0% found this document useful (0 votes)
515 views15 pages

Modbus

modbus

Uploaded by

sarathpara
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
515 views15 pages

Modbus

modbus

Uploaded by

sarathpara
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 15

Communication AC500

Modbus TCP

Scalable PLC AC500

ABB Group Version 3.1 (2012-07)
Technical Guides

ABB Group
March 11, 2013 | Slide 2
Modbus TCP with AC500
Configuration and parameterization
Program in CoDeSys

Modbus TCP Communication
Coming up

ABB Group
March 11, 2013 | Slide 3
AC500 is server. It is exchanging
data on clients request.

CP600 is client. It is initiating the
communication.
Modbus TCP Communication
AC500 as Server and / or Client
Data exchange between CPUs.

Modbus TCP communication also
via CM577 possible.

Each PLC can act as client and /or
server.


ABB Group
March 11, 2013 | Slide 4
Modbus TCP with AC500
Configuration and parameterization
Program in CoDeSys

Modbus TCP Communication
Coming up

ABB Group
March 11, 2013 | Slide 5
Modbus TCP Communication
Configure Modbus TCP (1)

Add Modbus TCP on Onboard_Ethernet or CM577_ETH
Result:

ABB Group
March 11, 2013 | Slide 6
Modbus TCP Communication
Configure Modbus TCP (2)
If the Port is acting as a server
configure number of
connections to be created
simmultaneously to different
clients

Byte order for AC500
communication is Big endian =
Motorola byte order


The other parameters could be
changed due to optimize the
communication.

ABB Group
March 11, 2013 | Slide 7
Modbus TCP Communication
Configure Modbus TCP (3)
In the server project the
Modbus buffer area could be
selected as %M or %R area
(default: %M area)

Optionally in the server project
areas could be protected
against write and / or read
access by clients.
Writing / reading is disabled
beginning at the set address
and is valid up to the set end
address (inclusive).



ABB Group
March 11, 2013 | Slide 8
Modbus TCP with AC500
Configuration and parameterization
Program in CoDeSys

Modbus TCP Communication
Coming up

ABB Group
March 11, 2013 | Slide 9
Modbus TCP Communication
Client: Program in CoDeSys
Enabling parameter (0 -> 1 edge)
Number of Communication Module
Function code. Here Read registers (words)
Addr. of the slave connected serial to the server
10 words

Starting from Server address 0 (%MW0.0 or %RW0.0)

Copy to own memory area starting with address
of the operand (an array or an addresable area)
IP-address of the Server
Result of
data
exchange
This FB is only for the Client (no FB for Server).

ABB Group
March 11, 2013 | Slide 10
Modbus TCP Communication
Function Codes
01 or 02 read n coils (bits)
255 bits (up to firmware version V01.33)
1800 bits (from firmware version V01.41)
03 or 04 read n registers (words)
100 words / 50 double words
05 write one coil (bit)
1 bit
06 write one register (word)
1 word
07 read 8 coils (bits)
8 bits
15 write n coils (bits)
255 bits (up to firmware version V01.33)
1800 bits (from firmware version V01.41)
16 write n registers (words)
100 words / 50 double words
22 mask one register (word)
only with CPUs with Onboard Ethernet
23 read and write n registers
(word)
only with CPUs with Onboard Ethernet

AC500 supports following Modbus function codes:

ABB Group
March 11, 2013 | Slide 11
Modbus TCP Communication
Program in CoDeSys
Enable FB by a puls signal
FB is dedicated to the CPU internal ETH port
IP-addres of the server is 10.33.71.175, no routing to another serial slave
Write 5 words to the 11. word of the servers Modbus buffer (%MW0.10 or
%RW0.10) from own area beginning with the address of the variable
ARRAYofWORD

ABB Group
March 11, 2013 | Slide 12
Modbus TCP Communication
Program in CoDeSys
Enable FB by a puls signal
FB is dedicated to the CPU internal ETH port
IP-addres of the server is 10.33.71.174, no routing to another serial slave
Read 5 words to the 11. word of the servers Modbus buffer (%MW0.10 or
%RW0.10) from own area beginning with the address of the variable
ARRAYofWORD

ABB Group
March 11, 2013 | Slide 13
Modbus TCP Communication
Read / Write Addresses
Input and Output cannot be directly accessed by using Modbus
The address assignment for word and double word accesses is done according to the
following table :








Line 0 %MW0.0 to %MW0.32767 and line 1 %MW1.0 to %MW1.32767
Line 0 only for PM554_ETH, PM564_ETH and PM57x_ETH

ABB Group
March 11, 2013 | Slide 14
Cross-References to Documentation
1. CoDeSys Help\Target System\
AC500 / S500\ Function Block Libraries AC500 \
Ethernet Library


2. CoDeSys Help\Target System\
AC500 / S500\System Technology \System
Technology of the AC500 Communication
Modules\The Ethernet Communication Module\
Modbus on TCP/IP

ABB Group
March 11, 2013 | Slide 15

You might also like