0% found this document useful (0 votes)
90 views9 pages

Data Sheet Service

Product data sheet 3RT2016-1BB42 CONTACTOR, AC-3, 4KW / 400V, 1NC, DC 24V, 3-POLE, SZ S00 SCREW TERMINAL. Product brand name SIRIUS Size of the contactor S00 Product extension auxiliary switch Yes function module for communication No Protection class IP / on the front IP20 Protection against electrical shock finger-safe Degree of pollution 3 Installation altitude / at a height over sea level / maximum m 2,000

Uploaded by

Pablo Guzman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
90 views9 pages

Data Sheet Service

Product data sheet 3RT2016-1BB42 CONTACTOR, AC-3, 4KW / 400V, 1NC, DC 24V, 3-POLE, SZ S00 SCREW TERMINAL. Product brand name SIRIUS Size of the contactor S00 Product extension auxiliary switch Yes function module for communication No Protection class IP / on the front IP20 Protection against electrical shock finger-safe Degree of pollution 3 Installation altitude / at a height over sea level / maximum m 2,000

Uploaded by

Pablo Guzman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

Product data sheet 3RT2016-1BB42

CONTACTOR, AC-3, 4KW/400V, 1NC, DC 24V,


3-POLE, SZ S00 SCREW TERMINAL
General technical data:
product brand name SIRIUS
Size of the contactor S00
Product extension
auxiliary switch Yes
function module for communication No
Protection class IP / on the front IP20
Protection against electrical shock finger-safe
Degree of pollution 3
Installation altitude / at a height over sea level / maximum m 2,000
Ambient temperature
during storage C -55 +80
during operating C -25 +60
Shock resistance
at rectangular impulse
at DC 6,7g / 5 ms, 4,2g / 10 ms
at sine pulse
at DC 10,5g / 5 ms, 6,6g / 10 ms
Impulse voltage resistance / rated value kV 6
Insulation voltage / rated value V 690
3RT2016-1BB42
Page 1/ 09/10/2014
subject to modifications
Copyright Siemens AG 2014 9
Maximum permissible voltage for protective separation / between coil
and main contacts / in accordance with EN 60947-1
V 400
Mechanical operating cycles as operating time
of the contactor / typical 30,000,000
of the contactor with added auxiliary switch block / typical 10,000,000
of the contactor with added electronics-compatible auxiliary
switch block / typical
5,000,000
Main circuit:
Number of NC contacts / for main contacts 0
Number of NO contacts / for main contacts 3
Connectable conductor cross-section / in main circuit
at AC-1
at 40 C / minimum permissible mm 4
at 60 C / minimum permissible mm 2.5
Operating current
at AC-1 / up to 690 V
at 40 C ambient temperature / rated value A 22
at 60 C ambient temperature / rated value A 20
at AC-2 / at 400 V / rated value A 9
at AC-3
at 400 V / rated value A 9
at 500 V / rated value A 7.7
at 690 V / rated value A 6.7
at AC-4 / at 400 V / rated value A 8.5
Operational current / for 200000 operating cycles / at AC-4
at 400 V / rated value A 4.1
at 690 V / rated value A 3.3
Operating current
with 1 current path / at DC-1
at 24 V / rated value A 20
at 110 V / rated value A 2.1
at 220 V / rated value A 0.8
at 440 V / rated value A 0.6
at 600 V / rated value A 0.6
with 2 current paths in series / at DC-1
at 24 V / rated value A 20
at 110 V / rated value A 12
at 220 V / rated value A 1.6
at 440 V / rated value A 0.8
at 600 V / rated value A 0.7
3RT2016-1BB42
Page 2/ 09/10/2014
subject to modifications
Copyright Siemens AG 2014 9
with 3 current paths in series / at DC-1
at 24 V / rated value A 20
at 110 V / rated value A 20
at 220 V / rated value A 20
at 440 V / rated value A 1.3
at 600 V / rated value A 1
Operating current
with 1 current path / at DC-3 / at DC-5
at 24 V / rated value A 20
at 110 V / rated value A 0.1
with 2 current paths in series / at DC-3 / at DC-5
at 24 V / rated value A 20
at 110 V / rated value A 0.35
with 3 current paths in series / at DC-3 / at DC-5
at 24 V / rated value A 20
at 110 V / rated value A 20
at 220 V / rated value A 1.5
at 440 V / rated value A 0.2
at 600 V / rated value A 0.2
Operating performance
at AC-1 / at 230 V / rated value kW 7.5
at AC-1 / at 400 V / rated value kW 13
at AC-1 / at 690 V / rated value kW 22
at AC-2
at 400 V / rated value kW 4
at AC-3
at 230 V / rated value kW 2.2
at 400 V / rated value kW 4
at 690 V / rated value kW 5.5
at AC-4
at 400 V / rated value kW 4
Operating performance / for 200000 operating cycles / at AC-4
at 400 V / rated value kW 2
at 690 V / rated value kW 2.5
Thermal short-time current / restricted to 10 s A 72
Active power loss / at AC-3 / at 400 V / with rated Operating current
value / per conductor
W 0.7
Off-load operating frequency
at DC 1/h 10,000
Frequency of operation
3RT2016-1BB42
Page 3/ 09/10/2014
subject to modifications
Copyright Siemens AG 2014 9
with AC-1 / maximum 1/h 1,000
with AC-2 / maximum 1/h 750
with AC-3 / maximum 1/h 750
with AC-4 / maximum 1/h 250
Control circuit/ Control:
Voltage type / of control feed voltage DC
Control supply voltage
for DC / rated value V 24
Operating range factor control supply voltage rated value / of the
magnet coil
for DC 0.8 1.1
Pull-in power / of the solenoid / for DC W 4
Holding power / of the solenoid / for DC W 4
Closing delay
at DC ms 30 100
Opening delay
at DC ms 7 13
Arcing time ms 10 15
Residual current / of electronics / for control with signal <0>
at 230 V / with AC / maximum permissible mA 3
at 24 V / with DC / maximum permissible mA 10
Auxiliary circuit:
Contact reliability / of the auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
Number of NC contacts / for auxiliary contacts / instantaneous
switching
1
Number of NO contacts / for auxiliary contacts / instantaneous
switching
0
Operating current
at AC-12 / maximum A 10
at AC-15
at 230 V / rated value A 10
at 400 V / rated value A 3
at 500 V / rated value A 2
at 690 V / rated value A 1
Operating current / at DC-12
at 24 V / rated value A 10
at 48 V / rated value A 6
at 60 V / rated value A 6
at 110 V / rated value A 3
3RT2016-1BB42
Page 4/ 09/10/2014
subject to modifications
Copyright Siemens AG 2014 9
at 125 V / rated value A 2
at 220 V / rated value A 1
at 440 V / rated value A 0.3
at 600 V / rated value A 0.15
Operating current / at DC-13
at 24 V / rated value A 10
at 48 V / rated value A 2
at 60 V / rated value A 2
at 110 V / rated value A 1
at 125 V / rated value A 0.9
at 220 V / rated value A 0.3
at 440 V / rated value A 0.14
at 600 V / rated value A 0.1
UL/CSA ratings:
yielded mechanical performance [hp]
for single-phase squirrel cage motors
at 110/120 V / rated value hp 0.33
at 230 V / rated value hp 1
for three-phase squirrel cage motors
at 200/208 V / rated value hp 2
at 220/230 V / rated value hp 3
at 460/480 V / rated value hp 5
at 575/600 V / rated value hp 7.5
Full-load current (FLA) / for 3-phase motor
at 480 V / rated value A 7.6
at 600 V / rated value A 9
Contact rating designation / for auxiliary contacts / according to UL A600 / Q600
Short-circuit:
Design of the fuse link
for short-circuit protection of the auxiliary switch / required fuse gL/gG: 10 A
for short-circuit protection of the main circuit
with type of assignment 1 / required gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE: 35
A
at type of coordination 2 / required gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED 5SE:
20A
Installation/ mounting/ dimensions:
mounting position +/-180 rotation possible on vertical mounting surface;
can be tilted forward and backward by +/- 22.5 on
vertical mounting surface
3RT2016-1BB42
Page 5/ 09/10/2014
subject to modifications
Copyright Siemens AG 2014 9
Mounting type screw and snap-on mounting onto 35 mm standard
mounting rail according to DIN EN 50022
Mounting type / series installation Yes
Width mm 45
Height mm 57.5
Depth mm 73
Distance, to be maintained, to the ranks assembly / sidewards mm 0
Connections/ terminals:
Design of the electrical connection
for main current circuit screw-type terminals
for auxiliary and control current circuit screw-type terminals
Type of the connectable conductor cross-section
for main contacts
solid or multi-stranded 2x (0,5 ... 1,5 mm), 2x (0,75 ... 2,5 mm), 2x 4 mm
finely stranded / with conductor end processing 2x (0.5 ... 1.5 mm), 2x (0.75 ... 2.5 mm)
for AWG conductors / for main contacts 2x (20 ... 16), 2x (18 ... 14), 2x 12
Type of the connectable conductor cross-section
for auxiliary contacts
solid or multi-stranded 2x (0,5 ... 1,5 mm), 2x (0,75 ... 2,5 mm), 2x 4 mm
finely stranded / with conductor end processing 2x (0.5 ... 1.5 mm), 2x (0.75 ... 2.5 mm)
for AWG conductors / for auxiliary contacts 2x (20 ... 16), 2x (18 ... 14), 2x 12
Safety related data:
B10 value / with high demand rate
according to SN 31920 1,000,000
T1 value / for proof test interval or service life
according to IEC 61508 a 20
Proportion of dangerous failures
with low demand rate / according to SN 31920 % 40
with high demand rate / according to SN 31920 % 73
Failure rate [FIT] / with low demand rate
according to SN 31920 FIT 100
Product function
mirror contact to IEC 60947-4-1 Yes
positively driven operation to IEC 60947-5-1 No
Certificates/ approvals:
3RT2016-1BB42
Page 6/ 09/10/2014
subject to modifications
Copyright Siemens AG 2014 9
General Product Approval Functional Safety /
Safety of Machinery
Declaration of
Conformity
Type Examination
Test Certificates
Special Test
Certificate
Type Test
Certificates/Test
Report
Shipping Approval
Shipping Approval other
Confirmation Environmental
Confirmations
Further information:
Information- and Downloadcenter (Catalogs, Brochures,)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
http://www.siemens.com/industrymall
Cax online generator
http://www.siemens.com/cax
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
http://support.automation.siemens.com/WW/view/en/3RT2016-1BB42/all
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, ...)
http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3RT2016-1BB42
3RT2016-1BB42
Page 7/ 09/10/2014
subject to modifications
Copyright Siemens AG 2014 9
3RT2016-1BB42
Page 8/ 09/10/2014
subject to modifications
Copyright Siemens AG 2014 9
last change: Sep 2, 2014
3RT2016-1BB42
Page 9/ 09/10/2014
subject to modifications
Copyright Siemens AG 2014 9

You might also like