Abb Cptik 10 & 15 Kva Rev C

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

CPT-IK-15 Control Power Transformer

10 & 15 kVA, 5 kV and 15 kV Class, 60 Hertz


Indoor Control Power Transformers
Product Bulletin #1VAP600002-DB

ABB

Product Features

Application

Completely dry-type transformer cast


in epoxy, eliminating oil

The CPT-IK is an indoor, self-cooled, single-phase, dry-type


control power transformer designed to provide control power
in medium voltage switchgear. Nominal primary voltages range
from 2.4 kV to 14.4 kV, 60 hertz. Secondary voltages are configured for series/parallel operation at 120 V or 240 V. Standard
BIL ratings of 60 kV are available for 5 kV applications, and 95
kV BIL for 15 kV applications.

5 kV and 15 kV class
10 kVA units, 55C Rise @ 30C
average daily ambient
15 kVA units, 75C rise @ 30C
average daily ambient

The CPT-IK is used in an ambient temperature of 30C for full


kVA rating or 55C for 86% of full kVA rating. The winding
temperature rise is 55C for 10 kVA units and 75C for 15 kVA
units. Styles in addition to those listed in this bulletin are available upon request.

All secondary outputs 120/240 V


Primary inputs 2400 V to 14400 V
with multiple taps

Construction Features

Meets all requirements of IEEE


57.13 - 1993, including full-wave and
chopped-wave impulse tests

The core is wound with grain-oriented electrical steel for low


losses. The high-voltage coil is vacuum encapsulated in epoxy
to seal out moisture and contaminates, and to provide a higher
ability to withstand short-circuit forces than conventional drytype transformers.

UL Recognized Component; File


No. E244068

The secondary terminals are 1/2" 13 brass bolts supplied with


series/parallel copper links. The primary terminals are 1/4" 20
brass screws. The primary tap terminals are either 1/4" 20 brass
screws or #10 brass screws, depending on the design selected,
and are supplied with a copper link. The frame is made of zincplated steel. Approximate weight is 230 pounds.

UL Recognized Component

Connection Diagrams

7 1/2% Primary Taps

2 2 1/2% Primary Taps

HI

120

X4

H2

HI

6 4 2

X2

X3

120

120

120

X4

X1

H2

1 3 5

X2

X3

X1

% Rated Voltage

Connect HV Link

% Rated Voltage

Connect HV Link

107.5
100
92.5

12
23
34

105
102.5
100
97.5
95

12
23
34
45
56

-2-

4 In-Line Tap Configuration


Dimensions

Connections

A
7 1/2% Primary Taps
HI

120

X4

H2

120

X2

X3

X1

% Rated Voltage

Connect HV Link

107.5
100
92.5

12
23
34

Outline Drawing D147

Note: Metric dimensions are


displayed in [mm].

Style

kVA

Voltage
Class

Primary
Rating

Secondary
Voltage

Taps

CPTA-60-10-2400-D147
CPTA-60-10-4160-D147
CPTA-60-10-4800-D147
CPTA-95-10-7200-D147
CPTA-95-10-8400-D147
CPTA-95-10-12000-D147
CPTA-95-10-12470-D147
CPTA-95-10-13200-D147
CPTA-95-10-13800-D147
CPTA-95-10-14400-D147
CPTA-60-15-2400-D147
CPTA-60-15-4160-D147
CPTA-60-15-4800-D147
CPTA-95-15-7200-D147
CPTA-95-15-8400-D147
CPTA-95-15-12000-D147
CPTA-95-15-12470-D147
CPTA-95-15-13200-D147
CPTA-95-15-13800-D147
CPTA-95-15-14400-D147

10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
15
15
15

5 kV
5 kV
5 kV
15 kV
15 kV
15 kV
15 kV
15 kV
15 kV
15 kV
5 kV
5 kV
5 kV
15 kV
15 kV
15 kV
15 kV
15 kV
15 kV
15 kV

2400
4160
4800
7200
8400
12000
12470
13200
13800
14400
2400
4160
4800
7200
8400
12000
12470
13200
13800
14400

120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A

Additional primary and secondary voltages available upon request. Call +1-252-827-3212 for more information.
-3-

4 Multi-Tap Configuration
Connections

Dimensions

A
7 1/2% Primary Taps
HI

120

X4

CPTA-60-10-2400-D149
CPTA-60-10-4160-D149
CPTA-60-10-4800-D149
CPTA-95-10-7200-D149
CPTA-95-10-8400-D149
CPTA-95-10-12000-D149
CPTA-95-10-12470-D149
CPTA-95-10-13200-D149
CPTA-95-10-13800-D149
CPTA-95-10-14400-D149
CPTA-60-15-2400-D149
CPTA-60-15-4160-D149
CPTA-60-15-4800-D149
CPTA-95-15-7200-D149
CPTA-95-15-8400-D149
CPTA-95-15-12000-D149
CPTA-95-15-12470-D149
CPTA-95-15-13200-D149
CPTA-95-15-13800-D149
CPTA-95-15-14400-D149

120

X2

X3

X1

% Rated Voltage

Connect HV Link

107.5
100
92.5

12
23
34

Outline Drawing D149

Style

H2

Note: Metric dimensions are


displayed in [mm].

kVA

Voltage
Class

Primary
Rating

Secondary
Voltage

Taps

10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
15
15
15

5 kV
5 kV
5 kV
15 kV
15 kV
15 kV
15 kV
15 kV
15 kV
15 kV
5 kV
5 kV
5 kV
15 kV
15 kV
15 kV
15 kV
15 kV
15 kV
15 kV

2400
4160
4800
7200
8400
12000
12470
13200
13800
14400
2400
4160
4800
7200
8400
12000
12470
13200
13800
14400

120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A

Additional primary and secondary voltages available upon request. Call +1-252-827-3212 for more information.
-4-

6 Multi-Tap Configuration
Connections

Dimensions

B
2 2 1/2% Primary Taps
HI

6 4 2

120

120

X4

CPTB-60-10-2400-D151
CPTB-60-10-4160-D151
CPTB-60-10-4800-D151
CPTB-95-10-7200-D151
CPTB-95-10-8400-D151
CPTB-95-10-12000-D151
CPTB-95-10-12470-D151
CPTB-95-10-13200-D151
CPTB-95-10-13800-D151
CPTB-95-10-14400-D151
CPTB-60-15-2400-D151
CPTB-60-15-4160-D151
CPTB-60-15-4800-D151
CPTB-95-15-7200-D151
CPTB-95-15-8400-D151
CPTB-95-15-12000-D151
CPTB-95-15-12470-D151
CPTB-95-15-13200-D151
CPTB-95-15-13800-D151
CPTB-95-15-14400-D151

X2

X3

X1

% Rated Voltage

Connect HV Link

105
102.5
100
97.5
95

12
23
34
45
56

Outline Drawing D151

Style

H2

1 3 5

Note: Metric dimensions are


displayed in [mm].

kVA

Voltage
Class

Primary
Rating

Secondary
Voltage

Taps

10
10
10
10
10
10
10
10
10
10
15
15
15
15
15
15
15
15
15
15

5 kV
5 kV
5 kV
15 kV
15 kV
15 kV
15 kV
15 kV
15 kV
15 kV
5 kV
5 kV
5 kV
15 kV
15 kV
15 kV
15 kV
15 kV
15 kV
15 kV

2400
4160
4800
7200
8400
12000
12470
13200
13800
14400
2400
4160
4800
7200
8400
12000
12470
13200
13800
14400

120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240
120/240

B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B
B

Additional primary and secondary voltages available upon request. Call +1-252-827-3212 for more information.
-5-

ABB
ABB Inc.
Highway 43 North
Pinetops, NC 27864
Tel: +1-252-827-3212
www.abb.com/mediumvoltage

1VAP600002-DB June 2004 Rev. C


Copyright 2004 ABB. All rights reserved.

For additional information, please contact your ABB Sales


Representative or visit our website at www.abb.com/mediumvoltage.

You might also like