Installation Techniques - Link-Seal Modular Seals: Connect

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Installation Techniques - Link-Seal Modular Seals

Online Installation Video


Visit www.linkseal.com

Connect
1. Center the pipe, cable or
conduit in wall opening or
casing. Make sure the pipe
will be adequately supported on both ends. LinkSeal modular seals are
not intended to support the
weight of the pipe.

2. Loosen rear pressure


plate with nut just enough
so links move freely. Connect both ends of belt
around the pipe.

3. Check to be sure all bolt


heads are facing the installer. Extra slack or sag is
normal. Do not remove
links if extra slack exists.
Note: On smaller diameter
pipe, links may need to be
stretched.

Bulge

Installation Complete
5a. LS-325 thru. LS-650
Using a hand socket or offset wrench ONLY, start at
12 O Clock. Do not tighten
any bolt more than 4 turns
at a time. Continue in a
clockwise manner until
links have been uniformly
compressed. (Approx. 2 or
3 rotations)

6. Make 2 or 3 more
passes at 4 turns per bolt
MAXIMUM, tightening all
bolts clockwise until all
sealing elements bulge
around all pressure plates.
On type 316 stainless steel
bolts, hand tighten ONLY
without power tool.

7. If the seal doesnt appear to be correct using


the instructions provided,
Call PSI at 800-423-2410.

4. Slide belt assembly into


annular space. For larger
size belts, start inserting
Link-Seal modular seal assembly at the 6 OClock
position and work both
sides up toward the 12 OClock position in the annular space.

5. LS-200 thru. LS-315


Using a hand socket allen
head or off-set wrench
ONLY, start at 12 O Clock.
Do not tighten any bolt
more than 4 turns at a
time. Continue in a clockwise manner until links
have been uniformly compressed. (Approx. 2 or 3
rotations)

Link-Seal Model

Tool Size/
Type Req.

LS-200, LS-275

4mm, Allen

LS-300, LS-315

6mm, Allen

LS-325, LS-340, LS-360

13mm, Hex

LS-400, LS-410, LS-425, LS-475

17mm, Hex

LS-500, LS-525, LS-575

19mm, Hex

LS-600

30mm, Hex

LS-650

19mm, Hex

Installation Notes: The Link-Seal modular seal bolt heads are usually recessed below
the wall opening or the edge of casing pipe and therefore a socket or offset wrench must
be used. Hand Tools: Review provided chart above. (Tools not provided.) Tools can be
purchased from hardware store, auto parts store, or home improvement store.

Always Wear Safety Equipment When Using Link-Seal Modular Seals!


Link-Seal Modular Seal - Dos

1. Make sure pipe is centered.


2. Install the belt with the
pressure plates evenly
spaced.
3. Install the exact number

of links indicated in sizing


charts.
4. Check to make sure pipe
is supported properly during backfill operations.
Note: Link-Seal modular
seals are not intended to
support the weight of the
pipe.
5. Make sure seal assembly and pipe surfaces are
free from dirt.
6. For tight fits, use nonpolluting liquid detergent to
assist
installation.

If the seal doesnt appear to be correct using the


techniques provided, Call PSI at 713-747-6948
or 800-423-2410.

Link-Seal Modular Seal - Donts

Dont
1. Dont Install the belt with
the pressure plates aimed
in irregular directions.
(Staggered)

2. Dont Install Link-Seal


modular seals where weldbeads or other irregular
surfaces exist without consideration of the sealing requirements.
3. Dont torque each bolt
completely before moving
on to the next.
4. Dont use high speed
power tools (450 rpm or
more)
5. Do not use power tools
on Link-Seal modular seal
316 stainless steel bolts.
6. Dont use grease installing Link-Seal modular
seals.

You might also like