K Factor rated transformers to operate at the drive produced K Factor levels.
Other transformer configurations are acceptable. Three single phase transformers can be
used if they are identical for phase to phase symmetry and balance. A wye connected
primary neutral should never be grounded. Great care should be taken with delta primary
delta secondary configurations. Any lack of phase to phase symmetry could result in
circulating currents and unacceptable transformer heating.
WARNING! Never use phase converters with drives as nuisance tripping and possible
damage may occur. Size the drive for single phase input using 50% derate factor.
WARNING! Use of Open Delta 230 volt power systems should be sized using the
50% derate factor. Consult factory.
Sometimes drive input isolation transformers are specified to deal with one or more of
the following issues:
1. Short Circuit Protection: Input transformers are sometimes used to provide impedance
to reduce the available short circuit current to levels that the input clearing devices,
such as fuses or circuit breakers, are rated to handle. Line reactors can perform this
impedance function much more cost effectively.
2. Transient Protection: Input transformers are sometimes used to provide transient
surge impedance. All the Aquavar CPC drives have capacitors and MOVs (Metal Oxide
Varistor transient protectors) providing 120 to 360 joules, line to line and line to ground
transient protection. Isolation transformers are not required for this protection within
those energy levels. Additional distribution transformer primary transient surge arrestors
may be required if the potential transient energy reflected to the drive exceed those
levels. MOVs are rated to handle high levels of one shot transient energy. MOVs are not
meant to handle continuously recurring transients. A problem of continuously recurring
transients should be corrected before connecting a drive.
3. Harmonic Mitigation: Input transformers are sometimes used to provide impedance to
reduce the harmonic currents generated in the drive. Line reactors can perform this
function much more cost effectively.
4. Power Factor Capacitor Isolation: Input transformers are sometimes used to provide
impedance to isolate drives from line connected power factor correction capacitors.
PWM drive inputs do not require power factor correction capacitors as drive power
factors are generally greater than 92% and cannot be significantly improved with
power factor correction capacitors which only correct for fundamental. However drives
should be isolated from power factor correction capacitors by about 3 to 6% additional
impedance with respect to the drives. Line reactors can perform this function much more
cost effectively than isolation transformers. ABB drives have either an internal 3% line
reactor or an equivalent 3 to 5% bus reactor.
5. RFI/EMI Mitigation: Neither input isolation transformers nor line or bus reactors provide
good high frequency filtering although an isolation transformer with a static shield will
provide some RFI mitigation. If RFI/EMI mitigation is required, an RFI/EMI filter mounted
inside the drive should be used together with all the proper wiring and grounding
techniques. Some RFI/EMI filters may operate only on a power source with a grounded
neutral. Establishing a local neutral ground may require the use of an input isolation
transformer.

12

INTRODUCTION
Study these installation instructions carefully before proceeding. Failure to observe the
warnings and instructions may cause a malfunction or personal hazard.
WARNING! Before you begin read Safety on page 7.

Installation Flow Chart


The installation of the AQUAVAR adjustable speed pump controller follows the outline below.
The steps must be carried out in the order shown. At the right of each step are references to
the detailed information needed for the correct installation of the unit.

Task

PREPARE for installation



UNPACK the drive

PREPARE the Mounting Location


REMOVE the front cover

MOUNT the drive

INSTALL wiring

CHECK installation

REINSTALL the cover

APPLY power

START-UP

See
Preparing for Installation on page 15.
Unpack the Drive on page 21.
Prepare the Mounting Location
on page 21.
Remove Front Cover on page 21.
Mount the Unit on page 22.
Install the Wiring on page 23.
Check Installation on page 32.
Reinstall Cover on page 33.
Apply Power on page 33.
Start-Up on page 33.

13

INTRODUCTION
AQUAVAR CPC Product Numbering
Voltage

Phase

NEMA 1 Base Model

Full Load Amps


Normal Duty

Frame Size

Normal Duty
Horsepower

CPC20071
3.7
R1
1
CPC20171
8.5
R1
2
CPC20241
12
R2
3
CPC20311
15.5
R2
5
CPC20461
23
R3
7.5
CPC20591
29.5
R3
10
230
1
CPC20881
44.0
R4
15
CPC21141
57.0
R4
20
CPC21431
71.5
R6
25
CPC21781
89.0
R6
30
CPC22481
124.0
R6
40
CPC22481
124.0
R6
50
CPC20041
4.6
R1
1
CPC20071
7.5
R1
2
CPC20121
11.8
R1
3
CPC20171
16.7
R1
5
CPC20241
24.2
R2
7.5
CPC20311
30.8
R2
10
CPC20461
46.2
R3
15
230
3
CPC20591
59.4
R3
20
CPC20751
74.8
R4
25
CPC20881
88.0
R4
30
CPC21141
114.0
R4
40
CPC21431
143.0
R6
50
CPC21781
178.0
R6
60
CPC22211
221.0
R6
75
CPC22481
248.0
R6
100
CPC40061
6.9
R1
3
CPC40081
8.8
R1
5
CPC40121
11.9
R1
7.5
CPC40151
15.4
R2
10
CPC40231
23
R2
15
CPC40311
31
R3
20
CPC40381
38
R3
25
CPC40451
45
R3
30
CPC40591
59
R4
40
CPC40721
72
R4
50
CPC40781
78
R4
60
460
3
CPC40971
97
R4
75
CPC41251
125
R5
100
CPC41571
157
R6
125
CPC41801
180
R6
150
CPC42451
245
R7
200
CPC43161
316
R7
250
CPC43681
368
R8
300
CPC44141
414
R8
350
CPC44861
486
R8
400
CPC45261
526
R8
450
CPC46021
602
R8
500
CPC46451
645
R8
550
CPC50031
2.7
R2
2
CPC50041
3.9
R2
3
CPC50061
6.1
R2
5
CPC50091
9
R2
7.5
CPC50111
11
R2
10
CPC50171
17
R2
15
CPC50221
22
R2
20
CPC50271
27
R3
25
575
3
CPC50321
32
R4
30
CPC50411
41
R4
40
CPC50521
52
R4
50
CPC50621
62
R4
60
CPC50771
77
R6
75
CPC50991
99
R6
100
CPC51251
125
R6
125
CPC51441
144
R6
150
*** - HP classifications are for reference purposes only, always size the Aquavar according to the output amps and the service factor amps of the motor.

14

INTRODUCTION
Preparing for Installation
Drive Identification
Drive Labels

To determine the type of drive you are installing, refer to either:


Serial number label attached on upper part of the chokeplate between the mounting
holes.
ACS550-01-08A8-4
U1
I2N / I2hd
PN / Phd

3~380480 V
8.8 A / 6.9 A
4 / 3 kW

Ser. no. *2030700001*

Type code label attached on the heat sink on the right side of the unit cover.
Input U1
I1N
f1

3~380480 V
8.8 A
4863 Hz

Input U2 3~0U1 V
I2N / I2hd 8.8 A / 6.9 A
f2
0500 Hz
Input PN / Phd

4 / 3 kW

UL

US

LISTED

Ser. no. *2030700001*

ACS550-01-08A8-4

Type Code

CPC 4 370 1 FD

AQUAVAR (Series)

Voltage
2 208-240 Volt
4 480 Volt
5 575 Volt

Amps
370 Amps


*See Technical Section


NEMA Enclosure Rating
1 NEMA 1
2 NEMA 12




** Fused Disconnect
Options
* Consult factory for other options, if available. Not all combinations may be available.
** Standard equipment on 200 HP and above 460 volt models.

15

INTRODUCTION
Ratings and Frame Size
The chart in Ratings on page 131 lists technical specifications, and identifies the drives
frame size significant, since some instructions in this document, vary, depending on the
drives frame size. To read the Ratings table, you need the Output current rating entry from
the type code. Also, when using the Ratings table, note that the table is broken into sections
based on the drives Voltage rating.
Motor Compatibility
The motor, drive and supply power must be compatible:


Motor
Specification
Motor type

Verify Reference
3-phase induction motor

NEMA MG1


Nominal current
Motor value is within this

range: 0.22.0 * I2hd

(I2hd = drive heavy duty)


Type code label on drive,


entry for Output Current or
Type code on drive and
rating current table in
Technical Data on
page 131.

50 70 Hz

Motor is compatible
with the AQUAVAR
voltage range.

208240 V (for CPC2XXXX) or


380480 V (for CPC4XXXX)

Nominal frequency


Voltage range

Tools Required
To install the AQUAVAR you need the following:
True RMS multimeter
Screwdrivers (as appropriate for the mounting hardware used)
Wire stripper
Tape measure
Drill
Mounting hardware: screws or nuts and bolts, four each. The type of hardware depends on
the mounting surface and the frame size:

Frame Size

Mounting Hardware


R1R4
M5
#10

R5
M6
in.
5
R6 M8 16 in.
Suitable Environment and Enclosure
Confirm that the site meets the environmental requirements. To prevent damage prior to
installation, store and transport the drive according to the environmental requirements
specified for storage and transportation. See Ambient Conditions on page 145.
Confirm that the enclosure is appropriate, based on the site contamination level:
IP 21 / UL type 1 enclosure, indoor use only. The site must be free of airborne dust,
corrosive gases or liquids, and conductive contaminants such as condensation, carbon
dust and metallic particles.
16

INTRODUCTION
IP 54 / UL type 12 enclosure, indoor use only. This enclosure provides protection from
airborne dust and light sprays or splashing water from all directions.
UL Type 3R- Enclosures are intended for outdoor use to provide a degree of protection
from falling rain. Undamaged by the formation of ice on the enclosure. May be cooled by
forced air and louvers for vents.
IP 56 / UL type 4 enclosure. Constructed for outdoor use or hose down applications.
Provides a degree of protection against falling dirt, rain, sleet, snow, windblown dust and
splashing water. Not suitable for direct sun. A sun shield or canopy may be required.
Suitable Mounting Location
Confirm that the mounting location meets the following constraints:
The drive must be mounted vertically on a smooth, solid surface, and in a suitable
environment as defined above.
The minimum space requirements for the drive are the outside dimensions (see Outside
Dimensions on page 141 and 143), plus air flow space around the unit (see Cooling on
page 137).
The distance between the motor and the drive is limited by the maximum motor cable
length. See Motor Connection on page 136.
The mounting site must support the drives modest weight and noise output. See
Dimensions and Weights on page 141.
Wiring and EMC Considerations
Determine electromagnetic compliance (EMC) requirements per local codes. In general,
always follow the NEC in the absence of a local code.
Follow local codes for cable size, conduit, grounding and motors.
Keep these four classes of wiring separated: input power wiring, motor wiring, control/
communications wiring. Always use separate conduit for motor/control wires.
Refer to the specifications/recommendations in:
Cable Sizing/Rating on page 131, Cable Terminals on page 135, Input Power (Mains)
Connection on page 136 and Motor Connection on page 136.
Multiple motor wire should always be run in separate conduit. Shielded and grounded!
Control Cables
General Recommendations
Use shielded cables, temperature rated at 60 C (140 F) or above:
Control cables must be multi-core cables with a braided copper wire screen.

Double Shielded
Example: JAMAK by Draka NK Cables

Single Shielded
Example: NOMAK by Draka NK Cables

The screen must be twisted together into a bundle not longer than five times its width and
connected to terminal X1-1 (for digital and analog I/O cables) or to either X1-28 or X1-32
(for RS485 cables).
17

INTRODUCTION
Route control cables to minimize radiation to the cable:
Route as far away as possible from the input power and motor cables (at least 20 cm (8 in)).
Where control cables must cross power cables make sure they are at an angle as near 90
as possible.
Stay at least 20 cm (8 in) from the sides of the drive.
Use care in mixing signal types on the same cable:
Do not mix analog and digital input signals on the same cable.
Run relay-controlled signals as twisted pairs (especially if voltage > 48 V). Relay-controlled
signals using less than 48 V can be run in the same cables as digital input signals.
NOTE! Never mix 24 VDC and AC power signals in the same cable.
Analog Cables
Recommendations for analog signal runs:
Use double shielded, twisted pair cable
Use one individually shielded pair for each signal.
Do not use a common return for different analog signals.
Digital Cables
Recommendations for digital signal runs:
A double shielded cable is the best alternative, but single shielded twisted multi-pair cable
is also usable.
Control Panel Cable
If the control panel is connected to the drive with a cable, use only Category 5 Patch ethernet
cable.

18

INSTALLATION (Frames R1-R6)


Supply Connection
Disconnecting Device (Mains)
Install a hand-operated input disconnecting device between the AC power source (MCC) and
the drive. The disconnecting device must be of a type that can be locked to the open position
for installation and maintenance work. Follow all local NEC codes.
Fuses
See Technical Data: Fuse Sizing/Rating on pages 133 and 134.

Thermal Overload and Short-circuit Protection


The drive protects itself and the input and motor cables against thermal overload when the
cables are dimensioned according to the nominal current of the drive. No additional thermal
protection devices are needed.
WARNING! If the drive is connected to multiple motors, a separate thermal overload
switch or a circuit breaker must be used for protecting each cable and motor. These
devices may require a separate fuse to cut off the short-circuit current.
The drive protects the motor cable and the motor in a short-circuit situation when the motor
cable is dimensioned according to the nominal current of the drive.
Mains Cable (AC line cable) Short-circuit Protection
Always protect the input cable with fuses. Standard gG (US: T or L) very fast acting, fuses
will protect the input cable in short-circuit situations and prevent damage to adjoining
equipment in case of a short-circuit inside the drive.
Size the fuses according to local safety regulations, appropriate input voltage and the rated
current of the drive. For fuse ratings, see Technical Data, pages 133 and 134.
WARNING! Circuit breakers are not capable of providing sufficient protection
because they are inherently slower than fuses. Always use fuses with circuit breakers, if
you are not sure of the circuit braking capacity and mains short circuit power.

Ground Fault Protection


The drive is equipped with an internal ground fault protective function to protect the unit
against ground faults in the motor and the motor cable. This is not a personal safety or a fire
protection feature. The ground fault protective function can be disabled with a parameter
contact factory for more information.
The EMC filter of the drive includes capacitors connected between the main circuit and the
frame. These capacitors and long motor cables increase the ground leakage current and may
cause fault current circuit breakers to function.

Emergency Off Devices


For safety reasons, install the emergency off devices at each operator control station and at other
operating stations where emergency off may be needed. Pressing the stop key
on the control
panel of the drive does not generate an emergency off of the motor or separate the drive from
dangerous potential.
19

INSTALLATION (Frames R1-R6)


Selecting the Power Cables (copper only)
General Rules
Dimension the mains (input power) and motor cables according to local regulations:
Do not use aluminum wires.
The cable must be able to carry the drive load current. See Technical Data for the rated
currents.
The cable must be rated for at least 70 C (158 F) maximum permissible temperature of
conductor in continuous use. For US, follow local codes for cable size, or refer to NEC table
310.16.
The inductance and impedance of the PE conductor/cable (grounding wire) must be rated
according to permissible touch voltage appearing under fault conditions (so that the fault
point voltage will not rise excessively when an ground fault occurs).
600 VAC cable is accepted for up to 500 VAC concerning the entire AQUAVAR CPC range.
For frame sizes R7 and R8, symmetrical shielded motor cable must be used (figure below). A
four-conductor system used up to 30 kW motors cannot be used.
Compared to a four conductor system, the use of symmetrical shielded cable reduces
electromagnetic emission of the whole drive system as well as motor bearing currents and wear
of bearings.
The motor cable and its PE pigtail (twisted screen) should be kept as short as possible in order
to reduce electromagnetic emission as well as capacitive current.
Insulation Jacket

Copper Wire Screen

Helix of Copper Tape

Inner Insulation

Cable Core

Motor Cable Shield


To effectively suppress radiated and conducted radio-frequency emissions, the shield
conductivity must be at least 1/10 of the phase conductivity. The requirements are easily met
with a copper or aluminum shield. The minimum requirement of the motor cable shield of the
drive is shown below. It consists of a concentric layer of copper wires with an open helix of
copper tape. The better and tighter the shield, the lower the emission level and the bearing
currents.

Additional US Requirements
Type MC continuous corrugated aluminum armor cable with symmetrical grounds or shielded
power cable must be used for the motor cables if metallic conduit is not used. For the North
American market, 600 VAC cable is accepted for up to 500 VAC. For drives rated over 100
amperes, the power cables must be rated for 70C (158F).

20

INSTALLATION (Frames R1-R6)


Conduit
Where conduits must be coupled together, bridge the joint with a ground conductor bonded
to the conduit on each side of the joint. Bond the conduits also to the drive enclosure. Use
separate conduits for input power, motor, brake resistors, and control wiring. Do not run
motor wiring from more than one drive in the same conduit.
Armored cable / shielded power cable
The motor cables can be run in the same cable tray as other 460 V power wiring. Control and
signal cables must not be run in the same tray as power cables. Six conductor (3 phases and 3
ground) type MC continuous corrugated aluminum armor cable with symmetrical grounds is
available from the following suppliers (tradenames in parenthesis):

Anixter Wire & Cable (Philsheath)
BICC General Corp (Philsheath)

Rockbestos Co. (Gardex)
Oaknite (CLX).
Shielded power cables are available from Belden, LAPPKABEL (OLEFLEX) and Pirelli.

Installing the Drive


WARNING! Before installing the AQUAVAR, ensure the input power supply to the
drive is off.
Unpack the Drive
1. Unpack the drive.
2. Check for any damage and notify the shipper immediately if
damaged components are found.
3. Check the contents against the order and the shipping label to verify
that all parts have been received.
Prepare the Mounting Location
The AQUAVAR should only be mounted where all of the requirements
defined Preparing for Installation on page 15 are met.
1. Mark the position of the mounting holes. Refer to page 138 for
mounting hole location.
2. Drill the holes.

1
X0002

NOTE! Frame sizes R3 and R4 have four holes along the top.
Use only two. If possible, use the two outside holes (to allow
room to remove the fan for maintenance).
Remove Front Cover
IP 21 / UL Type 1
1. Remove the control panel, if attached.
2. Loosen the captive screw at the top.
3. Pull near the top to remove the cover.

21

INSTALLATION (Frames R1-R6)


IP 54 / UL Type 12
1. If hood is present: Remove screws (2) holding hood in
place.
2. If hood is present: Slide hood up and off of the cover.
3. Loosen the captive screws around the edge of the cover.
4. Remove the cover.

Mount the Drive


IP 21 / UL Type 1
1. Position the AQUAVAR onto the mounting screws or bolts and
securely tighten in all four corners.
NOTE! Lift the AQUAVAR by its metal chassis.
2. Non-English speaking locations: Add a warning sticker in the
appropriate language over the existing warning on the top of
the module.

IP 54 / UL Type 12
For the IP54 / UL Type 12 enclosures, rubber plugs are required in
the holes provided for access to the drive mounting slots.
1. As required for access, remove the rubber plugs. Push plugs
out from the back of the drive.
2. Position the AQUAVAR onto the mounting screws or bolts and
securely tighten in all four corners.
NOTE! Lift the AQUAVAR by its metal chassis.
3. Reinstall the rubber plugs.
4. Non-English speaking locations: Add a warning sticker in the
appropriate language over the existing warning on the top of the module.

22

INSTALLATION (Frames R1-R6)


Install the Wiring
Conduit/Gland Kit
Wiring drives with the IP 21 / UL type 1 Enclosure requires a conduit/gland kit with the
following items:
Conduit/gland box
Screws
Cover
The kit is included with IP 21 / UL type 1 Enclosures.
Overview
As you install the wiring, observe the following:
There are four sets of wiring instructions one set for each combination of drive enclosure
type (IP 21 / UL type 1 and IP 54 / UL type 12), and wiring type (conduit or cable). Be sure
to select the appropriate procedure.
Connection Diagrams on page 24 shows the connection points on the drive.
Power Connections on page 29 describes specific instructions for wiring the power. Use
in combination with the appropriate general procedure.
Control Connections on page 29 describes specific instructions for wiring the control.
Use in combination with the appropriate general procedure.
Cable Terminals on page 135 list the recommended tightening torques.
Where applicable, observe EMC recommendations. For example, properly ground the wire
screen cable shields.

23

INSTALLATION (Frames R1-R6)


Three Phase Wiring/Connection Diagrams
The layout of connection terminals is similar for all frame sizes (R1R6). The only significant
layout difference is in the power and ground terminals for frame sizes R5 and R6. The
following diagrams show:
Terminal layout for frame size R3, which, in general, applies to all frame sizes except as
noted above.
Power and ground terminal layout for frame sizes R5 and R6.

WARNING! For floating networks remove screws at EM1 and EM3.

24

INSTALLATION (Frames R1-R6)


Three Phase Wiring/Connection Diagrams continued

Not used

WARNING! For floating networks remove screws at F1 and F2.

25

INSTALLATION (Frames R1-R6)


Single Phase Wiring/Connection Diagram

Not used

WARNING! For floating networks remove screws at EM1 and EM2.


WARNING! For single phase wiring, derate the 3 phase nominal HP and
amps 50%.

26

INSTALLATION (Frames R1-R6)


Wiring IP 21 / UL Type 1 Enclosure with Conduit
1. Open the appropriate knockouts in the conduit/
gland box.
2. Install thin-wall conduit clamps (not supplied).
3. Install conduit/gland box.
4. Connect conduit runs to box. Always follow
appropriate NEC or local electrical codes for inverter
drives, motor wiring.
5. Route input power and motor wiring through
conduits. Preferably metal, grounded type.
6. Strip wires.
7. Connect power, motor, and ground wires to the drive
terminals. See Power Connections on page 29.
8. Route the control cable, transducer cable through the
conduit.
9. Strip the control cable sheathing and twist the copper
screen into a pigtail.
10. Connect the transducer screen pigtail for digital and
analog I/O cables at X1-1.
11. Strip and connect the individual control wires to the
drive terminals. See Control Connections on page
29. Including transducer.
12. Install the conduit/gland box cover (1 screw).
13. Wire transducer leads to analog 2, terminal(s) +24V,
AI2 and GND.
14. Wire positive lead of transducer to terminal 10
(+24VDC). Color is red or brown.
15. Wire analog lead (negative) to terminal 10 of X1 for
4-20mA signal. Color is white or black.
16. Take the transducer cable screen to X1, #1 Terminal.

27

INSTALLATION (Frames R1-R6)


Wiring IP 54 / UL Type 12 Enclosure with Conduit
1. Remove and discard the clamping plate.
2. Remove and discard the cable seals where
conduit will be installed. (The cable seals are
cone-shaped, rubber seals on the bottom of the
drive.)

3. For each conduit run, install water tight conduit


connectors (not supplied).

4. Route the power wiring through the conduit.


5. Route the motor wiring through the conduit.
6. Strip the wires.
7. Connect the power, motor and ground wires to
the drive terminals. See Power Connections on
page 29.
8. Route the control wiring through the conduit.
9. Strip the control cable sheathing and twist the
copper screen into a pigtail.
10. Connect the ground screen pigtail for digital and
analog I/O cables X1-1.
11. Strip and connect the individual control wires to
the drive terminals. See Control Connections on
pages 29 and 30.
12. Install the conduit/gland box cover (1 screw).
13. Install and wire transducer as stated in previous
steps on pages 27 and 28.
28

INSTALLATION (Frames R1-R6)


Power Connections
WARNING! Ensure the motor is compatible for use with the AQUAVAR. The AQUAVAR
must be installed by a competent person in accordance with the considerations
defined in Preparing for Installation on page 15. If in doubt, contact your local AQUAVAR
sales or service office. Always consult the NEC for information.
Refer to the following table to complete the power connections. If appropriate, also
perform the instructions for the braking and floating networks.
Terminal

Description

Note



U1, V1, W1*
3-phase power supply input

Input Power (Mains) Connection


on page 136.

PE

Follow local rules for cable size.

Protective Ground



U2, V2, W2
Power output to motor

Motor Connection on
page 136.

* NOTE: The AQUAVAR (208240V series) can be used with a single phase supply, if output current is derated by 50%.
For single phase supply voltage, connect power at U1 and W1. Refer to page 26.

Floating Networks
For floating networks (also known as IT, ungrounded or high impedance networks):
Disconnect the internal RFI filter by removing both the EM1 and EM3 screws (frame sizes
R1R4, see page 24), or F1 and F2 screws (frame sizes R5R6, see page 25).
Where EMC requirements exist, check for excessive emission propagated to neighboring
low voltage networks. In some cases, the natural suppression in transformers and cables is
sufficient. If in doubt, use a supply transformer with static screening between the primary
and secondary windings.
Do NOT install an external filter. Using an RFI filter grounds the input power through the
filter capacitors, which could be dangerous and could damage the unit.
Control Connections
To complete the control connections, use:
Following tables
Single/Multipump
Complete Parameter Descriptions
Cable recommendations in Control Cables

29

INSTALLATION (All Frames)


X1

Transducer

1
SCR
Screen/

Shield

Control Wiring

ON

Terminal for transducer shield. (Connected internally to chassis ground.)


Analog input channel 1, 2nd transducer. Default2 = frequency reference.

2
AI1
Resolution 0.1%, accuracy 1%.

J1:AI1 OFF: 010 V (Ri = 312 k)

J1:AI1 ON: 020 mA (Ri = 100 )
Switch positions listed on page 25.

3
AGND
Analog input circuit common. (Connected internally to chassis gnd.

through 1 MW. Jumper wire to X1-11.)
Jumper
Wire

4
+10 V
10 V/10 mA reference voltage output for analog input potentiometer,

accuracy 2%. (Not used.)
()

Analog input channel 2.
Transducer

5
AI2
Resolution 0.1%, accuracy 1%.
(4-20mA)

Transducer input
Connection

420 mA
(White
or
Black)
6
AGND
Analog input circuit common. (Connected internally to chassis gnd.

through 1 M)

7
AO1
Analog output, programmable. Default2 = Not used. Current 020 mA

(load < 500 )

8
AO2
Analog output, programmable. Default2 = Not used. 020 mA
(+)

(load < 500 )
Transducer

9
AGND
Analog output circuit common (Connected internally to chassis gnd.
Power

through 1 M)
Supply
(Brown

10 +24V
Auxiliary voltage output 24 VDC / 250 mA (reference to GND). Short
or
Red)

circuit protected. Transducer/digital input power supply.

11 GND
Auxiliary voltage output common. (Connected internally as floating.)
Jumper
Wire

Digital input common. To activate a digital input, there must be +10 V
11 and 12
12 DCOM (or -10 V) between that input and DCOM. The 24 V may be provided by

the AQUAVAR (X1-10) or by an external 1224 V source of either polarity.
10 15

13 DI1
Digital input 1, programmable. Default2 = run enable (Group 24)
E-stop
or Jumper
14 DI2
Digital input 2, programmable. Default2 = low water (Group 24)

15 DI3
Digital input 3, programmable. Default2 = E-stop or jumper
E-stop/
Jump
16 DI4
Digital input 4, programmable. Default2 = set point selection
start
17 DI5
Digital input 5, programmable. Default2 = HOA (Group 12)
to +24V for
enable

18 DI6
Digital input 6, programmable. Default2 = not used
(15 to 10

19 RO1C
Relay output 1, programmable. Default2 = drive ready
Jumper)

20 RO1A
Maximum: 250 VAC / 30 VDC, 2 A
Minimum: 500 mW (12 V, 10 mA)

21 RO1B

22 RO2C
Relay output 2, programmable. Default2 = pump run

23 RO2A
Maximum: 250 VAC / 30 VDC, 2 A
Minimum: 500 mW (12 V, 10 mA)

24 RO2B

Relay Outputs

Digital Inputs1

Analog I/O

ON

25 RO3C
26 RO3A
27 RO3B

Relay output 3, programmable. Default2 = fault


Maximum: 250 VAC / 30 VDC, 2 A
Minimum: 500 mW (12 V, 10 mA)

Digital input impedance 1.5 k. Maximum voltage for digital inputs is 30 V.


Default values depend on the macro used. Values specified are for the default macro, single/multipump.
NOTE: Jumper Wires between 3 and 11, 10 and 15, 11 and 12.
1
2

NOTE! Terminals 3, 6 and 9 are at the same potential.


NOTE! For safety reasons the fault relay signals a fault when the AQUAVAR is
powered down.
30

INSTALLATION (Frames R1-R6)


You can wire the digital input terminals in either a PNP or NPN configuration.

PNP Connection (Source)


X1

NPN Connection (Sink)


X1

10 +24V
11 GND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6

10 +24V
11 GND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6

Communications
Terminals 2832 are for RS485 or modbus communications. Use shielded cables. For lengths
of cable beyond 100 feet, use screen connections.
Do not directly ground the RS485 network at any point. Ground all devices on the network
using their corresponding earthing terminals.
As always, the grounding wires should not form any closed loops, and all the devices should
be earthed to a common ground.
Terminate the RS485 network using 120 resistors at both ends of the network. Use the DIP
switch to connect or disconnect the termination resistors. See following diagram and table.
Terminated
Station

Station

X1 Identification
28 Screen
29 B

RS485
Multipump
Connections

30 A
31 AGND
32 Screen

Terminated
Station

Station

Hardware Description1
RS485 Multidrop Application
Other Modbus Devices

SCR
B
A
GND
B
A
GND
SCR

28
29
30
31
32

SCR
B
A
AGND
SCR

RS485 Interface
J2 J5
J2 J5
ON ON
ON ON

off position on position


Bus Termination

For functional descriptions, see Standard Serial Communication addendum.

31

INSTALLATION (Frames R1-R6)


Check Installation
Before applying power, perform the following checks.

Check


Installation environment conforms to the drives specifications for ambient
conditions.

The drive is mounted securely.

Space around the drive meets the drives specifications for cooling.

The motor and driven equipment are ready for start (3 phase motor).

For floating networks: The internal RFI filter is disconnected.

The drive is properly grounded, along with the pump, motor and control panel.

The input power (mains) voltage matches the drive nominal input voltage (watch
for open delta power).

The input power (mains) connections at U1, V1 and W1 are connected and
tightened as specified. Loose connections may cause arcing!

The input power (mains) fuses are installed, according to NEC.

The motor connections at U2, V2 and W2 are connected and tightened as


specified.

The motor cable is routed away from other cables and in separate conduit.

NO power factor compensation capacitors are in the motor cable.

The control connections are connected and tightened as specified.

NO tools or foreign objects (such as drill shavings) are inside the drive.

NO alternate power source for the motor (such as a bypass connection) is


connected no voltage is applied to the output of the drive.

Single phase power is connected to U1 and W1 with GND.

32

INSTALLATION (Frames R1-R6)


Reinstall Cover
IP 21 / UL Type 1
1. Align the cover and slide it on.
2. Tighten the captive screw.
3. Reinstall the control panel.

IP 54 / UL Type 12
1. Align the cover and slide it on.
2. Tighten the captive screws around the edge of the cover.
3. Slide the hood down over the top of the cover.
4. Install the two screws that attach the hood.
5. Reinstall the control panel.
NOTE! The control panel window must be closed to
comply with IP 54/UL type 12.
6. Optional: Add a lock (not supplied) to secure the control
panel window.
Apply Power
Always reinstall the front cover before turning power on.
WARNING! The AQUAVAR will start up automatically at power up, if the
external run command is on.
1. Apply input power.
When power is applied to the AQUAVAR, the green LED comes on.
NOTE! Before increasing motor speed, check that the motor is running in
the desired direction.
Start-Up
The AQUAVAR has default parameter settings that are sufficient for many situations. However,
review the following situations. Perform the associated procedures as appropriate. Proceed to
Start-Up section of this manual.

33

INSTALLATION (Frames R7-R8)


AQUAVAR Drive Manuals
GENERAL MANUALS
AQUAVAR Users Manual (IOM) (1150 HP)

Safety
Diagnostics

Installation
Maintenance

Start-Up
Technical Data
AQUAVAR Users Manual (IOM) (200550 HP)

Safety
Diagnostics

Installation
Maintenance

Start-Up
Technical Data
OPTION MANUALS
(Fieldbus Adapters, I/O Extension Modules etc.,
manuals delivered with optional equipment.)

Relay Output Extension Module (typical title)



Installation
Diagnostics

Start-Up
Technical Data

34

INSTALLATION (Frames R7-R8)


Introduction
AQUAVAR CPC drives include an extension module that
is not covered in the AQUAVAR Users Manual. The extension module is attached to the drive module at the factory,
which includes fusible disconnect.
This supplement provides the additional extension module information required for AQUAVAR drives:
Additional installation steps and considerations.
Steps for separating the drive from the extension module for drive service access.
Extension
Dimensions for the extension module.

Module

Drive
Module

WARNING! Only qualified electricians are allowed to carry out the work described
in this chapter. Follow requirements in Safety on the first pages of this manual.
Ignoring the safety instructions can cause injury or death.

Planning
When planning for cable/conduit routing, refer to the AQUAVAR Users Manual, but note that,
for the AQUAVAR, all connections are routed through the top of the extension module.

Moving the Unit


1. Move the transport package by pallet truck to the installation site.
2. Unpack the transport package.
3. To position the unit, use a lift, connected as shown.

Mounting
Fastening the Unit
See the Dimensional Drawings on page 41 for the exact locations
of the mounting points.
1. Use at least four screws two at the front, two at the back to attach the unit base plate to
the floor.
2. Use at least two screws to attach the back of the enclosure to a wall.
There are two holes available at the top of each: the extension module and the drive module.

35

INSTALLATION (Frames R7-R8)


Connecting Power and Control Cables
Additional considerations that apply with the enclosure extension:
The power cable connection diagram that applies for the AQUAVAR is:
AQUAVAR
Drive Module

Extension Module

OMIO
3
Switch-fuse
Disconnect

Control
Panel

U1 V1 W1

U2

V2

W2

PE

Control
Wiring

L1

L2

L3 PE

Supply

U1

V1

W1
PE

3~
Motor

Temporarily remove the upper high voltage shield (clear plastic) to gain access to the
power connections in the extension module.
To avoid metal shavings inside the cabinet, temporarily remove the gland/conduit plate
at the top of the extension module. Then drill holes and mount conduit or cable fittings as
needed.
Route all power and control wiring through the top of the extension module.

36

INSTALLATION (Frames R7-R8)


The following diagram shows the power and control connection points in the enclosure
module supplied with the R7 drive module.

37

INSTALLATION (Frames R7-R8)


The following diagram shows the power and control connection points in the enclosure
module supplied with the R8 drive module.

Re-mount the high voltage shield.


WARNING! Always replace all high voltage shields before applying power.
See the AQUAVAR Users Manual for detailed instructions on control connections,
installation check list and drive start-up process.

38

INSTALLATION (Frames R7-R8)


Maintenance
This section describes the procedure for separating the drive and extension modules, which is
required to provide service access to the drive module.
Safety
WARNING! Read Safety on the first pages of this manual before performing any
maintenance on the equipment. Ignoring the safety instructions can cause injury or
death. Note: There are parts carrying dangerous voltages near the OMIO board when the
drive is powered.
Separating the Drive and Extension Modules
The drive module is mounted on a trolley that straddles a pedestal. The following procedure
removes mechanical connections so that the drive module and trolley can roll forward for
service access.
1. Disconnect all power sources from the drive/extension modules
and wait at least 5 minutes for internal capacitors to fully
discharge.

R7

2. Remove all front covers from the drive module.


3. Disconnect the control panel cable.
4. Remove the upper side plate from the drive module if convenient.
5. Remove screws (if any) that fasten the drive module to the wall.
6. Inside the pedestal, toward the rear are screws that attach the
drive bus bars to the pedestal bus bars. The connections are
staggered for easy access using a wrench with an extension.
Remove these screws (6).
Torque when re-assembling:
R7: M8 (5/16 in) screws, 1522 Nm (1116 lb ft)
R8: M10 (3/8 in) screws, 3044 Nm (2232 lb ft)

WARNING! Be careful not to drop screws inside the pedestal.


Loose metal pieces inside the unit may cause damage.
R7
7. The following cables between the drive and the extension
module are split by a connector located at the front of the drive.
Disconnect both cables at this location.
The power supply cable to the OMIO board.
The power supply cable to the extensionmodule cooling fan.

8. At the OTIF board, disconnect the two fiber optic cables. Make
note of the terminal colors for use when reconnecting.

8
9

9. Carefully remove the cables disconnected in the above steps: Pull


the cables down inside the pedestal and bundle them so that they
will not get damaged or caught in the trolley when the drive module is wheeled out.
39

INSTALLATION (Frames R7-R8)


10. Remove screws fastening the drive module trolley to the
pedestal.

R7

12

WARNING! These screws are an important step during reassembly the screws are required for grounding the drive.
11. R8: The front of the trolley includes support braces that fold
out. Lift each brace slightly and fold it out.
12. Remove screws that fasten the drive module to the extension
module.
CAUTION! The drive module is now separated and could
tip over. Use care when moving the drive module.
13. Pull on the handle to wheel the drive module out.
Drive Maintenance
See the AQUAVAR Users Manual for drive maintenance
procedures, page 34.
Re-Assembly
Re-attach the modules in reverse order to the above.

40

13
10
10

Pedestal
Trolley

INSTALLATION (Frames R7-R8)


Technical Data
Dimensional Drawings
See the AQUAVAR Users Manual for drive module dimensions.
Extension Module R7

200
[7.87]

200
[7.87]

0
[.00]

161.4
[6.35]

361.4
[14.23]

Dimensions are listed in millimeters and [inches].

598.9
[23.58]
523
[20.59]

294
[11.57]

323
[12.72]

29
[1.14]
0
[.00]
BOTTOM PLATE HOLE 14 (6 pcs)

[.55]

81
[3.19]

12

81
[3.19]

520
[20]
381
[15.00]

29.55
[1.16]

33
[1.30]

286
[11.26]

A
LIFTING LUG (4 pcs)

(2 pcs.)

1501
[59.1]
1459
[57.44]

[.47]

352
[13.86]
190
[7.48]

DET. B

SEE SHEET 2

DET. A

SEE SHEET 2
465.5
[18]

MAIN
SWITCH

2.5
[.10]

12
[.47]

26.5
[1.04]

298.5
[11.75]

17
[.67]
45
[1.77]

734
[28.90]

193.7
[7.63]

27
[1.06]

A-A

C-C

425.1
[16.74]
598.4
[23.56]

3AFE 64626264 30.04.02

41

INSTALLATION (Frames R7-R8)


Detail R7
Dimensions are listed in millimeters and [inches].

520
[20.47]
0
[0.00]

133.9
[5.27]

0
[0.00]

U2, V2
V2
R, R+

52.1
[2.05]

223.3
[9.15]
278.3
[10.96]

201.5
[7.93]

0
[0.00]

132.5
[3.22]
125.3
[4.93]
102.5
[4.04]

155.5
[6.12]

78.8
[3.10]
24.8
[4.91]

<425.9 >
[16.77]

0
[0.00]

133.9
[5.27]

109.8
[4.32]

159.8
[6.29]

239.8
[10.23]

309.8
[12.19]

PE HOLE 2 (4 pcs.)
[.47]

488
[19.21]

U2

493.4
[19.43]

V2

R+

W2

540.5
[21.28]

578
[22.76]

U1

V1

W1

DET.B
2.5

42

250.5
[9.86]
256.8
[10.11]
285.5
[11.24]
300.5
[11.83]

186
[7.32]

151
[5.94]

2.5

87.5
[3.44]

DET.A

52.3
[2.07]

321.7
[12.67]

0
[0.00]

12 .5 (12 pcs.)
[.49]

11.1 (2 pcs.)
[0.43]

INSTALLATION (Frames R7-R8)


Extension Module R8
Dimensions are listed in millimeters and [inches].

260
[10.24]

152.3
[6.00]

35.5
[1.40]

700
[27.56]

BOTTOM PLATE HOLE 14


[.55]

446
[17.56]
260
[10.24]

491.4
[19.35]

21.2
[0.83]

26
[1.02]

393.9
[15.51]

1882.5
[74.11]

2018
[79.45]

93
[3.66]

617
[24.3]

611.8
[24.09]

272.2
[10.72]

946.7
[37.27]

563.1
[22.2]

17
[0.67]

392.5
[15.45]

46
[7.81]

2.5
[0.10]

12
[0.47]

B
554.5
[21.83]
787
[30.98]

3AFE 64626388 30.04.02

43

44
372
[14.65]

327
[12.87]

222.5
[8.76]

177.5
[6.99]

117
[4.61]

72
[2.83]

14 (6 pcs.)
[.55]

0
[0.00]

0
[0.00]

382.5
[15.06]

280.5
[11.04]

208.5
[8.21]

136.5
[5.37]

82
[3.23]

128
[5.04]

174
[6.85]

873.8
[34.40]

0
[0.00]

110.8
[4.36]

160.8
[6.33]

210.8
[8.30]

310.8
[12.24]

360.8
[14.20]

410.8
[16.17]

PE HOLE 11 (6 pcs.)
[.43]

0
[0.00]

0
[0.00]

47.5
[1.87]

115.5
[4.55]

379.3
[14.93]

INSTALLATION (Frames R7-R8)

Detail R8
Dimensions are listed in millimeters and [inches].

617
[24.3]

0
[0.00]

222.3
[8.75]

59.2
[2.33]

730.9
[28.77]

14 (6 pcs.)
[.55]

12.5 (2 pcs.)
[.49]

START-UP
Wizards
The Wizard configures the drive. This process sets parameters that define how the drive operates and communicates. Depending on the control and communication requirements, the
start-up process may require any or all of the following:
The Start-up Wizard steps you through the default configuration. The Start-up Wizard can
be activated at the first power up, or can be accessed at any time using the main menu.
Application macros can be selected to define common, alternate system configurations, using the default settings. See Single or Multipump Setup/Programming on page 73.
Additional refinements can be made using the control panel to manually select and set
individual parameters. See Complete Parameter Descriptions on page 50.

Assistant Control Panel (Display)


Features
The AQUAVAR CPC Control Panel features:
Alphanumeric control panel with a LCD display
Language selection for the display
Drive connection that can be made or detached at any time
Start-Up Wizard to ease drive commissioning
Copy function Parameters can be copied to the Control Panel memory for later transfer to
other drives or for backup of a particular system.
Context sensitive help
Control Panel (Keypad)
The following table summarizes the button functions and displays on the Control Panel.
LCD Display Divided into three main areas:
Top line variable, depending on the mode of operation.
For example, see Status Information
Middle area variable, in general, shows parameter values, menus or
lists.
Bottom line shows current function of the two soft keys and the clock
display, if enabled.

Soft key 1 Function varies and is


defined by the text in the lower-left
corner of the LCD display.
Up Arrow
Scrolls up through a menu or list
displayed in the middle of the LCD
Display.

Soft key 2 Function varies and is


defined by the text in the lower-right
corner of the LCD display.
REM

40.2 PSI sp
0.0 PSI ac
0.0 HZ

DIR

12:45

50%

Down Arrow

MENU

Decrements a value if a parameter


is selected.

Increments a value if a parameter


is selected.
Increments the reference if the
upper-right corner is highlighted
(in reverse video).

Scrolls down through a menu or list


displayed in the middle of the LCD
Display.

Decrements the reference if the


upper-right corner is highlighted
(in reverse video).

LOC
REM

Help Displays context sensitive


information when the button is pressed.
The information displayed describes the
item currently highlighted in the middle
area of the display.

LOC/REM Changes between local


and remote control of the AQUAVAR.
STOP Stops the drive.
START Starts the drive.

45

START-UP
Output mode
Use the output mode to read information on the drives status and to operate the drive. To
reach the Output Mode, press EXIT until the LCD display shows status information as described below.
Status Information
Top The top line of the LCD display shows the basic status information of the drive.
LOC indicates that the drive control is local, that is, from the control panel.
REM indicates that the drive control is remote, which is required to operate the pump
and automatically control pressure. This mode is also used for fieldbus control. (e.g. Transducer or PLC control)
indicates the drive status as follows:


Control Panel Display


Rotating arrow blinking

Significance
Drive is running

Stationary arrow

Drive is stopped

Upper right (50%) shows the percentage of full scale the transducer is operating.
Middle The middle of the LCD display will display:
For Single Pump
Reference or set point. Pressure SP
Actual set point. Pressure AC
Frequency in HZ.

REM

DIR

40.2 PSI sp
0.0 PSI ac
0.0 HZ
12:45

50%

MENU

NOTE! The AQUAVAR display will show (set pressure), (actual pressure) and Frequency
(Hz), in single pump mode.
Bottom The bottom of the LCD display shows:
Lower corners show the functions currently assigned to the two soft keys.
Lower middle (12:45) displays the current time (if configured to show the time).
Operating the Drive
LOC/REM The very first time the drive is powered up, it is in the remote control (REM) mode,
and is controlled from the Transducer and Control Panel.
To switch to local control (LOC) and control the drive using the Control Panel, press and hold
the
button. The drive must be stopped!
The Remote (REM) Mode uses the transducer and set point to control the speed output to
the pump.
The Local (LOC) Mode uses the control panel for manual control of the drive output. Speed
up or down.
LOC
REM

To switch back to remote control (REM) press and hold the


button until REMOTE CONTROL is displayed.
Start/Stop To start and stop the drive press the START or STOP buttons.
LOC
REM

46

START-UP
Other Modes
Besides the Output Mode, the Control Panel has:
Other operating modes that are available through the main menu.
A fault mode that is triggered by faults. The fault mode includes a diagnostic assistant
mode.
REM
MAIN MENU
1
Access to Main Menu Modes
PARAMETERS
To reach the main menu:
1. Press EXIT, as necessary, to step back through the menus or WIZARDS
CHANGED PAR
lists associated with a particular mode. Continue until you
EXIT
ENTER
are back to the Output Mode.
2. Press MENU from the Output Mode. At this point, the middle of the display is a listing of
the other modes, and the top-right text says Main Menu.
3. Press UP/DOWN to scroll to the desired mode.
4. Press ENTER to enter the mode that is highlighted. The following sections describe each
of the other modes.

Parameters Mode
Use the Parameters Mode to view and edit parameter values:
1. Select PARAMETERS in the main menu.

REM

MAIN MENU

PARAMETERS
WIZARDS
CHANGED PAR
EXIT

2. Press UP/DOWN to highlight the appropriate parameter


group, then press SEL.

REM

ENTER

PAR GROUPS

99 START-UP DATA
01 OPERATING DATA
04 FAULT HISTORY
10 START/STOP/DIR
11 REFERENCE SELECT
EXIT

3. Press UP/DOWN to highlight the appropriate parameter


in a group.

REM

01

SEL

PARAMETERS

1101 LANGUAGE
1102 APPLIC MACRO
SINGLE PUMP
NOTE! The current parameter value appears below the high- 1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
lighted parameter.
EXIT

EDIT

4. Press EDIT.
5. Press UP/DOWN to step to the desired parameter value.
NOTE! To view the parameter default value: In the set mode, press UP/DOWN
simultaneously.
Press SAVE to store the modified value or press CANCEL
to leave the set mode. Any modifications not saved are
cancelled.
Press EXIT to return to the listing of parameter groups
and again to return to the main menu.

LOC

PAR EDIT

1102 EXT1/EXT2 SEL

EXT1

CANCEL

SAVE
47

START-UP
Wizard Mode
When the drive is first powered up, the Start-Up Wizard guides you through the setup of a few
basic parameters. For example, at the first start, the drive automatically suggests entering the
first task, password.
The Start-Up Wizard is divided into tasks. You may activate the tasks one after the other, as the
Start-Up Wizard suggests, or independently. (You are not required to use the assistant, you
may use instead, the parameter mode to set the drive parameters.)
The order of the tasks presented by the Start-Up Wizard depends on your entries. The task list
in the following table (next page) is typical.

Start-Up Wizard
The start-up wizard is a tool that can be used to quickly program an Aquavar with the most
commonly used single / mult-pump parameters. The wizard will prompt the programmer to
enter the required parameters by automatically bringing them to the screen. To enable the
wizard following the steps below:
1. In the main screen select MENU. Then press enter.
2. Press the up / down arrow to select WIZARDS, then press SELECT.
3. Enter the values for the parameters as seen in the table below, and follow each entry by
pressing the SAVE key.
4. When complete, press the EXIT key until the main screen is displayed again.
5. Set the required system pressure using the up and down arrows, then start the pump
using the green START key.








Task Name

Description

10.02 Pass Code


Pass word setting to open the parameter lock.
10.01 Parameter Lock
Enables or disables the parameters from being changed.
11.01 Language
Selects the display language.
11.04 Motor Nom Voltage
Defines the motor nameplate voltage.
11.05 Motor Nom Current
Defines the motor nameplate current.
11.06 Motor Frequency
Defines the motor nameplate frequency.
11.08 Nominal Motor Power Defines the motor nominal power.
15.06 Sensor Min
Adjusts the transducer to a zero reference point.

Changed Parameters Mode
Use the Changed Parameters Mode to view (and edit) a listing of all parameters that have
been changed from default values.
Procedure:
1. Select CHANGED PAR in the Main Menu. The display lists all changed parameters.
2. Press ENTER.
3. Press UP/DOWN to select a changed parameter. As each parameter is highlighted, the
parameter value appears.
4. Press EDIT to edit the parameter value.

48

START-UP
5. Press UP/DOWN to select a new value / edit the parameter value. (Pressing both keys at
the same time sets a parameter to its default value.)
6. Press SAVE to save the new parameter value. (If the new value is the default value, the parameter will no longer appear on the Changed Parameters listing.)
Par Backup Mode
The Control Panel can store a full set of drive parameters. If two sets of parameters are defined, both are copied and transferred when using this feature.
The Par Backup Mode has three functions:
Upload to Panel Copies all parameters from the drive to the Control Panel. The Control
Panel memory is nonvolatile and does not depend on the panels battery.
Restore All (Download To Drive All) Restores the full parameter set(s) from the Control
Panel to the drive. Use this option to restore a drive or to configure identical drives. Drive
must be in local mode.
NOTE! The Restore All function writes all parameters to the drive, including motor parameters. Only use this function to restore a drive or to transfer parameters to systems that are
identical to the original system.
Download Application Copies partial parameter set(s) from the Control Panel to a drive.
The partial set does not include internal motor parameters. Use this option to transfer parameters to systems that use similar configurations - the drive and motor sizes do not need
to be the same.
1. Select COPY in the Main Menu.
2. Press UP/DOWN to step to the desired option.
3. Press SAVE. The parameter set is transferred as directed. During the transfer, the
display shows the transfer status as a percent of completion.
4. Press EXIT to step back to the Output Mode.
Clock Set Mode
Use the Clock Set Mode to:
Enable/disable the clock function.
Set date and time.
Select display format.
1. Select CLOCK SET in the Main Menu.
2. Press UP/DOWN to step to the desired option.
3. Press EDIT.
4. Press UP/DOWN to select the desired setting.
5. Press SAVE to save setting.

49

PARAMETER LISTINGS
Aquavar CPC Parameter List
The Aquavar CPC parameter list contains all of the necessary pump, drive, fault and control
parameters needed for programming this unit. Each group indicates a certain function and
control for the Aquavar, in order to set up single or multipump control.
To view the available parameter list, on your keypad, press the MENU button to access the
parameter list. The parameters are write protected with a password. Please contact your
Aquavar representative for more information on this password (located in GROUP 10 LOCKS/
PASSWORDS).
Group 01, VFD SIGNALS (READ ONLY DATA) This set of parameters sets up the drive and
motor. These parameters can only be adjusted and changed when the motor has stopped.
Monitoring of motor output, and various analog and digital outputs.
Group 02, PUMP SIGNALS (Data output only) Provides output set points, energy savings
and wire to water power.
Group 03, STATUS WORDS Provides status of drive and alarm condition.
Group 10, LOCKS/PASSWORDS Provides password and parameter save information.
Keypad and set point locks.
Group 11, START UP DATA Provides parameters used for initial start up information (e.g
language, application, voltage, motor current, motor RPM, horsepower). Used for initial motor
setup.
Group 12, START/ STOP Determines method(s) of starting and stopping the Aquavar. i.e.
Keypad, external switch, Modbus, manual, test run and motor jog.
Group 13, RAMPS & WINDOWS Parameters used for the acceleration and deceleration
of the pump. Window and Hysterisis contains modulation of algorithm (pressure control
regulation).
Group 14, SPD LIM/START LVL Parameters that contain speed control, max and min
frequency, restart value, priming delay.
Group 15, TRANSDUCER VAR Parameters used for the setup and tuning of the pressure
transducer, flow meter and adjustment of transducer range.
Group 16, REFERENCE SELECT Parameters that control how the set point is maintained. i.e.
Modbus, keypad, analog input (transducer).
Group 18, RELAY OUTPUTS Parameters that define how the Aquavar output relays are
controlled and what delay time is actuated for each relay. Three total relays can be used (RO1,
RO2, RO3).
50

PARAMETER LISTINGS
Aquavar CPC Parameter List (continued)
Group 19, ANALOG OUTPUTS Defines the analog outputs available on the drive. Two
possible analog outputs that can be used to monitor various parameters (AO1, AO2).
Group 21, REGULATE Defines type of control regulation with analog input from transducer.
Normal, Inverse modes. Friction loss compensation.
Group 22, MULTIPUMP CONTROL Defines parameters for multi-pump control algorithm.
Addresses each drive. Required group for alternating each pump.
Group 24, FAULT FUNCTIONS Defines parameters for faults, pump protection and run
enable mode (e.g. keypad failure, pump protect, low water, error reset).
Group 25, AUTOMATIC RESET This group defines conditions for automatic reset. An
automatic reset occurs after a particular fault is detected. The Aquavar holds for a delay time,
then automatically restarts. You can limit the number of restarts in a specific period of time for
a variety of faults (e.g. overcurrent, over/ under voltage).
Group 26, ENERGY SAVINGS Defines parameters used for energy savings, and kW/hr
usage.
Group 27, CRITICAL SPEEDS This group defines up to three critical speeds or resonant
frequencies. This mechanical resonance may occur on certain loads at certain frequencies.
Group 30, OPTION MODULES Defines parameters used for fieldbus communication
networks and optional fieldbus adapter.
Group 31, FIELD BUS SETUP Parameters used for actual set up for the field bus
communication via the RS485 terminals.
Group 32, MODBUS SETUP Defines parameters used for the Modbus setup and protocol,
baud rate, parity, status functions.
Group 50, MOTOR CONTROL Provides adjustment of the switching frequency for the drive.
Group 51, MAINTENANCE TRIGGERS Defines the parameters for trigger points on the
cooling fan, motor revolutions, run time, used power in Megawatts. Provides actual time run
on each component.
Group 99, INFORMATION Provides firmware version, drive rating for the Aquavar.

51

PARAMETER LISTINGS
Defaults
Group VFD Signals
Range
Description
01
0101 Motor
0.0...500.0 Hz

Frequency

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Calculated VFD output


frequency, Hz

0102 Motor Current 0...2.0*I2hd


Measured Motor Current, A
0103 Motor Power
-2...2*Phd
Motor Power, kW
0104 DC Bus Voltage 02.5*Vdn
Measured intermediate circuit

voltage, V
0105 Motor Voltage 02.0*Vdn
Calculated motor voltage, V
0106 Drive Temp
0150 C
VFD Temp, Deg C
0107 VFD On Time
09999h
Elapsed time counter; runs

when the drive is powered, Hrs

(since last reset). Re-settable by

parameter 2605.
0108 Run Time
09999h
Motor run time counter, Hrs

(since last reset). The counter

runs when the inverter

modulates. Re-settable by

parameter 2605.
0109 KWh Counter
09999kWh kWh counter, kWh (since last

reset). Re-settable by parameter

2605.
0110 DI6-1 Status
000000
Status of digital inputs.

111111
Example: 0000001=DI1 is on,

DI2-DI6 off
0111 AI1
0100 %
Value of analog input 1, %
0112 AI2 Trnsdcr Fdbk 0100 %
Value of analog input 2, %
0113 RO3-1 Status
000111
Status of relay outputs.

Example: 001=RO1 is energized,

RO2 & RO3 are de-energized.
0114 AO1[mA]
020 mA
Value of analog output 1, mA
0115 AO2[mA]
020 mA
Value of analog output 2, mA
0116 Last Fault
Fault Codes
Last fault code of the drive.
0117 Previous Fault 1 Fault Codes
Previous fault code of the drive.
0118 Previous Fault 2 Fault Codes
Oldest fault code of the drive.
0119 Fault Time 1
0120 Fault Time 2
0121 Speed at Flt
- RPM
Speed at the time of the latest

fault.
0122 Freq at Flt
- Hz
Frequency at the time of the

latest fault.
0123 Voltage at Flt
- V
DC bus voltage at the time of

the latest fault.
NOTE: Group 01 is read-only. Used for monitoring.

52

PARAMETER LISTINGS
Defaults
Group VFD Signals
Range
Description
01
0124 Current at Flt
- A

0125 Status at Flt
-

0126 DI 6-1 At Fault 000111

0127 Drive On Time Hi - Days
0128 Drive On Time Lo - Hrs : Min : Sec

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Motor current at the time of


the latest fault.
The drive status word at the
time of the latest fault.
The drive digital input status at
the time of the latest fault.
Drive on - time in days.
Drive on - time in hrs/min/secs.

Group Pump Signals


Range
Description
02

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

0201 Set Point


0max scale Controller set point; unit

determined by parameter 1501.
0202 Actual
0max scale Actual feedback; unit

determined by parameter 1501.
0203 Pump Speed
0 60 Hz
Actual frequency of motor, Hz.
0204 Wire to Water
0? Hp
Overall hp includes pump,

Power
motor and VFD.
0205 Set Point #1
0max scale Set Point (reference) #1; unit

determined by parameter 1501.
0206 Set Point #2
0max scale Set Point (reference) #2; unit

determined by parameter 1501.
0207 Energy Savings 065353 USD Calculated AV savings (option 1

or 2) since last reset. Savings are

compared to conventional

system ($). Re-settable by

parameter 26.05.
0208 Pump Number Stopped, Pump Actual pump number in multi
1Pump 4
pump control mode.
0209 Used Set Point 0max scale Same value as in 0205 or 0206,

depending on which is in use.
Group Status Words
Range
Description
03
0301
0302
0303
0304
0305
0306
0307
0308
0309

FB CMD Word 1
FB CMD Word 2
FB STS Word 1
FB STS Word 2
Fault Word 1
Fault Word 2
Fault Word 3
Alarm Word 1
Alarm Word 2

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Low word of drives control word


High word of drives control word
Low word of drives status word
High word of drives status word
Fault word 1 of the drive
Fault word 2 of the drive
Fault word 3 of the drive
Alarm word 1 of the drive
Alarm word 2 of the drive

53

PARAMETER LISTINGS
Defaults
Group Status Words
Range
Description
03
0310
0311
0312
0313
0314
Group
10

AV Alarm Word
AV Fault Word
Comm RO Word
Comm Value 1
Comm Value 2


Aquavar Alarm word

Aquavar Fault word


Locks/
Range Description
Passwords

1001 Parameter Lock





Open


Locked

(Default)







1002 Pass Code
0300000






1003 Local Lock





Off (Default)

On
1004 Parameter Save


Done (Default)



54

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Selects the state of the parameter Locked Locked Locked Locked Locked
lock. The lock prevents
parameters from being changed.
The lock is open. Parameter
values can be changed.
Parameter values cannot be
changed from the keypad. The
lock can be opened by entering
the valid password in parameter
10.02. When the keypad is
locked the AV keypad functionality is limited to starting,
stopping and changing the
reference (set point).
Password setting 66 opens the
0 0 0 0 0
lock and returns the value to
zero on the display. The password relocks when power is
disconnected. To relock the
keypad reset parameter 1001
to Locked.
Disables local control on the
Off Off Off Off Off
keypad. WARNING! Before
activating, ensure that the
control panel is not needed for
stopping the drive.
Local control allowed.
Local control disabled.
Saves the parameter values to Done Done Done
Done
Done
the permanent memory.
Parameters entered via the
keypad are automatically saved.
Parameters are not automatically
saved when altered through the
fieldbus connection.

PARAMETER LISTINGS
Defaults
Group
10

Locks/ Range Description


Passwords

1004 Parameter Save Save



(continued)


1005 New Pass Code 0300000


1006 Set Point Lock


Off (Default)

On
Group
11

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Used for manually saving


Done Done Done
Done
parameters that have been
altered through the fieldbus
connection.
Sets new pass code for
0
0
0
0
parameter lock. Returns to 0
after saving.
Disables set point changes
Off
Off
Off
Off
from the keypad.
Local control allowed.
Local control allowed.

Start-Up
Range Description
Data

Done

Off

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

1101 Language
Selects the display language English English English English

English (AM) American English.

(Default)

Espaol
Spanish (full translation)

Francais
French (full translation)
1102 Application
Selects the application macro




Macro

Single Pump One AV regulating to a set point

(Default)

Synchronous Lag pumps start as needed and

all pumps regulate to the set

point at the same speed. Note:

it is recommended that all

pumps be identical.

Multicontrol
Lag pumps start as needed. The

last lag pump to start regulates

to the set point; the remaining

pumps operate at an enable

sequence speed (2203).

Constant Slave The master unit starts up to

three fixed speed slave units

when needed. See RO1, RO2

and RO3 settings (parameters

1801, 1804 and 1807).

Speed Control AV follows a speed reference

only. Pump protect fault

function is inactive.
1103 Application
No
Resets parameters to default

Restore
Yes
settings.

English

55

PARAMETER LISTINGS
Defaults
Group
11

Start-Up Range
Description
Data

1104 Motor Nom


11345V/

Voltage
230690V

1105 Motor Nom
0.2*I2hd

Current
2.0*I2hd

1106 Motor Nom Freq 10.0500Hz


1107 Motor Nom RPM 5018000

RPM

1108 Motor Nominal 0.22.0*Phd

Power

Defines the motor voltage.


230/ 230/ 230/ 230/ 230/
Equal to the value on the
460/ 460/
460/
460/
460/
motor nameplate.
575 575 575 575 575
Defines the motor current.
1.0* 1.0* 1.0* 1.0* 1.0*
Equal to the value on the
I2hd
I2hd
I2hd
I2hd
I2hd
motor nameplate.
Defines the motor nominal
60 60 60 60 60
frequency. Equal to the value
on the motor nameplate.
Defines the motor nominal
3550 3550 3550 3550 3550
speed. Equal to the value on
the motor nameplate.
Defines the motor power (hp). 1.0*Phd 1.0*Phd 1.0*Phd 1.0*Phd 1.0*Phd
Equal to the value on the
nameplate.

Group Start/Stop Range


Description
12
1201 Start/Stop







Keypad






Fieldbus
1202 Auto Restart



Off

On

1203 Test Run


Not Sel (default)

56

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Defines the connections and


Keypad Keypad Keypad Keypad Keypad
source of the start/stop
commands.
Comment - DI1= Enable. 0= Disable,
1 = Enable. DI2 = Low Water. 0 = Fault,
1 = OK, DI3 = Estop 0 = Estop, 1 = OK,
After Estop restart from keypad required.
Start/Stop from keypad. After a
fault reset, the drive will restart
only if auto restart (1202) is set
to on. If auto restart is off the
drive must be started from the
keypad.
Start via fieldbus control word
Selects whether the AV will
On On On On On
automatically restart after a
power failure or fault reset.
Not selected
Selected. The AV will automatically restart if conditions permit.
Selects when the drive will
Not Sel Not Sel Not Sel Not Sel Not Sel
perform a test run
Not selected

PARAMETER LISTINGS
Defaults
Group Start/Stop Range
Description
12
1203 Test Run
Automatic

(continued)





Manual






1204 Test Speed % (FL) 0...100%

1205 Test Run Delay
0...3600 Hr

1206 Motor Jog

1209 Manual
Disabled

Override
(Default)

1210 Override
0-60 Hz

Freq
Group
13

Group
14

If selected and the drive has not


run for the test delay (1205) the
drive will start and run at 50%
of maximum speed (1401) for
20 seconds and shutdown.
Auto Restart 1202 must be on.
Once manual is selected the
Not Sel Not Sel Not Sel Not Sel Not Sel
drive will start and run at test
speed (1204) for 20 seconds
and shutdown. Once the
manual test is complete this
parameter will return to
Not Sel.
Selects the speed the test runs
25% 25% 25% 25% 25%
at in manual test mode (1203).
Selects how long after the drive 1000 1000 1000 1000 1000
is idle before it will do a test run.
Jogs motor for 10 sec @ 60 RPM Disabled Disabled Disabled Disabled Disabled
to check for motor rotation.
Drive will run at constant speed
as set in Parameter 1210 when
enabled and contact DI5 is active.
Sets motor speed when manual
override is active.

Ramps/
Range Description
Windows

1301 Ramp 1 Fast Accel 01800 sec


1302 Ramp 2 Fast Decel 01800 sec
1303 Ramp 3 Slow Accel 01800 sec
1304 Ramp 4 Slow Decel 01800 sec
1305 Ramp Hysteresis 0100 %

1306 Reg Window
0100 %

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Defines the fast acceleration time.


5
Defines the fast deceleration time.
5
Defines the slow acceleration time.
60
Defines the slow deceleration time.
60
Per cent of window set aside
80
for hysteresis error.
Window around the set point
which the control algorithm
8
operates.

Spd Lim/
Range Description
Strt Lvl

1401 Maximum
Minimum

Frequency/Speed Frequency

60 Hz

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Defines the allowable maxi-


mum speed. Default setting
is parameter 1106 Motor Nom
Freq. (May want to show RPM
or HZ.)

5
5
60
60
80

5
5
60
60
80

5
5
60
60
80

5
5
60
60
80

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control
60

60

60

60

60

57

PARAMETER LISTINGS
Defaults
Group
14

Spd Lim/ Range


Description
Strt/Lvl

1402 Minimum
0Max

Frequency/Speed Frequency



1403 Config Speed

Min




0 (Default)




Min Freq



1404 Stp Delay
01800 s

Min Spd






1405 Restart Value
0150 %


















1406 Restart Delay
01800 s

58

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Defines the minimum speed


6
6
6
6
range. Default setting is 10% of
parameter 1106 Motor Nom
Freq. (May want to show RPM
or HZ.)
Defines the reaction of the drive 0
0
0
0
when the AV tries to regulate at
a speed at or below minimum
frequency (1402).
The drive will stay at Minimum
Frequency until Stp Delay Min
Spd (1404) times out; the unit
will then shutdown.
The AV will stay at this speed
until the transient clears or unit
is manually shutdown; unless a
fault occurs.
The time period the drive will
0
0
0
0
stay at MinSpd (1402) before
stopping. Functions when 1403
is set to 0. Becomes active if set
point would result in regulation
below min spd, closed valve
condition in pressure control
and Secondary Protect A&B.
If the drive is shutdown by
0 0 0 0
Config speed min (1403) due to
no system demand (pressure
control and level control only)
the drive will sleep until the
process actual value drops
below a set restart value (1405)
for longer than the restart delay
(1406). If operating in inverse
mode (2101) the drive will sleep
until the process variable rises
above the restart value. Wakeup level in % of set point value.
To disable the Restart Value
function in both normal and
inverse settings enter 0%.
Auto Restart (parameter 1202)
does not influence the restart
function. Default = 0.
Time delay for restart value
0
0
0
0
(1405).(Default = 0 sec)

PARAMETER LISTINGS
Defaults
Group
14

Spd Lim/ Range


Description
Strt/Lvl

1407 Priming Delay


06000 s












Group
15

When the drive is starting from


0 RPM this parameter delays
pump protection faults (2404
and 2407) for the setting time.
The default setting is 0. Once
the priming delay time is
complete the protection delay
(parameter 2406) becomes
functional. During the priming
delay the pump runs at the
maximum speed setting
(parameter 1401) since it
cannot achieve the set point.

Transducer
Range Description
Var

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control
0

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

1501 Transducer Unit


Selects the units (default is
Psig
Psig
Psig
Psig

pressure) for the primary process

transmitter feedback located at

AI2. In speed control macro

default unit is RPM.

%

GPM

Psig (Default)

Ft

F Deg

C Deg
1502 Transducer Max 06553.5
For single pump and multipump
300
300
300
300

macros this parameter defines

the full-scale feedback (20 mA

setting) of the primary process

transmitter at AI2. This parameter

also correlates to the maximum

value of Reference (set points) 1

and 2. For the Speed Control

macro this parameter scales the

maximum (20 mA or keypad )

speed setting. Note when units

are in Ft, M, In or Cm: AI2 Max

is always based on a specific

gravity = 1 regardless of setting

for parameter 1506. Actual

pressure signals in Ft, M, In or

Cm are corrected for specific

gravity by the firmware. Signal

can be quadratic or linear.

Psig

60

59

PARAMETER LISTINGS
Defaults
Group
15

Transducer Range
Description
Var

1503 Transducer Min 06553.5





















1506 Sensor Min

(Not in Software)


4 mA (Default)


Tuned Value





Tune








60

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

For single pump and multipump


0
0
0
0
macros this parameter defines
the value (normally zero) of the
4 mA setting for the primary
process transmitter at AI2. This
parameter also correlates to the
minimum value of Reference
(set points) 1 and 2. For the
Speed Control macro this
parameter scales the value
(normally zero) of the 4 mA or
keypad speed setting. Note
when units are in Ft, M, In or
Cm: AI2 Min is always based on
a specific gravity = 1 regardless
of setting for parameter 1506.
Actual pressure signals in Ft, M,
In or Cm are corrected for
specific gravity by the firmware.
Signal can be quadratic or linear.
Defines the value for analog
4 mA 4 mA
4 mA
4 mA
sensor input.
4 mA is selected as the
minimum value.
Select tuned value after the tune
function has been completed.
This will select the tuned value
for the minimum value of
sensor input.
This parameter sets the minimum value of the signal to be
applied to sensor input. When
tune is selected and enter is
pressed the tuned value for
sensor input is set to the actual
sensor input value when the
tune function was activated.
This function is useful for zeroing
out any system hysteresis.

4 mA

PARAMETER LISTINGS
Defaults
Group
16

Reference Range
Description
Select

1601 SP1/SP2 Select





Reference 1

(Default)

DI4



Fieldbus

1602 Set Point 1 Select


Keypad

(Default)

Analog Input

Speed Control

Fieldbus

1603 Set Point 2 Select


Keypad

(Default)

AI 1


Fieldbus

1604 AI 1 Minimum


0-10 VDC




4 20 mA

(Default)

Tuned Value


Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Defines the source from which Ref 1 Ref 1


Ref 1
Ref 1
Ref 1
the drive reads the signal that
selects the setpoint.
Reference 1 (set point 1) is
being used only.
Digital Input 4 selects set point 1
or set point 2. 0pen = Set Point
1, Closed = Set Point 2.
The set point is sent via Fieldbus
control word.
Selects the signal source for
Keypad Keypad Keypad Keypad Keypad
Reference1 (set point #1).
The set point is selected from
the keypad.
The set point is selected by an
analog input (AI1).
The set point is selected via
Fieldbus control word.
Selects the signal source for
Keypad Keypad Keypad Keypad Keypad
Reference1 (set point #2).
The set point is selected from
the keypad.
The set point is selected by an
analog input (AI1).
The set point is selected via
Fieldbus control word.
Defines the minimum value for 4-20 4-20 4-20 4-20 4-20
analog input AI1.
mA mA mA mA mA
A 0VDC signal will activate a
Sensor Failure fault function
unless 24.01 and 24.02 are
disabled.
4 mA is selected as the
minimum value.
Select tuned value after the tune
function has been completed.
This will select the tuned value
for the minimum value of AI1.

61

PARAMETER LISTINGS
Defaults
Group
16

Reference Range
Description
Select

1604 AI 1 Minimum
Tune

(continued)







Group
18

62

This parameter sets the minimum 4-20


4-20
4-20
4-20
value of the signal to be applied mA
mA
mA
mA
to AI1. When tune is selected
and enter is pressed the tuned
value for AI1 is set to the actual
AI1 value when the tune
function was activated. This
function is useful for zeroing
out any system hysteresis.

Relay
Range Description
Outputs

1801 Relay RO1



Output






Not Sel

Run


Ready (Default)



VFD Fault

Low Water








Pump Protect


Start Slave


Stand by

1802 RO1 ON Delay 0...3600 s

1803 RO1 OFF Delay 03600 s

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control
4-20
mA

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Selects the AV status to be


Ready Ready Ready
Start
indicated through relay output 1
Slave
(RO1). The relay energizes when
the status meets the setting.
Relay warnings are reset
automatically, faults must be
manually reset.
The output is not used
The output indicates the drive is
running.
The output indicates that power
is supplied to the drive and it is
awaiting a start command.
The drive has faulted
The secondary protection
warning or fault function has
been activated. DI4 is low for
the protection delay setting
(2404). Closed = normal,
Open = Secondary Protect fault
function is active.
The pump protection warning or
fault function has been activated.
Used in multipump macro to
start slave pump only.
Drive is in sleep mode due to no
system demand.
Defines the operation delay for
0
0
0
0
relay output RO1.
Defines the release delay for
0
0
0
0
relay output RO1.

Ready

0
0

PARAMETER LISTINGS
Defaults
Group
18

Relay Range Description


Outputs

1804 Relay RO2



Output






Not Sel

Run (Default)


VFD Fault

Low Water







Pump Protect


Start Slave


Stand by

1805 RO2 ON Delay 03600 s

1806 RO2 OFF Delay 03600 s

1807 Relay RO3

Output






Not Sel (default)

Run


Ready



VFD Fault

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Selects the AV status to be


Run-
Run-
Run-
Start
Runindicated through relay output 2 ning
ning
ning
Slave
ning
(RO2). The relay energizes when
the status meets the setting.
Relay warnings are reset
automatically, faults must be
manually reset.
The output is not used
The output indicates the drive
is running.
The drive has faulted
The secondary protection
warning or fault function has
been activated. DI4 is low for
the protection delay setting
(2404). Closed = normal,
Open = Secondary Protect fault
function is active.
The pump protection warning or
fault function has been activated.
Used in multipump macro to
start slave pump only.
Drive is in sleep mode due to
no system demand.
Defines the operation delay for
0
0
0
0
0
relay output RO2.
Defines the release delay for
0
0
0
0
0
relay output RO2.
Selects the AV status to be
Not
Not
Not
Not
Not
indicated through relay output 3 Used Used
Used
Used
Used
(RO3). The relay energizes when
the status meets the setting.
Relay warnings are reset
automatically, faults must be
manually reset.
The output is not used
The output indicates the drive is
running.
The output indicates that power
is supplied to the drive and it is
awaiting a start command.
The drive has faulted

63

PARAMETER LISTINGS
Defaults
Group
18

Relay Range Description


Outputs


Low Water







Pump Protect


Start Slave


Stand by

1808 RO3 ON Delay 03600 s

1809 RO3 OFF Delay 0 3600 s

Group
19

64

The secondary protection


warning or fault function has
been activated. DI4 is low for
the protection delay setting
(2404). Closed = normal,
Open = Secondary Protect fault
function is active.
The pump protection warning or
fault function has been activated.
Used in multipump macro to
start slave pump only.
Drive is in sleep mode due to
no system demand.
Defines the operation delay for
0
0
0
0
relay output RO3.
Defines the release delay for
0
0
0
0
relay output RO3.

Analog
Range Description
Outputs

1901 AO 1 Content Sel




Not Sel (default)

Frequency


Current


Torque


Power


Proc Var/

Actual


Energy Saving



1902 AO1 Content
Various

Min
1903 AO1 Content
Various

Max

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

0
0

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Connects a AV signal to analog Not


Not
Not
Not
output 1 (AO1).
Used Used
Used
Used
Not in use.
Output frequency. 20 mA =
motor nominal frequency (1106).
Output current. 20 mA =
motor nominal current (1105).
Motor torque. 20 mA = 100%
of motor nominal rating.
Motor Power. 20 mA = 100%
of motor power rating.
Actual value of process variable
AI2. 20 mA = Reference 1 Max
(1603).
Calculated energy savings
(option 1 or 2) over a conventional fixed speed system.
20 mA = Savings scale (2603).
Selects the minimum value of the
characterisitc being monitored.
Selects the maximum value of the 4
4
4
4
characteristic being monitored.

Not
Used

PARAMETER LISTINGS
Defaults
Group
19

Analog Range
Description
Outputs

1904 Minimum AO1 0.020.0 mA



1905 Maximum AO1 0.020.0 mA

1906 AO 2 Content Sel


Not Sel (default)

Frequency


Current


Torque


Power


Proc Var/

Actual


Energy Saving



1907 AO2 Content
Various

Min
1908 AO2 Content
Various

Max
1909 Minimum AO2 0.020.0 mA

1910 Maximum AO2 0.020.0 mA

Defines the minimum value of


0.1
0.1
0.1
0.1
AO1. Default = 4 mA.
Defines the maximum value of
20
20
20
20
AO1. Default = 20 mA.
Connects a AV signal to analog
Not
Not
Not
Not
output 2 (AO2).
Used Used
Used
Used
Not in use.
Output frequency. 20 mA =
motor nominal frequency (1106).
Output current. 20 mA =
motor nominal current (1105).
Motor torque. 20 mA = 100%
of motor nominal rating.
Motor Power. 20 mA = 100%
of motor power rating.
Actual value of process variable
AI2. 20 mA = Reference 1 Max
(1603).
Calculated energy savings
(option 1 or 2) over a conventional fixed speed system.
20 mA = Savings scale (2603).
Selects the minimum value of the
characterisitc being monitored.
Selects the maximum value of the
characteristic being monitored.
Defines the minimum value of
4
4
4
4
AO2. Default = 4 mA
Defines the maximum value of
20
20
20
20
AO2. Default = 20 mA

Group
Regulate Range
Description
21
2101 Regulation Mode


Normal

(Default)



Inverse


Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control
0.1
20
Not
Used

4
20

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Selects the type of AV control with Normal Normal Normal Normal Normal
falling process variable signal.
Increases the output speed with
falling process variable signal.
For level control applications the
tank is on the discharge side.
Decreases the output speed with
falling process variable signal.
For level control applications the
tank is on the suction side.

65

PARAMETER LISTINGS
Defaults
Group
Regulate Range
Description
21
2102 Press Incr Speed 060 Hz





2103 Press Incr
0.10000








Group
22

Multipump
Range Description
Control

2201 Value Decrease 01000






2202 Value Increase 0.1000







2203 Enable Sequence 0 60 Hz





2204 Switch Lead Lag 1100 h





66

Sets the speed for which


additional pressure is added to
compensate for system frictional
losses at increased flow. Used for
single pump and backup modes
only. Default = 20 Hz.
The pressure increase in selected
units point which is added to the
set point pressure to compensate
for frictional losses at the pressure
increase speed. Used for single
pump and backup modes only.
Note the full set point pressure
increase (%) is achieved at
maximum speed (1401).

Defines how much the actual


can drop before the next lag
pump is started. Used for
multicontrol, synchronous
control and slave modes only.
Defines the increase in set point
when a lag pump starts. This
value is cumulative with each
lag pump that turns on. Used
for multicontrol, synchronous
control and slave modes only.
The default setting for 2202 is
equal to the value set in 2201.
Defines the speed the drive
must be at before multipump
operation is allowed.. Applies to
synchronous, multicontrol and
slave modes only. Default =
98% of 1401 Maximum Speed.
Defines the time the lead unit
will run before a new unit is
deemed the lead unit. Note if
set to 1001 (Not SEL) the
switching function is disabled
(including switching during a
fault). Default setting is 48 hrs.

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control
20 20 20 20 20

0 0 0 0 0

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control
5

59

59

59

59

59

48

48

48

48

48

PARAMETER LISTINGS
Defaults
Group
22

Multipump Range
Description
Control

2205 Sync Limit


060 Hz




2206 Sync Window
060 Hz







2207 Pump Address 14

2208 Setp2 Source
OFF, 14


Group
24

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Selects the speed at which lag


pump #1 (or slave #1 RO1)
should be turned off. Applies to
synchronous, multicontrol and
slave modes.
The speed step above the sync
limit (2206) used to turn off lag
pump #2 (or slave #2 RO2).
Twice the Sync Window is the
speed step at which lag pump
#3 (or slave #3 RO3) is turned
off. Used for synchronous and
slave modes only.
Defines the pump address for
1
multipump systems.
Defines which pump has the
Off
analog input connected for
second set point.

Fault
Range Description
Functions

45

45

45

Off

Off

Off

Off

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

2401 Keypad Failure


Selects how the AV will react to

a keypad communication break.

Disabled
Protection is inactive

Fault
The drive trips on fault and

the motor coasts to a stop.

A fault message is generated

Panel Loss.
2402 Pump Protect
Fault
Actual process value is lower
Dis-
Dis-
Dis-
Dis-

Ctrl
than protection limit (2403) for abled abled abled
abled

protection delay (2404) and AV

is at max speed for the

protection delay.

Disabled
Protection is disabled.

(Default)

Warning
The AV generates a warning

only Pump Protect; no other

action is taken.

Warn and
The AV generates a warning

Control
Pump Protect and controls

according to the setting of

Config Speed Min (1403).

Disabled

67

PARAMETER LISTINGS
Defaults
Group
24

Fault Range Description


Functions

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

2403 Protection Limit 06553.5


This is the protection limit in PSI 0
0
0
0

for the process value at which

Pump Protect Ctrl (2402)

activates when pump is at max

speed for the protection delay.
2404 Protection Delay 0200 s
This is the protection delay
0
0
0
0

period prior to activation of

Pump Protect Ctrl (2402).

Default setting is 0 sec.
2405 Low Water
Loss of digital input 2 (DI2) for
Dis-
Dis-
Dis-
Dis-

protection delay (2404).
abled abled abled
abled

Disabled
Protection is disabled.

(Default)

Warn
The AV generates a warning

only Secondary Protect A; no

other action is taken.

Warn and
Parameter 1202 Auto Restart

Control
must be set to On to

automatically restart once fault

has been reset.
2406 Error Reset
09999
Indicates number of fault resets. 0
0
0
0

Note parameter 1202 Auto

Restart must be set to on.

When set to 0 Error Reset is

disabled. Time between resets is

parameter 2407 Reset Delay.

Manual intervention is required

if fault is still active after set

number of resets has been

achieved. The drive reaction to

the fault will be according to

parameter 1405 Config Speed

Min setting. Reset is applicable

to parameters 2404 and 2405.
2407 Reset Delay
1250 s
Defines the time that the AV will 60 s
60
60
60

wait after an alarm and control

condition before attempting an

error reset.
2408 Run Enable
DI1 has to be closed for drive to

be able to run.

Disable
Run Enable is not in use

Enable
DI1 is used for Run Enable

Function.

68

Disabled

60

PARAMETER LISTINGS
Defaults
Group
24

Fault Range Description


Functions

2409 Comm Fault



Function




Not Selected

Fault

Last Speed


2410 Comm Fault
060.0s

Time

Group
25

Group
26

Selects how the drive reacts in a Last


Last
Last
Last
fieldbus comm break i.e.; if the Speed Speed Speed Speed
drive fails to receive command
word or reference. The time delays is given by parameter 2410.
No response
Drive Faults and coasts to stop
Drive displays a warning and
remains running at last speed
reference.
Defines the time delay for the
3.0 s
3
3
3
control word or reference
supervision.

Automatic
Range Description
Reset

2501 NR of Trials
05



2502 Trial Time
1.0600.0 s


2503 Delay Time
0.0120.0 s


2504 AR Overcurrent

Disable
2505 AR Overvoltage

Disable
2506 AR Undervoltage

Disable
2507 AR AI<Min

Disable

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control
Last
Speed

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Sets the number of allowed


0
0
0
0
0
automatic resets within a trial
period defined by parameter
2502.
Sets the time limit used for
30 s
30 s
30 s
30 s
30 s
counting and limiting the
number of resets.
Sets the delay between fault
0 s
0 s
0 s
0 s
0s
detection and attempted drive
restart.
Auto reset after overcurrent
Enabled Enabled Enabled Enabled Enabled
fault.
Auto reset of overvoltage
Enabled Enabled Enabled Enabled Enabled
fault.
Auto reset for undervoltage
Enabled Enabled Enabled Enabled Enabled
of drive.
Auto reset after transducer
Enabled Enabled Enabled Enabled Enabled
signal loss.

Energy
Range Description
Savings

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

2601 Energy Cost


0.0001.000 Cost of energy in USD
2602 Baseline Power 01000 hp
Baseline HP for a conventional

fixed speed system.
2603 Savings Scale
065535
This parameter scales the
10000 10000 10000 10000 10000

analog output when energy

savings is selected.
2604 Energy Save
Savings Savings Savings Savings Savings

Methd
Savings Op 1
Op 1 Op 1
Op 1
Op 1
Op 1

Savings Op 2

69

PARAMETER LISTINGS
Defaults
Group
26

Energy Range
Description
Savings

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

2605 Energy Save


Resets energy savings counter. Dis-
Dis-
Dis-
Dis-
Dis
Reset
After resetting, parameter 2605 abled abled abled abled abled

returns to disabled.

Disabled

Reset
Group
30

Option
Range Description
Modules

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

3001 Comm Protocol


Activates the optional external
No
No
No
No

Select
DCS and selects the interface.

Refer to the ABB IOM chapter

on fieldbus control. Can be used

only with Single Pump, Constant

Slave or Speed Control modes.

Not Selected No fieldbus communication.
Aquavar Aquavar

(Default)

Std Modbus
Drive uses Modbus protocol on

the standard RS485 port.

Protocol settings are in group 32.

Ext Fba
The drive communicates with a

fieldbus adapter module in

option slot 2 of the drive. Note

when Ext Fba is selected Param
eter Groups 31 is unlocked.

Aquavar
This protocol is used for

communication between the

drives in the Synchronous and

Multicontrol macros.
Group
31

Fieldbus
Range Description
Setup

3101 FBA Type








3102- FBA Parameters
3133

70

No

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

This parameter configures the


module type automatically by
the fieldbus adapter. No action
is required by the user unless
changes to default settings are
desired. Refer to the fieldbus
manual.
Meaning and values of these
parameters depend on the
fieldbus option connected to
the drive.

PARAMETER LISTINGS
Defaults
Group
32

Modbus Range
Description
Setup

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

3201 Protocol ID
00xFFFF
This parameter configures the

module type automatically by

the fieldbus adapter. No action

is required by the user unless

changes to default settings are

desired. Refer to the fieldbus

manual.
3202 Station ID
0...247
1
1
1
1
1
3203 Baud Rate
1.257.6
9.6
9.6
9.6
9.6
9.6

kbits/s
kbits/s kbits/s kbits/s kbits/s kbits/s
3204 Parity
Defines the data length, parity 8N2
8N2
8N2
8N2
8N2

and stop bits.

8N1
8 data bits, no parity and one

stop bit

8N2
8 data bits, no parity and two

stop bits

8E1
8 data bits, even parity and one

stop bit.

8O1

8 data bits, odd parity and one


stop bit.

3205 Control

Profile

ABB Drives


AV
3206 OK Messages
065535

3207 CRC Errors
3208 EFBUART Errors
3209 EFB Status


Idle


Exec. Init

Time Out


Config Error

Off-line


On-Line


Reset


Listen Only

Selects the communication


ABB
ABB
ABB
ABB
profile.
Drives Drives Drives
Drives
ABB Drives control word and
Status Word.
Alternate Profile.
Read only counter of good
Modbus messages.
Read only counter of CRC errors.
Read only counter of UART errors.
Contains the status of Modbus
protocol.
Drive is configured for Modbus,
but not receiving any messages.
Drive is initializing Modbus.
A time-out has occurred .
Drive has configuration error.
Drive is receiving messages that
are NOT addressed to itself.
Drive is receiving messages that
are addressed to itself.
Drive is performing hardware
reset.
Drive is in listen only mode.

ABB
Drives

71

PARAMETER LISTINGS
Defaults
Group
32

Modbus Range
Description
Setup

3210- EFB Parameters


3220

Group
50

Meaning and values of these


parameters depend on the
selected fieldbus protocol.

Motor
Range Description
Control

5001 Switching Freq 4, 8, 12 kHz


Sets the switching frequency


for the drive.

Group Maintenance
Range Description
51
Triggers
5101 Cooling Fan Trig 0.06553.5

kh

5102 Cooling Fan Act 0.06553.5

kh


5103 Revolution Trig
065535

MRev

5104 Revolution Act
065535

MRev


5105 Run Time Trig
0.06553.5

kh

5106 Run Time Act

72

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control
4 4 4 4 4
kHz kHz kHz kHz kHz
Single Synch- Multi- Constant Speed
Pump ronous Control Slave Control

Sets the trigger point for the


20
20
20
20
drives cooling fan counter.
0.0 = disabled
Defines the actual value of the
drives cooling fan counter. The
parameter is reset by writing
0.0 to it.
Sets the trigger point for the
32000 32000 32000
32000
motors accumulated revolutions
counter. 0.0 = disabled
Defines the actual value of the
motors accumulated revolutions
counter. The parameter is reset
by writing 0 to it.
Sets the trigger point for the
40
40
40
40
drives run time counter.
0.0 = disabled
Displays actual run time.

Group Information
Range Description
99
9901 FW Version
AXXX hex

9902 Drive Rating
XXXY










Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

Version of the firmware loaded


to the AV.
Indicates the drives current and
voltage rating. The format is
XXXY, where:
XXX = The nominal current
rating in amps. If present an A
indicates the decimal point in
the rating for the current.
Y = The voltage rating of the
drive, where Y=2 indicates a
208240 Volt rating and Y=4
indicates a 380480 Volt
rating.

20

32000

40

Single Synch- Multi- Constant Speed


Pump ronous Control Slave Control

PROGRAMMING
Single Pump Programming (Pressure transducer)
REM

Standard view of display in REM (remote) mode. You will see


the reference pressure (REF PRESSURE), actual pressure (ACT
PRESSURE) and motor frequency in HZ.

0.0%

40.2 PSI sp
0.0 PSI ac
0.0 HZ
DIR

MENU

RECOMMENDED INSTALLATION LAYOUT


1

SUPPLY POWER
U1
V1
W1
ND

5
AIR
6
U2

V2

W
3 PHASE OUTPUT
ND

TO MOTOR

9
SUCTION

FLOW

3
1
2
3
4
5

AQUAVAR CPC
FUSIBLE DISCONNECT
CENTRIFUGAL PUMP
CHECK VALVE (NON-SLAM TYPE)
PRESSURE TRANSDUCER (CABLE ASSEMBLY)

6
7
8
9

AIR BLADDER TANK


3 PHASE MOTOR
GATE VALVE (BALL VALVE)
PRESSURE GAUGE

NOTES: A. Use of load filter (reactor) should be used between the Aquavar and motor, if motor leads exceed
60 wire feet.
B. If single phase power is supplied on 200 - 240 volt three phase units, use U1 and W1 as input terminals
from single phase supply, and de-rate unit by 50% of three phase rating.
C. Tank size should be 10-20% (total volume) of flow in system. Pre-charge tank 10-15 PSI below system
pressure.

73

PROGRAMMING
Single Pump Programming (Pressure transducer)
Programming Step(s)
1. Access the main menu on the keypad. Press the MENU key
once and the display will show (PARAMETERS, WIZARDS,
CHANGED PAR). Using the arrow keys, highlight the
parameters option, then press the ENTER key .

REM

MAIN MENU

PARAMETERS
WIZARDS
CHANGED PAR
EXIT

2. Once the parameters option has been chosen, the


parameter groups will be displayed. Each group will be
numbered (see parameter groups list on page 50 for
detailed information). Use the arrow keys to highlight the
parameter group 10, LOCKS/PASSWORDS, then press the
SEL key.
3. Use the arrow keys to highlight group 1002 PASSCODE,
then press the EDIT key. Enter your factory password
number (Default is 66). Press the save key.

REM

ENTER

PAR GROUPS

01 VFD SIGNALS
02 PUMP SIGNALS
03 FB ACTUAL SIGNALS
10 LOCKS/PASSWORDS
11 START-UP DATA
EXIT

REM

10

SEL

PARAMETERS

1001 PARAMETER LOCK


1002 PASS CODE
0
1003 LOCAL LOCK
1004 PARAM SAVE
EXIT

4. Use up arrow to group 1001 PARAMETER LOCK, then


press the EDIT key. Next, use the up arrow to select OPEN,
then press the SAVE key. This group should appear as
OPEN, if it does not you have entered the pass code
incorrectly, or it has changed. Contact your local CentriPro
representative for the master code. Once your group 1001
is showing OPEN, you can access all of the pump and
drive parameters in the Aquavar.

REM

5. After the SAVE key is pressed in the above group, press


the EXIT key, then the down arrow to highlight the group
11 START UP DATA, then Press the SEL key once. Using
the arrows, highlight 1102 APPLIC MACRO, then press
the EDIT key. Default is set for SINGLE PUMP. Change
this group whether your system is Single Pump, MultiPump, Slave Pump etc. To exit press CANCEL, to save this
parameter, press the SAVE key once.

REM

6. Use down arrow until group parameter 1104 MOTOR


NOM VOLTAGE is highlighted, then press EDIT. Use the
arrows to enter your motors nameplate voltage, then press
the SAVE key.

REM

EDIT

PARAMETERS

1001 PARAMETER LOCK


OPEN
1002 PASS CODE
1003 LOCAL LOCK
1004 PARAM SAVE
EXIT

EDIT

PARAMETERS

1101 LANGUAGE
1102 APPLIC MACRO
SINGLE PUMP
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
EXIT

EDIT

PARAMETERS

1101 LANGUAGE
1102 APPLIC MACRO
1104 MOTOR NOM VOLT
230V
1105 MOTOR NOM CURR
EXIT

74

EDIT

PROGRAMMING
Single Pump Programming (Pressure transducer)
7. Use the down arrow until group parameter 1105 MOTOR
NOM CURRENT is highlighted, then press EDIT. Using
arrows, enter your motors maximum allowed amp draw at
speed, or Service Factor Amps. NOTE: Enter motors service
factor from nameplate or motor manual. Once you have
entered the amps, press the SAVE key.

REM

8. Use down arrow until you highlight group parameter 1107


MOTOR NOM RPM, then press the EDIT key. Use arrows
to enter the RPM from the motor nameplate, default is 3550
RPM. Press the SAVE key to store setting.

REM

PARAMETERS

the
1101 LANGUAGE
1102 APPLIC MACRO
full
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
3.4A
EXIT

EDIT

PARAMETERS

1104 MOTOR NOM VOLT


1105 MOTOR NOM CURR
1106 MOTOR NOM FREQ
1107 MOTOR NOM RPM
3550 RPM
EXIT

9. Use down arrow until you highlight group parameter 1108


MOTOR NOM POW, then press the EDIT key. Use arrows to
enter the motors Horsepower rating from nameplate, then
press the SAVE key.

REM

EDIT

PARAMETERS

1105 MOTOR NOM CURR


1106 MOTOR NOM FREQ
1107 MOTOR NOM RPM
1108 MOTOR NOM POW
1.0 HP
EXIT

10. Once you have saved parameter 1108, use the down
arrow until you highlight group parameter 1201 START/
STOP, then press EDIT. Default is KEYPAD. This parameter
determines how the operator will control the Aquavar; via
the keypad or via MODBUS communication. If no changes
are required, press the CANCEL key then EXIT and go to the
next step.

REM

EDIT

PARAMETERS

1111 MOTOR ID RUN


1201 START/STOP KEYPAD
1202 AUTO RESTART
1203 TEST RUN
EXIT

EDIT

11. From group 12, press the down arrow until group 14 SPD
REM
PARAMETERS
LIM/STRT LVL is highlighted, then press EDIT. Use down
1401 MAXIMUM FREQ
1402 MINIMUM FREQ
arrows to highlight group 1402 MINIMUM FREQ, then
30.0 HZ
press EDIT. Using the arrow keys select the appropriate
1403 CONFIG SPEED MIN
minimum speed in HZ. Default is 10% of the parameter
1404 STP DELY MIN SPD
EXIT
EDIT
1106 MOTOR NOM FREQ which is 6 HZ. For a submersible
motor or suction lift situation, this would be set to at least
30 HZ. For a positive suction booster system, leave at the default setting. Once changed,
press the SAVE key to store the setting.

75

PROGRAMMING
Single Pump Programming (Pressure transducer)
12. From group 1402, press the down arrow until group 1502
TRANSDUCER MAX is highlighted, then press EDIT. Default
pressure transducer setting is 300 psi. Adjust this based on
your maximum rating for a new transducer. NOTE: CentriPro
provides a 0 -300 psi transducer as standard. Select the
appropriate range, then press SAVE. If no changes are
necessary, press CANCEL.

REM

PARAMETERS

1410 UNDERVOLT CTRL


1411 PRIMING DELAY
1501 TRANSDUCER UNIT
1502 TRANSDUCER MAX
300.0
EXIT

EDIT

13. Use the down arrow to highlight 1503 TRANSDUCER MIN


0.0 , then press EDIT. Default should be 0 psi. Press CANCEL
to advance to the next step. If this group needs to be
changed based on another type of transducer value, press
SAVE to store.

REM

15
16
18
19
21

XDUCER VARIABLES
REFERENCE SELECT
RELAY OUTPUTS
ANALOG OUTPUTS
REGULATE

14. Use the down arrow to highlight 1506 SENSOR MIN,


then press EDIT. Use the up arrow until the TUNE value is
displayed, press the SAVE key. This provides the transducer
a tune value of 0 (ZERO) psi. NOTE: Make sure that your
transducer is wired to the Aquavar but free from any
pressure in the system. The transducer must be exposed to
0 psi only when this step is performed. Press the SAVE key to
tune your transducer.

REM

PARAMETERS

REM

4 mA

15. Final step is to enter your required pressure in


the system. After above programming has been
completed, press the EXIT key three (3) times, until
you arrive back to the first control display screen.
Then press the UP or DOWN arrow to select the
required system pressure. Once pressure has
been selected, press the green START key on the
keypad.

15

SEL

1504 SENSOR
1505 K-DP FLOW METER
1506 SENSOR MIN
4 mA
EXIT

EDIT

PAR EDIT

1506 SENSOR MIN

1506 SENSOR MIN


CANCEL

EXIT

REM

PAR EDIT

PAR GROUPS

TUNED VALUE

SAVE

CANCEL

SAVE

Status
LED

REM

UP
SOFT
KEY 1

DIR

40.2 PSI sp
0.0 PSI ac
0.0 HZ

11.1%

MENU

SOFT
KEY 2

DOWN
LOC
REM

76

LOC/REM

HELP

STOP

START

PROGRAMMING
Single Pump Programming (Pressure transducer)
16. Optional Step: To lock out access to the control panel (keypad), refer to page 109. This
will prevent unauthorized users from changing programming.
NOTE: If an error or fault occurs, refer to the troubleshooting/faults section of this
manual, page 116. When troubleshooting an Aquavar system, always break down into the
following components:
1. Aquavar programming check default settings recommended for single pump, multipump, slave pump etc.
2. Electrical supply/ motor/ wiring/grounding check your supply voltage, motor
wiring, transducer wiring, and grounding.
3. Mechanical/Pump/ Rotation check your pump rotation, rubbing or other mechanical
problems. Pump run out.
4. Hydraulic System/ Piping check to ensure proper suction and discharge piping
layout, proper NPSHa, air entrainment, vortex, friction loss, system curve compensation
etc.
5. Environment protect from high temperatures, direct sun, freezing temperatures, high
altitude, dust, vibration, lack of air flow.

77

PROGRAMMING
Single Pump Submersible Pump Constant Pressure

SINGLE PUMP SUBMERSIBLE


CONSTANT PRESSURE LAYOUT
1

6
U1
V1
W1
GND

U2
V2
W2
GND

U2
V2
W2
GND

4
5

8
FLOW

1
2
3
4
5
6
7
8
9
10

78

AQUAVAR CPC
FUSIBLE DISCONNECT
LOAD REACTOR
AIR DIAPHRAGM TANK
PRESSURE TRANSDUCER
3 PHASE OUTPUT (ALWAYS)
DISCHARGE CHECK VALVE
GATE VALVE (HIGHLY RECOMMENDED)
SUBMERSIBLE PUMP END
SUBMERSIBLE MOTOR (3 PHASE)

10

PROGRAMMING
Single Pump Submersible Pump Constant Pressure
It is possible to utilize the Aquavar Centrifugal Pump Controller on commercial/industrial
well and submersible turbine applications. Submersible pumps and motors require specific
installation, programming and pipe layout compared to above ground booster pump
systems. However, specific programming must be followed to meet minimum requirements
set forth by the motor manufacturer (i.e. Franklin Electric). Always consult with the appropriate
motor technical manual for motor compatibility and requirements when using a Variable
Frequency type drives.
NOTE: THE AQUAVAR IS NOT RECOMMENDED FOR RESIDENTIAL WELL APPLICATIONS.
CONSULT CENTRIPRO FOR SUITABLE VARIABLE SPEED CONTROLLERS DESIGNED FOR
RESIDENTIAL WELL PUMPS (e.g. BF15 series).
Service Factor Amps
The submersible pump will sometimes utilize the motor service factor or MAX AMPS.
Therefore, during peak use times, it is recommended to select the appropriate Aquavar based
on the MOTOR MAXIMUM AMPS or service factor amps. Normally, this can be found on
the motor nameplate or the AIM (application, installation manual). This will avoid nuisance
tripping or current overload by the Aquavar. The Aquavar is designed to protect the motor on
overcurrent! Compare the motor max amps with the list of Aquavar models.
NOTE: ALL MOTORS MUST BE THREE PHASE.
Minimum Frequency
Submersible pump motors require a minimum speed or frequency to operate properly.
Because submersible motors use the water to lubricate and cool, they require this minimum
frequency when controlled by a Variable Speed Drive. Franklin has suggested that the
Minimum Frequency is set to at least 30 HZ in the Aquavar. Therefore, it is recommended
to set the Aquavar Minimum Frequency to 30 to 35 HZ (depending on static head) in
programming group 1402. See programming section.
WARNING: FAILURE TO SET THE MINIMUM FREQUENCY FOR SUBMERSIBLE
TURBINE INSTALLATION COULD RESULT IN DAMAGE TO THE PUMP AND/OR
MOTOR.
Tank Sizing
An appropriate size diaphragm tank must be sized for smooth operation. The tank will also
provide a needed compressability at zero flow. A tank with approximately 20% of total system
volume in GPM would be recommended.

79

PROGRAMMING
Single Pump Submersible Pump Constant Pressure
Load Reactor (Filter)
A Load reactor or load filter is an electrical device that provides protection to the motor
windings from a specific variable speed drive. Motors are more susceptible to voltage
spikes and switching frequencies found in IGBT type drives, especially when the motor leads
exceed 50 ft. Therefore, a load reactor is required when all of the following conditions are met
for ANY type of AC induction motor (above ground or submersible type):
1. Motor cable length from the Aquavar to the motor is more than 50 wire feet.
2. Drive uses IGBT type of switching (which is industry standard and is used by the Aquavar).
If all of the conditions are present above, then it is recommended to wire a LOAD REACTOR
between the Aquavar output (U2, V2, W2) and the motor. Keep the load reactor as close to
the output of the Aquavar for best results. NOTE: See suggested layout drawing and always
refer to your specific motor manufacturers recommendation for VFDs.
Grounding
NOTE: Always follow local codes for wiring and grounding or refer to the National
Electrical Codes.
Submersible installations are susceptible to stray voltage or grounding problems. It is
recommended to ground the transducer shield to the chassis of the Aquavar cabinet and to
check with a meter for any stray voltage from the three phase motor. Each component of the
electrical Aquavar system should have the same grounding point or reference. Always follow
the submersible motor manufacturers recommended installation procedures.
NOTES:
Motors used must be three phase, equal to input voltage.
Standard enclosure is rated for NEMA 1 INDOOR USE ONLY. Consult Factory/ Price
pages for outdoor rated enclosures.
Aquavar CPC not for use on RESIDENTIAL WELL PUMP applications. Consult with factory
for appropriate variable speed controller like the BF15.
Input voltage for the Aquavar can be single phase. Use the U1 , W1 and Ground
connections, and derate the drive by 50% from the three phase rating. Example: 230 volt,
three phase 10 HP Aquavar becomes a 5 HP, 230 volt, single phase rated drive.

80

PROGRAMMING
Single Pump Submersible Pump Constant Pressure
Each component of the electrical Aquavar system should have the same grounding point or
reference.
Programming Step(s)
Standard view of the display in REM (remote) mode. You will see
the reference pressure (REF PRESSURE), actual pressure (ACT
PRESSURE) and motor frequency in HZ.

1. Access the main menu on the keypad. Press the MENU key
once and the display will show (PARAMETERS, WIZARDS,
CHANGED PAR). Using the arrow keys, highlight the
parameters option, then press the ENTER key.

REM

0.0%

40.2 PSI sp
0.0 PSI ac
0.0 HZ
DIR
REM

MENU
MAIN MENU

PARAMETERS
WIZARDS
CHANGED PAR
EXIT

2. Once the parameters option has been chosen, the


parameter groups will be displayed. Each group will be
numbered (see parameter groups list on page 51 for
detailed information). Use the arrow keys to highlight the
parameter group 10, LOCKS/PASSWORDS, then press the
SEL key.

REM

3. Use the arrow keys to highlight group 1002 PASSCODE,


then press the EDIT key. Using the up arrow, enter your
factory password number (Default is 66). Press the save key.

REM

ENTER

PAR GROUPS

01 VFD SIGNALS
02 PUMP SIGNALS
03 FB ACTUAL SIGNALS
10 LOCKS/PASSWORDS
11 START-UP DATA
EXIT

10

SEL

PARAMETERS

1001 PARAMETER LOCK


1002 PASS CODE
0
1003 LOCAL LOCK
1004 PARAM SAVE
EXIT

4. Use up arrow to group 1001 PARAMETER LOCK, then


press the EDIT key. Next, use the up arrow to select OPEN,
then press the SAVE key. This group should appear as
OPEN, if it does not you have entered the pass code
incorrectly, or it has changed. Contact your local CentriPro
representative for the master code. Once your group 1001
is showing OPEN, you can access the entire pump and
drive parameters in the Aquavar.

REM

5. After the SAVE key is pressed in the above group, press the
EXIT key, then the down arrow to highlight the group 11
START UP DATA, then Press the SEL key once. Using the
arrows, highlight 1102 APPLIC MACRO, then press the
EDIT key. Default is set for SINGLE PUMP. Change this group
whether your system is Single Pump, Multi-Pump, Slave
Pump etc. To exit press CANCEL, to save this parameter,
press the SAVE key once.

REM

EDIT

PARAMETERS

1001 PARAMETER LOCK


OPEN
1002 PASS CODE
1003 LOCAL LOCK
1004 PARAM SAVE
EXIT

EDIT

PARAMETERS

1101 LANGUAGE
1102 APPLIC MACRO
SINGLE PUMP
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
EXIT

EDIT

81

PROGRAMMING
Single Pump Submersible Pump Constant Pressure
6. Use down arrow until group parameter 1104 MOTOR NOM REM
PARAMETERS
VOLTAGE is highlighted, then press EDIT. Use the arrows to 1101 LANGUAGE
1102 APPLIC MACRO
enter your motors nameplate voltage, then press the SAVE
1104 MOTOR NOM VOLT
key.
230V
1105 MOTOR NOM CURR
EXIT

EDIT

7. Use the down arrow until group parameter 1105 MOTOR


REM
PARAMETERS
1101 LANGUAGE
NOM CURRENT is highlighted, then press EDIT. Using the
arrows, enter your motors maximum allowed amp draw at 1102 APPLIC MACRO
full
1104 MOTOR NOM VOLT
speed, or Service Factor Amps. NOTE: Enter motor service
1105 MOTOR NOM CURR
3.4A
factor from nameplate or motor manual. Once you have
E
X
I
T
EDIT
entered the amps, press the SAVE key.
8. Use down arrow until you highlight group parameter 1107
MOTOR NOM RPM, then press the EDIT key. Use arrows
to enter the RPM from the motor nameplate, default is 3550
RPM. Press the SAVE key to store setting.

REM

PARAMETERS

1104 MOTOR NOM VOLT


1105 MOTOR NOM CURR
1106 MOTOR NOM FREQ
1107 MOTOR NOM RPM
3550 RPM
EXIT

9. Use down arrow until you highlight group parameter 1108


MOTOR NOM POW, then press the EDIT key. Use arrows to
enter the motors Horsepower rating from nameplate, then
press the SAVE key.

REM

EDIT

PARAMETERS

1105 MOTOR NOM CURR


1106 MOTOR NOM FREQ
1107 MOTOR NOM RPM
1108 MOTOR NOM POW
1.0 HP
EXIT

EDIT

10. Once you have saved parameter 1108, use the down
REM
PARAMETERS
arrow until you highlight group parameter 1201 START/
1111 MOTOR ID RUN
STOP, then press EDIT. Default is KEYPAD. This parameter 1201 START/STOP KEYPAD
1202 AUTO RESTART
determines how the operator will control the Aquavar; via
1203 TEST RUN
the keypad or via MODBUS communication. If no changes
EXIT
EDIT
are required, press the CANCEL key then EXIT and go to the
next step.
11. From group 12, press the down arrow until group 14 SPD
REM
PARAMETERS
LIM/STRT LVL is highlighted, and then press SEL. Use down 1401 MAXIMUM FREQ
1402 MINIMUM FREQ
arrows to highlight group 1402 MINIMUM FREQ, then
30.0 HZ
press EDIT. Using the arrow keys select the appropriate
1403 CONFIG SPEED MIN
minimum speed in HZ. Default is 10% of the parameter 1106 1404 STP DELY MIN SPD
EXIT
EDIT
MOTOR NOM FREQ which is 6 HZ. For a submersible motor
or suction lift situation, this would be set to at least 30 HZ.
Depending upon the static water level, and pipe distance to the transducer, you may have
to increase this setting up to 40HZ. Once changed, press the SAVE key to store the setting.
82

PROGRAMMING
Single Pump Submersible Pump Constant Pressure
12. Next step will set the appropriate time delay in seconds at
the MINIMUM FREQUENCY. Use the down arrow until you
highlight parameter 1404 STP DELY MIN SPD, and then
press the EDIT key. Use the UP ARROW to select a time in
seconds. A suggested delay time is 5 seconds. When the
pump reaches the minimum frequency, it will have a delay
of 5 seconds before shutting down. Once entered, then
press the SAVE key.

REM

PARAMETERS

1401 MAXIMUM FREQ


1402 MINIMUM FREQ
1403 CONFIG SPEED MIN
1404 STP DELY MIN SPD
5s
EXIT

EDIT

13. From group 1404, press the down arrow until group 1502
REM
PARAMETERS
TRANSDUCER MAX is highlighted, then press EDIT. Default
1410 UNDERVOLT CTRL
1411 PRIMING DELAY
pressure transducer setting is 300 psi. Adjust this based on
1501 TRANSDUCER UNIT
your maximum rating for a new transducer. NOTE: CentriPro 1502 TRANSDUCER MAX
300.0
provides a 0 -300 psi transducer as standard. Select the
E
X
I
T
EDIT
appropriate range, then press SAVE. If no changes are
necessary, press CANCEL.
14. Use the down arrow to highlight 1503 TRANSDUCER MIN
0.0 , then press EDIT. Default should be 0 psi. Press CANCEL
to advance to the next step. If this group needs to be
changed based on another type of transducer valve, press
SAVE to store.

REM

15. Use the down arrow to highlight 1506 SENSOR MIN,


then press EDIT. Use the up arrow until the TUNE value is
displayed, press the SAVE key. This provides the transducer
a tune value of 0 (ZERO) psi.

REM

15
16
18
19
21

PAR GROUPS

XDUCER VARIABLES
REFERENCE SELECT
RELAY OUTPUTS
ANALOG OUTPUTS
REGULATE

EXIT

SEL

PARAMETERS

1504 SENSOR
1505 K-DP FLOW METER
1506 SENSOR MIN
4 mA
EXIT

NOTE: Make sure that your transducer is wired to the


Aquavar but free from any pressure in the system. The
transducer must be exposed to 0 psi when this step is
performed. Press the SAVE key to tune your transducer.

15

REM

EDIT

PAR EDIT

1506 SENSOR MIN

TUNED VALUE

CANCEL

SAVE

83

PROGRAMMING
Single Pump Submersible Pump Constant Pressure
16. Final step is to enter your required pressure in
the system. After above programming has been
completed, press the EXIT key three (3) times, until
you arrive back to the first control display screen.
Then press the UP or DOWN arrow to select the
required system pressure. Once pressure has been
selected, press the green START key on the keypad.

Status
LED

REM

UP
SOFT
KEY 1

DIR

40.2 PSI sp
0.0 PSI ac
0.0 HZ

11.1%

MENU

SOFT
KEY 2

DOWN
LOC
REM

LOC/REM

HELP

STOP

START

17. Optional Step: To lock out access to the control panel (keypad), refer to page 109. This
will prevent unauthorized users from changing programming.
NOTE: If an error or fault occurs, refer to the troubleshooting/faults section of this
manual, page 116. When troubleshooting an Aquavar system, always break down into the
following components:
1. Aquavar programming check default settings recommended for single pump, multipump, slave pump etc.
2. Electrical supply/ motor/ wiring/grounding check your supply voltage, motor
wiring, transducer wiring, and grounding.
3. Mechanical/Pump/ Rotation check your pump rotation, rubbing or other mechanical
problems. Pump run out.
4. Hydraulic System/ Piping check to ensure proper suction and discharge piping
layout, proper NPSHa, air entrainment, vortex, friction loss, system curve compensation
etc.
5. Environment protect from high temperatures, direct sun, freezing temperatures, high
altitude, dust, vibration, lack of air flow.

84

PROGRAMMING
SINGLE-PUMP LEVEL CONTROL
Submersible Transducer Setup
PARAMETER SETTINGS QUICK LIST
1002 Pass Code = 66
1001 Parameter Lock = OPEN
1102 Application Macro = SINGLE PUMP
1104 Motor Nom. Volt.
1105 Motor Nom. Current
1106 Motor Nom. Freq.
1107 Motor Nom. RPM
1108 Motor Nom. Pow.
2101 Regulation Mode = INVERSE
1501 Transducer Unit = FT

SYSTEM TUNING
Group 13 Ramps allow for tuning of the system response. Ramps 1 and 2 provide control
of start and stop ramps and can be used to produce smooth operation throughout pumping
level. Ramps 3 and 4 work within the regulation window to provide a final adjustment of
system operation when needed (reference pages 107-111).
NOTE: Level control application performance is dependant on sump size, maximum flow
rate and pump selection. An oversized pump may produce on/off type system operation,
similar to a level switch. This condition might not be fully correctable with ramp control.

85

PROGRAMMING
MULTI-PUMP LEVEL CONTROL
Submersible Transducer Setup
PARAMETER SETTINGS QUICK LIST
1002 Pass Code = 66
1001 Parameter Lock = OPEN
1102 Application Macro = MULTIPUMP
1104 Motor Nom. Volt.
1105 Motor Nom. Current
1106 Motor Nom. Freq.
1107 Motor Nom. RPM
1108 Motor Nom. Pow.
2101 Regulation Mode = INVERSE
1501 Transducer Unit = FT
2207 Pump Address = 1, 2, 3 or 4

SYSTEM TUNING
Group 13 Ramps allow for tuning of the system response. Ramps 1 and 2 provide control
of start and stop ramps and can be used to produce smooth operation throughout pumping
level. Ramps 3 and 4 work within the regulation window to provide a final adjustment of
system operation when needed (reference pages 112-114).
NOTE: Level control application performance is dependant on sump size, maximum flow
rate and pump selection. An oversized pump may produce on/off type system operation,
similar to a level switch. This condition might not be fully correctable with ramp control.

86

PROGRAMMING
MultiPump Constant Pressure Control
Overview
The Aquavar CPC has the ability to connect and control up to four centrifugal pumps, to
form a Multi-Pump, lead-lag and alternating pumping system. This will allow the operator to
maintain a constant pressure through a larger system flow range, and provides equal wear for
the pumps and motors. The Aquavar units will be hard wired together via the RS485 terminals
(29,30,31), and provide communication to maintain a constant pressure to the system. Once
the lead pump cannot maintain a certain pressure and allows a slight pressure drop, the next
(lag) pump will turn on and vary the speed according to the flow demand. This sequencing
can be programmed according to the specific system requirements, and is field adjustable. If
a pump or controller fails, the next pump will automatically turn on in its place. Each Aquavar
controlled pump will provide a fully functional lead/lag and automatic alternation system, with
automatic back up control when required.
System Curve - Friction Compensation
It is possible to program the Aquavar to maintain a constant pressure, and compensate for
increasing friction loss according to a system curve. As the flow rate increases in the system,
the friction loss will increase as well. The Aquavar can compensate for this friction loss with
the simple adjustment of the parameter 2202 VALUE INCREASE. When each Aquavar unit
enables the pump, it will increase the system pressure by the programmed amount. This
pressure is additive with each additional pump. Therefore, if you set this parameter for 3 psi,
and you initial constant pressure is 50 psi, and you have 4 pumps total: (50 psi + 3 psi + 3
psi + 3 psi) = 59 psi when all 4 pumps are operating at full speed. This final system pressure
should be enough to overcome your calculated head and friction loss, and to provide constant
pressure at the end of the pipe run. NOTE: This program function is not intended for
substitution of proper pipe layout and sizing according to Hydraulic Institute Standards.
This feature may not work for excessive friction losses!
Pump Sequencing
The Aquavar CPC has the ability to operate in a multiple pump with lead and lag pumps.
Each Aquavar will be given an address then operate as Pump 1, Pump 2, Pump 3 or Pump 4.
When Pump 1 cannot maintain the required system pressure and the speed reaches 60 Hz,
then that will trigger the lag pump to come on and help maintain the set pressure. In order
for the lag pump to turn on, the lead pump must be at full speed (Maximum Frequency)
and programmed system pressure drop must be met (VALUE DECREASE). Each Aquavar
controlled pump will vary its speed according to the demand on the entire system. In a
Duplex System, you could have Pump 1 running at full speed 60 Hz, and Pump 2 running at 50
Hz in order to maintain the system pressure at the flow demand. Each pump will operate in a
sequential mode, when called.

87

PROGRAMMING
MultiPump Constant Pressure Control
Wiring/Connection RS485
Each Aquavar unit must be connected via terminals
29, 30 and 31. Using a three wire shielded cable
between each Aquavar terminal. Suggested wire
specifications would be 3 or 4 wire, 22AWG, one
pair shielded, TYPE CM or CL3, 75 degree C(UL).
Remember to keep the color coded wires the same
to each terminal connection, and inspect for loose or
bad connections.
When using all the same Aquavar CPC units, you must
provide a BUS TERMINATION for the last drives in the
multi-pump system. The RS485 has two yellow DIP
SWITCHES that must be in the ON position when that Aquavar CPC unit is the last or first in
the system. Therefore, if you have 4 pumps in multi-pump configuration, Aquavar address 1
and Aquavar address 4 would have their DIP SWITCHES in the ON position (see diagram). If
you have a DUPLEX system, then Aquavar address 1 and Aquavar address 2 would have the
switches in the ON position.
Always follow your local codes or National codes and have a certified electrician perform the
necessary wiring.
NOTE: Fieldbus cannot be used with RS485 multipump (Modbus, Devicenet,
Profibus). Single pump only!
Terminated
Station

Station

X1 Identification
28 Screen

Multipump
Connections
for each
Aquavar

29 B
30 A
31 AGND
32 Screen

88

Terminated
Station

Station

Hardware Description1
RS485 Multidrop Application
Other Modbus Devices

SCR
B
A
GND
B
A
GND
SCR

28
29
30
31
32

SCR
B
A
AGND
SCR

RS485 Interface
J2 J5
J2 J5
ON ON
ON ON

off position on position


Bus Termination

For functional descriptions, see Standard Serial Communication addendum.

PROGRAMMING
MultiPump Constant Pressure Control
Pump Sizing
It is recommend to use the same size pump for a multi-pump configuration. This is to
ensure even distribution of flow rates especially when small flow demands are put on the
system. If the operator requires a flow range of 10 500 GPM for the system, it would be
recommended to select a TRIPLEX system, with each pump capable of a maximum of 167
GPM at the required TDH. (167 GPM x 3 pumps = 501 GPM ) A smaller sized pump is more
capable of providing the low flow rates, rather than a larger pump that may oscillate more
at the low flows. One of the immediate benefits is to have all the same pumps for parts and
spares. No smaller jockey pumps. Each pump is evenly distributing the required flow and
pressure. Remember to allow system friction losses at maximum flow!
Tank Sizing
Similar to the single pump constant pressure system, the multi-pump system should have
a diaphragm or bladder type tank for system cushion. The tank should be rated for the
maximum system pressure, and be sized for 10-25% of the single pump capacity. This is total
tank volume, not drawdown. If you have a triplex system of 167 GPM per pump capacity,
then your tank size should be a minimum of 17 Gallon capacity. Go to the next higher
tank volume if you have a suction lift or flooded suction. The tank provides small
drawdown capacities on drive start up and provides a cushion for the entire system at
normal operation and will provide compressibility at shut-down. The tank pressure will greatly
improve system operation. A larger tank is acceptable and sometimes required, just do not
exceed 50% volume of the flow for one pump, this may cause system problems.
Programming
The following steps are for multi-pump, constant pressure systems, with up to four (4) Aquavar
CPC. Each Aquavar CPC will have to be programmed according to this parameter guide. The
parameters will not transfer over to each unit. There are two options for downloading the
parameters into each Aquavar:
A) Manually entering each parameter into the Aquava
control panel/display with the following steps.
B) Using the first Aquavar control panel, you can
download the software to each additional Aquavar
via the control panel. Take the programmed control
panel from Aquavar #1, then insert and replace each
additional control panel for Aquavar #2, #3, #4. This will
automatically download saved parameters into the other
Aquavar units. See diagram to the left.

89

PROGRAMMING
MultiPump Constant Pressure Control
Programming Step(s)
Standard view of the display in REM (remote) mode. You will see REM
the reference pressure (REF PRESSURE), actual pressure (ACT
PRESSURE) and motor frequency in HZ.

0.0%

40.2 PSI sp
0.0 PSI ac
0.0 HZ

DIR

1. Access the main menu on the keypad. Press the MENU key
once and the display will show (PARAMETERS, WIZARDS,
CHANGED PAR). Using the arrow keys, highlight the
parameters option, then press the ENTER key.

REM

MENU
MAIN MENU

PARAMETERS
WIZARDS
CHANGED PAR
EXIT

2. Once the parameters option has been chosen, the


parameter groups will be displayed. Each group will be
numbered (see parameter groups list on page 51 for
detailed information). Use the arrow keys to highlight the
parameter group 10, LOCKS/PASSWORDS, then press the
SEL key.

REM

3. Use the arrow keys to highlight group 1002 PASSCODE,


then press the EDIT key. Using the up arrow, enter your
factory password number (Default is 66). Press the save key.

REM

ENTER

PAR GROUPS

10

02 PUMP SIGNALS
03 FB ACTUAL SIGNALS
10 LOCKS/PASSWORDS
11 START-UP DATA
12 START/STOP
EXIT

SEL

PARAMETERS

1001 PARAMETER LOCK


1002 PASS CODE
0
1003 LOCAL LOCK
1004 PARAM SAVE
EXIT

4. Use up arrow to group 1001 PARAMETER LOCK, then


press the EDIT key. Next, use the up arrow to select OPEN,
then press the SAVE key. This group should appear as
OPEN, if it does not you have entered the pass code
incorrectly, or it has changed. Contact your local CentriPro
representative for the master code. Once your group 1001
is showing OPEN, you can access the entire pump and
drive parameters in the Aquavar.

REM

5. After the SAVE key is pressed in the above group, press the
EXIT key, then the down arrow to highlight the group 11
START UP DATA, then Press the SEL key once. Using the
arrows, highlight 1102 APPLIC MACRO, then press the
EDIT key. Using the UP arrow, highlight MULTICONTROL
option, then press the SAVE key.

REM

90

EDIT

PARAMETERS

1001 PARAMETER LOCK


OPEN
1002 PASS CODE
1003 LOCAL LOCK
1004 PARAM SAVE
EXIT

EDIT

PAR GROUPS

02 PUMP SIGNALS
03 FB ACTUAL SIGNALS
10 LOCKS/PASSWORDS
11 START-UP DATA
12 START/STOP
EXIT

11

SEL

PROGRAMMING
MultiPump Constant Pressure Control
6. Use down arrow until group parameter 1104 MOTOR
NOM VOLTAGE is highlighted, then press EDIT. Use the
arrows to enter your motors nameplate voltage, then press
the SAVE key.

REM

PARAMETERS

1101 LANGUAGE
1102 APPLIC MACRO
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
EXIT

7. Use the down arrow until group parameter 1105 MOTOR


NOM CURRENT is highlighted, then press EDIT. Using the
arrows, enter your motors maximum allowed amp draw
at full speed, or Service Factor Amps. NOTE: Enter motors
service factor from nameplate or motor manual. Once you
have entered the amps, press the SAVE key.

REM

8. Use down arrow until you highlight group parameter 1107


MOTOR NOM RPM, then press the EDIT key. Use arrows
to enter the RPM from the motor nameplate, default is 3550
RPM. Press the SAVE key to store setting.

REM

EDIT

PARAMETERS

1101 LANGUAGE
1102 APPLIC MACRO
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
3.5A
EXIT

EDIT

PARAMETERS

1104 MOTOR NOM VOLT


1105 MOTOR NOM CURR
1106 MOTOR NOM FREQ
1107 MOTOR NOM RPM
3550 RPM
EXIT

9. Use down arrow until you highlight group parameter 1108


MOTOR NOM POW, then press the EDIT key. Use arrows to
enter the motors Horsepower rating from nameplate, then
press the SAVE key.

REM

EDIT

PARAMETERS

1105 MOTOR NOM CURR


1106 MOTOR NOM FREQ
1107 MOTOR NOM RPM
1108 MOTOR NOM POW
1.0 HP
EXIT

EDIT

10. After saving your motor horsepower, press the EXIT key. Use REM
PAR GROUPS
15
11
START-UP
DATA
the down arrow until you highlight the Group 15 XDUCER
12 START/STOP
VARIABLES, then press SEL.
13 RAMPS/WINDOWS
14 SPD LIM/STRT LEVL
15 XDUCER VARIABLES
EXIT

11. Press the down arrow until parameter 1502 TRANSDUCER


MAX is highlighted, then press EDIT. Default pressure
transducer setting is 300 psi. Adjust this based on your
maximum rating for a new transducer. NOTE: CentriPro
provides a 0-300 psi transducer as standard. Always check
the maximum range of your transducer before proceeding.
Select the appropriate range, then press SAVE. If no changes
are necessary, press CANCEL.

REM

SEL

PARAMETERS

1501 TRANSDUCER UNIT


1502 TRANSDUCER MAX
300.0 PSI
1503 TRANSDUCER MIN
1504 SENSOR
EXIT

EDIT

91

PROGRAMMING
MultiPump Constant Pressure Control
12. Use the down arrow to highlight 1503 TRANSDUCER MIN 0.0 , then press EDIT. Default
should be 0 psi. Press CANCEL to advance to the next step. If this group needs to be
changed based on another type of transducer value, press SAVE to store.
13. Use the down arrow to highlight 1506 SENSOR MIN,
then press EDIT. Use the up arrow until the TUNE value is
displayed, press the SAVE key. This provides the transducer
a tuned value of 0 (ZERO) psi. NOTE: Make sure that your
transducer is wired to the Aquavar but free from any
pressure in the system. The transducer must be exposed
to 0 psi when this step is performed. Press the SAVE key to
tune your transducer.
14. Once you have saved the parameter 1506, press the EXIT
key. Use down arrow until you highlight parameter Group 22
MULTIPUMP CTRL Then press the SEL key.

REM

PARAMETERS

1504 SENSOR
1505 K-DP FLOW METER
1506 SENSOR MIN
4mA
EXIT

REM

EDIT

PAR GROUPS

16 REFERENCE SELECT
18 RELAY OUTPUTS
19 ANALOG OUTPUTS
21 REGULATE
22 MULTIPUMP CTRL
EXIT

15. After above step, you should have parameter 2201 VALUE
DECREASE highlighted. Press the EDIT once. Uses the
up or down arrow to select the allowable pressure drop
before the next lag pump comes on. (Example: If the first
pump reaches maximum frequency, and the pressure drop
allowed before the lag pump turns on is 3 psi, you would
set this parameter for 3.0 psi). Once a pressure is set in
2201, then press the SAVE key.

REM

16. Use the down arrow to highlight parameter 2202 VALUE


INCREASE then press EDIT. Use the UP or DOWN arrow to
set your system pressure curve compensation. If you do not
require friction loss compensation at maximum frequency,
then enter 0 psi. Then press the SAVE key. (NOTE: System
friction loss or overcoming head loss, can be compensated
by setting this parameter for each pump. This value increase
is additive for each lag pump).

REM

22

SEL

PARAMETERS

2201 VALUE DECREASE


3.0 PSI
2202 VALUE INCREASE
2203 ENABLE SEQUENCE
2204 SWITCH LEAD/LAG
EXIT

EDIT

PARAMETERS

2201 VALUE DECREASE


2202 VALUE INCREASE
5.0 PSI
2203 ENABLE SEQUENCE
2204 SWITCH LEAD/LAG
EXIT

EDIT

REM
PARAMETERS
17. Once parameter 2202 has been saved, use the DOWN
2201
VALUE
DECREASE
arrow to highlight parameter 2203 ENABLE SEQUENCE
2202 VALUE INCREASE
then press the EDIT key. Using the up or down arrows
2203 ENABLE SEQUENCE
59.00 HZ
select the frequency in HZ that will turn the next lag pump
2204 SWITCH LEAD/LAG
on, when the lead pump has reached this frequency.
EXIT
EDIT
Normal setting is 59 HZ, which allows the lag pump to start
when the frequency has reached 59HZ on the lead pump, plus value decrease has been
met). NOTE: Always set this parameter at or BELOW the MAXIMUM FREQUENCY). If
no changes from default are required, press the CANCEL key.
92

PROGRAMMING
MultiPump Constant Pressure Control
18. After 2203 has been selected, press the down arrow to
highlight parameter 2204 SWITCH LEAD LAG. Press
the EDIT key once. Using the up or down arrows, select
the alternating time between lead and lag pumps. Once
selected, press the SAVE key.

REM

19. Once 2204 has been saved, press the down arrow to
highlight 2207 PUMP ADDRESS. Press the EDIT key once.
Use the up arrow to select your appropriate address for
each pump. Always start with address one. Once each
pump has a different address, press the SAVE key.

REM

20. Final step is to enter your required system


pressure. After above programming has been
completed for each Aquavar controlled pump,
press the EXIT key two (2) or three (3) times, until
you arrive back to the first control display screen.
(SEE DIAGRAM.) Then press the UP or DOWN
arrow to select the required system pressure for
your Aquavar controlled pump. Once pressure has
been selected, press the green START key on the
keypad.
21. Optional Step: To lock out access to the control
panel (keypad), refer to page 104. This will prevent
unauthorized users from changing programming.

PARAMETERS

2201 VALUE DECREASE


2202 VALUE INCREASE
2203 ENABLE SEQUENCE
2204 SWITCH LEAD/LAG
12 H
EXIT

EDIT

PARAMETERS

2204 SWITCH LEAD/LAG


2205 SYNC LIMIT
2206 SYNC WINDOW
2207 PUMP ADDRESS
0
EXIT

EDIT

Status
LED

REM

UP
SOFT
KEY 1

DIR

40.2 PSI sp
0.0 PSI ac
0.0 HZ

11.1%

MENU

SOFT
KEY 2

DOWN
LOC
REM

LOC/REM

HELP

STOP

START

NOTE: If an error or fault occurs, refer to the troubleshooting/faults section of this


manual. When troubleshooting an Aquavar system, always break down into the following
components:
1. Aquavar programming check default settings recommended for single pump, multipump, slave pump etc.
2. Electrical supply/ motor/ wiring/grounding check your supply voltage, motor
wiring, transducer wiring, and grounding.
3. Mechanical/Pump/ Rotation check your pump rotation, rubbing or other mechanical
problems. Pump run out.
4. Hydraulic System/ Piping check to ensure proper suction and discharge piping
layout, proper NPSHa, air entrainment, vortex, friction loss, system curve compensation
etc.
5. Environment protect from high temperatures, direct sun, freezing temperatures, high
altitude, dust, vibration, lack of air flow.
93

94

27 R03B

26 R03A

25 R03C

24 R02B

23 R02A

22 R02C

21 R01B

20 R01A

19 R01C

NOTE:
AQUAVAR ISSUES RUN COMMANDS TO
CONSTANT SPEED (SLAVE PUMP) VIA RELAY
OUTPUTS (R01, R02, R03)
CONTROL LOOP MUST BE POWERED (EG. 120 AC) BY
SEPARATE SOURCE OR CONTROL PANEL.

NOTE:
RELAY STATE
R01C = NC
R01A = CC
R01B = NO
RELAY OUTPUT SPECS
250 VAC MAX, 2 AMP
RELAY OUTPUTS

CONTROL LOOP
POWER SOURCE

RELAY OUTPUTS
CAN BE ASSIGNED
IN GROUP 18.
SET TO
START SLV

X1 TERMINAL BOARD
AQUAVAR

POWER
SUPPLY

AC

SLAVE PUMP
MOTOR

T1 T2 T3

START/STOP

SLAVE PUMP
STARTER

CUSTOMER SUPPLIED
CONTROL PANEL

AQUAVAR CPC (SLAVE PUMP) DIAGRAM

PROGRAMMING

MultiPump Slave Pump Control

PROGRAMMING
MultiPump Slave Pump Control
Overview
The Aquavar CPC has the ability to use up to three dry relay contacts for constant speed
SLAVE or lag pump control. This is useful if the operator requires a wide range of flow rates
in certain situations (i.e. emergency flow), and does not require all variable speed controlled
pumps. When the required demand increases beyond capacity of the variable speed
controlled lead pump, then the FULL SPEED lag pump will turn on. Each relay will be wired
to your constant speed pump starter, sized for the appropriate horsepower and voltage. The
relay outputs located on the terminal control board X1 (SEE DIAGRAM FROM PREVIOUS
PAGE) will actuate when programmed according to the operators desired output. The lag
pumps will turn on when the Aquavar controlled pump cannot keep up to the required
demand. The lag pumps will be operated by across the line starters, and signaled to start
via the Aquavar relays located on terminals 19 through 27 of the X1 terminal block. The lag
pumps are referred to as SLAVE pumps, because they operate with commands from the
Aquavar controlled LEAD pump. The Aquavar controller will actuate the relays, and provide
a time delay for ON/ OFF on each relay.

Head

Lag Pump
Starts

Lag Pump
Starts

Value Decrease
Pump 1

Pump
1+2

Pump
1+2+3

Capacity (GPM)

The figure shows Pump 1 when it cannot maintain the system pressure (value decrease). Next,
Pump 1 + lag pump 2 will operate as a lead and lag system. If Pump 1 + 2 cannot maintain
system flow, then lag # 2 pump will turn on, then you will have all three pumps ( 1 + 2 + 3 )
operating in the system. You can operate up to 3 slave pumps, with 1 Aquavar controlled
pump.
NOTE: Each lag pump is controlled by the speed of the lead Aquavar pump, system
pressure drop (value decrease), and a delay time in seconds. Do not set the pressure drop
too close to operating system pressure, or pump cycling will occur!

95

PROGRAMMING
MultiPump Slave Pump Control
Lead vs. Lag
The Aquavar controlled pump will always be considered the LEAD pump, and start first in
the system sequence. The constant speed pumps will always be the SLAVE or LAG pumps
in the system. When the Aquavar controlled pump, starts to run out or cannot meet the
system demand, then the first relay output will actuate based on a programmed pressure and
time delay. The Aquavar CPC has up to three contacts that can be used for SLAVE operation.
Wiring/ Connection
The relays used for the SLAVE pump control are dry relay contacts, rated for a MAXIMUM
250 VAC or 30VDC, 2 Amps free from inductivity. Minimum is 500 mW (12V, 10mA). Refer to
diagram below, or in APPENDIX section.
Each relay will be wired to a voltage starter DO NOT EXCEED 250 VOLTS AC through each
relay. Each relay is designed for control power only. It is up to the operator to provide
necessary starters, overloads or fuses for each SLAVE pump motor control. Always follow your
local codes or National codes and have a certified electrician perform the necessary wiring.
= Run power to drive

= Ready pump is running

= not used

NOTE: Normally Closed (NC) = R01A, R02A, R03A



Common Connection (CC) = R01C, R02C, R03C

Normally Open (NO) = R01B, R02B, R03B
SLAVE Pump Sizing/ Piping
It is recommended that each slave pump be sized the same and with the same performance
curve. All necessary check valves, ball valves, or gate valves should be installed in the system
to limit or choke each SLAVE pump discharge in order to maintain proper head conditions
and to prevent pressure oscillations or system hunting. Follow all recommended Hydraulic
Institute standards for piping size and pipe layout.

96

PROGRAMMING
MultiPump Slave Pump Control
Programming Steps
Default settings for each relay are set for NOT USED. Therefore, REM
27.0%
the operator will have to access the programming, and go to
40.2 PSI sp
GROUP 18 RELAY OUTPUTS and set each relay to START
0.0 PSI ac
SLAVE. (SEE BELOW FOR DETAILED PROGRAMMING
0.0 HZ
STEPS.) Each relay is labeled (R01, R02, R03) and can be
DIR
MENU
programmed to respond based on a drop in system pressure
and delay time in seconds. Therefore, you can control the relay
when the system pressure starts to drop, and you allow a certain time delay in seconds to
respond. When the demand stops, each LAG pump will stop after a time delay, and operation
will return solely to the Aquavar controlled pump.

1. Access the main menu on the keypad. Press the MENU key
once and the display will show (PARAMETERS, WIZARDS,
CHANGED PAR). Using the arrow keys, highlight the
parameters option, then press the ENTER key.

REM

MAIN MENU

PARAMETERS
WIZARDS
CHANGED PAR
EXIT

2. Once the parameters option has been chosen, the


parameter groups will be displayed. Each group will be
numbered (see parameter groups list on page 50 for
detailed information). Use the arrow keys to highlight the
parameter group 10, LOCKS/PASSWORDS, then press the
SEL key.

REM

ENTER

PAR GROUPS

01 VFD SIGNALS
02 PUMP SIGNALS
03 FB ACTUAL SIGNALS
10 LOCKS/PASSWORDS
11 START-UP DATA
EXIT

10

SEL

3. Use the arrow keys to highlight group 1002 PASSCODE,


REM
PARAMETERS
then press the EDIT key. Enter your factory password number 1001 PARAMETER LOCK
1002 PASS CODE
(Default is 66). Press the save key.
0
1003 LOCAL LOCK
1004 PARAM SAVE
EXIT

4. Use up arrow to group 1001 PARAMETER LOCK, then


press the EDIT key. Next, use the up arrow to select
OPEN, then press the SAVE key. This group should
appear as OPEN, if it does not you have entered the pass
code incorrectly, or it has changed. Contact your local
CentriPro representative for the master code. Once your
group 1001 is showing OPEN, you can access the entire
pump and drive parameters in the Aquavar.

REM

EDIT

PARAMETERS

1001 PARAMETER LOCK


OPEN
1002 PASS CODE
1003 LOCAL LOCK
1004 PARAM SAVE
EXIT

EDIT

97

PROGRAMMING
MultiPump Slave Pump Control
5. After the SAVE key is pressed in the above group, press the
EXIT key, then the down arrow to highlight the group 11
START UP DATA, then Press the SEL key once. Using the
arrows, highlight 1102 APPLIC MACRO, then press the
EDIT key. Using the UP arrow, highlight CONSTANT SLV
option, then press SAVE key.

REM

PAR GROUPS

01 VFD SIGNALS
02 PUMP SIGNALS
03 FB ACTUAL SIGNALS
10 LOCKS/PASSWORDS
11 START-UP DATA
EXIT

REM

11

SEL

PARAMETERS

1101 LANGUAGE
1102 APPLIC MACRO
CONSTANT SLV
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
EXIT

EDIT

6. Use down arrow until group parameter 1104 MOTOR NOM REM
PARAMETERS
VOLTAGE is highlighted, then press EDIT. Use the arrows to 1101 LANGUAGE
1102 APPLIC MACRO
enter your motors nameplate voltage, then press the SAVE
1104 MOTOR NOM VOLT
key.
230V
1105 MOTOR NOM CURR
EXIT

7. Use the down arrow until group parameter 1105 MOTOR


NOM CURRENT is highlighted, then press EDIT. Using the
arrows, enter your motors maximum allowed amp draw at
speed, or Service Factor Amps. NOTE: Enter motors service
factor from nameplate or motor manual. Once you have
entered the amps, press the SAVE key.

REM

8. Use down arrow until you highlight group parameter 1107


MOTOR NOM RPM, then press the EDIT key. Use arrows
to enter the RPM from the motor nameplate, default is 3450
RPM. Press the SAVE key to store setting.

REM

EDIT

PARAMETERS

1101 LANGUAGE
1102 APPLIC MACRO
full
1104 MOTOR NOM VOLT
1105 MOTOR NOM CURR
1.8A
EXIT

EDIT

PARAMETERS

1104 MOTOR NOM VOLT


1105 MOTOR NOM CURR
1106 MOTOR NOM FREQ
1107 MOTOR NOM RPM
3550 RPM
EXIT

9. Use down arrow until you highlight group parameter 1108


MOTOR NOM POW, then press the EDIT key. Use arrows
to enter the otors Horsepower rating from nameplate, then
press the SAVE key.

REM

PARAMETERS

1105 MOTOR NOM CURR


1106 MOTOR NOM FREQ
1107 MOTOR NOM RPM
1108 MOTOR NOM POW
1.0 HP
EXIT

98

EDIT

EDIT

PROGRAMMING
MultiPump Slave Pump Control
10. After saving your motor horsepower, press the EXIT key. Use REM
PAR GROUPS
15
the down arrow until you highlight the group 15 XDUCER
15 XDUCER VARIABLES
16 REFERENCE SELECT
VARIABLES, then press EDIT.
18 RELAY OUTPUTS
19 ANALOG OUTPUTS
21 REGULATE
EXIT

11. Press the down arrow until parameter 1502 TRANSDUCER


MAX is highlighted, then press EDIT. Default pressure
transducer setting is 300 psi. Adjust this based on your
maximum rating for a new transducer. NOTE: CentriPro
provides a 0 -300 psi transducer as standard. Select the
appropriate range, then press SAVE. If no changes are
necessary, press CANCEL.

REM

12. Use the down arrow to highlight 1503 TRANSDUCER MIN


0.0, then press EDIT. Default should be 0 psi. Press CANCEL
to advance to the next step. If this group needs to be
changed based on another type of transducer value, press
SAVE to store.

REM

13. Use the down arrow to highlight 1506 SENSOR MIN,


then press EDIT. Use the up arrow until the TUNE value is
displayed, press the SAVE key. This provides the transducer
a tuned value of 0 (ZERO) psi. NOTE: Make sure that your
transducer is wired to the Aquavar but free from any
pressure in the system. The transducer must be exposed
to 0 psi when this step is performed. Press the SAVE key to
tune your transducer.

REM

SEL

PARAMETERS

1501 TRANSDUCER UNIT


1502 TRANSDUCER MAX
300.0
1503 TRANSDUCER MIN
1504 SENSOR
EXIT

EDIT

PARAMETERS

1501 TRANSDUCER UNIT


1502 TRANSDUCER MAX
1503 TRANSDUCER MIN
0.0
1504 SENSOR
EXIT

EDIT

PARAMETERS

1504 SENSOR
1505 K-DP FLOW METER
1506 SENSOR MIN
TUNE
EXIT

REM

EDIT

PAR EDIT

1506 SENSOR MIN

4 mA

CANCEL

REM

SAVE

PAR EDIT

1506 SENSOR MIN

TUNED VALUE

CANCEL

SAVE

99

PROGRAMMING
MultiPump Slave Pump Control
14. Once you have saved the parameter 1506, press the EXIT
REM
PAR GROUPS
18
key. Use down arrow until you highlight parameter group 18 14 SPD LIM/STRT LEVL
15 XDUCER VARIABLES
RELAY OUTPUTS. Then press the SEL key.
16 REFERENCE SELECT
18 RELAY OUTPUTS
19 ANALOG OUTPUTS
EXIT

15. After above step, you should have parameter 1801 RELAY
OUTPUT 1 highlighted. Press the EDIT once. Uses the up
arrow to highlight START SLV, then press SAVE.

REM

SEL

PARAMETERS

1801 RELAY OUTPUT 1


NOT SEL
1802 R01 ON DELAY
1803 R01 OFF DELAY
1804 RELAY OUTPUT 2
EXIT

EDIT

16. Use the down arrow to highlight parameter 1802 RO 1 ON REM


PARAMETERS
1801 RELAY OUTPUT 1
DELAY, then press EDIT. Use the UP arrow to set your time
delay to TURN ON RELAY 1 in seconds. Then press the SAVE 1802 R01 ON DELAY
10.0 s
key. NOTE: You may have to adjust this time delay based 1803 R01 OFF DELAY
1804 RELAY OUTPUT 2
on your system.
EXIT

17. Once parameter 1802 has been saved, use the DOWN
arrow to highlight parameter 1803 RO 1 OFF DELAY, then
press the EDIT key. Use the UP arrow to select the OFF
DELAY for relay 1 in seconds. Press the SAVE key. This will
allow a timed delay when relay 1 turns off the first slave
pump.

REM

EDIT

PARAMETERS

1801 RELAY OUTPUT 1


1802 R01 ON DELAY
1803 R01 OFF DELAY
5.0 s
1804 RELAY OUTPUT 2
EXIT

EDIT

18. If you do not require other SLAVE relays, then proceed to the next step MULTIPUMP
CONTROL. If more relays are required, repeat steps above for RELAY 2 and RELAY 3,
parameters 1804, 1805, 1806, 1807, 1808.
REM

19. Once you have saved your last relay output, press the EXIT
key once. Use the down arrow until you highlight parameter
group 22 MULTIPUMP CTRL, then press SEL key.

PAR GROUPS

16 REFERENCE SELECT
18 RELAY OUTPUTS
19 ANALOG OUTPUTS
21 REGULATE
22 MULTIPUMP CTRL
EXIT

20. After above step, highlight parameter 2201 VALUE


DECREASE, then press EDIT. Use arrows to program the
required pressure drop allowed by the Aquavar pump,
before the first slave pump turns on. Press the SAVE key.
NOTE: Keep this pressure low enough from the Aquavar
pressure setting and adjust your relay ON TIME DELAY to
PREVENT PUMP CYCLING!
100

REM

22

SEL

PARAMETERS

2201 VALUE DECREASE


2.1 PSI
2202 VALUE INCREASE
2203 ENABLE SEQUENCE
2204 SWITCH LEAD/LAG
EXIT

EDIT

PROGRAMMING
MultiPump Slave Pump Control
21. Once previous step has been saved, use the Down Arrow
and highlight parameter 2203 ENABLE SEQUENCE, then
press EDIT. Using the up or down arrow, enter the frequency
in Hertz (HZ) that you wish the SLAVE pump will turn on once
the lead pump reaches this speed. Default is set for 59 HZ
and is typical for 60HZ systems. If you change this setting,
press the SAVE key. If no changes are required, then press
the EXIT key.

REM

PARAMETERS

2201 VALUE DECREASE


2202 VALUE INCREASE
2203 ENABLE SEQUENCE
59.00 HZ
2204 SWITCH LEAD/LAG
EXIT

EDIT

22. Group 2205 Enter frequency for slave pump to be turned off.
23. Final step is to enter your required pressure in
the system. After above programming has been
completed, press the EXIT key two (2) or three
(3) times, until you arrive back to the first control
display screen. (SEE DIAGRAM) Then press the
UP or DOWN arrow to select the required system
pressure for your Aquavar controlled pump. Once
pressure has been selected, press the green
START key on the keypad.

Status
LED

REM

UP
SOFT
KEY 1

DIR

40.2 PSI sp
0.0 PSI ac
0.0 HZ

27.8%

MENU

SOFT
KEY 2

DOWN
LOC
REM

24. Optional Step: To lock out access to the control


panel (keypad), refer to page 104. This will prevent
unauthorized users from changing programming.

LOC/REM

HELP

STOP

START

NOTE: If an error or fault occurs, refer to the faults/alarms section of this manual, page
115. When troubleshooting an Aquavar system, always break down into the following
components:
1. Aquavar programming check default settings recommended for single pump, multipump, slave pump etc.
2. Electrical supply/ motor/ wiring/grounding check your supply voltage, motor
wiring, transducer wiring, and grounding.
3. Mechanical/Pump/ Rotation check your pump rotation, rubbing or other mechanical
problems. Pump run out.
4. Hydraulic System/ Piping check to ensure proper suction and ischarge piping layout,
proper NPSHa, air entrainment, vortex, friction loss, system curve compensation etc.
5. Environment protect from high temperatures, direct sun, freezing temperatures, high
altitude, dust, vibration, lack of air flow.
101

FEATURES
Analog Outputs
The Aquavar CPC has two 4-20 mA analog outputs as standard. These outputs may be
configured by the user to output from a selection of nine actual pump signals. Parameter
group 19 is used to configure these outputs. Analog Outputs are found on X1 Terminal Block,
# 2 and # 5 pins. Reference the terminal block diagram on pages 24-31 for detailed wiring
connections.
Parameter

Name

Value/Range

Note(s)

19.01
AO 1

Content Sel




Not SEL (default)


MOTOR FREQUENCY
MOTOR CURRENT
MOTOR POWER
MOTOR PROC VAR
MOTOR ENERGY
SAVNGS

CONNECTS an ANALOG SIGNAL TO


THE ANALOG OUTPUT. RANGE IS
0-20mA input.

19.06
AO 2

Content Sel




Not SEL (default)


MOTOR FREQUENCY
MOTOR CURRENT
MOTOR POWER
MOTOR PROC VAR
MOTOR ENERGY
SAVNGS

CONNECTS an ANALOG SIGNAL TO


THE ANALOG OUTPUT. RANGE IS
0 20mA input.
THIS IS THE DEFAULT PRESSURE
TRANSDUCER INPUT. 4 20Ma.

21.01
REGULATION NORMAL (DEFAULT)

MODE
INVERSE


SELECTS THE TYPE OF AQUAVAR


CONTROL AS THE ANALOG SIGNAL
RISES OR FALLS. SET TO INVERSE FOR
DECREASED MOTOR SPEED BASED ON
SUCTION LEVEL TRANSDUCER.

26.03
SAVINGS
0-65535

SCALE
Default 10,000


If ENERGY SAVNG is selected as an


output, this parameter must be set to
scale the signal. 4 mA = $0.00 and
20 mA equals this amount. For example
20 mA = $10,000.

Auto Restart
The Aquavar drive can be configured to start automatically following a power failure.
Changing the value to ON will enable auto-restart. Selecting OFF disables the auto-restart.
AUTO RESTART is also used with ERROR RESET for automatic restarts following a shutdown
due to a pump fault. AUTO RESTART will also restart the pump once a secondary protection
fault is reset.
Parameter

Name

Value/Range

12.02
AUTO
OFF

RESTART
ON (DEFAULT)

25.04
AR OVER-
ENABLE

CURRENT
25.05
AR OVER-
ENABLE

VOLTAGE
25.06
AR UNDER-
ENABLE

VOLTAGE
25.07
AR AI <
ENABLE

MIN
102

Note(s)
When this is set to ON , the Aquavar
will automatically re-start after a power
failure or fault reset.
Allows the drive to restart after a motor
overcurrent error.
Allows the drive to restart after an
INPUT OVERVOLTAGE error.
Allows the drive to restart after an
INPUT UNDERVOLTAGE error.
Allows the drive to restart after a
transducer or analog signal loss.

FEATURES
Energy Savings Information [Group 26]
Aquavar can calculate the energy savings as compared to a constant speed pump application.
To enable this function to perform properly, local energy costs and comparative application
information must be entered.
Enter the local energy cost in $ (local currency) per kWh into parameter 26.01($/KWhr) and
then enter the nominal power rating of a comparable fixed speed unit into parameter 26.02
(baseline power). To find this, look at the fixed speed pump performance curve and enter the
power for the rated operating point or maximum Brake Horsepower for the specific pump/
impeller combination.
Example - If your power cost is $0.06 per kWh, enter a value of .06 into parameter 26.01.

Parameter

Name

Value/Range

26.01
$/kWh
0-1.00
26.02
BASELINE
0-1000 HP

POWER
26.03
SAVINGS
065535

SCALE
26.04
ENERGY
SAVINGS OP 1

SAVE

METHOD

SAVINGS OP 2



26.05
ENERGY
DISABLED (Default)

SAVE RESET
RESET

Note(s)
Default is zero.
Default is zero.
Scales the analog output when energy
savings is selected.
Calculates energy savings with the Aquavar
based on a fixed speed pump that turns
ON and OFF when not required.
Calculates energy savings with the
Aquavar based on a fixed speed pump
that operates 24 hrs a day. Does not
turn off.
Allows resetting of savings to zero.

One of the benefits of using Aquavar is its ability to automatically shut off the pump when not
required. Parameter 26.04 SAVINGS OPTION #2 allows the savings of using Aquavar to be
tracked during automatic shutdown. The OPTION # 2 will calculate according to a fixed speed
unit that is designed to run continuously 24 hrs a day, 7 days a week.
NOTE: This is an estimated comparative data used for ideal situations, CentriPro cannot
guarantee savings will be exactly as stated. Many system variables
may increase or decrease estimated savings.
Fieldbus Control
The Aquavar CPC may be integrated into BMS (Building Management Systems) or existing
Distributive Control Systems (DCS) via optional Fieldbus control modules. The use of Fieldbus
control modules allows selected Aquavar parameters and operating signals to be accessed
and modified.
Fieldbus control modules are available in numerous communication protocols, including:
DeviceNet, Modbus, Profibus.
Modbus is the DEFAULT protocol for the Aquavar CPC.
With the control module installed (See INSTALLATION manual), set parameter 30.01
FIELDBUS to YES. This will open up parameter groups 90 D SET REC ADDR and 92 D SET
TR ADDR. These parameter groups define the addresses and data sets that are exchanged
between Aquavar and the DCS.
103

FEATURES
Parameter

Name

Value/Range

30.01
COMM
NOT SELECTED

PROTOCOL
(Default)

SELECT
STD MODBUS



EXT FBA


Note(s)
No fieldbus communication
Drive uses MODBUS protocol on the
standard RS485 port. Protocol settings
are in group 32.
The drive communicates with a fieldbus
adapter module in option slot 2 of the
drive. NOTE: When EXT. FBA is selected
parameter group 31 is unlocked.

Any parameter changes that are made using a Fieldbus control system must be saved to the
drive.
Parameter

Name

Value/Range

10.04
PARAMETER
DONE (Default)

SAVE
SAVE


Note(s)
Parameters that are manually entered through
the keypad are automatically saved, only
parameters entered through a Fieldbus
connection must be saved. To save, select SAVE
and press the ENTER key.

Language
The Aquavar CPC system fully supports 3 languages; English(AM), French, and Spanish.
English(AM) refers to American English and is the default language. Units of power are in HP.
Parameter

Name

11.01
LANGUAGE

Value/Range
ENGLISH (AM)
ESPANOL
FRANCAIS

Note(s)
ENGLISH (AM) is the default setting.

Locking
The AQUAVAR CPC has three levels of control panel (keypad) locking; LOCAL LOCK,
PARAMETER LOCK and SET POINT LOCK.
PARAMETER LOCK - In parameter lock, parameters may be viewed, however they cannot
be changed. Starting, Stopping, set point changes and drive fault resets may still be
performed using the keypad. A valid password must be entered in parameter group 10.02.
LOCAL LOCK - In local lock, starting and stopping, and setpoint changes are prevented.
Resetting of drive faults is still possible and ON and OFF control.
SET POINT LOCK When in the ON position, the set-point cannot be changed from the
control panel. This prevents unwanted changes to Aquavar settings.
To change the drive parameters, including 10.03 LOCAL LOCK, the parameter lock must be
opened. To open the parameter lock, go to parameter 10.02 PASS CODE and scroll to the
number 66 and press ENTER. Parameter 10.01 PARAMETER LOCK will read OPEN.
NOTE: If power to the drive is lost [power failure, disconnect, etc] parameter 10.01
PARAMETER LOCK will automatically reset to LOCKED.

104

FEATURES
Parameter

Name

Value/Range

10.01
PARAMETER
LOCKED (Default)

OPEN


10.02
PASS CODE
-Not Displayed-




10.03
LOCAL LOCK OFF (Default)

ON
10.06
SET POINT
OFF (Default)

LOCK
ON

Note(s)
This parameter displays the status of the
parameter lock and can be used to lock
the parameters when necessary. To OPEN
the parameter lock, use parameter 10.02.
Using the arrow keys, scroll to the
number 66 and press enter. This will
open the parameter lock. Note - The
number entry will disappear once
ENTER has been pressed.
This parameter disables local control of
the drive (Start/Stop/setpoint changes).
This lock prevents the set point from
being changed on the control panel.
Must enter password first.

WARNING! It is not possible to stop the drive through the keypad with LOCAL LOCK
set to ON.
Use LOCAL LOCK only with a remote (external) stop/start method.
Keypad must be set in REMOTE before enabling LOCAL LOCK.
Minimum Speed Options
When the Aquavar CPC reaches the minimum speed that is set in parameter 14.02, it can be
programmed to stay at that minimum speed indefinitely, or to shut-down after a time delay.
This reaction applies to conditions where Aquavar is trying to regulate to a setpoint, when it
faults due to a secondary protect condition, or there is little or no process demand.
If the parameter 14.03 CONFIG SPEED MIN is set to MINIMUM FREQ the drive will stay at
minimum speed indefinitely, until the system demand increases, it is shutdown manually, or
a fault occurs forcing it to shutdown. If it is operating at minimum speed due to a Secondary
Protect fault, it will stay at minimum speed until the fault is reset.
If a Pump Protect condition exists and CONFIG SPEED MIN is set to MINIMUM FREQ, Aquavar
will try to reset the fault while at minimum speed if parameter 12.02 AUTO RESTART is set to
ON and parameter 24.06 ERROR RESET is set for the desired number of attempts. If the fault
has not cleared after the selected number of resets has been attempted, the pump will be
shut down. If parameter 24.06 ERROR RESET = 0, the pump will be shut down upon a Pump
Protect fault.
If parameter 14.03 CONFIG SPEED MIN is set to ZERO 0 (DEFAULT), the drive will stop the
pump for Pump Protect and Secondary Protect faults. The reaction to stop the pump when at
minimum speed can be delayed for up to 1800 seconds by programming parameter 14.04
(Stp Delay Min Spd).
For example, if the MINIMUM FREQ. is set for 35 HZ, and the Stp. Delay Min Spd is
set for 5 seconds, the pump will ramp down to 35HZ and remain at that speed for 5
seconds, then turn off. This is dependent upon the demand decreasing in the system.
Leaks will keep the pump running at slow speeds. Also check for properly seated check
valves and bladder tank pressure.
WARNING! It is not possible to manually set speed or frequency below the
MINIMUM SPEED setting in parameter 14.02
105

FEATURES
Minimum Speed Options (continued)
Parameter

Name

Value/Range

14.03
CONFIG
SPD=MINSPD

SPEED MIN
SPD=0 [default]




14.04
STP DELAY
0-1800 sec

MIN SPD
0 (default)

14.05
RESTART
0.0-150%

VALUE
0 (default)









14.06
RESTART
0-3600 Sec

DELAY
0 (default)

12.02
AUTO
OFF (default)

RESTART
ON
24.06
ERROR
0 (Default)

RESET
1-9999


24.07
RESET
0-250 seconds

DELAY
60 seconds (Default)

Note(s)
Selecting SPD=MINSPD will result in the drive
staying at minimum speed until it is manually
shut-off, process demand increases, a secondary
protection fault is cleared, or a pump protection
fault forces it to shutdown.If SPD=0 is selected,
the drive will stop.
This parameter enables the drive to remain at
minimum speed for a period (up to 1800
seconds) before shutting down.
If the drive is shutdown by CONFIG SPEED MIN
(14.03) due to no system demand (pressure
control and level control modes only) the drive
will sleep until the process actual value drops
below a set restart value (14.05) for longer than
the restart delay (14.06). If operating in inverse
mode (21.01) the drive will sleep until the
process variable rises above the restart value.
Wake-up level in % of setpoint value = 0 150%.
Default is 0%. To disable the Restart Value
function enter 0%.
This is the length of time the drive waits
between starting the pump according to
1405 value.
This enables the drive to restart on its own
following a power failure or ERROR RESET.
If the Aquavar unit faults on Pump Protection,
this parameter will reset the fault up to the
selected number of times before completely
shutting off the drive.
The automatic reset of protection faults can be
delayed. Default value is 60 seconds.

Restart Value
Allows a pressure or value drop before the Aquavar starts to maintain system pressure. Units
are in % of set value. (e.g. If set pressure is 100 PSI and 14.05 is set for 90%, then the Aquavar
will wait until system pressure drops to 90 PSI before starting.)
Priming Delay
This feature will override the PUMP PROTECT feature and is designed to allow self-priming
pumps sufficient time to prime before the Aquavar Pump Protection logic becomes active.
The delay period is applied only if the pump is being started from a zero-speed condition.
Once the priming delay is complete, the PROTECTION DELAY (24.06) becomes active, if set.
Parameter
14.07

Name
PRIMING
DELAY

Value/Range
0-6000 Seconds
0 (Default)

Note(s)
The priming delay time is added to the
pump protection delay time.

NOTE: Do not set beyond normal priming time for specific pumps or damage may occur.
Refer to pump manufacturer for maximum allowed priming times before shutdown.

106

FEATURES
Pump Protect Ctrl
This feature is designed to protect the pump from lack of available NPSH, loss of or low
suction, pump run-out. This pump protection feature is exclusive to the Aquavar and
measures the discharge pressure of the pump via the transducer, and compares it with the
minimum allowed system pressure as entered into parameter (2403) PROTECTION LIMIT. If
this parameter is set, then a time delay will need to be set in number of seconds allowed to
run at or below this limit, before shutting down on a fault.
Parameter
24.02


24.03

24.04

Name
PUMP
PROTECT
CTRL
PROTECTION
LIMIT
PROTECTION
DELAY

Value/Range

Note(s)

Disabled (Default)
WARN
WARN & CTRL.
0 6553.5

Provides no warning, warning or


warning and then shut off.

0 -200 seconds

Provides a time delay for 24.03.

Actual value units.

NOTE: It is recommended to set this pump protection according to


suggested minimum allowed system requirements. (i.e. pump run-out limits)
Regulation Mode
The regulation mode can either be NORMAL or INVERSE. The default and more common
selection is NORMAL, where the Aquavar software anticipates an increase in system pressure,
and will decrease speed of the pump based on a rising system pressure. If the regulation
mode is set to INVERSE, the process condition is expected to increase with a decrease in
pump speed.
Parameter
21.01

Name
REGULATION
MODE

Value/Range
NORMAL (Default)
INVERSE

Note(s)
Inverse is normally used for control of
suction side systems.

EXAMPLE If an Aquavar unit is trying to control the level in a suction-side tank or sump, the regulation mode
would be set to INVERSE. As the level in the sump increased, Aquavar would respond by increasing pump speed
to maintain a constant level.

Relay Outputs
The AQUAVAR CPC has three relay outputs that are configurable for different operating
and fault conditions. Relays will revert to original states once warnings or faults are reset or
cleared.
Comment(s)

Maximum Contact Voltage

30 VDC, 250 VAC

Maximum Continuous Current

2 A RMS

Refer to the terminal layout diagram for RELAY OUTPUT specifications.


Maximum Contact current/ power = 6A, 30 VDC, 1500 VA, 250 VAC

107

FEATURES
Parameter

Name

18.01
RELAY R0

OUTPUT
18.04
RELAY R02

OUTPUT
18.07
RELAY R03





Value/Range

Note(s)

NOT USED

Default for RO1

RUNNING

Default for RO2

READY
Default for RO3
OUTPUT
VFD FAULT
SECND PRTECT A
Secondary Protect A activation.
PUMP PROTECT
Pump protection activation.
START SLAVE
Used with multi-pump macro only.
STAND BY

NOTE: When using relay outputs to activate constant speed pumps in a multi-pump
application, the slave pumps 1, 2 and 3 should utilize relay outputs RO1, RO2, and RO3
accordingly (Slave 1 RO1). Sequence logic is affected by these selections.
Restart Options
Parameter 14.05 See MINIMUM SPEED OPTIONS
Low Water (Suction) Protection
The Aquavar provides protection from dry-run conditons in pressure, level, temperature and
speed control modes. This feature may also be used to provide inter-lock capabilities. In these
cases, additional system condition inputs (e.g. level switch, pressure switch, flow switch, etc)
are used to alert Aquavar of conditions that require protection of the pump.
Discharge Header

Flow Switch

Speed Signal

Once wired, parameter 24.05 LOW WATER must be set to WARNING or WARN AND
CONTROL. Digital Input 2 (DI 2), terminal # 14 on the X1 terminal board. If this contact is
OPEN, the response being:
1. WARN & CONTROL In this response, Aquavar will issue a warning and then either shut
down or reduce speed depending on your settings. At this point the pump will behave
similar to the description in MINIMUM SPEED. Alarm & Control is the recommended
setting.
108

FEATURES
2. WARNING ONLY In this response, Aquavar will simply issue an alarm/warning displayed
on the keypad screen, but continues to operate.
NOTE: The WARNING ONLY mode may result in damage to the pump if a low water
condition occurs. It is recommended to set this for WARN & CONTROL.
Keypad Failure
In the event of a keypad failure, Aquavar has been configured to fault and shut down the
controller. This functionality can be disabled, or configured to result in a drive fault.
Parameter
24.01

Name
KEYPAD
FAILURE

Value/Range
DISABLED (default)
FAULT

Note(s)
Fault message - PANEL LOSS

Set Points, Dual


The Aquavar can alternate between two fixed set points or one fixed point and a variable
set point. The alternating between set points may be accomplished using a digital switch or
through a Fieldbus command.
Parameter

Name

Value/Range

16.01
SP1/SP2
SETP 1 [Default]

SELECT
DI4

FIELDBUS





16.02
SET POINT 1 KEYPAD (Default)

SEL
AI 1

FIELDBUS



16.03
SET POINT 2 KEYPAD (Default)

SEL
ANALOG INPUT

FIELDBUS



22.08
SET POINT 2
OFF, 14

SOURCE

Note(s)
This parameter defines the source that
toggles the Aquavar unit between
Set Point 1 or Set Point 2.
SET POINT 1 (Default) indicates that
only set point 1 is being used.
DI4 is a digital input where 0
(Open) selects Set Point 1 and 1
(Closed) selects Set Point 2.
This selects where the value for
Set Point-1or 2 is coming from.
KEYPAD - a number [e.g. 100] will
be manually entered via the keypad.
Selecting ANALOG INPUT will require
entry of parameters 16.03-16.04.
This selects where the value for
Set Point-1or 2 is coming from.
KEYPAD - a number [e.g. 100] will
be manually entered via the keypad.
Selecting ANALOG INPUT will require
entry of parameters 16.03-16.04.
Must select source.

EXAMPLE for 16.02 and 16.03 An irrigation system requires 110 psi for watering all zones, then
during the daytime normal water pressure is set for 60 psi.

109

FEATURES
Parameter

Value

Notes

16.01
DI4

16.02
KEYPAD


16.03
KEYPAD

A switch would be wired into DI4 and the DCOM on the X1 terminal to
toggle between set point 1 and set point 2.
The setpoint would be manually entered using the Aquavar keypad.
When the switch [DI4] is set to 0 (Open), the set point would be entered
as 110 psi using the keypad REF button.
The set point would be manually entered using the Aquavar keypad.
When the switch [DI4] is set to 1 (Closed), the set point would be entered
as 60 psi using the keypad REF button.

WARNING! Parameter 16.01, 16.02 and 16.05 can only be changed when the motor
is not running. Most parameters require you to stop the pump, before programming.
System Curve Compensation
The AQUAVAR CPC system can automatically compensate for system friction losses due to
increased flow in single pump operation or multi-pump backup modes. Tables are available in
most pump catalogs to assist in determining the amount of friction loss that can be expected
for various pipe sizes and flow rates on simple systems. As flow increases, velocity increases
causing friction loss through piping and various fixtures. Normally this would provide a loss in
flow or overall pressure to the system. With the Aquavar you can compensate for this friction
loss!
The diagram below illustrates a typical system curve in relation to pump speed.
Head /
Pressure

N=100%

%N
System Curve

on

sati

%N

ys
gS

ltin

u
Res

Set
Pressure

o
eC

urv

C
tem

en
mp

Pressure Increase

%N

Constant Pressure Line

%N

Flow

In this case the system pressure set point is shown at shutoff ( 0 flow) and the increase in
setpoint pressure is shown for increasing flow. EXAMPLE - If the set point is 150 Ft [65 PSIG
@ 1.0 SG] and the system resistance increase 10 Ft at the maximum flow rate, or roughly 7%
of the set point, parameter 21.08 would be set as 7.
110

FEATURES
Parameter

Name

Value/Range

21.02
PRESS INCR
0- 60 HZ

SPEED
20 HZ (Default)

21.03
PRESS INCR
0-100%

0.0 %
0% (Default)

Note(s)
This is the frequency at which system curve
compensation begins. At speeds below this, no
compensation for increased resistance is made.
This is the amount that Aquavar will have
increased the set point at maximum speed.

Test Run
The TEST RUN capability allows the Aquavar system to run periodically if it has been inactive.
The most common circumstance for which Test Run would be applied is when a standby
pump is infrequently used; the test run would allow lubrication of bearings and help verify if
the unit is ready for operation. The TEST RUN DELAY sets the interval that automatic test runs
will occur at.
Test runs are factory programmed for 20 seconds. This duration cannot be changed. If
Automatic test run is selected, the test run is at 50% of maximum speed.
NOTE: Once manual test is selected and the test is complete, parameter 12.03 will return
to NOT SEL.
Parameter

Name

Value/Range

12.02
AUTO
OFF (Default)

RESTART
ON
12.03
TEST RUN
NOT SEL (default)

AUTOMATIC

MANUAL
12.04
TEST SPEED
0-100%

% (FL)
50% (Default)

12.05
TEST RUN
0-3600 hours

DELAY
1000 Hrs (Default)

Note(s)
Must be set to ON for test run function to
operate.

The speed, as a percent of maximum speed,


which the test run will occur at if MANUAL is
selected.
This is the period of pump inactivity before the
test run will begin, based on power up time.

Tuning, System Pressure


If the pump appears to oscillate in speed [e.g. Hunting], cannot maintain a uniform set point,
or shuts off too quickly or too slowly, the ramp rates and regulation window settings may need
to be modified, or adjustments.
When an operating mode is selected [i.e. Flow, Pressure, Level, etc], Aquavar engages
factory default settings for the rate that the drive adjusts at to meet the set point demand.
In most cases these settings will not require adjustment. The most common exceptions are
with process instruments with slow response times [e.g. insertion type flowmeter1], or in
temperature/level control applications, where variables such as tank size is unknown. HVAC
Systems with flow meters may require adjustment as well.
When the Aquavar system is adjusting speed to meet the set-point demand, it does so using
a fast rate and a slow rate. As shown in the figure below, the 2-point control algorithm uses
four ramp rates; fast acceleration, fast deceleration, slow acceleration, and slow deceleration.
Aquavar characterizes these rates in terms of seconds to meet the set point hysteresis window
maximum value (described later).
NOTE: In speed control mode, there is only fast acceleration and fast deceleration [R1, R2].
An insertion-type flowmeter uses a magnetic flux/Coriolis effect to measure fluid flow. This should not be confused with magnet flow meters
or differential pressure flow meters.
1

111

FEATURES

Set Point Scale


[e.g. Pressure - PSIG, Flow - GPM, etc.]

Set Point
Hysteresis
Window

R3

R4

Set Point

R1 - Ramp 1, Fast Acceleration


R2 - Ramp 2, Fast Deceleration
R3 - Ramp 3, Slow Acceleration
R4 - Ramp 4, Slow Deceleration

R1

R2

10s

50s

Time

Window Setting (Reg Window)


Aquavar controls the set-point within a defined window. This window, called the Regulation
Window [Parameter 13.06 REG WINDOW] is automatically set based upon the operating
modes and instrument type selected during programming. Values may be adjusted in
parameter 13.06.
EXAMPLE: if the Aquavar unit was in pressure control with the set point at 100 psig, the regulation window
would be factory preset at 8% of the set point. This would result in an 8 PSIG window; 4 PSIG above the set point
and 4 PSIG below the set point.

Parameter
13.06

Name

Value/Range

REG
0-100%
WINDOW

Note(s)
Constant Pressure = 8%
Flow [Direct] = 30%

Suggested settings are above in the notes. Sometimes the REGULATION WINDOW will have to be adjusted to
smooth out the system pressure. Default setting is 8%.

NOTE: If the system pressure drops below or goes above the hysteresis limits (DASHED
lines), then the Aquavar control software will adjust the speed with the fast ramps. This
would occur if you have a rapid demand of water in your system. Normally it takes a few
seconds to level off.

112

R3

R3
R4

R4

Hysteresis -%
Hysteresis -%

Window Setting
% of Set Point

Set Point

Set Point
Hysteresis
Window

Set Point Scale


[e.g. Pressure - PSIG, Flow - GPM, etc.]

FEATURES

R1

R1 - Ramp 1, Fast Acceleration


R2 - Ramp 2, Fast Deceleration
R3 - Ramp 3, Slow Acceleration
R4 - Ramp 4, Slow Deceleration
R1

Time

RAMP HYSTERESIS
Ramp hysteresis is the point at which the Aquavar controller changes over from the fast
ramp to the slow ramp. Default values of Ramp Hysteresis are in % of the regulation window.
The values for RAMP HYSTERESIS are automatically selected based upon the control mode
selection made during programming.
EXAMPLE: Using the same example above, the Regulation Window was 8 psig. An 80% ramp hysteresis would
be 3.2 PSIG. Note from the graph, this is 1.6 PSIG on the upper half of the regulation window, and 1.6 PSIG on
the lower half of the regulation window.

Parameter
13.05

Name

Value/Range

RAMP
0-100%
HYSTERESIS

Note(s)
Pressure = 80%
Flow [Direct] = 5%

As the figure shows, Aquavar attempts to keep the actual process reading within the Setpoint
Hysteresis Window using the slow acceleration and deceleration ramp rates. When the
process reading exceeds this window, it will compensate using the fast acceleration or
deceleration ramp rates.
Adjusting Ramp Rates
Ramp 1 - Fast Acceleration: This ramp is the fast run up time used when the pump first
starts and is trying to reach the setpoint. A setting too fast may overshoot the set-point, while
a setting too slow may cause the drive to respond too slowly to set point changes. NOTE:
FOR AQUAVAR UNITS ABOVE 10 HP, SET RAMP 1 AND RAMP 2 TO AT LEAST 8 10
SECONDS.
Parameter
13.01

Name

Value/Range

RAMP 1
0-1800s
FAST ACCEL

Note(s)
Pressure default = 5 seconds
Level, Temperature default = 20 seconds
113

FEATURES
Ramp 2 - Fast Deceleration: This ramp is the fast run down time used when the pump is
shutting down. If the setting R2 setting is too fast, the pump may oscillate, or hunt while it
tries to attain the set point. If it is too slow, the actual process value may rise well above the
set point. NOTE: AQUAVAR UNITS ABOVE 10 HP, RAMP 1 AND RAMP 2 SHOULD BE SET
FOR AT LEAST 8 10 SECONDS.
NOTE: Air in the pump system may cause a condition that looks like oscillation or hunting.
Make sure all the air is purged from the system before trying to change the Ramp 2 setting.
Parameter
13.02

Name

Value/Range

RAMP 2
0-1800s
FAST DECEL

Note(s)
Pressure default = 5 sec
Level, Temperature default = 20 seconds

Ramp 3, Slow Acceleration: This ramp is the slow run up time used when the pump is
operating within its setpoint window. If the R3 setting is too slow, pressure or flow may be
slow to respond to the set point as demand varies. A setting too fast may lead to oscillation.
Parameter

Name

Value/Range

13.03
RAMP 3
0-1800s

SLOW ACCEL

Note(s)
Pressure default = 60 seconds
Flow [magnetic flow meter] default = 50 sec
Level, Temperature default = 200 seconds

Ramp 4, Slow Deceleration: This ramp is the slow run down time used when the pump is
operating within its set point window. If the R4 setting is too slow, it will lead to oscillation. A
setting too fast may delay the motor shut-down when demand is reduced.
Parameter

Name

Value/Range

13.04
RAMP 4
0-1800s

SLOW DECEL

114

Note(s)
Pressure default = 60 seconds
Flow [magnetic flow meter] default = 50 sec
Level, Temperature default = 200 seconds

FAULTS/ALARMS
Warning! Do not attempt any measurement, parts replacement or other service
procedure not described in this manual. Such action will void the warranty, may
endanger correct operation, and increase downtime and expense.
Warning! All electrical installation and maintenance work described in this chapter
should only be undertaken by qualified service personnel. The Safety instructions on
the first pages of this manual must be followed.

Diagnostic Displays
The drive detects error situations and reports them using:
The green and red LED on the body of the drive.
The status LED on the control panel (if a control panel is attached to the drive).
The control panel display (if a control panel is attached to the drive).
The Fault Word and Alarm Word parameter bits (parameters 0310 to 0311).
See Group 03: FB Status Words on page 50 for the bit definitions.
The form of the display depends on the severity of the error. You can specify the severity for
many errors by directing the drive to:
Ignore the error situation.
Report the situation as an alarm.
Report the situation as a fault.
Red Faults
The drive signals that it has detected a severe error, or fault, by:
Enabling the red LED on the drive (LED is either steady on or blinking).
Setting an appropriate bit in a Fault Word parameter (0305 to 0307).
Overriding the control panel display with the display of a fault code.
Stopping the motor (if it was on).
The fault code on the control panel display is temporary. Pressing any of the following buttons
removes the fault message: MENU, ENTER, UP button or DOWN button. The message reappears after a few seconds if the control panel is not touched and the fault is still active.
Flashing Green Alarms
For less severe errors, called alarms, the diagnostic display is advisory. For these situations,
the drive is simply reporting that it had detected something unusual.
The drive signals that it has detected an alarm, by:
Flashing the green LED on the drive does not apply to alarms that arise from control
panel operation errors (Alarms 1 to 7).
Setting an appropriate bit in an Alarm Word parameter (0308 or 0309).
See Group 03: FB Status Words on page 50 for the bit definitions.
Overriding the control panel display with the display of an alarm code and/or name.
The alarm messages disappears from the control panel display if/when any of the following
are pressed on the control panel: MENU, ENTER, UP button, or DOWN button.
115

FAULTS/ALARMS
Correcting Faults
The recommended corrective action for faults is:
Use the Fault Listing table below to find and address the root cause of the problem.
Reset the drive. See Fault Resetting on page 119.
* Drive not ready fault. Check supply voltage / DC Bus = 1.35 x input voltage.
* Comm fault drive not responding. Internal communication lost.
Cycle Power Remove and reinstall panel Replace panel
Fault Listing
Fault Fault Name
Code In Panel

Description and Recommended Corrective Action

1 OVERCURRENT



2 DC OVERVOLT



3 DEV OVERTEMP





4 SHORT CIRC


5 OVERLOAD

6 DC UNDERVOLT


Output current is excessive. Check for and correct:


Excessive motor load, pump overload.
Insufficient acceleration time (parameters 1301 Ramp 1 and 1302 Ramp 2).
Faulty motor, motor cables or connections.
Intermediate circuit DC voltage is excessive. Check for and correct:
Static or transient overvoltages in the input power supply.
Insufficient deceleration time (parameters 1302 Ramp 2, increase to at least
8 seconds).
Drive heatsink is overheated. Temperature is at or above 115 C (239 F).
Check for and correct:
Fan failure
Excessive ambient temperature
Obstructions in the air flow Excessive motor load
Dirt or dust coating
Ambient temperature
on the heat sink
Altitude
Fault current. Check for and correct:
A short-circuit in the motor cable(s) or motor
Supply disturbances
Inverter overload condition. The drive output current exceeds the ratings given
in Ratings on pages 131-134 of this manual.
Intermediate circuit DC voltage is not sufficient. Check for and correct:
Missing phase in the input power supply
Blown fuse/check input wiring
Undervoltage on mains

7 AI1 LOSS


Analog input 1 loss. Analog input value is less than AI1 MIN (1604).
Check for and correct:
Source and connection for analog input.
Parameter settings for AI1 MIN (1604).

8 AI2 LOSS


Analog input 2 loss. Analog input value is less than SENSOR MIN (1506).
Check for and correct:
Source and connection for analog input.
Parameter settings for SENSOR MIN (1506) and (1503) TRANSDUCER MIN.

9 MOT OVERTEMP




Motor is too hot, based on either the drives estimate or on temperature


feedback device.
Check for overloaded motor.
Adjust the parameters used for the estimate (11041109).
Check the temperature sensors and Group 11 parameters.
Check motor wiring and connections. Possible MOTOR phase loss.

116

FAULTS/ALARMS
Fault Fault Name
Code In Panel

Description and Recommended Corrective Action

10 PANEL LOSS








11 ID RUN FAIL

12 MOTOR STALL




13 RESERVED
14 PUMP PROTECT
15 LOW WATER
16 EARTH FAULT


17 UNDERLOAD


18 THERM FAIL

19 OPEX LINK


20 OPEX PWR

21 CURR MEAS


22 SUPPLY PHASE



23 RESERVED
24 OVERSPEED




25 RESERVED
26 DRIVE ID

Panel communication is lost and either:


Drive is in local control mode (the control panel displays LOC) or
Drive is in remote control mode (REM) and is parameterized to accept start/
stop, direction or reference from the control panel.
To correct check:
Communication lines and connections for control panel.
Parameter 2401 KEYPAD FAILURE.
Parameters in Group 10: Command Inputs and Group 11:
Reference Select (if drive operation is REM).
The motor ID run was not completed successfully. Check for and correct:
Motor connections, wiring.
Motor or process stall. Motor is operating in the stall region.
Check for and correct:
Excessive load
Insufficient motor power
Blocked pump
Not used
Pressure has fallen below value in Group 2403
DI12 has been activated. Check for proper suction supply.
The load on the input power system is out of balance.
Check for/correct faults in the motor or motor cable.
Verify that motor cable does not exceed maximum specified length.
Motor load is lower than expected. Check for and correct:
Disconnected load
Drive oversized
Internal fault. The thermistor measuring the internal temperature of the drive is
open or shorted. Contact your local factory representative.
Internal fault. A communication-related problem has been detected on the
fiber optic link between the OITF and OINT boards. Contact your local factory
representative.
Internal fault. Low voltage condition detected on OINT power supply.
Contact your local factory representative.
Internal fault. Current measurement is out of range. Contact your local factory
representative.
Replace drive
Ripple voltage in the DC link is too high. Check for and correct:
Missing mains phase
Blown fuse
Input wiring/connections
Not used
Motor speed is greater than 120% of the larger (in magnitude) of 1402
MINIMUM SPEED or 1401 MAXIMUM SPEED. Check for and correct:
Parameter settings for 1401 and 1402
Adequacy of motor braking torque
Applicability of torque control
Not used
Internal fault. Configuration Block Drive ID is not valid.
Contact your local factory representative.

117

FAULTS/ALARMS
Fault Fault Name
Code In Panel

Description and Recommended Corrective Action

27 CONFIG FILE
Internal configuration file has an error. Contact your local factory

representative.

Cycle power
Check Group 9902 / Drive Size Type
28 SERIAL 1 ERR
Fieldbus communication has timed out. Check for and correct:

Fault setup (2409 COMM FAULT FUNC and 2410 COMM FAULT TIME).

Communication settings (Group 31 or 32 as appropriate).

Poor connections and/or noise on line.
29 EFB CON FILE
Error in reading the configuration file for the fieldbus adapter.
30 FORCE TRIP
Fault trip forced by the fieldbus. See the fieldbus Users Manual.
31 EFB 1
Fault code reserved for the EFB protocol application.
The meaning is protocol dependent.
32 EFB 2
33 EFB 3
34 MOTOR PHASE
Fault in the motor circuit. One of the motor phases is lost.

Check for and correct:

Motor fault
Motor wiring, connections

Motor cable fault
Internal fault
35 OUTP WIRING
Error in power wiring suspected. Check for and correct:

Input power wired to drive output

Ground faults
101 SERF CORRUPT
Error internal to the drive. Contact your local factory
representative and report the error number.
102 SERF IITFILE
103 SERF MACRO
104 SERF EFBPROT
105 SERF BPFILE
201 DSP T1 OVERLOAD
Error internal to the drive. Contact your local factory
representative and report the error number.
202 DSP T2 OVERLOAD
203
204
205
206

DSP T3 OVERLOAD
DSP STACK ERROR
DSP REV ERROR
OMIO ID ERROR

Faults that indicate conflicts in the parameter settings are listed below.
1000 PAR HZRPM






1001 PAR PFCREFNG

1003 PAR AI SCALE

1004 PAR AO SCALE

118

Parameter values are inconsistent. Check for any of the following:


2001 MINIMUM SPEED > 2002 MAXIMUM SPEED.
2007 MINIMUM FREQ > 2008 MAXIMUM FREQ.
2001 MINIMUM SPEED / 9908 MOTOR NOM SPEED > 128 (or < -128).
2002 MAXIMUM SPEED / 9908 MOTOR NOM SPEED > 128 (or < -128).
2007 MINIMUM FREQ / 9907 MOTOR NOM FREQ > 128 (or < -128).
2008 MAXIMUM FREQ / 9907 MOTOR NOM FREQ > 128 (or < -128).
Parameter values are inconsistent. Check for the following:
2007 MINIMUM FREQ is negative.
Parameter values are inconsistent. Check for any of the following:
1503 TRANSDUCER MIN > 1502 TRANSDUCER MAX.
Parameter values are inconsistent. Check for any of the following:
1904 AO 1 MIN > 1905 AO 1 MAX.
1909 AO 2 MIN > 1910 AO 2 MAX.

FAULTS/ALARMS
Fault Fault Name
Code In Panel
1005 PAR PCU 2




1007 PAR FBUS

1009 PAR PCU 1





Description and Recommended Corrective Action


Parameter values for power control are inconsistent: Improper motor nominal
kVA or motor nominal power. Check for the following:
1.1 (1104 MOTOR NOM CURR * 1103 MOTOR NOM VOLT * 1.73 / PN) 2.6
Where: PN = 1000 * 1107 MOTOR NOM POWER (if units are kW)
or PN = 746 * 1107 MOTOR NOM POWER (if units are HP, e.g. in US)
Parameter values are inconsistent. Check for and correct:
A parameter is set for fieldbus control (e.g. 1201 START/STOP = Fieldbus),
but 3001 COMM PROT SEL = 0.
Parameter values for power control are inconsistent: Improper motor nominal
frequency or speed. Check for both of the following:
1 (60 * 1105 MOTOR NOM FREQ / 1106 MOTOR NOM SPEED 16
0.8 1106 MOTOR NOM SPEED / (120 * 1105 MOTOR NOM FREQ / Motor Poles)
0.992

Fault Resetting
The AQUAVAR can be configured to automatically reset certain faults. Refer to parameter
Group 24: Fault Functions and Group 25: Automatic Reset.
Warning! If an external source for start command is selected and it is active, the
AQUAVAR may start immediately after fault reset.
Flashing Red LED
To reset the drive for faults indicated by a flashing red LED:
Turn the power off for 5 minutes.
Red LED
To reset the drive for faults indicated by a red LED (on, not flashing), correct the problem and
do one of the following:
From the control panel: Press RESET
Turn the power off for 5 minutes.
NOTE: In some cases a fault reset soft key will appear on the display. Press this button to
reset, then press the start key.
When the fault has been removed, the motor can be started.
Fault History
For reference, the last three fault codes are stored in Group 01: VFD Signals. Specifically parameters 01160118. The Aquavar CPC stores additional fault data, which helps the operator
identify operating conditions at the time of fault. (Parameters 01190126).
To clear the fault history, go to PAR GROUPS 01, VFD SIGNALS. Press the SEL key. Down arrow
to 0116 LAST FAULT, then press the EDIT key. Next press the UP and DOWN arrow at the
same time until NO RECORD shows on the display. This clears all the faults in the history.

119

FAULTS/ALARMS
Correcting Alarms
The recommended corrective action for alarms is:
Determine if the Alarm requires any corrective action (action is not always required).
Use Alarm Listing below to find and address the root cause of the problem.
Press the reset key (when available) or turn the power off for at least 5 minutes.
Alarm Listing
The following table lists the alarms by code number and describes each.
Alarm
Code

Display Description

2001 Reserved
2002
2003
2004 DIR LOCK

The change in direction being attempted is not allowed. Either:


Do not attempt to change the direction of motor rotation.

2005
I/O COMM
Fieldbus communication has timed out. Check for and correct:

Fault setup (2411 COMM FAULT FUNC and 2412 COMM FAULT TIME).

Communication settings (Group 31 or 32 as appropriate).

Poor connections and/or noise on the line.
2006
AI1 LOSS
Analog Input 1 is lost, or value is less than the minimum setting.

Check:

Input source and connections

Parameter that sets the minimum (1604)
2007 TRANSDUCER Analog Input 2 is lost, or value is less than the minimum setting.
LOSS Check:

Transducer, connection and wiring

Input source and connections

Parameter that sets the minimum (1506)
2008 PANEL LOSS
Panel communication is lost and either:

Drive is in local control mode (the control panel displays LOC), or

Drive is in remote control mode (REM) and is parameterized to accept

start/stop, direction or reference from the control panel.

To correct check:

Communication lines and connections

Parameter 2401 KEYPAD FAILURE
2009
RESERVED

120

FAULTS/ALARMS
Alarm
Code

Display Description

2010 MOT
OVERTEMP

2011 UNDERLOAD


2012 MOTOR STALL

Motor is hot, based on either the drives estimate or on temperature feedback.


This alarm warns that a Motor Underload fault trip may be near. Check:
Check for overloaded motor, pump.
Motor load is lower than expected. This alarm warns that a Motor Underload
fault trip may be near. Check:
Motor and drive ratings match (motor is NOT undersized for the drive).
Motor is operating in the stall region. This alarm warns that a Motor Stall fault
trip may be near. Check motor connections.

2013
AUTORESET
(note 1)

2015
ALARM 2015

PUMP

PROTECT


2016
LOW WATER
2017
NOT USED
2023
E-STOP
FAULT

This alarm warns that the drive is about to perform an automatic fault reset,
which may start the motor.
To control automatic reset, use parameter Group 12 AUTOMATIC RESET.
Pump protection has been triggered via parameter 2403 (protection limit)
and 2404 (protection delay). This protection is enabled when the pump
reaches maximum frequency and cannot maintain system set point for the
specific delay time. Check for air entrainment, plugged impeller, blocked
suction, lack of NPSHa, pump run-out.
Check DI2 contact or suction switch continuity.
Check jumper / connection, between Terminal 10 and 15 (DI3).

121

MAINTENANCE (Frame Sizes R1-R6)


WARNING! Read Safety on page 7 before performing any maintenance on
the equipment. Ignoring the safety instructions can cause injury or death.

Maintenance Intervals
If installed in an appropriate environment, the drive requires very little maintenance. This table
lists the routine maintenance intervals recommended by CentriPro.
Maintenance

Interval

Depends on the dustiness of the


environment (every 612 months).

Instruction

Heatsink Temperature
Check and Cleaning

Main Cooling
Every five years
Fan Replacement

See Main Fan Replacement


on pages 122, 123, 126 and 127

Internal Enclosure
Every three years
Cooling Fan Replacement
(IP 54/UL Type 12 units)

See Internal Enclosure Fan


Replacement on page 123

Capacitor Change
Every ten years
(Frame size R5 and R6)

See Capacitors on page 124

Replace Battery in Advanced


Control Panel

See Battery on page 124

Every ten years

See Heatsink on page 122

Heatsink
The heatsink fins accumulate dust from the cooling air. Since a dusty heatsink is less efficient
at cooling the drive, overtemperature faults become more likely. In a normal environment
(not dusty, clean) check the heatsink annually, in a dusty environment check more often.
Clean the heatsink as follows (when necessary):
1. Remove power from drive
2. Remove the cooling fan (see section Main Fan Replacement below)
3. Blow clean compressed air (not humid) from bottom to top and simultaneously use a
vacuum cleaner at the air outlet to trap the dust.
Note: If there is a risk of the dust entering adjoining equipment, perform the cleaning in
another room.
4. Replace the cooling fan
5. Restore power

Main Fan Replacement


The drives main cooling fan has a life span of about 60,000 operating hours at maximum
rated operating temperature and drive load. The expected life span doubles for each 10 C
(18 F) drop in the fan temperature (fan temperature is a function of ambient temperatures
and drive loads).
Fan failure can be predicted by the increasing noise from fan bearings and the gradual rise
in the heatsink temperature in spite of heatsink cleaning. If the drive is operated in a critical
part of a process, fan replacement is recommended once these symptoms start appearing.
Replacement fans are available from the factory. Do not use other than factory specified spare
parts.
122

MAINTENANCE (Frame Sizes R1-R6)


Frame Size R1R4
To replace the fan:
1. Remove power from drive
2. Remove drive cover
3. For Frame Size:
R1, R2: Press together the retaining clips on the fan cover sides
and lift.
R3, R4: Press in on the lever located on the left side of the fan
mount and rotate the fan up and out.
4. Disconnect the fan cable.
5. Install the fan in reverse order
6. Restore power
Frame Size R5 and R6
To replace the fan:
1. Remove power from drive
2. Remove the screws attaching the fan
3. Disconnect the fan cable.
4. Install the fan in reverse order
5. Restore power

Internal Enclosure Fan Replacement


IP 54 / UL Type 12 enclosures have an additional internal fan
to circulate air inside the enclosure.
Frame Size R1 to R4
To replace the internal enclosure fan in frame sizes R1 to R4:
1. Remove power from drive
2. Remove the front cover
3. The housing that holds the fan in place has barbed retaining
clips at each corner. Press all four clips toward the center to
release the barbs.
4. When the clips/barbs are free, pull the housing up to remove
from the drive.
5. Disconnect the fan cable
6. Install the fan in reverse order
The fan air flow is up (refer to arrow on fan)
The fan wire harness is toward the front
The notched housing barb is located in the right-rear corner
The fan cable connects just forward of the fan at the top of
the drive
123

MAINTENANCE (Frame Sizes R1-R6)


Frame Size R5 and R6
To replace the internal enclosure fan in frame sizes R5 or R6:
1. Remove power from drive
2. Remove the front cover
3. Lift the fan out and disconnect the cable
4. Install the fan in reverse order
5. Restore power

Capacitors
The drive intermediate circuit employs several electrolytic capacitors. Their life span is from
35,00090,000 hours depending on drive loading and ambient temperature. Capacitor life
can be prolonged by lowering the ambient temperature.
It is not possible to predict a capacitor failure. Capacitor failure is usually followed by a input
power fuse failure or a fault trip. Contact factory if capacitor failure is suspected. Replacements for frame size R5 and R6 are available from the factory. Do not use other than factory
specified spare parts.

Control Panel
Cleaning
Use a soft damp cloth to clean the control panel. Avoid harsh cleaners which could scratch the
display window.
Battery
A battery is only used in control panels that have the clock function available and enabled.
The battery keeps the clock operating in memory during power interruptions. To remove the
battery, use a coin to rotate the battery holder on the back of the control panel. Replace the
battery with type CR2032.

124

MAINTENANCE (Frame Sizes R7-R8)


Layout
The layout stickers of the drive are shown below. The stickers show all possible components
concerning maintenance activities. Not all of them are present in each delivery.

Designation
Component

A49
Control Panel

A41
Motor Control and I/O Board (OMIO)

Y41
Cooling Fan
_
C Capacitors

125

MAINTENANCE (Frame Sizes R1-R6)


Heatsink
The heatsink fins pick up dust from the cooling air. The drive runs into overtemperature warnings and faults if the heatsink is not clean. In a normal environment (not dusty, not clean) the
heatsink should be checked annually, in a dusty environment more often.
Clean the heatsink as follows (when necessary):
1. Remove the cooling fan (see section Fan below).
2. Blow dry clean compressed air from bottom to top and simultaneously use a vacuum
cleaner at the air outlet to trap the dust. Note: Prevent dust from entering adjoining
equipment.
3. Replace the cooling fan

Fan
The life span of the cooling fan of the drive is about 50,000 (R7) and 60,000 (R8) hours. The
actual life span depends on the running time of the fan, ambient temperature and dust concentration. See the appropriate Aquavar CPC User Manual for the actual signal which indicates the running time of the cooling fan.
Replacement fans are available from CentriPro. Do not use other than factory specified spare
parts.

Replacing the Fan (R7)


1. Remove the upper front cover and disconnect the control panel cables.
2. Disconnect the discharging resistor wire.
4
3

3
3

DCDC+

2
7
3
8

5
3
3
3

126

DC+

DC-

MAINTENANCE (Frame Sizes R7-R8)


3. Remove the DC capacitor pack by undoing the black fixing screws.
4. Disconnect the fan supply wires (detachable terminal).
5. Disconnect the fan capacitor wires.
6. Undo the black fixing screws of the fan cassette.
7. Press the snap-on holders to release the side cover.
8. Lift from the handle and pull the fan cassette out.
9. Install the fan in reverse order to the above and replace the fan capacitor.

Replacing the Fan (R8)


1. Remove the upper front cover.
2. Remove the OMIO board.
3. Disconnect the fan capacitor and power supply wires. Replace the starting capacitor.
4. Undo the black fastening screws of the plastic side cover of the fan and lift the cover off.
5. Undo the black fastening screws of the fan.
6. Lift the fan out of the cabinet.
7. Install the fan in reverse order to the above.

127

MAINTENANCE (Frame Sizes R1-R6)


Capacitors
The drive intermediate circuit employs several electrolytic capacitors. Their life span is at
least 90,000 hours depending on the operating time of the drive, loading and ambient
temperature. Capacitor life can be prolonged by lowering the ambient temperature.
It is not possible to predict a capacitor failure. Capacitor failure is usually followed by damage
to the unit and an input cable fuse failure or a fault trip. Contact your CentriPro authorized
Aquavar CPC distributor or the factory.

Replacing the Capacitor Pack (R7)


Replace the capacitor pack as described in section Replacing the Fan (R7) on page 126.

Replacing the Capacitor Pack (R8)


1. Remove the upper front cover and the side plate equipped with control panel mounting slot.
2. Disconnect the discharging resistor wire.
3. Undo the fastening screws.
4. Lift the capacitor pack out.
5. Install the capacitor pack in reverse order to the above.

128

MAINTENANCE (Frame Sizes R7-R8)


LEDs
This table describes LEDs of the drive.

Where

OMIO Board

LED
Red (blinking)
Green

When the LED is lit


Drive in fault state.
The power supply on the board is OK.

Control Panel
Red
Mounting Platform
Green

Drive in fault state.


The main +24 V power supply for the control
panel and the OMIO board is OK.

OITF Board
V204 (green)

V309 (red)

V310 (green)

+5 V voltage of the board is OK.


Prevention of unexpected start is ON.
IGBT control signal transmission to the gate
driver control boards is enabled.

Control Panel
Cleaning
Use a soft damp cloth to clean the control panel. Avoid harsh cleaners which could scratch the
display window.
Battery
A battery is only used in Assistant Control Panels that have the clock function available and
enabled. The battery keeps the clock operating in memory during power interruptions.
The expected life for the battery is greater than ten years. To remove the battery, use a coin
to rotate the battery holder on the back of the control panel. Replace the battery with type
CR2032.

129

TECHNICAL DATA
Sizing
The current ratings are the same regardless of the supply voltage within one voltage range.
To achieve the rated motor power given in the table, the rated current of the drive must be
higher than or equal to the rated motor current.
Note 1: The maximum allowed motor shaft power is limited to 1.5 ATimes Rated HP. If
the limit is exceeded, motor torque and current are automatically restricted. The function
protects the input bridge of the drive against overload.
Note 2: The ratings apply in ambient temperature of 40 C (104 F).
Derating
The load capacity (current and power) decreases if the installation site altitude exceeds 1000
meters (3300 ft), or if the ambient temperature exceeds 40 C (104 F) or if 8 kHz switching
frequency (parameter 5001) is used.
Temperature Derating
In the temperature range +40 C50 C (+104 F122 F) the rated output current is decreased 1% for every 1 C (1.8 F) above +40 C (+104 F). The output current is calculated by
multiplying the current given in the rating table by the derating factor.
Example: If the ambient temperature is 50 C (+122 F) the derating factor is
100% - 1%/C x 10 C = 90% or 0.90.
The output current is then 0.90 x I2N or 0.90 x I2hd.
Altitude Derating
The derating is 1% for every 100 m (330 feet) above 3300 feet. If the installation site is higher
than 2000 m (6600 feet) above sea level, please contact the factory for assistance.
Single Phase Supply Derating
For 208240 Volt series drives, a single phase supply can be used. In that case, the derating
is 50%, for the maximum amps and corresponding power rating of the three phase drive at
208-230 Volt input.
Switching Frequency Derating
If the 8 kHz switching frequency (parameter 5001) is used, derate HP and current output to
80%.

130

TECHNICAL DATA
Cable Sizing/Ratings
208240 Volt Drives
The following tables provide current, horsepower, frame size and recommended cable sizes
for the Aquavar CPC.
CENTRIPRO AQUAVAR CPC


NEMA 1
Full
NORMAL

Output
Frame
Voltage Phase
Base
Load
DUTY

Cable
Size
Size2 Min. AWG1

Model
Amps HORSEPOWER
CPC20171 8.5
2
R1
14
CPC20241 12
3
R2
12
CPC20311 15.5
5
R2
12
CPC20461 23
7.5
R3
10
CPC20591 29.5
10
R3
8
230
1 CPC20881 44.0
15
R4
6
CPC21141 57.0
20
R4
4
CPC21431 71.5
25
R6
3
CPC21781 89.0
30
R6
2
CPC22211 110.5
40
R6
1/0
CPC22481 124.0
50
R6
2/0
CPC20121 11.8
3
R1
14
CPC20171 16.7
5
R1
10
CPC20241 24.2
7.5
R2
8
CPC20311 30.8
10
R2
8
CPC20461 46.2
15
R3
6
CPC20591 59.4
20
R3
4
230
3 CPC20751 74.8
25
R4
3
CPC20881 88.0
30
R4
2
CPC21141 114.0
40
R4
1/0
CPC21431 143.0
50
R6
3/0
CPC21781 178.0
60
R6
4/0
CPC22211 221.0
75
R6 300MCM
CPC22481 248.0
100
R6 350MCM

Input
Cable Size
Min. AWG1
10
8
8
6
4
2
1/0
3/0
4/0
300MCM
350MCM
14
10
8
8
6
4
3
2
1/0
3/0
4/0
300MCM
350MCM

(1) Recommended AWG Size based on NEC table 310.16, 40 C ambient, 90 C, UL type copper wire. For other
wire sizes or types, consult local, state or NEC codes.
(2) Frame sizes R7 and R8, the Aquavar CPC will have multiple conductor terminals for each phase. Consult
technical section (CABLE TERMINALS).

131

TECHNICAL DATA
Cable Sizing/Ratings
380480 Volt Drives
The following table provides Aquavar CPC rating information and
recommended wire sizing for the input and output cables.
CENTRIPRO AQUAVAR CPC


NEMA 1
Full
NORMAL

Output
Input
Frame
Voltage Phase
Base
Load
DUTY

Cable
Size
Cable
Size
Size2 Min. AWG1 Min. AWG1

Model
Amps HORSEPOWER
CPC40061 6.9
3
R1
14
14
CPC40081 8.8
5
R1
14
14
CPC40121 11.9
7.5
R1
14
14
CPC40151 15.4
10
R2
12
12
CPC40231 23
15
R2
12
12
CPC40311 31
20
R3
10
8
CPC40381 38
25
R3
8
8
CPC40451 45
30
R3
8
6
CPC40591 59
40
R4
6
4
CPC40721 72
50
R4
4
3
CPC40771 77
60
R4
4
3
460
3 CPC40971 97
75
R4
3
1
CPC41251 125
100
R5
1
2/0
CPC41571 157
125
R6
2/0
3/0
CPC41801 180
150
R6
3/0
4/0
CPC42451 245
200
R7 350MCM 350MCM

CPC43161
316
250
R7
2 X 250MCM 2 X 250MCM

CPC43681
368
300
R8
2 X 300MCM 2 X 300MCM

CPC44141
414
350
R8
2 X 400MCM 2 X 400MCM

CPC44861
486
400
R8
2 X 500MCM 2 X 500MCM

CPC45261
526
450
R8
2 X 350MCM 2 X 350MCM

CPC46021
602
500
R8
2 X 500MCM 2 X 500MCM

CPC46451
645
550
R8
2 X 500MCM 2 X 500MCM
(1) Recommended AWG Size based on NEC table 310.16, 40 C ambient, 90 C, UL type copper wire. For other
wire sizes or types, consult local, state or NEC codes.
(2) Frame sizes R7 and R8, the Aquavar CPC will have multiple conductor terminals for each phase. Consult
technical section (CABLE TERMINALS) for maximum wire diameter and torque values.

132

TECHNICAL DATA
Fuse Sizing/Ratings
208240 Volt Drives
Branch circuit protection must be provided by the end user, electrical contractor or distributor, sized per local, state or local National Electrical Codes. Recommendations for fused
circuit protection are in the following tables.
CENTRIPRO AQUAVAR CPC


NEMA 1
Full
NORMAL

Input
Frame
Fuse Type3
Voltage Phase
Base
Load
DUTY
Current
Size
JJN

Model
Amps HORSEPOWER
Amps
CPC20171 8.5
2
R1 17.3
20
CPC20241 12
3
R2 24.5
30
CPC20311 15.5
5
R2
31.6
40
CPC20461 23
7.5
R3 46.9
60

CPC20591
29.5 10 R3
60.2 70
230
1 CPC20881 44.0
15
R4
89.8
110
CPC21141 57.0
20
R4 116.3
150
CPC21431 71.5
25
R6 145.9
175
CPC21781 89.0
30
R6 181.6
225
CPC22211 110.5
40
R6
225.4
300
CPC22481 124.0
50
R6
252.9
300
CPC20121 11.8
3
R1
12.0
15
CPC20171 16.7
5
R1
17.0
25
CPC20241 24.2
7.5
R2
24.7
30

CPC20311
30.8 10 R2
31.4 40

CPC20461
46.2 15 R3
47.1 60

CPC20591
59.4 20 R3
60.6 70

230
3
CPC20751
74.8 25 R4
76.3 90
CPC20881 88.0
30
R4
89.8
110
CPC21141 114.0
40
R4
116.3
150
CPC21431 143.0
50
R6
145.9
175
CPC21781 178.0
60
R6
181.6
225
CPC22211 221.0
75
R6
225.4
300

CPC22481
248.0 100 R6
252.9 300
(3) UL Class T fuses are recommended for short circuit protection. Very fast acting Bussmann* T-tron type
JJN and JJS are shown in the Aquavar CPC tables. Other manufaturers are acceptable if they meet fuse
requirements.
* Bussmann is a registered trademark of Cooper Industries Inc.

133

TECHNICAL DATA
Fuse Sizing/Ratings
380480 Volt Drives
The following table provides Aquavar CPC rating information and recommended fuse sizing
for the input short circuit protection. Branch circuit protection must be provided by the end
user, contractor or distributor. Sized according to local or applicable NEC codes.
CENTRIPRO AQUAVAR CPC


NEMA 1
Full
NORMAL

Input
Frame
Fuse Type3
Voltage Phase
Base
Load
DUTY
Current
Size
JJN

Model
Amps HORSEPOWER
Amps
CPC40061 6.9
3
R1
7.0
10
CPC40081 8.8
5
R1
9.0
15
CPC40121 11.9
7.5
R1
12.1
15

CPC40151
15.4 10 R2
15.7 20
CPC40231 23
15
R2 23.5
30
CPC40311 31
20
R3 31.6
40
CPC40381 38
25
R3 38.8
45
CPC40451 45
30
R3 44.9
60
CPC40591 59
40
R4 60.2
70
CPC40721 72
50
R4 73.4
90
CPC40771 77
60
R4 78.5
90
460
3 CPC40971 97
75
R4
98.0
125
CPC41251 125
100
R5 126.5
150
CPC41571 157
125
R6 160.1
200
CPC41801 180
150
R6 183.6
225
CPC42451 245
200
R7 250.0
300
CPC43161 316
250
R7 322.3
400
CPC43681 368
300
R8 375.4
450
CPC44141 414
350
R8 422.3
500
CPC44861 486
400
R8 495.8
600
CPC45261 526
450
R8 536.5
800
CPC46021 602
500
R8 614.0
800
CPC46451 645
550
R8 658.0
800
(3) UL Class T fuses are recommended for short circuit protection. Very fast acting Bussmann* T-tron type
JJN and JJS are shown in the Aquavar CPC tables. Other manufaturers are acceptable if they meet fuse
requirements.

134

TECHNICAL DATA
Cable Terminals (Frames R1-R6)
Mains and motor cable maximum sizes (per phase) accepted at the cable
terminals and the tightening torques are listed below.

U1, V1, W1
Earthing PE
Control Wire


U2, V2, W2
Ground
Frame

Maximum Torque Maximum Torque Maximum Torque
Size

Wire Size
Wire Size
Wire Size
mm2 AWG Nm lb-ft mm2 AWG Nm lb-ft mm2 AWG Nm lb-ft
R1
6
8 1.4 1.0 4 10 1.4 1.0

R2 10
6
1.4
1.0
10
8
1.4
1.0

R3 25
3
1.8
1.3
16
6
1.8
1.3
2

2.0 1.5 1.5 16 0.4 0.3

R4

50 1/0 2.0 1.5 35


R5

70 2/0 15 11.1 70 2/0 15 11.1

R6 185 350 40 29.5 95 4/0 8 5.9


MCM

Cable Terminals (Frames R7-R8)


Mains and motor cable maximum sizes (per phase) accepted at the cable terminals and the
tightening torques are listed below.

U1, V1, W1, U2, V2, W2
Earthing PE

Number


Frame
Cable
Tightening
Tightening

of holes


Size
Diameter Screw Screw
Torque
Torque
per

phase mm in Nm lb-ft Nm lb-ft


R7
R8

2
3

58
58

2.28
2.28

M12 5075 3555


M12 5075 3555

M8
M8

1522 1016
1522 1016

NOTE: Maximum AWG size for R7 Frame is (2) x 500MCM.



Maximum AWG size for R8 Frame is (3) x 500MCM.

135

TECHNICAL DATA
Input Power (Mains) Connection

Input Power (Mains) Connection Specifications



Voltage (U1)

208/220/230/240 VAC 3-phase (1-phase) +10%-15% for CPC2XXXX.


400/415/440/460/480 VAC 3-phase +10%-15% for CPC4XXXX.

Prospective Short-Circuit
Current (IEC 629)

Maximum allowed prospective short-circuit current in the supply is


65 kA in a second providing that the mains cable of the drive is
protected with appropriate fuses. US: 65,000 AIC.

Frequency

4863 Hz

Imbalance

Max. 3% of nominal phase to phase input voltage.

Fundamental Power
Factor (cos phi1)

0.98 (at nominal load)

Cable Temperature
Rating

90 C (194 F) rating minimum

Motor Connection

Motor Connection Specifications

Voltage (U2) 0U1, 3-phase symmetrical, Umax at the field weakening point.
Frequency
0500 Hz
Frequency Resolution
0.01 Hz
Current
See Ratings on pages 131-134
Power Limit
1.5 x Rated HP
Field Weakening Point
1060 Hz
Switching Frequency
Selectable: 1, 4 or 8 kHz
Cable Temperature
90 C (194 F) rating minimum
Rating


Maximum Motor Cable Length
Frame Size

fsw = 1 or 4 kHz
fsw = 8 kHz
Maximum Motor
R1
100 m
50 m
Cable Length
R2 - R4
200 m
100 m

R5 - R6
300 m
150 m

R7 - R8
300 m
NA

WARNING! Using a motor cable longer than specified in the chart above may cause
permanent damage to the drive or motor.
WARNING! Use of an output load filter or reactor is required when motor leads
exceed the above recommendations. Consult motor manufacturer on required use
of inverter drives.

136

TECHNICAL DATA
Control Connection

Control Connection Specifications

Analog Inputs
and Outputs

See table heading Hardware Description on page 29.

Digital Inputs

Digital input impedance 1.5 k. Maximum voltage for digital


inputs is 30 V.




Relays
(Digital Outputs)


Maximum contact voltage: 30 V DC, 250 V AC


Maximum contact current / power: 6 A, 30 V DC; 1500 VA, 250 V AC
Maximum. continuous current: 2 A rms (cos = 1), 1 A rms
(cos = 0.4)
Minimum load: 500 mW (12 V, 10 mA)
Contact material: Silver-nickel (AgN)
Isolation between relay digital outputs, test voltage:
2.5 kV rms, 1 minute

Cable Specifications

See Control Cables on page 17.

Efficiency (Frames R1-R8)


Approximately 98% at nominal power level.

Cooling (Frames R1-R6)



Method

Requirement

Cooling Specifications
Internal fan, flow direction from bottom to top.
Free space around the unit:
200 mm (8 in) above and below the unit.
25 mm (1 in) along each side of the unit.

137

TECHNICAL DATA
Cooling (Frames R7-R8)
Installation Procedure
Choose the mounting orientation (a, b, c or d).
a)

b)

c)
Lifted from above

Symbols:
required free space
air inlet surface
wall fixing point (recommended)
control panel mounting slot


Required Free Space Around the Unit for
Frame Mounting
Mounting, Maintenance, Service and Cooling*
Size Orientation
Front
Side
Above
mm in mm in mm in

a,d
500
20


200
7.9


b


500
20
200
7.9
R7


lifting lifting
c


200**
7.9**
space space


a,d
600
24


300
12


b


600
24
300
12
R8


lifting lifting
c


300**
12**
space space

* Space for the installer not included.
** Space for the fan and capacitor replacement not included.

Mounting orientations a and b


Make holes in the wall (recommended):
1. Lift the unit against the wall into the mounting place.
2. Mark the locations for the two fixing points in the wall.
3. Mark the bottom edges of the unit to the floor.

138

TECHNICAL DATA
Air Flow, 380480 Volt Drives
The following table lists heat loss and air flow data for 380480 Volt drives.
CENTRIPRO AQUAVAR CPC


NEMA 1
Full
NORMAL

Heat Loss Air
Frame
Voltage Phase
Base
Load
DUTY
Flow
Size

Model
Amps HORSEPOWER
Watts BTU/HR CFM
CPC40061 6.9
3
R1 97 331 26
CPC40081 8.8
5
R1 127 433 26
CPC40121 11.9
7.5
R1 172 587 26
CPC40151 15.4
10
R2 232 792 52
CPC40231 23
15
R2 337 1150 52
CPC40311 31
20
R3 457 1560 79
CPC40381 38
25
R3 562 1918 79
CPC40451 45
30
R3 667 2276 165
CPC40591 59
40
R4 907 3096 165
CPC40721 72
50
R4 1120 3820 165
CPC40771 77
60
R4 1295 4420 168
460
3 CPC40971 97
75
R4 1440 4915 168
CPC41251 125
100
R5 1940 6621 239
CPC41571 157
125
R6 2310 7884 239
CPC41801 180
150
R6 2810 9590 239
CPC42451 245
200
R7 3850 13144 319
CPC43161 316
250
R7 6850 23386 319
CPC43681 368
300
R8 6850 23386 721
CPC44141 414
350
R8 7850 26800 721
CPC44861 486
400
R8 7850 26800 721
CPC45261 526
450
R8 7600 25946 721
CPC46021 602
500
R8 8100 27653 721
CPC46451 645
550
R8 9100 31067 721

139

TECHNICAL DATA
Air Flow, 208240 Volt Drives
The following table lists heat loss and air flow data for 208240 Volt drives.
CENTRIPRO AQUAVAR CPC


NEMA 1
Full
NORMAL

Heat Loss Air
Frame
Voltage Phase
Base
Load
DUTY
Flow
Size

Model
Amps HORSEPOWER
Watts BTU/HR CFM
CPC20171 8.5
2
R1 161 551 26
CPC20241 12
3
R2 227 776 52
CPC20311 15.5
5
R2 285 373 52
CPC20461 23
7.5
R3 420 1434 79
CPC20591 29.5
10
R3 536 1829 79
230
1 CPC20881 44.0
15
R4 786 2685 165
CPC21141 57.0
20
R4 1014 3463 165
CPC21431 71.5
25
R6 1268 4431 238
CPC21781 89.0
30
R6 1575 5379 238
CPC22211 110.5
40
R6 1952 6666 238
CPC22481 124.0
50
R6 2189 7474 238
CPC20121 11.8
3
R1 116 404 26
CPC20171 16.7
5
R1 161 551 26
CPC20241 24.2
7.5
R2 227 776 52
CPC20311 30.8
10
R2 285 373 52
CPC20461 46.2
15
R3 420 1434 79
CPC20591 59.4
20
R3 536 1829 79
230
3 CPC20751 74.8
25
R4 671 2290 165
CPC20881 88.0
30
R4 786 2685 165
CPC21141 114.0
40
R4 1014 3463 165
CPC21431 143.0
50
R6 1268 4431 238
CPC21781 178.0
60
R6 1575 5379 238
CPC22211 221.0
75
R6 1952 6666 238
CPC22481 248.0
100
R6 2189 7474 238

140

TECHNICAL DATA
Dimensions and Weights
Frames R1-R6
The dimensions and mass for the AQUAVAR depend on the frame size and enclosure type.
If unsure of frame size, first, find the Type code on the drive labels. Then look up that type
code in the Technical Data on page 142, to determine the frame size. A complete set of dimensional drawings for AQUAVAR drives is located in the Technical Data section.
Units with UL Type 1 Enclosures
Outside Dimensions

UL Type 1 Dimensions for each Frame Size



R1 R2 R3 R4 R5 R6
Ref.
mm in mm in mm in mm in mm in mm in




W
H
H2
H3
D

125 4.9 125 4.9 203 8.0 203 8.0 265 10.4 300 11.8
330 13.0 430 16.9 490 19.3 596 23.4 602 23.7 700 27.6
315 12.4 415 16.3 478 18.8 583 23.0 578 22.8 698 27.5
369 14.5 469 18.5 583 23.0 689 27.1 739 29.1 880 34.6
212 8.3 222 8.7 231 9.1 262 10.3 286 11.3 400 15.8

NOTE: Enclosures are standard NEMA 1, indoor use only.

141

TECHNICAL DATA
Frames R1-R6
Mounting Dimensions

UL Type 1 Dimensions for each Frame Size



R1 R2 R3 R4 R5 R6
Ref.
mm in mm in mm in mm in mm in mm in
W1* 98.0 3.9 98.0 3.9 160 6.3 160 6.3 238 9.4 263 10.4
W2*




98.0 3.9 98.0 3.9


H1* 318 12.5 418 16.4 473 18.6 578 22.8 588 23.2 675 26.6

a
5.5 0.2 5.5 0.2 6.5 0.25 6.5 0.25 6.5 0.25 9.0 0.35

b 10.0 0.4 10.0 0.4 13.0 0.5 13.0 0.5 14.0 0.55 14.0 0.55

c 5.5 0.2 5.5 0.2 8.0 0.3 8.0 0.3 8.5 0.3 8.5 0.3

d 5.5 0.2 5.5 0.2 6.5 0.25 6.5 0.25 6.5 0.25 9.0 0.35
* Center to center dimension.

Weight

UL Type 1 Weight for each Frame Size


R1 R2 R3 R4 R5 R6

kg lb. kg lb. kg lb. kg lb. kg lb. kg lb.
6.1 13.4 8.9 19.5 14.7 32.4 22.8 50.2 37 82 78 176

142

TECHNICAL DATA
Units with IP 54 / UL Type 12 Enclosures
Outside Dimensions

IP 54 / UL Type 12 Dimensions for each Frame Size



R1 R2 R3 R4 R5 R6
Ref.
mm in mm in mm in mm in mm in mm in



W
W2
H3
D

215 8.5 215 8.5 257 10.1 257 10.1 369 14.5 410 16.1
225 8.9 225 8.9 267 10.5 267 10.5 369 14.5 410 16.1
441 17.4 541 21.3 604 23.8 723 28.5 776 30.5 924 36.4
238 9.37 245 9.6 276 10.9 306 12.0 309 12.2 423 16.6

Mounting Dimensions
Mounting dimensions are the same as for the IP 21 / UL Type 1 Enclosure. See Mounting
Dimensions on page 144.
Weight

IP 54 / UL Type 12 Weight for each Frame Size


R1 R2 R3 R4 R5 R6

kg lb. kg lb. kg lb. kg lb. kg lb. kg lb.
8.4 18.6 11.5 25.4 18.1 40.0 26.6 58.7 42 93 86 190

143

E1

Top View

E1

TECHNICAL DATA

E2
X2

Weights and Dimensions

W2

Frames R7-R8
E1

Top View

E1

E2
X2

H1
D

W2

H1

NEMA 1 Enclosure

H1
W2 Depth Weight E1
E2
Frame
mm in mm in mm in kg lb. mm in mm in

R7

R8 2130 83.86 800 31.5 585 23.03 375 827 92 3.62 250 9.84

1503 59.17 609 23.98 495 19.49 195 430 92 3.62 250 9.84

Drawing is not for engineering purposes.

Degrees of Protection
Available enclosures:
IP 21 / UL Type 1 Enclosure. The site must be free of airborne dust, corrosive gases or
liquids, and conductive contaminants such as condensation, carbon dust and metallic particles. Indoor use only.
IP 54 / UL Type 12 Enclosure. This enclosure provides protection from airborne dust and
light sprays or splashing water from all directions. Indoor use only.
UL Type 3R- Enclosures are intended for outdoor use to provide a degree of protection
from falling rain. Undamaged by the formation of ice on the enclosure. May be cooled
by forced air and louvers for vents. This rating is met by placing the drive into a NEMA 3R
Enclosure.
Compared to the IP 21 / UL Type 1 Enclosure, the IP 54 / UL Type 12 Enclosure has:
The same internal plastic shell as the IP 21 Enclosure.
A different outer plastic cover.
An additional internal fan to improve cooling.
Larger dimensions.
The same rating (does not require a derating).
Plastic gasketed cover for keypad.

144

TECHNICAL DATA
Ambient Conditions
The following table lists the AQUAVAR environmental requirements.
Ambient Environment Requirements

Storage and Transportation
Installation Site

in the protective package

01000 m (03,300 ft)


Altitude1

10002000 m (3,3006,600 ft)


if PN and I2 derated 1% every
100 m above 1000 m
(300 ft above 3,300 ft).

Ambient
Temperature2

-1540 C (5104 F)
Max. 50 C (122 F) if PN and I2
derated to 90%.

Relative humidity

< 95% (non-condensing)




Contamination
levels

No conductive dust allowed.


The ACS550 should be installed
in clean air according to
enclosure classification.

Storage
No conductive dust allowed.
Chemical gases: Class 1C2
Solid particles: Class 1S2

(IEC 721-3-3)


Cooling air must be clean, free


from corrosive materials and free
from electrically conductive dust.
Chemical gases: Class 3C2
Solid particles: Class 3S2

Transportation
No conductive dust allowed.
Chemical gases: Class 2C2
Solid particles: Class 2S2


Sinusoidal
Vibration

Mechanical conditions: Class 3M4


(IEC 60721-3-3)
29 Hz 3.0 mm (0.12 in)
9200 Hz 10 m/s2 (33 ft/s2)

In accordance with ISTA-1A and 1B


specifications.

-4070 C (-40158 F)

Shock
Not allowed
(IEC 68-2-29)

Maximum 100 m/s2 (330 ft/s2),


11ms (36 ft)




Free Fall3
Not allowed


76 cm (30 in), frame size R1


61cm (24 in), frame size R2
46 cm (18 in), frame size R3
31 cm (12 in), frame size R4
25 cm (10 in), frame size R5
15 cm (6 in), frame size R6

(1) Consult factory above 6600 altitude.


(2) Derate drive one HP size from motor for higher temperatures (e.g. motor HP = 10 HP; use 15 HP Aquavar in
temperature up to 122 F).
(3) R7-R8 not allowed for free fall any distance.

145

TECHNICAL DATA
Materials
Materials Specifications

Drive
Enclosure

Package






Disposal




PC/ABS 2.5 mm, color NCS 1502-Y (RAL 90021 / PMS 420 C and 425 C)
Hot-dip zinc coated steel sheet 1.52 mm, thickness of coating 100 micrometers.
Cast aluminium AlSi
Extruded aluminium AlSi
Corrugated board (drives and option modules), expanded polystyrene.
Plastic covering of the package: PE-LD, bands PP or steel.
The drive contains raw materials that should be recycled to preserve energy and natural
resources. The package materials are environmentally compatible and recyclable. All
metal parts can be recycled. The plastic parts can either be recycled or burned under
controlled circumstances, according to local regulations. Most recyclable parts are
marked with recycling marks.
If recycling is not feasible, all parts excluding electrolytic capacitors and printed circuit
boards can be landfilled. The DC capacitors contain electrolyte and the printed circuit
boards contain lead, both of which will be classified as hazardous waste within the EU.
They must be removed and handled according to local regulations.
For further information on environmental aspects and more detailed recycling
instructions, please contact your local recycler.

Applicable Standards
The drive complies with the following standards. The compliance with the European Low Voltage Directive is verified according to standards EN 50178 and EN 60204-1.
Applicable Standards
EN 50178 (1997)
EN 60204-1
(1997)



EN 60529: 1991
(IEC 529), IEC
60664-1 (1992)
EN 61800-3
(1996) +
Amendment
A11 (2000)
UL 508C

146

Electronic equipment for use in power installations.


Safety of machinery. Electrical equipment of machines. Part 1: General requirements.
Provisions for compliance: The final assembler of the machine is responsible for
installing:
An emergency-stop device
A supply disconnecting device
Degrees of protection provided by enclosures (IP code).

EMC product standard including specific test methods.

UL Standard for Safety, Power Conversion Equipment, second edition.

TECHNICAL DATA
UL Markings
The AQUAVAR is suitable for use on a circuit capable of delivering not more than 65,000 RMS
symmetrical amperes, 480 V maximum. The AQUAVAR has an electronic motor protection
feature that complies with the requirements of UL 508C. When this feature is selected and
properly adjusted, additional overload protection is not required unless more than one motor
is connected to the drive or unless additional protection is required by applicable safety
regulations.
The drives are to be used in a controlled environment. See section Ambient Conditions on
page 145 for specific limits.
Liability Limits
The manufacturer is not responsible for:
Any costs resulting from a failure if the installation, commissioning, repair, alteration
or ambient conditions of the drive do not fultill the requirements specified in the
documentation delivered with the unit and other relevant documentation.
Units subjected to mususe, negligence or accident.
Units comprised of materials provided or designs stipulated by the purchaser.
In no event shall the manufacturer, its suppliers or subcontractors be liable for special,
indirect, incidental or consequential damages, losses or penalties.
If you have any questions concerning your product, please contact the local distributor or
CentriPro. The technical data, information and specifications are valid at the time of printing.
The manufacturer reserves the right to modifications without prior notice.

147

APPENDIX

PRESSURE TRANSDUCER
300 PSI 4-20 mA
P/N 9K515
(To order sensor with 200 inch (16 ft.) cable, use P/N 9K391)

Packard 3-pin
Metri-Pack
Series 150
Output
White
3/16 Dia
sphere of
silicon
grease at
base of
terminals

3.25
Snubber
added

+Supply
Brown

3
1

No
Connection

1/4 MNPT
0.875 HEX

LABEL
CentriPro
www.centripro.com

UL

US

0300SB

PART#: 9K515
LISTED
79BN
PRESSURE: 0-300PSI
INPUT: 10-28VDC
MADE IN USA
OUTPUT: 4-20mA
SERIAL #: AXXXXXX
YYMMDD

SPECIFICATIONS
Parameter
Value
Pressure Range
300 PSI
Output (0 - 100%)
4-20 mA
Supply Voltage
10-28 VDC
Burst Pressure Minimum
5x rated
Pressure Overload Maximum
2x rated
Supply Current Maximum
<22mA
Pressure Cycles Minimum
100 million
Accuracy (combined lin/hyst/rep)
< 0.5% BFSL
Zero Offset Maximum
< 1% of FS / C
Span Tolerance Maximum
< 2% of FS / C
148

Parameter
Value
Operating Temp. Range
-40 to 85C
Compensation Temp. Range
0 to 55C
Zero Thermal Error Maximum
< .035% of FS
Span Thermal Error Maximum
< .035% of FS
Pressure Port Material
17-4 PH
Housing Material
304 stainless steel
Isolation Voltage Minimum
500VDC
Seal Material
N/A


UL cUL 508
Listings

CE ENG/326

K No.
9K514
9K515
9K516
9K517

Part No.
A00462C 1
A00462C 2
A00462C 3
A00462C 4

A00439C 4

A00439C 3

A00439C 2

A00439C 1

0-1000 PSI

0-500 PSI

0-300 PSI

0-150 PSI

Transducer Part
Pressure Range
No.

A00436C 360

Cable Part
No.

APPENDIX

Transducer Data/Specifications

149

150
A00436C 100
A00436C 50
A00436C 30
A00436C 16

100
50
30
16
(standard)

NOTE: Not available in 200 feet.

Drawing
Number
A (ft)

9K400

9K399

9K398

9K397

K No.

APPENDIX

Transducer Cable Specification

APPENDIX
Spare Parts List

Part Number

Description

64732048

Control Panel (Keypad) Connector

CPCCPA

Control Panel (Keypad)

OCAT01

Control Panel Extension Cable 8 ft.

CPCB01

Control Board (OMIO) fits all sizes.

OFAN KIT R1

Fan Kit, R1 Frame Size, Aquavar CPC

OFAN KIT R2

Fan Kit, R2 Frame Size, Aquavar CPC

OFAN KIT R3

Fan Kit, R3 Frame Size, Aquavar CPC

OFAN KIT R4

Fan Kit, R4 Frame Size, Aquavar CPC

OFAN KIT R5

Fan Kit, R5 Frame Size, Aquavar CPC

OFAN KIT R6

Fan Kit, R6 Frame Size, Aquavar CPC

64391615

Fan Kit, R7 Frame Size, Aquavar CPC

64391658

Fan Kit, R8 Frame Size, Aquavar CPC

CPCEXTKIT

Control Panel Mounting Kit

151

CENTRIPRO LIMITED WARRANTY


This warranty applies to all Aquavar CPC controllers manufactured by Xylem, Inc.
Any part or parts found to be defective within the warranty period shall be replaced at no charge to the dealer during the warranty period. The warranty period shall exist
for a period of twenty-four (24) months from date of installation or thirty (30) months from date of manufacture, whichever period is shorter.
A dealer who believes that a warranty claim exists must contact the authorized CentriPro distributor from whom the controller was purchased and furnish complete details
regarding the claim. The distributor is authorized to adjust any warranty claims utilizing the CentriPro Customer Service Department.
The warranty excludes:
(a) Labor, transportation and related costs incurred by the dealer;
(b) Reinstallation costs of repaired equipment;
(c) Reinstallation costs of replacement equipment;
(d) Consequential damages of any kind; and,
(e) Reimbursement for loss caused by interruption of service.
For purposes of this warranty, the following terms have these definitions:
(1) Distributor means any individual, partnership, corporation, association, or other legal relationship that stands between CentriPro and the dealer in purchases,
consignments or contracts for sale of the subject controllers.
(2) Dealer means any individual, partnership, corporation, association, or other legal relationship which engages in the business of selling or leasing controllers to
customers.
(3) Customer means any entity who buys or leases the subject controllers from a dealer. The customer may mean an individual, partnership, corporation, limited
liability company, association or other legal entity which may engage in any type of business.

THIS WARRANTY EXTENDS TO THE DEALER ONLY.

Xylem Inc.
2881 East Bayard Street Ext., Suite A
Seneca Falls, NY 13148
Phone: (800) 453-6777
Fax: (888) 322-5877
www.centripro.com
CentriPro and Aquavar are trademarks of Xylem Inc. or one of its subsidiaries.
2012 Xylem Inc.

IM167 Revision 8

December 2013

You might also like