85001-0548 - Optical Beam Smoke Detector

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Page 1 of 4 D A T A S H E E T 85001-0548

Not to be used for installation purposes. Issue 5


EST Catalog u Conventional Initiating
0
6
-
2
1
-
1
0
Overview
The Fireray 2000 is a projected beam smoke detector designed to
detect smoke in a large volume. The system is comprised of three
pieces, a transmitter head, a receiver head, and a control box.
The transmitter projects a modulated infrared light beam to the
receiver. At the receiver, the signal is sent to the controller, where
it is analyzed. If there is smoke in the beam path, the receivers
signal is reduced by a level proportional to the density of the
smoke. When the signal strength is reduced to a level between the
obscuration threshold and 93% for more than 8 to 10 seconds,
the re alarm output relay is activated. The alarm obscuration
threshold may be set at 25%, 35% or 50% obscuration, depend-
ing on the application. Reduction in signal strength below 93% is
indicated as a fault condition.
The controller is designed to mount near ground level where it is
convenient for maintenance. The controller is powered by the re
alarm control panel (FACP) and returns both alarm and trouble
signals to the FACP via relay contacts. The controller features
an automatic gain control that automatically compensates for
component aging, and dirt on the optical surfaces. The optional
installation aid is used to quickly align the beam and a test card is
supplied with each controller to perform functional tests.
Standard Features
Coverage up to 330 ft (100m) x 50 ft (15.24m) - 16,000 ft
(1,524 m)
Use with prism reectors
Supervised
Automatic gain control
Alarm and trouble contacts
Controls located at convenient level
Wide beam angle simplies alignment and provides stability
Low current consumption
MEA
Optical Beam
Smoke Detector
FIRERAY 2000
Page 2 of 4 D A T A S H E E T 85001-0548
Not to be used for installation purposes. Issue 5
Application
Projected beam smoke detectors are ideal for large volume ap-
plications such as atria, warehouses, factories, churches, power
stations, and industrial plants. Detection time depends on a
number of factors including the location of the detectors within the
protected area, the volume of smoke produced by the re, roof
construction and the ventilation arrangements.
For at ceiling applications, smoke typically makes its way into the
detection beam from the point on the ceiling directly above the
re due to air currents and heat layering effects. At the maximum
range of 330 ft (100m) the diameter of the beam is approximately
10 ft (3m). For reliable detection, the maximum distance either
side of the beam axis has been determined to be 25 ft (7.6m). Us-
ing this spacing yields a maximum total coverage area of 16,500
square feet (1,524m). Smoke layering is overcome by mounting
detectors such that the beam is below the heat layer and project-
ing into the smoke layer. For at ceiling applications the system is
designed to be mounted approximately 19 inches (482mm) below
and parallel to the roof or ceiling. Detection time is increased in
buildings with peaked roofs should a re occur at the fringes of
the protected area. No more than approximately 10 ft (3m) of the
beam path should be within 19 in (482mm) of any wall or partition
and the centerline of the beam.
When access to the opposite wall is restricted or where wiring is dif-
cult, the transmitter may be installed adjacent to the receiver. A prism
is then mounted on a far wall and used to reect the signal from the
transmitter back to the receiver. When prisms are used, maximum
beam length is reduced as shown in the specication table.
Typical Wiring
Shielded cable recommended for all wiring.
The control unit must be grounded to the power supply.
Terminate shields outside the control cabinet at the cable
clamp. Do NOT let shields enter the cabinet.
Use metal junction boxes only, no plastic boxes permitted.
Relay wiring
as required
CABLE
CLAMP
CABLE
CLAMP
CABLE
CLAMP
CABLE
CLAMP
Remote reset switch
or relay close momentarily
to reset
May be same P.S.U.
as for control unit
P.S.U. (24 Vdc)
TEST
METER
EXTERNAL
RESET
-VE +VE
(0V) (24Vdc)
-VE +VE
(0V) (24Vdc)
P.S.U.
B R
R +V Rx
SIGNAL Rx
0V Rx
Y
B
SIGNAL LEVEL
LOW HIGH
TEST/RESET
ON OFF
SW5
TROUBLE LED
Rx
Tx
A
L
A
R
M
T
R
O
U
B
L
E
N/O
N/C
COM
N/O
N/C
COM
100 MA
ALARM LATCH
COMP
25%
35%
50%
+
+
-
-
S
U
P
P
L
Y
2
4
V
d
c
Page 3 of 4 D A T A S H E E T 85001-0548
Not to be used for installation purposes. Issue 5
Ordering Information
Specications
Controller
Power Requirements
Standby
Alarm
8.5 mA
14.5 mA
Output Relays
Alarm
Trouble
Form C rated 0.5 A @ 30 Vdc
Form C rated 0.5 A @ 30 Vdc
LED Indicators Alarm Signal High Signal Low Fault
Reset Congurable, manual or automatic
Dimensions (HxWxD) 10.5 in (260 mm) x 8.5 in (210 mm) x 3.5 in (89 mm)
Weight 5 lb (2.25 kg)
Operating Environment
Temperature
Humidity
32 F to 100 F (0 C to 38 C)
93%RH, Non-condensing
Detector Heads
Beam
Width
Length
25 ft (7.62 m) either side of transmitter centerline
33 ft (10 m) to 330 ft (100 m)
Alarm Threshold 25%, 35%, or 50% obscuration
Wiring Requirements
Transmitter
Receiver
2 conductor twisted-shielded, 18 AWG (0.75 mm)
3 conductor twisted-shielded, 18 AWG (0.75 mm), 330 ft (100 m) max.
Power Requirements
Transmitter
Receiver
5 mA @ 24 Vdc
Nominal Supplied by controller
Dimensions (HxWxD) with
Bracket
3.75 in (95 mm) x 3.25 in (83 mm) x 4 in (101 mm)
Weight with Bracket 14 oz (400 g)
Environment
Temperature
Humidity
32 F to 100 F (0 C to 38 C)
93%RH, Non-condensing
Beam Ranges using Prism(s)
1 Prism
4 Prisms in a square
6 Prisms in a rectangle
6.5 ft (1.98 m) to 82 ft (25 m)
82 ft (25 m) to 115 ft (35 m)
115 ft (35 m) to 148 ft (45 m)
Construction Zinc Alloy housing nished in white enamel
Prism Dimensions (HxWxD) 4 in (100 mm) x 4 in (100mm) x 5/16 in (9 mm)
Model Description Ship Wt., lb (kg)
22310-18-01 Beam Smoke Detector Controller with Heads 8.5 (3.9)
0201-01-A Beam Alignment Aid 1 (.45)
23901-00 Prism - Beam Detector 0.3 (.14)
Page 4 of 4 D A T A S H E E T 85001-0548
Not to be used for installation purposes. Issue 5
0
6
-
2
1
-
1
0
Detection & alarm since 1872
U.S.
T 888-378-2329
F 866-503-3996
Canada
Chubb-Edwards
T 519 376 2430
F 519 376 7258
Southeast Asia
T : +65 6391 9300
F : +65 6391 9306

India
T : +91 80 4344 2000
F : +91 80 4344 2050

Australia
T +61 3 9239 1200
F +61 3 9239 1299
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Latin America
T 305 593 4301
F 305 593 4300
utcreandsecurity.com
2010 UTC Fire & Security.
All rights reserved.

You might also like