Busbar Protection 7SS85
Technical Data
Extract from manual C53000-G5040-C019-1, chapter 10
Energy Automation
i i
NOTE
For your own safety, please observe the warnings and safety instructions contained in this manual.
Disclaimer of Liability
This document has been subjected to rigorous technical
review before being published. It is revised at regular inter-
vals, and any modifications and amendments are included
in the subsequent issues. The content of this document
has been compiled for information purposes only. Although
Siemens AG has made best efforts to keep the document
as precise and up-to-date as possible, Siemens AG shall
not assume any liability for defects and damage which
result through use of the information contained herein.
This content does not form part of a contract or of business
relations; nor does it change these. All obligations of
Siemens AG are stated in the relevant contractual agree-
ments.
Siemens AG reserves the right to revise this document
from time to time.
Document version: C53000-G5040-C019-1.01
Release status: 09.2013
Version of the product described: V4.00
Copyright
Copyright Siemens AG 2013. All rights reserved.
The disclosure, duplication, distribution and editing of this
document, or utilization and communication of the content
are not permitted, unless authorized in writing. All rights,
including rights created by patent grant or registration of a
utility model or a design, are reserved.
Registered Trademarks
SIPROTEC
, DIGSI
, SIGUARD
, SIMEAS
and SICAM
Device manuals
Each device manual describes the functions and applications of a specific SIPROTEC 5 device. The
printed manual and the online help for the device have the same informational structure.
Hardware manual
The hardware manual describes the hardware building blocks and device combinations of the
SIPROTEC 5 device family.
Operating manual
The operating manual describes the basic principles and procedures for operating and assembling the
devices of the SIPROTEC 5 range.
SIPROTEC 5, Busbar Protection 7SS85 , Manual 3
C53000-G5040-C019-1, Release 09.2013
Product Information
The product information includes general information about conditions when preparing for operation.
This document is provided with each SIPROTEC 5 device.
Engineering Guide
The engineering guide describes the important steps in engineering with DIGSI 5. In addition, you learn
in the Engineering Guide how to load a projected configuration in a SIPROTEC 5 device and update the
device functionality of the SIPROTEC 5 device.
System catalog
The system catalog describes the SIPROTEC 5 system features.
Device catalogs
The device catalogs describe device-specific features such as functional scope, hardware and applica-
tions.
Indication of Conformity
This product complies with the directive of the Council of the European Communi-
ties on harmonization of the laws of the Member States relating to electromagnetic
compatibility (EMC Council Directive 2004/108/EC) and concerning electrical equip-
ment for use within specified voltage limits (Low Voltage Directive 2006/95/EC).
This conformity has been proved by tests performed according to the Council Direc-
tive in accordance with the generic standards EN 61000-6-2 and EN 61000-6-4 (for
EMC directive) and with the standard EN 60255-27 (for Low Voltage Directive) by
Siemens AG.
The device is designed and manufactured for application in an industrial environ-
ment.
The product conforms with the international standards of IEC 60255 and the
German standard VDE 0435.
Other Standards
IEEE Std C 37.90
This product is UL-certified with the values shown in the Technical data.
File E194016
[scpreful-070211-01.tif, 1, --_--]
Preface
4 SIPROTEC 5, Busbar Protection 7SS85 , Manual
C53000-G5040-C019-1, Release 09.2013
Additional Support
For questions about the system, please contact your Siemens sales partner.
Support
Our Customer Support Center provides a 24-hour service.
Phone: +49 (180) 524-8437
Fax: +49 (180) 524-2471
E-mail: [email protected]
Training Courses
Inquiries regarding individual training courses should be addressed to our Training Center:
Siemens AG
Siemens Power Academy TD
Humboldtstrae 59
90459 Nuremberg
Phone: +49 (911) 433-7415
Fax: +49 (911) 433-5482
E-mail: [email protected]
Internet: http://www.siemens.com/poweracademy
Safety Information
This manual is not a complete index of all safety measures required for operation of the equipment (module
or device). However, it comprises important information that must be followed for personal safety, as well as
to avoid material damage. Information is highlighted and illustrated as follows according to the degree of
danger.
!
DANGER
DANGER means that death or severe injury will result if the measures specified are not taken.
Comply with all instructions, in order to avoid death or severe injuries.
!
WARNING
WARNING means that death or severe injury may result if the measures specified are not taken.
Comply with all instructions, in order to avoid death or severe injuries.
!
CAUTION
CAUTION means that or medium-severe or slight injuries can occur if the specified measures are not
taken.
Comply with all instructions, in order to avoid moderate or minor injuries.
Preface
SIPROTEC 5, Busbar Protection 7SS85 , Manual 5
C53000-G5040-C019-1, Release 09.2013
NOTICE
NOTE means that property damage can result if the measures specified are not taken.
Comply with all instructions, in order to avoid property damage.
i i
NOTE
Important information about the product, product handling or a certain section of the documentation, which
must be given particular attention.
Qualified Electrical Engineering Personnel
Only qualified electrical engineering personnel may commission and operate the equipment (module, device)
described in this document. Qualified electrical engineering personnel in the sense of this manual are people
who can demonstrate technical qualifications as electrical technicians. These persons may commission,
isolate, ground and label devices, systems and circuits according to the standards of safety engineering.
Use as Prescribed
The equipment (device, module) may only be used for such applications as set out in the catalogs and the
technical description, and only in combination with third-party equipment recommended and approved by
Siemens.
Problem-free and safe operation of the product depends on the following:
Proper transport
The equipment must be grounded at the grounding terminal before any connections are made.
All circuit components connected to the power supply may be subject to dangerous voltage.
Hazardous voltages may be present in equipment even after the supply voltage has been disconnected
(capacitors can still be charged).
Equipment with exposed current-transformer circuits must not be operated. Before disconnecting the
equipment, ensure that the current-transformer circuits are short-circuited.
The limit values stated in the document may not be exceeded. This must also be considered during
testing and commissioning.
Preface
6 SIPROTEC 5, Busbar Protection 7SS85 , Manual
C53000-G5040-C019-1, Release 09.2013
Technical Data
10.1 General Device Data 336
10.2 Date and Time Synchronization 342
10.3 Busbar Differential Protection 343
10.4 Circuit-Breaker Failure Protection (1-Pole/3-Pole) 344
10.5 Circuit-Breaker Failure Protection( 3-pole) 345
10.6 Inherent Circuit-Breaker Failure Protection 346
10.7 End-fault Protection 347
10.8 External Tripping Busbar Section (Direct) 348
10.9 External Tripping Busbar Section (from Bay) 349
10.10 Differential Current Supervision 350
10.11 Zero-Crossing Supervision 351
10.12 Disconnector Supervision 352
10.13 Circuit-Breaker Supervision 353
10.14 Trip-Circuit Supervision 354
10.15 Supervision of the Device-Internal Analog-Digital Converters 355
10.16 Operational Measured Values 356
10.17 Analog Units Function Group 357
10.18 Temperature Supervision 358
10.19 Protection Interface and Protection Topology 359
10
SIPROTEC 5, Busbar Protection 7SS85 , Manual 335
C53000-G5040-C019-1, Release 09.2013
General Device Data
Analog Inputs
Current Inputs
All current, and power data are specified as RMS values.
Rated frequency f
rated
50 Hz, 60 Hz
Protection-class current
transformers
Rated current I
rated
Measuring range
5 A
1 A
500 A
100 A
Power consumption per
current circuit at rated
current
Approx. 0.1 VA
Thermal rating
(Protection-class current
transformers)
500 A for 1 s
150 A for 10 s
20 A continuously
25 A for 3 min
30 A for 2 min
Dynamic load-carrying
capacity
1250 A one half wave
Measuring-Transducer Inputs (via Module ANAI-CA-4EL)
Connector type 8-pin multiple contact strip
Differential current input channels 4
Measuring range -24 mA DC to +24 mA DC
Fault <0.5 % of measuring range
Input impedance 140
Conversion principle Delta-sigma (16 bit)
Permissible potential difference between channels DC 20 V
Electrical separation from ground/housing DC 700 V
Permissible overload 100 mA DC, continuously
Measurement repetition 200 ms
Supply Voltage
Integrated Power Supply
For modular devices, the following printed circuit-board assemblies have a power supply:
PS201 Power supply of the base module and of the 1st device row
PS203 Voltage supply of 2nd device row
CB202 Plug in module assembly with integrated power supply, for example, to accommodate communica-
tion modules
Permissible voltage
ranges
(PS201, PS203, CB202)
DC 19 V to DC 60 V DC 48 V to DC 300 V
AC 80 V to AC 265 V
Auxiliary rated voltage V
H
(PS201, PS203, CB202)
DC 24 V/DC 48 V DC 60 V/DC 110 V/ DC 125 V/ DC 220 V/
DC 250 V DC or
AC 100 V/AC 115 V/ AC 230 V, 50 Hz/60 Hz
10.1
10.1.1
10.1.2
Technical Data
10.1 General Device Data
336 SIPROTEC 5, Busbar Protection 7SS85 , Manual
C53000-G5040-C019-1, Release 09.2013
Integrated Power Supply
Permissible voltage
ranges (PS101)
DC 19 V to DC 60 V DC 48 V to DC 150 V DC 88 V to DC 300 V
AC 80 V to AC 265 V
Auxiliary rated voltage V
H
(PS101)
DC 24 V/DC 48 V DC 60 V/DC 110 V/
DC 125 V
DC 110 V/ DC 125 V/
DC 220 V/DC 250 V
or
AC 100 V/AC 115 V/
AC 230 V, 50 Hz/60 Hz
Superimposed alternating voltage, peak-to-peak,
IEC 60255-11
15% of the DC auxiliary rated voltage (applies only
to direct voltage)
Inrush current 18 A
Recommended external protection Miniature circuit breaker 6 A, characteristic C
according to IEC 60898
Internal fuse
DC 24 V to DC 48 V DC 60 V to DC 125 V DC 24 V to DC 48 V
AC 100 V to AC 230 V
PS101 4 A inert, AC 250 V,
DC 150 V,
UL recognized
SIBA type 179200 or
Schurter type SPT 5x20
2 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
PS201, PS203, CB202 2 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
Power consumption (life relay active)
DC AC 230 V/50 Hz AC 115 V/50 Hz
1/3 base module, non-
modular
Without plug-in modules
7.0 W 11.5 VA 15 VA
1/3 base module
Without plug-in modules
13 W 33 VA 24 VA
1/6 expansion module 3 W 6 VA 6 VA
1/6 plug-in module
assembly without plug-in
modules (modules
CB202)
3.5 W 14 VA 7 VA
Plug-in module for base
module or plug-in module
assembly (for example,
communication module)
<5 W <6 VA <6 VA
Stored-energy time for auxiliary voltage outage or
short circuit, modular devices
For V DC 24 V 50 ms
For V DC 110 V 50 ms
For V AC 115 V 50 ms
Stored-energy time for auxiliary voltage outage or
short circuit, non-modular devices
For V DC 24 V 20 ms
For V DC 60 V/DC 110 V 50 ms
For V AC 115 V 200 ms
Binary Inputs
Rated voltage
range
DC 24 V to DC 250 V (bipolar)
10.1.3
Technical Data
10.1 General Device Data
SIPROTEC 5, Busbar Protection 7SS85 , Manual 337
C53000-G5040-C019-1, Release 09.2013
Current
consumption,
excited
Approx. DC 0.6 mA to DC 1.8 mA (independent of the operating voltage)
Pickup time Approx. 3 ms
Dropout Time Approx. 4 ms
Switching
thresholds
Adjustable with DIGSI 5
Range 1 for 24 V, 48 V, and 60 V
Operating voltage
V
low
DC 10 V
V
high
DC 19 V
Range 2 for 110 V and 125 V
Operating voltage
V
low
DC 44 V
V
high
DC 88 V
Range 3 for 220 V and 250 V
Operating voltage
V
low
DC 88 V
V
high
DC 176 V
Maximum
permitted
voltage
DC 300 V
The binary inputs contain interference suppression capacitors. In order to ensure EMC, use the terminals
shown in the terminal diagrams/connection diagrams to connect the binary inputs to the common potential.
Relay Outputs
Standard Relay (Type S)
Switching capacity On: 1000 W/VA
Off: 30 VA; 40 W ohmic;
25 W/VA at L/R 40 ms
AC and DC contact voltage 250 V
Permissible current per contact (continuous) 5 A
Permissible current per contact (switching on and
holding)
30 A for 1 s (make contact)
Short-time current across closed contact 250 A for 30 ms
Total permissible current for contacts connected to
common potential
5 A
Switching time OOT (Output Operating Time)
Additional delay of the output medium used
10 ms
Rated data of the output contacts in accordance with
UL certification
DC 24 V, 8 A, general purpose
DC 48 V, 0.8 A, general purpose
DC 240 V, 0.1 A, general purpose
AC 240 V, 5 A, general purpose
AC 120 V, 1/3 hp
AC 250 V, 1/2 hp
B300
R300
Interference suppression capacitors across the
contacts
4.7 nF, 20 %, AC 250 V
Fast Relay (Type F)
Switching capacity On: 1000 W/VA
Off: 30 VA; 40 W ohmic;
25 W/VA at L/R 40 ms
10.1.4
Technical Data
10.1 General Device Data
338 SIPROTEC 5, Busbar Protection 7SS85 , Manual
C53000-G5040-C019-1, Release 09.2013
AC and DC contact voltage 250 V
Permissible current per contact (continuous) 5 A
Permissible current per contact (switching on and
holding)
30 A for 1 s (make contact)
Short-time current across closed contact 250 A for 30 ms
Total permissible current for contacts connected to
common potential
5 A
Switching time OOT (Output Operating Time)
Additional delay of the output medium used
Closing time, typical: 4 ms
Opening time, typical: 2 ms
Maximum: 5 ms
Rated data of the output contacts in accordance with
UL certification
AC 120 V, 8.5 A, General Purpose
AC 277 V, 6 A, General Purpose
AC 277 V, 0.7 hp
AC 347 V, 4.5 A, General Purpose
B300
R300
Interference suppression capacitors across the
contacts
4.7 nF, 20 %, AC 250 V
Supervision 2-channel activations with cyclic testing (only for
make contact)
High-Speed Relay with Semiconductor Acceleration (Type HS)
Switching capacity On/Off: 1000 W/VA
Contact voltage AC 200 V, DC 250 V
Permissible current per contact (continuous) 5 A
Permissible current per contact (switching on and
holding)
30 A for 1 s (make contact)
Short-time current across closed contact 250 A for 30 ms
Total permissible current for contacts connected to
common potential
5 A
Switching time OOT (Output Operating Time)
Additional delay of the output medium used
1 ms
Rated data of the output contacts in accordance with
UL certification
B150
Q300
Design Data
Masses
Device Dize
Ground of the Modular Devices
Type of construction 1/3 1/2 2/3 5/6 1/1
Flush-mounting device 4.8 kg 8.1 kg 11.4 kg 14.7 kg 18.0 kg
Surface-mounted device with
integrated on-site operation panel
7.8 kg 12.6 kg 17.4 kg 22.2 kg 27.0 kg
Surface-mounted device with
detached on-site operation panel
5.1 kg 8.7 kg 12.3 kg 15.9 kg 19.5 kg
Size Weight
Detached on-site operation panel 1/3 1.9 kg
Detached on-site operation panel 1/6 1.1 kg
10.1.5
Technical Data
10.1 General Device Data
SIPROTEC 5, Busbar Protection 7SS85 , Manual 339
C53000-G5040-C019-1, Release 09.2013
Device Dize
Ground of the Non-Modular Devices 7xx82
Type of construction 1/3
Flush-mounting device 3.7 kg
Dimensions of the Basic and 1/3 Models
Type of Construction (Maximum Dimensions) Width x Height x Depth (in Inches)
Flush-mounting device 145 mm x 268 mm x 228.5 mm (5.71 x 10.55 x 9)
Surface-mounted device with integrated on-site oper-
ation panel
145 mm x 314 mm x 337 mm (5.71 x 12.36 x 13.27)
Surface-mounted device with detached on-site opera-
tion panel
145 mm x 314 mm x 230 mm (5.71 x 12.36 x 9.06)
Dimensions of Device Rows
Type of
Construction
(Maximum
Dimensions)
Width x Height x Depth (in Inches)
Type of
construction
1/3 1/2 2/3 5/6 1/1
Flush-mounting
device
145 mm x 268
mm x 228.5 mm
220 mm x 268
mm x 228.5 mm
295 mm x 268
mm x 228.5 mm
370 mm x 268
mm x 228.5 mm
445 mm x 268
mm x 228.5 mm
Surface-
mounted device
with integrated
on-site operation
panel
145 mm x
314 mm x
337 (8.66 x
17.52 x 13.27)
220 x 314 x
337 (8.66 x
17.52 x 13.27)
295 x 314 x
337 (8.66 x
17.52 x 13.27)
370 x 314 x
337 (8.66 x
17.52 x 13.27)
445 mm x
314 mm x
337 (8.66 x
17.52 x 13.27)
Surface-
mounted device
with detached
on-site operation
panel
145 mm x
314 mm x
230 (14.57 x
12.36 x 9.06)
220 x 314 x
230 (14.57 x
12.36 x 9.06)
295 x 314 x
230 (14.57 x
12.36 x 9.06)
370 x 314 x
230 (14.57 x
12.36 x 9.06)
445 mm x
314 mm x
230 (14.57 x
12.36 x 9.06)
Expansion Module Dimensions
Type of Construction (Maximum Dimensions) Width x Height x Depth (in Inches)
Flush-mounting device 75 mm x 268 mm x 228.5 mm (2.95 x 10.55 x 9)
Surface-mounted device with integrated on-site oper-
ation panel
75 mm x 314 mm x 337 mm (2.95 x 12.36 x 13.27)
Surface-mounted device with detached on-site opera-
tion panel
75 mm x 314 mm x 230 mm (2.95 x 12.36 x 9.06)
Plug-In Module Dimensions
Type of Construction (Maximum Dimensions) Width x Height x Depth (in Inches)
USART-Ax-xEL, ETH-Bx-xEL 61 mm x 45 mm x 120.5 mm (2.4 x 1.77 x 4.74)
USART-Ax-xFO, ETH-Bx-xFO (without protective
cover)
61 mm x 45 mm x 132.5 mm (2.4 x 1.77 x 5.22)
ANAI-CA-4EL 61 mm x 45 mm x 119.5 mm (2.4 x 1.77 x 4.7)
Technical Data
10.1 General Device Data
340 SIPROTEC 5, Busbar Protection 7SS85 , Manual
C53000-G5040-C019-1, Release 09.2013
Minimum Bending Radii of the Connecting Cables Between the On-Site Operation Panel and the Base Module
Fiber-optic cable R =50 mm
Pay attention to the length of the cable protection
sleeve, which you must also include in calculations.
D-Sub cable R =50 mm (minimum bending radius)
Degree of Protection Compliant with IEC 60529
For equipment in the surface-mounting housing IP50
For equipment in the flush-mounting housing Front IP51
Back side of the modular devices IP50
Back side of the non-modular devices IP40
For operator protection IP2X for current terminals
IP1X for voltage terminals
Degree of pollution, IEC 60255-27 2
UL Note
Type 1 if mounted into a door or front cover of an enclosure.
Tightening Torques for Terminal Screws
Type of Line Current Terminal Voltage Terminal with
Spring-Loaded Termi-
nals
Voltage Terminal with
Screw Connection
Litz wire with ring-type lug 2.7 Nm No ring-type lug No ring-type lug
Stranded wires with boot-
lace ferrules or pin-type
lugs
2.7 Nm 1.0 Nm 0.6 Nm
Solid conductor, bare
(2 mm
2
)
2.0 Nm 1.0 Nm
i i
NOTE
Use copper cables only.
Technical Data
10.1 General Device Data
SIPROTEC 5, Busbar Protection 7SS85 , Manual 341
C53000-G5040-C019-1, Release 09.2013
Date and Time Synchronization
Date format DD.MM.YYYY (Europe)
MM/DD/YYYY (USA)
YYYY-MM-DD (China)
Time source 1, time source 2 None
IRIG-B 002(003)
IRIG-B 006(007)
IRIG-B 005(004) with extension according to
IEEE C37.118-2005
DCF77
PI (protection interface)
5
SNTP
IEC 60870-5-103
DNP3
Time zone 1, time zone 2 Local
UTC
Failure indication after 0 s to 3600 s
Time zone and daylight saving time Transfer of PC settings
Manually setting the time zones
Time zone offset with respect to GMT -720 min to 840 min
Switching over to daylight saving time Active
Inactive
Beginning of daylight saving time Input: day and time
End of daylight saving time Input: day and time
Offset daylight saving time -120 to 120 [steps of 15]
10.2
5
If provided
Technical Data
10.2 Date and Time Synchronization
342 SIPROTEC 5, Busbar Protection 7SS85 , Manual
C53000-G5040-C019-1, Release 09.2013
Busbar Differential Protection
General Differential Protection Setting Values
Rated object current I
rated obj.
100 to 50000 Increments of 1
Check Zone Setting Values
Threshold value I
diff
0.20 to 4.00 Increments of 0.01
Threshold value I
diff
(sensitive characteristic curve) 0.05 to 4.00 Increments of 0.01
Threshold value I
stab
(sensitive characteristic curve) 0.00 to 25.00 Increments of 0.01
Threshold value I
stab
(sensitive characteristic curve/
CBFP)
0.00 to 25.00 Increments of 0.01
Stabilization factor k 0.10 to 0.80 Increments of 0.01
General Busbar Section Setting Values
Threshold value I
diff
0.20 to 4.00 Increments of 0.01
Threshold value I
diff
(sensitive characteristic curve) 0.05 to 4.00 Increments of 0.01
Threshold value I
stab
(sensitive characteristic curve) 0.00 to 25.00 Increments of 0.01
Threshold value I
stab
(sensitive characteristic curve/
CBFP)
0.00 to 25.00 Increments of 0.01
Stabilization factor k 0.10 to 0.80 Increments of 0.01
Setting Values for Differential Current Supervision
Limiting value of current I/I
nObj
(I
nObj
=Rated object current)
0.05 to 0.80
0.25 to 4.00
Increments of 0.01
Increments of 0.01
Time Delay
for check zone and busbar-selective protection
1.00 s to 10.00 s Increments of 0.01
Operate Time
Minimum operate time High speed relay (type HS) approx. 3 ms
Fast relay (type F) approx. 7 ms
Frequency
Frequency range 50 Hz or 60 Hz; - 10 %, +5 %
Tolerances
Power 5 % of the setting value or 50 mA
k factor 5 % of the setting value
Times 5 % of the Setting Value or 50 ms
10.3
Technical Data
10.3 Busbar Differential Protection
SIPROTEC 5, Busbar Protection 7SS85 , Manual 343
C53000-G5040-C019-1, Release 09.2013
Circuit-Breaker Failure Protection (1-Pole/3-Pole)
Starting Conditions
For circuit-breaker failure protection 1-pole tripping externally, for example via binary input
3-pole tripping, for example via binary input
Setting Values
Phase-current threshold
values
For I
rated
=1 A 0.03 A to 100.00 A Increments of 0.01 A
For I
rated
=5 A 0.25 A to 500.00 A
Ground-current threshold
value
For I
rated
=1 A 0.03 A to 100.00 A Increments of 0.01 A
For I
rated
=5 A 0.25 A to 500.00 A
Supervision time of release signal 0.06 s to 1.00 s Increments of 0.01 s
Time Delays 0.05 s to 60.00 s Increments of 0.01 s
Dropout Ratios
Current threshold values About 0.95
Circuit-Breaker Supervision
Position supervision of the circuit-breaker auxiliary contacts
For 3-pole CB tripping 1 input each for make contact and break contact
For 1-pole CB tripping 1 input each for auxiliary contact per pole or
1 input for each series connection make contact and
break contact
i i
NOTE
The circuit-breaker failure protection can also work without the circuit-breaker auxiliary contacts stated.
Auxiliary contacts are required for circuit-breaker failure protection in cases where the current flow is
absent or too low for tripping (for example with a transformer or a Buchholz protection).
Times
Pickup time, in the case of an internal start
Pickup time, in the case of an external start
<1 ms
<5 ms
Dropout time for Unbalancing Operating Mode Approx. 2 ms
Dropout time
6
via the current-flow criterion, for sinus-
oidal quantities
<10.5 ms
Dropout time, via the current-flow criterion, under all
conditions
<15 ms
Dropout time, via circuit-breaker auxiliary-contact
criterion
<5 ms
Tolerances
Threshold values, dropout thresholds 2 % of the setting value or 1 % of the rated current
Times 1 % of the Setting Value or 10 ms
10.4
6
The dropout time is the time required by the CBFP function to detect that the CB is open. The time for mechanically switching a
contact is not included.
Technical Data
10.4 Circuit-Breaker Failure Protection (1-Pole/3-Pole)
344 SIPROTEC 5, Busbar Protection 7SS85 , Manual
C53000-G5040-C019-1, Release 09.2013
Circuit-Breaker Failure Protection( 3-pole)
Starting Conditions
For circuit-breaker failure protection 3-pole tripping, for example via binary inputs
Setting Values
Phase-current threshold
values
For I
rated
=1 A 0.03 A to 100.00 A Increments of 0.01 A
For I
rated
=5 A 0.15 A to 500.00 A
Ground-current threshold
value
For I
rated
=1 A 0.03 A to 100.00 A Increments of 0.01 A
For I
rated
=5 A 0.15 A to 500.00 A
Supervision time of release signal 0.06 s to 1.00 s Increments of 0.01 s
Time Delays 0.05 s to 60.00 s Increments of 0.01 s
Dropout Ratios
Current threshold values About 0.95
Circuit-Breaker Supervision
Position supervision of the circuit-breaker auxiliary contacts
For 3-pole CB tripping 1 input each for make contact and break contact
i i
NOTE
The circuit-breaker failure protection can also work without the circuit-breaker auxiliary contacts stated.
Auxiliary contacts are required for circuit-breaker failure protection in cases where the current flow is
absent or too low for tripping (for example with a transformer or a Buchholz protection).
Times
Pickup time, in the case of an internal start
Pickup time, in the case of an external start
<1 ms
<5 ms
Dropout time for Unbalancing operating mode Approx. 2 ms
Dropout time
7
via the current-flow criterion, for sinus-
oidal quantities
<10.5 ms
Dropout time, via the current-flow criterion, under all
conditions
<15 ms
Dropout time, via circuit-breaker auxiliary-contact
criterion
<5 ms
Tolerances
Threshold values, dropout thresholds 2 % of the setting value or 1 % of the rated current
Times 1 % of the Setting Value or 10 ms
10.5
7
The dropout time is the time required by the CBFP function to detect that the CB is open. The time for mechanically switching a
contact is not included.
Technical Data
10.5 Circuit-Breaker Failure Protection( 3-pole)
SIPROTEC 5, Busbar Protection 7SS85 , Manual 345
C53000-G5040-C019-1, Release 09.2013
Inherent Circuit-Breaker Failure Protection
Setting Values
Phase-current threshold
values
For I
rated
=1 A 0.03 A to 100.00 A Increments of 0.01 A
For I
rated
=5 A 0.15 A to 500.00 A
Ground-current threshold
value
For I
rated
=1 A 0.03 A to 100.00 A Increments of 0.01 A
For I
rated
=5 A 0.15 A to 500.00 A
Time delay T2 (3-pole) 0.05 s to 60 s Increments of 0.01 s
Operating Ranges
10 Hz <f <80 Hz Operating range
(normal behavior, normal tolerance values)
Tolerances
Threshold values 2 % of the setting value or 1 % of the rated current
Times 1 % of the Setting Value or 10 ms
10.6
Technical Data
10.6 Inherent Circuit-Breaker Failure Protection
346 SIPROTEC 5, Busbar Protection 7SS85 , Manual
C53000-G5040-C019-1, Release 09.2013
End-fault Protection
Setting Values
Phase-current threshold
values
For I
rated
=1 A 0.05 A to 20.00 A Increments of 0.01 A
For I
rated
=5 A 0.25 A to 100.00 A
Delay CB open 0.00 s to 15.00 s Increments of 0.01 s
Tripping delay 0.00 s to 60.00 s Increments of 0.01 s
Minimum trip duration 0.00 s to 60.00 s Increments of 0.01 s
Dropout Ratios
Current threshold values About 0.95
Tolerances
Threshold values, dropout thresholds 2 % of the setting value or 1 % of the rated current
Times 1 % of the setting value or 10 ms
10.7
Technical Data
10.7 End-fault Protection
SIPROTEC 5, Busbar Protection 7SS85 , Manual 347
C53000-G5040-C019-1, Release 09.2013
External Tripping Busbar Section (Direct)
Setting Values
Supervision Time 0.00 s to 60.00 s Increments of 0.01 s
Operate Time
Minimum operate time High speed relay (type HS) approx. 4 ms
Fast relay (type F) approx. 8 ms
Tolerance
Process tolerance for the supervision time 1 % of the Setting Value or 10 ms
10.8
Technical Data
10.8 External Tripping Busbar Section (Direct)
348 SIPROTEC 5, Busbar Protection 7SS85 , Manual
C53000-G5040-C019-1, Release 09.2013
External Tripping Busbar Section (from Bay)
Setting Values
Supervision Time 0.06 s to 1.00 s Increments of 0.01 s
Operating Ranges
10 Hz <f <80 Hz Operating range (normal behavior, normal tolerance
values)
Operate Time
Minimum operate time High speed relay (type HS) approx. 5 ms
Fast relay (type F) approx. 9 ms
Tolerances
Process tolerance for the supervision time 1 % of the Setting value or 10 ms
10.9
Technical Data
10.9 External Tripping Busbar Section (from Bay)
SIPROTEC 5, Busbar Protection 7SS85 , Manual 349
C53000-G5040-C019-1, Release 09.2013
Differential Current Supervision
You can find information on the technical data of the Differential current supervision in chapter 10.3 Busbar
Differential Protection .
10.10
Technical Data
10.10 Differential Current Supervision
350 SIPROTEC 5, Busbar Protection 7SS85 , Manual
C53000-G5040-C019-1, Release 09.2013
Zero-Crossing Supervision
Times
Pickup time 32 ms for f
rated
=50 Hz
27 ms for f
rated
=60 Hz
Setting Values
Threshold for time-to-zero supervision 0.5 * I
diff
busbar section
10.11
Technical Data
10.11 Zero-Crossing Supervision
SIPROTEC 5, Busbar Protection 7SS85 , Manual 351
C53000-G5040-C019-1, Release 09.2013
Disconnector Supervision
Setting Values
Disconnector runtime 1.00 s to 180.00 s Increments of 0.01 s
10.12
Technical Data
10.12 Disconnector Supervision
352 SIPROTEC 5, Busbar Protection 7SS85 , Manual
C53000-G5040-C019-1, Release 09.2013
Circuit-Breaker Supervision
Setting Values
Supervision time 1.00 s to 180.00 s Increments of 0.01 s
10.13
Technical Data
10.13 Circuit-Breaker Supervision
SIPROTEC 5, Busbar Protection 7SS85 , Manual 353
C53000-G5040-C019-1, Release 09.2013
Trip-Circuit Supervision
Setting Values
Number of monitored circuits per circuit-breaker function group 1 to 3
Operating mode per circuit With 1 binary input
With 2 binary inputs
Pickup and dropout time Approx. 1 s to 2 s
Adjustable indication delay with 1 binary input 1.00 s to 600.00 s Increments of 0.01 s
Adjustable indication delay with 2 binary inputs 1.00 s to 30.00 s Increments of 0.01 s
10.14
Technical Data
10.14 Trip-Circuit Supervision
354 SIPROTEC 5, Busbar Protection 7SS85 , Manual
C53000-G5040-C019-1, Release 09.2013
Supervision of the Device-Internal Analog-Digital Converters
Setting Values
Threshold Value 10 % of the rated value of the current transformer
Slope of the Characteristic
Curve
0.1
Times
Pickup time 0.25 ms (faster than the fastest protection function)
Dropout Time Approx. 100 ms (after response >1s continuous blocking)
Blockings
Blocked protection functions Busbar differential protection, busbar tripping by the circuit-breaker failure
protection
10.15
Technical Data
10.15 Supervision of the Device-Internal Analog-Digital Converters
SIPROTEC 5, Busbar Protection 7SS85 , Manual 355
C53000-G5040-C019-1, Release 09.2013
Operational Measured Values
Currents, Protection-Class Current Transformer
Feeder currents I
L1
, I
L2
, I
L3
, 3I
0
Differential currents (of all busbar sections and the
check zone) I
dL1
, I
dL2
, I
dL3
Stabilization currents (of all busbar sections and the
check zone) I
sL1
, I
sL2
, I
sL3
A secondary
% I
rated
% I
rated
Current range
Rated range
Measuring ranges
Frequency range
Measurement from 0.1 A to 25 A
1 A, 5 A
100 I
rated
47.5 Hz to 52.5 Hz at f
rated
=50 Hz
57.5 Hz to 62.5 Hz at f
rated
=60 Hz
Tolerance 0.3 % of the measured value or 0.1 % of I
rated
(larger
of the 2 values) in the above-mentioned ranges
Frequency
Frequency f Hz and % f
rated
Range 10 Hz to 80 Hz
Tolerance 20 mHz in the range f
rated
10% for rated variables
10.16
Technical Data
10.16 Operational Measured Values
356 SIPROTEC 5, Busbar Protection 7SS85 , Manual
C53000-G5040-C019-1, Release 09.2013
Analog Units Function Group
20 mA On. Ether.
Max. number of connected 20-mA units 4
Max. number of channels per 20-mA unit 12
20 mA On. Serial
Max. number of connected 20-mA units 4
Max. number of channels per 20-mA unit 12
RTD Unit (Ziehl TR1200)
Max. number of connected RTD units 4
Max. number of sensors per RTD unit 12
Sensor type Pt 100 as per EN 60751
RTD Unit (Ziehl TR1200) IP
Max. number of connected RTD units 4
Max. number of sensors per RTD unit 12
Sensor type Pt 100 as per EN 60751; connection of Ni 100 and
Ni 120 sensors possible. The measured values must
be converted in the evaluation unit.
Temperature Measured Values
Unit of measurement for temperature C or F, can be adjusted
Pt 100 -199 C to 850 C (-326 F to 1472 F)
Resolution 1 C or 1 F
Tolerance 0.5 % of the measured value 1 K
10.17
Technical Data
10.17 Analog Units Function Group
SIPROTEC 5, Busbar Protection 7SS85 , Manual 357
C53000-G5040-C019-1, Release 09.2013
Temperature Supervision
Setting Values
Pickup value -50C to 250C
-58F to 482F
Increments of 1C
Increments of 1F
Time delay 0 s to 60 s
or
Increments of 1 s
Dropout Conditions
Dropout differential 3 C or 6 F
Tolerances
Tripping delay 1 % of the setting value or 10 ms
Measured temperature value 0.5 % of the setting value or 1 C or 2 F
10.18
Technical Data
10.18 Temperature Supervision
358 SIPROTEC 5, Busbar Protection 7SS85 , Manual
C53000-G5040-C019-1, Release 09.2013
Protection Interface and Protection Topology
Setting Values
Mode On
Off
PPS Synchronization Telegr. and PPS
Telegr. or PPS
PPS synchronization off
Blocking of the asymmetrical
runtimes
Yes
No
Maximum signal runtime threshold 0.1 ms to 30.0 ms Increments of 0.1 ms
Maximum runtime difference 0.000 ms to 3.000 ms Increments of 0.001 ms
Failure indication after 0.05 s to 2.00 s Increments of 0.01 s
Failure indication after 0.0 s to 6.0 s Increments of 0.1 s
Max. error rate/h 0.000 % to 100.000 % Increments of 0.001 %
Max. error rate/min 0.000 % to 100.000 % Increments of 0.001 %
PPS failure indication after 0.5 s to 60.0 s Increments of 0.1 s
Transmission Rate
Direct connection:
Transmission rate 2048 kbit/s
Connection via communication networks:
Supported network interfaces G703.1 with 64 kBit/s
G703-T1 with 1.455 MBit/s
G703-E1 with 2.048 MBit/s
X.21 with 64 kBit/s or 128 kBit/s or 512 kBit/s
Pilot wires with 128 kbit/s
Transmission rate 64 kBit/s at G703.1
1.455 MBit/s at G703-T1
2.048 MBit/s at G703-E1
512 kBit/s or 128 kBit/s or 64 kBit/s at X.21
128 kBit/s for pilot wires
Transmission Times
Priority 1
Response time, total approx.
For 2 ends Minimum 8 ms
Typical 10 ms
For 3 ends Minimum 10 ms
Typical 14 ms
Dropout times, total approx.
For 2 ends Typical 20 ms
For 3 ends Typical 20 ms
Priority 2
Response time, total approx.
For 2 ends Minimum 9 ms
Typical 16 ms
10.19
Technical Data
10.19 Protection Interface and Protection Topology
SIPROTEC 5, Busbar Protection 7SS85 , Manual 359
C53000-G5040-C019-1, Release 09.2013
For 3 ends Minimum 12 ms
Typical 18 ms
Dropout times, total approx.
For 2 ends Typical 24 ms
For 3 ends Typical 25 ms
Priority 3
8
Response time, total approx.
For 2 ends Minimum
Typical 100 ms
For 3 ends Minimum
Typical 150 ms
Dropout times, total approx.
For 2 ends Typical 100 ms
For 3 ends Typical 150 ms
8
Times cannot be determined because the signals are transmitted in fragments.
Technical Data
10.19 Protection Interface and Protection Topology
360 SIPROTEC 5, Busbar Protection 7SS85 , Manual
C53000-G5040-C019-1, Release 09.2013