A trip circuit receives signals from protection systems like relays or PLCs and initiates opening a circuit breaker through mechanical or electrical systems like springs or motors. If the trip circuit is damaged or open, the circuit breaker will not open during a fault, leaving the network unprotected. A trip circuit supervision relay uses low-level current injection to monitor the health of the trip circuit. It has three states - normal, fault detected, and auxiliary power fault detected - indicated by a green or red light and energized or de-energized output relays.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
210 views2 pages
TCS Function
A trip circuit receives signals from protection systems like relays or PLCs and initiates opening a circuit breaker through mechanical or electrical systems like springs or motors. If the trip circuit is damaged or open, the circuit breaker will not open during a fault, leaving the network unprotected. A trip circuit supervision relay uses low-level current injection to monitor the health of the trip circuit. It has three states - normal, fault detected, and auxiliary power fault detected - indicated by a green or red light and energized or de-energized output relays.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 2
Trip circuit what its functions
A trip circuit should be always ready to trip or disconnect an electrical system or
mechanical system. Trip circuit receives signal from the protection system watch dog like relays, PLC etc. After receiving a signal trip circuit initiates the opening or disconnecting means of a circuit by opening or disconnecting a circuit breaker by means of actuating some mechanical or electrical systems. This electrical or mechanical systems might be spring, motor. As to open a circuit breaker it will require some strength. o a relay as a watch dog is always activated also the trip circuit but on the other hand the circuit breaker is always inactive. Why the trip circuit is required to be live always: As the trip circuit has some important purpose the functionality or health of it must be ensured. !hat happens if a trip circuit is open or damaged" #n this case the circuit will be totally unprotected. The relay$ PLC will send out signal after happening a fault but as trip circuit is dead , the breaker will not open or disconnect. In a protection system the tripping of a circuit breaker is crucial. If an interruption occurs in the trip circuit, the possible network fault will not be disconnected and the fault would have to be cleared by another protection upstream in the power system. The supervision function is particularly important when there is only one tripping coil and CB tripping is vital. (For instance, in the case of generator circuit breakers or any other important circuit breaker in distribution networks. Functions of a typical trip circuit supervision relay %alvaa&Below is trip circuit supervision relay function described based on a specific model! the settings and data might varied to models but the core principle is same. The supervision function is based on a low'level () * mA+ current in,ection principle. The in,ected current is sensed by two opto'couplers. The supervision function in three steady states of circuit breaker'trip circuit is below image.#n normal condition the indicator L-. glows green and output relays are in /picked'up0 condition. #n the event of a fault, the measuring current goes below the operating value of the relay (1.* 2 1.3 mA+ or completely stops flowing. The supervision relay operates (drops'off+ after a delay of 1.4 sec and the indicator L-. turns red. The supervision relay, for its functioning requires an au5iliary voltage (AC or .C+ of a rated value . This voltage can be the same as that of the supervised circuit or it could be a separate source with same magnitude (AC or .C+. hould a fault occur in the au5iliary voltage supply, the L-. does not glow and the output relay drops off. 6elays with differing rated voltage for supervision circuit and au5iliary supply can be supplied as a special e5ecution. Tri p circuit supervision relay function