The document describes an earth fault current relay. It provides details on the applications, characteristics, design, operation, and testing of the relay. The relay can be used for zero-current differential protection of transformers and as a highly stabilized differential relay for alternators, transformers and motors.
The document describes an earth fault current relay. It provides details on the applications, characteristics, design, operation, and testing of the relay. The relay can be used for zero-current differential protection of transformers and as a highly stabilized differential relay for alternators, transformers and motors.
The document describes an earth fault current relay. It provides details on the applications, characteristics, design, operation, and testing of the relay. The relay can be used for zero-current differential protection of transformers and as a highly stabilized differential relay for alternators, transformers and motors.
The document describes an earth fault current relay. It provides details on the applications, characteristics, design, operation, and testing of the relay. The relay can be used for zero-current differential protection of transformers and as a highly stabilized differential relay for alternators, transformers and motors.
C&S Electric Limited (Protection & Control Division) IRI1-ER- Stablized Earth Fault Current Relay 2 Contents 1. Introduction 2. Applications 3. Characteristics and features 4. Design 4.1 Connections 4.1.1 Analog inputs 4.1.2 Output relays 4.2 Front plate 4.2.1 LEDs 4.2.2 DIP-switches 4.2.3 <RESET> push button 4.3 Code jumper 5. Working principle 6. Operations and settings 6.1 Layout of the operating elements 6.2 Setting of the pick-up value for the differential current ID 6.2.1 Indication of fault 6.3 Reset 6.3.1 Reset by pressing the <RESET> push button 6.3.2 Automatic reset 6.4 Calculation of the tripping current and the stabilizing resistance 6.4.1 Sample calculation - alternator 6.4.2 Example calculation - transformer 6.5 Application of IRI1-3ER relay as High Impedance Bus Differential Protection 7. Housing 7.1 Individual housing 7.2 Rack mounting 7.3 Terminal connections 8. Relay testing and commissioning 8.1 Power On 8.2 Checking the set values 8.3 Secondary injection test 8.3.1 Test equipment 8.3.2 Example of a test circuit for a IRI1-3ER- relay 8.3.3 Checking the pick-up and tripping values ( I RI 1-ER) 8.3.4 Checking the operating and resetting values (IRI1-3ER) 8.4 Primary injection test 8.5 Maintenance 9. Technical Data 9.1 Measuring input 9.2 Auxiliary voltage 9.3 General data 9.4 Output relay 9.5 System data 9.6 Setting ranges and steps 9.7 Dimensional drawing 10. Order form IRI1-ER- Stablized Earth Fault Current Relay 3 1. Introduction The application of powerful microprocessors with MR- and IR-relays of the HIGH TECH RANGE provides a large variety of advantages over power protection systems of the traditional type. The MR-protection relays are based exclusively on the microprocessor technology. They represent our most efficient generation of power protection systems. Because of their capabilities to process measured values digitally and to perform arithmetical and logical operations, they are superior to the traditional analog systems. Besides, the digital protection relays offer important additional advantages such as very low power consumption, adaptability, flexible construction, selection of relay characteristics etc. The I R- pr ot ect i on r el ays ar e based on t he mi croprocessor t echnol ogy or on t he anal og technology. They represent a more cost saving generation of relays of the HIGH TECH RANGE, used for basic equipment protection. The IR-protection relays are superior to conventional prot ect i ve devi ces because of t hei r fol l owi ng characteristics: Integration of multiple protective functions into one compact housing User-friendly setting procedure by means of DIP- switches Compact construction type by SMD-technology MR-protection relays are used for more complex protective functions, such as earth fault directional detection, and also in cases where easy operation, quick fault-analysis and optimal communication capabilities are required. All relays of the HIGH TECH RANGE are available for flush mounted installation, as well as for 19 rack mounting. Plug-in technology is used. Of course, all relays comply with the IEC/DIN regulations required for the specific protection application. 2. Applications The stabilized earth fault current relay IRI1-ER serves as a suppl ement for t he t ransformer di fferent i al protection. It allows for example implementation of a zero-current differential protection by integrating the star-point current (IRI1-ER). With the view to its higher resistance to disturbances from outside the protection area, it can be set much more sensitively than the simple transformer differential protection, in order to prevent false trippings. The IRI1-ER can be used as: Zero-current differential protection of the star point winding (restricted earth fault) of a transformer (IRI1-ER), see figure 2.1 Highly stabilized differential current relay for alternator, transformers and motors (IRI-3ER), see figure 2.2 Fig. 2.1: Zero-current differential protection of a transformer in star-connection (IRI1-ER) Fi g. 2. 2: Hi ghl y st abi l i zed di f f er ent i al prot ect i on f or al t ernat ors, t ransf ormers and motors (IRI-3ER) l l l l l l l l L1 Transformer L2 L3 R sr IRI1-ER I> L1 L2 L3 l l l l l l l l l l IRI1-3ER R sr R sr R sr Motor Transformer Alternator 3. Characteristics and features static protective device single-phase current measuring (IRI1-ER) as zero-current differential protection (restricted earth fault 64 REF) three-phase current measuring (IRI1-3ER) as phase-current differential protection high stability by serial stabilizing resistor Rsr per phase high sensitivity by low input burden of C.T. extremely wide setting range with fine grading wide range of operation of the supply voltage (AC/DC) coding for the self-holding function or automatic reset of the LEDs and trip relays frequency range 50/60 Hz rated current 1A or 5A output relay with 2 change-over contacts IRI1-ER- Stablized Earth Fault Current Relay 4 Fig. 4.2: Connection diagram IRI1-3ER 4.1.1 Analog inputs At three-phase measuring, the analog input signals of the differential currents are fed to the protective device via terminals B1 to B6 (IRI1-3ER), respectively at single phase measuring via terminals B1/B2 (IRI1-1ER). L1 L2 L3 P1 S2P2 S2P2 S1P1 P2 S1P1 S1 S2 P1 S2P2 S2P2 S1P1 P2 S1P1 S1 S2 l l l l l l l l l l l 50/60Hz 50/60Hz 50/60Hz l ~ D9 E9 C9 L-/N L+/L D1 C1 E1 D2 C2 E2 R sr R sr R sr B2 B3 B4 B5 B6 B1 Reset Trip I D I D I D Power Supply ~ 4. Design 4.1 Connections Fig. 4.1: Connection diagram IRI1-ER l l l l l l l P1 P2 S1 S2 P1 S2P2 S2P2 S2 S1 S1P1 P2 S1P1 L1 L2 L3 D9 D1 C1 E1 D2 C2 R sr 50/60Hz B2 B1 E2 Reset Trip I D I D E9 C9 L-/N L+/L Power Supply I D ~ 4.1.2 Output relays Both relay types are equipped with a trip relay with two change-over contacts. Tripping I D : D1, C1, E1 D2, C2, E2 IRI1-ER- Stablized Earth Fault Current Relay 5 4.2 Front plate Fig. 4.3: Front plate The front plate of the IRI1-ER comprises the following operation and indication elements: 1 set of DIP-switches for setting the tripping value 2 LEDs for indication of faults- and readyness for operation 1 <RESET> push button 4.2.1 LEDs On the front plate of the IRI1-ER 2 LEDs are installed, signalizing the following 2 service conditions: LED ON (green): readyness for service LED I D (red): tripping 4.2.2 DIP-switches The set of DIP switches on the front plate serves for setting the tripping value for the differential current I D . 4.2.3 <RESET>-push button The <RESET> push but t on i s used f or acknowledgement and reset of the LED and the tripping relay after tripping at the specifically preset value (see 4.3). 4.3 Code jumper Behind the front plate, two coding jumpers are installed at the bottom side for setting the LED-display, as well as for the tripping function of the output relay. Fig. 4.4: Code jumper Code Function Position of Operating mode jumper code jumper 3 Differential current OFF latching of the red LED I D indication ON automatic reset of the red LED I D 4 Differential current OFF latching of the tripping relay tripping ON automatic reset of the tripping relay Table 4.1 Code jumper I D I D ON Code jumper Code jumper ON Front plate 3 4 Code jumper OFF RESET 7.5% 5 10 20 40 ON I D 5 0 0 0 0 I D IRI1-3ER IRI1-ER- Stablized Earth Fault Current Relay 6 6. Operations and settings 6.1 Layout of the operating elements The DIP-switch required for setting of parameters is located on the front plate of the relay. 6.2. Setting of the pick-up value for the differential current I D The pick-up value of the differential current tripping I D can be set by means of the DIP-switches set I D in the range of 5% to 82.5% x I N with a grading of 2.5%. The pick-up value is calculated by adding up the values of all DIP-switches. 5. Working principle The protection relay IRI1-ER is connected to the differential circuit of the c.t.s as a current differential protection relay. When used as zero-current differential protection (restricted earth fault), the relay (IRI1-ER) is to be connected acc. figure 2.1. When used as highly stabilized differential current relay, the relay (IRI1-3ER) is to be connected acc. figure 2.2. The knee voltage U Kn is an important characteristic of the transformer. The transformer does not work linearly anymore above this voltage. Two transformers of the same class still show the same behavior below U Kn within the scope of their precision class. Above U Kn they can, however, show very different saturation behavior. Connected in a differential current circuit an apparent fault current can thus be measured at large primary current intensity which really results only from the different saturation of both transformers. An additional stabilizing resistor R ST counteracts this effect. It attenuates the current flow through the measuri ng devi ce. Thi s way t he unsat urat ed transformer drives part of its current into the saturated Fig. 5.1 Single line diagram IRI1-ER transformer and minimizes the faulty differential current effect on secondary side. By small currents the stabilizing resistor effects however also the accuracy of the real fault current measurement. Because this effect lies in a linear range it can be taken into consideration mathmatically by adjusting the protection device. (see para. 6.4). For demonstrating the working principle, figure 5.1 shows the single-line diagram of the IRI1-ER. Protecting object R S I F I R U S Z Z Z = 0 R At saturated C.T. R sr R L R L I F R S The harmonics existing during a transformer saturation and the DC-component are suppressed by a filter circuit located in the input circuit of the relay; the filter circuit is adjusted to the mains frequency (50/60Hz). The IRI1-ER has a single-phase differential current supervision with an adjustable pick-up value. The current measured in the differential circuit is constantly compared with the set reference value. Measuring principle IRI1-ER The analog current signals are galvanically decoupled via the input transformer and are led over a low pass with subsequent band-pass for suppression of the harmonics, then rectified and compared with the set reference value of a comparator. In case the current measur ed exceeds t he r ef er ence val ue, an instantaneous tripping takes place (figure 4.1). The IRI1-3ER has a three-phase differential current supervision with adjustable pick-up value. The currents measured in the individual differential circuits are constantly compared with the set reference value. Measuring principle IRI1-3ER The analog current signals are galvanically decoupled via three input transformers and led over a low pass with subsequent band-pass for suppressing the harmonics. Then rectified and compared with the set reference value of a comparator. In case one of the three currents measured exceeds the reference value, an instantaneous tripping takes place (figure 4.2). IRI1-ER- Stablized Earth Fault Current Relay 7 Exampl e: A pick-up value of 30% of the rated current is required. 6.2.1 Indication of fault The fault alarm is shown by the LED I D on the front plate of the relay, which lights up red at tripping. Depending on the coding by means of the code jumper (see chapter 6.3.2), the fault alarm extinguishes automatically or after pressing the <RESET> push button, after the fault is eliminated. 6.3 Reset 6.3.1 Reset by pressing the <RESET>- push-button By pressing the <RESET> push button, the tripping relay is reset and the LED-signal extinguishes. All coding switches must be plugged out for this (see chapter 4.3). 6.3.2 Automatic reset Code jumper 1 If no code jumper is plugged in at coding place 1, the red fault alarm LED I D is coded latching. The fault signal can only be reset manually by pressing the <RESET> push button. If the code jumper is plugged in at coding place 1, the red fault signal LED I D is automatically reset, after the fault is eliminated. Code jumper 2 The tripping relay is coded latching, if no code jumper is plugged in on coding place 2. The tripping relay can only be reset manually by pressing the <RESET> push button. If the code jumper is plugged in on coding place 2, the tripping relay is automatically reset after elimination of the fault. 5 0 0 0 7.5% 5 10 20 40 I D I D = 5 + 5 + 20 = 30% x I N 6.4 Calculation of the tripping current and the stabilizing resistance Prior to setting the relay, the stabilizing resistance R sr , as well as the tripping current I set must be calculated. For the correct setting, the knee-point voltage in the magnetizing circuit of the c.t. is of special importance. In order to obtain a sufficient differential current for tripping on account of internal faults, the knee-point voltage U kn of the transformer should be twice as high as the maximum expected stabilizing voltage U S in case of faults from outside the protection zone. From this results the following calculation: U Kn = 2 U S = 2 I f,sek (R S + R L ) Expl anati on: U kn knee-point voltage of the magnetizing circuit of the transformer U s maximum stabilizing voltage in case of external faults I f,sek maximum expected fault current (secondary-side) in case of external faults R S secondary resistance of the transformer R L Resistance of the connection line between c.t. and relay The tripping current of the relay is then calculated, as follows: I D > Expl anati on: R Sr stabilizing resistance The strength of the stabilizing resistance must be selected in a way to ensure that the tripping current is within the setting range (5% to 82.5% of I N ). When the pick-up value is exceeded, nearly an immediate tripping is initiated. With 30 ms the tripping time is approx. five times as high as the tripping value. In case of lower currents, the tripping time is slightly higher (about 100ms), in order to reach a stabilization of the protective function against external faults (see also chapter 5). 6.4.1 Sample calculation - alternator An IRI1-ER protection relay is used for the earth-fault protection of an alternator. In the starpoint, the following c.t. is provided: transformation ratio : 100/1A class : 5 P 10 output : 2.5 VA secondary resistance of the transformer : <0.7 U Kn 2 . R Sr IRI1-ER- Stablized Earth Fault Current Relay 8 The individual resistance values are: 2 x R L = 150 m, at 20 m, 2.5 mm Cu 2 R L + R r + R S = 0.87 Therefore, the following is valid: R kreis = = 62.5 Calculation of the stabilizing resistance The stabilizing resistance is calculated from above ratios, as follows: R S = S r circuit - (2 R L + R r + R S ) = R circuit - 0.87 = 61.6 In operational mode < I D , the output requirement P N is as follows: P N < I x R sr = 0.2 A x 61.6 < 2.47 W In this case, P N represents the minimum output required (pure current-heat losses). A considerably increased output P F is required in the event of a fault. Example: The fault current is: I F,prim = 13.1 kA If one neglects the transformer saturation, the following peak voltage U P occurs: U p = (R Sr + 2 R L + R r + R S ) U p = (62.5) = 8187.5 V If one considers the transformer saturation, a short- term peak voltage U SS occurs, as shown in the following calculation: U SS = 2(2U Kn (U p - U Kn )) +0.5 < 3 kV U SS = 2(225 V (8187.5 V - 25 V)) +0.5 = 1.28 kV Pr = = 26.6 kW The calculation of P N and P F must be effected in any case, in order to get the exact power range of the stabilizing resistor. Take over of power by the resistor in the event of a fault P F creates a short-term peak value. 6.4.2 Example calculation -transformer An IRI1-ER protection relay is used for the earth-fault protection of a 1.6 MVA-transformer (11000/415 V, 6%), see figure 2.1. The following c.t.s are used in the rigidly earthed starpoint: transformation ratio: 2 500/1A class: X resistance Rs: 8 knee-point voltage: 250 V The relay is situated about 20m away from the c.t.s and is connected with a 2.5 mm 2 cable. Calculation of the stabilizing voltage The primary-side fault-current I F,prim is: I F,prim = = 37.1 kA Line resistance R L (2.5 mm ~ 7.46 /km) RL = 20 m X = 0.15 Additional resistance R r (ca. 0.02 ) A primary-side fault current of 20% x I N shall be recorded. The secondary current i s used for calculation. Calculation of the knee-point voltage If the knee-point voltage is not indicated by the manufacturer, as is the case in our example, the approximate value can be calculated, as follows: U kn = = 25V Expl anati on: S output of the c.t. k lu overcurrent factor of the c.t. I N secondary-side rated current of the transformer Calculation of the active resistances The relevant resistances in the differential circuit add up to a total (circle-) resistance: R circuit = = R Sr + 2R L +R S +R r Expl anati on: R kreis total resistance in the differential circuit R sr stabilizing resistance R L resistance of the connection line between c.t. and relay R s secondary resistance of the transformer (<0.7) R r relay input resistance (B1 - B2 = 0.02 W) I D tripping current 2.510 1 Sk lu I N U Kn 2I Set 25 V 20.2 A I F,prim n 13100A 1 100 U SS 2 R Sr 1280 2 V 2 61.6 1600000 VA 3 X 415 V X 6% 7.46 1000 m IRI1-ER- Stablized Earth Fault Current Relay 9 I F,prim n 37100 A 1 2500 From this results the stabilizing voltage for: U S = X (2 X R L + R S + R r ) U S = X (2 X 0.15 + 8+ 0.01) =123.5 U p = X (8 + 2 X 0.15 + 0.02 + 308.75) = 4.7 kV U SS = 2 X (2 X 250 V X (4700 V X 250 V)) +0.5 = 298 Since the requirement is met, the set values and the resulting resistance values can be accepted. The calculation of the output requirement for the stabilizing resistance can be carried out similar to the calculation of sample 6.4.1. 37.1 kA 1 2500 Since the knee-point voltage shall be U kn = 2x U S (2 x 123.5V = 247 V), the above transformer with U kn = 250 V can be used. Calculation of the set current and the stabilizing resistance (sample value) The rating for the set current of 20% is calculated: I D = 20 % x I N = 0.2 x 1 A = 0.2 A From this results the stabilizing resistance for: R circuit = ~ R Sr => = 617.5 In the event of a fault, the stabilizing resistance must withstand a secondary-side false current of: I F sek = = 14.84 A The calculation of the short-term peak voltages provides the following result: U S = X (8 + 2 X 0.15 + 0.02 + 615) =9.25 kV Thus, the ratio U SS = 2 X (2 X U Kn X (U p - U Kn )) +0.5 < 3 kV U SS = 2X(2X250 V X(9250 V - 250V)) +0.5 = 4.24 kV is not reached and the calculation must be repeated with a higher set current. Calculation of the set current and the stabilizing resistance (actual value) The rating for the set current of 40% is calculated again: I D = 40 % x I N = 0.4 x 1 A = 0.4 A From this results the stabilizing resistance for: R circuit = ~ R Sr => = 308.75 Thus, the requirement of the short-term peak voltage is met. 1600000 VA 3 X 415 V X 6% X 2500 37.1 kA 1 2500 123.5 V 0.2 A U S I D U S I D 123.5 V 0.4 A 6.5 Application of IRI1-3ER relay as High Impedance Bus Differential Protection: IRI-1ER or IRI1-3ER (a 3-phase version of IRI1-1ER) relays also offers reliable Bus protection based on High Impedance Differential Principle. The figure below indicates a typical Single Bus system using IRI-ER relay for Bus Protection. This sample system incorporates two incoming and two outgoing bays. In case of normal operation, following Kirchoffs law, the currents terminating on bus and going put adds up to Zero with corresponding reproduction on CT secondary side of respective bays. As the vector summation of the currents balances each other out, the Relay does not operate. In case of internal faults, as the fault currents will be fed from all sources possible, the differential current will operate the relay. For External fault, though the amount of current flowing into the fault will increase, the net summation of the current again will zero and the relay will restrain. Here, it is important to consider unequal saturation characteristics of the Current transformers involved. It is also important to ascertain that the relay remains stable in presence of Harmonics and DC currents. Fig. 6.1 IRI1-ER- Stablized Earth Fault Current Relay 10 Especially for a Bus Differential relay, following factors are vital: Because of higher concentration of fault MVA, the Relay should operate very fast for heavy internal faults. The Relay should be reliably stable in presence of Harmonics especially 2 nd and 3 rd harmonics and presence of DC currents. IRI1-ER relays ensure: Operating time of less than 15 milliseconds at more than 5 times of the setting. 2 nd Harmonic rejection ratio of more than 4. 3 rd Harmonic rejection ratio of more than 40. Remains very stable against superimposed DC currents. Kpv 2.Rs RL : = 0.5 Rct : = 6 Zr : = Zr = 0.125 Kpv : = Ifs . (Rct + 2.RL) Kpv : = 186.667 Knee point required for the CT core should higher than, KpvCT : = 2 . Kpv KpvCT = 373.333 Rs : = -Zr Rs = 466.542 Up : = Ifs . (Rs + 2.RL + Rct + Zr) Up = 1.263 x 10 4 1.594 . 10000 = 1.594 x 10 4 Uss : = 2 . [2 . Kpv. (Up - Kpv]0.5 Uss = 4.311 x 103 =0.2 The use of Metrosil can be avoided as the relay can reliably withstand Uss up to 5 kV. For fault currents exceeding this level, the Metrosils should be used. [( ) ] Kpv Id 0.02 Id 2 Rs : Stabilising Resistance in Ohms Id : Differential Current Setting Up : Peak Voltage neglecting Saturation Uss : Short term peak Voltage considering Saturation Ifs: Secondary value of Fault Current Ifmax : 40000 kV : = 220 CTR : = 1500 MVAf : =3.kV.Ifmax MVAf = 1.524 x 10 7 Id : = 4 Ifs : = Ifs = 26.667 Ifmax CTR IRI1-ER- Stablized Earth Fault Current Relay 11 7. Housing The IRI1-ER can be supplied in an individual housing for flush-mounting or as a plug-in module for installation in a 19" mounting rack according to DIN 41494. Both versions have plug-in connections. Relays of variant D are complete devices for flush mounting, whereas relays of variant A are used for 19 rack mounting. 7.1 Individual housing The individual housing of the IRI1-ER is constructed for flush-mounting. The dimensions of the mounting frame correspond to the requirements of DIN 43700 (76 x 142 mm). The cut-out for mounting is 68.7 x 136.5 mm. The front of the IRI1-ER is covered with a transparent, sealable flap (IP54). 7.2 Rack mounting The IRI1-ER is in general suitable for installation in a modular carrier according to DIN 41494. The installation dimensions are: 12 TE; 3 HE. According to requirements, the IRI1-ER-devices can be delivered mounted in 19" racks. If 19" racks are used the panel requires protection class IP51. 7.3 Terminal connections The plug-in module has very compact base with plug connectors and screwed-type connectors. max. 15 poles screw-type terminals for voltage and current circuits (terminal connectors series A and B with a short time current capability of 500 A / 1 s). 27 poles tab terminals for relay outputs, supply voltage etc.(terminal connectors series C, D and E, max. 6 A current carryi ng capaci t y) . Connection with tabs 6.3 x 0.8 mm for cable up to max. 1.5 mm 2 or with tabs 2.8 x 0.8 mm for cable up to max. 1 mm 2 . By using 2.8 x 0.8 mm tabs a bridge connection between different poles is possible. The current terminals are equipped with self-closing short-circuit contacts. Thus, the IRI1-ER-module can be unplugged even with current flowing, without endangering the current transformers. The following figure shows the terminal block of IRI1- ER: Fig. 7.1: Terminal block of IRI1-ER 8. Relay testing and commissioning The following instructions should help to test the protection relay performance before or during commissioning of the protection system. To avoid a relay damage and to ensure a correct relay operation, be sure that: the auxiliary power supply rating corresponds to the auxiliary voltage on site the rated current and rated voltage of the relay correspond to the plant data on site the current transformer circuits are connected to the relay correctly all signal circuits and output relay circuits are connected correctly 8.1 Power On NOTE! Prior to switch on the auxiliary power supply, be sure that the auxiliary supply voltage corresponds to the rated data on the type plate. Switch on the auxiliary power supply to the relay (terminal C9/E9) and check that the LED ON on the front plate lights up green. 8.2 Checking the set values Check the DIP-switch positions, in order to verify the parameterized set value. If necessary, the set value can be corrected by means of the DIP-switch. IRI1-ER- Stablized Earth Fault Current Relay 12 8.3.3 Checking the pick-up and tripping values ( IRI1-ER ) With the IRI1-ER, the analog input signal of the singlephase testing AC must be supplied to the relay via the terminals B1/B2 for checking the pick-up value I D . For testing the differential current pick-up value, first the injected current must be set below the set pick-up value I d . Then the injected current is increased gradually, until the relay trips. This is indicated by the LED I D lighting up red, with the relay tripping at the same time. Check that the value shown at the ammeter does not deviate by more than +/- 3% from the set pick-up value I D . The resetting value of the differential current pick-up value is determined, by slowly decreasing the testing AC, until the output relay I D trips. The LED I D extinguishes (supposed the respective coding was effected). Check that the resetting value is greater than 0.97 times the pick up value, i.e. the resetting ratio of the differential current supervision is below 1. 8.3.4 Checking the operating and resetting values (IRI1-3ER) With the IRI1-3ER, all analog input signals of the single-phase current must be supplied to the relay via the terminals B1/B2; B3/B4; B5/B6 one after another for checking the pick-up value I D in similar manner as indicated above in para 8.3.3. 8.4 Primary injection test Principally, a primary injection test (real-time test) of a c.t. can be carried out in the same way as a secondary injection test. Since the cost and potential hazards may be very high for such tests, they should only be carried out in exceptional cases, if absolutely necessary. 8.5 Maintenance Maintenance testing is generally done on site at regular intervals.These intervals may vary among users depending on many factors: e.g. type of protective relays employed; type of application; operating safety of the equipment to be protected; the users past experience with the relay etc. For st at i c r el ays such as t he I RI 1- ER/- 3ER, maintenance testing once per year is sufficient. 8.3 Secondary injection test 8.3.1 Test equipment ammeter auxi l i ar y power suppl y wi t h a vol t age corresponding to the rated data on the type plate single-phase AC-power supply (adjustable from 0 - 2.0 x I N ) test leads and tools potentiometer Fig. 8.3.1 Test circuit IRI1-3ER L+/L L-/N ~ D9 E9 C9 Power Supply 50/60Hz 50/60Hz 50/60Hz l D1 C1 E1 D2 C2 E2 Reset I D Trip I D + I D 2 A 3 1. Current source 2. Amperemeter 3. Relay under test 4. Potentiometer adjust resistor 5. Switching device 6. Timer Stop Timer 6 + Start 4 5 Current source 1 B6 B5 B4 B3 B2 B1 - switching device timer 8.3.2 Example of a test circuit for a IRI1-3ER -relay For testing the IRI1-3ER-relay, only power signals are required. Fig. 8.3.1 shows an example of a test circuit with adjustable power supply. The phases are tested individually one after the other. IRI1-ER- Stablized Earth Fault Current Relay 13 9. Technical Data 9.1 Measuring input Rated data: Nominal current I N : 1A/5A Nominal frequency f N : 50/60 Hz Power consumption : <1 VA/at I N = 1A in current circuit : <5 VA/at I N = 5 A Thermal withstand : dynamic current withstand (half-wave) 250 x I N capability of current : for 1 s 100 x I N circuit : for 10 s 30 x I N continuously 4 x I N 9.2 Auxiliary voltage Rated auxiliary voltage U H : 24 V - working range : 16 - 60 V AC / 16 - 80 V DC 110 V - working range : 50 - 270 V AC / 70 - 360 V DC Power consumption: 24 V - working range : standby approx. 3 W operating approx. 6 W 110 V - working range : standby approx. 3 W operating approx. 6 W 9.3 General data Permissible interruption of the supply voltage without influence on the function : 50 ms Dropout to pickup ratio : >97% Returning time : 30 ms Minimum operating time : 30 ms 9.4 Output relay The output relay has the following characteristics: Maximum breaking capacity : 250 V AC / 1500 VA / continuous current 6 A Breaking capacity for DC: Max. rated making current : 64 A (acc. VDE 0435/0972 and IEC 65 / VDE 0860 / 8.86) Making current : minimum 20 A (16ms) Mechanical life span : 30 x 10 6 switching cycles Electrical life span : 2 x 10 5 switching cycles at 220 V AC / 6 A Contact material : silver-cadmium-oxide Ohmic L/R = 4 ms L/R = 7 ms 300 V DC 0.3 A / 90 W 0.2 A / 63 W 0.18 A / 54 W 250 V DC 0.4 A / 100 W 0.3 A / 70 W 0.15 A / 40 W 110 V DC 0.5 A / 55 W 0.4 A / 40 W 0.20 A / 22 W 60 V DC 0.7 A / 42 W 0.5 A / 30 W 0.30 A / 17 W 24 V DC 6.0 A / 144 W 4.2 A / 100 W 2.50 A / 60 W IRI1-ER- Stablized Earth Fault Current Relay 14 9.5 System data Design standard : VDE 0435, part 303, IEC 255.4, BS 142 Specified ambient service Temperature range: for storage : - 40C to + 85C for operating : - 20C to + 70C Environmental protection class F as per DIN 40040 and per DIN IEC 68 2-3 : relative humidity 95 % at 40C for 56 days Insulation test voltage, inputs and outputs between themselves and to the relay frame as per VDE 0435, part 303 IEC 255-5 : 5 kV; 1.2/50 Hz; 1 min. (except supply voltage inputs) Impulse test voltage, inputs and outputs between themselves and to the relay frame as per VDE 0435, part 303 IEC 255-5 : 5 kV; 1.2 / 50 s; 0.5 J High frequency interference test voltage, inputs and outputs between themselves and to the relay frame as per DIN IEC 255-6 : 2.5 kV / 1MHz Electrostatic discharge (ESD) test as per DIN VDE 0843, part 2 IEC 801-2 : 8 kV Electrostatic discharge (ESD) test as per DIN VDE 0843, part 4 IEC 801-4 : 4 kV / 2.5 kHz, 15 ms Radio interference suppression test as per EN 55011 : limit value class B Radio interference field test as per DIN DVE 0843, part 3 IEC 801-4 : electrical field strength 10 V/m Mechanical tests: Shock : class 1 acc. to DIN IEC 255-21-2 Vibration : class 1 acc. to DIN IEC 255-21-1 Degree of protection - front of relay : IP 54 by enclosure of the relay case and front panel (relay version D) Weight : approx. 1.5 kg Degree of pollution : 2 by using housing type A 3 by using housing type D Overvoltage class : III Influence variable values: Frequency influence : 40 Hz < f < 70 Hz: <3 % of set value Auxiliary voltage influence : no influence within the admissible range 9.6 Setting ranges and steps Relay type Parameter Setting range Steps Tolerances IRI1-ER I D 5 % ... 82.5 % x I N 2.5 % 3 % of set value IRI1-3ER I D 5 % ... 82.5 % x I N 2.5 % 3 % of set value IRI1-ER- Stablized Earth Fault Current Relay 15 9.7 Dimensional drawing Pl ease note: A distance of 50 mm is necessary when the units are mounted one below the other in order to allow easy opening of the front cover of the housing. The front cover opens downwards. 260 230 36 76 Cut Out Dimensions Installation Depth : 275mm All dimensions in : mm 68.7 1 3 6 . 5 1 4 2 1 4 2 16 7 6 10. Order form Stabilized earth-fault current relay IRI1- Measuring of earth current 1 phase measuring 1ER 3 phase measuring 3ER Rated current in the earth-fault phase 1 A 1 5A 5 Auxiliary voltage 24 V (16 to 60 V AC/16 to 80 V DC) L 110 V (50 to 270 V AC/70 to 360 V DC) H Housing (12TE) 19 rack A Flush mounting D Technical data subject to change without notice! H R / I R I 1 - E R / 1 2 . 1 2 . 2 0 0 8 BASIC RANGE Micro-controller based compact economical design DIN rail mounted Status indication via LED Step-less settings through front potentiometer FUNCTIONAL RANGE Genset Supervision & Control Auto Synchroniser Load Balancing & Control Related Protection HIGH-TECH RANGE Microprocessor based numerical protection Event & fault recording RS 485 communication Bright alpha-numeric display INTEGERATED RANGE Numeric protection, solution for sub-station in association with INGETEAM T&D, Spain Distance protection Comprehensive transformer protection a. Three winding transformer b. Two winding transformer Multi-functional relay: variety of protection combination Range of Protection Relays C&S Electric Limited (Protection & Control Division) 44, Okhla Industrial Estate, New Delhi -110 020 (INDIA) Phone : +91 11- 66602414, 30883745/54/64 Fax: +91 11- 66602413 E-mail: [email protected] Web : www.cselectric.co.in Marketing Offices : AHMEDABAD: +91 79 30074534/35/36 FAX : +91 79 30074519 BANGALORE: +91 80 25586147, 25594939 FAX : +91 25584839 BHUBANESWAR : +91 674 2507265 FAX : +91 674 2507265 CHANDIGARH : +91 172 272613, 3062624 FAX : +91 172 2726153 CHENNAI : +91 44 39180531/32/33/34 FAX :+91 44 39180514 DELHI : +91 11 30838822-25 Fax :+91 11 30838826 HYDERABAD : +91 40 27813003 FAX : +91 40 27812987 KOLKATA : +91 33 22275850/51 FAX : +91 33 22275849 MUMBAI : +91 22 24114727/28 FAX : +91 22 24126631 NAGPUR : +91 712 5616651 FAX : +91 712 5616651 PUNE : +91 20 30283244/45 FAX : +91 20 30283245 RAIPUR : +91 771 320852433/34