Process Control Fundamentals
Process Control Fundamentals
protocol.
(See Module 8: Communication Technologies for more information
on digital communication protocols.)
INDICATORS
While most instruments are connected to a control system, operators
sometimes need to check a measurement on the factory floor at the
measurement point. An indictor makes this reading possible. An
indicator is a human-readable device that displays information about
the process. Indicators may be as simple as a pressure or temperature
gauge or more complex, such as a digital read-out device. Some
indicators simply display the measured variable, while others have
control buttons that enable operators to change settings in the field.
6. The ___________ is a
human-readable device that
displays information about the
process or the instrument it is
connected to.
7. Which of the following are examples
of a digital signal?
Select all options that apply.
Profibus
4 - 20 mA
1 - 5 v
Fieldbus
3 - 15 psig
1
2
3
4
5
1. indicator
2. recorder
3. sensor
Activities
16 Fundamentals of Control
2006 PAControl.com
Components of Control Loops and ISA Symbology
Control Loop Equipment and Technology
RECORDERS
A recorder is a device that records the output of a measurement
devices. Many process manufacturers are required by law to provide a
process history to regulatory agencies, and manufacturers use
recorders to help meet these regulatory requirements. In addition,
manufacturers often use recorders to gather data for trend analyses.
By recording the readings of critical measurement points and
comparing those readings over time with the results of the process,
the process can be improved.
Different recorders display the data they collect differently. Some
recorders list a set of readings and the times the readings were taken;
others create a chart or graph of the readings. Recorders that create
charts or graphs are called chart recorders.
A controller is a device that receives data from a measurement
instrument, compares that data to a programmed setpoint, and, if
necessary, signals a control element to take corrective action.
Local controllers are usually one of the three types: pneumatic,
electronic or programmable. Contollers also commonly reside
in a digital control system.
Controllers
DCS
Controller
(CPU)
I/O card Power
supply
Computer-based
central controller
Pneumatic, electronic, or
programmable local controller
Transmitter Single-loop
controller
Valve
8. A recorder is a device that records
CONTROLLERS
the ________________ of a
measurement or control device.
1. input
2. output
3. diagnostic status
Components of Control Loops and ISA Symbology
Control Loop Equipment and Technology
Fundamentals of Control 17
2006 PAControl.com
Activities
Controllers may perform complex mathematical functions to compare
a set of data to setpoint or they may perform simple addition or
subtraction functions to make comparisons. Controllers always have
an ability to receive input, to perform a mathematical function with
the input, and to produce an output signal. Common examples of
controllers include:
Programmable logic controllers (PLCs)PLCs are usually
computers connected to a set of input/output (I/O) devices. The
computers are programmed to respond to inputs by sending
outputs to maintain all processes at setpoint.
Distributed control systems (DCSs)DCSs are controllers that,
in addition to performing control functions, provide readings of
the status of the process, maintain databases and advanced
man-machine-interface.
9. Which of the following have the
ability to receive input, to perform
P I D
Setpoint
Pipestand Controller Analog Rack Mount Controller
(Pneumatic or Electronic) (Electronic)
Single Loop Digital Converter Distributed Control System
(Electronic) (Electronic)
Types of Process Controllers
a mathematical function with the
input, and produce an output signal?
Actuators
Transmitters
Transducers
Controllers
10. Which of the following is the most
common final control element in
process control industries?
Agitator
Pump motor
Valve
Louver
1
2
3
4
1
2
3
4
Activities
18 Fundamentals of Control
2006 PAControl.com
Components of Control Loops and ISA Symbology
Control Loop Equipment and Technology
CORRECTING ELEMENTS/FINAL CONTROL ELEMENTS
The correcting or final control element is the part of the control
system that acts to physically change the manipulated variable. In
most cases, the final control element is a valve used to restrict or cut
off fluid flow, but pump motors, louvers (typically used to regulate air
flow), solenoids, and other devices can also be final control elements.
Final control elements are typically used to increase or decrease fluid
flow. For example, a final control element may regulate the flow of
fuel to a burner to control temperature, the flow of a catalyst into a
reactor to control a chemical reaction, or the flow of air into a boiler
to control boiler combustion.
In any control loop, the speed with which a final control element
reacts to correct a variable that is out of setpoint is very important.
Many of the technological improvements in final control elements are
related to improving their response time.
ACTUATORS
An actuator is the part of a final control device that causes a physical
change in the final control device when signalled to do so. The most
common example of an actuator is a valve actuator, which opens or
closes a valve in response to control signals from a controller.
Actuators are often powered pneumatically, hydraulically, or
electrically. Diaphragms, bellows, springs, gears, hydraulic pilot
valves, pistons, or electric motors are often parts of an actuator system.
11. _______________ is a part
Digital Valve Controller
(Smart Positioner)
(Provides PID Output)
Smart Transmitter
Smart
Transmitter
Types of Process Controllers
final control device that causes a
physical change in the final control
device when signaled to do so.
1. Actuator
2. Indicator
3. Recorder
Activities
Components of Control Loops and ISA Symbology
Fundamentals of Control 19
2006 PAControl.com
ISA Symbology
The Instrumentation, Systems, and Automation Society (ISA) is one of
the leading process control trade and standards organizations. The ISA
has developed a set of symbols for use in engineering drawings and
designs of control loops (ISA S5.1 instrumentation symbol
specification). You should be familiar with ISA symbology so that you
can demonstrate possible process control loop solutions on paper to
your customer. Figure 7.5 shows a control loop using ISA symbology.
Drawings of this kind are known as piping and instrumentation
drawings (P&ID).
Piping and Instrumentation Drawing
(P&ID)
TY
123
TIC
123
FT
123
TT
123
FIC
123
YIC
123
SP
12. What does the acronym P&ID
stand for?
Piping and Instrument Designing
Piping and Instrumentation
Drawing
Process Control and Installation
Drawing
Proportional, Intergral and
Derivative control
1
2
3
4
Activities
20 Fundamentals of Control
2006 PAControl.com
Components of Control Loops and ISA Symbology
ISA Symbology
SYMBOLS
In a P&ID, a circle represents individual measurement instruments,
such as transmitters, sensors, and detectors (Figure 7.6).
A single horizontal line running across the center of the shape
indicates that the instrument or function is located in a primary
location (e.g., a control room). A double line indicates that the
function is in an auxiliary location (e.g., an instrument rack). The
absence of a line indicates that the function is field mounted, and a
dotted line indicates that the function or instrument is inaccessible
(e.g., located behind a panel board).
A square with a circle inside represents instruments that both display
measurement readings and perform some control function
(Figure 7.7). Many modern transmitters are equipped with
microprocessors that perform control calculations and send control
output signals to final control elements.
Shared Control/Display Elements
A hexagon represents computer functions, such as those carried out
by a controller (Figure 7.8).
Computer Functions (Controllers)
Figure 7.6: Discrete Instruments
LOCATION
Control Room
Field Auxiliary Not Accessible
DISPLAY AND CONTROL TYPES
Control Room Field
Not Accessible
Square
Root
Flow/
Control Types
Control Room
Auxiliary Not Accessible Field
13. Which of the following is a symbol of
a transmitter in an auxiliary
location?
14. Which of the following is a symbol of
a field-mounted control/display
element?
1
2
3
4
1
2
3
4
Activities
Components of Control Loops and ISA Symbology
Fundamentals of Control 21
2006 PAControl.com
ISA Symbology
15. Which of the following is a symbol of
a controller located behind a
panel?
1
2
3
4
Components of Control Loops and ISA Symbology
ISA Symbology
Fundamentals of Control 22
2006 PAControl.com
Activities
A square with a diamond inside represents PLCs (Figure 7.9).
PLCs
Two triangles with their apexes contacting each other (a bow tie
shape) represent a valve in the piping. An actuator is always drawn
above the valve (Figure 7.10).
Valves
Pumps
Directional arrows showing the flow direction represent a pump
(Figure 7.11).
Pumps
Pneumatic valve Manual valve Electric valve
16. The symbol displayed below denotes
a PLC in a primary location.
PLC Types
Auxiliary Field Control Room Not accessible
17. Which of the following is a symbol
of a pneumatic valve?
Is this statement true or false?
1
2
3
4
Activities
23 Fundamentals of Control
2006 PAControl.com
Components of Control Loops and ISA Symbology
ISA Symbology
Piping and Connections
Piping and connections are represented with several different symbols
(Figure 7.12):
A heavy solid line represents piping
A thin solid line represents process connections to instruments
(e.g., impulse piping)
A dashed line represents electrical signals (e.g., 420 mA
connections)
A slashed line represents pneumatic signal tubes
A line with circles on it represents data links
Other connection symbols include capillary tubing for filled systems
(e.g., remote diaphragm seals), hydraulic signal lines, and guided
electromagnetic or sonic signals.
Piping and Connection Symbols
Capillary tubing for
filled systems
Hydraulic
signal line
Data
link
Pneumatic
signal
Guided
electromagnetic
or sonic signal
Electrical
signal
Process
connection
Piping
18. The symbols displayed below represent
a data link and a process connection.
Is this statement true or false?
Components of Control Loops and ISA Symbology
ISA Symbology
Fundamentals of Control 24
2006 PAControl.com
Activities
IDENTIFICATION LETTERS
Identification letters on the ISA symbols (e.g., TT for temperature
transmitter) indicate:
The variable being measured (e.g., flow, pressure, temperature)
The devices function (e.g., transmitter, switch, valve, sensor,
indicator)
Some modifiers (e.g., high, low, multifunction)
Table 7.1 on page 26 shows the ISA identification letter designations.
The initial letter indicates the measured variable. The second letter
indicates a modifier, readout, or device function. The third letter
usually indicates either a device function or a modifier.
For example, FIC on an instrument tag represents a flow indicating
controller. PT represents a pressure transmitter. You can find
identification letter symbology information on the ISA Web site at
http://www.isa.org.
TAG NUMBERS
Numbers on P&ID symbols represent instrument tag numbers. Often
these numbers are associated with a particular control loop (e.g., flow
transmitter 123). See Figure 7.13.
Identification Letters and Tag Number
FIC
123
Identification
letters
Tag number
19. The initial letter on an ISA symbol
indicates the measured variable. Is
this statement true or false?
20. What does the third letter on an ISA
symbol indicate?
Device function or a modifier
Measured variable
Readout
Type of process fluid
1
2
3
4
Activities
25 Fundamentals of Control
2006 PAControl.com
Components of Control Loops and ISA Symbology
ISA Symbology
Measured Variable Modifier Readout Device Function Modifier
A Analysis Alarm
B Burner, combustion Users choice Users choice Users choice
C Users choice Control
D Users choice Differential
E Voltage
Sensor (primary
element)
F Flow rate Ration (fraction)
G Users choice Glass, viewing device
H Hand High
I Electrical Current Indication
J Power Scan
K Time, time schedule Time rate of change Control station
L Level Light Low
M Users choice Momentary Middle, intermediate
N Users choice Users choice Users choice Users choice
O Users choice Orifice, restriction
P Pressure, vacuum Point, test connection
Q Quantity Integrate, totalizer
R Radiation Record
S Speed, frequency Safety Switch
T Temperature Transmit
U Multivariable Multifunction Multifunction Multifunction
V
Vibration, mechanical
analysis
Valve, damper, louver
W Weight, force Well
X Unclassified X axis Unclassified Unclassified Unclassified
Y
Event, state, or
presence Y axis
Relay, compute,
convert
Z Position, dimension Z axis Driver, actuator
ISA Identification Letters
Components of Control Loops and ISA Symbology
ISA Symbology
Fundamentals of Control 26
2006 PAControl.com
Activities
ISA SYMBOLOGY REVIEW
Figure 7.14 shows the elements of ISA symbology used in a P&ID.
P&ID with ISA Symbology
TY
123
TIC
123
FT
123
TT
123
FIC
123
YIC
123
SP
Flow indicating controller that
performs a square root flow
calculation (primary location)
Data link
Electrical
signal
Temperature
computer
Temperature
transmitter
Flow
transmitter
PLC
Temperature
indicating
controller (field
mounted)
Pneumatic
line
Pneumatically
actuated valve
Electrically
actuated valve
Pipe
21.. In Figure 7.14, what kind of
signal is transmitted out from the
temperature transmitter?
COMPLETE WORKBOOK EXERCISE - COMPONENTS OF CONTROL LOOPS AND
Impulse
Tubing
Data link
Mechanical signal
Electrical signal
Pneumatic signal
1
2
3
4
ISA SYMBOLOGY
Fundamentals of Control 27
2006 PAControl.com
Controller Algorithms and Tuning
The previous sections of this module described the purpose of control, defined individual elements within
control loops, and demonstrated the symbology used to represent those elements in an engineering drawing.
The examples of control loops used thus far have been very basic. In practice, control loops can be fairly
complex. The strategies used to hold a process at setpoint are not always simple, and the interaction of
numerous setpoints in an overall process control plan can be subtle and complex. In this section, you will be
introduced to some of the strategies and methods used in complex process control loops.
LEARNING OBJECTIVES
After completing this section, you will be able to:
Differentiate between discrete, multistep, and continuous controllers
Describe the general goal of controller tuning.
Describe the basic mechanism, advantages and disadvantages of the following mode of controller action:
Proportional action
Intergral action
Derivative action
Give examples of typical applications or situations in which each mode of controller action would be
used.
Identify the basic implementation of P, PI and PID control in the following types of loops:
Pressure loop
Flow loop
Level loop
Temperature loop
Note: To answer the activity questions the Hand Tool (H) should be activated.
Controller Algorithms and Tuning
Activities
28 Fundamentals of Control
2006 PAControl.com
Controller Algorithms
The actions of controllers can be divided into groups based upon the
functions of their control mechanism. Each type of contoller has
advantages and disadvantages and will meet the needs of different
applications. Grouped by control mechanism function, the three
types of controllers are:
Discrete controllers
Multistep controllers
Continuous controllers
DISCRETE CONTROLLERS
Discrete controllers are controllers that have only two modes or
positions: on and off. A common example of a discrete controller is a
home hot water heater. When the temperature of the water in the tank
falls below setpoint, the burner turns on. When the water in the tank
reaches setpoint, the burner turns off. Because the water starts
cooling again when the burner turns off, it is only a matter of time
before the cycle begins again. This type of control doesnt actually
hold the variable at setpoint, but keeps the variable within proximity
of setpoint in what is known as a dead zone (Figure 7.15).
Discrete Control
Dead
zone
Control action
Process variable action
1. Which one of the following is an
everyday example of a discrete
controller?
Select the options that apply.
Refrigerator
Electric iron
Air conditioner
Rice cooker
1
2
3
4
Controller Algorithms and Tuning
Controller Algorithms
Fundamentals of Control 29
2006 PAControl.com
Activities
MULTISTEP CONTROLLERS
Multistep controllers are controllers that have at least one other
possible position in addition to on and off. Multistep controllers
operate similarly to discrete controllers, but as setpoint is approached,
the multistep controller takes intermediate steps. Therefore, the
oscillation around setpoint can be less dramatic when multistep
controllers are employed than when discrete controllers are used
(Figure 7.16).
Figure 7.16: Multistep Control Profile
CONTINUOUS CONTROLLERS
Controllers automatically compare the value of the PV to the SP to
determine if an error exists. If there is an error, the controller adjusts
its output according to the parameters that have been set in the
controller. The tuning parameters essentially determine:
How much correction should be made? The magnitude of the
correction( change in controller output) is determined by the
proportional mode of the controller.
How long should the correction be applied? The duration of the
adjustment to the controller output is determined by the integral mode
of the controller
How fast should the correction be applied? The speed at which a
correction is made is determined by the derivative mode of the
controller.
Control action
Process variable action
2. A controller with three or more
set positions is called a continuous
controller. Is this statement true or
false?
Controller Algorithms and Tuning
Controller Algorithms
Fundamentals of Control 30
2006 PAControl.com
LIC
LT
I/P
Controller
SP
PV
P I D
Setpoint
PV
SP
Load
Activities
Automatic Feedback Control
When there is an error, the controller
makes a change in its output.
It determines:
How much? Proportional Mode
How long? Integral Mode
How fast? Derivative Mode
Controller Algorithms and Tuning
Activities
31 Fundamentals of Control
2006 PAControl.com
Why Controllers Need Tuning?
Controllers are tuned in an effort to match the characteristics of the
control equipment to the process so that two goals are achieved:
is the foundation of process control measurement in that electricity:
The system responds quickly to errors.
The system remains stable (PV does not oscillate around
the SP).
GAIN
Controller tuning is performed to adjust the manner in which a control
valve (or other final control element) responds to a change in error.
In particular, we are interested in adjusting the gain of the controller
such that a change in controller input will result in a change in
Gain is defined simply as the change in output divided by the change
in input.
Examples:
Change in Input to Controller - 10%
Change in Input to Controller - 10%
Change in Controller Output - 5%
Gain = 5% / 10% = 0.5
convey measurements and instructions to other instruments in a
control loop to maintain the highest level of safety and efficiency.
The next three sections in this module discuss electricity, circuits,
transmitters, and signals in greater detail so you can understand the
importance of electricity in process control.
controller output that will, in turn, cause sufficient change in
valve position to eliminate error, but not so great a change as
to cause instability or cycling.
Change in Controller Output - 20%
Gain = 20% / 10% = 2
3. The change in the controller output
divided by the change in the input to the
controller is known as __________ .
1. error
2. gain
3. set point
4. offset
Controller Algorithms and Tuning
Activities
32 Fundamentals of Control
2006 PAControl.com
Why Controllers Need Tuning?
Gain Plot - The Figure below is simply another graphical way of
representing the concept of gain.
Gain Kc = Output % / Input %
0 50 100
Gain=2 Gain=1
Gain=0.5
Examples - The following examples help to illustrate the purpose of
setting the controller gain to different values.
Controllers May be Tuned to Help Match the Valve to the Process
Large volume gas process
Small volume liquid process
Fast Process May Require Less Gain To Achieve Stability
Slow Process May Require Higher Gain To Achieve Responsiveness
Output %
Graphical Representaion of Gain Concept
Input %
LT
LT
LIC LIC I/P I/P
Fast and Slow Processes May Require Different Controller Gain Settings
0
50
100
4. Fast or slow processes have no impact
on controller gain settings. Is this
statement true or false?
Activities
33 Fundamentals of Control
2006 PAControl.com
Controller Algorithms and Tuning
Proportional Mode
The proportional mode is used to set the basic gain value of the
controller. The setting for the proportional mode may be expressed
as either:
1. Proportional Gain
2. Proportional Band
proportional gain. Proportional Gain (Kc) answers the question:
"What is the percentage change of the controller output relative to the
percentage change in controller input?"
Proportional Gain is expressed as:
Gain, (Kc) = Output% /Input %
PROPORTIONAL BAND
Proportional Band (PB) is another way of representing the same
information and answers this question:
"What percentage of change of the controller input span will cause a
100% change in controller output?"
PB = Input (% Span) For 100%Output
Converting Between PB and Gain
A simple equation converts gain to proportional Band:
added.
PB = 100/Gain
Also recall that:
5. Identify the major disadvantage
of proportional action.
In electronic controllers, proportional action is typically expressed as
PROPORTIONAL GAIN
Gain = 100%/PB
Proportional Gain, (Kc) = Output% / Input %
PB= Input(%Span) For 100%Output
Tends to leave an offset
Reset Windup during shutdown
Possible overshoot during
startup
Can cause cycling in fast process
by amplifying noisy signals
1
2
3
4
PROPORTIONAL ACTION
Controller Algorithms and Tuning
Activities
34 Fundamentals of Control
2006 PAControl.com
Proportional Mode
DETERMINING THE CONTROLLER OUTPUT
Controller Output - In a proportional only controller, the output is a
function of the change in error and controller gain.
Output Change, % = (Error Change, %) (Gain)
Example: If the setpoint is suddenly changed 10% with a proportional
band setting of 50%, the output will change as follows:
6. If proportional gain is 0.5, and a
level reading is 5% above setpoint,
a proportional controller will signal
the outflow control valve to open
0 50 100 150 200
Input %
0
50
100
Output %
Gain=2 Gain=1 Gain=0.5
PB= 50% PB=100% PB=200%
Relationship of Proportional Gain and Proportional Band
LIMITS OF PROPORTIONAL ACTION
Responds Only to a Change in error - Proportional action responds
only to a change in the magnitude of the error.
Does Not Return the PV to Setpoint - Proportional action will not
return the PV to setpoint. It will, however, return the PV to a value
that is within a defined span (PB) around the PV.
Calculating Controller Output
Controller Output = Input, % X Gain
Gain = 100%/PB
EXAMPLE
Input = 10%
PB = 50%, so Gain = 100%/50% = 2
by <1 / 2.5 / 5> % of its full range.
Controller Algorithms and Tuning
Activities
35 Fundamentals of Control
2006 PAControl.com
Proportional Mode
Controller Output = Input X Gain
Controller Output = 10% X 2 = 20%
Expressed in Units:
Controller Output Change = (0.2)(12 psi span) = 2.4 psiOR
(0.2)(16 mA span) = 3.2 mA
PROPORTIONAL ACTION - CLOSED LOOP
Loop Gain - Every loop has a critical or natural frequency. This is the
frequency at which cycling may exist. This critical frequency is
Low Gain Example - In the example below, the proportional band is
high (gain is low). The loop is very stable, but an error remains between
SP and PV.
determined by all of the loop components. If the loop gain is too high
at this frequency, the PV will cycle around the SP; i.e., the process
will become unstable.
Proportional Control Closed Loop - Low Gain Example
0 1 2 3 4 5 6 7 8 9 10
SP
PV
IVP
0
1
2
3
4
7
8
9
10
6
5
Time
%
PB= 200%
High Gain Example - In the example, the proportional band is
small resulting in high gain, which is causing instability. Notice that
the process variable is still not on set point.
Controller Algorithms and Tuning
Activities
36 Fundamentals of Control
2006 PAControl.com
Proportional Mode
Proportional Summary - For the proportional mode, controller output
is a function of a change in error. Proportional band is expressed in
terms of the percentage change in error that will cause 100% change in
controller output. Proportional gain is expressed as the percentage
change in output divided by the percentage change in input.
PB = (Input, % / Output, % ) x 100 = 100/Gain
Controller Output = (Change in Error)(Gain)
1. Proportional Mode Responds only to a change in error
2. Proportional mode alone will not return the PV to SP.
Advantages - Simple
Proportional Control Closed Loop - High Gain example
IVP
SP
Gain= Input % / Output %
Disadvantages - Error
Settings - PB settings have the following effects:
Small PB (%) Minimize Offset
High Gain (%) Possible cycling
Large PB (%) Large Offset
Low Gain Stable Loop
Tuning - reduce PB (increase gain) until the process cycles following
a disturbance, then double the PB (reduce gain by 50%).
0 1 2 3 4 5 6 7 8 9 10
TIME 0
1
2
3
4
5
6
7
8
9
10
PB=10%
%
PV
7. What will be the result if the
proportional gain is set too high?
Select all options that apply.
Large offset
Minimized offset
Possible cycling
Stable loop
1
2
3
4
Controller Algorithms and Tuning
Activities
37 Fundamentals of Control
2006 PAControl.com
Integral Mode
INTEGRAL ACTION
Duration of Error and Integral Mode - Another component of error
OPEN LOOP ANALYSIS
Purpose- The purpose of integral action is to return the PV to SP. This is
accomplished by repeating the action of the proportional mode as
long as an error exists. With the exception of some electronic
controllers, the integral or reset mode is always used with the
proportional mode.
Setting - Integral, or reset action, may be expressed in terms of:
Repeats Per Minute - How many times the proportional
action is repeated each minute.
8. _____________ action is the type of
control algorithm that eliminates offset. is the duration of the error, i.e., how long has the error existed?
The controller output from the integral or reset mode is a function of
the duration of the error.
0 1 2 3 4 5 6 7 8 9 10
Duration
PV
SP
%
0
100
90
80
70
60
50
40
30
10
20
INTEGRAL(RESET)
Minutes Per Repeat - How many minutes are required for
1 repeat to occur.
1. Proportional
2. Derivative
3. Integral
Controller Algorithms and Tuning
Activities
38 Fundamentals of Control
2006 PAControl.com
Integral Mode
CLOSED LOOP ANALYSIS
Closed Loop With Reset - Adding reset to the controller adds one more
Fast Reset Example - In the example the rest is too fast and the PV is
cycling around the SP.
gain component to the loop. The faster the reset action, the greater
the gain.
Slow Reset Example - In this example the loop is stable because
the total loop gain is not too high at the loop critical frequency.
Notice thatthe process variable does reach set point due to the reset
action.
SP
PV
IVP
0 1 2 3 4 5 6 7 8 9 10
TIME
%
0
10
20
30
40
50
60
70
80
90
100
PB=80%
Repeat=2.0 Repeats/min
SLOW RESET, CLOSED LOOP
%
0
10
20
30
40
50
60
70
80
90
100
0 1 2 3 4 5 6 7 8 9 10
PB=80%
Repeat=10 Repeats/min
PV
IVP
SP
TIME
FAST RESET, CLOSED LOOP
9. Which of the following are integral
or reset actions expressed in
terms of?
Select all options that apply.
Repeats per setting
Repeats per minute
Repeats per loop
Minutes per repeat
1
2
3
4
Controller Algorithms and Tuning
Activities
39 Fundamentals of Control
2006 PAControl.com
Integral Mode
RESET WINDUP
Defined - Reset windup is described as a situation where the controller
output is driven from a desired output level because of a large
difference between the set point and the process variable.
0
100
Output%
IVP
INPUT(ERROR)
ARW
Reset Windup - Ant-Reset Windup
Shutdown - Reset windup is common on shut down because the
process variable may go to zero but the set point has not changed,
therefore this large error will drive the output to one extreme.
Reset Windup - Shutdown and Startup
Startup - At start up, large process variable overshoot may occur
because the reset speed prevents the output from reaching its desired
value fast enough.
Anti Reset Windup - Controllers can be modified with an anti-reset
Shutdown Input(Error) Startup
SP
PV
ARW
0
100
Input %
10. Identify the major disadvantages
of integral action.
Select all options that apply.
Tends to leave an offset
Reset windup during shutdown
Possible overshoot during start up
by amplifying noisy signals
Can cause cycling in fast process
1
2
3
4
Controller Algorithms and Tuning
Activities
40 Fundamentals of Control
2006 PAControl.com
Integral Mode
windup (ARW) device. The purpose of an anti-reset option is to allow
the output to reach its desired value quicker, therefore minimizing
the overshoot.
Fast Reset 1.High Gain
(Large Repeats/Min.,Small Min./Repeat) 2.Fast Return To Setpoint
Slow Reset 1.Low Gain
(Small Repeats/Min.,Large Min./Repeats) 2.Slow Return To Setpoint
3.Stable Loop
Trailing and Error Tuning - Increase repeats per minute until the
PV cycles following a disturbance, then slow the reset action to a
value that is 1/3 of the initial setting.
SUMMARY
Integral (Reset) Summary - Output is a repeat of the proportional
action as long as error exists. The units are in terms of repeats per
minute or minutes per repeat.
Advantages - Eliminates error
Disadvantages - Reset windup and possible overshoot
3.Possible Cycling
Controller Algorithms and Tuning
Activities
41 Fundamentals of Control
2006 PAControl.com
Derivative Mode
DERIVATIVE ACTION
Derivative Mode Basics - Some large and/or slow process do not
The derivative action is initiated whenever there is a change in the
rate of change of the error (the slope of the PV). The magnitude of
the derivative action is determined by the setting of the derivative . The
11. ___________ action is a control
algorithm that is tied to the rate of
change in the error.
respond well to small changes in controller output. For example,
a large liquid level process or a large thermal
process (a heat exchanger) may react very slowly to a small change
in controller output. To improve response, a large initial change in
controller output may be applied. This action is the role of the
derivative mode.
mode of a PID controller and the rate of change of the PV. The
Derivative setting is expressed in terms of minutes. In oper ation, the
the controller first compares the current PV with the last value of the
PV. If there is a change in the slope of the PV, the controller
etermines what its output would be at a future point in time
(the future point in time is determined by the value of the derivative
setting, in minutes). The derivative mode immediately increases
the output by that amount.
0 1 2 3 4 5 6 7 8 9 10
TIME
%
0
10
20
30
40
50
60
70
80
90
100
Derivative Action is based on the rate of change in Error (Y/X)
PV
SP
X
Y
Slope= Rate of Error Change(Y/X)
12. Which of the following are derivative or
rate actions expressed in terms of?
Repeats per minute
Hours
Seconds
Minutes
Milliseconds
1
2
3
4
5
1. Proportional
2. Derivative
3. Integral
Controller Algorithms and Tuning
Activities
42 Fundamentals of Control
2006 PAControl.com
Derivative Mode
Example - Let's start a closed loop example by looking at a
temperature control system. IN this example, the time scale has been
lengthened to help illustrate controller actions in a slow process.
Rate Effect - To illustrate the effect of rate action, we will add the
are mode with a setting of 1 minute. Notice the very large controller
output at time 0. The output spike is the result of rate action. Recall
Assume a proportional band settingof 50%. There is no reset at
this time. The proportional gain of 2 acting on a 10% change in set
pint results in a change in controller output of 20%. Because
temperature is a slow process the setting time after a change in error
is quite long. And, in this example, the PV never becomes equal to
the SP because there is no reset.
that the change in output due to rate action is a function of the speed
(rate) of change of error, which in a step is nearly infinite. The
addition of rate alone will not cause the process variable to match the
set point.
0 100 200 300 400
SP
IVP
PV
TIME
TIME
PB=50%
Reset=0
Rate=0
PB=50%
Reset=0
Rate=1 min
PV
PV
IVP
SP
SP
0
10
20
30
40
50
60
70
80
90
100
0
10
20
30
40
50
60
70
80
90
100
0 100 200 300 400
No Rate, Small Rate examples, Closed Loop
13. The addition of derivative or rate alone
to a close loop control can cause the
process variable to match the set point.
Is this statement true or false?
Controller Algorithms and Tuning
Activities
43 Fundamentals of Control
2006 PAControl.com
Derivative Mode
Effect of Fast Rate - Let's now increase the rate setting to 10 minutes.
The controller gain is now much higher. As a result, both the IVP
(controller output) and the PV are cycling. The point here is that
Need for Reset Action - It is now clear that reset must be added to
bring process variable back to set point.
Applications - Because this component of the controller output is
greatest change when the input changes rapidly.
Controller Option to Ignore Change in SP - Many controllers,
especially digital types, are designed to respond to changes in the PV
only, and to ignore changes in SP. This feature eliminates a major upset
increasing the rate setting will not cause the PV to settle at the SP.
0 100 200 300 400
dependent on the speed of change of the input or error, the output
will be very erratic if rate is used on fast process or one with noisy
signals. The controller output, as a result of rate, will have the
upset that would occur following a change in the setpoint.
0
10
20
30
40
50
60
70
80
90
100
P+D, High Rate Setting, Closed Loop Analysis
TIME
IVP
SP
PV
PB= 50%
Reset=0
Rate= 10 min
Controller Algorithms and Tuning
Activities
44 Fundamentals of Control
2006 PAControl.com
Derivative Mode
SUMMARY
Derivative (Rate) Sumary - Rate action is a function of the speed of
change of the error. The units are minutes. The action is to apply an
Disadvantage - Dramatically amplifies noisy signals; can cause
cycling in fast processes.
Settings
Large (Minutes) 1.High Gain
2.Large Output Change
3.Possible Cycling
Small (Minutes) 1.Low Gain
2.Small Output Change
3.Stable Loop
Trial-and-Error Tuning
immediate response that is equal to the proportional plus reset action
that would have occurred some number of minutes I the future.
Advantages - Rapid output reduces the time that is required to return
PV to SP in slow process.
Increase the rate setting until the process cycles following a
disturbance, then reduce the rate setting to one-third of the initial
value.
Controller Algorithms and Tuning
Controller Algorithms
Fundamentals of Control 45
2006 PAControl.com
Activities
Proportional, PI, and PID Control
By using all three control algorithms together, process operators can:
K Achieve rapid response to major disturbances with derivative
control
K Hold the process near setpoint without major fluctuations with
proportional control
K Eliminate offset with integral control
Not every process requires a full PID control strategy. If a small offset
has no impact on the process, then proportional control alone may be
sufficient.
PI control is used where no offset can be tolerated, where noise
(temporary error readings that do not reflect the true process variable
condition) may be present, and where excessive dead time (time after
a disturbance before control action takes place) is not a problem.
In processes where no offset can be tolerated, no noise is present, and
where dead time is an issue, customers can use full PID control.
Table 7.2 shows common types of control loops and which types of
control algorithms are typically used.
Controlled
Variable
Proportional
Control PI Control PID Control
Flow Yes Yes No
Level Yes Yes Rare
Temperature Yes Yes Yes
Pressure Yes Yes Rare
Analytical Yes Yes Rare
Table 7.2: Control Loops and Control Algorithms
14. What type of control is used in
an application where noise is
present, but where no offset can
be tolerated?
P only
PD
PI
PID
1
2
3
4
COMPLETE WORKBOOK EXERCISE - CONTROLLER ALGORITHMS AND TUNING
Fundamentals of Control 46
2006 PAControl.com
Process Control Loops
In this section, you will learn about how control components and control algorithms are integrated to create a
process control system. Because in some processes many variables must be controlled, and each variable can
have an impact on the entire system, control systems must be designed to respond to disturbances at any point
in the system and to mitigate the effect of those disturbances throughout the system.
LEARNING OBJECTIVES
After completing this section, you will be able to:
Explain how a multivariable loop is different from a single loop.
Differentiate feedback and feedforward control loops in terms of their operation, design, benefits, and
limitations
Perform the following functions for each type of standard process control loop (i.e., pressure, flow, level,
and temperature):
State the type of control typically used and explain why it is used
Identify and describe considerations for equipment selection (e.g., speed, noise)
Identify typical equipment requirements
Diagram the loop using ISA symbology
Explain the basic implementation process, including a description of equipment requirements and
considerations, for each of the following types of control:
Cascade control
Batch control
Ratio control
Selective control
Fuzzy control
Describe benefits and limitations of each type of control listed above
Give examples of process applications in which each type of control described in this section might be
used
Note: To answer the activity questions the Hand Tool (H) should be activated.
Process Control Loops
Activities
47 Fundamentals of Control
2006 PAControl.com.
Single Control Loops
Control loops can be divided into two categories: Single variable
loops and multi-variable loops.
FEEDBACK CONTROL
A feedback loop measures a process variable and sends the
measurement to a controller for comparison to setpoint. If the
process variable is not at setpoint, control action is taken to return the
process variable to setpoint. Figure 7.18 illustrates a feedback loop in
which a transmitter measures the temperature of a fluid and, if
necessary, opens or closes a hot steam valve to adjust the fluids
temperature.
Feedback Loop
An everyday example of a feedback loop is the cruise control system
in an automobile. A setpoint is established for speed. When the car
begins to climb a hill, the speed drops below setpoint and the
controller adjusts the throttle to return the cars speed to setpoint.
Feedback loops are commonly used in the process control industry.
The advantage of a feedback loop is that it directly controls the
desired process variable. The disadvantage to feedback loops is that
the process variable must leave setpoint for action to be taken.
Process
fluid
Controller
Transmitter
Steam valve
1. What type of control loop takes
action in response to measured
deviation from setpoint?
Discrete control loop
Multi-step control loop
Open loop
Feedback control loop
1
2
3
4
Activities
Process Control Loops
Fundamentals of Control 48
2006 PAControl.com
Examples of Single Control Loops
While each application has its own characteristics, some general
statements can be made about pressure, flow, level, and temperature
loops.
PRESSURE CONTROL LOOPS
Pressure control loops vary in speedthat is, they can respond to
changes in load or to control action slowly or quickly. The speed
required in a pressure control loop may be dictated by the volume of
the process fluid. High-volume systems (e.g., large natural gas storage
facilities) tend to change more slowly than low-volume systems
(Figure 7.21).
A Pressure Loop
Process
fluid
Fluid
pump
Pneumatic
controller
Pressure
transmitter
Relief
valve
2. How does a high-volume pressure
control loop react as compared to a
small-volume pressure control loop?
Same rate
Quicker
Slower
Extremely fast
1
2
3
4
Activities
49 Fundamentals of Control
2006 PAControl.com.
Process Control Loops
Examples of Single Control Loops
FLOW CONTROL LOOPS
Generally, flow control loops are regarded as fast loops that respond
to changes quickly. Therefore, flow control equipment must have fast
sampling and response times. Because flow transmitters tend to be
rather sensitive devices, they can produce rapid fluctuations or noise
in the control signal. To compensate for noise, many flow transmitters
have a damping function that filters out noise. Sometimes, filters are
added between the transmitter and the control system. Because the
temperature of the process fluid affects its density, temperature
measurements are often taken with flow measurements and
compensation for temperature is accounted for in the flow
calculation. Typically, a flow sensor, a transmitter, a controller, and a
valve or pump are used in flow control loops (Figure 7.22).
A Flow Loop
Process
fluid
Fluid
pump
Pneumatic
controller
Flow
transmitter
Valve
3. Flow control loops are generally
considered to be slow responding
loops. Is this statement true or false?
Process Control Loops
Examples of Single Control Loops
Fundamentals of Control 50
2006 PAControl.com
Activities
LEVEL CONTROL LOOPS
The speed of changes in a level control loop largely depends on the
size and shape of the process vessel (e.g., larger vessels take longer to
fill than smaller ones) and the flow rate of the input and outflow
pipes. Manufacturers may use one of many different measurement
technologies to determine level, including radar, ultrasonic, float
gauge, and pressure measurement. The final control element in a level
control loop is usually a valve on the input and/or outflow
connections to the tank (Figure 7.23). Because it is often critical to
avoid tank overflow, redundant level control systems are sometimes
employed.
A Level Loop
Differential
pressure
transmitter
Level
controller
Level
controller
Converter
4. Redundant control systems are
sometimes used in level applications
because preventing tank overflow is
often critically important. Is this
statement true or false?
Activities
51 Fundamentals of Control
2006 PAControl.com
Process Control Loops
Examples of Single Control Loops
TEMPERATURE CONTROL LOOPS
Because of the time required to change the temperature of a process
fluid, temperature loops tend to be relatively slow. Feedforward
control strategies are often used to increase the speed of the
temperature loop response. RTDs or thermocouples are typical
temperature sensors. Temperature transmitters and controllers are
used, although it is not uncommon to see temperature sensors wired
directly to the input interface of a controller. The final control element
for a temperature loop is usually the fuel valve to a burner or a valve
to some kind of heat exchanger. Sometimes, cool process fluid is
added to the mix to maintain temperature (Figure 7.24).
A Temperature Loop
Process
fluid
Controller
Temperature
transmitter
Valve
5. What type of control strategy is
often used to increase the speed
of a temperature control loop?
Feedforward control
Feedback control
Cascade control
Ratio control
1
2
3
4
Activities
52 Fundamentals of Control
2006 PAControl.com
Process Control Loops
Multi-Variable / Advanced Control Loops
MULTIVARIABLE LOOPS
Multivariable loops are control loops in which a primary controller
controls one process variable by sending signals to a controller of a
different loop that impacts the process variable of the primary loop.
For example, the primary process variable may be the temperature of
the fluid in a tank that is heated by a steam jacket (a pressurized steam
chamber surrounding the tank). To control the primary variable
(temperature), the primary (master) controller signals the secondary
(slave) controller that is controlling steam pressure. The primary
controller will manipulate the setpoint of the secondary controller to
maintain the setpoint temperature of the primary process variable
(Figure 7.17).
.
Multivariable Loop
When tuning a control loop, it is important to take into account the
presence of multivariable loops. The standard procedure is to tune the
secondary loop before tuning the primary loop because adjustments
to the secondary loop impact the primary loop. Tuning the primary
loop will not impact the secondary loop tuning.
Transmitter
Transmitter
Primary
controller
Secondary
controller Valve
SP
6. A multivariable control loop
contains a primary and
secondary controller assigned
to different process variables? Is
this statement true or false?
Process Control Loops
Multi-Variable / Advanced Control Loops
Fundamentals of Control 53
2006 PAControl.com
Activities
FEEDFORWARD CONTROL
Feedforward control is a control system that anticipates load
disturbances and controls them before they can impact the process
variable. For feedforward control to work, the user must have a
mathematical understanding of how the manipulated variables will
impact the process variable. Figure 7.19 shows a feedforward loop in
which a flow transmitter opens or closes a hot steam valve based on
how much cold fluid passes through the flow sensor.
Feedforward Control
An advantage of feedforward control is that error is prevented, rather
than corrected. However, it is difficult to account for all possible load
disturbances in a system through feedforward control. Factors such as
outside temperature, buildup in pipes, consistency of raw materials,
humidity, and moisture content can all become load disturbances and
cannot always be effectively accounted for in a feedforward system.
In general, feedforward systems should be used in cases where the
controlled variable has the potential of being a major load disturbance
on the process variable ultimately being controlled. The added
complexity and expense of feedforward control may not be equal to
the benefits of increased control in the case of a variable that causes
only a small load disturbance.
Cold
process
fluid
Controller
Flow
transmitter
Steam valve
7. What type of control loop
anticipates and controls load
disturbances before they can
impact the process variable?
Feedback control loop
Feedforward control loop
Ratio control loop
Single variable loop
1
2
3
4
Activities
54 Fundamentals of Control
2006 PAControl.com.
Process Control Loops
Multi-Variable / Advanced Control Loops
FEEDFORWARD PLUS FEEDBACK
Because of the difficulty of accounting for every possible load
disturbance in a feedforward system, feedforward systems are often
combined with feedback systems. Controllers with summing
functions are used in these combined systems to total the input from
both the feedforward loop and the feedback loop, and send a unified
signal to the final control element. Figure 7.20 shows a
feedforward-plus-feedback loop in which both a flow transmitter and
a temperature transmitter provide information for controlling a hot
steam valve.
Feedforward Plus Feedback Control
System
Process
fluid
Flow
transmitter
Steam valve
Feedforward
controller
Summing
controller
Feedback
controller
Temperature
transmitter
8. A controller with a summing function
totals the input from both the
feedforward loop and the feedback
loop and sends a unified signal to
the final control element. This is
how a single control signal is sent to
the final control element in a
feedforward plus feedback system.
Is this statement true or false?
Activities
Process Control Loops
Fundamentals of Control 55
2006 PAControl.com
Multi-Variable / Advanced Control Loops
This module has discussed specific types of control loops, what
components are used in them, and some of the applications (e.g., flow,
pressure, temperature) they are applied to. In practice, however, many
independent and interconnected loops are combined to control the
workings of a typical plant. This section will acquaint you with some
of the methods of control currently being used in process industries.
CASCADE CONTROL
Cascade control is a control system in which a secondary (slave)
control loop is set up to control a variable that is a major source of load
disturbance for another primary (master) control loop. The controller
of the primary loop determines the setpoint of the summing contoller in
the secondary loop (Figure 7.25).
Cascade Control
Process
fluid
Primary
controller
Temperature
transmitter
Valve
Flow
transmitter
Secondary
controller
9. Ratio control is the term used to
describe a system in which the
controller of the primary loop determines
the setpoint of a secondary loop. Is
this statement true or false?
Activities
56 Fundamentals of Control
2006 PAControl.com
Process Control Loops
Multi-Variable / Advanced Control Loops
BATCH CONTROL
Batch processes are those processes that are taken from start to finish
in batches. For example, mixing the ingredients for a juice drinks is
often a batch process. Typically, a limited amount of one flavor (e.g.,
orange drink or apple drink) is mixed at a time. For these reasons, it is
not practical to have a continuous process running. Batch processes
often involve getting the correct proportion of ingredients into the
batch. Level, flow, pressure, temperature, and often mass
measurements are used at various stages of batch processes.
A disadvantage of batch control is that the process must be frequently
restarted. Start-up presents control problems because, typically, all
measurements in the system are below setpoint at start-up. Another
disadvantage is that as recipes change, control instruments may need
to be recalibrated.
RATIO CONTROL
Imagine a process in which an acid must be diluted with water in the
proportion two parts water to one part acid. If a tank has an acid
supply on one side of a mixing vessel and a water supply on the other,
a control system could be developed to control the ratio of acid to
water, even though the water supply itself may not be controlled. This
type of control system is called ratio control (Figure 7.26). Ratio
control is used in many applications and involves a contoller that
receives input from a flow measurement device on the unregulated
(wild) flow. The controller performs a ratio calculation and signals the
appropriate setpoint to another controller that sets the flow of the
second fluid so that the proper proportion of the second fluid can be
added.
Ratio control might be used where a continuous process is going on
and an additive is being put into the flow (e.g., chlorination of water).
Ratio Control
Acid flow Water flow
10. Which term describes a control
system in which controlled
flow is added proportionately to
an uncontrolled flow?
Selective control
Cascade control
Ratio control
Fuzzy control
1
2
3
4
Process Control Loops
Multi-Variable / Advanced Control Loops
Fundamentals of Control 57
2006 PAControl.com
Activities
SELECTIVE CONTROL
Selective control refers to a control system in which the more
important of two variables will be maintained. For example, in a
boiler control system, if fuel flow outpaces air flow, then
uncombusted fuel can build up in the boiler and cause an explosion.
Selective control is used to allow for an air-rich mixture, but never a
fuel-rich mixture. Selective control is most often used when
equipment must be protected or safety maintained, even at the cost of
not maintaining an optimal process variable setpoint.
FUZZY CONTROL
Fuzzy control is a form of adaptive control in which the controller
uses fuzzy logic to make decisions about adjusting the process. Fuzzy
logic is a form of computer logic where whether something is or is
not included in a set is based on a grading scale in which multiple
factors are accounted for and rated by the computer. The essential
idea of fuzzy control is to create a kind of artificial intelligence that
will account for numerous variables, formulate a theory of how to
make improvements, adjust the process, and learn from the result.
Fuzzy control is a relatively new technology. Because a machine
makes process control changes without consulting humans, fuzzy
control removes from operators some of the ability, but none of the
responsibility, to control a process.
11. In which type of control system
will the more important of two
variables be maintained?
COMPLETE WORKBOOK EXERCISE - PROCESS CONTROL LOOPS
Fuzzy control
Cascade control
Ratio control
Selective control
12. ___________ control is the term
used to describe a control system in
which the controller uses computer
logic to make decisions about adjusting
the process.
1
2
3
4
1. Fuzzy
2. Selective
3. Ratio
Module 7: Workbook Exercises
EXERCISE 7.1 THE IMPORTANCE OF PROCESS CONTROL
1. Which of the following options best represents the reasons to control a process?
(Select three options that apply)
(1) Reduce variability
(2) Increase productivity
(3) Increase efficiency
(4) Reduce cost
(5) Ensure safety
2. Process is defined as the method of changing or refining raw materials to create end
products. Is this statement true or false?
(1) True
(2) False
3. Which of the following are advantages of reducing variability in a process
application?
(1) Helps ensure a consistently high-quality end product.
(2) Helps ensure an increase in the reaction rate of the process.
(3) Helps ensure increase in efficiency of the process.
(4) Helps ensure safety
Page 58 Workbook Exercises
2006 PAControl.com
Module 7: Workbook Exercises
EXERCISE 7.2 CONTROL THEORY BASICS
1. Which of the following tasks is associated with process control? (Select three options
that apply)
(1) Measurement
(2) Comparison
(3) Quality Analysis
(4) Adjustment
(5) Calculation
2. Which of the following variables are commonly measured or monitored in process
control applications? (Select three options that apply)
(1) Pressure
(2) Viscosity
(3) Nitrogen content
(4) Flow rate
(5) Temperature
3. A process liquid level needs to be held within 5 ft of 150 ft in a large tank. A pressure
transmitter monitors the liquids level using a pressure reading and sends the result
to a controller. The controller compares the level reading to the set point and opens
or closes an inflow or outflow pipe depending on the liquid level. Keeping in mind the
given scenario, match the terms in Column A with their values in Column B.
(1) Inferred process variable (A) 150 ft
(2) Manipulated variable (B) Pressure
(3) Measured variable (C) Flow of liquid to the tank
(4) Set point (D) Level
Workbook Exercises Page 59
2006 PAControl.com
Module 7: Workbook Exercises
4. Match each term to its correct definition.
(1) Load disturbance
(2) Control algorithm
(3) Manual control
(4) Manipulated variable
(5) Set point
(A) The factor that is changed to keep a measured variable at set point.
(B) An undesired change in a factor that can affect the process variable.
(C) A value or range of values for a process variable that must be maintained to
keep the process running properly.
(D) A control operation that directly involves human action.
(E) A mathematical expression of a control function
5. Match each term to its correct description.
(1) Closed-loop, automatic control _____
(2) Closed-loop, manual control _____
(3) Open-loop, automatic control _____
(A) An operator turns off the heater coil when the temperature transmitter outputs
a certain reading.
(B) A controller turns off the heater coil at set intervals, regardless of the process
temperature.
(C) A temperature sensor measures process temperature, sends the result to a
controller to compare to the setpoint, and the controller turns off the heater
coil.
6. __________ is a deviation from set point due to load disturbance.
(1) Error
(2) Offset
(3) Rate of change
7. __________ is a continuing error due to the inability of a control system to keep the
measured variable at set point.
(1) Load disturbance
(2) Offset
(3) Pressure
Page 60 Workbook Exercises
2006 PAControl.com
Module 7: Workbook Exercises
EXERCISE 7.3 COMPONENTS OF CONTROL LOOPS AND ISA SYMBOLOGY
1. The basic function of a __________ is to convert a reading from a transducer into a
standard signal and transmit that signal to a controller or computer monitor.
(1) recorder
(2) transmitter
(3) converter
2. 420 mA is the most common standard analog signal used in the process control
industry today. Is this statement true or false?
(1) True
(2) False
3. Match the signal type in Column A with its example/application in Column B.
(1) Analog signal (A) 3 15 psig
(2) Pneumatic signal (B) Fieldbus, Profibus and Modbus
(3) Digital signal (C) 4-20 mA and 1 5 V
4. A customer would use __________to read the temperature of a process fluid on a
display.
(1) an indicator
(2) a volt-meter
(3) an actuator
5. Match each control loop equipment to its correct description.
(1) Recorder _____
(2) Controller _____
(3) Final control element _____
(4) Actuator _____
6. A pump motor is the most commonly used final control element. Is this statement
true or false?
(1) True
(2) False
Workbook Exercises Page 61
2006 PAControl.com
Module 7: Workbook Exercises
7. Match the ISA symbols in Column A with its respective description in Column B.
(1) (A) Programmable logic control
(2) (B) Temperature transmitter
(3) (C) Pneumatically actuated valve
(4) (D) Electrically actuated valve
Page 62 Workbook Exercises
2006 PAControl.com
Module 7: Workbook Exercises
EXERCISE 7.4 CONTROL ALGORITHMS AND TUNING
1. Match each term to its correct definitions.
(1) Proportional band
(2) Proportional/integral (PI) control
(3) Proportional control
(4) Derivative control
(5) Integral control
(A) A type of control that corrects error and eliminates offset.
(B) A type of control that produce erratic output in noisy applications.
(C) The percent change in error that will cause a 100% change in controller
output.
(D) A type of control that is prone to leaving an offset.
(E) A type of control that repeats the action of the proportional mode as long as
an error exists.
2. Identify the two effects on a process variable if the proportional gain (Pgain) is set too
high? (Select all that apply)
(1) Minimize offset
(2) Large offset
(3) Stable loop
(4) Possible cycling
3. Derivative gain (Dgain) is typically set to zero in flow applications since flow
applications are usually noisy and derivative control will react to readings that are in
fact noise, thus preventing the process from holding set point. Is this statement true
or false?
(1) True
(2) False
Workbook Exercises Page 63
2006 PAControl.com
Module 7: Workbook Exercises
EXERCISE 7.5 PROCESS CONTROL LOOPS
1. Which control system anticipates load disturbances and controls them before they
can impact the process variable?
(1) Selective control
(2) Fuzzy control
(3) Feed forward control
(4) Cascade control
2. Match the component label in Column A to its ISA symbol representation in Column
B.
(1) Flow transmitter (A)
(2) Temperature transmitter (B)
(3) Flow controller (C)
(4) Valve (D)
3. If R
1
= 60 , R
2
= 100 , and R
3
= 100 , what is the equivalent resistance (R
eq
) in
the circuit?
(1) slow
(2) fast
(3) variable speed
Page 64 Workbook Exercises
2006 PAControl.com.
Module 7: Workbook Exercises - Answers
Exercise 7.1 The Importance of Process Control
1. 1, 3, 5
2. 1
3. 1
Exercise 7.2 Control Theory Basics
1. 1, 2, 4
2. 1, 4, 5
3. D, C, B, A
4. B, E, D, A, C
5. C, A, B
6. 1
7. 2
Exercise 7.3 Components of Control Loops and ISA Symbology
1. 2
2. 1
3. C, A, B
4. 1
5. C, D, B, A
6. 2
7. B, C, D, A
Exercise 7.4 Control Algorithms and Tuning
1. C, A, D, B, E
2. 1, 4
3. 1
Exercise 7.5 Process Control Loops
1. 3
2. B, C, D, A
3. 1
Workbook Exercises Page 65
2006 PAControl.com
Module 7: Activity Answers
The Importance of Process Control
1. True
2. 1,3,5
3. 1,2,4
Control Theory Basics
1. True
2. True
3. True
4. 4
5. 3
6. False
7. False
8. 2,4
Components of Control Loops and ISA Symbology
1. 1,2,5
2. False
3. 3
4. True
5. 2,3,4
6. 1
7. 1,4
8. 2
9. 4
10. 3
11. 1
12. 2
13. 1
14. 2
15. 3
16. True
17. 4
18. True
19. True
20. 1
21. 3
Page 66 Activity Answers
2006 PAControl.com
Module 7: Activity Answers
Controller Algorithms and Tuning
1. 1,2,3,4
2. False
3. 2
4. False
5. 1
6. 2.5
7. 2,3
8. 3
9. 2,4
10. 2,3
11. 2
12. 4
13. False
14. 3
Process Control Loops
1. 4
2. 3
3. False
4. True
5. 1
6. True
7. 2
8. True
9. False
10. 3
11. 4
12. 1
Activity Answers Page 67
2006 PAControl.com