11.example Calculation - Transformer

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

High-Tech Range

IRI1-ER (Stablized Earth Fault Current Relay)


C&S Electric Limited
(Protection & Control Division)
IRI1-ER- Stablized Earth Fault Current Relay
2
Contents
1. Introduction
2. Applications
3. Characteristics and features
4. Design
4.1 Connections
4.1.1 Analog inputs
4.1.2 Output relays
4.2 Front plate
4.2.1 LEDs
4.2.2 DIP-switches
4.2.3 <RESET> push button
4.3 Code jumper
5. Working principle
6. Operations and settings
6.1 Layout of the operating elements
6.2 Setting of the pick-up value for the
differential current ID
6.2.1 Indication of fault
6.3 Reset
6.3.1 Reset by pressing the <RESET> push
button
6.3.2 Automatic reset
6.4 Calculation of the tripping current and
the stabilizing resistance
6.4.1 Sample calculation - alternator
6.4.2 Example calculation - transformer
6.5 Application of IRI1-3ER relay as High
Impedance Bus Differential Protection
7. Housing
7.1 Individual housing
7.2 Rack mounting
7.3 Terminal connections
8. Relay testing and commissioning
8.1 Power On
8.2 Checking the set values
8.3 Secondary injection test
8.3.1 Test equipment
8.3.2 Example of a test circuit for a IRI1-3ER-
relay
8.3.3 Checking the pick-up and tripping values
( I RI 1-ER)
8.3.4 Checking the operating and resetting
values (IRI1-3ER)
8.4 Primary injection test
8.5 Maintenance
9. Technical Data
9.1 Measuring input
9.2 Auxiliary voltage
9.3 General data
9.4 Output relay
9.5 System data
9.6 Setting ranges and steps
9.7 Dimensional drawing
10. Order form
IRI1-ER- Stablized Earth Fault Current Relay
3
1. Introduction
The application of powerful microprocessors with MR-
and IR-relays of the HIGH TECH RANGE provides a
large variety of advantages over power protection
systems of the traditional type.
The MR-protection relays are based exclusively on the
microprocessor technology. They represent our most
efficient generation of power protection systems.
Because of their capabilities to process measured
values digitally and to perform arithmetical and logical
operations, they are superior to the traditional analog
systems.
Besides, the digital protection relays offer important
additional advantages such as very low power
consumption, adaptability, flexible construction,
selection of relay characteristics etc.
The I R- pr ot ect i on r el ays ar e based on t he
mi croprocessor t echnol ogy or on t he anal og
technology. They represent a more cost saving
generation of relays of the HIGH TECH RANGE, used
for basic equipment protection.
The IR-protection relays are superior to conventional
prot ect i ve devi ces because of t hei r fol l owi ng
characteristics:
Integration of multiple protective functions into
one compact housing
User-friendly setting procedure by means of DIP-
switches
Compact construction type by SMD-technology
MR-protection relays are used for more complex
protective functions, such as earth fault directional
detection, and also in cases where easy operation,
quick fault-analysis and optimal communication
capabilities are required.
All relays of the HIGH TECH RANGE are available
for flush mounted installation, as well as for 19 rack
mounting. Plug-in technology is used. Of course, all
relays comply with the IEC/DIN regulations required
for the specific protection application.
2. Applications
The stabilized earth fault current relay IRI1-ER serves as
a suppl ement for t he t ransformer di fferent i al
protection. It allows for example implementation of a
zero-current differential protection by integrating the
star-point current (IRI1-ER). With the view to its higher
resistance to disturbances from outside the protection
area, it can be set much more sensitively than the
simple transformer differential protection, in order to
prevent false trippings.
The IRI1-ER can be used as:
Zero-current differential protection of the star
point winding (restricted earth fault) of a
transformer (IRI1-ER), see figure 2.1
Highly stabilized differential current relay for
alternator, transformers and motors (IRI-3ER),
see figure 2.2
Fig. 2.1: Zero-current differential protection of
a transformer in star-connection (IRI1-ER)
Fi g. 2. 2: Hi ghl y st abi l i zed di f f er ent i al
prot ect i on f or al t ernat ors, t ransf ormers and
motors (IRI-3ER)
l
l
l
l
l l
l
l
L1
Transformer
L2
L3
R
sr
IRI1-ER I>
L1
L2
L3
l
l
l
l
l
l
l
l
l
l
IRI1-3ER
R
sr
R
sr
R
sr
Motor
Transformer
Alternator
3. Characteristics and features
static protective device
single-phase current measuring (IRI1-ER) as
zero-current differential protection (restricted
earth fault 64 REF)
three-phase current measuring (IRI1-3ER) as
phase-current differential protection
high stability by serial stabilizing resistor Rsr per
phase
high sensitivity by low input burden of C.T.
extremely wide setting range with fine grading
wide range of operation of the supply voltage
(AC/DC)
coding for the self-holding function or automatic
reset of the LEDs and trip relays
frequency range 50/60 Hz
rated current 1A or 5A
output relay with 2 change-over contacts
IRI1-ER- Stablized Earth Fault Current Relay
4
Fig. 4.2: Connection diagram IRI1-3ER
4.1.1 Analog inputs
At three-phase measuring, the analog input signals of
the differential currents are fed to the protective device
via terminals B1 to B6 (IRI1-3ER), respectively at single
phase measuring via terminals B1/B2 (IRI1-1ER).
L1 L2 L3
P1
S2P2 S2P2
S1P1
P2
S1P1 S1
S2
P1
S2P2 S2P2
S1P1
P2
S1P1
S1
S2
l l l
l
l
l
l
l
l l
l
50/60Hz
50/60Hz
50/60Hz
l
~
D9 E9 C9
L-/N L+/L
D1
C1
E1
D2
C2
E2
R
sr
R
sr
R
sr
B2
B3
B4
B5
B6
B1
Reset
Trip
I
D
I
D
I
D
Power
Supply
~
4. Design
4.1 Connections
Fig. 4.1: Connection diagram IRI1-ER
l
l
l l
l l
l
P1
P2
S1
S2
P1
S2P2 S2P2 S2
S1 S1P1
P2
S1P1
L1 L2 L3
D9
D1
C1
E1
D2
C2
R
sr
50/60Hz B2
B1
E2
Reset
Trip
I
D
I
D
E9 C9
L-/N L+/L
Power
Supply
I
D
~
4.1.2 Output relays
Both relay types are equipped with a trip relay with two
change-over contacts.
Tripping I
D
: D1, C1, E1
D2, C2, E2
IRI1-ER- Stablized Earth Fault Current Relay
5
4.2 Front plate
Fig. 4.3: Front plate
The front plate of the IRI1-ER comprises the following
operation and indication elements:
1 set of DIP-switches for setting the tripping value
2 LEDs for indication of faults- and readyness for
operation
1 <RESET> push button
4.2.1 LEDs
On the front plate of the IRI1-ER 2 LEDs are installed,
signalizing the following 2 service conditions:
LED ON (green): readyness for service
LED I
D
(red): tripping
4.2.2 DIP-switches
The set of DIP switches on the front plate serves for
setting the tripping value for the differential current I
D
.
4.2.3 <RESET>-push button
The <RESET> push but t on i s used f or
acknowledgement and reset of the LED and the tripping
relay after tripping at the specifically preset value (see
4.3).
4.3 Code jumper
Behind the front plate, two coding jumpers are installed
at the bottom side for setting the LED-display, as well
as for the tripping function of the output relay.
Fig. 4.4: Code jumper
Code Function Position of Operating mode
jumper code jumper
3 Differential current OFF latching of the red LED I
D
indication ON automatic reset of the red LED I
D
4 Differential current OFF latching of the tripping relay
tripping ON automatic reset of the tripping relay
Table 4.1 Code jumper
I
D
I
D ON
Code jumper
Code jumper ON
Front plate
3 4
Code jumper OFF
RESET
7.5%
5
10
20
40
ON
I
D
5
0
0
0
0
I
D
IRI1-3ER
IRI1-ER- Stablized Earth Fault Current Relay
6
6. Operations and settings
6.1 Layout of the operating elements
The DIP-switch required for setting of parameters is
located on the front plate of the relay.
6.2. Setting of the pick-up value for the
differential current I
D
The pick-up value of the differential current tripping I
D
can be set by means of the DIP-switches set I
D
in the
range of 5% to 82.5% x I
N
with a grading of 2.5%.
The pick-up value is calculated by adding up the values
of all DIP-switches.
5. Working principle
The protection relay IRI1-ER is connected to the
differential circuit of the c.t.s as a current differential
protection relay. When used as zero-current differential
protection (restricted earth fault), the relay (IRI1-ER) is
to be connected acc. figure 2.1. When used as highly
stabilized differential current relay, the relay (IRI1-3ER)
is to be connected acc. figure 2.2.
The knee voltage U
Kn
is an important characteristic of
the transformer. The transformer does not work
linearly anymore above this voltage. Two transformers
of the same class still show the same behavior below
U
Kn
within the scope of their precision class. Above U
Kn
they can, however, show very different saturation
behavior.
Connected in a differential current circuit an apparent
fault current can thus be measured at large primary
current intensity which really results only from the
different saturation of both transformers.
An additional stabilizing resistor R
ST
counteracts this
effect. It attenuates the current flow through the
measuri ng devi ce. Thi s way t he unsat urat ed
transformer drives part of its current into the saturated
Fig. 5.1 Single line diagram IRI1-ER
transformer and minimizes the faulty differential
current effect on secondary side. By small currents the
stabilizing resistor effects however also the accuracy of
the real fault current measurement. Because this effect
lies in a linear range it can be taken into consideration
mathmatically by adjusting the protection device.
(see para. 6.4).
For demonstrating the working principle, figure 5.1
shows the single-line diagram of the IRI1-ER.
Protecting object
R
S
I
F
I
R
U
S
Z Z
Z = 0 R
At saturated C.T.
R
sr
R
L
R
L
I
F
R
S
The harmonics existing during a transformer saturation
and the DC-component are suppressed by a filter circuit
located in the input circuit of the relay; the filter circuit
is adjusted to the mains frequency (50/60Hz).
The IRI1-ER has a single-phase differential current
supervision with an adjustable pick-up value. The
current measured in the differential circuit is constantly
compared with the set reference value.
Measuring principle IRI1-ER
The analog current signals are galvanically decoupled
via the input transformer and are led over a low pass
with subsequent band-pass for suppression of the
harmonics, then rectified and compared with the set
reference value of a comparator. In case the current
measur ed exceeds t he r ef er ence val ue, an
instantaneous tripping takes place (figure 4.1).
The IRI1-3ER has a three-phase differential current
supervision with adjustable pick-up value. The currents
measured in the individual differential circuits are
constantly compared with the set reference value.
Measuring principle IRI1-3ER
The analog current signals are galvanically decoupled
via three input transformers and led over a low pass
with subsequent band-pass for suppressing the
harmonics. Then rectified and compared with the set
reference value of a comparator. In case one of the
three currents measured exceeds the reference value,
an instantaneous tripping takes place (figure 4.2).
IRI1-ER- Stablized Earth Fault Current Relay
7
Exampl e:
A pick-up value of 30% of the rated current is required.
6.2.1 Indication of fault
The fault alarm is shown by the LED I
D
on the front
plate of the relay, which lights up red at tripping.
Depending on the coding by means of the code jumper
(see chapter 6.3.2), the fault alarm extinguishes
automatically or after pressing the <RESET> push
button, after the fault is eliminated.
6.3 Reset
6.3.1 Reset by pressing the <RESET>-
push-button
By pressing the <RESET> push button, the tripping
relay is reset and the LED-signal extinguishes. All
coding switches must be plugged out for this (see
chapter 4.3).
6.3.2 Automatic reset
Code jumper 1
If no code jumper is plugged in at coding place 1, the
red fault alarm LED I
D
is coded latching.
The fault signal can only be reset manually by pressing
the <RESET> push button.
If the code jumper is plugged in at coding place 1, the
red fault signal LED I
D
is automatically reset, after the
fault is eliminated.
Code jumper 2
The tripping relay is coded latching, if no code jumper
is plugged in on coding place 2.
The tripping relay can only be reset manually by
pressing the <RESET> push button.
If the code jumper is plugged in on coding place 2, the
tripping relay is automatically reset after elimination of
the fault.
5
0
0
0
7.5%
5
10
20
40
I
D
I
D
= 5 + 5 + 20 = 30% x I
N
6.4 Calculation of the tripping current
and the stabilizing resistance
Prior to setting the relay, the stabilizing resistance R
sr
, as
well as the tripping current I
set
must be calculated. For
the correct setting, the knee-point voltage in the
magnetizing circuit of the c.t. is of special importance.
In order to obtain a sufficient differential current for
tripping on account of internal faults, the knee-point
voltage U
kn
of the transformer should be twice as high
as the maximum expected stabilizing voltage U
S
in case
of faults from outside the protection zone. From this
results the following calculation:
U
Kn
= 2 U
S
= 2 I
f,sek
(R
S
+ R
L
)
Expl anati on:
U
kn
knee-point voltage of the magnetizing circuit of
the transformer
U
s
maximum stabilizing voltage in case of external
faults
I
f,sek
maximum expected fault current (secondary-side)
in case of external faults
R
S
secondary resistance of the transformer
R
L
Resistance of the connection line between c.t. and
relay
The tripping current of the relay is then calculated, as
follows:
I
D
>
Expl anati on:
R
Sr
stabilizing resistance
The strength of the stabilizing resistance must be
selected in a way to ensure that the tripping current is
within the setting range (5% to 82.5% of I
N
).
When the pick-up value is exceeded, nearly an
immediate tripping is initiated. With 30 ms the tripping
time is approx. five times as high as the tripping value.
In case of lower currents, the tripping time is slightly
higher (about 100ms), in order to reach a stabilization
of the protective function against external faults (see
also chapter 5).
6.4.1 Sample calculation - alternator
An IRI1-ER protection relay is used for the earth-fault
protection of an alternator. In the starpoint, the
following c.t. is provided:
transformation ratio : 100/1A
class : 5 P 10
output : 2.5 VA
secondary resistance
of the transformer : <0.7
U
Kn
2 . R
Sr
IRI1-ER- Stablized Earth Fault Current Relay
8
The individual resistance values are:
2 x R
L
= 150 m, at 20 m, 2.5 mm Cu
2 R
L
+ R
r
+ R
S
= 0.87
Therefore, the following is valid:
R
kreis
= = 62.5
Calculation of the stabilizing resistance
The stabilizing resistance is calculated from above
ratios, as follows:
R
S
= S
r circuit
- (2 R
L
+ R
r
+ R
S
)
= R
circuit
- 0.87
= 61.6
In operational mode < I
D
, the output requirement P
N
is
as follows:
P
N
< I x R
sr
= 0.2 A x 61.6 < 2.47 W
In this case, P
N
represents the minimum output required
(pure current-heat losses). A considerably increased
output P
F
is required in the event of a fault.
Example: The fault current is: I
F,prim
= 13.1 kA
If one neglects the transformer saturation, the following
peak voltage U
P
occurs:
U
p
= (R
Sr
+ 2 R
L
+ R
r
+ R
S
)
U
p
= (62.5) = 8187.5 V
If one considers the transformer saturation, a short-
term peak voltage U
SS
occurs, as shown in the following
calculation:
U
SS
= 2(2U
Kn
(U
p
- U
Kn
))
+0.5
< 3 kV
U
SS
= 2(225 V (8187.5 V - 25 V))
+0.5
= 1.28 kV
Pr = = 26.6 kW
The calculation of P
N
and P
F
must be effected in any
case, in order to get the exact power range of the
stabilizing resistor.
Take over of power by the resistor in the event of a
fault P
F
creates a short-term peak value.
6.4.2 Example calculation -transformer
An IRI1-ER protection relay is used for the earth-fault
protection of a 1.6 MVA-transformer (11000/415 V,
6%), see figure 2.1. The following c.t.s are used in the
rigidly earthed starpoint:
transformation ratio: 2 500/1A
class: X
resistance Rs: 8
knee-point voltage: 250 V
The relay is situated about 20m away from the c.t.s
and is connected with a 2.5 mm
2
cable.
Calculation of the stabilizing voltage
The primary-side fault-current I
F,prim
is:
I
F,prim
= = 37.1 kA
Line resistance R
L
(2.5 mm ~ 7.46 /km)
RL = 20 m X = 0.15
Additional resistance R
r
(ca. 0.02 )
A primary-side fault current of 20% x I
N
shall be
recorded. The secondary current i s used for
calculation.
Calculation of the knee-point voltage
If the knee-point voltage is not indicated by the
manufacturer, as is the case in our example, the
approximate value can be calculated, as follows:
U
kn
= = 25V
Expl anati on:
S output of the c.t.
k
lu
overcurrent factor of the c.t.
I
N
secondary-side rated current of the transformer
Calculation of the active resistances
The relevant resistances in the differential circuit add
up to a total (circle-) resistance:
R
circuit
= = R
Sr
+ 2R
L
+R
S
+R
r
Expl anati on:
R
kreis
total resistance in the differential circuit
R
sr
stabilizing resistance
R
L
resistance of the connection line between c.t. and
relay
R
s
secondary resistance of the transformer (<0.7)
R
r
relay input resistance (B1 - B2 = 0.02 W)
I
D
tripping current
2.510
1
Sk
lu
I
N
U
Kn
2I
Set
25 V
20.2 A
I
F,prim
n
13100A 1
100
U
SS
2
R
Sr
1280
2
V
2
61.6
1600000 VA
3 X 415 V X 6%
7.46
1000 m
IRI1-ER- Stablized Earth Fault Current Relay
9
I
F,prim
n
37100 A 1
2500
From this results the stabilizing voltage for:
U
S
= X (2 X R
L
+ R
S
+ R
r
)
U
S
= X (2 X 0.15 + 8+ 0.01)
=123.5
U
p
= X (8 + 2 X 0.15
+ 0.02 + 308.75) = 4.7 kV
U
SS
= 2 X (2 X 250 V X (4700 V X 250 V))
+0.5
= 298
Since the requirement is met, the set values and the
resulting resistance values can be accepted.
The calculation of the output requirement for the
stabilizing resistance can be carried out similar to the
calculation of sample 6.4.1.
37.1 kA 1
2500
Since the knee-point voltage shall be U
kn
= 2x U
S
(2 x
123.5V = 247 V), the above transformer with U
kn
=
250 V can be used.
Calculation of the set current and the stabilizing
resistance (sample value)
The rating for the set current of 20% is calculated:
I
D
= 20 % x I
N
= 0.2 x 1 A = 0.2 A
From this results the stabilizing resistance for:
R
circuit
= ~ R
Sr
=> = 617.5
In the event of a fault, the stabilizing resistance must
withstand a secondary-side false current of:
I
F sek
= = 14.84 A
The calculation of the short-term peak voltages
provides the following result:
U
S
= X (8 + 2 X 0.15
+ 0.02 + 615) =9.25 kV
Thus, the ratio
U
SS
= 2 X (2 X U
Kn
X (U
p
- U
Kn
))
+0.5
< 3 kV
U
SS
= 2X(2X250 V X(9250 V - 250V))
+0.5
= 4.24 kV
is not reached and the calculation must be repeated
with a higher set current.
Calculation of the set current and the stabilizing
resistance (actual value)
The rating for the set current of 40% is calculated
again:
I
D
= 40 % x I
N
= 0.4 x 1 A = 0.4 A
From this results the stabilizing resistance for:
R
circuit
= ~ R
Sr
=>
= 308.75
Thus, the requirement of the short-term peak voltage
is met.
1600000 VA
3 X 415 V X 6% X 2500
37.1 kA 1
2500
123.5 V
0.2 A
U
S
I
D
U
S
I
D
123.5 V
0.4 A
6.5 Application of IRI1-3ER relay as
High Impedance Bus Differential
Protection:
IRI-1ER or IRI1-3ER (a 3-phase version of IRI1-1ER)
relays also offers reliable Bus protection based on High
Impedance Differential Principle.
The figure below indicates a typical Single Bus system
using IRI-ER relay for Bus Protection. This sample system
incorporates two incoming and two outgoing bays.
In case of normal operation, following Kirchoffs law, the
currents terminating on bus and going put adds up to Zero
with corresponding reproduction on CT secondary side of
respective bays. As the vector summation of the currents
balances each other out, the Relay does not operate.
In case of internal faults, as the fault currents will be fed
from all sources possible, the differential current will
operate the relay.
For External fault, though the amount of current flowing
into the fault will increase, the net summation of the
current again will zero and the relay will restrain.
Here, it is important to consider unequal saturation
characteristics of the Current transformers involved. It is
also important to ascertain that the relay remains stable
in presence of Harmonics and DC currents.
Fig. 6.1
IRI1-ER- Stablized Earth Fault Current Relay
10
Especially for a Bus Differential relay, following factors
are vital:
Because of higher concentration of fault MVA, the
Relay should operate very fast for heavy internal
faults.
The Relay should be reliably stable in presence of
Harmonics especially 2
nd
and 3
rd
harmonics and
presence of DC currents.
IRI1-ER relays ensure:
Operating time of less than 15 milliseconds at more
than 5 times of the setting.
2
nd
Harmonic rejection ratio of more than 4.
3
rd
Harmonic rejection ratio of more than 40.
Remains very stable against superimposed DC
currents.
Kpv
2.Rs
RL : = 0.5 Rct : = 6 Zr : = Zr = 0.125
Kpv : = Ifs . (Rct + 2.RL)
Kpv : = 186.667
Knee point required for the CT core should higher than,
KpvCT : = 2 . Kpv KpvCT = 373.333
Rs : = -Zr Rs = 466.542
Up : = Ifs . (Rs + 2.RL + Rct + Zr)
Up = 1.263 x 10
4
1.594 . 10000 = 1.594 x 10
4
Uss : = 2 . [2 . Kpv. (Up - Kpv]0.5
Uss = 4.311 x 103
=0.2
The use of Metrosil can be avoided as the relay can
reliably withstand Uss up to 5 kV. For fault currents
exceeding this level, the Metrosils should be used.
[( ) ]
Kpv
Id
0.02
Id
2
Rs : Stabilising Resistance in Ohms
Id : Differential Current Setting
Up : Peak Voltage neglecting Saturation
Uss : Short term peak Voltage considering Saturation
Ifs: Secondary value of Fault Current
Ifmax : 40000 kV : = 220 CTR : = 1500
MVAf : =3.kV.Ifmax MVAf = 1.524 x 10
7
Id : = 4
Ifs : = Ifs = 26.667
Ifmax
CTR
IRI1-ER- Stablized Earth Fault Current Relay
11
7. Housing
The IRI1-ER can be supplied in an individual housing
for flush-mounting or as a plug-in module for
installation in a 19" mounting rack according to DIN
41494.
Both versions have plug-in connections.
Relays of variant D are complete devices for flush
mounting, whereas relays of variant A are used for 19
rack mounting.
7.1 Individual housing
The individual housing of the IRI1-ER is constructed for
flush-mounting. The dimensions of the mounting frame
correspond to the requirements of DIN 43700 (76 x
142 mm). The cut-out for mounting is 68.7 x 136.5
mm.
The front of the IRI1-ER is covered with a transparent,
sealable flap (IP54).
7.2 Rack mounting
The IRI1-ER is in general suitable for installation in a
modular carrier according to DIN 41494. The
installation dimensions are: 12 TE; 3 HE.
According to requirements, the IRI1-ER-devices can be
delivered mounted in 19" racks.
If 19" racks are used the panel requires protection
class IP51.
7.3 Terminal connections
The plug-in module has very compact base with plug
connectors and screwed-type connectors.
max. 15 poles screw-type terminals for voltage
and current circuits (terminal connectors series A
and B with a short time current capability of 500
A / 1 s).
27 poles tab terminals for relay outputs, supply
voltage etc.(terminal connectors series C, D and
E, max. 6 A current carryi ng capaci t y) .
Connection with tabs 6.3 x 0.8 mm for cable up
to max. 1.5 mm
2
or with tabs 2.8 x 0.8 mm for
cable up to max. 1 mm
2
.
By using 2.8 x 0.8 mm tabs a bridge connection
between different poles is possible.
The current terminals are equipped with self-closing
short-circuit contacts. Thus, the IRI1-ER-module can
be unplugged even with current flowing, without
endangering the current transformers.
The following figure shows the terminal block of IRI1-
ER:
Fig. 7.1: Terminal block of IRI1-ER
8. Relay testing and commissioning
The following instructions should help to test the
protection relay performance before or during
commissioning of the protection system. To avoid a
relay damage and to ensure a correct relay operation,
be sure that:
the auxiliary power supply rating corresponds to
the auxiliary voltage on site
the rated current and rated voltage of the relay
correspond to the plant data on site
the current transformer circuits are connected to
the relay correctly
all signal circuits and output relay circuits are
connected correctly
8.1 Power On
NOTE!
Prior to switch on the auxiliary power supply, be sure
that the auxiliary supply voltage corresponds to the
rated data on the type plate.
Switch on the auxiliary power supply to the relay
(terminal C9/E9) and check that the LED ON on the
front plate lights up green.
8.2 Checking the set values
Check the DIP-switch positions, in order to verify the
parameterized set value. If necessary, the set value
can be corrected by means of the DIP-switch.
IRI1-ER- Stablized Earth Fault Current Relay
12
8.3.3 Checking the pick-up and tripping
values ( IRI1-ER )
With the IRI1-ER, the analog input signal of the
singlephase testing AC must be supplied to the relay via
the terminals B1/B2 for checking the pick-up value I
D
.
For testing the differential current pick-up value, first
the injected current must be set below the set pick-up
value I
d
. Then the injected current is increased
gradually, until the relay trips. This is indicated by the
LED I
D
lighting up red, with the relay tripping at the
same time. Check that the value shown at the ammeter
does not deviate by more than +/- 3% from the set
pick-up value I
D
.
The resetting value of the differential current pick-up
value is determined, by slowly decreasing the testing
AC, until the output relay I
D
trips. The LED I
D
extinguishes (supposed the respective coding was
effected).
Check that the resetting value is greater than 0.97
times the pick up value, i.e. the resetting ratio of the
differential current supervision is below 1.
8.3.4 Checking the operating and
resetting values (IRI1-3ER)
With the IRI1-3ER, all analog input signals of the
single-phase current must be supplied to the relay via
the terminals B1/B2; B3/B4; B5/B6 one after another
for checking the pick-up value I
D
in similar manner as
indicated above in para 8.3.3.
8.4 Primary injection test
Principally, a primary injection test (real-time test) of a
c.t. can be carried out in the same way as a secondary
injection test. Since the cost and potential hazards may
be very high for such tests, they should only be carried
out in exceptional cases, if absolutely necessary.
8.5 Maintenance
Maintenance testing is generally done on site at regular
intervals.These intervals may vary among users
depending on many factors: e.g. type of protective
relays employed; type of application; operating safety
of the equipment to be protected; the users past
experience with the relay etc.
For st at i c r el ays such as t he I RI 1- ER/- 3ER,
maintenance testing once per year is sufficient.
8.3 Secondary injection test
8.3.1 Test equipment
ammeter
auxi l i ar y power suppl y wi t h a vol t age
corresponding to the rated data on the type plate
single-phase AC-power supply (adjustable from 0
- 2.0 x I
N
)
test leads and tools
potentiometer
Fig. 8.3.1 Test circuit IRI1-3ER
L+/L L-/N
~
D9 E9 C9
Power
Supply
50/60Hz
50/60Hz
50/60Hz
l
D1
C1
E1
D2
C2
E2
Reset
I
D
Trip
I
D
+
I
D
2
A
3
1. Current source
2. Amperemeter
3. Relay under test
4. Potentiometer adjust resistor
5. Switching device
6. Timer
Stop
Timer
6
+
Start
4
5
Current source
1
B6
B5
B4
B3
B2
B1
-
switching device
timer
8.3.2 Example of a test circuit for a
IRI1-3ER -relay
For testing the IRI1-3ER-relay, only power signals are
required. Fig. 8.3.1 shows an example of a test circuit
with adjustable power supply. The phases are tested
individually one after the other.
IRI1-ER- Stablized Earth Fault Current Relay
13
9. Technical Data
9.1 Measuring input
Rated data:
Nominal current I
N
: 1A/5A
Nominal frequency f
N
: 50/60 Hz
Power consumption : <1 VA/at I
N
= 1A
in current circuit : <5 VA/at I
N
= 5 A
Thermal withstand : dynamic current withstand (half-wave) 250 x I
N
capability of current : for 1 s 100 x I
N
circuit : for 10 s 30 x I
N
continuously 4 x I
N
9.2 Auxiliary voltage
Rated auxiliary voltage U
H
:
24 V - working range : 16 - 60 V AC / 16 - 80 V DC
110 V - working range : 50 - 270 V AC / 70 - 360 V DC
Power consumption:
24 V - working range : standby approx. 3 W operating approx. 6 W
110 V - working range : standby approx. 3 W operating approx. 6 W
9.3 General data
Permissible interruption of
the supply voltage without
influence on the function : 50 ms
Dropout to pickup ratio : >97%
Returning time : 30 ms
Minimum operating time : 30 ms
9.4 Output relay
The output relay has the following characteristics:
Maximum breaking capacity : 250 V AC / 1500 VA / continuous current 6 A
Breaking capacity for DC:
Max. rated making current : 64 A (acc. VDE 0435/0972 and IEC 65 / VDE 0860 / 8.86)
Making current : minimum 20 A (16ms)
Mechanical life span : 30 x 10
6
switching cycles
Electrical life span : 2 x 10
5
switching cycles at 220 V AC / 6 A
Contact material : silver-cadmium-oxide
Ohmic L/R = 4 ms L/R = 7 ms
300 V DC 0.3 A / 90 W 0.2 A / 63 W 0.18 A / 54 W
250 V DC 0.4 A / 100 W 0.3 A / 70 W 0.15 A / 40 W
110 V DC 0.5 A / 55 W 0.4 A / 40 W 0.20 A / 22 W
60 V DC 0.7 A / 42 W 0.5 A / 30 W 0.30 A / 17 W
24 V DC 6.0 A / 144 W 4.2 A / 100 W 2.50 A / 60 W
IRI1-ER- Stablized Earth Fault Current Relay
14
9.5 System data
Design standard : VDE 0435, part 303, IEC 255.4, BS 142
Specified ambient service
Temperature range:
for storage : - 40C to + 85C
for operating : - 20C to + 70C
Environmental protection
class F as per DIN 40040
and per DIN IEC 68 2-3 : relative humidity 95 % at 40C for 56 days
Insulation test voltage, inputs
and outputs between themselves
and to the relay frame as per
VDE 0435, part 303 IEC 255-5 : 5 kV; 1.2/50 Hz; 1 min.
(except supply voltage inputs)
Impulse test voltage, inputs
and outputs between themselves
and to the relay frame as per
VDE 0435, part 303 IEC 255-5 : 5 kV; 1.2 / 50 s; 0.5 J
High frequency interference
test voltage, inputs and outputs
between themselves and to the
relay frame as per DIN IEC 255-6 : 2.5 kV / 1MHz
Electrostatic discharge (ESD)
test as per DIN VDE 0843, part 2
IEC 801-2 : 8 kV
Electrostatic discharge (ESD)
test as per DIN VDE 0843, part 4
IEC 801-4 : 4 kV / 2.5 kHz, 15 ms
Radio interference suppression
test as per EN 55011 : limit value class B
Radio interference field
test as per DIN DVE 0843, part 3
IEC 801-4 : electrical field strength 10 V/m
Mechanical tests:
Shock : class 1 acc. to DIN IEC 255-21-2
Vibration : class 1 acc. to DIN IEC 255-21-1
Degree of protection - front of relay : IP 54 by enclosure of the relay case and front panel
(relay version D)
Weight : approx. 1.5 kg
Degree of pollution : 2 by using housing type A
3 by using housing type D
Overvoltage class : III
Influence variable values:
Frequency influence : 40 Hz < f < 70 Hz: <3 % of set value
Auxiliary voltage influence : no influence within the admissible range
9.6 Setting ranges and steps
Relay type Parameter Setting range Steps Tolerances
IRI1-ER I
D
5 % ... 82.5 % x I
N
2.5 % 3 % of set value
IRI1-3ER I
D
5 % ... 82.5 % x I
N
2.5 % 3 % of set value
IRI1-ER- Stablized Earth Fault Current Relay
15
9.7 Dimensional drawing
Pl ease note:
A distance of 50 mm is necessary when the units are mounted one below the other in order to allow easy opening
of the front cover of the housing. The front cover opens downwards.
260
230
36
76
Cut Out Dimensions
Installation Depth : 275mm
All dimensions in : mm
68.7
1
3
6
.
5
1
4
2
1
4
2
16
7
6
10. Order form
Stabilized earth-fault current relay IRI1-
Measuring of earth current 1 phase measuring 1ER
3 phase measuring 3ER
Rated current in the earth-fault phase 1 A 1
5A 5
Auxiliary voltage 24 V (16 to 60 V AC/16 to 80 V DC) L
110 V (50 to 270 V AC/70 to 360 V DC) H
Housing (12TE) 19 rack A
Flush mounting D
Technical data subject to change without notice!
H
R
/
I
R
I
1
-
E
R
/
1
2
.
1
2
.
2
0
0
8
BASIC RANGE
Micro-controller based compact economical design
DIN rail mounted
Status indication via LED
Step-less settings through front potentiometer
FUNCTIONAL RANGE
Genset Supervision & Control
Auto Synchroniser
Load Balancing & Control
Related Protection
HIGH-TECH RANGE
Microprocessor based numerical protection
Event & fault recording
RS 485 communication
Bright alpha-numeric display
INTEGERATED RANGE
Numeric protection, solution for sub-station in association
with INGETEAM T&D, Spain
Distance protection
Comprehensive transformer protection
a. Three winding transformer
b. Two winding transformer
Multi-functional relay: variety of protection combination
Range of Protection Relays
C&S Electric Limited
(Protection & Control Division)
44, Okhla Industrial Estate, New Delhi -110 020 (INDIA)
Phone : +91 11- 66602414, 30883745/54/64 Fax: +91 11- 66602413
E-mail: [email protected] Web : www.cselectric.co.in
Marketing Offices :
AHMEDABAD: +91 79 30074534/35/36 FAX : +91 79 30074519 BANGALORE: +91 80 25586147, 25594939 FAX : +91 25584839
BHUBANESWAR : +91 674 2507265 FAX : +91 674 2507265 CHANDIGARH : +91 172 272613, 3062624 FAX : +91 172 2726153
CHENNAI : +91 44 39180531/32/33/34 FAX :+91 44 39180514 DELHI : +91 11 30838822-25 Fax :+91 11 30838826 HYDERABAD : +91 40 27813003
FAX : +91 40 27812987 KOLKATA : +91 33 22275850/51 FAX : +91 33 22275849 MUMBAI : +91 22 24114727/28 FAX : +91 22 24126631
NAGPUR : +91 712 5616651 FAX : +91 712 5616651 PUNE : +91 20 30283244/45 FAX : +91 20 30283245 RAIPUR : +91 771 320852433/34

You might also like