Aci 350.4R-04
Aci 350.4R-04
Aci 350.4R-04
Jerry Parnes
Jon B. Ardahl
Clifford Gordon
||
Larry G. Mrazek Lawrence J. Valentine
Paul Hedli Javeed A. Munshi Miroslav Vejvoda
Jerry A. Holland Paul Zoltanetzky, Jr.
Charles S. Hanskat
Chair
Lawrence M. Tabat
Secretary
*
Committee Secretary while this document was being prepared.
Resultant
within the base
1.0
*
Table is not intended to apply to retaining structures that rely on anchorage devices, such
as rock or soil anchors, for stability. Loads used to calculate safety factors should
be service loads.
Low safety factor was established based on short-term nature of load, the ability of
soil to resist higher short-term loads, and the rarity of sliding and overturning failures
in earthquakes.
Copyright American Concrete Institute
Provided by IHS under license with ACI Licensee=Bechtel Corp Loc 1-19/9999056100
Not for Resale, 05/09/2013 07:27:57 MDT No reproduction or networking permitted without license from IHS
-
-
`
`
`
`
`
`
,
`
,
`
`
`
`
`
,
`
,
,
`
`
,
,
,
`
,
`
`
,
-
`
-
`
,
,
`
,
,
`
,
`
,
,
`
-
-
-
ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES 350.4R-9
(3-4)
where B
c
= base width remaining in compression.
CHAPTER 4SPECIAL DESIGN CONDITIONS
4.1Load combinations
4.1.1 Loading combinations for wallsWalls of liquid-
containing structures are commonly subjected both to liquid
pressure from the inside and earth pressure from the
outside. Such walls and their supports should be designed
for each of these loads acting independently. External
earth pressure generally should not be relied on to resist
liquid pressure because:
Wall backfill may not be in place when the tank is filled
initially for leakage testing;
Earth pressures may be removed due to excavating for
an addition, modification, or repair adjacent to the
structure; and
The resulting change in earth pressures due to the
outward wall movements are difficult to predict.
For multicell fluid-containment structures, the effects of
combinations of empty and full cells should be considered in
the design.
4.1.2 Tension loadsContinuous walls and slabs between
ends of rectangular liquid-containing structures should be
designed to transfer tension forces between endwalls to
balance the lateral forces due to the contained liquid. This
direct tension force should be considered in the reinforcement
design at corners, wall-to-slab connections, and along the
entire length of the wall or slab. Where the cross section is
fully in tension, the required tensile reinforcement should be
distributed proportionately to each face. If significant flexural
loads are present, the required area of tension reinforcement
may either be conservatively added directly to the required
area of flexural tension reinforcement, or the combined
flexure and tension may be evaluated in accordance with
ACI 340R (SP-17).
4.2Expansion and contraction conditions
Roofs over environmental engineering concrete structures
often cover large areas and they may be exposed to significant
thermal movements. Stresses can occur in the walls and roof
due to difference in thermal movement between the walls and
roof. The stresses can be reduced by providing movement joints
between the walls and the roof and within the wall and roof
elements. Low-friction bearings or suitable flexible bearing
pads should be incorporated into the design of the movement
joints to prevent spalling and other damage due to direct tension.
Stresses can also occur in the walls and roof due to the
difference in temperature and moisture through the thickness
of the wall and roof section. These stresses should be considered
in the design where applicable.
Large-diameter tanks expand and contract appreciably due
to thermal changes, shrinkage, creep, and elastic deformations
as they are filled and drained. The connection between the
wall and footing of such tanks should be detailed to permit
these movements to occur freely or design them strong
B
c
3 B 2e ( )
2
----------------------- =
enough to resist the movements without cracking. Similarly,
the roof-to-wall connection should account for such movements.
Refer to Chapter 5 for additional discussion of design of
joints in concrete structures.
4.3Foundation conditions
Foundation design is critical to control cracking and
maintenance of liquid tightness in liquid-containing
structures. Differential movements can cause cracking in
structures, failure of joints, failure of rigid pipe connections,
or damage to operating equipment. Thus, variations in
foundation stiffness should be avoided; for example,
soil-supported elements should not be combined with
elements supported on deep piles or drilled piers unless
differential vertical movements are taken into consideration.
Similarly, where a portion of a structure is much shallower
than an adjacent portion of the structure, the shallower
portion may be prone to differential settlement due to the
relative depth of fill materials below it. In some cases, the
shallower portion of the structure may need to be supported
on a deep foundation.
Typically, sliding resistance between the bottom of the
structure and the soil is neglected when the structure is
supported on piles or drilled piers.
4.4Design and detailing considerations
Proper consolidation of concrete is essential in a liquid-
tight structure. Thin, cast-in-place, reinforced concrete walls
make placement and consolidation of concrete more
difficult. The minimum thickness for walls that are greater
than or equal to 10 ft (3 m) in height is 12 in. (300 mm)
(ACI 350-01, Section 14.6.2). For lower walls, 10 in.
(250 mm) is the practical minimum thickness for walls with
reinforcement in each face. If 8 in. (200 mm) walls are
used, a single mat of reinforcement placed 2 in. (50 mm)
from one face is preferred to allow space for placing and
consolidating the concrete. Greater thicknesses are desirable
where waterstops are used, due to the limited space available
for both reinforcement and waterstop placement with
adequate concrete cover. For walls greater than 10 ft (3 m)
in height, a reasonable rule of thumb is to use a minimum
wall thickness equal to 1/12 the wall height for cantilever
walls and 1/16 the height for propped cantilever walls.
The minimum thickness of footings and mat foundations
should generally be 12 in. (300 mm).
Liquid-containment walls may be designed as cantilever
walls, propped cantilever walls, pinned endwalls, or two-
way plates with various edge conditions, depending on
support conditions. For propped cantilever walls and two-
way plate walls, the assumption of full fixity at the base may
not be entirely accurate, especially if supported on soil. A
fixed-base assumption is normally conservative for design of
the reinforcement at the base of the wall, but it may not be
conservative for midspan reinforcement. Thus, consideration
should be given to assuming partial fixity at the base. A
conservative approach is to bracket the design by
detailing wall reinforcement for both the fixed-base and
pinned-base design conditions.
Copyright American Concrete Institute
Provided by IHS under license with ACI Licensee=Bechtel Corp Loc 1-19/9999056100
Not for Resale, 05/09/2013 07:27:57 MDT No reproduction or networking permitted without license from IHS
-
-
`
`
`
`
`
`
,
`
,
`
`
`
`
`
,
`
,
,
`
`
,
,
,
`
,
`
`
,
-
`
-
`
,
,
`
,
,
`
,
`
,
,
`
-
-
-
350.4R-10 ACI COMMITTEE REPORT
Except near corners and intersecting walls, long walls may
be designed as one-way vertical spans. Near corners and
intersecting walls, two-way plate action should be considered. A
reasonable approximation of corner moments is to use two-
way plate design tables based on a wall with the maximum
tabulated aspect ratio.
Where two-way plate tables are used for wall design, the
actual fluid depth may be somewhat less than the full wall
height, as shown in the design tables. An approximate design
method is to calculate the total lateral force on a unit length
of wall due to the actual fluid depth and then redistribute this
total lateral force over the full height of the wall.
The minimum required area of flexural tension reinforcement
for structural slabs and footings of uniform thickness can be
reduced to that permitted for minimum shrinkage and
temperature reinforcement per ACI 350. Where one-way
slabs and walls are uniformly loaded by liquid or earth loads
and are intended to be liquid-tight, consideration should be
given to the use of the minimum recommended flexural
reinforcement as required for beams where an overload
condition could result in a sudden or brittle failure.
Reinforcement in each face of structural members should
be extended for the full length of the member for improved
crack control and structural ductility. For crack control,
smaller bars at closer spacing are preferred over larger bars
at a wider spacing.
4.5Vibration conditions
4.5.1 GeneralMost types of process equipment associated
with treatment plants, such as clarifiers, scrapers, and paddle
mixers, are relatively slow moving and will not cause structural
vibrations. For such equipment, a separate design for dynamic
loading is unnecessary. Other commonly used equipment, such
as centrifugal pumps, fans, blowers, compressors, centrifuges,
and generator engines, however, can have much higher
operational frequencies and will require special consideration in
the design of their support structures and foundations. Usually,
the value of such equipment and its reliability is much greater
than the cost of the foundation, so that it is imprudent to
economize on foundation costs and run the risk of shortened
machine life, increased maintenance costs, and breakdowns.
In treatment plants, machines that most often cause vibration
problems are large forced-draft fans (blowers), as used for
aeration tanks, and centrifuges, as used for dewatering of
sludge. These are very sensitive machines and require carefully
designed foundations to prevent resonant vibration. Chemical
mixers may also produce of significant dynamic loads that
should be considered in the design of their supports.
4.5.2 Design for vibrationThe key to successful
dynamic design is to ensure that the natural frequency of the
equipment support structure is significantly different from
the frequency of the disturbing force caused by the equipment.
If the two frequencies approach each other, resonant vibrations
will occur in the support structure. Resonant vibrations in the
support structure that result in large amplitude oscillations
can cause damage to the structure, to the equipment, or both.
To minimize resonant vibrations, the ratio of the natural
frequency of the structure to the frequency of the disturbing
force should be outside of the range of 0.5 to 1.5. It is difficult to
obtain an accurate determination of the natural frequency of
concrete members due to variations in concrete strength,
modulus of elasticity, and cracked or uncracked sections.
Theoretically, the structure can be designed to have a
natural frequency that is lower than the operating frequency
of the equipment. This practice is commonly referred to as
low tuning and is intended to avoid resonant vibration. This
method is generally not recommended, but sometimes cannot
be avoided. Low-tuned structures tend to be relatively flexible
and have higher deflections. Low tuning is most practical for
equipment that has an operating frequency that is much
higher than the natural frequency that can be practically
achieved for the supporting structure. A disadvantage of low
tuning is that the machine would pass through the resonant
frequency of the supporting structure at startup and shut-
down. If the resonant condition is transient, it is unlikely that
it would cause damage to the machine, but it is generally
preferable to keep operational deflections low. Many types
of equipment come up to full operating speed in a few
seconds. For this equipment, the short period when a resonant
condition exists would not be long enough to allow excessive
amplitude to build. The resonant condition can be more of
a concern for equipment that takes a long time to reach full
operating speed. Of special concern is equipment where the
operating speed can be adjusted over a range that includes the
resonant frequency of the supporting structure. If the equipment
was set to operate at the resonant frequency of the supporting
structure, excessive amplitude may occur, possibly causing
damage to the supporting structure and the equipment.
Furthermore, if the supporting structure is stiffer than
estimated, its natural frequency may be higher than calculated.
Some causes of the supporting structure being stiffer than
calculated would include the concrete being stronger than the
design strength, a cracked section being assumed for calculations
and the concrete cracks less than assumed, construction
tolerances resulting in larger members than used in design, and
the length of members used in calculations not taking into
account the member thickness at joints. Simplified analysis
methods that overestimate structure deflections may also
result in the structures actual natural frequency being higher
than calculated. Therefore, it is preferred to use a stiff structural
support system with a natural frequency at least 1-1/2 times
the equipment frequency (also known as high tuning). With
high tuning, any underestimation of the support structure
natural frequency will not create a risk of resonant vibration.
If the equipment is not supported directly on a solid
foundation but is supported on columns and beams, the
natural frequency of the support members is of primary
importance. The supporting members should have both
sufficient stiffness and strength to eliminate the risk of
resonant vibrations. It may be desirable to use vibration
isolators, especially on elevated structures, to reduce the
magnitude of vibrations transferred to the structure. This
should not be used as an alternate to considering dynamic
effects because all isolators transmit some vibration. The
amount of equipment vibration transmitted through the
vibration isolators will vary with the operating frequency of
Copyright American Concrete Institute
Provided by IHS under license with ACI Licensee=Bechtel Corp Loc 1-19/9999056100
Not for Resale, 05/09/2013 07:27:57 MDT No reproduction or networking permitted without license from IHS
-
-
`
`
`
`
`
`
,
`
,
`
`
`
`
`
,
`
,
,
`
`
,
,
,
`
,
`
`
,
-
`
-
`
,
,
`
,
,
`
,
`
,
,
`
-
-
-
ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES 350.4R-11
the equipment and the design of the vibration isolators.
Detailed information on transmissibility can be obtained
from the isolator vendor.
The natural frequencies of a structure should be calculated for
the vertical direction and for the two principal horizontal
directions. In some cases, torsional frequency may also need to
be examined. To combine the effects of several masses, the
combined natural frequency can be estimated using the Raleigh
Method. Where masses are not closely coupled dynamically
(that is, natural frequencies are not too close to one another), the
following Southwell-Dunkerley
12
formula may be used
(4-1)
where
F
n
= combined natural frequency;
F
1
= natural frequency due to mass 1;
F
2
= natural frequency due to mass 2;
F
3
= natural frequency due to mass 3; and
F
4
= natural frequency due to mass 4.
Drilled-in expansion anchors that rely solely on friction
for pullout resistance should not be used to anchor vibrating
equipment, as they can work loose. Cast-in-place anchor
bolts are preferred. Alternately, epoxy-grouted anchor bolts
may be considered where drilled-in anchors are necessary.
4.5.3 Calculating natural frequencyReadily available
commercial software programs can be used to calculate the
natural frequency of structures and members of structures.
Formulas are also available in technical books on vibration
for calculating the natural frequency of beams.
A method of estimating the natural frequency of a structure is
to apply gravity to the masses being considered, with gravity
applied in the direction being considered (that is, apply
gravity horizontally instead of vertically for horizontal
natural frequency). Then calculate the deflection due to this
loading assumption and calculate the fundamental natural
frequency (due to the first mode of vibration) from the
following formula for a single degree of freedom system
(4-2)
where
D = calculated deflection;
F
n
= fundamental natural frequency; and
g = acceleration due to gravity.
This formula is derived from the general equation for natural
frequency of a single degree of freedom system as follows
1
F
2
n
--------
1
F
2
1
--------
1
F
2
2
--------
1
F
2
3
--------
1
F
2
4
-------- ... + + + + =
F
n
1
2
------
g
D
---- =
(4-3)
where
F
n
= fundamental natural frequency;
k = W/D = spring constant (force per unit deflection);
M = W/g = mass; and
W = weight of considered mass.
The masses multiplied by the acceleration due to gravity
(equivalent to the weight of the masses under consideration)
are applied to obtain the effective spring constant of the
structure, which is directly related to the stiffness of the
structure as calculated by its deflection. Thus, the deflection
calculation for determining natural frequency should not
include any live loads or dynamic operational loads. The
deflection calculations should only include the weights
associated with the masses that contribute to the
frequency of the system (for example, the equipment
mass, the mass of any contained fluids, and the
supporting structure mass).
Natural frequency of beams in cycles per second can be
calculated using the expressions given in Table 4.1. These
equations provide a simple method of calculating the
approximate natural frequency of a beam from its static
deflection; D is the immediate elastic deflection at the noted
location due to the uniform or concentrated weight applied in the
direction under consideration to a beam with the noted end
F
n
1
2
------
k
M
----- =
Table 4.1Natural frequency of beams
End condition
End 1-End 2 Load
Position of
deflection D
Natural
frequency
(cycles per s)
Fixed-Free Uniform End 2
Pin-Pin or
Fixed- Fixed
Uniform Midspan
Fixed-Fixed or
Fixed-Free or
Pin-Pin
Concentrated
(any position)
Under load
Notes: D = deflection in inches (mm); g = 386 in./s
2
(9804 mm/s
2
).
Multiply natural frequency by 60 to calculate RPM.
0.20
g
D
----
0.18
g
D
----
0.16
g
D
----
Table 4.2Recommended maximum static
deflections of beams supporting
vibratory equipment
Operating frequency
of equipment,
cycles per min
Minimum natural
frequency of
structure, cycles
per min
Maximum static deflection
due to dead load and
equipment load,
in. (mm)
400 600 0.10 (2.5)
600 900 0.044 (1.1)
800 1200 0.025 (0.64)
1000 1500 0.016 (0.41)
1200 1800 0.011 (0.28)
2000 3000 0.004 (0.10)
2400 3600 0.0027 (0.069)
Copyright American Concrete Institute
Provided by IHS under license with ACI Licensee=Bechtel Corp Loc 1-19/9999056100
Not for Resale, 05/09/2013 07:27:57 MDT No reproduction or networking permitted without license from IHS
-
-
`
`
`
`
`
`
,
`
,
`
`
`
`
`
,
`
,
,
`
`
,
,
,
`
,
`
`
,
-
`
-
`
,
,
`
,
,
`
,
`
,
,
`
-
-
-
350.4R-12 ACI COMMITTEE REPORT
conditions. Instead of a comprehensive deflection analysis, D
can be estimated using the methods outlined in ACI 318.
Table 4.2 shows the minimum recommended natural
frequency of the structure to be at least 1-1/2 times the operating
speed of the equipment. Table 4.2 also shows the maximum
static deflection permissible for the supporting structure, as
calculated using the equation for a concentrated mass on a beam.
The effect of the mass of the beam can be approximated as a
concentrated load at the center of the beam, or a more refined
analysis accounting for uniform loads can be developed. This
approximation will result in a larger deflection and in a lower
calculated natural frequency. The resulting natural frequency
should be evaluated in comparison with the equipment operating
frequency and checked for susceptibility for resonance. The
small deflections (or stiffer structures) required for high-
frequency equipment (that is, greater than 1200 cycles per
minute) may not be practical to achieve, and low tuning may be
required. Motors used to drive pumps and other equipment often
operate at high rotational speeds, but electrical motors are
generally well balanced and do not tend to cause significant
vibrational problems. Consequently, motor supports are
generally not designed for vibrational effects due to the usually
high motor speed, but such supports should be relatively stiff to
avoid vibrational problems. Vibration isolators may be desirable
at the motor support points.
4.5.4 Foundations at gradeWhere dynamic equipment
loads are to be supported using spread foundations, the safe
design bearing load is often assumed as 1/2 of the allowable
foundation bearing load for a statically loaded foundation at
the same location.
13,14
Some sources recommend minimum
foundation-to-equipment mass ratios, generally in the range
of 2 to 5.
9
Adherence to this rule has not always proven
satisfactory,
15
and to ensure that critical equipment will not
be in resonance with the foundation, the natural frequency of the
foundation system should be calculated. For natural
frequency calculations, follow the methods recommended
in Reference 13. For pile-supported foundations, follow the
recommendations found in References 16 through 18. Often
the equipment foundation is intentionally isolated from the
floors or other parts of the structure to minimize the transmission
of vibrations to other parts of the structure.
Block foundations should typically be at least 24 in. (600 mm)
in thickness and have a width greater than the vertical distance
from the top of foundation to the center of gravity of the
equipment. Preferably, the center of gravity of the foundation in
plan should match the center of gravity of the equipment.
12
More detailed information on dynamic analysis methods
and the dynamic design of foundations can be found in
References 19 through 23. Additional information may be
available for the design of equipment foundations from ACI
Committee 351, Foundations for Equipment and Machinery.
4.6Hazardous design conditions
Superstructures of environmental engineering concrete
structures are frequently similar to conventional structures.
In some facilities, the gases generated within the structure,
adjacent to it, or below it may be toxic or may present an
explosion hazard. Where buildings or equipment rooms are
located over or adjacent to tanks or digesters, the tanks may
require gas-proofing by means of liners, installation of gas-
detection equipment, or both.
At least one access point should be provided into each
enclosed cell for inspection and maintenance. Where practical,
two access points should be provided at opposite ends of
enclosed structures for improved safety.
Confined space entry (CSE) requirements, as defined by
OSHA, should be considered in the design of all below-grade or
unventilated structures. Provisions for adequate ventilation
and safe exit passage may eliminate CSE limitations for
operating personnel.
4.7Corrosive conditions
Special consideration should also be given to the possible
hazardous and corrosive effects of gases such as chlorine,
oxygen, ozone, hydrogen sulfide, and methane gases in
closed tanks. Corrosion-resistant linings may be required
to protect the concrete, especially where hydrogen
sulfide gases occur above the water surface in closed
structures. Corrosive effects on metal embedments are
also very important. Furthermore, consideration should
be given to corrosive effects of stored or applied chemi-
cals in the treatment process. Where hazardous chemicals
are stored, containment basins should be provided to contain the
chemicals in case of leakage. Corrosion-resistant linings in the
containment basins may be necessary to protect the concrete
in the event of a spill or leakage. Refer to ACI 350-01 for
a listing of chemicals commonly associated with environmental
structures and their relative effects on concrete.
4.8Construction conditions
Low-permeability concrete is obtained by using a water-
cementitious material ratio (w/cm) as low as possible and
consistent with satisfactory workability and good consolidation.
The use of a water-reducing admixture will generally permit the
use of a lower w/cm. Air entrainment increases workability
and reduces segregation and bleeding, thus, the use of an air-
entraining admixture generally permits the use of a lower w/cm.
Pozzolans also improve workability and reduce permeability.
Permeability is reduced with extended moist curing and with
the use of smooth forms or troweling. The filling and
patching of tie holes is also essential to long-term durability.
Form ties with waterstop collars should be used in walls
intended to be liquid-tight.
Liquid-containment structures are generally tested for
liquid-tightness before backfilling around the structure. Such
testing should be performed in accordance with the
recommendations of ACI 350.1.
The contractor is normally responsible for construction
loading conditions. The engineer, however, should anticipate
interim loading conditions, design for such conditions, and
note permitted interim conditions on the drawings where
such designs will simplify construction and reduce costs. For
example, a wall may be designed to resist backfill loads
before the top slab is in place, where it will simplify
construction. This condition may be especially important if
Copyright American Concrete Institute
Provided by IHS under license with ACI Licensee=Bechtel Corp Loc 1-19/9999056100
Not for Resale, 05/09/2013 07:27:57 MDT No reproduction or networking permitted without license from IHS
-
-
`
`
`
`
`
`
,
`
,
`
`
`
`
`
,
`
,
,
`
`
,
,
,
`
,
`
`
,
-
`
-
`
,
,
`
,
,
`
,
`
,
,
`
-
-
-
ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES 350.4R-13
an upper slab-on-ground cannot be constructed until backfill
is placed against a lower foundation wall.
Where the dewatering of excavations is required due to the
presence of ground water, the engineer should identify at
what stage of construction dewatering can be terminated
based on the strength and flotation resistance of the structure.
CHAPTER 5JOINTS IN CONCRETE
5.1General
The engineer should consider the structural effects of joint
locations and details on the design. Generally, the engineer
should show all required joints on the construction documents.
Any joints proposed to be added or deleted by the contractor
should be reviewed by the engineer after consideration of
effects on the structures design and crack control.
Movement joints permit dimensional changes in concrete
due to load, thermal effects, drying shrinkage, or differential
foundation movements; serve to separate or isolate areas or
members that could be affected by such dimensional
changes; and allow relative in-plane movements or
displacements due to such dimensional changes. Dowels
are often used in movement joints to resist out-of-plane
movements. The design should provide for slippage of the
dowel on one side of the joint. Keyways may be used in
nonmovement joints but should be used with caution in
movement joints due to the potential for a crack to occur
across the keyway and around the outside of the water-
stop. Figure 5.1 illustrates some of the most common
types of movement joints.
All joints should be considered as potential sources of
leakage. Leakage tends to occur more frequently in movement
joints, with expansion joints being the most likely to leak.
While closer spacing of movement joints may reduce
cracking between joints, the additional joints may increase
the potential for overall basin leakage. Thus, increased joint
spacing, in conjunction with increased reinforcement to
control crack widths, may reduce total basin leakage.
Effects of movement joints on load transfer should be
considered in design. For example, at joints in which
reinforcement is interrupted, the transfer of tension across
the joint is also interrupted. Movement joints may also affect
continuity of shearwalls or diaphragms.
Where joint materials will be in contact with water being
treated for use as potable water, the materials must be
nontoxic, generally after 30 days of curing.
5.2Construction joints
Construction joints are generally located at natural breaks in
concrete placements, such as between wall and slab placements,
and at intervals to limit length and volume of concrete
placements. Movement joints also function as effective
construction joints, that is, breaks in concrete placements. Unless
otherwise noted or shown, construction joints are typically
designed for full transfer of stresses across the joint. Keyways or
roughened surfaces with shear-friction reinforcement are
typically used for shear transfer at construction joints.
Cracking can occur in long wall or slab placements due to
the effects of thermal movements and drying shrinkage in
combination with movement restraints on the element. The
maximum length of wall placed at one time for conventionally
reinforced straight walls should usually not exceed 60 ft
(18 m), with 30 to 50 ft (9 to 15 m) being more common.
2
At
vertical construction joints, 48 h should be allowed between
placement of adjacent wall sections. Extra horizontal
reinforcement may be desirable near the base of the wall to
assist in control of cracks near the base.
Large circular basins typically use only construction joints
and no movement joints. Typically, a center circular
concrete placement is made, with the remainder of the slabs
and walls placed in equal segments.
5.3Movement joints
5.3.1 Contraction jointsContraction joints are often
used to dissipate shrinkage stresses and to control cracking.
Where used, contraction joints should be located at intervals
not exceeding 30 ft (9 m), unless additional reinforcement is
provided as required in ACI 350-01, Section 7.12. Shrinkage
will occur regardless of the amount of reinforcement
provided; however, the increased reinforcement tends to
distribute cracks and limit crack widths. Because cracks
occur at weak points, the intent of contraction joints is to
concentrate full-depth cracks at specific locations where
measures can be taken to protect against leakage.
Two types of contraction joints, known as full and partial
contraction joints, are in common use. In full contraction
joints, all reinforcement should be terminated 2 in. (50 mm)
clear of the joint. In partial contraction joints, at least 50% of
the reinforcement should be terminated 2 in. (50 mm) clear
of the joint, with the remainder being continuous through the
joint. The surface of the joint should be treated to prevent
bonding with the adjacent concrete placement where fresh
concrete is placed against hardened concrete. Full contraction
joints provide less restraint against shrinkage at the joint;
however, partial contraction joints provide some shear
transfer and limit differential movements across the joint due
to partial continuity of the reinforcement. Because the use of
a partial contraction joint creates a weak plane, consideration
should be given to seismic performance of these joints (for
Fig. 5.1Movement joints.
Copyright American Concrete Institute
Provided by IHS under license with ACI Licensee=Bechtel Corp Loc 1-19/9999056100
Not for Resale, 05/09/2013 07:27:57 MDT No reproduction or networking permitted without license from IHS
-
-
`
`
`
`
`
`
,
`
,
`
`
`
`
`
,
`
,
,
`
`
,
,
,
`
,
`
`
,
-
`
-
`
,
,
`
,
,
`
,
`
,
,
`
-
-
-
350.4R-14 ACI COMMITTEE REPORT
example, effects due to high, localized energy dissipation).
Partial contraction joints are typically spaced at about 2/3 the
spacing used for full contraction joints. Even though
partially reinforced, such joints should be assumed to
open when considering the moment, shear, and diaphragm
shear capacity at such joints.
5.3.2 Expansion joints and isolation jointsExpansion joints
allow for thermal expansion and act as effective contraction
joints. Expansion joints tend to have the most problems with
long-term leakage in liquid-containment structures, so their
usage should be limited. Expansion joints are generally used in
very long structures (typically over 150 ft [45 m] in length) or
where abrupt changes in configuration or support occur.
All expansion joints should include some type of
preformed compressible filler and a joint sealant at the liquid
face. If the structure must be liquid-tight, a suitable waterstop
should be included to act as the primary barrier against leakage.
The waterstop, preformed filler, and joint sealant should be
selected to allow for the anticipated movement and should be
suitable for the service environment. Refer to ACI 504R for
recommended joint design and materials of construction.
Isolation joints serve to separate portions of a structure,
such as between vibrating equipment foundations and building
foundations or between column foundations and floating slabs.
Such joints should include some type of preformed
compressible filler and a joint sealant at the exposed face to
keep dirt, debris, and water from entering the joint, as well as a
waterstop, where required, for liquid tightness.
5.4Waterstops
Waterstops are required in all types of joints where liquid
tightness is required. Rubber waterstops permit the greatest joint
movement and last indefinitely when placed in a dark and humid
environment that is not corrosive to rubber. Polyvinyl chloride
(PVC) waterstops permit somewhat less movement than rubber
but are less sensitive to light exposure during construction and to
drying. Another advantage of PVC waterstops is the simplicity
of splicing by applying heat. The minimum sizes of either type
of flexible waterstop commonly used in environmental
structures is 3/8 x 9 in. (10 x 230 mm) for expansion joints and
1/4 x 6 in. (6 x 150 mm) for construction or contraction joints.
Minimum 3/8 x 6 in. (10 x 150 mm) waterstops should be
used at wall base joints where possible to avoid folding
under wet concrete placement. Copper waterstops have
also been used effectively. Stainless steel waterstops are
typically used in ozone process environments, due to the
damaging effect of ozone on other materials used for
waterstops. Refer to ACI 504R for additional discussion
of waterstop materials.
Rigid (metal) waterstops should not be used in movement
joints. Rubber or PVC waterstops with a center bulbs are
common in movement joints. Concrete cover at flat waterstops
should be equal to or greater than 1/2 the width of the waterstop.
Adequate support and careful concrete placement should be
provided to ensure proper position and embedment of the water-
stop in the concrete. For vertical waterstops, the use of tie wires
tied to the reinforcement to anchor the waterstop in position
should be considered. For flexible horizontal waterstops, the
following construction sequence should be considered:
a. Fold the waterstop upward along its entire length and
hold in position;
b. Place and consolidate concrete up to the elevation of the
waterstop;
c. Reposition the waterstop into the top of the fresh
concrete; and
d. Complete concrete placement and consolidation around
the remainder of the waterstop.
A number of alternative waterstop types have become
available, such as premolded adhesive waterstops;
premolded, expansive, water-reactive waterstops; and injection
tube waterstops that are injected with water-reactive chemical
grout. Some waterstops are available that combine more than
one of the above types. The effectiveness and applicability of
a particular waterstop system to any given situation should
be evaluated by the engineer. Some of these alternative
waterstops can provide solutions where new construction is
to be tied to existing construction and should be liquid-tight
or where backup systems to ensure liquid-tightness are
required. Waterstops that expand and contract with varying
exposure to moisture may leak initially until the reaction
with moisture takes full effect. Such waterstops may be less
desirable where frequent wetting-and-drying cycles may
occur or where water is not in contact with the joint during
normal operations. Also, such waterstops may not be effective
for containment of liquids other than water, and most of these
alternative waterstops are not recommended for movement
joints. Where such alternative waterstops intersect rubber or
PVC waterstops, the method of connecting for continuity of
liquid tightness should be specified.
5.5Joint fillers
Preformed joint filler serves dual tasks: it serves as a form for
the second placement of concrete while preserving the space into
which the concrete may intrude, and it prevents dirt and water
from filling the formed space in service. An ideal joint filler will
permit compression to 1/2 its original width and will re-expand
to fill the joint when the adjacent members contract. Cork,
rubber, foam, and other materials conforming to ASTM D
1056 and D 1752 are satisfactory joint fillers. In general, these
joint fillers are not capable of expanding beyond their initial
width and require precompression to exhibit expansion
characteristics. The effect of precompression, however, may be
reduced with time due to relaxation.
5.6Joint sealants
Sealants used in movement joints should be placed on the
liquid side and should be suitable for the service environment,
such as submerged service and exposure to wastewater and
chemicals. Sealants and joint fillers should be compatible with
each other. Joint sealants are not expected to function for the
entire life of a structure. Owners should be advised of the
need to repair, maintain, and reseal joints with proper
sealants at proper maintenance intervals. Joint sealants
should not be relied on to act as the primary barrier to
leakage in containment structures.
Copyright American Concrete Institute
Provided by IHS under license with ACI Licensee=Bechtel Corp Loc 1-19/9999056100
Not for Resale, 05/09/2013 07:27:57 MDT No reproduction or networking permitted without license from IHS
--``````,`,`````,`,,``,,,`,``,-`-`,,`,,`,`,,`---
ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES 350.4R-15
Where the movement will be not more than 25% of the joint
width, polyurethane elastomers, as referred to in ACI 504R, are
suitable joint sealants. These materials are available in two types:
self-leveling or pourable for horizontal joints, and nonsagging
for vertical or sloping joints. Bituminous joint fillers should not
be used in conjunction with polyurethane sealants, as they may
impair adhesion (ACI 504R).
Polysulfide sealants are not suitable for use in wastewater
treatment plants because they generally have low resistance to
the chemical and biological reactions inherent to wastewater
treatment. In addition, the chemical reactions necessary for the
curing process of these sealants are impeded by the presence
of moisture.
CHAPTER 6REFERENCES
6.1Referenced standards and reports
The standards and reports listed below were the latest
editions at the time this document was prepared. Because
these documents are revised frequently, the reader is
advised to contact the proper sponsoring group if desired
to refer to the latest version.
American Association of State Highway and Transportation
Officials
Standard Specifications for Highway Bridges
American Concrete Institute
318 Building Code Requirements for Structural
Concrete
350/350R Code Requirements for Environmental Engineering
Concrete Structures and Commentary
350.1 Tightness Testing of Environmental Engineering
Concrete Structures
350.2R Concrete Structures for Containment of Hazardous
Materials
350.3 Seismic Design for Liquid-Containing Concrete
Structures
504R Guide to Sealing Joints in Concrete Structures
SP-17 ACI Design Handbook
American Society of Civil Engineers
ASCE 7 Minimum Design Loads for Buildings and Other
Structures
American Water Works Association
C 560 Cast-Iron Slide Gates
C 513 Open-Channel Fabricated-Metal Slide Gates
American Water Works Association/American Society for
Civil Engineers
Water Treatment Plant Design
ASTM International
D 1056 Standard Specification for Flexible Cellular
MaterialsSponge or Expanded Rubber
D 1752 Standard Specification for Preformed Sponge
Rubber and Cork Expansion Joint Fillers for
Concrete Paving and Structural Construction
These publication may be obtained from the following
organizations:
American Association of State Highway and Transportation
Officials
444 Capitol St NW Suite 249
Washington, DC 20001
American Concrete Institute
P.O. Box 9094
Farmington Hills, MI 48333-9094
American Society of Civil Engineers
1801 Alexander Bell Dr.
Reston, VA 20191
American Water Works Association
6666 West Quincy Ave.
Denver, CO 80235
ASTM International
100 Barr Harbor Drive
West Conshohocken, PA 19428
6.2Cited references
1. Portland Cement Association, Circular Concrete
Tanks Without Prestressing, ISO72, 1992.
2. Portland Cement Association, Rectangular Concrete
Tanks, IS003, 1998.
3. U.S. Department of the Interior, Bureau of Reclamation,
Moments and Reactions for Rectangular Plates, Engineering
Monograph No. 27, 1963.
4. American Water Works Association/American Society of
Civil Engineers, Water Treatment Plant Design, 1990,
McGraw-Hill Book Co.
5. American Society of Civil Engineers, Retaining and
Flood Walls, 1994. (as adapted from U.S. Army Corps of
Engineers Publication EM 1110-2-2502, 1989).
6. Golder Associates and W. M. Slater and Associates, Inc.,
Deterioration and Repair of Above Ground Water Tanks in
Ontario, Canada, Ontario Ministry of the Environment, 1987.
7. Das, B. M., Principles of Soil Dynamics, Brooks/Cole,
Pacific Grove, 1993.
8. Kramer, S. L., Geotechnical Earthquake Engineering,
Prentice-Hall, Inc., Upper Saddle River, N.J., 1996.
9. Seed, H. B., and Whitman, R. V., Design of Earth
Retaining Structures for Dynamic Loads, Proceedings,
Specialty Conference on Lateral Stresses in the Ground and
Design of Earth Retaining Structures, ASCE, 1970, pp. 103-147.
10. Davis, C. V., and Sorensen, K. B., Handbook of
Applied Hydraulics, Third Edition, McGraw Hill Book Co.,
New York, 1969.
11. Verma, S. P., Flood Considerations for Sanitary
Structures, Civil Engineering, ASCE, Oct., 1981.
12. Arya, S.; ONeill, M.; and Pincus, G., Design of
Structures and Foundations for Vibrating Machines,
Gulf Publishing Co., 1981.
Copyright American Concrete Institute
Provided by IHS under license with ACI Licensee=Bechtel Corp Loc 1-19/9999056100
Not for Resale, 05/09/2013 07:27:57 MDT No reproduction or networking permitted without license from IHS
-
-
`
`
`
`
`
`
,
`
,
`
`
`
`
`
,
`
,
,
`
`
,
,
,
`
,
`
`
,
-
`
-
`
,
,
`
,
,
`
,
`
,
,
`
-
-
-
350.4R-16 ACI COMMITTEE REPORT
13. Whitman, R. V., and Richart, F. E., Design Procedures
for Dynamically Loaded Foundations, Proceedings, ASCE,
V. 93, No. SM6, Nov. 1967, pp. 169-193.
14. Irish, K., and Walker, W. P., Foundations for Reciprocating
Machines, Concrete Publications Ltd., London, 1969, 103 pp.
15. Karabinis, A. H., and Fowler, T. J., Design Consid-
erations for Dynamically Loaded Equipment Foundations,
Foundations for Equipment and Machinery, SP-78, American
Concrete Institute, Farmington Hills, Mich., 1982, pp. 61-78.
16. Novak, M., Vertical Vibration of Floating Piles,
Proceedings, ASCE, V. 103, No. EM1, Feb. 1977, pp. 155-168.
17. Novak, M., and Howell, J. F., Torsional Vibration of
Pile Foundations, Proceedings, ASCE, V. 103, No. GT4,
Apr. 1977, pp. 272-285.
18. Singh, J., P.; Donovan, N. C.; and Jobsis, A. C.,
Design of Machine Foundations on Piles, Proceedings,
ASCE, V. 102, No. GT8, Aug. 1977, pp. 863-877.
19. Barkan, D. D., Dynamics of Bases and Foundations,
McGraw-Hill Book Co., New York, 1962, 496 pp.
20. Biggs, J. M., Introduction to Structural Dynamics,
McGraw-Hill Book Co., New York, 1964, 341 pp.
21. Church, A. H., Mechanical Vibrations, John Wiley &
Sons, New York, 1963, 432 pp.
22. Skipp, B. O., ed., Vibrations in Civil Engineering,
Butterworths, London, 1966, 298 pp.
23. Major, A., Vibration Analysis and Design of Foundations
for Machines and Turbines, Colets, London, 1962, 828 pp.
Copyright American Concrete Institute
Provided by IHS under license with ACI Licensee=Bechtel Corp Loc 1-19/9999056100
Not for Resale, 05/09/2013 07:27:57 MDT No reproduction or networking permitted without license from IHS
-
-
`
`
`
`
`
`
,
`
,
`
`
`
`
`
,
`
,
,
`
`
,
,
,
`
,
`
`
,
-
`
-
`
,
,
`
,
,
`
,
`
,
,
`
-
-
-