XLR130 – XLR170
Instructions Manual
dIXEL Installing and Operating Instructions rel.2
rel.2.0 - cod. 1592017000
COOLMATE
XLR130C – XLR170C
INDEX
To translate this manual in you language you can start from the manual of XW570L code: “1592009130 XW570L GB.doc” and translate the part in
RED colour.
1. GENERAL WARNING 3
2. GENERAL DESCRIPTION 3
3. CONTROLLING LOADS 3
4. KEYBOARD 5
5. REAL TIME CLOCK FUNCTION – ONLY FOR INSTRUMENTS WITH RTC 8
6. PARAMETER LIST 8
7. DIGITAL INPUTS 11
8. INSTALLATION AND MOUNTING 12
9. DIMENSIONS 14
10. ELECTRICAL CONNECTIONS 14
11. TTL SERIAL LINE 14
12. HOW TO USE THE HOT KEY 14
13. ALARM SIGNALS 15
14. TECHNICAL DATA 15
15. CONNECTIONS 16
16. DEFAULT SETTING VALUES 17
1. GENERAL WARNING
2. GENERAL DESCRIPTION
Models XLR130 and XLR170, 210x230mm format, are microprocessor based controllers suitable for applications on medium or low temperature
refrigerating units. They are provided with four (XLR130) or six (XLR170) relay outputs to control compressor, defrost - which can be either electrical
or hot gas (XLR170) - the evaporator fans (XLR170), the lights, the alarm and an auxiliary output. They are also provided with three NTC or PTC
probe inputs, one for temperature control, one to control the defrost end temperature of the evaporator and the third, optional, for the display. There
are two digital inputs (free contact) for the door switch and configurable by parameter.
The standard TTL output allows the user to connect, by means of a TTL/RS485 external module, a ModBUS-RTU compatible monitoring system and
to programme the parameter list with the “Hot Key”.
Each model in the XLR100 can be provided with a Real Time Clock which allows programming of up to eight daily defrost cycles, divided into
holidays and workdays. A “Day and Night” function with two different set points is fitted for energy saving.
3. CONTROLLING LOADS
3.3 DEFROST
3.3.1 XLR130 – TIMED DEFROST
The defrost interval is controlled by means of parameter “EdF”:
- with EdF=in the defrost is made every “IdF” time,
- with EdF=Sd the interval “IdF” is calculate through Smart Defrost algorithm (the counter is increased only when the compressor is ON).
- with real time clock present EdF can be set to “rtc”, In this case, the defrost is made in real time depending on the hours set in the parameters
Ld1..Ld8 on workdays and in Sd1…Sd8 in holidays;
Defrost is performed through a simple stop of the compressor. Parameter “IdF” controls the interval between defrost cycles, while its length is
controlled by parameter “MdF”.
At the end of defrost the drip time is controlled through the “Fdt” parameter.
An additional parameter “FSt” provides the setting of temperature, detected by the evaporator probe, above which the fans are always OFF. This can
be used to make sure circulation of air only if his temperature is lower than set in “FSt”.
B. Auxiliary thermostat (I.E.. anti condensing heater) with the possibility of switching it on and off also by keyboard
Parameters involved:
- ACH Kind of regulation for the auxiliary relay: heating /cooling;
- SAA Set point for auxiliary relay
- ArP Probe for auxiliary relay
By means of these 3 parameters the functioning of the auxiliary relay can be set.. The differential is given by the Hy parameter.
The auxiliary relay can be switched on also by the AUX button. In this case it remains on till it’s manually switched off.
The defrost doesn’t affect the status of auxiliary relay.
3.5.4 XLR170: Second defrost relay for applications with 2 evaporators – oA1 = dF2
Parameters involved:
- dtS end defrost temperature for second defrost relay;
- MdS maximum defrost duration for second defrost relay;
- dSP probe selection for second defrost
With 2 evaporators the regulation restarts when both the defrosts are finished.
4. KEYBOARD
Panic LED
To display and modify target set point; in programming mode it selects a parameter or confirms an operation.
By holding it pressed for 3s when max or min temperature is displayed, it will be erased.
Only for models with RTC: by pressing it when the current time is displayed, it allows the User to re-set the current time and three
holidays.
To see the max. stored temperature; in programming mode it browses the parameter codes or increases the displayed value. By
holding it pressed for 3s the fast freezing cycle is started.
To see the min stored temperature; in programming mode it browses the parameter codes or decreases the displayed value.
Only for models with RTC: by holding it pressed for 3s the current time is displayed and it permits the User to enter Energy saving,
Defrost and Clock parameter menu.
KEY COMBINATIONS
4.4 4.4 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED
To reset the stored temperature, when max or min temperature is displayed :
1. Press SET key until “rST” label starts blinking.
Push the DEF key for more than 2 seconds and a manual defrost will start.
Another possibility is the following: after switching ON the instrument the user can push Set and DOWN keys within 30 seconds.
NOTE: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing “SET” + n. When a parameter is present in “Pr1” “decimal
point “ is on.
followe
2. e LED switches ON and the current time is displayed.
d by
3. By pushing the SET key, the e LED will start flashing and setting the current hour, minutes, day and the weekly holidays (up
to 3) will be possible.
4. To exit, press SET + UP or wait 15s without pressing any key.
followe
2. e LED switches ON and the current time is displayed.
d by 3. By pushing DEF key, the DEF led will start flashing and setting defrost time will be possible.
4. To exit, press SET + UP or wait 15s without pressing any key.
followe
2. e LED switches ON and the current time is displayed.
d by 3. By pushing the ES key, the ES led will start flashing and setting Energy Saving time will be possible.
4. To exit, press SET + UP or wait 15s without pressing any key.
6. PARAMETER LIST
REGULATION
Hy Differential: (0,1÷25,5°C; 1÷45°F): Intervention differential for set point, always positive. Compressor Cut IN is Set Point Plus Differential (Hy).
Compressor Cut OUT is when the temperature reaches the set point.
LS Minimum set point limit: (-50,0°C÷SET; -58°F÷SET) Sets the minimum acceptable value for the set point.
US Maximum set point limit: (SET÷110°C; SET÷230°F) Set the maximum acceptable value for set point.
odS Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up of the instrument and inhibits any output
activation for the period of time set in the parameter. (AUX and Light can work)
cco Compressors: kind of activation. Used only if oA1 =cP2: SE = sequential activation; AL = by turn activation
AC Anti-short cycle delay: (0÷30 min) interval between the compressor stop and the following restart.
Ac1 2nd compressor delay at start up (0÷255s) Time interval between the switching on of the first compressor and the second one. (0÷225s).
CCt Thermostat override: (0min ÷23h 50min) allows to set the length of the continuous cycle. Can be used, for instance, when the room is filled
with new products.
Con Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is active in case of faulty thermostat probe. With
COn=0 compressor is always OFF.
1592017000 XLR 130-170 GB r2.0 08.09.2006.doc XL130 - XLR170 8/19
dIXEL Installing and Operating Instructions rel.2
rel.2.0 - cod. 1592017000
COF Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is off in case of faulty thermostat probe. With
COF=0 compressor is always active.
CH Type of action - Only for XLR130: CL = cooling; Ht = heating..
DISPLAY
CF Temperature measurement unit: °C = Celsius; °F = Fahrenheit . When the measurement unit is changed the SET point and the values of the
regulation parameters have to be modified
rES Resolution (for °C): (in = 1°C; de = 0,1°C) allows decimal point display. dE = 0,1°C; in = 1 °C
Lod Local display : select which probe is displayed by the instrument: P1 = Thermostat probe; P2 = Evaporator probe; P3 = auxiliary probe
1r2 = difference between P1 and P2 (P1-P2)
DEFROST
tdF Defrost type Only for XLR170: rE = electrical heater (Compressor OFF); rT = thermostat defrost. During the defrost time “MdF”, the heater
switches On and OFF depending on the evaporator temperature and “dtE” value; in = hot gas (Compressor and defrost relays ON)
EdF Defrost mode:
rtc = Real Time Clock mode. Defrost time follows Ld1÷Ld8 parameters on workdays and Sd1÷Sd8 on holidays. Available only if the ’RTC
option is present
in = interval mode. The defrost starts when the time “Idf” is expired.
Sd = Smartfrost mode. The time IdF (interval between defrosts) is increased only when the compressor is running (even non consecutively)
and only if the evaporator temperature is less than the value in "SdF” (set point for SMARTFROST).
SdF Set point for SMARTFROST: (-30÷30 °C/ -22÷86 °F) evaporator temperature which allows the IdF counting (interval between defrosts) in
SMARTFROST mode.
dtE Defrost termination temperature Only for XLR170: (-50,0÷110,0°C; -58÷230°F) (Enabled only when the evaporator probe is present) sets
the temperature measured by the evaporator probe which causes the end of defrost.
dtS Defrost termination temperature 2nd evaporator – Only for XLR170 if oA1=dF2 : (-50,0÷110,0°C; -58÷230°F) sets the temperature
measured by the 2nd evaporator probe which causes the end of defrost.
IdF Interval between defrosts: (1÷120h) Determines the time interval between the beginning of two defrost cycles.
MdF (Maximum) duration of defrost: (0÷255 min) When P2P = n, no evaporator probe, it sets the defrost duration, when P2P = y, defrost end
based on temperature, it sets the maximum length for defrost.
MdS (Maximum) duration of defrost for 2nd evaporator – Only for XLR170 if oA1=dF2: (0÷255 min) It sets the maximum duration of the defrost
for 2nd evaporator.
dFd Display during defrost: rt = real temperature; it = temperature at the defrost start; Set = set point; dEF = “dEF” label; dEG = “dEG” label;
dAd Defrost display time out: (0÷255 min) Sets the maximum time between the end of defrost and the restarting of the real room temperature
display.
dSd Start defrost delay - Only for XLR170: ( 0÷99min) This is useful when different defrost start times are necessary to avoid overloading the
plant.
Fdt Drain down time: (0÷60 min.) time interval between reaching defrost termination temperature and the restoring of the control’s normal
operation. This time allows the evaporator to eliminate water drops that might have formed due to defrost.
dPO First defrost after start-up:
y = Immediately; n = after the IdF time
dAF Defrost delay after fast freezing: (0min÷23h 50min) after a Fast Freezing cycle, the first defrost will be delayed for this time.
dFP End defrost probe for first evaporator selection – Only for XLR170: nP = no probe, defrost by time. Duration set by MdF parameter; P1 =
Probe 1 (thermostat probe); P2 = Probe 2 (evaporator probe); P3 = Probe 3 (display probe).
dSP End defrost probe for second evaporator selection – Only for XLR170: nP = no probe, defrost by time. Duration set by MdS parameter; P1
= Probe 1 (thermostat probe); P2 = Probe 2 (evaporator probe); P3 = Probe 3 (display probe).
FANS
FnC Fan operating mode: C-n = running with the compressor, OFF during the defrost;
C-y = running with the compressor, ON during the defrost;
O-n = continuous mode, OFF during the defrost;
O-y = continuous mode, ON during the defrost;
Fnd Fan delay after defrost: (0÷255 min) The time interval between the defrost end and evaporator fans start.
FSt Fan stop temperature: (-50÷110°C; -58÷230°F) setting of temperature, detected by evaporator probe, above which the fan is always OFF.
dSP Fan probe selection: nP = no probe, fans act according to the Fnc parameter, without temperature control set in FSt parameter; P1 = Probe 1
(Thermostat probe); P2 = Probe 2 (evaporator probe); P3 = Probe 3 (display probe).
ALARMS
ALC Temperature alarm configuration: rE = High and Low alarms related to Set Point;
Ab = High and low alarms related to the absolute temperature.
ALU High temperature alarm setting: ( ALC= rE, 0 ÷ 50°C or 90°F; ALC= Ab, ALL ÷ 110°C or 230°F)
when this temperature is reached and after the ALd delay time the HA alarm is enabled.
ALL Low temperature alarm setting: ( ALC = rE , 0 ÷ 50 °C or 90°F; ALC = Ab , - 50°C or -58°F ÷ ALU)
when this temperature is reached and after the ALd delay time, the LA alarm is enabled,.
AFH Temperature alarm and fan differential: (0,1÷25,5°C; 1÷45°F) Intervention differential for temperature alarm set point and fan regulation set
point, always positive.
1592017000 XLR 130-170 GB r2.0 08.09.2006.doc XL130 - XLR170 9/19
dIXEL Installing and Operating Instructions rel.2
rel.2.0 - cod. 1592017000
ALd Temperature alarm delay: (0÷255 min) time interval between the detection of an alarm condition and the corresponding alarm signalling.
dAO Delay of temperature alarm at start-up: (0min÷23h 50min) time interval between the detection of the temperature alarm condition after the
instrument power on and the alarm signalling.
EdA Alarm delay at the end of defrost: (0÷255 min) Time interval between the detection of the temperature alarm condition at the end of defrost
and the alarm signalling.
dot Delay of temperature alarm after closing the door : (0÷255 min) Time delay to signal the temperature alarm condition after closing the door.
doA Open door alarm delay:(0÷254min,nu) delay between the detection of the open door condition and its alarm signalling: the flashing message
“dA” is displayed. If doA=nu the door alarm will be not signalled.
rrd Output restart after door open alarm doA: no = outputs unchanged after doA alarm; yES = outputs restart after doA alarm;
tbA Buzzer and alarm relay silencing: by pushing one of the keypad buttons.
n= Only the Buzzer is silenced; y= Buzzer and relay are silenced.
nPS Pressure switch number: (0 ÷15) Number of activation of the pressure switch, during the “did” interval, before signalling the alarm event (I2F=
PAL).
PROBE INPUTS
Ot Thermostat probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offset of the thermostat probe.
OE Evaporator probe calibration – Only for XLR170: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offsets of the evaporator probe.
O3 Auxiliary probe calibration: (-12.0÷12.0°C/ -21÷21°F) allows to adjust possible offsets of the evaporator probe.
P2P Evaporator probe presence - Only for XLR170:
n= not present: the defrost stops only by time; y= present: the defrost stops by temperature and time.
P3P Auxiliary probe presence (display): n= not present; y= present.
Pbr Thermostat probe selection P1 = Probe 1 (Thermostat probe); P2 = Probe 2 (evaporator probe); P3 = Probe 3 (display probe); 1r2 = P1-P2.
HES Temperature increase during the Energy Saving cycle : (-30÷30°C / -54÷54°F) sets the increasing value of the set point during the Energy
Saving cycle.
DIGITAL INPUTS
odc Compressor and fan status when open door:
no = normal; Fan = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF.
I1P Door switch input polarity: CL : the digital input is activated by closing the contact; OP : the digital input is activated by opening the contact.
I2P Configurable digital input polarity: CL : the digital input is activated by closing the contact;
OP : the digital input is activated by opening the contact
I2F Digital input operating mode: configure the digital input function: EAL = generic alarm; bAL = serious alarm mode; PAL = Pressure switch;
dFr = Start defrost; AUS = Relay AUX actuation; Es = Energy Saving; onF = remote On/OFF; HdF = Holiday function.
did Time interval/delay for digital input alarm:(0÷255 min.) Time interval to calculate the number of the pressure switch activation when
I2F=PAL. If I2F=EAL or bAL (external alarms), “did” parameter defines the time delay between the detection and the successive signalling of
the alarm.
TO SET CURRENT TIME AND WEEKLY HOLIDAYS ( 3SEC followed by ) – Only for models with RTC
Hur Current hour (0 ÷ 23 h)
Min Current minute (0 ÷ 59min)
dAY Current day (Sun ÷ SAt)
Hd1 First weekly holiday (Sun ÷ nu) Set the first day of the week which follows the holiday times.
Hd2 Second weekly holiday (Sun ÷ nu) Set the second day of the week which follows the holiday times.
Hd3 Third weekly holiday (Sun ÷ nu) Set the third day of the week which follows the holiday times.
OTHER
Adr RS485 serial address (1÷247): Identifies the instrument address when connected to a ModBUS compatible monitoring system.
PbC Probe selection: (Ptc=PTC probe; ntc=NTC probe). It allows to select the kind of probe.
Rel Release software: (read only) Software version of the microprocessor.
Ptb Parameter table: (read only) it shows the original code of the dIXEL parameter map.
dP1 Probe 1 temperature (thermostat): it displays the temperature detected by the thermostat probe.
dP2 Probe 2 temperature (evaporator): it displays the temperature detected by the evaporator probe.
dP3 Probe 3 temperature (display): it displays the temperature detected by the display probe.
Pr2 Access to the protected parameter list (read only).
7. DIGITAL INPUTS
The Wing series can support up to 2 free contact digital inputs. One is always configured as door switch, the second is programmable in seven
different configurations by the “I2F” parameter.
F G F
D E B
C
D
A
A C B
FIG. 2
FIG. 1
87 230
I
H
130
MAX
28
MAX
210
120
37
FIG. 3
200
A
61
10
6 .4
4°
0 0 18 172 190
Fig. 6 Fig. 4
200
8.5
R5
192.5
18561
10
6.4
8.5 4° R
5
12
6
0
0 190
4 186
11 179
14.5 175.5
22.5 167.5
29.5 160.55
Fig. 5
9. DIMENSIONS
210 87
230
NOTE: the “Err” message is displayed for failed programming. In this case push again o key if you want to restart the upload again or remove the
NOTE the message “Err” is displayed for failed programming. In this case turn the unit off and then on if you want to restart the download again or
remove the “Hot key” to abort the operation.
15. CONNECTIONS
15.1 XLR130
15.1.1 FREE VOLTAGE CONTACTS
20A 250V
35 36 16FLA(96LRA)
20A 250V 16A 8A
RS 485 16FLA(96LRA) 250V~ 250V~
optional
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
NC N
15.2 XLR170
15.2.1 FREE VOLTAGE CONTACTS
20A 250V
35 36 16FLA(96LRA)
20A 250V 16A 16A 8A 8A
RS 485 16FLA(96LRA) 250V~ 250V~ 250V~ 250V~
optional
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
NC NC Line N
Dixell S.p.A. Via dell’Industria, 27 - 32010 Z.I Pieve d’Alpago (BL) ITALY
tel. +39 – 0437 - 98 33 – fax +39 - 0437 - 98 93 13
E-mail: [email protected] - http://www.dixell.com