PGH FC FB Fuer s7cp 76

Download as pdf or txt
Download as pdf or txt
You are on page 1of 191

Preface

Overview and general


information on working with
FCs and FBs

1
FCs / FBs for Industrial
Ethernet

2
FCs / FBs for PROFINET

3
FCs / FBs for PROFIBUS

4
FBs for PROFIBUS FMS

5
SIMATIC NET

Functions (FC) and function blocks
(FB) for SIMATIC NET S7 CPs
Programming Manual
03/2008
C79000-G8976-C229-01




Safety Guidelines
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE
indicates that an unintended result or situation can occur if the corresponding information is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and
operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes
in this documentation qualified persons are defined as persons who are authorized to commission, ground and
label devices, systems and circuits in accordance with established safety practices and standards.
Prescribed Usage
Note the following:
WARNING
This device may only be used for the applications described in the catalog or the technical description and only
in connection with devices or components from other manufacturers which have been approved or
recommended by Siemens. Correct, reliable operation of the product requires proper transport, storage,
positioning and assembly as well as careful operation and maintenance.
Trademarks
All names identified by are registered trademarks of the Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights of the
owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.

Siemens AG
Automation and Drives
Postfach 48 48
90327 NRNBERG
GERMANY
C79000-G8976-C229-01
05/2008
Copyright Siemens AG 2008.
Technical data subject to change

Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 3
Preface
Preface
Target group and motivation
The interface to the communication services is implemented by readymade program blocks
(FCs and FBs). This manual provides you with a full description of the FCs and FBs for
SIMATIC NET S7 CPs. It extends the descriptions in the online help of the configuration
tools for STEP 7.
The manual is intended for programmers of STEP 7 programs and service personnel.
Structure of the manual
The manual is structured according to network types and communications services.
Each function and each function block is described in the following sections:
Meaning
Call interface
Operating principle
Explanation of the formal parameters
Condition codes
These sections may included further specific information.
Scope of this manual
This version of the manual is valid as of version V5.4 SP4 of the STEP 7 / NCM S7
configuration software.
New in this release
This manual groups together the block descriptions that were previously in the manuals for
S7 CPs structured according to network types. These manuals will no longer include the
block descriptions.
Compared with the previously valid versions of the manuals for S7 CPs, this version 1
includes the following innovations in the block descriptions:
In the section on Industrial Ethernet
A new function block FB 40 is available for the FTP client mode of advanced CPs. Using
this FB, complete FTP job sequences can be created efficiently in the user program.
In the section on PROFINET IO
Preface

Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
4 Programming Manual, 03/2008, C79000-G8976-C229-01
Parameter modification in the blocks for PROFINET IO
FC11 PNIO_SEND (block version 2.0)
FC12 PNIO_RECV (block version 2.0)
These two functions must be used for CPs that use PROFINET IO controller and device
mode at the same time.
CP documentation in the Manual Collection (order no. A5E00069051)
The SIMATIC NET Manual Collection DVD ships with each S7 CP. This DVD is regularly
updated and contains the device manuals and descriptions valid at the time it is created.
Information on the current block versions (FCs/FBs)
Always use the latest block versions for new user programs. You will find information on the
current block versions and the current blocks to download from the Internet at Download .
When replacing a CP, follow the instructions in the device-specific part of the device manual
for your S7 CP.
Version history for the blocks (FCs/FBs) and for the SIMATIC NET S7 CPs
The "Version History/Current Downloads for SIMATIC NET S7 CPs" provides information on
all CPs available up to now for SIMATIC S7 (Industrial Ethernet, PROFIBUS, IE/PB Link)
and the blocks (FCs/FBs).
An up-to-date version of this document can be found at:
http://support.automation.siemens.com/WW/view/de/9836605 ()

SIMATIC NET Quick Start CD: Examples relating to communication
The Quick Start CD that can be ordered separately is a treasure-trove of sample programs
and configurations.
You can order this directly over the Internet at:
http://support.automation.siemens.com/WW/view/de/21827955 ()
Additional information on SIMATIC S7 and STEP 7
The additional documentation on the basic software STEP 7 of the SIMATIC automation
system is included in electronic format in your STEP 7 installation.
You will also find information on SIMATIC automation systems on the Quick Start CD and
from the Customer Support Online services at:
http://www.automation.siemens.com/net/index_00.htm ()
(General information on SIMATIC NET)
or
http://support.automation.siemens.com/WW/view/de ()
Preface

Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 5
(Product information and downloads)
See also
http://support.automation.siemens.com/WW/view/de/8797900 ()

Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 7
Table of contents
Preface...................................................................................................................................................... 3
1 Overview and general information on working with FCs and FBs ............................................................ 11
1.1 FCs / FBs for Ind. Ethernet / PROFINET.....................................................................................11
1.2 FCs / FBs for PROFIBUS ............................................................................................................13
1.3 Setting parameters for block / function calls................................................................................15
1.4 Parameters for CP and connection assignment (input parameters)............................................16
1.5 Parameters for specifying a CPU data area (input parameters)..................................................17
1.6 Status information (output parameters) .......................................................................................17
2 FCs / FBs for Industrial Ethernet.............................................................................................................. 19
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)...........................................19
2.1.1 Overview of FCs and their use.....................................................................................................19
2.1.2 FC5 AG_SEND / FC50 AG_LSEND / FC53 AG_SSEND............................................................23
2.1.2.1 Meaning and call - AG_SEND / AG_LSEND / AG_SSEND.........................................................23
2.1.2.2 How AG_SEND / AG_LSEND / AG_SSEND work.......................................................................24
2.1.2.3 Explanation of the formal parameters - AG_SEND / AG_LSEND / AG_SSEND.........................27
2.1.2.4 Condition codes of AG_SEND, AG_LSEND and AG_SSEND ....................................................28
2.1.3 FC6 AG_RECV / FC60 AG_LRECV / FC63 AG_SRECV............................................................30
2.1.3.1 Meaning and call - AG_RECV / AG_LRECV / AG_SRECV.........................................................30
2.1.3.2 How AG_RECV / AG_LRECV / AG_SRECV work.......................................................................31
2.1.3.3 Explanation of the formal parameters - AG_RECV / AG_LRECV / AG_SRECV.........................36
2.1.3.4 Condition codes of AG_RECV, AG_LRECV and AG_SRECV ....................................................37
2.2 FCs for access coordination with FETCH/WRITE.......................................................................40
2.2.1 Overview of FCs and their use.....................................................................................................40
2.2.2 FC7 AG_LOCK ............................................................................................................................42
2.2.2.1 Meaning and call - AG_LOCK......................................................................................................42
2.2.2.2 Explanation of the formal parameters - AG_LOCK......................................................................43
2.2.2.3 Condition codes of AG_LOCK .....................................................................................................43
2.2.3 FC8 AG_UNLOCK.......................................................................................................................44
2.2.3.1 Meaning and call - AG_UNLOCK.................................................................................................44
2.2.3.2 Explanation of the formal parameters - AG_UNLOCK ................................................................44
2.2.3.3 Condition codes of AG_UNLOCK................................................................................................45
2.3 FCs for connection diagnostics....................................................................................................46
2.3.1 FC 10 AG_CNTRL - meaning and call.........................................................................................46
2.3.2 How AG_CNTRL works ...............................................................................................................47
2.3.3 Explanation of the formal parameters - AG_CNTRL....................................................................48
2.3.4 Condition codes of AG_CNTRL ...................................................................................................49
2.3.5 Commands and job results - AG_CNTRL....................................................................................50
2.4 FBs / FCs for FTP services..........................................................................................................55
2.4.1 Overview of FTP ..........................................................................................................................55
2.4.2 FB40 FTP_CMD - universal block for FTP services ....................................................................56
2.4.2.1 Meaning and call - FTP_CMD......................................................................................................56
Table of contents

Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
8 Programming Manual, 03/2008, C79000-G8976-C229-01
2.4.2.2 Input parameter - FTP_CMD....................................................................................................... 58
2.4.2.3 Output parameters and status information - FTP_CMD ............................................................. 61
2.4.2.4 Migration from FC 40-44 to FB40 ............................................................................................... 64
2.4.3 FC40 FTP_CONNECT................................................................................................................ 65
2.4.3.1 Meaning and call - FTP_CONNECT ........................................................................................... 65
2.4.3.2 Explanation of the formal parameters - FTP_CONNECT ........................................................... 65
2.4.4 FC41 FTP_STORE ..................................................................................................................... 67
2.4.4.1 Meaning and call - FTP_STORE................................................................................................. 67
2.4.4.2 Explanation of the formal parameters - FTP_STORE................................................................. 68
2.4.5 FC42 FTP_RETRIEVE................................................................................................................ 69
2.4.5.1 Meaning and call - FTP_RETRIEVE........................................................................................... 69
2.4.5.2 Explanation of the formal parameters - FTP_RETRIEVE........................................................... 70
2.4.6 FC43 FTP_DELETE.................................................................................................................... 71
2.4.6.1 Meaning and call - FTP_DELETE............................................................................................... 71
2.4.6.2 Explanation of the formal parameter - FTP_DELETE................................................................. 71
2.4.7 FC44 FTP_QUIT ......................................................................................................................... 73
2.4.7.1 Meaning and call - FTP_QUIT..................................................................................................... 73
2.4.7.2 Explanation of the formal parameters - FTP_QUIT .................................................................... 73
2.4.8 Parameters for CP and connection assignment (input parameters)........................................... 74
2.4.9 Status information (output parameters) ...................................................................................... 75
2.5 FBs for programmed connections............................................................................................... 78
2.5.1 FB 55 IP_CONFIG - meaning and call ........................................................................................ 78
2.5.2 How IP_CONFIG works .............................................................................................................. 79
2.5.3 Explanation of the formal parameters - IP_CONFIG .................................................................. 80
2.5.4 Reserved port numbers - IP_CONFIG........................................................................................ 81
2.5.5 Condition codes of the IP_CONFIG block................................................................................... 81
2.6 Configuration limits / resources required by the FCs and FBs (Ethernet) .................................. 84
3 FCs / FBs for PROFINET......................................................................................................................... 87
3.1 FBs for PROFINET CBA............................................................................................................. 87
3.1.1 FB88 PN_InOut / FB90 PN_InOut_Fast - meaning and call ....................................................... 87
3.1.2 Explanation of the formal parameters - PN_InOut / PN_InOut_Fast........................................... 89
3.1.3 Condition codes of the PN_InOut and PN_InOut_Fast blocks.................................................... 89
3.1.4 Timedriven PN_InOut / PN_InOut_Fast call - recommendation on application .......................... 92
3.2 FCs/FBs for PROFINET IO (S7-300).......................................................................................... 93
3.2.1 Overview of FCs/FBs and their use ............................................................................................ 93
3.2.2 FC11 PNIO_SEND...................................................................................................................... 94
3.2.2.1 Meaning and call - PNIO_SEND................................................................................................. 94
3.2.2.2 Explanation of the formal parameters - PNIO_SEND................................................................. 95
3.2.2.3 Condition codes of PNIO_SEND................................................................................................. 98
3.2.3 FC12 PNIO_RECV.................................................................................................................... 100
3.2.3.1 Meaning and call - PNIO_RECV............................................................................................... 100
3.2.3.2 Explanation of the formal parameters - PNIO_RECV............................................................... 102
3.2.3.3 Condition codes of PNIO_RECV............................................................................................... 105
3.2.4 General characteristics of the FCs for PROFINET IO.............................................................. 106
3.2.5 Data consistency....................................................................................................................... 107
3.2.6 Substitute values....................................................................................................................... 108
3.2.7 FB52 PNIO_RW_REC............................................................................................................... 109
3.2.7.1 Meaning and call - PNIO_RW_REC.......................................................................................... 109
3.2.7.2 Explanation of the formal parameters - PNIO_RW_REC.......................................................... 110
3.2.7.3 Condition codes of PNIO_RW_REC......................................................................................... 111
3.2.8 FB54 PNIO_ALARM.................................................................................................................. 113
3.2.8.1 Meaning and call - PNIO_ALARM............................................................................................. 113
3.2.8.2 Explanation of the formal parameters - PNIO_ALARM............................................................. 114
Table of contents

Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 9
3.2.8.3 Condition codes of PNIO_ALARM.............................................................................................115
3.2.9 Configuration limits / resources required by the FCs and FBs (PROFINET) ............................117
4 FCs / FBs for PROFIBUS ...................................................................................................................... 119
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface).........................................119
4.1.1 Overview of FCs and their use...................................................................................................119
4.1.2 FC5 AG_SEND / FC50 AG_LSEND..........................................................................................121
4.1.2.1 Meaning and call - AG_SEND / AG_LSEND .............................................................................121
4.1.2.2 How AG_SEND / AG_LSEND work ...........................................................................................124
4.1.2.3 Explanation of the formal parameters - AG_SEND / AG_LSEND .............................................125
4.1.2.4 Condition codes of AG_SEND and AG_LSEND........................................................................126
4.1.3 FC6 AG_RECV / FC60 AG_LRECV ..........................................................................................128
4.1.3.1 Meaning and call - AG_RECV / AG_LRECV .............................................................................128
4.1.3.2 How AG_RECV / AG_LRECV work ...........................................................................................130
4.1.3.3 Explanation of the formal parameters - AG_RECV / AG_LRECV .............................................131
4.1.3.4 Condition codes of AG_RECV and AG_LRECV........................................................................132
4.2 FCs for DP (distributed I/O) with S7-300 ...................................................................................134
4.2.1 Overview of FCs and their use...................................................................................................134
4.2.2 FC1 DP_SEND...........................................................................................................................135
4.2.2.1 Meaning and call - DP_SEND....................................................................................................135
4.2.2.2 How DP_SEND works................................................................................................................136
4.2.2.3 Explanation of the formal parameters - DP_SEND....................................................................137
4.2.2.4 Condition codes of the DP_SEND block....................................................................................138
4.2.3 FC2 DP_RECV ..........................................................................................................................139
4.2.3.1 Meaning and call - DP_RECV....................................................................................................139
4.2.3.2 How DP_RECV works................................................................................................................141
4.2.3.3 Explanation of the formal parameters - DP_RECV....................................................................142
4.2.3.4 Condition codes of the DP_RECV block....................................................................................143
4.2.3.5 DPSTATUS - DP_RECV............................................................................................................144
4.2.4 FC3 DP_DIAG............................................................................................................................146
4.2.4.1 Meaning and call - DP_DIAG.....................................................................................................146
4.2.4.2 How DP_DIAG works.................................................................................................................147
4.2.4.3 Explanation of the formal parameters - DP_DIAG.....................................................................148
4.2.4.4 Job types - DP_DIAG.................................................................................................................149
4.2.4.5 Ring buffer for diagnostics data - DP_DIAG..............................................................................151
4.2.4.6 Condition codes of DP_DIAG.....................................................................................................151
4.2.5 FC4 DP_CTRL...........................................................................................................................154
4.2.5.1 Meaning and call - DP_CTRL ....................................................................................................154
4.2.5.2 How DP_CTRL works ................................................................................................................156
4.2.5.3 Explanation of the formal parameters - DP_CTRL ....................................................................157
4.2.5.4 Job types - DP_CTRL ................................................................................................................158
4.2.5.5 Command mode and group select - DP_CTRL .........................................................................161
4.2.5.6 Condition codes of the DP_CTRL block ....................................................................................162
4.3 Configuration limits / resources required by the FCs and FBs (PROFIBUS) ............................165
5 FBs for PROFIBUS FMS ....................................................................................................................... 167
5.1 Overview of FBs and their use...................................................................................................167
5.2 FMS block parameters...............................................................................................................168
5.3 FB2 IDENTIFY...........................................................................................................................172
5.3.1 Meaning and call - IDENTIFY....................................................................................................172
5.3.2 How IDENTIFY works................................................................................................................173
5.4 FB3 READ..................................................................................................................................174
5.4.1 Meaning and call - READ...........................................................................................................174
Table of contents

Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
10 Programming Manual, 03/2008, C79000-G8976-C229-01
5.4.2 How READ works...................................................................................................................... 175
5.5 FB4 REPORT............................................................................................................................ 177
5.5.1 Meaning and call - REPORT..................................................................................................... 177
5.5.2 How REPORT works................................................................................................................. 178
5.6 FB5 STATUS ............................................................................................................................ 179
5.6.1 Meaning and call - STATUS...................................................................................................... 179
5.6.2 How STATUS works ................................................................................................................. 181
5.7 FB6 WRITE............................................................................................................................... 182
5.7.1 Meaning and call - WRITE........................................................................................................ 182
5.7.2 How WRITE works.................................................................................................................... 183
5.8 Condition codes and error messages - FMS blocks ................................................................. 185
5.8.1 Error detected locally ................................................................................................................ 186
5.8.2 Errors detected by FMS partner................................................................................................ 188
5.9 Quantity framework / resource requirements of FBs (PROFIBUS FMS).................................. 190


Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 11
Overview and general information on working with
FCs and FBs
1
1.1 FCs / FBs for Ind. Ethernet / PROFINET
How supplied - block library
The SIMATIC NET FCs (functions) and FBs (function blocks) are supplied with the STEP 7
basic package unless indicated otherwise.
The following list shows the block numbers as they are supplied. You can change these
block numbers.
Under SIMATIC_NET_CP, you can also see which folders contain blocks. Please note that
you must use different FCs/FBs for the S7300 and S7400 (separate libraries).

SIMATIC Manager Library
SIMATIC_NET_CP
Communication service / functional
area
Block type
CP 300 CP 400
FC5 AG_SEND x x
FC50 AG_LSEND x
2)
x
FC53 AG_SSEND x
3)

FC6 AG_RECV x x
FC60 AG_LRECV x
2)
x
FC63 AG_SRECV x
3)

FC7 AG_LOCK x x
FC8 AG_UNLOCK x x
SEND / RECEIVE
(S5compatible communication)
FC10 AG_CNTRL x
3)
x
3)

Programmed communication
connections
FB55 IP_CONFIG x x
FB12 BSEND x
FB13 BRCV x
FB15 PUT x
FB14 GET x
FB8 USEND x
FB9 URCV x
S7 communication
4)

FC62 C_CNTRL x
FB40 FTP_CMD x x FTP (advanced CPs)
FC40 FTP_CONNECT x x
Overview and general information on working with FCs and FBs
1.1 FCs / FBs for Ind. Ethernet / PROFINET
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
12 Programming Manual, 03/2008, C79000-G8976-C229-01
SIMATIC Manager Library
FC41 FTP_STORE x x
FC42 FTP_RETRIEVE x x
FC43 FTP_DELETE x x
FC44 FTP_QUIT x x
FB88
1)
PN_InOut
1)
x
1)
x
1)
PROFINET CBA
FB90
1)
PN_InOut_Fast
1)
x
1)

FC11 PNIO_SEND x
FC12 PNIO_RECV x
FB52 PNIO_RW_REC x
PROFINET IO
FB54 PNIO_ALARM x
Legend:
1) FB88 / FB90 is supplied along with the engineering tool SIMATIC iMap and is entered in the PROFINET system library
when you install the STEP 7 addon.
2) Not to be used with the current CPs and not part of the current SIMATIC_NET_CP library.
3) depending on the CP type
4) Described in the STEP 7 documentation
Which block version should I use?
The following descriptions also include information on differences in behavior between the
various block versions. Please check and note the version identifiers of the blocks you are
using.
The SIMATIC Manager block libraries installed with STEP 7 / NCM S7 contain the block
versions that were current at the time of the STEP 7 release.

Note
We recommend that you always use the latest block versions for all module types.
You will find information on the current block versions and the current blocks to download
from the Internet in Customer Support:
http://support.automation.siemens.com/WW/view/en/8797900 ()
This recommendation assumes that you are using the latest firmware for the particular
module type.

FCs when modules are replaced
Module replacement means the replacement of a module with another module that may be a
more recent version.
Overview and general information on working with FCs and FBs
1.2 FCs / FBs for PROFIBUS
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 13

NOTICE
Please remember that if you replace a module, you must only use the blocks permitted for
the configured CP type in the user program.
This means:
If you replace the module without adapting the configuration data to the possibly newer
module type, you do not need to make any changes to the blocks used.
If you replace the module and you do adapt the configuration data to the newer module
type, make sure you use the block versions approved for this module type.
We recommend that you always use the latest block versions for all module types.
This recommendation assumes that you are using the latest firmware for the particular
module type.

The specific device manuals contain information on the compatibility of the S7-CPs and the
corresponding blocks (FCs / FBs).
1.2 FCs / FBs for PROFIBUS
How supplied - block library
The SIMATIC NET FCs (functions) and FBs (function blocks) are supplied with the STEP 7
basic package unless indicated otherwise.
The following list shows the block numbers as they are supplied. You can change these
block numbers.
Under SIMATIC_NET_CP, you can also see which folders contain blocks. Please note that
you must use different FCs/FBs for the S7300 and S7400 (separate libraries).

SIMATIC Manager Library
SIMATIC_NET_CP
Communication service / functional
area
Block type
CP 300 CP 400
FC1 DP_SEND x
FC2 DP_RECV x
FC3 DP_DIAG x
PROFIBUS DP
FC4 DP_CTRL x
FC5 AG_SEND x x
FC50 AG_LSEND x
2)

FC6 AG_RECV x x
SEND / RECEIVE
(S5compatible communication)
FC60 AG_LRECV x
2)

FB12 BSEND x
1)

FB13 BRCV x
1)

FB15 PUT x
1)

S7 communication
1)

FB14 GET x
1)

Overview and general information on working with FCs and FBs
1.2 FCs / FBs for PROFIBUS
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
14 Programming Manual, 03/2008, C79000-G8976-C229-01
SIMATIC Manager Library
FB8 USEND x
1)

FB9 URCV x
1)

FC62 C_CNTRL x
1)

FB2 IDENTIFY x x
FB3 READ x x
FB4 REPORT x x
FB5 STATUS x x
PROFIBUS FMS
FB6 WRITE x x
1) as described in the STEP 7 documentation. As with S7-400 any SFBs that can be used are available in the System
Function Library.


2) Can be used but has no special function with PROFIBUS.

Which block version should I use?
The following descriptions also include information on differences in behavior between the
various block versions. Please check and note the version identifiers of the blocks you are
using.
The SIMATIC Manager block libraries installed with STEP 7 / NCM S7 contain the block
versions that were current at the time of the STEP 7 release.

Note
We recommend that you always use the latest block versions for all module types.
You will find information on the current block versions and the current blocks to download
from the Internet in Customer Support:
http://support.automation.siemens.com/WW/view/en/8797900 ()
This recommendation assumes that you are using the latest firmware for the particular
module type.

FCs / FBs and module replacement
Module replacement means the replacement of a module with another module that may be a
more recent version.
Overview and general information on working with FCs and FBs
1.3 Setting parameters for block / function calls
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 15

NOTICE
Please remember that if you replace a module, you must only use the blocks permitted for
the configured CP type in the user program.
This means:
If you replace the module without adapting the configuration data to the possibly newer
module type, you do not need to make any changes to the blocks used.
If you replace the module and you do adapt the configuration data to the newer module
type, make sure you use the block versions approved for this module type.
We recommend that you always use the latest block versions for all module types.
This recommendation assumes that you are using the latest firmware for the particular
module type.

The manuals contain information on the compatibility of the S7-CPs and the corresponding
blocks (FCs / FBs).
1.3 Setting parameters for block / function calls
Before describing the blocks / FCs in detail, a few general comments on calling and setting
parameters for FCs will be useful at this point.
The general information below applies to the following parameter groups that exist for all
FCs / FBs:
Parameters for CP and connection assignment (input parameters)
Parameters for specifying a CPU data area (input parameters)
Status information (output parameters)
Calling communication blocks for an S7300
CAUTION
The communication blocks for S7-300 (SIMATIC NET block libraries for S7300 in STEP 7)
must not be called in more than one priority class! If, for example, you call a communication
block in OB1 and in OB35, block execution could be interrupted by the higherpriority OB.
If you call blocks in more than one OB, you must write your program so that a
communication block that is currently executing cannot be interrupted by another
communication block (for example by disabling/enabling SFC interrupts).

Overview and general information on working with FCs and FBs
1.4 Parameters for CP and connection assignment (input parameters)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
16 Programming Manual, 03/2008, C79000-G8976-C229-01
1.4 Parameters for CP and connection assignment (input parameters)
When you call an FC, you transfer the module start address of the S7 CP in the CPLADDR
or LADDR parameter. The module start address of the S7 CP can be found in the properties
dialog of the CP in the "Address/Input" tab (can be selected in the SIMATIC Manager or in
HW Config).
With connectionoriented jobs, you must also reference the connection to be used by its
connection ID. You will find this in the properties dialog of the connection under "Block
parameters" (refer to the information in NetPro).
Setting block parameters automatically
To ensure correct parameter settings for the block calls, The LAD/STL/FBD editor in STEP 7
provides you with the option of accepting all the relevant parameters automatically from the
hardware configuration (HW Config) and from the connection configuration (NetPro).
When assigning the parameters for the block in the user program, follow the steps outlined
below:
1. Select the block call and its block parameters;
2. Rightclick and select the menu command "Connections...".
3. Depending on the block type, you can now select the connection and/or module intended
for the block from a list.
4. Confirm your selection; as far as possible, the available parameter values are entered in
the block call.
Response to incorrect addresses
If the S7CPU cannot communicate with the PROFIBUS CP using the specified module start
address or cannot identify it as a CP, the errors described below result.

Cause Reaction / code
No module can be addressed or
identified at the specified CP
address.
The CPU remains in STOP with system error state; in this case,
evaluate the diagnostic buffer of the CPU.
The CP address points to a
different module type.
Possible error code in the STATUS parameter of the
communication block:
8184H System error
80B0H The module does not recognize the data record.
80C0H The data record cannot be read.
80C3H Resources (memory) occupied.
80D2H Logical base address is wrong.


NOTICE
If you inadvertently address not a CP but another module type, errors occur that cannot be
indicated by the error messages of the FCs/FBs themselves.

Overview and general information on working with FCs and FBs
1.5 Parameters for specifying a CPU data area (input parameters)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 17
1.5 Parameters for specifying a CPU data area (input parameters)
Specifying the data area on the CPU
When you call an FC, you transfer the address and length of the data area on the CPU in
which the user data is available or will be stored or which can contain further parameter
information.
The ANY pointer data type is used to address this area. For more detailed information on
this data type, refer to the STEP 7 online help under the appendix topic "Format of the
parameter type ANY".
1.6 Status information (output parameters)
Evaluating status codes
For status evaluation, the following parameters must be evaluated in the user program:
DONE or NDR
These parameters (DONE with send jobs and NDR with receive jobs) signal (successful)
completion of the job.
ERROR
This indicates that the job could not be executed errorfree.
STATUS
This parameter supplies detailed information about the execution of the job. Status codes
can be returned during execution of the job (DONE=0 and ERROR=0).



Note
Remember that the status codes DONE, NDR, ERROR, STATUS are updated at each
block call.
Status codes during CP startup
With a complete restart or restart of the Ethernet CP (for example after activating a switch on
the module), the output parameters of the FC are reset as follows:
DONE = 0
NDR = 0
ERROR = 0
STATUS =
8180H for AG_RECV / AG_LRECV
8181 H for AG_SRECV
8181H for AG_SEND /AG_LSEND / AG_SSEND

Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 19
FCs / FBs for Industrial Ethernet
2
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
2.1.1 Overview of FCs and their use
Overview
The following FCs are available for transferring data on the SEND/RECEIVE interface:

Can be used with
1)
FC
S7-300 S7-400
Meaning
AG_SEND (FC5) x x for sending data
AG_RECV (FC6) x x for receiving data
AG_LSEND (FC50) x for sending data
AG_LRECV (FC60) x for receiving data
AG_SSEND (FC 53) x for sending data
AG_SRECV (FC 63) x for receiving data
1) Notes on the FCs for an S7300 and S7400
S7300:
With the latest versions of the Ethernet CPs, only FCs AG_SEND and AG_RECV are
used; data with a length of up to 8192 bytes can be transferred.
With S7300 CPs (up to 6GK7 3431EX100XE0 with firmware version V2.2), use
FC60 on TCP connections instead of FC6. For the CP 343-1 (EX10), you can use
FC5/FC6 up to block version V3.0.
S7400:
With FCs AG_SEND / AG_RECV, the data length per job is restricted to <=240 bytes.
Longer data records (up to 8192 bytes) can be transferred with FCs AG_LSEND or
AG_LRECV.
The FCs AG_SSEND and AG_SRECV are for accelerated transfer of data by using
optimized block communication between CPU and CP in the S7 station. The fast
communication has no effect on LAN communication. These two blocks are supported
as of STEP 7 V5.4 SP3.
On an S7400, FC6 cannot be used on TCP connections but only FC60 or FC63.
FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
20 Programming Manual, 03/2008, C79000-G8976-C229-01
Further information
Please check the supported data area for the S7CP you are using in the manual for the
specific device. You will find an overview of the versions of the FCs/FBs in the SIMATIC NET
block history.
Application
The following diagram illustrates the use of the FCs described here for bidirectional data
transfer on one configured connection.
AG_RECV
Ethernet-CP CPU
AG_SEND AG_RECV
AG_SEND
Ethernet-CP CPU
STEP 7
user
program
User
data areas
send
receive
Connection
STEP 7
user
program
User
data areas
receive
send




Note
Unless specifically stated otherwise, the information on this and the following pages refers to
the AG_SEND / AG_LSEND / AG_SSEND or AG_RECV / AG_LRECV / AG_SRECV blocks.

Sample programs
Please note that the following sample programs are also available on the Internet.
Sample program for the Send-Receive interface with the blocks FC5 (AG_SEND) and
FC6 (AG_RECV) for S7-300:
http://support.automation.siemens.com/WW/view/en/17853532 ()
Sample program for the Send-Receive interface with the functions FC50 (AG_LSEND)
and FC60 (AG_LRECV) for S7-400:
http://support.automation.siemens.com/WW/view/en/18513371 ()
FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 21
Specifying the data area on the CPU
When you call an FC, you transfer the address and length of the data area in the CPU.
Remember, that the maximum length of the data area depends on the block type and block
version being used.
AG_SEND and AG_RECV
Up to version V3.0 of these blocks, a maximum of 240 bytes can be sent or received. The
current block versions allow a data area of up to 8192 bytes for an S7300. With an S7-
400, the FCs AG_LSEND / AG_LRECV must still be used for larger data areas.
AG_LSEND / AG_LRECV
Using the CPs of the S7400 and with earlier versions of the S7300, larger data areas can
only be transferred with the FCs AG_LSEND or AG_LRECV. Please check the length of
the data area in the product information of the CP.
AG_SSEND / AG_SRECV
With CPs of the S7400 that support PROFINET communication in conjunction with
CPUs as of version 5.1, data can be transferred at higher transmission speeds with the
FCs AG_SSEND or AG_SRECV (does not apply to the CP 4431 Advanced 6GK7 443
1EX410XE0).
You can check which CP types are supported by CPUs as of version 5.1 in the manual of
your CP (Section "Requirements for use").
The following table shows the limit values of the various connection types.

FC ISO transport ISO-on-TCP TCP UDP
AG_LSEND (S7-400)
AG_SEND (S7-300)
8192 bytes 8192 bytes 8192 bytes 2048 bytes
AG_SEND (S7-400) 240 bytes 240 bytes 240 bytes 240 bytes
AG_LRECV (S7-400)
AG_RECV (S7-300)
8192 bytes 8192 bytes 8192 bytes 2048 bytes
AG_RECV (S7-400) 240 bytes 240 bytes 240 bytes 240 bytes
AG_SSEND (S7-400)
AG_SRECV (S7-400)
1452 bytes 1452 bytes 1452 bytes 1452 bytes


Note
For information on the length of the data area you can transfer with older versions of the
Ethernet CPs, refer to the product information bulletin / manual of the Ethernet CP you are
using.

Use without job header
On specified connections, the address and job parameters are specified by the connection
configuration. The user program only provides the user data in the UDP data area when
sending with AG_SEND / AG_LSEND / AG_SSEND or receives the data with AG_RECV /
AG_LRECV / AG_SRECV.
FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
22 Programming Manual, 03/2008, C79000-G8976-C229-01
Use with header
Free UDP connections require a job header in the user data area.
The following schematic illustrates the structure of the job buffer and the meaning and
location (high byte / low byte) of the parameters in the job header.
Port 03H (High Byte)
0BH 8EH
23H
EBH (Low Byte)
28H
Byte 0, 1
Byte 2046, 2047
Byte 6, 7
Byte 4, 5
Byte 2, 3
Data byte 1
Data byte 2040
Data byte 0
Data byte 2041
Job header
User data area
Job buffer
User data
lP address

Figure 2-1 Sending and receiving on a free UDP connection with programmed addresses

In the diagram (entries in hexadecimal) the following IP address is assumed as an
example: 142.11.40.35;
For the port address 1003, the following would be entered: For high byte: 03H; For low
byte: EBH.
The user data area can be up to 2048 bytes. Up to 2042 bytes of user data can be
transferred. 6 bytes are reserved for the job header.
Please note that the data length specified in the block call (LEN parameter) must include
the header and the user data!
Change call parameters only after job confirmation
NOTICE
Once the job has been triggered, you can only change the call parameters of the FC call
interface of the FCs AG_SEND or AG_RECV after the FC has confirmed completion of the
job with DONE=1 or with ERROR=1.
If you do not keep to this rule, it is possible that the job will be aborted with an error.

Status display on the FC call interface; Special case with FC versions (only for S7-300) *)
With the FCs AG_SEND (FC5) and AG_RECV (FC6), you will receive the codes shown
below in the following situations:
CP is in STOP;
Connection is not configured;
Connection is not established
FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 23
Connection is aborted;
Codes:
AG_SEND:
DONE=0; ERROR=1; Status=8183H
AG_RECV:
DONE=0; ERROR=0; Status=8180H
or
DONE=0; ERROR=1; Status=8183H
*) applies to FCs as of version 4.0
2.1.2 FC5 AG_SEND / FC50 AG_LSEND / FC53 AG_SSEND
2.1.2.1 Meaning and call - AG_SEND / AG_LSEND / AG_SSEND
Meaning of the block
The FCs AG_SEND / AG_LSEND / AG_SSEND pass data to the Ethernet CP for transfer
over a configured connection.
The selected data area can be a memory bit area or a data block area.
Errorfree execution of the function is indicated when the entire user data area could be sent
over Ethernet.
The way in which the FC functions depends on the CP type you are using. Please note the
differences in the following section.
Note:
Unless otherwise stated, all the following information applies equally to the FCs AG_SEND,
AG_LSEND and AG_SSEND.
Call interface
Call interface in FBD representation
AG_SEND / AG_LSEND / AG_SSEND
BOOL
ANY
BOOL
BOOL
WORD
lNT
WORD
lNT
ACT
LEN
STATUS
ERROR
DONE
SEND
LADDR
lD


Example in STL representation

FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
24 Programming Manual, 03/2008, C79000-G8976-C229-01
STL Explanation
call fc 5(
ACT:=M 10.0,
ID:=MW 12,
LADDR:=W#16#0100,
SEND := P#db99.dbx10.0 byte 240,
LEN:=MW 14,
DONE:=M 10.1,
ERROR:=M 10.2,
STATUS:=MW 16 );
//Block call
//Job triggered by memory bit
//Connection ID acc. to configuration
//=LADDR 256 dec. in HW Config
//Buffer with send data
//Length for send data
//Execution code
//Error code
//Status code


Note
If you want to use FC53 AG_SSEND, you will need to select the "SPEED SEND/RECV"
mode in the connection properties during configuration of the connection.

2.1.2.2 How AG_SEND / AG_LSEND / AG_SSEND work
Operating principle
The following diagrams illustrate the normal sequence of data transmission triggered in the
user program using AG_SEND.
The way in which the FC functions depends on the CP type you are using.
Case 1: Sequence with FC5, FC50, FC53 in S7-400 CPs
In the S7400, the transfer of the entire data area regardless of its length is handled by
the CP after the first block call.
Case 2: Sequence with FC5 in S7300 CPs
In the S7-300, the transfer takes place several data segments (each with 240 bytes of
user data) and requires several FC calls to transfer the entire data.
FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 25
Case 1: Sequence with FC5, FC50, FC53 in S7400 CPs
The send job is executed as soon as the parameter ACT = 1 is passed.
Following this, the parameter ACT = 0 must be passed in at least one further call.
The status code in the output parameters DONE, ERROR and STATUS is updated in each
block call and can be evaluated. To update the status code without starting a new send job,
start a new block call with the parameter ACT = 0.
AG_SEND
AG_SEND
AG_SEND
Ethernet-CP
Job active 1)
Time
Supply AG_SEND
ACT = 0
Supply AG_SEND with
data 'X'
ACT = 1
User program
(CPU cycle)
The communication partner
Job active 1)
Job completed without errors 1)
Time Time
Transfer of 'X'
via Ethernet active
1) Parameter transfer DONE, ERROR, STATUS


FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
26 Programming Manual, 03/2008, C79000-G8976-C229-01
Case 2: Sequence with FC5 in S7300 CPs
The send job is started as soon as the parameter ACT = 1 is passed.
In contrast to case 1, the protocol used here to transfer the data segments (each 240 bytes
of user data) requires the FC to be called again for each segment.
Depending on the length of the user data, you must therefore continue to call the FC with
ACT=0 until transfer of the entire data record is indicated; at least one further call is
necessary. The data is transferred to the communication partner in segments of 240 bytes.
The status code in the output parameters DONE, ERROR and STATUS is updated in each
block call and can be evaluated.
AG_SEND
AG_SEND
AG_SEND
Ethernet-CP
Job active 1)
Time
Supply AG_SEND
ACT = 0
Supply AG_SEND with
data 'X'
ACT = 1
User program
(CPU cycle)
The communication partner
Job active 1)
Job completed without errors 1)
Time Time
Accept block 1
in send buffer
Accept block 2
in send buffer
Accept block n
in send buffer
Transfer
via Ethernet active
Data record X is
transferred.
AG_SEND
Job active 1)
1) Parameter transfer DONE, ERROR, STATUS



Note
In principle, it is possible to call the FC more than once within the CPU cycle to speed up the
handling of the job. Do not forget, however, that this increases the load during the CPU cycle
(the load differs depending on the CPU type)!

FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 27
2.1.2.3 Explanation of the formal parameters - AG_SEND / AG_LSEND / AG_SSEND
Explanation of the formal parameters
The following table explains all the formal parameters for the
AG_SEND / AG_LSEND / AG_SSEND functions:

Parameter Declaration Data type Possible values Description
ACT INPUT BOOL 0,1 If an FC is called with ACT=1, LEN bytes are sent from
the ISO transport data area specified with the SEND
parameter.
If an FC is called with ACT = 0, the status codes DONE,
ERROR and STATUS are updated.
ID INPUT INT 1,2...64
(S7-400)
1,2...16
(S7-300)
The connection number of the connection is specified in
the parameter ID.
LADDR INPUT WORD Module start address
When you configure the CP with STEP 7 HW Config,
the module start address is displayed in the
configuration table. Specify this address here.
SEND INPUT ANY Specifies the address and length
The address of the data area points to one of the
alternatives:
Memory bit area
Data block area
LEN INPUT INT On ISO transport and
ISOonTCP / TCP:
1,2,...8192 (or up to
"length specified for
SEND parameter")

On UDP:
1,2,...2048 (or up to
"length specified for
SEND parameter")
Number of bytes to be sent from the data area with this
job. The possible values range from 1 to length
specified for the SEND parameter.
Note the block type:
For S7-300
The current versions of FC AG_SEND allow up
to 8192 bytes (2048 bytes for UDP) to be
transferred.
For S7-400
With FC AG_SEND, the data area is restricted to
a maximum of 240 bytes.

Note the following with an S7-400:
Improved performance with shorter data records:
Transfer of data records up to 240 bytes results in
better performance! This applies regardless of the
block type used (AG_SEND/AG_LSEND).
With AG_SSEND, the data area is restricted to a
maximum of 1452 bytes.
DONE OUTPUT BOOL 0: Job active
1: Job done
The status parameter indicates whether or not the job
was completed without errors.
As long as DONE = 0, no further job can be triggered.
DONE is set to 0 by the CP when it accepts a new job.
For the meaning in conjunction with the ERROR and
STATUS parameters, refer to the following table.
FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
28 Programming Manual, 03/2008, C79000-G8976-C229-01
Parameter Declaration Data type Possible values Description
ERROR OUTPUT BOOL 0: -
1: Error
Error code
For the meaning in conjunction with the DONE and
STATUS parameters, refer to the follow table.
STATUS OUTPUT WORD See following table Status code
The following table shows the condition codes formed
by the DONE and ERROR parameters.

2.1.2.4 Condition codes of AG_SEND, AG_LSEND and AG_SSEND
Condition codes
The following table shows the condition codes formed based on DONE, ERROR and
STATUS that must be evaluated by the user program.

Note
For entries coded with 8FxxH in STATUS, refer to the information in the STEP 7 Standard
and System Functions reference manual. The chapter describing error evaluation with the
RET_VAL output parameter contains detailed information.
To find out which SFCs are used and are relevant for error evaluation, display the properties
dialog of the FC described here in the "Calls" tab.



DONE ERROR STATUS Meaning
1 0 0000H Job completed without error.
0 0 0000H No job being executed.
0 0 8181H Job active.
0 1 7000H The condition code is possible only with S7-400: The FC was called with ACT=0; the
job has not yet been processed.
0 1 8183H No configuration or the ISO/TCP service has not yet started on the Ethernet CP.
0 1 8184H Illegal data type specified for the SEND parameter.
System error (the source data area is incorrect).
0 1 8185H LEN parameter longer than SEND source area.
0 1 8186H ID parameter invalid.
ID != 1,2....16 (S7-300).
ID != 1,2....64.(S7-400)
0 1 8302H No receive resources on the destination station; the receiving station cannot process
received data quickly enough or has not prepared any receive resources.
0 1 8304H The connection is not established. The send job should only be attempted again after
waiting for at least 100 ms.
0 1 8311H The destination station cannot be obtained under the specified Ethernet address.
0 1 8312H Ethernet error on the CP.
FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 29
DONE ERROR STATUS Meaning
0 1 8F22H Source area invalid, e.g.:
Area does not exist in the DB
LEN parameter < 0
0 1 8F24H Area error reading a parameter.
0 1 8F28H Alignment error reading a parameter.
0 1 8F32H Parameter contains a DB number that is too high.
0 1 8F33H DB number error.
0 1 8F3AH Area not loaded (DB).
0 1 8F42H Timeout reading a parameter from the
I/O area.
0 1 8F44H Access to a parameter to be read during block execution is prevented.
0 1 8F7FH Internal error, e.g. illegal ANY reference
e.g. parameter LEN=0
0 1 8090H Module with this module start address does not exist;
The FC being used does not match the system family being used (remember to use
different FCs for S7300 and S7400).
0 1 8091H Module start address not at a doubleword boundary.
0 1 8092H In the ANY reference, a type other than BYTE is specified.
(S7-400 only)
0 1 80A4H The communication bus connection between the CPU and CP is not established.
(With newer CPU versions)
0 1 80B0H The module does not recognize the data record.
0 1 80B1H The specified length (in the LEN parameter) is incorrect.
0 1 80B2H The communication bus connection between the CPU and CP is not established.
0 1 80C0H The data record cannot be read.
0 1 80C1H The specified data record is currently being processed.
0 1 80C2H There are too many jobs pending.
0 1 80C3H CPU resources (memory) occupied.
0 1 80C4H Communication error (occurs temporarily and a repetition in the user program will often
remedy the problem).
0 1 80D2H Module start address incorrect.

FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
30 Programming Manual, 03/2008, C79000-G8976-C229-01
2.1.3 FC6 AG_RECV / FC60 AG_LRECV / FC63 AG_SRECV
2.1.3.1 Meaning and call - AG_RECV / AG_LRECV / AG_SRECV
Meaning of the block
The AG_RECV / AG_LRECV / AG_SRECV function receives the data transferred on a
configured connection from the Ethernet CP.
The data area specified for the receive data can be a memory bit area or a data block area.
Errorfree execution is indicated when the data could be received from the Ethernet CP.
Note:
Unless otherwise stated, all the following information applies to both the FCs AG_RECV and
AG_LRECV / AG_SRECV.
Call
Call interface in FBD representation
AG_RECV / AG_LRECV / AG_SRECV
ANY
BOOL
BOOL
WORD
lNT
WORD
lNT LEN
STATUS
ERROR
NDR
RECV
LADDR
lD


Example in STL representation

STL Explanation
call fc 6(
ID:=MW 40,
LADDR:=W#16#0100,
RECV:=P#M 0.0 BYTE 100,
NDR:=DB 110.DBX 0.6,
ERROR:=DB 110.DBX 0.7,
STATUS:=DB 110.DBW 2,
LEN:=DB 110.DBW 4 );
//Block call
//Connection ID acc. to configuration
//=LADDR 256 dec. in HW Config
//Buffer for received data
//Receive code
//Error code
//Status code
//Received data length


Note
If you want to use FC63 AG_SRECV, you will need to select the "SPEED SEND/RECV"
mode in the connection properties during configuration of the connection.

FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 31
2.1.3.2 How AG_RECV / AG_LRECV / AG_SRECV work
Operating principle
The following diagram illustrates the normal sequence of data acceptance triggered by an
AG_RECV in the user program.
Each AG_RECV job in the user program is acknowledged by the Ethernet CP with an entry
in the output parameters NDR, ERROR and STATUS.
The way in which the FC functions depends on the CP type you are using and the
connection types.
Case 1: Sequence with FC6 in S7-300 CPs
With the newer CP types, optimized data transfer on the SEND/RECEIVE interface is
available. In particular with longer data records, this allows a much higher data
throughput on the interface between the CPU and CP.
Case 2: Sequence with FC6 and FC60 in S7-400 CPs
With FC6 / FC60 AG_RECV, the response on the S7-400 depends on the protocol used.
Case 2a: Sequence with ISO transport, ISO-on-TCP, UDP connections
Wit these connection types, the transfer is handled by the CP with one or more FC6
/FC60 calls depending on the length of the data area.
Case 2b: Sequence with TCP connections
On a TCP connection, the length specified in the ANY pointer of the RECV parameter
is the deciding factor. An FC6 /FC60 job is completed with the condition code NDR=1,
as soon as an amount of data corresponding to the specified length has been written
to the receive buffer.
Case 3: Sequence with FC63 in S7-400 CPs
With FC63 AG_SRECV, the response on the S7-400 depends on the protocol used.
Case 3a: Sequence with ISO transport, ISO-on-TCP, UDP connections
With these connection types, the transfer of the entire data area regardless of its
length is started by the CP after the first block call.
Case 3b: Sequence with TCP connections
On a TCP connection, the data on the CP is accepted up to the maximum specified
job length with every call.
The call must be repeated until a data record has been entered completely and
consistently in the receive buffer. The reception of the completed data record is
indicated in one of the later FC calls with the parameter NDR=1.
FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
32 Programming Manual, 03/2008, C79000-G8976-C229-01
Case 1: Sequence with FC6 in S7-300 CPs
When FC6 is called, the user program prepares the buffer to receive data and instructs the
CP to enter the received data there.
The protocol used here to transfer the data to the receive buffer requires the FC to be called
again for each segment (240 bytes of user data).
Depending on the length of the user data, the FC must be called repeatedly until the
complete transfer is indicated by parameter NDR=1.
The status code in the output parameters NDR, ERROR and STATUS is updated in each
block call and can be evaluated.
AG_RECV
AG_RECV
AG_RECV
AG_RECV
AG_RECV
AG_RECV
User program
(CPU cycle)
1) Parameter transfer NDR, ERROR, STATUS
Ethernet CP
Job completed without errors 1)
Time
Accept / evaluate
received data 'A'
Accept / evaluate
received data 'B'
The communication partner
Time Time
Transfer of 'A' (e.g.
520 bytes) via
Ethernet active
Transfer of 'B' (e.g. 240
bytes) via Ethernet
active
Transfer of 'C'
via Ethernet active
Job completed without errors 1)
There is not yet any data available 1)
There is not yet any data available 1)
There is not yet any data available 1)


FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 33
Case 2a: Sequence with FC6 and FC60 in S7-400 CPs (with ISO transport, ISO-on-TCP, UDP
connections)
When the FC is called, the user program prepares the buffer to receive data and instructs
the CP to enter all available data there.
As soon as a data record has been entered fully and consistently in the receive buffer, this is
indicated by the parameter NDR=1 in one of the next FC calls.
The status code in the output parameters NDR, ERROR and STATUS is updated in each
block call and can be evaluated.
AG_RECV
AG_RECV
AG_RECV
Ethernet-CP
Job completed without errors 1)
Time
Accept / evaluate
received
data 'A'
Accept / evaluate
received
data 'B'
User program
(CPU cycle)
The communication partner
Time Time
Transfer of 'A'
via Ethernet active
Transfer of 'B'
via Ethernet active
Transfer of 'C'
via Ethernet active
AG_RECV
Job completed without errors 1)
AG_RECV
There is not yet any data available 1)
There is not yet any data available 1)
1) Parameter transfer DONE, ERROR, STATUS


FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
34 Programming Manual, 03/2008, C79000-G8976-C229-01
Case 2b: Sequence with FC6 / FC60 in S7-400 CPs (only for TCP connections)
On a TCP connection, the length specified in the ANY pointer of the RECV parameter is the
deciding factor. An FC6 /FC60 job is completed with the condition code NDR=1, as soon as
an amount of data corresponding to the specified length has been written to the receive
buffer.
The sequence example shows a situation in which the length in the ANY pointer was set to
400 bytes for an FC60.
AG_RECV
AG_RECV
AG_RECV
AG_RECV
AG_RECV
AG_RECV
User program
(CPU cycle)
1) Parameter transfer NDR, ERROR, STATUS
Ethernet CP
Job completed without errors 1)
Time
Accept / evaluate
received data 'A'
Accept / evaluate
received data 'B'
The communication partner
Time Time
Transfer of 'A' (e.g.
520 bytes) via
Ethernet active
Transfer of 'B' (e.g. 240
bytes) via Ethernet
active
Transfer of 'C'
via Ethernet active
Job completed without errors 1)
There is not yet any data available 1)
There is not yet any data available 1)
There is not yet any data available 1)


FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 35
Case 3a: Sequence with FC63 in S7-400 CPs (with ISO transport, ISO-on-TCP, UDP connections)
When the FC is called, the user program prepares the buffer for the received data and
instructs the CP to enter all data until the end of the transfer there; in other words, when the
length specified in the ANY pointer is reached.
As soon as the data record has been entered fully and consistently in the receive buffer, this
is indicated by the parameter NDR=1 in one of the next FC calls.
The maximum length for received data is 1452 bytes. The size of the receive buffer must
always be set to this value.
The status code in the output parameters NDR, ERROR and STATUS is updated in each
block call and can be evaluated.
AG_RECV
User program
(CPU cycle)
1) Parameter transfer NDR, ERROR, STATUS
Ethernet CP
Job completed without errors 1)
Time
Accept / evaluate
received data 'A'
The communication partner
Time Time
Transfer of 'A' via
Ethernet active
All data from data
record A will be
entered in the buffer.


FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
36 Programming Manual, 03/2008, C79000-G8976-C229-01
Case 3b: Sequence with FC63 in S7-400 CPs (only for TCP connections)
When the FC is called, the user program prepares the buffer to receive data and instructs
the CP to enter the currently available data there. Until the data has been completely entered
in the receive buffer, the message "Job active" (8181H) is sent.
With each new FC call, the currently available data is entered in the receive buffer. When the
data record has been entered fully and consistently in the receive buffer, this is indicated by
the parameter NDR=1 in one of the next FC calls.
The maximum length for received data is 1452 bytes. The size of the receive buffer must
always be set to this value.
The status code in the output parameters NDR, ERROR and STATUS is updated in each
block call and can be evaluated.
AG_RECV
AG_RECV
User program
(CPU cycle)
1) Parameter transfer NDR, ERROR, STATUS
Ethernet CP
Job completed without errors 1)
Time
Accept / evaluate
received data 'A'
The communication partner
Time Time
Transfer of 'A' via
Ethernet active
STATUS = 8181
Available data in the buffers


2.1.3.3 Explanation of the formal parameters - AG_RECV / AG_LRECV / AG_SRECV
Explanation of the formal parameters
The following table explains all the formal parameters for the
AG_RECV / AG_LRECV / AG_SRECV function:

Parameter Declaration Data type Possible values Description
ID INPUT INT 1,2...64 (S7-400)
1,2...16 (S7-300)
The connection number of the ISO transport
connection is specified in the ID parameter.
LADDR INPUT WORD Module start address
When you configure the CP with STEP 7 HW Config,
the module start address is displayed in the
configuration table. Specify this address here.
FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 37
Parameter Declaration Data type Possible values Description
RECV INPUT ANY Specifies the address and length
The address of the data area points to one of the
alternatives:
Memory bit area
Data block area
Note on length:
Performance is improved when transferring data
records up to 212 bytes if you also restrict the length to
212 bytes at the RECV parameter.
Note on FC63 AG_SRECV:
With FC63 AG_SRECV, always set RECV to the
maximum receive buffer length of 1452 bytes.
Otherwise, the following error can occur in certain
situations:
NDR=0; ERROR=1; STATUS=8185H
NDR OUTPUT BOOL 0: -
1: new data
The parameter indicates whether or not new data was
accepted.
For the meaning in conjunction with the ERROR and
STATUS parameters, refer to the following table.
ERROR OUTPUT BOOL 0: -
1: Error
Error code
For the meaning in conjunction with the NDR and
STATUS parameters, refer to the following table.
STATUS OUTPUT WORD See following table Status code
For the meaning in conjunction with the NDR and
ERROR parameters, refer to the following table.
LEN OUTPUT INT On ISO Transport and
ISOonTCP:
1,2,...8192

On UDP:
1,2,...2048
Specifies the number of bytes accepted from the
Ethernet CP and entered in the data area.
Note the block type:
For S7-300
The current versions of FC AG_RECV allow up to
8192 bytes (2048 bytes for UDP) to be transferred.
For S7-400
With FC AG_RECV, the data area is restricted to a
maximum of 240 bytes.
With FC AG_SRECV, the data area is restricted to
a maximum of 1452 bytes.

2.1.3.4 Condition codes of AG_RECV, AG_LRECV and AG_SRECV
Condition codes
The following table shows the codes formed by the NDR, ERROR and STATUS parameters
that must be evaluated by the user program.
FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
38 Programming Manual, 03/2008, C79000-G8976-C229-01

Note
For entries coded with 8FxxH in STATUS, refer to the information in the STEP 7 Standard
and System Functions reference manual. The chapter describing error evaluation with the
RET_VAL output parameter contains detailed information.
To find out which SFCs are used and are relevant for error evaluation, display the properties
dialog of the FC described here in the "Calls" tab.


Table 2-1 AG_RECV / AG_LRECV / AG_SRECV condition codes
NDR ERROR STATUS Meaning
1 0 0000H New data accepted.
0 0 8180H There is no data available yet (not with AG_SRECV).
0 0 8181H Job active.
0 1 8183H The configuration is missing;
The ISO transport service has not yet started on the Ethernet CP;
The connection is not established.
0 1 8184H Illegal type specified for the RECV parameter;
System error.
0 1 8185H Destination buffer (RECV) is too short.
0 1 8186H ID parameter invalid.
ID != 1,2....16 (S7-300).
ID != 1,2....64.(S7-400)
0 1 8304H The connection is not established. The send job should only be attempted again after
waiting for at least 100 ms.
0 1 8F23H Source area invalid, e.g.:
Area does note exist in the DB.
0 1 8F25H Area error writing a parameter.
0 1 8F29H Alignment error writing a parameter
0 1 8F30H Parameter is in the writeprotected first current data block.
0 1 8F31H Parameter is in the writeprotected second current data block.
0 1 8F32H Parameter contains a DB number that is too high.
0 1 8F33H DB number error.
0 1 8F3AH Destination area not loaded (DB).
0 1 8F43H Timeout writing a parameter to the
I/O area.
0 1 8F45H Address of the parameter to be read is disabled in the access track.
0 1 8F7FH Internal error, e.g. illegal ANY reference.
0 1 8090H No module with this module start address exists or the CPU is in STOP mode;
The FC being used does not match the system family being used (remember to use
different FCs for S7300 and S7400).
0 1 8091H Module start address not at a doubleword boundary.
0 1 8092H In the ANY reference, a type other than BYTE is specified.
(S7-400 only)
FCs / FBs for Industrial Ethernet
2.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 39
NDR ERROR STATUS Meaning
0 1 80A0H Negative acknowledgment reading from the module.
0 1 80A4H The communication bus connection between the CPU and CP is not established.
0 1 80B0H The module does not recognize the data record.
0 1 80B1H Destination area invalid.
0 1 80B2H The communication bus connection between the CPU and CP is not established.
0 1 80C0H The data record cannot be read.
0 1 80C1H The specified data record is currently being processed.
0 1 80C2H There are too many jobs pending.
0 1 80C3H CPU resources (memory) occupied.
0 1 80C4H Communication error (occurs temporarily and a repetition in the user program will often
remedy the problem).
0 1 80D2H Module start address incorrect.

FCs / FBs for Industrial Ethernet
2.2 FCs for access coordination with FETCH/WRITE
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
40 Programming Manual, 03/2008, C79000-G8976-C229-01
2.2 FCs for access coordination with FETCH/WRITE
2.2.1 Overview of FCs and their use
Overview
The following FCs are available for FETCH/WRITE function to coordinate access:

can be used with: FC
S7-300 S7-400
Meaning
AG_LOCK (FC7) x x Locks external data access with
FETCH/WRITE.
AG_UNLOCK (FC8) x x Releases external data access with
FETCH/WRITE.

Caution when Configuring
If you use FCs AG_LOCK and AG_UNLOCK, you must specify the following information for
CPs in S7400 stations in the configuration:
Under "Properties > Addresses"
The "Address setting for LOCK/UNLOCK" option must be selected if the selection is
available.
FCs / FBs for Industrial Ethernet
2.2 FCs for access coordination with FETCH/WRITE
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 41
How It works
With these FCs, you can coordinate access to system memory areas so that no inconsistent
data is created and transferred. The control is from the user program in the S7 CPU that can,
if necessary, disable an external FETCH/WRITE access using an AG_LOCK call. After a
certain time or after the local write/read access is completed, an AG_UNLOCK job can be
used to enable external access again.
Another advantage is that this access lock only applies to the FETCH/WRITE connection
specified in the call. If more than one FETCH/WRITE connection is configured, these can, for
example, be used for certain specific system areas and a selective access coordination can
be implemented.
The following diagram illustrates the usual chronological sequence of memory access
coordination controlled in the user program with AG_LOCK and AG_UNLOCK.
{
{
{
{
AG_LOCK
AG_LOCK
AG_UNLOCK
AG_LOCK
FETCH/WRlTE
LOCKED = 1
STATUS = 700x
LOCKED = 0
LOCKED = 0
User program
(CPU cycle)
Ethernet CP
Time
Data processing
in DB x
Communications partner
Time Time
FETCH/WRlTE access
to DB x active
FETCH/WRlTE denied
FETCH/WRlTE access
to DB x active
Cycle n
....
Cycle n+m
Cycle n+2
Cycle n+1


The lock job must first be monitored in the user program using the code in the return
parameter LOCKED. As long as LOCKED=0 is indicated, it must be assumed that there is
still an external FETCH/WRITE access active.
FCs / FBs for Industrial Ethernet
2.2 FCs for access coordination with FETCH/WRITE
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
42 Programming Manual, 03/2008, C79000-G8976-C229-01
If LOCKED=1 is indicated, this shows that the lock is active; data can now be modified by the
user program.
The status code is updated at each block call.
2.2.2 FC7 AG_LOCK
2.2.2.1 Meaning and call - AG_LOCK
Meaning of the block
Using the AG_LOCK block the data exchange using FETCH or WRITE on the connection
selected with the parameter ID is disabled. The LOCKED output indicates whether or not the
lock was successful. If the lock was not successful, the job must be triggered again in a later
CPU cycle.
The STATUS output indicates the status of the CP for this connection.
Call
Call interface in FBD representation
AG_LOCK
STATUS
LOCKED
LADDR
lD


Example in STL representation

STL Explanation
call fc 7(
ID:=DB 100.DBW 2,
LADDR:=W#16#0100,
LOCKED:=DB 100.DBX 0.6,
STATUS:=DB 100.DBW 4 );
//Block call
//Connection ID acc. to configuration
//=LADDR 256 dec. in HW Config
//Status code of access lock
//Status code

FCs / FBs for Industrial Ethernet
2.2 FCs for access coordination with FETCH/WRITE
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 43
2.2.2.2 Explanation of the formal parameters - AG_LOCK
Explanation of the formal parameters
The following table explains all the formal parameters for the AG_LOCK function:

Parameter Declaration Data type Possible values Description
ID INPUT INT 1,2...16 for S7300
1,2...64 for S7400
The connection number of the connection is specified
in the parameter ID. (See Configuration)
LADDR INPUT WORD Module start address
When you configure the CP with STEP 7 HW Config,
the module start address is displayed in the
configuration table. Specify this address here.
LOCKED OUTPUT BOOL 0: not (yet) locked
1: locked
Shows the status of the access lock requested on the
specified FETCH/WRITE connection.
STATUS OUTPUT WORD See following table Status code
For meaning, refer to the table below.

2.2.2.3 Condition codes of AG_LOCK
Condition codes
The following table shows the STATUS code that must be evaluated by the user program.
Table 2-2 AG_LOCK condition codes
STATUS Meaning
7000H CP is not processing a job
7001H FETCH active
7002H WRITE active
8183H FETCH/WRITE not configured for this connection (S7-400 only)
8186H ID number not in permitted range (e.g. 1...64 for S7-400 Industrial Ethernet CPs)
80A4H The communication bus connection between the CPU and CP is not established. (Only with newer CPU
versions)
80B0H The module does not recognize the data record.
80B1H The specified length (in the LEN parameter) is incorrect.
80B2H The communication bus connection between the CPU and CP is not established.
80C0H The data record cannot be read.
80C1H The specified data record is currently being processed.
80C2H There are too many jobs pending.
80C3H CPU resources (memory) occupied.
80C4H Communication error (occurs temporarily and a repetition in the user program will often remedy the
problem).
80D2H Module start address incorrect.
FCs / FBs for Industrial Ethernet
2.2 FCs for access coordination with FETCH/WRITE
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
44 Programming Manual, 03/2008, C79000-G8976-C229-01
2.2.3 FC8 AG_UNLOCK
2.2.3.1 Meaning and call - AG_UNLOCK
Meaning of the block
Using the AG_UNLOCK function, the external access to system areas on the S7 CPU with
FETCH or WRITE on the connection specified by the ID parameter is released.
The next external FETCH/WRITE job to arrive for the CP can then be processed.
The AG_UNLOCK follows an access lock with AG_LOCK.
Call
Call interface in FBD representation
AG_UNLOCK
STATUS
LADDR
lD


Example in STL representation

STL Explanation
call fc 8(
ID:=DB 100.DBW 2,
LADDR:=W#16#0100,
STATUS:=DB 100.DBW 4 );
//Block call
//Connection ID acc. to configuration
//=LADDR 256 dec. in HW Config
//Status code

How it works
To release the connection again, the LOCK request bit must be cleared again by the FC.
The FC also shows the current status using error messages.
2.2.3.2 Explanation of the formal parameters - AG_UNLOCK
Explanation of the formal parameters
The following table explains all the formal parameters for the AG_UNLOCK function:
FCs / FBs for Industrial Ethernet
2.2 FCs for access coordination with FETCH/WRITE
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 45

Parameter Declaration Data type Possible values Description
ID INPUT INT 1,2...16 for S7300
1,2...64 for S7400
The connection number of the connection is specified
in the parameter ID. (See Configuration)
LADDR INPUT WORD Module start address
When you configure the CP with STEP 7 HW Config,
the module start address is displayed in the
configuration table. Specify this address here.
STATUS OUTPUT WORD Status code:


2.2.3.3 Condition codes of AG_UNLOCK
Condition codes
The following table shows the STATUS code that must be evaluated by the user program.
Table 2-3 AG_UNLOCK condition codes
STATUS Meaning
7000H CP is not processing a job
7001H FETCH active
7002H WRITE active
8183H FETCH/WRITE not configured for this connection (S7-400 only)
8186H ID number not in permitted range (e.g. 1...64 for S7-400 Industrial Ethernet CPs)
80A4H The communication bus connection between the CPU and CP is not established. (Only with newer CPU
versions)
80B0H The module does not recognize the data record.
80B1H The specified length (in the LEN parameter) is incorrect.
80B2H The communication bus connection between the CPU and CP is not established.
80C0H The data record cannot be read.
80C1H The specified data record is currently being processed.
80C2H There are too many jobs pending.
80C3H CPU resources (memory) occupied.
80C4H Communication error (occurs temporarily and a repetition in the user program will often remedy the
problem).
80D2H Module start address incorrect.

FCs / FBs for Industrial Ethernet
2.3 FCs for connection diagnostics
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
46 Programming Manual, 03/2008, C79000-G8976-C229-01
2.3 FCs for connection diagnostics
2.3.1 FC 10 AG_CNTRL - meaning and call
How it works
With the AG_CNTRL function, you can diagnose connections. When necessary, you can
initialize connection establishment again using the FC.
The following actions are possible by setting commands:
Reading out connection information
Based on status information, you can decide whether or not it would be useful to reset all
or individual connections of the CP.
Resetting configured connections
You can reset individual connections or all connections of a CP.
Aborting the active connection and establishing it again
The commands of the AG_CNTRL function (FC) are permitted only for SEND/RECV
connections based on the ISO / RFC / TCP / UDP protocols.
Call interface
Call interface in FBD representation
AG_CNTRL
lNT
BOOL
BOOL
WORD
lNT
WORD
DWORD RESULT 1
STATUS
ERROR
DONE
CMD
LADDR
lD
BOOL ACT
RESULT 2
BOOL
DWORD

Example in STL representation
STL Explanation
call fc 10 (
ACT:=M1.0,
ID:=MW8,
LADDR:=W#16#100,
CMD:=MW6,
DONE:=M20.1,
ERROR:=M20.2,
STATUS:=MW22,
RESULT1:=MD24,
RESULT2:=MD28 );
//AG_CNTRL block call
//Job triggered by memory bit
//Connection ID acc. to configuration
//=LADDR 256 dec. in HW Config
//=Command ID
//Execution code
//Error code
//Status code
//Job result 1
//Job result 2

FCs / FBs for Industrial Ethernet
2.3 FCs for connection diagnostics
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 47
2.3.2 How AG_CNTRL works
Operating principle
The following diagram shows a typical sequence of AG_CNTRL jobs in the user program.
Es wird ein Ereignis erkannt,
das den Abbruch und Zeuauf-
bau einer Verbindung sinnvoll
macht.
AG_CNTRL (Statusabfrage)
AG_CNTRL (Reset-Kommando)
AG_CNTRL (Statusabfrage)
Ethernet-CP
Status connection lD1 1)
Time
Supply AG_CNTRL for
reset:
ACT = 1; CMD=2
lD =1 (connection)
Supply AG_CNTRL for
status query:
ACT = 1; CMD=1
lD =1 (connection)
User program
(CPU cycle)
Acknowledgment job acceptance:
RESULT1: "connection terminati-
on started" 1)
Acknowledgement:
RESULT1: B095H
"Reset was executed" 1)
Time
Status query for connection 1
is acknowledged
1) Parameter transfer DONE, ERROR, STATUS and RESULT1/2
Reset request active:
Reset lD (bit 15 in RESULT1)
is set
Status query is acknowledged;
afterwards the reset
lD (bit 15 in RESULT1)
reset
Connection being terminated
and re-initialized:
Reset lD (bit 15 in
RESULT1) remains set
Diagnostic buffer entry
Supply AG_CNTRL for
status query:
ACT = 1; CMD=1
lD =1 (connection)
Status connection lD1 1)


The diagram shows how the connection status is initially queried and then, in a second job,
how the connection termination is triggered with the reset command.
The reset ID (bit 15 in RESULT1) is set on the CP. If there is a status query later, it is
therefore clearly recognizable whether the connection has been reset due to a reset job. The
FCs / FBs for Industrial Ethernet
2.3 FCs for connection diagnostics
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
48 Programming Manual, 03/2008, C79000-G8976-C229-01
reset ID is cleared on the CP only after this status query (or as a result of an explicit
CN_CLEAR_RESET command)

NOTICE
The block must be called with ACT = 1; if it is called with ACT=0, there is no function call
and the block is exited again immediately.
Since the job result of FC10 is obtained synchronous to the call, it can be called again in
the same cycle.


2.3.3 Explanation of the formal parameters - AG_CNTRL
Explanation of the formal parameters
The following table explains all the formal parameters for the AG_UNLOCK function:

Parameter Declaration Data type Possible values Description
ACT INPUT BOOL 0, 1 The FC must be called with ACT=1.
If it is called with ACT=0, there is no function call and
the block is exited again immediately.
ID INPUT INT 1, 2, .., n,
or
0
The connection number of the connection is specified
in the parameter ID. The connection number can be
found in the configuration. n is the maximum number of
connections and is dependent on the product (S7-300
or S7-400).
If the call addresses all connections (_ALL function with
CMD 3 or 4), 0 must be specified as the ID.
LADDR INPUT WORD Module start address
When you configure the CP with STEP 7 HW Config,
the module start address is displayed in the
configuration table. Specify this address here.
CMD INPUT INT Command to FC AG_CNTRL.
DONE OUTPUT BOOL 0:
Job still being
processed or not yet
triggered
1:
Job done
This parameter indicates whether or not the job was
completed without errors.
For the meaning in conjunction with the ERROR and
STATUS parameters, refer to the following table.
Note:
If DONE=1, RESULT can be evaluated
ERROR OUTPUT BOOL 0: No error
1: Error
Error code
For the meaning in conjunction with the DONE and
STATUS parameters, refer to Table 1-6 below.
STATUS OUTPUT WORD Status code
For the meaning in conjunction with the DONE and
ERROR parameters, refer to Table 1-6 below.
FCs / FBs for Industrial Ethernet
2.3 FCs for connection diagnostics
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 49
Parameter Declaration Data type Possible values Description
RESULT1 OUTPUT DWORD Information returned according to the command sent to
FC AG_CNTRL.
RESULT2 OUTPUT DWORD Only to be evaluated for S7-400:
Part 2 of information returned according to the
command sent to FC AG_CNTRL.

2.3.4 Condition codes of AG_CNTRL
Condition codes
The following table shows the condition codes formed based on DONE, ERROR and
STATUS that must be evaluated by the user program.
The command results in the RESULT1/2 parameters must also be evaluated according to
" ".
Table 2-4 AG_CNTRL codes
DONE ERROR STATUS Meaning
1 0 0000H A job (CMD) was transferred successfully to the CP (for example RESET) or a status
was read successfully from the CP.
The RESULT1/2 parameters can be evaluated.
0 0 0000H There has been no block call yet or the block was called with ACT=0.
0 0 8181H Job active
The block call must be repeated with the same parameters until DONE or ERROR is
signaled.
0 1 8183H No configuration or the service has not yet started on the Ethernet CP.
0 1 8186H The ID parameter is invalid. The permitted ID depends on the selected command; see
CMD parameter in "".
0 1 8187H The CMD parameter is invalid.
0 1 8188H Sequence error in the ACT control (Note: this code does not occur in the product
version of the CP / firmware).
0 1 8189H The CP version / firmware used does not support FC10.
The code is set when you call a CP 3431-EX20 with firmware as of V1.3.9; with other
CP types, the code 80B0H is set instead.
Note: FC10 in version V1.0 is supported by the CPs as of CP 343-1EX21/GX21; this
code does not occur with these modules.
0 1 8090H No module with this module start address exists.
or
The FC being used does not match the system family being used (remember to use
different FCs for S7300 and S7400).
or
The function is not supported by this module.
0 1 8091H The module start address is not at a doubleword boundary.
FCs / FBs for Industrial Ethernet
2.3 FCs for connection diagnostics
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
50 Programming Manual, 03/2008, C79000-G8976-C229-01
DONE ERROR STATUS Meaning
0 1 80B0H The module does not recognize the data record.
0 1 80C0H The data record cannot be read.
0 1 80C1H The specified data record is currently being processed.
0 1 80C2H There are too many jobs pending.
0 1 80C3H CPU resources (memory) occupied.
0 1 80C4H Communication error
The error occurs temporarily; it is usually best to repeat the job in the user program.
0 1 80D2H The module start address is incorrect.

2.3.5 Commands and job results - AG_CNTRL
Commands and evaluating the job results
The following table shows you the possible commands and the results that can be evaluated
in the RESULT1/2 parameters.
Table 2-5 Commands to FC AG_CNTRL
CMD Meaning
NOP no operation
The block executes without a job being sent to the CP.
RESULT (for CMD = 0)
Parameter Hex value/range
Meaning
RESULT1 0000 0001H Executed without error
0
RESULT2 0000 0000H Default


CMD Meaning
CN_STATUS connection status
This command returns the status of the connection selected with the ID.
The CP is selected in the LADDR parameter.
If bit 15 (reset ID) is set, this is automatically reset (this action corresponds to the CN_CLEAR_RESET job -
see CMD = 5).
RESULT (for CMD = 0)
Parameter Hex value/range Bit/value
Meaning
Bits 0-3: Codes for the send direction
(excluded values: 0x2)
1
RESULT1 0000 000*H
Bit 0
0
1
Connection Type
No send and receive connection
Connection reserved for send and receive jobs
FCs / FBs for Industrial Ethernet
2.3 FCs for connection diagnostics
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 51
CMD Meaning
Bit 1
0
1
Status of current job
No send job being executed
Send job being executed
Bits 2+3
00

01

10
Previous job:
No information available on previous send job
previous send job completed successfully
previous send job not completed successfully
Bits 47: Codes for the receive direction
(excluded values: 0x2)
Bit 4
0
1
Connection Type
No send and receive connection
Connection reserved for send and receive jobs
Bit 5
0
1
Status of current job
No receive job being executed
Receive job being executed
RESULT1 0000 00*0H
Bits 6+7
00

01

10
Previous job:
No information available on previous receive job
previous receive job completed successfully
previous receive job not completed successfully
Bits 8-11: Codes for FETCH/WRITE
(excluded values: 0x3,0x7,0x8,0xB,0xF)
Bit 8
0
1
Connection type:
No FETCH connection
Connection reserved for FETCH jobs
Bit 9
0
1
Connection type:
No WRITE connection
Connection reserved for WRITE jobs
Bit 10
0
1
Job status (FETCH/WRITE):
Job status OK
Job status NOT OK
This ID is set in the following situations:
The job was acknowledged negatively by the CPU
The job could not be forwarded to the CPU
because the connection was in the "LOCKED"
status.
The job was rejected because the FETCH/WRITE
header did not have the correct structure.
RESULT1 0000 0*00H
Bit 11
0
1
Status of FETCH/WRITE job
No job active
Job from LAN active
RESULT1 0000 *000H Bits 12-15: General CP information
(excluded values: 0x3,0xB)
FCs / FBs for Industrial Ethernet
2.3 FCs for connection diagnostics
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
52 Programming Manual, 03/2008, C79000-G8976-C229-01
CMD Meaning
Bit 12 + 13




00
01
10
11
Information on connection status:
(only available for SEND/RECV connections based on
the ISO/RFC/TCP protocols, with UDP, the
corresponding internal information is output)
Connection is terminated
Connection establishment active
Connection termination active
Connection is established
Bit 14
0
1
CP information:
CP in STOP
CP in RUN
Bit 15
0


1
Reset ID
FC10 has not yet reset a connection or the reset ID
was cleared.
The control block has executed a connection reset.
RESULT1 **** 0000H Bits 16-31: Reserved
0 reserved for later expansions
RESULT2 0000 0000H - reserved for later expansions


CMD Meaning
CN_RESET connection reset
This command resets the connection selected with ID.
The CP is selected in the LADDR parameter.
Resetting the connection means that a connection is aborted and established again (active or passive
depending on the configuration).
An entry is also generated in the diagnostics buffer in which the job result can be found.
RESULT (for CMD = 2)
Parameter Hex value/range
Meaning
0000 0001H The reset job was transferred to the CP successfully.
The connection abort and subsequent connection
establishment were triggered.
RESULT1
0000 0002H The reset job could not be transferred to the CP because
the service has not started on the CP (for example, CP in
STOP).
2
RESULT2 0000 0000H Default


FCs / FBs for Industrial Ethernet
2.3 FCs for connection diagnostics
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 53
CMD Meaning
CN_STATUS_ALL all connections status
This command returns the connection status of all connections (established/terminated) in the RESULT1/2
parameters (at total of 8 bytes of group information).
The ID parameter must be set to "0" (checked for 0).
The CP is selected in the LADDR parameter.
When necessary, you can obtain detailed information about a terminated or unconfigured connection using a
further connection status call with CMD=1.
RESULT (for CMD = 3)
Parameter Hex value/range
Meaning
RESULT1 **** ****H 32 bits: Connection 1 - 32
0 connection terminated / not configured
1 connection established
3
RESULT2 **** ****H 32 bits: Connection 33 - 64
0 connection terminated / not configured
1 connection established


CMD Meaning
CN_RESET_ALL all connections reset:
This command resets all connections.
The ID parameter must be set to "0" (checked for 0).
The CP is selected in the LADDR parameter.
Resetting the connections means that connections are aborted and established again (active or passive
depending on the configuration).
An entry is also generated in the diagnostics buffer in which the job result can be found.
RESULT (for CMD = 4)
Parameter Hex value/range
Meaning
RESULT1 0000 0001H The reset job was transferred to the CP successfully. The
connection abort and subsequent connection
establishment of all connections were triggered.
RESULT1 0000 0002H The reset job could not be transferred to the CP because
the service has not started on the CP (for example, CP in
STOP).
4
RESULT2 0000 0000H Default


CMD Meaning
CN_CLEAR_RESET Clear the reset ID
This command resets the reset ID (bit 15 in RESULT1) for the connection selected with ID.
The CP is selected in the LADDR parameter.
This job executes automatically when the connection status is read (CMD=1); the separate job described here
is therefore only required in special situations.
RESULT (for CMD = 5)
5
Parameter Hex value/range
Meaning
FCs / FBs for Industrial Ethernet
2.3 FCs for connection diagnostics
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
54 Programming Manual, 03/2008, C79000-G8976-C229-01
CMD Meaning
RESULT1 0000 0001H The clear job was transferred to the CP successfully.
RESULT1 0000 0002H The Clear job could not be transferred to the CP because
the service has not started on the CP (for example, CP in
STOP).
RESULT2 0000 0000H Default


CMD Meaning
CN_DISCON connection disconnect
This command resets the connection selected with ID and LADDR.
Resetting the connection is achieved by aborting the connection.
Any data in the stack is lost without any message being displayed. The connection is not established again
automatically afterwards. The connection can be established again with the CN_STARTCON control job. A
diagnostics buffer entry is created in which you will find the job result.
RESULT (for CMD = 6)
Parameter Hex value/range
Meaning
RESULT1 0000 0001H The job was transferred to the CP successfully. The
connection abort was initiated.
RESULT1 0000 0002H The job could not be transferred to the CP because the
service has not started on the CP (for example, CP in
STOP).
6
RESULT2 0000 0000H Default


CMD Meaning
CN_STARTCON start connection
This command establishes a connection selected with ID and LADDR and aborted earlier with the control job
CN_DISCON. A diagnostics buffer entry is created in which you will find the job result.
RESULT (for CMD = 6)
Parameter Hex value/range
Meaning
RESULT1 0000 0001H The connection establishment job was transferred to the
CP successfully. The connection establishment was
initiated.
RESULT1 0000 0002H The connection establishment job could not be
transferred to the CP because the service has not started
on the CP (for example, CP in STOP).
7
RESULT2 0000 0000H Default

FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 55
2.4 FBs / FCs for FTP services
2.4.1 Overview of FTP
FB and FCs for FTP services (FTP client)
The following list shows the blocks available for the FTP client services. You can change the
block numbers used when the blocks ship.

NOTICE
Note that the FTP client services of old SIMATIC S7-300 CPUs, for example the CPU 312
or CPU 315-1AF01, cannot be used because they do not support SFC24.
In S7-300 the CP requires the supplied FC5 (AG_SEND) to start the FTP FCs; do not
rename the FC5 for this application.


can be used with: FB/FC
S7-300 S7-400
Meaning
FB40 x x Handling of complete FTP job sequences

FC40 x x Establishing an FTP connection from client to server.
FC41 x x Transferring a DB from client to server.
FC42 x x Transferring a file from client to server.
FC43 x x Deleting a file on the server.
FC44 x x Terminating a connection established with the ID.
Using the blocks
Use either FB40 or the functions FC40...44 for the data transfer depending on the module
type.
FB40
FB40 can be used as of the following module types:
As of CP 343-1 Advanced (GX30)
As of CP 443-1 Advanced (GX20)
These module types continue to support the functions FC40...44.
The following module types, on the other hand, do not support FB40:
IT / Advanced CPs up to CP 343-1 Advanced (GX21)
IT / Advanced CPs up to CP 443-1 Advanced (EX41)
FC40...44
The functions FC40...44 can be used with all Advanced CPs.
FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
56 Programming Manual, 03/2008, C79000-G8976-C229-01
Requirement - configured FTP connection
To manage an FTP request sequence between the S7 station as FTP client and an FTP
server, you will need to configure an FTP connection. To do this, first configure an
unspecified TCP connection with the additional "for FTP protocol" attribute.
See also
Migration from FC 40-44 to FB40 (Page 64)
2.4.2 FB40 FTP_CMD - universal block for FTP services
2.4.2.1 Meaning and call - FTP_CMD
Meaning
Using FB40, you can establish FTP connections and transfer files from and to an FTP
server.
FB40 replaces the FTP functions FC40 to FC44 used previously. The differences in these
functions are mapped to a command parameter in FB40.
The advantages of FB40 are as follows:
Simplification in the user program by using a command variable instead of different
function calls
Additional function "APPEND"
"APPEND" allows data to be appended to an existing file.
Additional function "RETR_PART"
"RETR_PART" allows selected data areas to be retrieved from a file.
Validity
FB40 can be used as of the following module types:
As of CP 343-1 Advanced (GX30)
As of CP 443-1 Advanced (GX20)
FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 57
Call interface
Call interface in FBD representation
DWORD
DWORD LEN
OFFSET
FTP_CMD
lNT
ANY
BOOL
BOOL
BYTE
WORD
WORD
lNT
lD
FlLE_DB_NR
STATUS
ERROR
DONE
NAME_STR
CMD
LADDR


Example of a call in STL representation

STL Explanation
CALL FB 40, DB 40 (
ID:= 4,
LADDR := W#16#3FFD,
CMD:= B#16#3,
NAME_STR := P#DB44.DBX 170.0 BYTE 220,
FILE_DB_NR:= 42,
OFFSET:= DW#16#0,
LEN:= DW#16#0,
DONE:= M 420.1,
ERROR:= M 420.2,
STATUS:= MW 422);
// Block call
// FTP connection ID according to configuration
// Module address according to configuration
// The FTP command to be executed
// Address and length of the destination data area
// Number of the data block
// (not relevant in the example)
// (not relevant in the example)
// Status parameter
// Error code
// Status code
System functions called
The following system functions are called by FB40:
SFC 1, SFC 20, SFC 24, SFC 58, SFC 59

NOTICE
Note that the FTP client services of old SIMATIC S7-300 CPUs, for example the CPU 312
or CPU 315-1AF01, cannot be used because they do not support SFC24.

FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
58 Programming Manual, 03/2008, C79000-G8976-C229-01
2.4.2.2 Input parameter - FTP_CMD
Explanation of the input parameters
Each FTP block call must be supplied with the following input parameters:
Table 2-6 Formal parameters of FB40 (FTP_CMD) - input parameters
Parameter Declaration Type Possible values Meaning / remarks
ID INPUT INT 1, 2...64 The FTP jobs are handled on FTP connections.
The parameter identifies the connection being
used.
LADDR INPUT WORD Module start address
When you call an FC, you transfer the module
start address of the ADVANCED-CP in the
LADDR parameter.
You will find the module start address of the
ADVANCED CP in the configuration of the
ADVANCED CP in
"Properties>Addresses>Inputs".
CMD INPUT BYTE 0: NOOP
1: CONNECT
2: STORE
3: RETRIEVE
4: DELETE
5: QUIT
6: APPEND
7: RETR_PART
FTP commands executed when FB40 is called.
You will find further information following the table.
If a command is not supported by the CP
firmware, an error message with STATUS =
8F6BH is output.
NAME_STR INPUT ANY Only "BYTE" is
permitted as
VARTYPE:
The address references a data block area. Here,
you specify the address and length of the data
area in which the target data is entered.
When CMD = 1:
With this command, the "NAME_STR"
parameter specifies the FTP server to be
addressed over the FTP connection with the
following attributes:
- IP address of the FTP server
- User name
- Password for the login
These values must be specified as
consecutive strings in the destination range of
the ANY pointer.
When CMD = 2, 3, 4, 6, 7:
With this command, the "NAME_STR"
parameter specifies the file name on the FTP
server, in other words, the data source or data
destination. The file name is specified as a
string in the destination range of the ANY
pointer.
When CMD = 5: Parameter not relevant
You will find example of content further below.
FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 59
Parameter Declaration Type Possible values Meaning / remarks
FILE_DB_NR INPUT INT The data block specified here contains the file DB
to be read / written.
The parameter is relevant only when CMD = 2, 3,
6 and 7.
OFFSET INPUT DWORD Only when CMD = 7:
Offset in bytes starting at which the file will be
read.
LEN INPUT DWORD Only when CMD = 7:
Sublength in bytes that is read starting at the
value specified in "OFFSET".
Special features:
If "DW#16#FFFFFFFF" is specified, the
available rest of the file will be read.
Result OK (DONE = 1, STATUS = 0) if no
other error occurred.
When OFFSET > length of the original file:
Length of the destination file (ACT_LENGTH
in file DB): 0 bytes on the CPU.
Result OK (DONE = 1, STATUS = 0) if no
other error occurred.
When OFFSET + LEN > length of the original
file (and LEN 0xFFFFFFFF):
Length of the destination file (ACT_LENGTH
in file DB): Available bytes starting at
"OFFSET".
Result OK (DONE = 1, STATUS = 0) if no
other error occurred.
FTP commands in the "CMD" parameter
The following table explains the meaning of the commands of the "CMD" parameter and
which input parameters need to be supplied. The ID and LADDR parameters must always be
set to identify the connection.

CMD Relevant input
parameters (in addition to
ID and LADDR)
Meaning / handling
0 (NOOP) - The called FC does not execute any action. The status codes are set
as follows when these parameters are supplied:
DONE=1; ERROR=0; STATUS=0
1 (CONNECT) NAME_STR With this command, the FTP client establishes an FTP connection to
an FTP server.
The connection is available under the connection ID specified here
for all further FTP commands. Data is then exchanged with the FTP
server specified for this user.
2 (STORE) NAME_STR
FILE_DB_NR
This function call transfers a data block (file DB) from the FTP client
(S7-CPU) to the FTP server.
Caution: If the file (file DB) already exists on the FTP server, it will be
overwritten.
FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
60 Programming Manual, 03/2008, C79000-G8976-C229-01
CMD Relevant input
parameters (in addition to
ID and LADDR)
Meaning / handling
3 (RETRIEVE) NAME_STR
FILE_DB_NR
This function call transfers a file from the FTP server to the FTP client
(S7-CPU).
Caution: If the data block (file DB) on the FTP client already contains
a file, it will be overwritten.
4 (DELETE) NAME_STR With this function call, you delete a file on the FTP server.
5 (QUIT) No others With this function call, you establish the FTP connections selected
with the ID.
6 (APPEND) NAME_STR
FILE_DB_NR
Similar to "STORE", the "APPEND" command saves a file on the
FTP server. With "APPEND", the file on the FTP server is, however,
not overwritten. The new content is appended to the existing file.
7 (RETR_PART) NAME_STR
FILE_DB_NR
OFFSET
LEN
Using the "RETR_PART" command (retrieve part) , you can request
a section of a file from the FTP server.
If very large files are involved, this allows you to restrict the read to
the part you currently require.
To do this, you need to know the structure of the file.
Enter the required part of the file using the two parameters "OFFSET"
and "LEN" in FB40.

Examples of the content of the "NAME_STR" parameter
The parameter record has the following content:
Table 2-7 Content of the parameter record for CMD = 1
Relative
address
2)

Name Type
1)
Example Meaning
0.0 ip_address STRING[100] 142.11.25.135 IP address of the FTP server
102.0 username STRING[32] 'user' User name for the login on the FTP
server
136.0 password STRING[32] 'password' Password for the login on the FTP
server
1) The maximum possible string length is specified
2) The specified values relate to the string lengths specified in "Type".

Table 2-8 Content of the parameter record for CMD = 2, 3, 4, 6, 7
Relative
address
2)

Name Type
1)
Example Meaning
170.0 filename STRING[220] 'plant1/tank2/press.dat' File name of the source or
destination file
1) The maximum possible string length is specified
2) The specified values relate to the string lengths specified in "Type".

FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 61
2.4.2.3 Output parameters and status information - FTP_CMD
Introduction
For status evaluation, the following parameters must be evaluated in the user program:
Table 2-9 Formal parameters of FB40 (FTP_CMD) - output parameters
Parameter Declaration Type Possible values Meaning / remarks
DONE OUTPUT BOOL 0: -
1: Job executed
This parameter indicates whether
or not the job was completed
without errors.
ERROR OUTPUT BOOL 0: -
1: Error
Error code
This parameter signals that the
job could not be executed error-
free.
STATUS OUTPUT WORD See following table Status code
This parameter supplies detailed
information about the execution
of the job.
The DONE, ERROR and STATUS parameters are updated at every block call.
Example
During job execution, the FB40 returns the following codes:
DONE=0
ERROR=0
STATUS=8181H
Significance: Job still running.
Evaluating status codes
Note
For entries coded with 8FxxH in STATUS, refer to the information in the STEP 7 Standard
and System Functions reference manual. The chapter describing error evaluation with the
RET_VAL output parameter contains detailed information.


Table 2-10 FB 40: Meaning of the STATUS parameter in conjunction with DONE and ERROR
DONE ERROR STATUS Meaning
0 0 0000H No job being executed.
1 0 0000H Job completed without error.
FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
62 Programming Manual, 03/2008, C79000-G8976-C229-01
DONE ERROR STATUS Meaning
0 0 8181H Job active.
If 8181H is indicated permanently:
The CP is not released for FB40 (an illegal command for the firmware
version (CMD 6 or CMD 7) was called.)
0 1 8090H No module with this module start address exists.
The block being used does not match the system family being used
(remember to use different blocks for S7300 and S7400).
0 1 8091H Module start address not at a doubleword boundary
0 1 8092H Type information in the ANY pointer is not byte
0 1 80A4H The communication bus connection between the CPU and CP is not
established (with newer CPU versions).
This can, for example, be caused by the following:
No connection configuration
Maximum number of CPs operating at the same time was
exceeded
0 1 80B0H The module does not recognize the data record.
0 1 80B1H Destination area invalid;
for example, destination area > 240 bytes.
0 1 80B2H The communication bus connection between the CPU and CP is not
established (with older CPU versions).
(with newer CPU versions, see 80A4H)
0 1 80C0H The data record cannot be read.
0 1 80C1H The specified data record is currently being processed.
0 1 80C2H There are too many jobs pending.
0 1 80C3H Resources occupied (memory).
0 1 80C4H Communication error (occurs temporarily, it is usually best to repeat
the job in the user program).
0 1 80D2H Module start address incorrect.
0 1 8183H The configuration does not match the job parameters.
0 1 8184H Illegal data type specified for the NAME_STR parameter.
0 1 8186H ID parameter invalid. ID = 1, 2....64
0 1 8F22H Source area invalid, for example:
Area does not exist in the DB
0 1 8F24H Area error reading a parameter
0 1 8F28H Alignment error reading a parameter
0 1 8F32H Parameter contains a DB number that is too high.
0 1 8F33H DB number error
0 1 8F3AH Area not loaded (DB)
0 1 8F50H File DB DB 0 or DB does not exist
0 1 8F51H Specified file DB data area larger than existing data area
0 1 8F52H File DB in write-protected memory
0 1 8F53H File DB max. length < current length
0 1 8F54H File DB does not contain any valid data.
0 1 8F55H Header status bit: Locked
0 1 8F56H The NEW bit in the file DB header was not reset
FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 63
DONE ERROR STATUS Meaning
0 1 8F57H The FTP client does not have write access to the file DB but rather the
FTP server (header status bit: WriteAccess).
0 1 8F60H Bad user data, for example bad IP address of the FTP server
0 1 8F61H FTP server not obtainable
0 1 8F62H Job not supported or rejected by FTP server
0 1 8F63H File transfer aborted by the FTP server
0 1 8F64H Error on the FTP control connection; data could not be sent or
received; the FTP control connection must be established again after
such an error.
0 1 8F65H Error on the FTP data connection; data could not be sent or received.
The job must be called again.
This error can, for example, be caused by RETRIEVE (CMD=3) when
the addressed file is already open on the FTP server.
0 1 8F66H Error reading/writing data from/to the CPU (for example DB does not
exist or too short)
0 1 8F67H Error in the FTP client on the ADVANCED CP; for example attempting
to open more than 10 FTP connections.
0 1 8F68H The job was rejected by the FTP client.
This error can, for example, be caused by RETRIEVE (CMD=3) when
the value for the parameter MAX_LENGTH was selected too low in the
file DB header.
0 1 8F69H The FTP connection in an incorrect status, for example:
The connection is called without a previous connection termination
(with the same NetPro ID)
There is a connection termination for a connection that has already
been terminated:
A STORE command was sent on a connection that is not
established.
0 1 8F6AH No new socket could be opened / temporary resource problem: Repeat
the block call.
0 1 8F6BH Possible causes:
Bad value for the CMD parameter
Values from 0 to 15 are permitted.
An FB40 command is not supported.
Possible cause: Wrong firmware on the CP
Remedy: Firmware update (with older CPs, use the functions
FC 40...FC 44 instead of FB 40.)
0 1 8F7FH Internal error, for example illegal ANY reference

FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
64 Programming Manual, 03/2008, C79000-G8976-C229-01
2.4.2.4 Migration from FC 40-44 to FB40
Comparison of the function block FB40 with older functions FC40...44
All CPs with FTP functionality support the functions FC40...44. This means that existing user
programs can be used unchanged.
If you want to convert from the FTP functions FC40...44 to FB40, you will need to modify
your user program.
The following table shows the FB40 commands used to replace the functions FC40...44.
Correlation is indicated by "X".
Where there is no correlation, this is indicated by "-".

Commands of the "CMD" parameter of FB40
Older FTP
functions
FC40...44
CMD = 1 CMD = 2 CMD = 3 CMD = 4 CMD = 5 CMD = 6 CMD = 7
FC40 X
1)

FC41 X
2)

FC42 X
3)

FC43 X
4)

FC44 X
-
-
1)
...
4)
The parameters of FC40...43 and CMD 1...4 (FB40) are not identical.
(See table below)

The corresponding parameters that specify a particular function in the functions FC40...FC43
or in the commands of FB40 are listed in the following table.

Parameters of the FC Parameters in FB40 (with CMD 1...4)
FC40: LOGIN CMD = 1: NAME_STR
FC41: FILE_NAME CMD = 2: NAME_STR
FC42: FILE_NAME CMD = 3: NAME_STR
FC43: FILE_NAME CMD = 4: NAME_STR
FC40...43: BUFFER_DB_NR Omitted (replaced by instance DB)

FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 65
2.4.3 FC40 FTP_CONNECT
2.4.3.1 Meaning and call - FTP_CONNECT
Meaning
With this function call, the FTP client establishes an FTP connection to an FTP server.
The IP address of the FTP server, the user identification (username) and (if necessary) the
password for user identification must be transferred to the FTP server.
All further access by the FTP client is then based on this user identification if you use the
same FTP connection ID. Data is then exchanged with the FTP server specified for this user.
Call interface
FTP_CONNECT
BOOL
ANY
BOOL
BOOL
WORD
lNT
WORD
lNT
ACT
BUFFER_DB_NR
STATUS
ERROR
DONE
LOGlN
LADDR
lD


Example of a call in STL representation

STL Explanation
call fc40 (
ACT:= M 420.0,
ID:= 4,
LADDR:= W#16#3FFD,
LOGIN := P#DB40.DBX 0.0 BYTE 170,
BUFFER_DB_NR:= 9,
DONE:= M 420.1,
ERROR:= M 420.2,
STATUS:= MW 422);
//FTP_CONNECT block call
// Job triggered by memory bit
// FTP connection ID acc. to configuration
// Module address acc. to configuration
// Information for LOGIN in DB40
// Buffer area for FTP service


2.4.3.2 Explanation of the formal parameters - FTP_CONNECT
Explanation of the general call parameters
The general parameters have the same significance in every FTP function call; they are
therefore described in one section.
FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
66 Programming Manual, 03/2008, C79000-G8976-C229-01
Explanation of the formal parameters specific to the call
Table 2-11 Formal parameters for FTP_CONNECT
Parameter Declaration Data type Description
LOGIN INPUT ANY
(only the
following are
permitted as
VARTYPE:
BYTE)
This parameter specifies the FTP server to be accessed on the FTP
connection.
(for further details, refer to the following table)
Here, you specify the address and length of the data area in which the
target data are entered.
The address references a data block area.
The ANY pointer data type is used to address this area. For more
detailed information on this data type, refer to the STEP 7 online help
under the appendix topic "Format of the parameter type ANY".
BUFFER_DB_NR INPUT INT Here, you enter a data block required as a buffer area by the FTP
client for FTP transfer.
You can use the same data block as the buffer area for all FTP jobs.
Note:
The length of the reserved DB must be at least 255 bytes!

LOGIN parameter
This parameter record has the following content for FTP_CONNECT:

Relative
address
2)

Name Type
1)
Example Meaning
0.0 ip_address STRING[100] '142.11.25.135' IP address of the FTP server.
102.0 username STRING[32] 'user' User name for the login on the FTP server.
136.0 password STRING[32] 'password' Password for the login on the FTP server.
170.0 filename STRING[220] 'plant1/tank2/pressur
e.dat'
Name of the destination or source file
1)
in each case, the maximum possible string length is specified
2)
The specified values relate to the string lengths specified in "Type".
Note: The rows shown on a gray background are irrelevant for this call.
FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 67
2.4.4 FC41 FTP_STORE
2.4.4.1 Meaning and call - FTP_STORE
Meaning
This function call transfers a data block (file DB) from the FTP client (S7-CPU) to the FTP
server.
You need to specify the data block that contains the file. You will also have to select the
path/file name under which the file will be created on the FTP server.
If the file (file DB) already exists on the FTP server, it will be overwritten.
Call interface
FTP_STORE
BOOL
BOOL
BOOL
INT
WORD
ACT
STATUS
ERROR
DONE
ID
ANY
WORD
FILE_NAME
LADDR
BUFFER_DB_NR INT
FILE_DB_NR INT


Example of a call in STL representation

STL Explanation
call fc41 (
ACT:= M 420.0,
ID:= 4,LADDR:= W#16#3FFD,
FILE_NAME := P#DB40.DBX 170.0 BYTE 220,
BUFFER_DB_NR:= 9,
FILE_DB_NR:= 42,
DONE:= M 420.1,
ERROR:= M 420.2,
STATUS:= MW 422);
//FTP_STORE block call
// Job triggered by memory bit
// FTP connection ID acc. to configuration
// Module address acc. to configuration
// Information for destination file in DB40
// Buffer area for FTP service
// DB no. of source file


FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
68 Programming Manual, 03/2008, C79000-G8976-C229-01
2.4.4.2 Explanation of the formal parameters - FTP_STORE
Explanation of the general call parameters
The general parameters have the same significance in every FTP function call; they are
therefore described in one section.
Explanation of the formal parameters specific to the call
Table 2-12 Formal parameters for FTP_STORE
Parameter Declaration Data type Description
FILE_NAME INPUT ANY
(only the
following are
permitted as
VARTYPE:
BYTE)
This parameter specifies the data destination.
(for further details, refer to the following table)
Here, you specify the address and length of the data area in which the
target data are entered.
The address references a data block area.
The ANY pointer data type is used to address this area. For more
detailed information on this data type, refer to the STEP 7 online help
under the appendix topic "Format of the parameter type ANY".
BUFFER_DB_
NR
INPUT INT Here, you enter a data block required as a buffer area by the FTP
client for FTP transfer.
You can use the same data block as the buffer area for all FTP jobs.
Note:
The length of the reserved DB must be at least 255 bytes!
FILE_DB_NR INPUT INT The data block specified here contains the file DB to be read.

Parameter FILE_NAME
This parameter record has the following content for FTP_STORE:

Relative
address
2)

Name Type
1)
Example Meaning
0.0 ip_address STRING[100] '142.11.25.135' IP address of the FTP server.
102.0 username STRING[32] 'user' User name for the login on the FTP server.
136.0 password STRING[32] 'password' Password for the login on the FTP server.
170.0 filename STRING[220] 'plant1/tank2/pressure.dat' Name of the destination or source file
1)
in each case, the maximum possible string length is specified
2)
The specified values relate to the string lengths specified in "Type".
Note: The rows shown on a gray background are irrelevant for this call.
FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 69
2.4.5 FC42 FTP_RETRIEVE
2.4.5.1 Meaning and call - FTP_RETRIEVE
Meaning
This function call transfers a file from the FTP server to the FTP client (S7-CPU).
You need to specify the data block in which the file will be entered. You will also have to
select the path/file name under which the file is located on the FTP server.
If the data block (file DB) on the FTP client already contains a file, it will be overwritten.
Call interface
FTP_RETRIEVE
BOOL
BOOL
BOOL
INT
WORD
ACT
STATUS
ERROR
DONE
ID
ANY
WORD
FILE_NAME
LADDR
BUFFER_DB_NR INT
FILE_DB_NR INT


Example of a call in STL representation

STL Explanation
call fc42 (
ACT:= M 420.0,
ID:= 4,
LADDR:= W#16#3FFD,
FILE_NAME := P#DB40.DBX 170.0 BYTE 220,
BUFFER_DB_NR:= 9,
FILE_DB_NR:= 42,
DONE:= M 420.1,
ERROR:= M 420.2,
STATUS:= MW 422);
//FTP_RETRIEVE block call
// Job triggered by memory bit
// FTP connection ID acc. to configuration
// Module address acc. to configuration
// Information for source file in DB40
// Buffer area for FTP service
// DB no. of destination file


FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
70 Programming Manual, 03/2008, C79000-G8976-C229-01
2.4.5.2 Explanation of the formal parameters - FTP_RETRIEVE
Explanation of the general call parameters
The general parameters have the same significance in every FTP function call; they are
therefore described in one section.
Explanation of the formal parameters specific to the call
Table 2-13 Formal parameters for FTP_RETRIEVE
Parameter Declaration Data type Description
FILE_NAME INPUT ANY
(only the
following are
permitted as
VARTYPE:
BYTE)
This parameter specifies the data source.
(for further details, refer to the following table)
Here, you specify the address and length of the data area in which the
target data are entered.
The address references a data block area.
The ANY pointer data type is used to address this area. For more
detailed information on this data type, refer to the STEP 7 online help
under the appendix topic "Format of the parameter type ANY".
BUFFER_DB_
NR
INPUT INT Here, you enter a data block required as a buffer area by the FTP
client for FTP transfer.
You can use the same data block as the buffer area for all FTP jobs.
Note:
The length of the reserved DB must be at least 255 bytes!
FILE_DB_NR INPUT INT The data block specified here contains the file DB to be written (data
destination).

FILE_NAME parameter
This parameter record has the following content for FTP_RETRIEVE:

Relative
address
2)

Name Type
1)
Example Meaning
0.0 ip_address STRING[100] '142.11.25.135' IP address of the FTP server.
102.0 username STRING[32] 'user' User name for the login on the FTP server.
136.0 password STRING[32] 'password' Password for the login on the FTP server.
170.0 filename STRING[220] 'plant1/tank2/pressure.dat' Name of the destination or source file
1)
in each case, the maximum possible string length is specified
2)
The specified values relate to the string lengths specified in "Type".
Note: The rows shown on a gray background are irrelevant for this call.
FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 71
2.4.6 FC43 FTP_DELETE
2.4.6.1 Meaning and call - FTP_DELETE
Meaning
With this function call, you delete a file on the FTP server.
Call interface
FTP_DELETE
BOOL
BOOL
BOOL
INT
WORD
ACT
STATUS
ERROR
DONE
ID
ANY
WORD
FILE_NAME
LADDR
BUFFER_DB_NR INT


Example of a call in STL representation

STL Explanation
call fc43 (
ACT:= M 420.0,
ID:= 4,
LADDR:= W#16#3FFD,
FILE_NAME := P#DB40.DBX 170.0 BYTE 220,
BUFFER_DB_NR:= 9,
DONE:= M 420.1,
ERROR:= M 420.2,
STATUS:= MW 422);
//FTP_DELETE block call
// Job triggered by memory bit
// FTP connection ID acc. to configuration
// Module address acc. to configuration
// Information for destination file in DB40
// Buffer area for FTP service


2.4.6.2 Explanation of the formal parameter - FTP_DELETE
Explanation of the general call parameters
The general parameters have the same significance in every FTP function call; they are
therefore described in one section.
FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
72 Programming Manual, 03/2008, C79000-G8976-C229-01
Explanation of the formal parameters specific to the call
Table 2-14 Formal parameters for FTP_DELETE
Parameter Declaration Data type Description
FILE_NAME INPUT ANY
(only the
following are
permitted as
VARTYPE:
BYTE)
This parameter specifies the data destination.
(for further details, refer to the following table)
Here, you specify the address and length of the data area in which the
target data are entered.
The address references a data block area.
The ANY pointer data type is used to address this area. For more
detailed information on this data type, refer to the STEP 7 online help
under the appendix topic "Format of the parameter type ANY".
BUFFER_DB_
NR
INPUT INT Here, you enter a data block required as a buffer area by the FTP
client for FTP transfer.
You can use the same data block as the buffer area for all FTP jobs.
Note:
The length of the reserved DB must be at least 255 bytes!

LOGIN parameter
This parameter record has the following content for FTP_DELETE:

Relative
address
2)

Name Type
1)
Example Meaning
0.0 ip_address STRING[100] '142.11.25.135' IP address of the FTP server.
102.0 username STRING[32] 'user' User name for the login on the FTP server.
136.0 password STRING[32] 'password' Password for the login on the FTP server.
170.0 filename STRING[220] 'plant1/tank2/pressure.dat' Name of the destination or source file
1)
in each case, the maximum possible string length is specified
2)
The specified values relate to the string lengths specified in "Type".
Note: The rows shown on a gray background are irrelevant for this call.
FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 73
2.4.7 FC44 FTP_QUIT
2.4.7.1 Meaning and call - FTP_QUIT
Meaning
With this function call, you establish the FTP connections selected with the ID.
Call interface
FTP_QUIT
BOOL
BOOL
BOOL
INT
WORD
ACT
STATUS
ERROR
DONE
ID
WORD LADDR


Example of a call in STL representation

STL Explanation
call fc44 (
ACT:= M 420.0,
ID:= 4,
LADDR:= W#16#3FFD,
DONE:= M 420.1,
ERROR:= M 420.2,
STATUS:= MW 422);

//FTP_QUIT block call
// Job triggered by memory bit
// FTP connection ID acc. to configuration
// Module address acc. to configuration



NOTICE
The output of FC44 must be assigned a memory word as value. If you enter DBx.DWy, an
error message is displayed (applies only to S7-300).

2.4.7.2 Explanation of the formal parameters - FTP_QUIT
Explanation of the general call parameters
The general parameters have the same significance in every FTP function call; they are
therefore described in one section.
FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
74 Programming Manual, 03/2008, C79000-G8976-C229-01
2.4.8 Parameters for CP and connection assignment (input parameters)
Parameters for CP and connection assignment (input parameters)
Apart from the input parameters specific to the jobs started with each FTP block call, the
following general input parameters must also have values supplied to them:

Parameter Declaration Type
1)
Possible
values
Meaning
ACT INPUT BOOL 0,1 The parameter contains the initialization bit for triggering the job.
If ACT = 1, the job is executed.
During job execution, the FC returns the following codes:
DONE=0
ERROR=0
STATUS=8181H
If ACT = 0, the called FC does not execute any actions; the
status codes are then as follows for these parameters settings:
DONE=0
ERROR=1
STATUS=8F70H
Note / recommendation:
You should execute the FTP calls conditionally in your application,
for example by evaluating the codes. It is not a good idea to
control the call using the ACT bit.
The ACT bit must be set to 1 until the execution is signaled by the
DONE bit.
ID INPUT INT 1,2...64 The FTP jobs are handled on FTP connections. The parameter
identifies the connection being used.
LADDR INPUT WORD Module start address
When you call an FC, you transfer the module start address of the
ADVANCED-CP in the LADDR parameter.
You will find the module start address of the ADVANCED-CP in
the configuration of the properties of the ADVANCED-CP in
"Addresses > Inputs".


CAUTION
Make sure that only one FTP client block is called per ID used as long as ACT = 1 is set.
For example, FC STORE and FC RETRIEVE must not be active on the same FTP
connection at the same time. This corresponds to normal FTP functionality. If this is
nevertheless attempted, you cannot rely on the output parameters (DONE bit, ERROR bit
and STATUS word) being correct.

FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 75
2.4.9 Status information (output parameters)
Status information (output parameters)
For status evaluation, the following parameters must be evaluated in the user program:

Parameter Declaration Type
1)
Possible
values
Meaning
DONE OUTPUT BOOL 0: -
1: Job done
This parameter indicates whether or not the job was completed
without errors.
ERROR OUTPUT BOOL 0: -
1: Error
Error code
This parameter signals that the job could not be executed error-
free.
STATUS OUTPUT WORD See
following
table
Status code
This parameter supplies detailed information about the execution
of the job.


NOTICE
For FC FTP_QUIT, use only the data type memory word for the STATUS parameter
(applies only to the CP 343-1 IT).


Example
During job execution, the FC returns the following codes:
DONE=0
ERROR=0
STATUS=8181H
Evaluating status codes
Remember that the status codes DONE, ERROR, STATUS are updated at each block call.


Note
For entries coded with 8FxxH in STATUS, refer to the information in the STEP 7 Standard
and System Functions reference manual. The chapter describing error evaluation with the
RET_VAL output parameter contains detailed information



FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
76 Programming Manual, 03/2008, C79000-G8976-C229-01
DONE ERROR STATUS Meaning
1 0 0000H Job completed without error.
0 0 0000H No job being executed.
0 0 8181H Job active.
0 1 8090H No module with this module start address exists.
The FC being used does not match the system family being used (remember to use
different FCs for S7300 and S7400).
0 1 8091H Module start address not at a doubleword boundary.
0 1 8092H Type information in the ANY pointer is not byte.
0 1 80A4H The communication bus connection between the CPU and CP is not established. (with
newer CPU versions).
This can, for example, be caused by the following:
No connection configuration;
The maximum number of CPs that can be operated at the same time has been
exceeded.
0 1 80B0H The module does not recognize the data record.
0 1 80B1H Destination area invalid.
for example, destination area > 240 bytes.
0 1 80B2H The communication bus connection between the CPU and CP is not established (with
older CPU versions; otherwise 80A4H; for further information, refer to this code)
0 1 80C0H The data record cannot be read.
0 1 80C1H The specified data record is currently being processed.
0 1 80C2H There are too many jobs pending.
0 1 80C3H Resources occupied (memory).
0 1 80C4H Communication error (occurs temporarily, it is usually best to repeat the job in the user
program).
0 1 80D2H Module start address incorrect.
0 1 8183H The configuration does not match the job parameters.
0 1 8184H Bad data type specified for the FILE_NAME / LOGIN parameter.
0 1 8186H ID parameter invalid. ID != 1,2....64.
0 1 8F22H Source area invalid, for example:
Area does not exist in the DB
0 1 8F24H Area error reading a parameter.
0 1 8F28H Alignment error reading a parameter.
0 1 8F32H Parameter contains a DB number that is too high.
0 1 8F33H DB number error.
0 1 8F3AH Area not loaded (DB).
0 1 8F50H File DB DB 0 or DB does not exist
0 1 8F51H Specified file DB data area larger than existing data area
0 1 8F52H File DB in write-protected memory
0 1 8F53H File DB max. length < current length
0 1 8F54H File DB does not contain any valid data
0 1 8F55H Header status bit: Locked
0 1 8F56H The NEW bit in the file DB header was not reset
0 1 8F57H The FTP client does not have write access to the file DB but rather the FTP server
(header status bit: WriteAccess)
FCs / FBs for Industrial Ethernet
2.4 FBs / FCs for FTP services
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 77
DONE ERROR STATUS Meaning
0 1 8F5AH Buffer DB DB 0 or DB does not exist
0 1 8F5BH Buffer DB data area too short
0 1 8F5CH Buffer DB in write-protected memory
0 1 8F60H Bad user data, for example bad IP address of the FTP server
0 1 8F61H FTP server not obtainable
0 1 8F62H Job not supported or rejected by FTP server
0 1 8F63H File transfer aborted by the FTP server
0 1 8F64H Error on the FTP control connection; data could not be sent or received; the FTP
control connection must be established again after such an error.
0 1 8F65H Error on the FTP data connection; data could not be sent or received; the job
(FTP_STORE or FTP_RETRIEVE) must be called again.
This error can, for example, be caused by FTP_RETRIEVE when the addressed file is
already open on the FTP server.
0 1 8F66H Error reading/writing data from/to the CPU (for example DB does not exist or too short)
0 1 8F67H Error in the FTP client on the IP-CP; for example attempting to open more than 10 FTP
connections.
0 1 8F68H The job was rejected by the FTP client
This error can, for example, be caused by FTP_RETRIEVE when the value for the
parameter MAX_LENGTH was selected too low in the file DB header.
0 1 8F69H FTP connection in the incorrect status for this call, for example a double connect call or
when attempting to retrieve without previously connecting (using the same NetPro ID)
0 1 8F6AH No new socket could be opened, temporary resource problem, repeat the block call.
0 1 8F70H Calling an FTP client block with ACT = 0
0 1 8F7FH Internal error, for example illegal ANY reference

FCs / FBs for Industrial Ethernet
2.5 FBs for programmed connections
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
78 Programming Manual, 03/2008, C79000-G8976-C229-01
2.5 FBs for programmed connections
2.5.1 FB 55 IP_CONFIG - meaning and call
Meaning of the block
Connections can be specified in a DB (configuration DB) and transferred to the CP with an
FB.
You can use this variant of programmed communication connections as an alternative to
connection configuration with STEP 7.
With the function block FB55, a configuration data block (CONF_DB) is transferred to the
CP. The configuration data block contains all the connection data for an Ethernet CP.
Depending on the size of the configuration DB, the data may be transferred to the CP in
several segments. This means that the FB must continue to be called until the FB signals
complete transfer by setting the DONE bit to 1.

Note
Read the description of the configuration data block CONF_DB.

Call
Call interface in FBD representation
lP_CONFlG
lNT
BOOL
BOOL
ANY
WORD
WORD
WORD EXT_STATUS
STATUS
ERROR
DONE
LEN
CONF_DB
LADDR
BOOL ACT BOOL

Example in STL representation

STL Explanation
call fb 55(
ACT:=M 10.0,
LADDR:=W#16#0100,
CONF_DB:= P#db99.dbx10.0 byte 240,
LEN:=MW 14,
DONE:=M 10.1,
ERROR:=M 10.2,
STATUS:=MW 16,
EXT_STATUS :=MW 18);
//IP_CONFIG block call
//Job initiated by memory bit
//=LADDR 256 dec. in hardware configuration
//Data block with connection data
//Length info for the connection data
//Execution code
//Error code
//Status code
//Cause of error in connection data
FCs / FBs for Industrial Ethernet
2.5 FBs for programmed connections
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 79
2.5.2 How IP_CONFIG works
Operating principle
The following diagram illustrates the normal sequence of connection configuration triggered
by an IP_CONFIG in the user program.
The job executes as soon as the parameter ACT is transferred with value 1.
Due to the segmented transfer of the CONF_DB, you will need to repeat the job with ACT =
1 until completion of the job is indicated in the parameters DONE, ERROR, and STATUS.
If you want to transfer a connection configuration again later, the parameter ACT must first
be transferred with value 0 in at least one further call.
Call lP_CONFlG
Ethernet-CP
Call lP_CONFlG
Call lP_CONFlG
Call lP_CONFlG
0,0, job active 1)
Time
Supply CONF_DB with
data
User program
(CPU cycle)
Time
CP is supplied with system
data (incl. lP address);
Connections are configured
on the CP.
1) Parameter transfer DONE, ERROR, STATUS
Set ACT = 1
0,0, job active 1)
.
.
CONF_DB is
transferred in segments
Job completed without errors 1)
Set ACT = 0



NOTICE
The data transferred with the configuration DB are stored in volatile memory on the CP and
must be downloaded to the CP again following a power down!

FCs / FBs for Industrial Ethernet
2.5 FBs for programmed connections
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
80 Programming Manual, 03/2008, C79000-G8976-C229-01
2.5.3 Explanation of the formal parameters - IP_CONFIG
Explanation of the formal parameters
The following table explains the formal parameters for the call interface of the IP_CONFIG
function block :

Parameter Declaration Data type Possible values Description
ACT INPUT BOOL 0,1 When the FB is called with ACT = 1, the DBxx is sent
to the CP.
If the FB is called with ACT = 0, only the status codes
DONE, ERROR and STATUS are updated.
LADDR INPUT WORD Module start address
When you configure the CP with STEP 7 HW Config,
the module start address is displayed in the
configuration table. Specify this address here.
CONF_DB INPUT ANY The parameter points to the start address of the
configuration data area in a data block (data type:
byte).
LEN INPUT INT Length information in bytes for the configuration data
area.
DONE OUTPUT BOOL 0: -
1: Job completed with
data transfer.
The parameter indicates whether the configuration data
area was completely transferred.
Remember that it may be necessary to call the FB
several times depending on the size of the
configuration data area (in several cycles) until the
DONE parameter is set to 1 to signal completion of the
transfer.
For the meaning of this parameter in conjunction with
the ERROR and STATUS parameters, refer to the
following table.
ERROR OUTPUT BOOL 0: -
1: Error
Error code
For the meaning of this parameter in conjunction with
the DONE and STATUS parameters, refer to the
following table.
STATUS OUTPUT WORD See following table Status code
For the meaning of this parameter in conjunction with
the DONE and ERROR parameters, refer to the
following table.
EXT_
Status
OUTPUT WORD If an error occurs in the execution of a job, the
parameter indicates which parameter was detected as
the cause of the error in the configuration DB.
High byte: Index of the parameter field
Low byte: Index of the subfield within the parameter
field

FCs / FBs for Industrial Ethernet
2.5 FBs for programmed connections
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 81
2.5.4 Reserved port numbers - IP_CONFIG
Reserved Port Numbers
The following local port numbers are reserved; do not use these in the connection project
engineering.
Table 2-15 Reserved Port Numbers
Protocol Port number Service
TCP 20, 21 FTP
TCP 25 SMTP
TCP 80 HTTP
TCP 102 RFC1006
TCP 135 RPC-DCOM
TCP 502 ASA application protocol
UDP 161 SNMP_REQUEST
UDP 34964 PN IO
UDP 65532 NTP
UDP 65533 NTP
UDP 65534 NTP
UDP 65535 NTP

2.5.5 Condition codes of the IP_CONFIG block
Condition codes
The following table shows the condition codes formed based on DONE, ERROR and
STATUS that must be evaluated by the user program.
Table 2-16 Condition codes for FB55 IP_CONFIG
DONE ERROR STATUS Meaning
General codes relating to job execution
1 0 0000H Job completed without errors
0 0 8181H Job active
Errors detected on the interface between CPU and CP.
0 1 80A4H Communication error on the K-bus
or
Data error: Configuration by the user program is not set.
0 1 80B1H The number of data bytes to be sent exceeds the upper limit for this service. (upper
limit = 16 Kbytes)
FCs / FBs for Industrial Ethernet
2.5 FBs for programmed connections
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
82 Programming Manual, 03/2008, C79000-G8976-C229-01
DONE ERROR STATUS Meaning
0 1 80C4H Communication error
The error can occur temporarily; it is usually best to repeat the job in the user program.
0 1 80D2H Configuration error
The module you are using does not support this service.
Errors detected in the evaluation of the FB in the CPU or on the interface between CPU and CP.
0 1 8183H The CP rejects the requested data record number.
0 1 8184H System error or bad parameter type. (data type of the ANY pointer CONF_DB not OK)
(Currently only the byte data type is accepted)
0 1 8185H The value of the LEN parameter is larger than the CONF_DB less the reserved header
(4 bytes) or the length information is incorrect.
0 1 8186H Illegal parameter detected
The ANY pointer CONF_DB does not point to a data block.
0 1 8187H Illegal status of the FB
Data in the header of CONF_DB was possibly overwritten.
Further errors detected on the interface between the CPU and CP.
0 1 8A01H The status code in the data record is invalid (value is >= 3).
0 1 8A02H There is no job running on the CP; the FB, however, expected an acknowledgment for
a completed job.
0 1 8A03H There is no job running on the CP and the CP is not ready; the FB triggered the first job
to read a data record.
0 1 8A04H There is no job running on the CP and the CP is not ready; the FB nevertheless
expected an acknowledgment for a completed job.
0 1 8A05H There is a job running, but there was no acknowledgment; the FB nevertheless
triggered the first job for a read data record job.
0 1 8A06H A job is complete but the FB nevertheless triggered the first job for a read data record
job.
Errors detected when evaluating the FB on the CP.
0 1 8B01H Communication error
The DB could not be transferred.
0 1 8B02H Parameter error
Double parameter field
0 1 8B03H Parameter error
The subfield in the parameter field is not permitted.
0 1 8B04H Parameter error
The length specified in the FB does not match the length of the parameter fields /
subfields.
0 1 8B05H Parameter error
The length of the parameter field is invalid.
0 1 8B06H Parameter error
The length of the subfield is invalid.
0 1 8B07H Parameter error
The ID of the parameter field is invalid
0 1 8B08H Parameter error
The ID of the subfield is invalid
FCs / FBs for Industrial Ethernet
2.5 FBs for programmed connections
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 83
DONE ERROR STATUS Meaning
0 1 8B09H System error
The connection does not exist
0 1 8B0AH Data error
The content of the subfield is not correct.
0 1 8B0BH Structure error
A subfield exists twice.
0 1 8B0CH Data error
The parameter does not contain all the necessary parameters.
0 1 8B0DH Data error
The CONF_DB does not contain a parameter field for system data.
0 1 8B0EH Data error / structure error
The CONF_DB type is invalid.
0 1 8B0FH System error
The CP does not have enough resources to process CONF_DB completely.
0 1 8B10H Data error
Configuration by the user program is not set.
0 1 8B11H Data error
The specified type of the parameter field is invalid.
0 1 8B12H Data error
Too many connections were specified (either in total or too many for a specific type; for
example, only one Email connection is possible).
0 1 8B13H CPinternal error
0 1 8B14H The active protection level does not permit the change that will result from the action.
Further errors detected on the program interfaces within the CPU (SFC errors).
0 1 8F22H Area length error reading a parameter (e.g. DB too short).
0 1 8F23H Area length error writing a parameter (e.g. DB too short).
0 1 8F24H Area error reading a parameter.
0 1 8F25H Area error writing a parameter.
0 1 8F28H Alignment error reading a parameter.
0 1 8F29H Alignment error writing a parameter.
0 1 8F30H The parameter is in the writeprotected first current data block.
0 1 8F31H The parameter is in the writeprotected second current data block.
0 1 8F32H The parameter contains a DB number that is too high.
0 1 8F33H DB number error
0 1 8F3AH The target area was not loaded (DB).
0 1 8F42H Timeout reading a parameter from the I/O area.
0 1 8F43H Timeout writing a parameter to the I/O area.
0 1 8F44H Access to a parameter to be read during block execution is prevented.
0 1 8F45H Access to a parameter to be written during block execution is prevented.
0 1 8F7FH Internal error
For example, an illegal ANY reference was detected.

FCs / FBs for Industrial Ethernet
2.6 Configuration limits / resources required by the FCs and FBs (Ethernet)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
84 Programming Manual, 03/2008, C79000-G8976-C229-01
2.6 Configuration limits / resources required by the FCs and FBs
(Ethernet)
Required resources
NOTICE
Please note the version information of the blocks. Blocks with other versions have different
resource requirements.

Table 2-17 Information for FCs / FBs with an S7-400
NAME Version FC/FB no. Load memory
bytes
Work memory
bytes
MC7
bytes
Local data
bytes
AG_SEND 1.1 FC5 732 576 540 20
AG_RECV 1.1 FC6 656 522 486 20
AG_LOCK 1.0 FC7 272 200 164 6
AG_UNLOCK 1.0 FC8 256 186 150 6
AG_LSEND 3.0 FC50 1044 846 810 52
AG_LRECV 3.0 FC60 1190 992 956 58
AG_SSEND 1.0 FC53 1642 1386 1350 118
AG_SRECV 1.0 FC63 1600 1356 1320 122
FTP_CMD 1.0 FB40 1998 1726 1690 58
FTP_CONNECT 1.0 FC40 1482 1236 1200 86
FTP_STORE 1.0 FC41 1794 1514 1478 102
FTP_RETRIEVE 1.0 FC42 1934 1642 1606 106
FTP_DELETE 1.0 FC43 1478 1232 1196 86
FTP_QUIT 1.0 FC44 968 796 760 46

Table 2-18 Information for FCs / FBs with an S7-300
NAME Version FC/FB no. Load memory
bytes
Work memory
bytes
MC7
bytes
Local data
bytes
AG_SEND 4.2 FC5 1976 1664 1628 50
AG_RECV 4.7 FC6 1440 1206 1170 40
AG_LOCK 4.0 FC7 748 636 600 34
AG_UNLOCK 4.0 FC8 712 604 568 32
AG_CNTRL 1.0 FC10 1402 1138 1102 82
IP_CONFIG 1.1 FB55 2478 2056 2020 62
FTP_CMD 1.0 FB40 2590 2240 2204 70
FTP_CONNECT 1.1 FC40 928 774 738 68
FTP_STORE 1.1 FC41 1232 1046 1010 74
FCs / FBs for Industrial Ethernet
2.6 Configuration limits / resources required by the FCs and FBs (Ethernet)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 85
NAME Version FC/FB no. Load memory
bytes
Work memory
bytes
MC7
bytes
Local data
bytes
FTP_RETRIEVE 1.1 FC42 1310 1118 1082 84
FTP_DELETE 1.1 FC43 922 770 734 68
FTP_QUIT 1.1 FC44 452 370 334 28


Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 87
FCs / FBs for PROFINET
3
3.1 FBs for PROFINET CBA
3.1.1 FB88 PN_InOut / FB90 PN_InOut_Fast - meaning and call
How It works
The task of function block FB88 / FB90 is to transfer data from the interface DB to the CP
and from the CP to the interface DB. The interface DB itself is the interface to the user
program.
FB88 / FB90 is called cyclically. It is also possible to call FB88 /FB90 more than once in a
cycle.
At its interface, FB88 /FB90 only needs to be supplied with the module address of the CP.
To ensure data consistency, you can only modify the data to be transferred or start to read
the received data when the job is completed (DONE=1 or ERROR=1).
As soon as DONE=1 or ERROR=1 is set, the transfer is complete or has been terminated
with an error message. Data can now be evaluated or set again. Data will only be transferred
with the next call.
In your user program, make sure that on completion of data transfer FB88 /FB90 is called
again only after all the input data has been read and all output data has been written to the
interface DB.
Calling the FB88 / FB90 blocks time-driven is permitted in principle. Refer to the notes on
this mode later in this chapter.
Differences between FB88 and FB90
The activities of the function blocks FB90 and FB88 on the interface to the user program are
largely identical. You can use FB90 with certain CP/CPU types with an S7-400; refer to the
information in the manual of the CP.
If FB90 is approved for the CP type being used, we recommend that you use it. As a result,
you can achieve shorter reaction times than with FB88. You should, however, remember the
constraints regarding its use.
The following points apply:
The interface parameters are identical;
For FB90, there are several additional codes in the STATUS parameter;
FCs / FBs for PROFINET
3.1 FBs for PROFINET CBA
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
88 Programming Manual, 03/2008, C79000-G8976-C229-01
With some errors, there are different codes in the STATUS parameter of FB88 and FB90;
There are differences in the configuration limits of the interface DB (see relevant manual).



Note
For more detailed information on handling the interface DB, refer to the SIMATIC iMap
documentation.
NOTICE

When you reload user program blocks, data consistency is only guaranteed if the CPU
is first changed to STOP.
How supplied - block library
FB88 and FB90 are supplied with SIMATIC iMap. There are different block types for S7-300
and S7-400.
After installation, the blocks are available in the PROFINET Library under
"PROFINET_System_Library/CP300 or /CP400".
Call interface
Call interface in FBD representation
PN_InOut / PN_InOut_Fast
BOOL
WORD
WORD STATUS
ERROR
DONE LADDR BOOL


Example of a call in STL representation

STL Explanation
Call FB 88 , DB88 (
LADDR:=W#16#0120,
DONE:=M 99.1,
ERROR:=M 99.0,
STATUS:=MW 104);
//Block call with instance DB88

FCs / FBs for PROFINET
3.1 FBs for PROFINET CBA
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 89
3.1.2 Explanation of the formal parameters - PN_InOut / PN_InOut_Fast
Explanation of the formal parameters
The following table explains all the formal parameters for FB88 / FB90:

Parameter Declaration Data type Description
LADDR INPUT WORD Module start address
When you configure the CP, the module start address is displayed in
the configuration table. Specify this address here.
Do not modify the parameter until the job is completed (DONE=1 or
ERROR=1).
DONE OUTPUT BOOL Reports the (positive) completion of a job.
ERROR OUTPUT BOOL This indicates that the job could not be executed errorfree.
STATUS OUTPUT WORD This parameter supplies detailed information about the execution of
the job. Status codes can be returned during execution of the job
(DONE=0 and ERROR=0).

3.1.3 Condition codes of the PN_InOut and PN_InOut_Fast blocks
Evaluating status codes
Remember that the status codes DONE, ERROR, STATUS are updated at each block call.
The following table shows the condition codes formed based on DONE, ERROR and
STATUS that must be evaluated by the user program.
Table 3-1 Codes for PN_InOut (FB88) and PN_InOut_Fast (FB90)
DONE ERROR STATUS Meaning
1 0 0000H Job completed without error.
0 0 0000H No job being processed; the block can be called.
0 0 8181H Job active.
or
(only with FB90): Connection establishment to addressed module active (see also
information under 8090H).
0 1 8183H (S7-300 only)
The service has not yet started; data acceptance is not yet possible.
0 1 8184H Bad instance DB, generally triggered by illegal writing of the instance DB by the
user program.
or
(only with FB90)
Bad send or receive job.
0 1 8085H (only with FB90)
Bad interface DB.
FCs / FBs for PROFINET
3.1 FBs for PROFINET CBA
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
90 Programming Manual, 03/2008, C79000-G8976-C229-01
DONE ERROR STATUS Meaning
0 1 8090H (S7-400 only)
Parameter assignment error
An incorrect module address was specified; the address points to an empty slot.
Note (only with FB90):
In the following cases, the value 8181H is shown in STATUS (job active); In actual fact,
there is no communication:
The address points to a slot that contains a different module type.
The addressed module is configured for PROFINET CBA operation.
0 1 80A1H (only with FB90)
Possible communications errors:
Stationinternal connection to addressed module being terminated;
The configuration limits for connections of the CPU has been exceeded;
The interface is being reinitialized.
0 1 80B0H (S7-300 only)
Block error: The data record number is wrong.
This status can also occur after the following actions:
Cold or warm restart after power DOWN/UP
Cold or warm restart on the CPU
0 1 80B1H (S7-300 only)
Block error: Data record length or offset wrong.
0 1 80B3H (S7-300 only)
Parameter error: Wrong CP address.
0 1 80C1H (S7-300 only)
Temporary error: The specified data record is currently being processed.
0 1 80C2H (S7-300 only)
Temporary error: There is a job bottleneck; the data record cannot be read yet.
0 1 80C3H (S7-300 only)
Temporary error: Resources occupied (memory).
0 1 80C4H (S7-300 only)
Communication error: Occurs temporarily and a repetition in the user program will often
remedy the problem.
0 1 80D0H (S7-300 only)
Configuration error:
The maximum number of blocks of input and output data has been exceeded; the
interface DB is too large.
0 1 80D1H (S7-300 only)
Configuration error
Possible causes:
The interface of the configured component does not match the one used in the
program (outputs).
The wrong module was inserted; The PROFINET service is not supported.
FCs / FBs for PROFINET
3.1 FBs for PROFINET CBA
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 91
DONE ERROR STATUS Meaning
0 1 80D2H (S7-300 only)
Configuration error
Possible causes:
The interface of the configured component does not match the one used in the
program (inputs).
The wrong module was inserted; The PROFINET service is not supported.
Parameter error: Wrong CP address
0 1 8322H (only with FB90)
Bad interface DB.
0 1 8332H (only with FB90)
The number of the interface DB is too high.
0 1 833AH (only with FB90)
Access to the interface DB is not possible (possibly because the interface DB was
deleted).
0 1 8623H (only with FB90)
Bad interface DB.
0 1 863AH (only with FB90)
Access to the interface DB is not possible (possibly because the interface DB was
deleted).

To find out which SFCs are used that are relevant for error evaluation, display the properties
dialog of the FB described here in the "Calls" tab.

Note
For entries with the coding 8FxxH (for S7-300) or 8xxxH (for S7-400) under STATUS, note
the information in the Reference Manual STEP 7 Standard and System Functions. The
chapter describing error evaluation with the RET_VAL output parameter contains detailed
information

Status codes during CP startup
With a complete restart or restart of the PROFINET CP (after activating a switch on the
module), the output parameters of the block are reset as follows:
DONE = 0
ERROR = 0
STATUS = 8181H
FCs / FBs for PROFINET
3.1 FBs for PROFINET CBA
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
92 Programming Manual, 03/2008, C79000-G8976-C229-01
3.1.4 Timedriven PN_InOut / PN_InOut_Fast call - recommendation on application
Timedriven call - recommendation on application
If your application requires timedriven transfer of the CBA data instead of cyclic or event-
driven processing, we recommend the following procedure to call the FB88 / FB90 blocks.
If you use a timedriven call, remember that the block must be called repeatedly after it has
been started until the DONE flag is set. To allow the CBA data to be copied between the
CPU and CP without any longer interruptions, the followon calls should be as fast as
possible and independent of the timing.
Note the following recommendations for programming:
The timing is provided by a timer OB; the timer OB should only cause the first call for the
PROFINET CBA blocks FB88 or FB90 not by calling the block directly but, for example,
by setting a start flag.
The call of the PROFINET CBA blocks FB88 and FB90 should then always be made in
OB1; OB1 starts the call as soon as the start flag is set by the timer OB.
After the first block call, this is repeated in OB1 until the DONE bit is set (or until an error
occurs); the start flag must then be reset.
Result:
The CBA user data can be copied between the CPU and CP without any significant
interruption thanks to separating the timer OB from the actual block calls in OB1. You can
select the interval between the first calls depending on the requirements of your application.

FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 93
3.2 FCs/FBs for PROFINET IO (S7-300)
3.2.1 Overview of FCs/FBs and their use
Overview
The FCs listed below are available for transferring data cyclically on the PROFINET IO
interface. The significance of the FCs differs depending on how you use the CP (as a
PROFINET IO controller or PROFINET IO device) in an S7 station.

can be used with: FC
S7-300 S7-400
Meaning
PNIO_SEND (FC11) x - Depending on the mode of the CP:
For a PROFINET IO controller
Sending output data to the
PROFINET IO devices.
On a PROFINET IO device
Forwarding process input data to the
PROFINET IO controller.
PNIO_RECV (FC12) x - Depending on the mode of the CP:
On a PROFINET IO controller
Receiving process input data from
the PROFINET IO devices.
On a PROFINET IO device
Receiving process output data from
the PROFINET IO controller.
For CPs operating as PROFINET IO controller and IO device at the same time, the FCs as
of version 2.0 are available.
The FBs listed below are available for transferring data (data records, alarm information)
acyclically on the PROFINET IO interface. The two blocks can only be used in
PROFINET IO controller mode.

can be used with: FB
S7-300 S7-400
Meaning
PNIO_RW_REC (FB52) x - Read data record
(from a PROFINET IO device)
Write data record
(to a PROFINET IO device)
PNIO_ALARM (FB54) x - Receive alarm information from the
PROFINET IO devices

FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
94 Programming Manual, 03/2008, C79000-G8976-C229-01
3.2.2 FC11 PNIO_SEND
3.2.2.1 Meaning and call - PNIO_SEND
How It works
The PNIO_SEND FC is used to transfer data in the PROFINET IO controller or PROFINET
IO device modes of the CP.
Operating as PROFINET IO controller
The block transfers the process data (outputs) of a specified output area to the CP to be
forwarded to PROFINET IO devices and as status display returns the IO consumer status
(IOCS) of the outputs of the PROFINET IO devices.
Operating as PROFINET IO device
The block reads the preprocessed process inputs of the CPU on the PROFINET IO
device and transfers them to the PROFINET IO controller (configured I addresses); the
block also returns the IO Consumer Status (IOCS) of the PROFINET IO controller as a
status display.
The preprocessed process data is available in a DB or bit memory area.
For CPs operating as PROFINET IO controller and IO device at the same time, the FC as of
version 2.0 is available. With the additional MODE parameter, you set the mode for which
the FC will be called.
Call interface (block version 2.0)
Call interface in FBD representation
PNlO_SEND
ANY
BOOL
WORD
lNT WORD
ANY lOCS
STATUS
ERROR
DONE
SEND
LEN
BYTE
CPLADDR
CHECK_lOCS
BOOL
BOOL
MODE


Example in STL representation

STL Explanation
call fc 11(
CPLADDR:=W#16#0100,
MODE:=0,
LEN:=20,
IOCS:=P#DB10.DBX20.0 BYTE 3,
DONE:=M 70.0,
ERROR:=M 70.1,
STATUS:=MW 72,
//PNIO_SEND block call
//Module address from hardware configuration
//Controller mode or device mode
//Length of the data area
//Per send data byte one bit status in DB10
//Address for return parameter DONE
//Address for return parameter ERROR
//Address for return parameter STATUS
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 95
STL Explanation
CHECK_IOCS:=M 70.2,
SEND:=P#DB10.DBX0.0 BYTE 20 );
//Address for return parameter CHECK_IOCS
//Data area to be transferred from DB10
//(20 bytes)

3.2.2.2 Explanation of the formal parameters - PNIO_SEND
Explanation of the formal parameters
The following table explains all the formal parameters for FC11:

Parameter Declaration Data type Possible values Description
CPLADDR INPUT WORD - Module start address
MODE
(parameters
version 2.0 or
later)
INPUT BYTE 0:
IO controller mode
IO device operation
(without parallel
operation)
Not compatible with FC in
version 1.0
1:
IO device mode (both modes
at same time)
Specifies the mode of the CP
Notes on compatibility;:
The version 1.0 FC can continue to
be used as long as the CP is not
being operated as an IO controller
and IO device at the same time.
When MODE=0, the FC as of version
2.0 behaves like the FC version 1.0.
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
96 Programming Manual, 03/2008, C79000-G8976-C229-01
Parameter Declaration Data type Possible values Description
SEND IN_OUT ANY
(as
VARTYPE
only BYTE
is
permitted)
The address of the data area
points to one of the alternatives:
Memory bit area
Data block area
Specifies the address and length
IO controller mode:
The length should match the total length
of the distributed IO configured, whereby
address gaps are also transmitted.
The length can also be shorted than the
total length of the distributed IO, for
example when the block is called more
than once in one OB. It must, however,
have the total length in at least one call.
IO device mode:
The data structure results from the order
of the slots of the input modules
configured for this PROFINET IO device
on the PROFINET IO controller line and
their length without address gaps.
(Please note the more extensive
explanations or examples for your CP in
the devicespecific Part B of this manual)
Notes:
The block begins to transfer the data
at address 0 regardless of how you
configured the addresses (regardless
of the lowest configured address).
Specifying an I/O area is not
permitted since you must first check
the IOCS for GOOD before data can
be accepted in the I/O.
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 97
Parameter Declaration Data type Possible values Description
LEN INPUT INT Value > 0
The maximum total length of the
data areas to be transferred can
be found in the devicespecific
Part B of this manual in the
"Performance data" chapter. This
may differ for controller or device
mode.
Length of the data area to be transferred
in bytes.
The transfer of the data always begins
with address 0 regardless of the
configuration. Please note that the IO
address "0" with a length of 1 is included.
IO controller mode:
The highest configured address of
the devices must be specified here.
The individual areas are not grouped
together.
If the block is called more than once,
LEN can also be shorter than the
highest address. The highest address
should be specified in at least one
call (compare "SEND" parameter).
The data is transferred in the order of
the logical addresses (as with
PROFIBUS DP).

IO device mode:
The data is transferred in the order of
the slots as the configured input
modules on the PROFINET IO
controller chain for this PROFINET IO
device.

Note:
Make sure that the length
programmed here and the
configuration of the PROFINET IO
controller are consistent. The entire
data area length including any gaps
is transferred for the device.
DONE OUTPUT BOOL 0: -
1: New data accepted
This parameter indicates whether or not
the job was completed without errors.
ERROR OUTPUT BOOL 0: -1: Error Error code
STATUS OUTPUT WORD - Status code
CHECK_IOCS OUTPUT BOOL 0: All IOCS set to GOOD
1: At least one IOCS set to BAD
Auxiliary bit that indicates whether or not
it is
necessary to evaluate the IOCS status
area.
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
98 Programming Manual, 03/2008, C79000-G8976-C229-01
Parameter Declaration Data type Possible values Description
IOCS OUTPUT ANY (as
VARTYPE
only BYTE
is
permitted)
The address of the data area
points to one of the alternatives:
Memory bit area
Data block area

Length:
For the maximum value, refer to
the devicespecific Part B of this
manual in the section
"Performance data". This may
differ for controller or device
mode.
A status bit is transferred per byte of user
data.
The length information depends on the
length in the LEN parameter (one bit per
byte)
= (Length LEN + 7/ 8)
Controller mode:
Address gaps are also transferred
according to the SEND parameter.
Address gaps are transferred with the
status GOOD.
Device mode:
Address gaps are not transferred.

The block begins the transfer of the
status for address 0.
Note:
The minimum length of the ANY pointer
is (length LEN + 7/8)


Note
Remember that all output parameters may only be evaluated when the block signals either
DONE = 1 or ERROR = 1.

NOTICE
You must assume that the returned IOCS status does not arrive timesynchronized with the
data (SEND parameter) but delayed by one user program cycle. This means: User data
and IOCS are not consistent.

3.2.2.3 Condition codes of PNIO_SEND
Condition codes
The following table shows the condition codes formed based on DONE, ERROR and
STATUS that must be evaluated by the user program.

Note
For entries coded with 8FxxH in STATUS, refer to the information in the STEP 7 Standard
and System Functions reference manual. The chapter describing error evaluation with the
RET_VAL output parameter contains detailed information.
To find out which SFCs are used and are relevant for error evaluation, display the properties
dialog of the FC described here in the "Calls" tab.

FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 99

Table 3-2 Condition codes PNIO_SEND
DONE ERROR STATUS Meaning
0 0 8180H Data transfer active;
or
The CP is in STOP mode.
0 0 8181H Module does not support block version 2.0.
Remedy: Use block version 1.0.
1 0 0000H New data transferred without error.
0 1 8183H PROFINET IO configuration missing;
or
wrong CPLADDR;
or
The CP is in STOP mode.
or
Interconnection of MODE does not match module configuration or incorrect
interconnection with MODE > 1

Extra in device mode:
The connection between PROFINET IO controller and PROFINET IO device is
down,
or
PROFINET IO controller not reachable
or
Total lengths (configuration and LEN parameter) are not consistent.
0 1 8184H System error or bad parameter type.
0 1 8185H Parameter LEN is greater than source area SEND or target buffer (IOCS) is too small.
0 1 8F22H Area length error reading a parameter (e.g. DB too short).
0 1 8F23H Area length error writing a parameter (e.g. DB too short).
0 1 8F24H Range error when reading a parameter.
0 1 8F25H Range error when writing a parameter.
0 1 8F28H Alignment error when reading a parameter.
0 1 8F29H Alignment error when writing a parameter.
0 1 8F30H Parameter is in the write-protected 1st current data block.
0 1 8F31H Parameter is in the write-protected 2nd current data block.
0 1 8F32H Parameter contains a DB number that is too high.
0 1 8F3AH Destination area is not loaded (DB).
0 1 8F42H Timeout reading a parameter from the I/O area.
0 1 8F43H Timeout writing a parameter to the I/O area.
0 1 8F44H Access to a parameter to be read during block execution is prevented.
0 1 8F45H Access to a parameter to be written during block execution is prevented.
0 1 8F7FH Internal error, e.g. illegal ANY reference.
0 1 8090H Module with this address does not exist.
0 1 80A0H Negative acknowledgment writing to the module.
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
100 Programming Manual, 03/2008, C79000-G8976-C229-01
DONE ERROR STATUS Meaning
0 1 80A1H Negative acknowledgment writing to the module.
0 1 80B0H The module does not recognize the data record.
0 1 80B1H The specified data record length is incorrect.
or
The CP changes to STOP.
0 1 80C0H The data record cannot be read.
0 1 80C1H The specified data record is currently being processed.
0 1 80C2H There are too many jobs pending.
0 1 80C3H Resources occupied (memory).
0 1 80C4H Communication error (occurs temporarily, it is usually best to repeat the job in the user
program).

3.2.3 FC12 PNIO_RECV
3.2.3.1 Meaning and call - PNIO_RECV
How It works
The PNIO_RECV FC is used to accept data in the PROFINET IO controller or PROFINET IO
device CP modes.
Operating as PROFINET IO controller
The block accepts the process data from PROFINET IO devices (inputs of the controller)
and transfers the IO provider status (IOPS) from the PROFINET IO devices to the
specified input areas.
Operating as PROFINET IO device
The block receives the data transferred by the PROFINET IO controller (configured O
addresses) as well as the IO Provider Status (IOPS) of the PROFINET IO controller and
writes them to the data areas on the CPU of the PROFINET IO device reserved for the
process outputs.
For CPs operating as PROFINET IO controller and IO device at the same time, the FC as of
version 2.0 is available. With the additional MODE parameter, you set the mode for which
the FC will be called.
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 101
Call interface (block version 2.0)
Call interface in FBD representation
PNlO_RECV
BOOL BYTE
BOOL
WORD STATUS
ERROR
NDR
RECV
MODE
WORD CPLADDR
lOPS
ANY
ANY
BOOL
WORD ADD_lNFO
CHECK_lOPS
LEN lNT


Example in STL representation

STL Explanation
call fc 12(
CPLADDR:=W#16#0100,
MODE:=0,
LEN:=7,
IOPS:=P#DB11.DBX7.0 BYTE 1,
NDR:=M 74.0,
ERROR:=M 74.1,
STATUS:=MW76,
CHECK_IOPS:=M74.2,
ADD_INFO:=MW 26,
RECV:=P#DB11.DBX0.0 BYTE 7 );
//PNIO_RECV block call
//Module address from hardware configuration
//Controller mode or device mode
//Length of the data area
//Per receive data byte one status bit in DB11
//Address for return parameter NDR
//Address for return parameter ERROR
//Address for return parameter STATUS
//Address for return parameter CHECK_IOPS
//Diagnostic information
//Received data in DB11 (7 bytes)

See also
Data consistency (Page 107)
Substitute values (Page 108)
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
102 Programming Manual, 03/2008, C79000-G8976-C229-01
3.2.3.2 Explanation of the formal parameters - PNIO_RECV
Explanation of the formal parameters
The following table explains all the formal parameters for FC12:

Parameter Declaration Data type Possible values Description
CPLADDR INPUT WORD - Module start address
MODE
(parameters
version 2.0
or later)
INPUT BYTE 0:
IO controller mode
IO device operation
(without parallel
operation)
Not compatible with FC in
version 1.0
1:
IO device mode (both modes
at same time)
Specifies the mode of the CP.
Notes on compatibility;:
The version 1.0 FC can continue to be
used as long as the CP is not being
operated as an IO controller and IO
device at the same time.
When MODE=0, the FC as of version 2.0
behaves like the FC version 1.0.
RECV IN_OUT ANY (as
VARTYPE
only BYTE
is
permitted)
The address of the data area
points to one of the alternatives:
Memory bit area
Data block area
Specifies the address and length
IO controller mode:
The length should match the total length of
the distributed IO configured, whereby
address gaps are also transmitted.
The length can also be shorted than the total
length of the distributed IO, for example when
the block is called more than once in one OB.
It must, however, have the total length in at
least one call.
IO device mode:
The data structure results from the order of
the slots of the output modules configured for
this PROFINET IO device on the PROFINET
IO controller line and their length without
address gaps.
Notes:
The block begins to transfer the data at
address 0 regardless of how you
configured the addresses (regardless of
the lowest configured address).
Specifying an I/O area is not permitted
since you must first change the IOPS for
GOOD before data can be accepted in the
I/O.
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 103
Parameter Declaration Data type Possible values Description
LEN INPUT INT Value > 0
The maximum total length of the
data to be transferred can be
found in the devicespecific Part
B of this manual in the section
"Performance data". This may
differ for controller or device
mode.
Length of the data area to be transferred in
bytes.
The transfer of the data always begins with
address 0 regardless of the configuration.
Please note that the IO address "0" with a
length of 1 is included.
IO controller mode:
The highest configured address of the
devices must be specified here. The
individual areas are not grouped together.
If the block is called more than once, LEN
can also be shorter than the highest
address. The highest address should be
specified in at least one call (compare
"RECV" parameter).
The data is transferred in the order of the
logical addresses (as with PROFIBUS
DP).

IO device mode:
The data is transferred in the order of the
slots corresponding to the configuration of
the input modules on the PROFINET IO
controller line for this PROFINET IO
device.
Note:
Make sure that the length programmed
here and the configuration of the
PROFINET IO controller are consistent.
The entire data area length including any
gaps is transferred for the device.
NDR OUTPUT BOOL 0: -
1: Data accepted
This parameter indicates whether or not the
job was completed without errors.
ERROR OUTPUT BOOL 0: -
1: Error
Error code
STATUS OUTPUT WORD - Status code
CHECK_
IOPS
OUTPUT BOOL 0: All IOPS set to GOOD
1: At least one IOPS set to BAD
Auxiliary bit that indicates whether or not it is
necessary to evaluate the IOPS status area.
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
104 Programming Manual, 03/2008, C79000-G8976-C229-01
Parameter Declaration Data type Possible values Description
IOPS OUTPUT ANY (as
VARTYPE
only BYTE
is
permitted)
The address of the data area
points to one of the alternatives:
Memory bit area
Data block area
Length:
For the maximum value, refer to
the devicespecific Part B of this
manual in the section
"Performance data". This may
differ for controller or device
mode.
A status bit is transferred per byte of user
data.
The length information depends on the length
in the RECV parameter (one bit per byte)
= (Length LEN + 7/ 8)
Controller mode:
Address gaps are also transferred according
to the RECV parameter.
Address gaps are transferred with the status
GOOD.
Device mode:
Address gaps are not transferred.
The block begins the transfer of the status for
address 0.
Note:
The minimum length of the ANY pointer is
(length LEN + 7/8)
ADD_INFO OUTPUT WORD Additional Diagnostic Information
In controller mode:
0: No alarm
>0: Number of pending
alarms
In device mode, the parameter is
always = 0.
Parameter expansion
Note:
The ADD_INFO parameter is also updated
when there are no INPUT addresses
configured on the PROFINET IO controller. In
this case, the PNIO_RECV block is called
with a length LEN > 0 (for example
LEN = 1 byte). It then transfers an address
gap of 1 byte.
The parameter expansion can be used for
CPs as of the following firmware version:
CP 3431 (EX30) as of firmware V2.0
CP 3431 Lean (CX10) as of firmware
V2.0
CP 3431 Advanced (GX30) as of
firmware V1.0
In older firmware versions, the parameter is
reserved.


Note
Remember that all output parameters may only be evaluated when the block signals either
NDR = 1 or ERROR = 1.

FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 105
3.2.3.3 Condition codes of PNIO_RECV
Condition codes
The following table shows the codes formed by the NDR, ERROR and STATUS parameters
that must be evaluated by the user program.

Note
For entries coded with 8FxxH in STATUS, refer to the information in the STEP 7 Standard
and System Functions reference manual. The chapter describing error evaluation with the
RET_VAL output parameter contains detailed information.
To find out which SFCs are used and are relevant for error evaluation, display the properties
dialog of the FC described here in the "Calls" tab.


Table 3-3 Condition codes PNIO_RECV
NDR ERROR STATUS Meaning
0 0 8180H Data acceptance active;
or
The CP is in STOP mode.
0 0 8181H Module does not support block version 2.0.
Remedy: Use block version 1.0.
1 0 0000H New data accepted without error.
0 1 8183H PROFINET IO configuration missing;
or
wrong CPLADDR;
or
The CP is in STOP mode.
or
Interconnection of MODE does not match module configuration or incorrect
interconnection with MODE > 1.

Extra in device mode:
The connection between PROFINET IO controller and PROFINET IO device is
down,
or
PROFINET IO controller not reachable
or
Total lengths (configuration and LEN parameter) are not consistent
0 1 8184H System error or bad parameter type.
0 1 8185H Destination buffer (RECV of IOCS) is too small.
0 1 8F22H Area length error reading a parameter (e.g. DB too short).
0 1 8F23H Area length error writing a parameter (e.g. DB too short).
0 1 8F24H Range error when reading a parameter.
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
106 Programming Manual, 03/2008, C79000-G8976-C229-01
NDR ERROR STATUS Meaning
0 1 8F25H Range error when writing a parameter.
0 1 8F28H Alignment error when reading a parameter.
0 1 8F29H Alignment error when writing a parameter.
0 1 8F30H Parameter is in the write-protected 1st current data block.
0 1 8F31H Parameter is in the write-protected 2nd current data block.
0 1 8F32H Parameter contains a DB number that is too high.
0 1 8F3AH Destination area is not loaded (DB).
0 1 8F42H Timeout reading a parameter from the I/O area.
0 1 8F43H Timeout writing a parameter to the I/O area.
0 1 8F44H Access to a parameter to be read during block execution is prevented.
0 1 8F45H Access to a parameter to be written during block execution is prevented.
0 1 8F7FH Internal error, e.g. illegal ANY reference.
0 1 8090H Module with this address does not exist.
0 1 80A0H Negative acknowledgment writing to the module.
0 1 80A1H Negative acknowledgment writing to the module.
0 1 80B0H The module does not recognize the data record.
0 1 80B1H The specified data record length is incorrect.
or
The CP changes to STOP.
0 1 80C0H The data record cannot be read.
0 1 80C1H The specified data record is currently being processed.
0 1 80C2H There are too many jobs pending.
0 1 80C3H Resources occupied (memory).
0 1 80C4H Communication error (occurs temporarily, it is usually best to repeat the job in the user
program).

3.2.4 General characteristics of the FCs for PROFINET IO
IO Consumer Status (IOCS) and IO Provider Status (IOPS)
For both communication partners - CPU/CP on the one hand and IO device on the other -
there is the status information GOOD or BAD for the data. This status information is
transferred parallel to the data. The status of the partner that sends the data is called IOPS
(IO Provider Status), the status of the receiving partner is called IOCS (IO Consumer
Status).
The IOPS and IOCS status are not necessarily identical. It is, for example, possible that the
S7-300 CPU is in STOP mode (output disable or no PROFINET IO blocks active). In this
case, the CP as PROFINET IO controller transfers the BAD status to the IO devices.
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 107
Relationship between block call and IO data
Operation as PROFINET IO controller
As a PROFINET IO controller, the CP does not monitor the cyclic calls of the
PNIO_SEND/RECV blocks. If the blocks are not called, the last transferred IO data and
IOCS/IOPS data are taken as valid.
Operation as PROFINET IO device
FC11 and FC12 each have their own watchdog. Depending on the CPU cycle time, the
connection to the PROFINET IO controller is terminated if one of the two blocks is no
longer called following the initialization phase.
Optimizing data transfer (only when operating as PROFINET IO controller)
It is possible to call the blocks with a length (LEN parameter) that is shorter than the
configured total length of the IO data on the PNIO chain.
You can use this so that timecritical data is transferred in every CPU cycle whereas non
critical data is not transferred in every cycle.
Example:
You could, for example, transfer only the first data area (timecritical data) in every cycle and
the total length of the configured IO data in every second cycle. To do this, place the time-
critical data in the lower area (starting at IO address 0) during configuration.

3.2.5 Data consistency
The entire input or output data area of the PNIO controller is always transferred in its entirety
and is therefore consistent.
Operating as PROFINET IO controller
Regardless of this, using the length information in the block call, you can also read or
output an input or output area smaller than the configured area consistently.
Note: You should, however, bear in mind that in terms of the "IO user data" within a
PROFINET IO system, data consistency can only be guaranteed within the individual IO
slots. This applies regardless of the fact that consistent data transfer between CPU and IO
controller is guaranteed for the blocks described here.
Block call
To guarantee data consistency, you may, however, only access the IO data when the block
has completed free of errors (output parameter NDR = TRUE). You must also check that the
IOCS or IOPS status for the data is GOOD.
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
108 Programming Manual, 03/2008, C79000-G8976-C229-01
Example
In a normal situation (depending on the total length of the IO data), the block will run over
several user program cycles until the condition code DONE/NDR = 1 is signaled.
Call PNlO_RECV block until NDR=1
Check lOPS status (from PNlO devices) of received data,
if necessary, error handling.
Check lOCS status values received from PNlO devices,
if necessary, error handling.
Preprocess and process data, prepare new output data.
Call PNlO_SEND block until DONE=1


Note: The user program cycle and the cycle of the IO data exchange between the PNIO
controller and PNIO devices are independent of each other.
3.2.6 Substitute values
Operational situations
The setting of substitute values is supported for the two following operational situations:
Substitute values during startup (mode change on the CPU from STOP to RUN)
Substitute values if problems are detected (remove/insert or station failure/return)
Substitute values during startup
You can initialize the outputs with substitute values by setting a memory bit ("startup"
memory bit) in the startup OB. In cyclic mode (OB1), evaluate this "startup" memory bit to
call PNIO_SEND with the initialization values when appropriate.
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 109
Substitute values if a problem occurs (only when operating as PROFINET IO controller)
If there is a fault (device/submodule failed), you can find out which submodules have failed
by querying the status information IOCS / IOPS status. You then have the option of setting
substitute values.

3.2.7 FB52 PNIO_RW_REC
3.2.7.1 Meaning and call - PNIO_RW_REC
How It works
FB52 is used both for the "read data record" and the "write data record" function in
PROFINET IO controller mode. FB52 can only execute one of the functions at any one time.
The "read data record" or "write data record" function is controlled by the WRITE_REC
parameter.
Example: The CP can be informed of the location ID and plant designation using the "write
data record" function (if this parameter was not already set in the properties dialog of the CP
in STEP 7). This is done using the maintenance data record "IM1" with index AFF1H.
You will find details of the supported data records and their structure at the following Internet
address:
http://support.automation.siemens.com/WW/view/en/19289930
Call interface
Call interface in FBD representation:
PNIO_RW_REC
BOOL
BOOL ERROR
DONE
WRITE_REC
WORD CPLADDR
STATUS WORD
BOOL
WORD
ANY
INT
WORD
LEN
ID
RECORD
INDEX


Example in STL representation:


FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
110 Programming Manual, 03/2008, C79000-G8976-C229-01
STL Explanation
CALL FB 52, DB 52(

CPLADDR:=W#16#0110,
WRITE_REC:=M 1.1,

ID:=W#16#86A,
INDEX:=W#16#8000,
DONE:=M 1.3,
ERROR:=M 1.1,
STATUS:=MW 12,
LEN:=MW 16,

RECORD:=P#DB3.DBX0.0 BYTE 80 );
//PNIO_RW_REC block call
// (read/write data record)
//Module address from hardware configuration
//TRUE: Write data record;
//FALSE: Read data record
//Logical address of the submodule to be addressed
//Data record number
//Address for return parameter DONE
//Address for return parameter ERROR
//Address for return parameter STATUS
//Length of the read data record /
// data record to be written in bytes
//Destination or source of the data record
// to be transferred (here max. 80 bytes)

3.2.7.2 Explanation of the formal parameters - PNIO_RW_REC
Explanation of the formal parameters
The following table explains all the formal parameters for FB52:

Parameter Declaration Data type Possible values Description
CPLADDR INPUT WORD - Module start address
WRITE_REC INPUT BOOL 0: Read data record
1: Write data record
Job type;
The parameter must not be changed while the block is
executing.
ID INPUT WORD Logical address of the PROFINET IO component
(module or submodule). For an output module, bit 15 is
set
(example of output address 5: ID:=DW#16#8005).
For a mixed module, the lower of the two addresses
must be specified.
INDEX INPUT WORD See vendor information
for the data record
numbers supported by
the module.
Data record number that the user wants to read or
write.
DONE OUTPUT BOOL 0: -
1: Data record
transferred successfully
This parameter indicates whether or not the job was
completed without errors.
ERROR OUTPUT BOOL 0: -
1: Error
Error code
STATUS OUTPUT WORD 0: No error
Different value: Error
(see "")
Status code
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 111
Parameter Declaration Data type Possible values Description
LEN IN_OUT INT The maximum length is
480 bytes.
Read data record:
OUTPUT parameter only; after a successful read,
the length of the read data record is indicated;
otherwise 0.
Write data record:
INPUT parameter only; length of the data record to
be written is entered here by the user. The length
must match the definition of the data record.
RECORD IN_OUT ANY (as
VARTYP
E, BYTE,
WORD
and
DWORD
are
permitted
)
The address of the
data area points to one
of the alternatives:
Memory bit area
Data block area
The length of the ANY
pointer must be greater
than or equal to the
definition of the data
record.
Read data record:
OUTPUT parameter only; after a successful read,
the data of the data record is stored here. If the
ANY pointer is too short, as much data as possible
is transferred.
Write data record:
INPUT parameter only; the data to be written from
the data record is stored here by the user. The ANY
pointer must be at least as long as specified in the
LEN parameter.

3.2.7.3 Condition codes of PNIO_RW_REC
Condition codes
The following table shows the condition codes formed based on DONE, ERROR and
STATUS that must be evaluated by the user program.

Note
For entries with the coding 8FxxH under STATUS, note the information in the Reference
Manual "STEP 7 - System and Standard Functions for S7-300 and S7-400". The chapter
describing error evaluation with the RET_VAL output parameter contains detailed
information.


Table 3-4 PNIO_RW_REC condition codes
DONE ERROR STATUS Meaning
0 0 8180H Data transfer active
1 0 0000H Data record transferred successfully
0 1 8183H No PNIO controller configuration,
wrong CPLADDR
or
CP in STOP mode
0 1 8184H System error or illegal parameter type
0 1 8185H Destination buffer (RECORD) is too short
0 1 8F22H Area length error reading a parameter (e.g. DB too short)
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
112 Programming Manual, 03/2008, C79000-G8976-C229-01
DONE ERROR STATUS Meaning
0 1 8F23H Area length error writing a parameter (e.g. DB too short)
0 1 8F24H Area error reading a parameter
0 1 8F25H Area error writing a parameter
0 1 8F28H Orientation error when reading a parameter
0 1 8F29H Alignment error writing a parameter
0 1 8F30H Parameter is in the write-protected first active data block
0 1 8F31H Parameter is in the write-protected second active data block
0 1 8F32H The DB number in the parameter is too high
0 1 8F3AH Destination area not loaded (DB)
0 1 8F42H Timeout reading a parameter from the I/O area
0 1 8F43H Timeout writing a parameter to the I/O area
0 1 8F44H Address of the parameter to be read is disabled in the accessed rack
0 1 8F45H Address of the parameter to be written is disabled in the accessed rack
0 1 8F7FH Internal error, e.g. illegal ANY reference
0 1 8090H Module with this address does not exist
0 1 80A0H Negative acknowledgment reading from the module
0 1 80A1H Negative acknowledgment writing to the module
0 1 80A3H General PROFINET IO context management error
0 1 80A9H PROFINET IO device or module reports an illegal type
0 1 80B0H Module does not recognize the data record
0 1 80B1H The specified data record length is incorrect
or
The CP changes to STOP
0 1 80B2H The logical address or the configured slot is not in use
0 1 80B4H PROFINET IO device or module signaling access to an illegal area
0 1 80B6H PROFINET IO device or module denies access
0 1 80B8H The module is signaling an illegal parameter
0 1 80C0H The data record cannot be read
0 1 80C1H The specified data record is being processed
0 1 80C2H Too many jobs pending
0 1 80C3H Resources (memory) occupied
0 1 80C4H Communication error (occurs temporarily, it is usually best to repeat the job in the user
program).

FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 113
3.2.8 FB54 PNIO_ALARM
3.2.8.1 Meaning and call - PNIO_ALARM
How It works
FB54 is used for alarm evaluation by a CP 3431 operating as PROFINET IO controller and
should be called in its user program when the ADD_INFO parameter in FC12 is not equal to
0. After complete and errorfree transfer of all OUTPUT parameters of FB54, the received
alarms are acknowledged automatically.
The alarms are forwarded to the user program in the chronological order in which they were
signaled. Older alarms that have not yet been signaled to the user program and that become
invalid due to more recent alarms are not deleted by the newer alarms.

Note
As long as the block has not yet been called, the alarms are acknowledged automatically in
the CP.
If FB54 has been called (at least) once in the user program, it must continue to be called to
acknowledge pending alarms. This is the situation when FC12 signals a value not equal to
"0" in the ADD_INFO parameter.
If FB54 is no longer called after it has been called once or more in the user program, alarms
are not acknowledged and there is no guarantee that the IO image will be updated correctly.
The can occur, for example, following a station return alarm. The need to call FB54 can only
be reset by restarting the CP (power cycle).

Call interface
Call interface in FBD representation
PNIO_ALARM
BOOL
DWORD
BOOL
WORD STATUS
NEW
ERROR
DONE
MODE
WORD CPLADDR
ID
BOOL
WORD
INT LEN
ANY
ANY AINFO
TINFO


Example in STL representation:


FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
114 Programming Manual, 03/2008, C79000-G8976-C229-01
STL Explanation
CALL FB 54, DB 54(

CPLADDR:=W#16#0110,
DONE:=M 1.1,
ERROR:=M 1.2,
NEW:=M 1.3,
STATUS:=MW 12,
ID:=MW14,


LEN:=MW 16,
MODE:=MD 18,
TINFO:=P#DB4.DBX0.0 BYTE 32,


AINFO:= P#DB4.DBX32.0 BYTE 532 );
//PNIO_ALARM block call
// (read/write data record)
//Module address from hardware configuration
//Address for return parameter DONE
//Address for return parameter ERROR
//TRUE: A new alarm was received
//Error code of the SFB or PNIOCtrl
//Logical base address of the component
//(module or submodule) from which an alarm
//was received
//Length of the received alarm information (AINFO)
//RESERVED (value always = 0)
//(task information) destination area for OB
//start information and management information;
// fixed length 32 bytes of diagnostic information
//(alarm information) destination area for
//header information and additional alarm information

3.2.8.2 Explanation of the formal parameters - PNIO_ALARM
Explanation of the formal parameters
The following table explains all the formal parameters for FB54:

Parameter Declaration Data type Possible values Description
CPLADDR INPUT WORD - Start address of the module that caused the error
DONE OUTPUT BOOL 0: -
1: Alarm information
transferred
successfully
This parameter indicates whether or not the job was
completed without errors.
If DONE = 1, the NEW parameter must also be
checked.
ERROR OUTPUT BOOL 0: -
1: Error
Error code
NEW OUTPUT BOOL 0: Data transfer active
or no new alarm
1: New alarm received
and acknowledged
If DONE = 1 and NEW = 1, a new received alarm is
signaled.
STATUS OUTPUT WORD 0: No error
Different value: Error
(see Table 114)
Status code
ID OUTPUT WORD Logical start address of the PNIO component that
triggers the alarm (module or submodule).
For an output module, bit 15 is set (example of output
address 5: ID:=DW#16#8005).
For a mixed module, the lower of the two addresses is
specified.
LEN OUTPUT INT Length of the received alarm information (AINFO)
MODE IN_OUT DWORD 0 Reserved
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 115
Parameter Declaration Data type Possible values Description
TINFO IN_OUT ANY (as
VARTYPE
, BYTE,
WORD
and
DWORD
are
permitted)
The address of the
data area points to one
of the alternatives:
Memory bit area
Data block area
The length of the ANY
pointer must be >= 32
bytes.
task information
Destination area for the alarm management information.
The error OB start information (OB header = byte 0...19
of TINFO) is reproduced as far as possible by the CP
firmware.
See also 1)
AINFO IN_OUT ANY (as
VARTYPE
, BYTE,
WORD
and
DWORD
are
permitted)
The address of the
data area points to one
of the alternatives:
Memory bit area
Data block area
The length of the ANY
pointer must be
greater than or equal
to the maximum
additional alarm
information that can be
expected, maximum
1432 bytes (see LEN
parameter)
alarm information
Destination area for header information and additional
alarm information. If the ANY pointer AINFO is too low,
the information will be truncated.
See also 1)

1) Reference Manual "STEP 7 - System and Standard Functions for S7-300 and S7-400",
receiving an alarm with SFB54 "RALRM"
3.2.8.3 Condition codes of PNIO_ALARM
Condition codes
The following table shows the condition codes formed by the DONE, NEW, ERROR and
STATUS parameters that must be evaluated by the user program.

Note
For entries with the coding 8FxxH under STATUS, note the information in the Reference
Manual "STEP 7 - System and Standard Functions for S7-300 and S7-400". The chapter
describing error evaluation with the RET_VAL output parameter contains detailed
information.



DONE NEW ERROR STATUS Meaning
0 0 0 8180H Data transfer active
1 1 0 0000H Alarm data successfully transferred and alarm acknowledged
1 0 0 0000H No alarm data exist
FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
116 Programming Manual, 03/2008, C79000-G8976-C229-01
DONE NEW ERROR STATUS Meaning
0 0 1 8183H No PNIO controller configuration,
wrong CPLADDR
or
CP in STOP mode
0 0 1 8184H System error or illegal parameter type
0 0 1 8185H Destination buffer (TINFO or AINFO) is too short
0 0 1 8F22H Area length error reading a parameter (e.g. DB too short)
0 0 1 8F23H Area length error writing a parameter (e.g. DB too short)
0 0 1 8F24H Area error reading a parameter
0 0 1 8F25H Area error writing a parameter
0 0 1 8F28H Orientation error when reading a parameter
0 0 1 8F29H Alignment error writing a parameter
0 0 1 8F30H Parameter is in the write-protected first active data block
0 0 1 8F31H Parameter is in the write-protected second active data block
0 0 1 8F32H The DB number in the parameter is too high
0 0 1 8F3AH Destination area not loaded (DB)
0 0 1 8F42H Timeout reading a parameter from the I/O area
0 0 1 8F43H Timeout writing a parameter to the I/O area
0 0 1 8F44H Address of the parameter to be read is disabled in the accessed rack
0 0 1 8F45H Address of the parameter to be written is disabled in the accessed rack
0 0 1 8F7FH Internal error, e.g. illegal ANY reference
0 0 1 8090H Module with this address does not exist
0 0 1 80A0H Negative acknowledgment reading from the module
0 0 1 80A1H Negative acknowledgment writing to the module
0 0 1 80B0H Module does not recognize the data record
0 0 1 80B1H The specified data record length is incorrect
or
The CP changes to STOP
0 0 1 80C0H The data record cannot be read
0 0 1 80C1H The specified data record is being processed
0 0 1 80C2H Too many jobs pending
0 0 1 80C3H Resources (memory) occupied
0 0 1 80C4H Communication error (occurs temporarily, it is usually best to repeat the job in
the user program).

FCs / FBs for PROFINET
3.2 FCs/FBs for PROFINET IO (S7-300)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 117
3.2.9 Configuration limits / resources required by the FCs and FBs (PROFINET)
Required resources
NOTICE
Please note the version information of the blocks. Blocks with other versions have different
resource requirements.

Table 3-5 Information for FCs / FBs with an S7-400
NAME Version FC/FB no. Load memory
bytes
Work memory
bytes
MC7
bytes
Local data
bytes
PN_InOut 1.3 FB88 2678 2234 2198 48
PN_InOut_Fast 1.0 FB90 2906 2266 2230 48

Table 3-6 Information for FCs / FBs with an S7-300
NAME Version FC/FB no. Load memory
bytes
Work memory
bytes
MC7
bytes
Local data
bytes
PN_InOut 1.5 FB88 2470 2066 2030 54
PNIO_SEND 1.0 FC11 1272 1058 1022 42
PNIO_SEND 2.0 FC11 1342 1116 1080 42
PNIO_RECV 1.0 FC12 1122 928 892 42
PNIO_RECV 2.0 FC12 1192 986 950 42
PNIO_RW_REC 1.1 FB52 1636 1378 1342 62
PNIO_ALARM 1.1 FB54 1168 960 924 62


Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 119
FCs / FBs for PROFIBUS
4
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
4.1.1 Overview of FCs and their use
Overview
The following FCs are available for the SEND/RECEIVE interface for transferring data on
configured FDL connections:

Can be used with
1)
FC
S7-300 S7-400
Meaning
AG_SEND (FC5) x x for sending data
AG_RECV (FC6) x x for receiving data
AG_LSEND (FC50) x for sending data
AG_LRECV (FC60) x for receiving data
1) Notes on the FCs for an S7300 and S7400
To ensure the compatibility of PROFIBUS and Ind. Ethernet on the interface in the user
program, you can use the FCs AG_LSEND and AG_LRECV on PROFIBUS as alternatives
to AG_SEND and AG_RECV. There is no difference in the interface or the way they function.
On PROFIBUS, however, you can only transfer data up to a maximum of 240 bytes even
with these FCs although they are intended for longer data records on Industrial Ethernet.
This is only possible if the block type and block version are permitted for the CP type you are
using.
With the S7 CPs for S7300, only the FCs AG_SEND and AG_RECV are used; on Industrial
Ethernet even for the transfer of longer data records.
The manuals contain information on the compatibility of the S7-CPs and the corresponding
blocks (FCs / FBs). You will find an overview of the versions of the FCs/FBs in the
documentation and block history.
FCs / FBs for PROFIBUS
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
120 Programming Manual, 03/2008, C79000-G8976-C229-01
Application
The following diagram illustrates the use of the FCs AG_SEND / AG_LSEND and AG_RECV
/ AG_LRECV for bi-directional data transfer on one configured FDL connection.
With certain connection types, a job header should be included in the user data area.
AG_RECV
PROFIBUS-CP CPU
AG_SEND AG_RECV
AG_SEND
PROFIBUS-CP CPU
STEP 7
user
program
DP
data areas
send
receive
FDL connection
over
PROFIBUS
STEP 7
user
program
DP
data areas
receive
send

Figure 4-1 Using AG_SEND and AG_RECV on both communications partners
Application without job header
With a specified FDL connection, the address and job parameters are specified by the
configuration of the connection. The user program only provides the user data in the FDL
data area when sending with AG_SEND / AG_LSEND or receives the data with AG_RECV /
AG_LRECV.
Up to 240 bytes of user data can be transferred. This applies to PROFIBUS for both the
AG_SEND or AG_LSEND functions.
FCs / FBs for PROFIBUS
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 121
Working with the job header
The following connection types require a job header in the FDL (user) data area:
Unspecified FDL connection with free layer 2 access
FDL connection with broadcast
FDL connection with multicast
The following schematic illustrates the structure of the job buffer and the meaning and
location of the parameters in the job header.
PBAdresse
unbenutzt Service
Datenbyte 1
LSAP
Datenbyte 0
Byte 0, 1
Byte 238, 239
Byte 4, 5
Byte 2, 3
Data byte 234 Data byte 235
Job header
User data area
Job buffer
User data

Figure 4-2 Sending and receiving via an FDL connection with programmed broadcast addressing
|The user data area can be up to 240 bytes. Up to 236 bytes of user data can be transferred.
4 bytes are reserved for the job header.
Please note that the data length specified in the block call (LEN parameter) must include the
header and the user data!
4.1.2 FC5 AG_SEND / FC50 AG_LSEND
4.1.2.1 Meaning and call - AG_SEND / AG_LSEND
Meaning of the block
FC AG_SEND / AG_LSEND transfers data to the PROFIBUS CP for transmission on a
configured FDL connection.
The selected data area can be a process image area, a memory bit area or a data block
area.
Error free execution of the function is indicated when the entire FDL data area could be sent
on PROFIBUS.
Note:
Unless otherwise stated, all the following information applies equally to the FCs AG_SEND
and AG_LSEND.
FCs / FBs for PROFIBUS
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
122 Programming Manual, 03/2008, C79000-G8976-C229-01
Call
Call interface in FBD representation
AG_SEND / AG_LSEND / AG_SSEND
BOOL
ANY
BOOL
BOOL
WORD
lNT
WORD
lNT
ACT
LEN
STATUS
ERROR
DONE
SEND
LADDR
lD


Example in STL representation

STL Explanation
call fc 5(
ACT:=M 20.0,
ID:=MW 22,
LADDR:=W#16#0100,
SEND:= P#db99.dbx10.0 byte 240,
LEN:=MW 24,
DONE:=M 20.1,
ERROR:=M 20.2,
STATUS:=MW 26 );
//AG_SEND / AG_LSEND block call
//Job triggered by memory bit
//Connection ID acc. to configuration
//=LADDR 256 dec. in HW Config
//Buffer with send data
//Length for send data
//Execution code
//Error code
//Status code

Calls with job header
The following table shows the connection types and job types for which parameters must be
supplied in the job header.
The job header is located in the FDL (user ) data area. It occupies the first 4 bytes and must
be added to the length specified in the LEN parameter. The maximum user data length is
therefore reduced for jobs with a job header to 236 bytes.
Table 4-1 Supplying the job header in the user data area
FDL connection type Parameter
Unspecified: free layer 2
2)
Broadcast Multicast
PB address Address of the destination station
Range of values:
0..126 depending on node /
127 for broadcast/multicast
For AG_SEND no
relevance; but area
must be reserved.
For AG_SEND no
relevance; but area
must be reserved.
LSAP LSAP of the destination station
Range of values:
0..62 depending on node /
63 for broadcast
No significance but
area must be reserved.
No significance but
area must be reserved.
FCs / FBs for PROFIBUS
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 123
FDL connection type
Service
1)
SDA ( Send Data with
Acknowledge):
Value: 00H
SDN ( Send Data with No
Acknowledge):
Value: 01H
No significance but
area must be reserved.
No significance but
area must be reserved.
1)
for broadcast and multicast, only the SDN service is possible.
2)
The information on broadcast and multicast in this column is relevant only when an
unspecified FDL connection is used for broadcast or multicast. On a configured FDL
connection (recommended application) with broadcast or multicast as the connection
partner, the address parameters are assigned automatically according to the configuration.
FCs / FBs for PROFIBUS
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
124 Programming Manual, 03/2008, C79000-G8976-C229-01
4.1.2.2 How AG_SEND / AG_LSEND work
Operating principle
The following diagram illustrates the normal sequence of data transmission triggered in the
user program using AG_SEND.
The send job in executed as soon as the parameter ACT = 1 is passed.
Following this, the parameter ACT = 0 must be passed in at least one further call.
The status code in the output parameters DONE, ERROR and STATUS is updated in each
block call and can be evaluated. To update the status code without starting a new send job,
start a new block call with the parameter ACT = 0.
Refer to the sample program at the end of this section.
DP_SEND
AG_SEND
AG_SEND
1, 0, 0000
1)
0, 0, 8181
1)
0, 0, 8181
1)
1) Parameter transfer DONE, ERROR, STATUS
User program
(CPU cycle)
PROFlBUS CP
Time
Supply AG_SEND with data 'X'
ACT = 1
Communication partners
Time Time
Transfer
of 'X'
via PROFlBUS
in progress
Supply AG_SEND
ACT = 0
Legend:


FCs / FBs for PROFIBUS
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 125
4.1.2.3 Explanation of the formal parameters - AG_SEND / AG_LSEND
Explanation of the formal parameters
The following table explains all the formal parameters for the
AG_SEND /AG_LSEND functions:

Parameter Declaration Data type Possible values Description
ACT INPUT BOOL 0,1 If an FC is called with ACT=1, LEN bytes are sent from
the ISO transport data area specified with the SEND
parameter.
If an FC is called with ACT = 0, the status codes DONE,
ERROR and STATUS are updated.
ID INPUT INT 1,2...64
(S7-400)
1,2...16
(S7-300)
The connection number of the FDL connection is
specified in the parameter ID.
LADDR INPUT WORD Module start address
When you configure the CP, the module start address is
displayed in the configuration table. Specify this
address here.
SEND INPUT ANY
(only the
following are
permitted as
VARTYPE:
WORD and
DWORD are
permitted)
Specifies the address and length
The address of the data area points to one of the
alternatives:
PI area
Memory bit area
Data block area
With a call with job header, the FDL data area contains
the job header and the user data.
LEN INPUT INT 1,2, to 240 (or up to
"length specified for
SEND parameter")
Number of bytes to be sent from the FDL data area with
this job. The possible values range from 1 to length
specified for the SEND parameter.
In a call, with job header, the length information is made
up of the job header (4 bytes) + user data (1 to 236
bytes). Therefore LEN >= 4 !
DONE OUTPUT BOOL 0: -
1: new data
The status parameter indicates whether or not the job
was completed without errors.
For the meaning in conjunction with the ERROR and
STATUS parameters, refer to the following table.
ERROR OUTPUT BOOL 0: -
1: Error
Error code
For the meaning in conjunction with the DONE and
STATUS parameters, refer to the following table.
STATUS OUTPUT WORD See following table Status code
For the meaning in conjunction with the DONE and
ERROR parameters, refer to the following table.

FCs / FBs for PROFIBUS
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
126 Programming Manual, 03/2008, C79000-G8976-C229-01
4.1.2.4 Condition codes of AG_SEND and AG_LSEND
Condition codes
The following table shows the condition codes formed based on DONE, ERROR and
STATUS that must be evaluated by the user program.

Note
For entries coded with 8FxxH in STATUS, refer to the information in the STEP 7 Standard
and System Functions reference manual. The chapter describing error evaluation with the
RET_VAL output parameter contains detailed information.
To find out which SFCs are used and are relevant for error evaluation, display the properties
dialog of the FC described here in the "Calls" tab.


Table 4-2 AG_SEND condition codes
DONE ERROR STATUS Meaning
1 0 0000H Job completed without error.
0 0 0000H No job being executed.
0 0 8181H Job active.
0 1 7000H The condition code is possible only with S7-400: The FC was called with ACT=0; the
job has not yet been processed.
0 1 8183H No configuration or the FDL service has not yet started on the PROFIBUS CP.
0 1 8184H Illegal data type specified for the SEND parameter.
FDL connection without job buffer: System error.
FDL connection with job buffer: Parameter LEN<4 or illegal parameter in job header
(with free layer 2 access).
0 1 8185H LEN parameter longer than SEND source area.
0 1 8186H ID parameter invalid. ID!=1,2 to 15,16.
0 1 8301H SAP not activated on destination station.
0 1 8302H No receive resources on the destination station; the receiving station cannot process
received data quickly enough or has not prepared any receive resources.
0 1 8303H The PROFIBUS service (SDA Send Data with Acknowledge) is not supported on this
SAP by the destination station.
This condition code can also occur temporarily when connections or gateways are
downloaded "in RUN".
0 1 8304H The FDL connection is not established.
0 1 8311H The destination station is not obtainable at the specified PROFIBUS address or the
service is not possible for the specified PROFIBUS address.
0 1 8312H PROFIBUS error on the CP: for example, bus short-circuit, own station not in ring.
0 1 8315H Internal parameter error on an FDL connection with job header: Parameter LEN<4 or
illegal parameter in job header (with free layer 2 access).
0 1 8F22H Source area invalid, e.g.:
Area does not exist in the DB
LEN parameter < 0
FCs / FBs for PROFIBUS
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 127
DONE ERROR STATUS Meaning
0 1 8F24H Area error reading a parameter.
0 1 8F28H Alignment error reading a parameter.
0 1 8F32H Parameter contains a DB number that is too high.
0 1 8F33H DB number error.
0 1 8F3AH Area not loaded (DB).
0 1 8F42H Timeout reading a parameter from the I/O area.
0 1 8F44H Address of the parameter to be read is disabled in the access track.
0 1 8F7FH Internal error, e.g. illegal ANY reference
e.g. parameter LEN=0
0 1 8090H No module with this module start address exists.
The FC being used does not match the system family being used (remember to use
different FCs for S7300 and S7400).
0 1 8091H Module start address not at a doubleword boundary.
0 1 8092H In the ANY reference, a type other than BYTE is specified.
(S7-400 only)
0 1 80A4H The communication bus connection between the CPU and CP is not established. (with
newer CPU versions).
This can, for example, be caused by the following:
No connection configuration;
The maximum number of CPs that can be operated at one time has been exceeded
(for further information, refer to the CP manual).
0 1 80B0H The module does not recognize the data record.
0 1 80B1H Destination area is invalid.
The amount of data to be sent exceeds the upper limit permitted for this service
(e.g. destination area > 240 bytes).
0 1 80B2H The communication bus connection between the CPU and CP is not established (with
older CPU versions; otherwise 80A4H; for further information, refer to this code)
0 1 80C0H The data record cannot be read.
0 1 80C1H The specified data record is currently being processed.
0 1 80C2H There are too many jobs pending.
0 1 80C3H Resources occupied (memory).
0 1 80C4H Communication error (occurs temporarily, it is usually best to repeat the job in the user
program).
0 1 80D2H Module start address incorrect.

FCs / FBs for PROFIBUS
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
128 Programming Manual, 03/2008, C79000-G8976-C229-01
4.1.3 FC6 AG_RECV / FC60 AG_LRECV
4.1.3.1 Meaning and call - AG_RECV / AG_LRECV
Meaning of the block
The AG_RECV / AG_LRECV function receives the data transferred on a configured FDL
connection from the PROFIBUS CP.
The data area specified for the receive data can be a process image area, a bit address area
or a data block area.
Errorfree execution is indicated when the data could be received from the PROFIBUS CP.
Note:
Unless otherwise stated, all the following information applies equally to the FCs AG_SEND
and AG_LSEND.
Call interface
Call interface in FBD representation
AG_RECV / AG_LRECV / AG_SRECV
ANY
BOOL
BOOL
WORD
lNT
WORD
lNT LEN
STATUS
ERROR
NDR
RECV
LADDR
lD


Example in STL representation

STL Explanation
call fc 6(
ID:=MW 30,
LADDR:=W#16#0100,
RECV:=P#M 10.0 BYTE 100,
NDR:=DB 100.DBX 0.6,
ERROR:=DB 100.DBX 0.7,
STATUS:=DB 100.DBW 2,
LEN:=DB 100.DBW 4 );
//AG_RECV / AG_LRECV block call
//Connection ID acc. to configuration
//=LADDR 256 dec.in HW Config
//Buffer for received data
//Receive code
//Execution code
//Error code
//Status code

FCs / FBs for PROFIBUS
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 129
Calls with job header
Table 4-3 Return parameters in the job header in the FDL (user) data area
FDL connection type Parameter
Unspecified: free layer 2) Broadcast Multicast
PB address Address of the sender
Values: 0 to 126 depending on node
LSAP LSAP of the sender
Values: 0 to 63 depending on node
Service SDN indication
( Send Data with No
Acknowledge - Indication):
Value: 01H
or
SDA indication ( Send Data with
Acknowledge - Indication):
Value: 00H
SDN indication
( Send Data with No
Acknowledge -
Indication):
Value: 7FH
SDN indication
( Send Data with No
Acknowledge -
Indication):
Value: 7FH

FCs / FBs for PROFIBUS
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
130 Programming Manual, 03/2008, C79000-G8976-C229-01
4.1.3.2 How AG_RECV / AG_LRECV work
Operating principle
The following diagram illustrates the normal sequence of data acceptance triggered by an
AG_RECV in the user program.
Each AG_RECV job in the user program is acknowledged by the Ethernet CP with an entry
in the output parameters NDR, ERROR and STATUS.
AG_RECV
AG_RECV
AG_RECV
0, 0, 8180
1)
0, 0, 8180
1) 2)
1, 0, 0000
1)
AG_RECV
1, 0, 0000
1)
AG_RECV
1) Parameter transfer DONE, ERROR, STATUS
User program
(CPU cycle)
PROFlBUS CP
Time
The communication
partner
Time Time
Transfer
of 'A'
via PROFlBUS
active
Transfer
of 'C'
via PROFlBUS
active
Transfer
of 'B'
via PROFlBUS
active
Accept / evaluate received
data 'A'
Accept / evaluate received
data 'B'
Key:


FCs / FBs for PROFIBUS
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 131
4.1.3.3 Explanation of the formal parameters - AG_RECV / AG_LRECV
Explanation of the formal parameters
The following table explains all the formal parameters for the
AG_RECV / AG_LRECV function:

Parameter Declaration Data type Possible values Description
ID INPUT INT 1,2...16 (S7-300)
1,2...32 (S7-400)
The connection number of the FDL connection is
specified in the parameter ID.
LADDR INPUT WORD Module start address
When you configure the CP, the module start address
is displayed in the configuration table. Specify this
address here.
RECV INPUT ANY
(only the
following are
permitted as
VARTYPE:
WORD and
DWORD are
permitted)
Specifies the address and length
The address of the FDL data area points to one of the
alternatives:
PI area
Memory bit area
Data block area
With a call with job header, the FDL data area contains
the job header and the user data.
LEN OUTPUT INT 1,2,...240 Specifies the number of bytes to be received in the
FDL data area from the PROFIBUS CP.
In a call, with job header, the length information is
made up of the job header (4 bytes) + user data (1 to
236 bytes). Therefore LEN >= 4 !
NDR OUTPUT BOOL 0: -
1: new data
This parameter indicates whether new data were
received.
For the meaning in conjunction with the ERROR and
STATUS parameters, refer to the following table.
ERROR OUTPUT BOOL 0: -
1: Error
Error code
For the meaning of this parameter in conjunction with
the NDR and STATUS parameters, refer to the
following table.
STATUS OUTPUT WORD See following table Status code
For the meaning in conjunction with the NDR and
ERROR parameters, refer to the following table.

FCs / FBs for PROFIBUS
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
132 Programming Manual, 03/2008, C79000-G8976-C229-01
4.1.3.4 Condition codes of AG_RECV and AG_LRECV
Condition codes
The following table shows the codes formed by the NDR, ERROR and STATUS parameters
that must be evaluated by the user program.

Note
For entries coded with 8FxxH in STATUS, refer to the information in the STEP 7 Standard
and System Functions reference manual. The chapter describing error evaluation with the
RET_VAL output parameter contains detailed information.
To find out which SFCs are used and are relevant for error evaluation, display the properties
dialog of the FC described here in the "Calls" tab.


Table 4-4 AG_RECV / AG_LRECV condition codes
NDR ERROR STATUS Meaning
1 0 0000H New data accepted.
0 0 8180H There is no data available yet.
The configuration is missing or the FDL service has not started on the PROFIBUS
CP (occurs here instead of the code 0,1,8183H).
0 0 8181H Job active.
0 1 8183H No configuration or the FDL service has not yet started on the PROFIBUS CP.
0 1 8184H Illegal data type specified for the RECV parameter.
System error.
0 1 8185H Destination buffer (RECV) is too short.
0 1 8186H ID parameter invalid. ID!=1,2 to 15,16.
0 1 8303H The PROFIBUS service ( SDA - Send Data with Acknowledge) is not supported on this
SAP.
This condition code can also occur temporarily when connections or gateways are
downloaded "in RUN".
0 1 8304H The FDL connection is not established.
0 1 8F23H Source area invalid, e.g.:
Area does note exist in the DB.
0 1 8F25H Area error writing a parameter.
0 1 8F29H Alignment error writing a parameter
0 1 8F30H Parameter is in the writeprotected 1st current data block.
0 1 8F31H Parameter is in the writeprotected 2nd current data block.
0 1 8F32H Parameter contains a DB number that is too high.
0 1 8F33H DB number error.
0 1 8F3AH Destination area not loaded (DB).
0 1 8F43H Timeout writing a parameter to the
I/O area.
0 1 8F45H Address of the parameter to be read is disabled in the access track.
FCs / FBs for PROFIBUS
4.1 FCs for S5-compatible communication (SEND/RECEIVE interface)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 133
NDR ERROR STATUS Meaning
0 1 8F7FH Internal error, e.g. illegal ANY reference.
0 1 8090H No module with this module start address exists.
The FC being used does not match the system family being used (remember to use
different FCs for S7300 and S7400).
0 1 8091H Module start address not at a doubleword boundary.
0 1 8092H In the ANY reference, a type other than BYTE is specified.
(S7-400 only)
0 1 80A0H Negative acknowledgment reading from the module.
0 1 80A4H The communication bus connection between the CPU and CP is not established. (with
newer CPU versions).
This can, for example, be caused by the following:
No connection configuration;
The maximum number of CPs that can be operated at one time has been exceeded
(for further information, refer to the CP manual).
0 1 80B0H The module does not recognize the data record.
0 1 80B1H Destination area invalid.
The destination area is too short.
0 1 80B2H The communication bus connection between the CPU and CP is not established.
0 1 80C0H The data record cannot be read.
0 1 80C1H The specified data record is currently being processed.
0 1 80C2H There are too many jobs pending.
0 1 80C3H Resources occupied (memory).
0 1 80C4H Communication error (occurs temporarily, it is usually best to repeat the job in the user
program).
0 1 80D2H Module start address incorrect.

FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
134 Programming Manual, 03/2008, C79000-G8976-C229-01
4.2 FCs for DP (distributed I/O) with S7-300
4.2.1 Overview of FCs and their use
Overview
The following FCs are available for the DP master and DP slave modes with an S7300:

can be used with: FC
DP master DP slave
Meaning
DP_SEND (FC1) X X for sending data
DP_RECV (FC2) X X for receiving data
DP_DIAG (FC3) X - for diagnostic functions initiated by
the DP master
DP_CTRL (FC4) X - for control functions
Application
The following diagram illustrates the use of the DP_SEND and DP_RECV FCs on the DP
master and DP slave.
DP_RECV
PROFlBUS-CP CPU
DP_SEND DP_RECV
DP_SEND
PROFlBUS-CP CPU
DP~Master DP~Slave
STEP 7
user
program
DP
data areas
send
receive
PROFlBUS
STEP 7
user
program
DP
data areas
receive
send

Figure 4-3 Using the FCs DP_SEND and DP_RECV with DP master and DP slave
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 135
4.2.2 FC1 DP_SEND
4.2.2.1 Meaning and call - DP_SEND
Meaning
FC DP_SEND transfers data to the PROFIBUS CP. Depending on the mode of the
PROFIBUS CP, DP_SEND has the following significance:
When used in the DP master
The block transfers the data of a specified DP output area to the PROFIBUS CP for output to
the distributed I/O system.
When used in the DP slave
The block transfers the input data of the DP slave to the PROFIBUS CP for transfer to the
DP master
The selected data area can be a process image area, a memory bit area or a data block
area.
Correct execution is signaled when the entire DP data area could be accepted by the
PROFIBUS CP.
Note that FC DP_SEND must then be called successfully at least once for the DP slave in
the user program if inputs were configured for this slave. Please read the information in the
manual as well.
Call interface
DP_SEND
BOOL
BOOL WORD
ANY
WORD
CPLADDR
STATUS
ERROR
DONE
SEND


Example of a call in STL representation

STL Explanation
call fc 1(
CPLADDR:=W#16#0120,
SEND:=P#db17.dbx0.0 byte 103,
DONE:=M 99.1,
ERROR:=M 99.0,
STATUS:=MW 104 );

//DP_SEND function call
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
136 Programming Manual, 03/2008, C79000-G8976-C229-01
4.2.2.2 How DP_SEND works
Operating principle
The following flow diagram illustrates the normal sequence of data transfer triggered with
DP_SEND in the user program.
Each DP_SEND job in the user program is acknowledged by the PROFIBUS CP setting
values in the DONE, ERROR and STATUS output parameters.
{
...
DP_SEND
DP_SEND
DP_SEND
1, 0, 0000
1)
0, 0, 8180
1) 2)
0, 0, 8180
1)
...
DP_SEND
DP_SEND
DP_SEND
1, 0, 0000
1)
0, 0, 8180
1)
0, 0, 8180
1)
DP_SEND
0, 0, 8180
1)
1) Parameter transfer DONE, ERROR, STATUS
User program
(CPU cycle ~ DP master)
Time
Assigning DP_SEND user data
(all outputs 'A')
Communication partners
(DP slaves)
Time Time
Startup phase
2) Display 8183H is available during startup for older CP types
Assigning DP_SEND user data
(all outputs 'B')
Assigning DP_SEND user data
(all outputs 'B')
Legend:
Do not change
user data 'A'.
Do not change
user data 'C'.
Do not change
user data 'B'.
Transfer
of 'substitute data (0)'
via PROFlBUS in
progress
Transfer
of 'A'
via PROFlBUS in
progress
Transfer
of 'B'
via PROFlBUS in
progress
PROFlBUS CP
(DP polling cycle)


FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 137
Guarantee of data transfer
The diagram also shows that with the confirmation DONE=1, ERROR=0 and STATUS=0000,
data transfer to the communications partner is functioning correctly.
The latest send data transferred to the PROFIBUS CP is always passed on to the
communications partner. For this reason, new user data must only be entered in the send
buffer following a positive acknowledgment (DONE=1, ERROR=0, STATUS=0000).
4.2.2.3 Explanation of the formal parameters - DP_SEND
Explanation of the formal parameters
The following table explains all the formal parameters for the DP_SEND function:

Parameter Declaration Data type Possible values Description
CPLADDR INPUT WORD Module start address
When you configure the CP, the module start address
is displayed in the configuration table. Specify this
address here.
SEND INPUT ANY
(only the
following are
permitted as
VARTYPE:
With FC1 as of
V3: BYTE
With FC1 up to
V2.x: BYTE,
WORD and
DWORD)
Specifies the address and length
The address of the DP data area points to one of the
alternatives:
PI area
Memory bit area
Data block area

The length must be set for
DP master: 1...21600
DP slave: 1...240
DONE OUTPUT BOOL 0: -
1: new data
The status parameter indicates whether or not the job
was completed without errors.
For the meaning in conjunction with the ERROR and
STATUS parameters, refer to ""..
ERROR OUTPUT BOOL 0: -
1: Error
Error code
For the meaning in conjunction with the DONE and
STATUS parameters, refer to "".
STATUS OUTPUT WORD See " " Status code
For the meaning in conjunction with the DONE and
ERROR parameters, refer to "".

FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
138 Programming Manual, 03/2008, C79000-G8976-C229-01
4.2.2.4 Condition codes of the DP_SEND block
Condition codes
The following table shows the condition codes formed based on DONE, ERROR and
STATUS that must be evaluated by the user program.

Note
For entries coded with 8FxxH in STATUS, refer to the information in the STEP 7 Standard
and System Functions reference manual. The chapter describing error evaluation with the
RET_VAL output parameter contains detailed information.
To find out which SFCs are used and are relevant for error evaluation, display the properties
dialog of the FC described here in the "Calls" tab.


Table 4-5 DP_SEND condition codes
DONE ERROR STATUS Meaning
0 0 8180H DP not started due to:
CP STOP or
"no parameter assignment"
(occurs here instead of the code 0,1,8183H).
1 0 0000H New data transferred without error.
0 1 8183H No configuration or the DP service has not yet started on the PROFIBUS CP.
0 1 8184H System error or bad parameter type.
0 1 8F22H Area length error reading a parameter (e.g. DB too short).
0 1 8F23H Area length error writing a parameter (e.g. DB too short).
0 1 8F24H Area error reading a parameter.
0 1 8F25H Area error writing a parameter.
0 1 8F28H Alignment error reading a parameter.
0 1 8F29H Alignment error writing a parameter.
0 1 8F30H Parameter is in the writeprotected 1st current data block.
0 1 8F31H Parameter is in the writeprotected 2nd current data block.
0 1 8F32H Parameter contains a DB number that is too high.
0 1 8F33H DB number error.
0 1 8F3AH Destination area not loaded (DB).
0 1 8F42H Timeout reading a parameter from the I/O area.
0 1 8F43H Timeout writing a parameter to the I/O area.
0 1 8F44H Address of the parameter to be read is disabled in the access track.
0 1 8F45H Address of the parameter to be written is disabled in the access track.
0 1 8F7FH Internal error, e.g. illegal ANY reference.
0 1 8090H No module with this address exists.
0 1 8091H Logical base address not at a double word boundary.
0 1 80A1H Negative acknowledgment writing to the module.
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 139
DONE ERROR STATUS Meaning
0 1 80B0H The module does not recognize the data record.
0 1 80B1H The number of data bytes to be sent exceeds the upper limit for this service (applies to
DP master and DP slave mode).
0 1 80C0H The data record cannot be read.
0 1 80C1H The specified data record is currently being processed.
0 1 80C2H There are too many jobs pending.
0 1 80C3H Resources occupied (memory).
0 1 80C4H Communication error (occurs temporarily, it is usually best to repeat the job in the user
program).
0 1 80D2H Logical base address incorrect.

4.2.3 FC2 DP_RECV
4.2.3.1 Meaning and call - DP_RECV
Meaning
The DP_RECV function (FC) receives data over PROFIBUS. DP_RECV has the following
significance depending on the mode of the PROFIBUS CP:
When used in the DP master
DP_RECV receives the process data from the distributed I/O along with status
information and enters this in a specified DP input area.
When used on the DP slave
DP_RECV accepts the output data transferred by the DP master in the DP data area
specified in the block.
The data area specified for the receive data can be a process image area, a bit address area
or a data block area.
Errorfree execution of the function is signaled when the entire DP data input area could be
transferred by the PROFIBUS CP.
Note that FC DP_RECV must be called successfully at least once on the DP slave in the
user program if output data was configured for this DP slave. Please read the information in
the manual.
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
140 Programming Manual, 03/2008, C79000-G8976-C229-01
Additional task: Entering the status byte
The DP_RECV function has the following additional task:
Updating the DP status byte DPSTATUS. This means that DP_RECV handles tasks for
DP diagnostics
If no receive data is configured, DP_RECV must be called with a length of 1 to update the
DPSTATUS status byte (applies only to DP masters; with DP slaves, the status byte
cannot be read without data).
Please read the information in the manual as well.
Enabling the station list (see DP_DIAG).
Call interface
DP_RECV
WORD
BYTE
BOOL
BOOL
ANY
WORD
CPLADDR
STATUS
ERROR
NDR
DPSTATUS
RECV


Example in STL representation

STL Explanation
call fc 2(
CPLADDR:=W#16#0120,
RECV:= P#db17.dbx240.0 byte 103,
NDR:=M 99.1,
ERROR:=M 99.0,
STATUS:=MW 104,
DPSTATUS:=MB 0 );

//DP_RECV function call

FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 141
4.2.3.2 How DP_RECV works
Operating principle
The following flow diagram illustrates the normal sequence of data transfer triggered with
DP_RECV in the user program.
Each DP_RECV job in the user program is acknowledged by the PROFIBUS CP setting
values in the NDR, ERROR and STATUS output parameters.
...
DP_RECV
DP_RECV
DP_RECV
1, 0, 0000
1)
0, 0, 8180
1) 2)
0, 0, 8180
1)
...
DP_SEND
DP_RECV
DP_RECV
0, 0, 8180
1)
0, 0, 8180
1)
1, 0, 0000
1)
DP_RECV
1, 0, 0000
1)
...
1) Parameter transfer DONE, ERROR, STATUS
User program
(CPU cycle ~ DP master)
Time
Accept received data '0' or '0' and 'A'
and evaluate DPSTATUS / station list
Communication partners
(DP slaves)
Time Time
Transfer
of 'B'
via PROFlBUS
in progress
2) Display 8183H is available during startup for older CP types
Transfer
of 'A'
via PROFlBUS
in progress
Accept received data 'A' or 'A' and 'B'
and evaluate DPSTATUS / station list
Accept received data 'B'
and evaluate DPSTATUS / station
list
Legend:
Startup phase:
during startup phase
the DP master
(PROFlBUS~CP) will
assign 0
to each in
PROFlBUS CP
(DP polling cycle)


FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
142 Programming Manual, 03/2008, C79000-G8976-C229-01
Guarantee of data acceptance
The diagram also shows that the confirmation NDR=1, ERROR=0 and STATUS=0000
indicates reliable data reception. Requirement: The DP master and the DP slaves are in the
data transfer phase.
Note the following:
In DP master mode:
If a DB slave is not in the data transfer phase, the corresponding received data is set to 0.
If the DP master is neither in the RUN nor CLEAR state (bits 4 and 5 in DPSTATUS), all
the received data is set to 0.
If data has been received from the DP slave several times since the last DP_RECV
function call, only the last received data is fetched with the next DP_RECV.
In DP slave mode:
If the DP slave is not in the data transfer phase (bit 1 in DPSTATUS) or the DP master is
in the CLEAR state (bit 2 in DPSTATUS), the received data is set to 0.
If data has been received from the DP master several times since the last DP_RECV
function call, only the last received data is fetched with the next DP_RECV.
4.2.3.3 Explanation of the formal parameters - DP_RECV
Explanation of the formal parameters
The following table explains all the formal parameters for the function DP_RECV:

Parameter Declaration Data type Possible values Description
CPLADDR INPUT WORD Module start address
When you configure the CP, the module start address
is displayed in the configuration table. Specify this
address here.
RECV INPUT ANY
(only the
following are
permitted as
VARTYPE:
With FC1 as of
V3: BYTE
With FC1 up to
V2.x: BYTE,
WORD and
DWORD)
Specifies the address and length
The address of the DP data area points to one of the
alternatives:
PI area
Memory bit area
Data block area

The length must be set for:
DP master: 1...2160
DP slave: 1...240
DP master; only read status byte: 1
(see also CP manual)
NDR OUTPUT BOOL 0: -
1: New data
accepted
The status parameter indicates whether or not new
data
was accepted.
For the meaning in conjunction with the ERROR and
STATUS parameters, refer to "".
ERROR OUTPUT BOOL 0: -
1: Error
Error code
For the meaning in conjunction with the NDR and
STATUS parameters, refer to "".
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 143
Parameter Declaration Data type Possible values Description
STATUS OUTPUT WORD See "" Status code
For the meaning in conjunction with the NDR and
ERROR parameters, refer to "".
DPSTATUS OUTPUT Byte For coding, see
below under
DPSTATUS
DP status code

4.2.3.4 Condition codes of the DP_RECV block
Condition codes
The following table shows the codes formed by the NDR, ERROR and STATUS parameters
that must be evaluated by the user program.

Note
For entries coded with 8FxxH in STATUS, refer to the information in the STEP 7 Standard
and System Functions reference manual. The chapter describing error evaluation with the
RET_VAL output parameter contains detailed information.
To find out which SFCs are used and are relevant for error evaluation, display the properties
dialog of the FC described here in the "Calls" tab.



NDR ERROR STATUS Meaning
0 0 8180H DP not started due to:
CP STOP or
"no parameter assignment"
(occurs here instead of the code 0,1,8183H).
1 0 0000H New data accepted without error.
0 1 8183H No configuration or the DP service has not yet started on the PROFIBUS CP.
0 1 8184H System error or bad parameter type.
0 1 8F22H Area length error reading a parameter (e.g. DB too short).
0 1 8F23H Area length error writing a parameter (e.g. DB too short).
0 1 8F24H Area error reading a parameter.
0 1 8F25H Area error writing a parameter.
0 1 8F28H Alignment error reading a parameter.
0 1 8F29H Alignment error writing a parameter.
0 1 8F30H Parameter is in the writeprotected 1st current data block.
0 1 8F31H Parameter is in the writeprotected 2nd current data block.
0 1 8F32H Parameter contains a DB number that is too high.
0 1 8F33H DB number error.
0 1 8F3AH Destination area not loaded (DB).
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
144 Programming Manual, 03/2008, C79000-G8976-C229-01
NDR ERROR STATUS Meaning
0 1 8F42H Timeout reading a parameter from the I/O area.
0 1 8F43H Timeout writing a parameter to the I/O area.
0 1 8F44H Address of the parameter to be read is disabled in the access track.
0 1 8F45H Address of the parameter to be read is disabled in the access track.
0 1 8F7FH Internal error, e.g. illegal ANY reference.
0 1 8090H No module with this address exists.
0 1 8091H Logical base address not at a double word boundary.
0 1 80A0H Negative acknowledgment writing to the module.
0 1 80B0H The module does not recognize the data record.
0 1 80B1H The number of data bytes to be sent exceeds the upper limit for this service (applies to
DP master and DP slave mode).
0 1 80C0H The data record cannot be read.
0 1 80C1H The specified data record is currently being processed.
0 1 80C2H There are too many jobs pending.
0 1 80C3H Resources occupied (memory).
0 1 80C4H Communication error (occurs temporarily, it is usually best to repeat the job in the user
program).
0 1 80D2H Logical base address incorrect.

4.2.3.5 DPSTATUS - DP_RECV
DPSTATUS
The coding of the DPSTATUS output parameter is different for the DP master mode and DP
slave mode.
DP master mode
0
7 6 4 3 1 5 0 2


Table 4-6 Meaning of the bits in DPSTATUS in DP master mode
Bit Meaning
7 not used
6 This bit is not set.
Please read the information in the manual as well.
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 145
Bit Meaning
5,4 Values for DPSTATUS of the DP master:
00 RUN
01 CLEAR
10 STOP (this is now the OFFLINE mode)
11 OFFLINE
Please read the information in the manual as well.
3 Value 1: Cyclic synchronization is active
2 Value 0: No new diagnostic data exists
Value 1: Evaluation of diagnostic list useful; at least one station has new diagnostic data
1 Value 0: All DP slaves are in the data transfer phase
Value 1: Evaluating the station list is useful
0 DP mode
Value 0: DP master mode
The other bits only have the specified meaning when this bit is not set.

DP slave mode
1
7 6 4 3 1 5 0 2


Table 4-7 Meaning of the bits in DPSTATUS in DP slave mode
Bit Meaning
7-5 not used
4 This bit is not set.
Please read the information in the manual as well.
3 This bit is not set.
Please read the information in the manual as well.
2 Value 1: DP master 1 is in the CLEAR mode. The DP slave receives the value 0 in the DP data intended for the
outputs. This has no effect on the send data.
1 Value 1: The configuration/parameter assignment is not yet completed.
0 Value 1: DP slave mode.
The other bits only have the specified meaning when this bit is set.


NOTICE
Please note, that DPSTATUS must not be evaluated until the return parameter NDR=1 is
set.

FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
146 Programming Manual, 03/2008, C79000-G8976-C229-01
4.2.4 FC3 DP_DIAG
4.2.4.1 Meaning and call - DP_DIAG
Meaning of the block
FC DP_DIAG is used to request diagnostic information. The following types of job are
possible:
Request DP station list
Request DP diagnostics list;
Request DP single status;
Read input/output data of a DP slave acyclically
Read older DP single diagnostic information
Read DP status.
Read DP mode for PLC/CP stop
Read current status of the DP slave.
Diagnostics data can also be requested for a specific slave by specifying a station address.
To transfer the diagnostic data to the CPU, you should reserve a memory area in the CPU
and specify this area in the call. This memory area can be a data block area or a bit memory
area. The maximum length of the available memory area must also be specified in the job.

Note
FC DP_DIAG is only of practical use in the DP master mode.

Exclusion
As long as this block is running, it must not be supplied with new job data.
Exception: Requesting the DP station list or DP diagnostics list.
Call interface
DP_DIAG
WORD
BYTE
BOOL
BOOL
BYTE
WORD
CPLADDR
STATUS
ERROR
NDR
DIAGLNG
DTYPE
ANY
BYTE
DIAG
STATION

Example in STL representation
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 147
STL Explanation
call fc 3(
CPLADDR:=W#16#0120,
DTYPE:=B#16#00,
STATION:=B#16#03,
DIAG:=P#db18.dbx0.0 byte 16,
NDR:=M 70.0,
ERROR:=M 70.1,
STATUS:=MW 72,
DIAGLNG:=MB 20 );

//DP_DIAG function call

4.2.4.2 How DP_DIAG works
Sequence / handling on the call interface
The DP_DIAG function call is processed during cyclic execution of the user program as
follows:
The job is triggered with the first call. Diagnostic data is only returned in the acknowledgment
of one of the subsequent calls.
DP_DlAG
DP_DlAG
PROFlBUS-CP
(DP-Pollzyklus)
DP_DlAG
0, 0, 8181 1)
Time
Evaluate old / return
values
User program
(CPU cycle - DP master)
0, 0, 8181 1)
Time
1, 0, 0000 1)
1) Parameter transfer NDR, ERROR, STATUS


FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
148 Programming Manual, 03/2008, C79000-G8976-C229-01

Note
Please note the following special feature of the job types read_DP_station_list and
read_DP_diagnostic_list:
The diagnostic job supplies the diagnostic data available at the time of the last DPRECV
call. Reading a list prevents the data from being read out again (return value 0x8182).
The lists are released again after a new diagnostic event followed by a DPRECV call.

After calling DP_DIAG, you obtain information indicating one of the situations below:
NDR=0, ERROR=0, STATUS=8181
As long as the code combination NDR=0, ERROR=0 and STATUS=8181 is set, the job
parameters must not be modified.
NDR=1
The parameter value NDR=1 indicates that valid diagnostic data is available. Additional
information is possible in the STATUS parameter.
NDR=0, ERROR=1
An error has occurred. The diagnostic data is invalid. The error message is located in
STATUS.
4.2.4.3 Explanation of the formal parameters - DP_DIAG
Explanation of the formal parameters
The following table explains all the formal parameters for the function DP_DIAG:

Parameter Declaration Data type Possible values Description
CPLADDR INPUT WORD Module start address
When you configure the CP, the module start
address is displayed in the configuration table.
Specify this address here.
DTYPE INPUT BYTE 0: Station list
1: Diagnostic list
2: Current diagnostic
info
3: Older diagnostic info
4: Read status

5: Read status for
CPU STOP
6: Read status for
CP STOP
7: Read input data
(acyclically)
8: Read output data
(acyclically)
10: Read current status
of the DP slave
Diagnostic type
STATION INPUT BYTE Station address of the DP slave
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 149
Parameter Declaration Data type Possible values Description
DIAG INPUT ANY
(only the
following are
permitted as
VARTYPE:
BYTE, WORD
and DWORD)
The length must be set
from 1 to 240
Specifies the address and length
Address of the data area. References the
following alternatives:
PI area
Memory bit area
Data block area
Note:
If more diagnostic data exist than can be entered
in the DIAG area, only as much data as specified
in the DIAG length will be transferred. The actual
length is indicated in DIAGLNG.
NDR OUTPUT BOOL 0: -
1: new data
This parameter indicates whether or not new data
were accepted.
For the meaning in conjunction with the ERROR
and STATUS parameters, refer to "".
ERROR OUTPUT BOOL 0: -
1: Error
Error code
For the meaning in conjunction with the NDR and
STATUS parameters, refer to "".
STATUS OUTPUT WORD See list Status code
For the meaning in conjunction with the NDR and
ERROR parameters, refer to "".
DIAGLNG OUTPUT BYTE See list This contains the actual length (in bytes) of the
data made available by the PROFIBUS CP,
regardless of the buffer size specified in the DIAG
parameter.

4.2.4.4 Job types - DP_DIAG
Job types
The following overview of the specifications for DTYPE, STATION and DIAGLNG shows the
permitted or useful entries.
Table 4-8 Job types for DP_DIAG
DTYPE Corresponds
to job
Parameter
STATION
DIAGLNG Acknowledgement code
(contained in the STATUS parameter; shown in Table
"DP_DIAG codes")
0 Read DP station
list
--- - ignored - Module start address
When you configure the CP, the module start address is
displayed in the configuration table. Specify this address
here.
1 Read DP
diagnostic list
--- - ignored - The DP diagnostics list informs the CPU program about the
DP slaves with new diagnostics data.
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
150 Programming Manual, 03/2008, C79000-G8976-C229-01
DTYPE Corresponds
to job
Parameter
STATION
DIAGLNG Acknowledgement code
(contained in the STATUS parameter; shown in Table
"DP_DIAG codes")
2 Read current
DP single
diagnostic data
1...126 >=6 The current DP single diagnostics informs the CPU program
of the current diagnostic data of a DP slave.
3 Read older DP
single
diagnostic
information
1...126 >=6 The older DP single diagnostics informs the CPU program
of the older diagnostic data of a DP slave. This data is
stored on the PROFIBUS CP and read according to the
"last in - first out" principle in the ring buffer.
The structure of the ring buffer is explained below.
If changes occur quickly in the DP slave diagnostic data,
this function allows the diagnostic data of a DP slave to be
acquired and evaluated in the CPU program of the DP
master.
4 Read the
requested
operating mode
with the DP-
CTRL job
(CYTPE=4)
>=0 With this job, you can read the DP status. The following
statuses are possible: :
RUN
CLEAR
STOP (now the OFFLINE mode)
OFFLINE
Please read the information in the manual as well.
5 Read DP status
for CPU STOP
>=0 With this job you can find out the DP status to which the
PROFIBUS CP changes if the CPU changes to STOP:
RUN
CLEAR
STOP (now the OFFLINE mode)
OFFLINE

As default, the PROFIBUS CP changes to the DP status
CLEAR if the CPU changes to STOP.
Please read the information in the manual as well.
6 Read DP status
for CP STOP
>=0 With this job you can find out the DP status to which the
PROFIBUS CP changes if the CP changes to STOP:
STOP (now the OFFLINE mode)
OFFLINE

As default, the PROFIBUS CP changes to the DP status
OFFLINE if the CP changes to STOP.
Please read the information in the manual as well.
7 Read input data 1...126 >=1 With this job, the DP master (class 2) reads the input data
of the DP slave. This function is also known as shared
input.
8 Read output
data
1...126 >=1 With this job, the DP master (class 2) reads the output data
of a DP slave. This function is also known as shared output.
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 151
DTYPE Corresponds
to job
Parameter
STATION
DIAGLNG Acknowledgement code
(contained in the STATUS parameter; shown in Table
"DP_DIAG codes")
10 Read current
status of the DP
slave
1...126 >=0 With this job, you can read out the current status of the DP
slave. The following statuses are possible :
The DP master exchanges data with the DP slave
cyclically.
The DP master reads the input data of the DP slave
cyclically.
The DP master reads the output data of the DP slaves
cyclically.
The DP master is not currently processing this DP slave
cyclically.

4.2.4.5 Ring buffer for diagnostics data - DP_DIAG
Ring Buffer for Diagnostic Data
The following diagram illustrates how diagnostic data is read using the "read older DP single
diagnostic data" function. The first access reads the most recent of the older diagnostic data.
Current diag info 9th read access;
1st older diag info 1st read access; 10th read
8th older diag info 8th read access;

Figure 4-4 Ring Buffer for Diagnostic Data
When the current diagnostic data is read out, the read pointer is reset to the first older
diagnostic data.
4.2.4.6 Condition codes of DP_DIAG
Condition codes
The following table shows the codes formed by the NDR, ERROR and STATUS parameters
that must be evaluated by the user program.
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
152 Programming Manual, 03/2008, C79000-G8976-C229-01

Note
For entries coded with 8FxxH in STATUS, refer to the information in the STEP 7 Standard
and System Functions reference manual. The chapter describing error evaluation with the
RET_VAL output parameter contains detailed information.
To find out which SFCs are used and are relevant for error evaluation, display the properties
dialog of the FC described here in the "Calls" tab.


Table 4-9 DP_DIAG codes
NDR ERROR STATUS Possible
with
DTYPE
Meaning
0 0 8181H 2-10 Job active.
DP master not started due to
CP STOP or
"no parameter assignment"
(occurs here instead of the code 0,1,8183H).
0 0 8182H 0 Triggering job pointless.
DP master not started due to
CP STOP or
"no parameter assignment"
(occurs here instead of the code 0,1,8183H).
0 0 8182H 1 No new diagnostic data exist.
DP master not started due to
CP STOP or
"no parameter assignment"
(occurs here instead of the code 0,1,8183H).
1 0 0000H 0-10 Job completed without error.
1 0 8222H 7,8 Job completed without error.
The length of the DP slave data that was read is not the same as the data
length expected by the DP master based on the module list of the DP slave in
the CP database.
1 0 8227H 7,8 Job completed without error.
Message: No data exists.
1 0 8231H 4,5,6 Job completed without error.
Message: The DP status is already "RUN"
1 0 8232H 4,5,6 Job completed without error.
Message: The DP status is already "CLEAR"
1 0 8233H 4,5,6 Job completed without error.
Message: The DP status is already STOP
The STOP status is now the OFFLINE status (here code 8234H).
Please read the information in the manual as well.
1 0 8234H 4,5,6 Job completed without error.
Message: The DP status is already
"OFFLINE"
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 153
NDR ERROR STATUS Possible
with
DTYPE
Meaning
1 0 823AH 2,3,7,8 Job completed without error.
Message: 241 or 242 bytes of data were read. 240 bytes of data are available.
1 0 8241H 2,3,10 Job completed without error.
Message: The specified DP slave was not configured.
1 0 8243H 2,3,10 Job completed without error.
Message: The module list of the DP slave in the CP database only contains
empty modules.
1 0 8245H 2,3,10 Job completed without error.
Message: The DP slave is in the "read input data cyclically" mode.
1 0 8246H 2,3,10 Job completed without error.
Message: The DP slave is in the
"read output data cyclically" mode.
1 0 8248H 2,3,10 Job completed without error.
Message: The module list of the DP slave in the CP database contains input,
output or
I/O modules.
1 0 8249H 2,3,10 Job completed without error.
Message: The DP slave is deactivated due to a DP mode change ( e.g. CP
mode selector set to STOP).
1 0 824AH 2,3,10 Job completed without error.
Message: The DP slave is deactivated due to a DP_CTRL job in the CPU
program.
0 1 8090H 0-10 Logical base address of the module is invalid
0 1 80B0H 0-10 The module does not recognize the data record or is changing from RUN -->
STOP.
0 1 80B1H 0-10 Specified data record length incorrect
0 1 80C0H 0-10 Data record cannot be read
0 1 80C1H 0-10 The specified data record is being processed
0 1 80C2H 0-10 Too many jobs pending
0 1 80C3H 0-8 Resources (memory) occupied
0 1 80C4H 0-10 Communication error
0 1 80D2H 0-10 Logical base address wrong
0 1 8183H 0-10 DP master not configured.
0 1 8184H 0-8 System error or bad parameter type.
0 1 8311H >=2 DTYPE parameter outside range of values.
0 1 8313H 2,3,7,8,10 STATION parameter outside range of values.
0 1 8321H >=2 The DP slave is not providing any valid data.
0 1 8326H 7,8 The DP slave has more than 242 bytes of data available. The PROFIBUS CP
supports a maximum of 242 bytes.
0 1 8335H 7,8 The PROFIBUS CP is in PROFIBUS status: "Station not in ring".
0 1 8341H 2,3,7,8,10 The specified slave was not configured
0 1 8342H 7,8 The DP slave with the PROFIBUS address specified in the STATION
parameter is not obtainable.
0 1 8349H 7,8 The DP master is in the OFFLINE mode.
0 1 8F22H 0-10 Area length error reading a parameter (e.g. DB too short)
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
154 Programming Manual, 03/2008, C79000-G8976-C229-01
NDR ERROR STATUS Possible
with
DTYPE
Meaning
0 1 8F23H 0-10 Area length error writing a parameter (e.g. DB too short)
0 1 8F24H 0-10 Area error reading a parameter
0 1 8F25H 0-10 Area error writing a parameter
0 1 8F28H 0-10 Alignment error reading a parameter
0 1 8F29H 0-10 Alignment error writing a parameter
0 1 8F30H 0-10 Parameter is in the writeprotected 1st current data block
0 1 8F31H 0-10 Parameter is in the writeprotected 2nd current data block
0 1 8F32H 0-10 The DB number in the parameter is too high
0 1 8F33H 0-10 DB number error
0 1 8F3AH 0-10 Area not loaded (DB)
0 1 8F42H 0-10 Timeout reading a parameter from the I/O area
0 1 8F43H 0-10 Timeout writing a parameter to the I/O area
0 1 8F44H 0-10 Address of the parameter to be read locked in the access track
0 1 8F45H 0-10 Address of the parameter to be written is disabled in the access track
0 1 8F7FH 0-10 Internal error, e.g. illegal ANY reference

4.2.5 FC4 DP_CTRL
4.2.5.1 Meaning and call - DP_CTRL
Meaning of the block
FC DP_CTRL transfers control jobs to the PROFIBUS CP. You specify a job field
(CONTROL parameter) to specify the control job in greater detail.
The following types of job are possible:
Global control acyclic/cyclic;
Delete older diagnostic data;
Set current DP mode;
Set DP mode for PLC/CP STOP;
Read input/output data cyclically;
Set the operating mode of the DP slave.
There are restrictions relating to the job types listed here (please refer to the information in
the manual for the module).

Note
FC DP_CTRL is only of practical use in the DP master mode.
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 155

Connector
As long as this block is running, it must not be supplied with new job data.
Call interface
DP_CTRL
WORD
BOOL
BOOL
ANY
WORD
CPLADDR
STATUS
ERROR
DONE
CONTROL


Example in STL representation

STL Explanation
call fc 4(
CPLADDR:=W#16#0120,
CONTROL:=P#db14.dbx0.0 byte 30,

DONE:=M 70.0,
ERROR:=M 70.1,
STATUS:=MW 72 );
//DP_CTRL block call

// The buffer for the control job
// occupies the first 30 bytes in DB 14.

FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
156 Programming Manual, 03/2008, C79000-G8976-C229-01
4.2.5.2 How DP_CTRL works
Sequence / handling on the call interface
The DP_CTRL function call is processed within the cyclic execution of the user program as
shown below:
The job is triggered with the first call. Diagnostic data is only returned in the acknowledgment
of one of the subsequent calls.
.
.
.
DP_CTRL
DP_CTRL
DP_CTRL
1, 0, 0000
1)
0, 0, 8181
1)
0, 0, 8181
1)
1) Parameter transfer DONE, ERROR, STATUS
User program
(CPU cycle)
Time
Order completed without errors
Time
Legend:
Communication partners
(DP slave)
Time
PROFlBUS CP
(DP polling cycle)



After calling DP_CTRL, you obtain one of the following condition code patterns as the
reaction:
DONE=0, ERROR=0, STATUS=8181
As long as the code combination DONE=0, ERROR=0 and STATUS=8181 is set, the job
parameters must not be modified.
DONE=1
The parameter value DONE=1 indicates that the job was executed. Additional information
is possible in the STATUS parameter.
DONE=0, ERROR=1
An error has occurred. The error message is located in STATUS.
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 157
4.2.5.3 Explanation of the formal parameters - DP_CTRL
Explanation of the formal parameters
The following table explains all the formal parameters for the DP_CTRL function:

Parameter Declaration Data type Possible values Description
CPLADDR INPUT WORD Module start address
When you configure the CP, the module
start address is displayed in the configuration table.
Specify this address here.
CONTROL INPUT ANY
(only the
following are
permitted as
VARTYPE:
BYTE, WORD
and DWORD)
The length must
be set from 1 to
240
Specifies the address and length of the CONTROL job
field
Address of the data area. References the following
alternatives:
PI area
Memory bit area
Data block area
The length must be at least as long as the number of
parameters.
DONE OUTPUT BOOL 0: -
1: Job executed
without error.
Indicates whether the job was sent and completed
without errors.
For the meaning in conjunction with the ERROR and
STATUS parameters, refer to the following table.
ERROR OUTPUT BOOL 0: -
1: Error
Error code
For the meaning in conjunction with the DONE and
STATUS parameters, refer to the follow table.
STATUS OUTPUT WORD See following
table 'Return
Codes'
Status code
The following table shows the condition codes formed
by the DONE and ERROR parameters.
Structure of the CONTROL job field
The control job has the following structure:
CONTROL
address
Refer to 'Parameter'
(number and name)
CTYPE
Param. 2nd byte
Param. nth byte
Param. 1st byte


FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
158 Programming Manual, 03/2008, C79000-G8976-C229-01
Example of the job field
With a job field as shown below, a cyclic global control job SYNC and Unfreeze is sent for
group 4 and group 5 without the autoclear option.
Byte 0 01H
Byte 2 18H
Byte 3 00H
Byte 1 24H
CTYPE
DB 14
Autoclear
Group Select
Command Mode



The length in the ANY pointer must be at least 4 (in the example, 30 has been selected).
4.2.5.4 Job types - DP_CTRL
Job types
Permitted or feasible specifications for the job are shown in the following overview based on
the specification for CTYPE and the information in the job field.

Parameter in job field CTYPE Corresponds to
job
Name Quantity
Description
0 Trigger global
control
1. byte:
command mode
2nd byte:
group select
(See section following
this table.)
2 A single global control job is sent to the DP slaves
selected with group select. The command mode
parameter specifies the following global control jobs:
SYNC
UNSYNC
FREEZE
UNFREEZE
CLEAR - is not supported (please read the
information in the manual as well)
It is possible to specify more than one job in the
command mode parameter.
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 159
Parameter in job field
1 Trigger cyclic
global control
1. byte:
command mode
2nd byte:
group select
3rd byte:
autoclear
(See section
following this table.)
3 The sending of cyclic global control jobs to the DP
slaves selected with group select is triggered on the
PROFIBUS CP.
The autoclear parameter is only evaluated with the
SYNC global control job. If at least one DP slave in the
selected group is not in the data transfer phase and
autoclear=1 is set, the CLEAR mode is activated, in
other words, the output data of the DP slaves is set to
"0".
The following global jobs can be activated in the
command mode parameter:
SYNC
FREEZE
CLEAR (CLEAR-Bit = 1) - is not supported (please
read the information in the manual as well)

or deactivated:
UNSYNC
UNFREEZE
UNCLEAR (CLEAR bit = 0)
It is possible to specify more than one job in the
command mode parameter.
An active cyclic global control job can only be
terminated by a further global control job (cyclic or
acyclic).
To terminate the job set in the command mode, the job
must be canceled. For example, the SYNC job
is canceled by an UNSYNC job.
3 Delete older DP
single diagnostic
data
1. Byte:
Slave address
1 to 126
127 = all
slaves
1 The older diagnostic data stored on the PROFIBUS CP
is deleted for one or all DP slaves.
5 Set DP mode for
CPU STOP
1. Byte:
RUN = 00H
CLEAR = 01H
STOP = 02H
OFFLINE = 03H
1 This job specifies which DP mode the PROFIBUS CP
changes to if the CPU changes to STOP:
RUN
CLEAR
STOP (now the OFFLINE mode)
OFFLINE
As default, the PROFIBUS CP changes to the DP
status CLEAR if the CPU changes to STOP.
This mode remains set during a CP mode change from
RUN --> STOP --> RUN.
Please read the information in the manual as well.
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
160 Programming Manual, 03/2008, C79000-G8976-C229-01
Parameter in job field
6 Set DP mode for
CP STOP
1. Byte:
STOP =02H
OFFLINE=03H
1 This job specifies which DP mode the PROFIBUS CP
changes to if the CP changes to STOP.
STOP (now the OFFLINE mode)
OFFLINE
As default, the PROFIBUS CP changes to the DP
status OFFLINE if the CP changes to STOP.
This mode remains set during a CP mode change from
RUN --> STOP --> RUN.
Please read the information in the manual as well.
7 Read input data
cyclically (DP
master class 2)
1. byte:
slave address
1 to 125
1 This job is not supported.
Please read the information in the manual as well.
8 Read output
data cyclically
(DP master
class 2)
1. byte:
slave address
1 to 125
1 This job is not supported.
Please read the information in the manual as well.
9 Terminate cyclic
processing of
the DP slave by
the DP master
(class 1, class
2)
1. byte:
slave address
1 to 125
1 This job terminates the cyclic reading of the input data
or output data of the addressed DP slave or the data
transfer (DP master class 1).
The DP slave is then no longer processed by the
PROFIBUS CP acting as DP master (class 2).
This deactivates the DP slave.
10 Start cyclic
processing as
DP master
(class 1)
1. byte:
slave address
1 to 125
1 The PROFIBUS CP acting as the DP master (class 1)
then assigns parameters to the addressed DP slave
and starts cyclic data transfer (writing outputs/reading
inputs).
This activates the DP slave.

FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 161
4.2.5.5 Command mode and group select - DP_CTRL
Structure of command mode
In the command mode parameter, you specify the modes for input and output data for the
cyclic and acyclic global control jobs.
The meaning is as follows:
1 = activated
0 = not activated
7 6 4 3 1 5 0 2
not used
Bit number:
CLEAR
UNFREEZE
FREEZE
UNSYNC
SYNC
not used


Structure of group select
In the group select parameter, you specify the group to be addressed by the control job
specified in the command mode parameter. The group select parameter occupies the
second byte in the control job. Each bit defines a possible DP slave group.
The meaning is as follows:
1 = assigned
0 = not assigned
1
7 6 4 3 1 5 0 2
7 6 4 3 5 2 8
Bit number:
Group;


FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
162 Programming Manual, 03/2008, C79000-G8976-C229-01
4.2.5.6 Condition codes of the DP_CTRL block
Condition codes
The following table shows the return codes formed by the DONE, ERROR and STATUS
parameters that must be evaluated by the user program.

Note
For entries coded with 8FxxH in STATUS, refer to the information in the STEP 7 Standard
and System Functions reference manual. The chapter describing error evaluation with the
RET_VAL output parameter contains detailed information.
To find out which SFCs are used and are relevant for error evaluation, display the properties
dialog of the FC described here in the "Calls" tab.


Table 4-10 DP_CTRL condition codes
DONE ERROR STATUS Possible with
CTYPE
Meaning
0 0 8181H 0..10 Job active.
DP master not started due to:
CP STOP or
"no parameter assignment"
(occurs here instead of the code 0,1,8183H).
1 0 0000H 0..10 Job completed without error.
1 0 8214H 0,1 Job completed without error.
Message: Cyclic global control job is sent as acyclic global control job
1 0 8215H 0,1 Job completed without error.
The slaves addressed in the selected group are all deactivated.
1 0 8219H 0,1 Job completed without error.
An attempt was made to send an already active cyclic global control
again. The global control continues unchanged.
1 0 8228H 0,1 Job completed without error.
Message: The DP slaves addressed in the selected groups do not have
any input modules.
1 0 8229H 0,1 Job completed without error.
Message: The DP slaves addressed in the selected groups do not have
any output modules.
1 0 8231H 4,5,6 Job completed without error.
Message: The DP status is already "RUN"
1 0 8232H 4,5,6 Job completed without error.
Message: The DP status is already "CLEAR"
1 0 8233H 4,5,6 Job completed without error.
Message: The DP status is already "STOP"
1 0 8234H 4,5,6 Job completed without error.
Message: The DP status is already "OFFLINE"
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 163
DONE ERROR STATUS Possible with
CTYPE
Meaning
1 0 8235H 4 Job completed without error.
Message: The DP status is already "RUN" with activated AUTOCLEAR
1 0 8236H 4 Job completed without error.
Message: The DP status is already "RUN" with deactivated AUTOCLEAR
1 0 8241H 7-10 Job completed without error.
Message: The specified DP slave was not configured.
1 0 8243H 7-10 Job completed without error.
Message: The DP slave is already deactivated since the module list of the
DP slave in the CP database only contains empty modules.
1 0 8245H 7-10 Job completed without error.
Message: The DP slave is already in the "read input data cyclically" mode
1 0 8246H 7-10 Job completed without error.
Message: The DP slave is already in the "read output data cyclically"
mode
1 0 8248H 7-10 Job completed without error.
Message: The module list of the DP slave in the CP database contains
input, output, or input/output modules.
1 0 8249H 7-10 Job completed without error.
Message: This slave is deactivated due to a change in the DP mode.
1 0 824AH 7-10 Job completed without error.
Message: The DP slave is already deactivated due to a DP_CTRL job in
the CPU program
0 1 8090H 0..10 No module with this address exists.
0 1 8091H 0..10 Logical base address not at a double word boundary.
0 1 80B0H 0..10 The module does not recognize the data record.
0 1 80B1H 0..10 The specified data record length is incorrect.
0 1 80C0H 0..10 The data record cannot be read.
0 1 80C1H 0..10 The specified data record is currently being processed.
0 1 80C2H 0..10 There are too many jobs pending.
0 1 80C3H Resources occupied (memory).
0 1 8183H 0..10 The DP master is not configured.
0 1 8184H System error or bad parameter type.
0 1 8311H 0..10 CTYPE parameter outside the range of values
0 1 8312H 0..10 The length of the area in the CONTROL parameter is too short.
0 1 8313H 3,7,8,9, 10 The slave address parameter is outside the range of values.
0 1 8315H 0,1 All DP slaves of the group specified in the global control are deactivated
(always occurs with an empty group).
0 1 8317H 8 The length of the configured output data is greater than the configured
receive area of the DP slave.
Activating the slave mode "Read output data" is not possible.
0 1 8318H 0,1,4,5,6 The parameter 1st byte of the job data field is outside the range of values.
With GLOBAL CONTROL, CLEAR was used with SYNC or a GLOBAL
CONTROL with CLEAR set was sent to group 0.
0 1 831AH 0,1 At least one DP slave cannot handle FREEZE.
0 1 831BH 0,1 At least one DP slave cannot handle SYNC.
0 1 8333H 0,1 This job is not permitted in the DP "STOP" mode.
FCs / FBs for PROFIBUS
4.2 FCs for DP (distributed I/O) with S7-300
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
164 Programming Manual, 03/2008, C79000-G8976-C229-01
DONE ERROR STATUS Possible with
CTYPE
Meaning
0 1 8334H 0, 1 This job is not permitted in the DP "OFFLINE" mode.
0 1 8335H 0, 1 The PROFIBUS CP is in PROFIBUS status: "Station not in ring".
0 1 8339H 0, 1 At least one DP slave in the selected group is not in the data transfer
phase.
0 1 833CH 1 Cyclic global control must not be used in
the "PLC <-> CP free running" mode. This error does not occur on the CP
3425 because this mode is not possible with this CP (PBUS data records
are always used for data transfer).
0 1 8341H 7-10 The specified DP slave was not configured.
0 1 8183H 0..10 DP master not configured.
0 1 8184H - System error or bad parameter type.
0 1 8F22H 0..10 Area length error reading a parameter. (e.g. DB too short).
0 1 8F23H 0..10 Area length error writing a parameter.
0 1 8F24H 0..10 Area error reading a parameter.
0 1 8F25H 0..10 Area error writing a parameter.
0 1 8F28H 0..10 Alignment error reading a parameter.
0 1 8F29H 0..10 Alignment error writing a parameter.
0 1 8F30H 0..10 The parameter is in the writeprotected first current data block.
0 1 8F31H 0..10 The parameter is in the writeprotected second current data block.
0 1 8F32H 0..10 Parameter contains a DB number that is too high.
0 1 8F33H 0..10 DB number error.
0 1 8F3AH 0..10 Area not loaded (DB).
0 1 8F42H 0..10 Timeout reading a parameter from the I/O area.
0 1 8F43H 0..10 Timeout writing the parameter to the I/O area.
0 1 8F44H 0..10 Access to a parameter to be read during block execution is prevented.
0 1 8F45H 0..10 Access to a parameter to be written during block execution is prevented.
0 1 8F7FH 0..10 Internal error, e.g. illegal ANY reference.
0 1 80C4H 0..10 Communication error (occurs temporarily, it is usually best to repeat the
job in the user program).
0 1 80D2H 0..10 Logical base address incorrect.

FCs / FBs for PROFIBUS
4.3 Configuration limits / resources required by the FCs and FBs (PROFIBUS)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 165
4.3 Configuration limits / resources required by the FCs and FBs
(PROFIBUS)
Required resources
NOTICE
Please note the version information of the blocks. Blocks with other versions have different
resource requirements.

Table 4-11 Information for FCs / FBs with an S7400
NAME Version FC/FB no. Load memory
bytes
Work memory
bytes
MC7
bytes
Local data
bytes
AG_SEND 1.1 FC5 732 576 540 20
AG_RECV 1.1 FC6 656 522 486 20
AG_LSEND 3.0 FC50 1044 846 810 52
AG_LRECV 3.0 FC60 1190 992 956 58

Table 4-12 Information for FCs / FBs with an S7300
NAME Version FC/FB no. Load memory
bytes
Work memory
bytes
MC7
bytes
Local data
bytes
DP_SEND 3.0 FC1 1066 886 850 42
DP_RECV 3.0 FC2 1144 950 914 46
DP_DIAG 3.0 FC3 1956 1638 1602 58
DP_CTRL 3.0 FC4 1532 1292 1256 52
AG_SEND 4.2 FC5 1976 1664 1628 50
AG_RECV 4.7 FC6 1440 1206 1170 40


Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 167
FBs for PROFIBUS FMS
5
5.1 Overview of FBs and their use
Overview
The following function blocks are available for an S7 station involved in FMS communication.
The list shows the block numbers as they are when supplied. You can change these block
numbers.

Function block Can be used in the function of
the PROFIBUS CP as:
Type Block number FMS client FMS server
Meaning /
function
IDENTIFY FB2 X X For querying device properties
READ FB3 X - For reading data
REPORT FB4 - X For transferring data
unconfirmed
STATUS FB5 X X For a status query
WRITE FB6 X - For writing data
Difference between S7300 and S7400
Different FBs are supplied for the S7300 and S7400. Make sure you access the appropriate
block library (SIMATIC_NET_CP) depending on whether you are creating a user program for
an S7300 or an S7400.
FBs for PROFIBUS FMS
5.2 FMS block parameters
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
168 Programming Manual, 03/2008, C79000-G8976-C229-01
5.2 FMS block parameters
FB call interfaces
The following sections describe the call interface for each FB as shown below:
FB x
BYTE
WORD
BYTE PHYS
STATUS
ERROR
DONE
lD
REQ
LOG
BOOL
BYTE
ANY LOCAL
BYTE
ANY
BOOL
BOOL DWORD


Depending on the FB type, the FB has different parameters of the type INPUT, OUTPUT or
INOUT.
The following tables explain the meaning, data type, range of values and memory area of all
block parameters.
INPUT parameters

INPUT parameters Meaning Data type Value range/memory
area
Used in
FB
REQ Edge signal for executing
the block
BOOL 0=FALSE; 1=TRUE
0->1: "Start"/
I,Q,M,D,L
2 3 4 5 6
ID This identifier identifies the
FMS connection.
S7300:
The ID specifies both the
LAN connection and the P
bus address.
S7400:
The ID specifies both the
LAN connection and the K
bus connection.
Make sure you use the ID
from connection
configuration or match it to
this ID.
DWORD
(with FB
1:
WORD)
0001 0001 .. FFFF
FFFF /
I,Q,M,D,L
2 3 4 5 6
FBs for PROFIBUS FMS
5.2 FMS block parameters
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 169
INPUT parameters Meaning Data type Value range/memory
area
Used in
FB
VAR_1 The parameter addresses
the remote communications
variable to be read or
written.
Depending on the
configuration on the FMS
server, a name or index can
be specified.
ANY String:
Max. length = 254 bytes
e.g.
'<102>' (index access)
"SLAVE2" (named
access)
D
2 3 4 - 6
SD_1 Address of a local data
area from which the
variables will be
transferred.
ANY This type corresponds
to a reference to a DB,
I/O process image or bit
memory area.
Example:
SD_1 :=
P#DB17.DBX0.0 BYTE
16
In this example, the first
16 bytes of DB17 are
transferred.
I,Q,M,D,L,C,T,DBx
- - 4 - 6
RD_1 Address of a local data
area to which the variables
will be transferred.
ANY This type corresponds
to a reference to a DB,
I/O process image or bit
memory area.
Example:
SD_1 :=
P#DB17.DBX0.0 BYTE
16
In this example, the first
16 bytes of DB17 are
transferred.
I,Q,M,D,L,DBx
Note on array of bytes
for S7-300:
If there is an odd
number of bytes to be
read, the length of the
receive area must be
configured up to the
next higher even
number of bytes.
Example:
For an array[1..13] of
bytes, reserve a receive
buffer size of 14 bytes.
- 3 - - -
FBs for PROFIBUS FMS
5.2 FMS block parameters
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
170 Programming Manual, 03/2008, C79000-G8976-C229-01
OUTPUT parameters

OUTPUT parameters Meaning Data type Range of values/
memory area
Used in FB
DONE Indicates that the job is
completed.
BOOL 0=FALSE
1=TRUE: Job completed;
I,Q,M,D,L
- - 4 - 6
NDR Indicates reception of
data.
BOOL 0=FALSE
1=TRUE: New data were
accepted;
I,Q,M,D,L
2 3 - 5 -
ERROR Indicates whether or not
an error occurred.
BOOL 0=FALSE
1=TRUE: Error occurred;
I,Q,M,D,L
2 3 4 5 6
STATUS Provides detailed
information about
warnings or errors after
the job has been
completed.
WORD You will find detailed decoding
information in the sections
following.
I,Q,M,D,L
2 3 4 5 6
INPUT/OUTPUT parameters

INOUT parameters Meaning Data type Range of values/
memory area
Used in FB
PHYS Indicates the physical
status of the partner
device (VFD).
BYTE 0...3
I,Q,M,D,L
- - - 5 -
LOG Indicates the logical status
of the partner (VFD).
BYTE 0...3
I,Q,M,D,L
- - - 5 -
LOCAL "local detail" parameter of
the partner
ANY This detail can be up to 16 bytes
long.
I,Q,M,D,L
- - - 5 -
VENDOR Name of the device
vendor.
STRING Length<255
D
2 - - - -
MODEL Name of the device model. STRING Length<255
D
2 - - - -
REVISION Version (revision) of the
device.
STRING Length<255
D
2 - - - -
Memory area
The abbreviated forms for the memory areas in the table correspond to the following:

Short form Type
I Input
Q Output
FBs for PROFIBUS FMS
5.2 FMS block parameters
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 171
Short form Type
M Bit memory
L Temporary local data
D Data block area
C Counter
T Timer
DBX Data block
FB output parameters during the CP startup (S7400)
When the FB is called (REQ:0->1, EN_R=1) while the PROFIBUS CP is starting up (for
example due to a power cycle or activating a switch) the following output parameters are
possible:
DONE = 0
NDR = 0
ERROR = 1
STATUS = 0001 (connection has not been established yet) or
STATUS = 0601 (Get-OV still running)
FBs for PROFIBUS FMS
5.3 FB2 IDENTIFY
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
172 Programming Manual, 03/2008, C79000-G8976-C229-01
5.3 FB2 IDENTIFY
5.3.1 Meaning and call - IDENTIFY
Meaning of the block
With the IDENTIFY function block, you can fetch the following information about the partner
device (with S7 stations about the CPU):
Name of the device vendor.
Name of the device model.
Version (revision) of the device.
Depending on the information you receive, you could, for example:
Set the local program function to match the performance and response of the partner
Set communication parameters
Call interface
lDENTlFY
WORD
STRlNG VENDOR
STATUS
ERROR
NDR
lD
REQ
MODEL
BOOL
STRlNG
STRlNG REVlSlON
BOOL
BOOL DWORD


Example in STL representation

STL Explanation
call FB 2, DB 22 (
REQ := M 1.0,
ID := DW#16#10001,

NDR := M 1.1,
ERROR := M 1.2,
STATUS := MW 20,
VENDOR := "SLAVE2".VENDOR_ABBILD,
MODEL := "SLAVE2".MODEL_ABBILD,
REVISION := "SLAVE2".REV_ABBILD );
//IDENTIFY block call with instance DB
//Edge signal for executing the FB
//Matched with configuration of the
//FMS connection
//Indicates when "new data accepted"
//Indicates error in execution
//Detailed error decoding
//Data area for vendor name
//Data area for model
//Data area for revision
Additional information
FBs for PROFIBUS FMS
5.3 FB2 IDENTIFY
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 173
"SLAVE2"
is the symbolic name of a data block. This name is defined in the corresponding symbols
table.
VENDOR_IMAGE, MODEL_IMAGE and REVISION_IMAGE
are variables of the data type STRING. These are defined in the "SLAVE2" data block.
5.3.2 How IDENTIFY works
Operating principle
The following flow chart illustrates the normal sequence of an IDENTIFY job.
The job is activated by a (positive-going) edge change at the parameter REQ.
Each IDENTIFY job of the user program is acknowledged by the PROFIBUS CP with a value
in the output parameters NDR, ERROR and STATUS.
{
{
0, 0, XX
1)
PROFlBUS-CP
0, 0, XX
1)
1, 0, 0000
1)
lDENTlFY
Confirmed-PDU
lDENTlFY-PDU
PROFlBUS-CP
FMS-Client FMS-Server
Time
Supply lNPUT parameters
CALL FB2 (REQ=0)
User program
(CPU cycle)
Time Time
1) Parameter transfer NDR, ERROR, STATUS
Supply lNPUT parameters
CALL FB2 (REQ=1)
ldentification data
Reading
Prompt
active
Status code
exists


FBs for PROFIBUS FMS
5.4 FB3 READ
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
174 Programming Manual, 03/2008, C79000-G8976-C229-01
5.4 FB3 READ
5.4.1 Meaning and call - READ
Meaning
The READ function block reads data from a data area of the communication partner
specified by a name or index depending on the assignment of parameters for the job. The
data that is read is saved locally in a data block, an area in the process image of the
inputs/outputs or in a bit memory area.
Requirement: Configuration of communications variables
The structure of the variables on the communications partner (FMS server) is fixed. When
the FMS connection is established, the structure description is read out from the
communications partner. This is then available on the PROFIBUS CP to convert the data to
the FMS representation.
The structure description is only read when the connection is established if the
communications variable was selected during configuration of the FMS connection.
Access rights
Remember that access rights can be set for the data transfer. Data transmission is then only
possible if the FMS client has been assigned suitable rights.
FB call interface
READ
ANY
BOOL
BOOL
ANY
DWORD
WORD STATUS
ERROR
NDR
RD_1
VAR_1
lD
BOOL REQ BOOL


Example in STL representation

STL Explanation
call FB 3, DB 29 (
REQ := M 1.0,
ID := DW#16#10001,

VAR_1 := "SLAVE2".INDEX,
//READ block call with instance DB
//Signal edge change to execute the FB
//Compared with configuration of
//FMS connection
//Addresses K variable that will be read
FBs for PROFIBUS FMS
5.4 FB3 READ
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 175
STL Explanation
RD_1 := "PROZESS".Motor1,
NDR := M 1.1,
ERROR := M 1.2,
STATUS := MW 20 );
//Addresses data area as destination
//Confirmation of execution
//Indicates incorrect execution
//Detailed error decoding

5.4.2 How READ works
Operating principle
The following sequence chart shows the normal sequence of data reception triggered with
READ in the user program.
The job is activated by a (positive-going) edge change at the parameter REQ.
Every READ job in the user program is acknowledged by the PROFIBUS CP with values in
the output parameters NDR, ERROR and STATUS.
{
{
0, 0, XX
1)
PROFlBUS-CP
0, 0, XX
1)
1, 0, 0000
1)
READ
Confirmed-PDU
READ Request-PDU
PROFlBUS-CP
FMS-Client FMS-Server
Time
Supply lNPUT parameters
CALL FB3 (REQ=0)
User program
(CPU cycle)
Time Time
1) Parameter transfer NDR, ERROR, STATUS
Supply lNPUT parameters
CALL FB3 (REQ=1)
Read data from the user
data area and convert to
FMS format
Reading
active
Reading
completed


FBs for PROFIBUS FMS
5.4 FB3 READ
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
176 Programming Manual, 03/2008, C79000-G8976-C229-01
Guarantee of data transfer
The diagram shows that the reading out of the data is confirmed with the code NDR=1,
ERROR=0 and STATUS=0000.
Positive confirmation of the read job does not necessarily mean that the read job was
registered by the partner application.
FBs for PROFIBUS FMS
5.5 FB4 REPORT
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 177
5.5 FB4 REPORT
5.5.1 Meaning and call - REPORT
Meaning of the block
The REPORT function block allows unconfirmed transmission of variables by an FMS
server. This job type is used particularly for transmission on broadcast/multicast FMS
connections.
The structure of the variables to be reported must be configured locally on the FMS server.
S7 station as communications partner
To allow the reported variables to be accepted by the communications partner, the variables
must be entered during configuration of the communications partner (FMS client).
Call interface
REPORT
ANY
BOOL
BOOL
ANY
DWORD
WORD STATUS
ERROR
DONE
VAR_1
SD_1
lD
BOOL REQ BOOL



Example in STL representation

STL Explanation
call FB 4, DB 28 (
REQ := M 1.0,
ID := DW#16#10001,
VAR_1 := "SLAVE2".INDEX,
SD_1 := "PROZESS".Motor1,
DONE := M 1.1,
ERROR := M 1.2,
STATUS := MW 20 );
//REPORT block call with instance DB
//Signal edge change to execute the FB
//Compared with configuration of FMS connection
//Names the C variable to be reported
//Addresses the source data area
//Confirmation of execution
//Indicates incorrect execution
//Detailed error decoding

FBs for PROFIBUS FMS
5.5 FB4 REPORT
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
178 Programming Manual, 03/2008, C79000-G8976-C229-01

NOTICE
The parameter SD_1 is used to address the data area from which the variable values are
read and reported. According to the FMS conventions, you also need to specify the variable
index on the FC interface. The consistency of this information is not, however, checked
when the call is executed.

5.5.2 How REPORT works
Operating principle
The following flow chart shows the normal sequence of a data transfer transferred by
REPORT in the user program.
The job is activated by a (positive-going) edge change at the parameter REQ.
Every REPORT job in the user program is acknowledged by the PROFIBUS CP with values
in the output parameters DONE, ERROR and STATUS.
{
PROFlBUS-CP
1, 0, 0000
1)
REPORT-PDU
PROFlBUS-CP
FMS-Server FMS-Client
Time
Supply lNPUT parameters
CALL FB4 (REQ=0)
User program
(CPU cycle)
Time Time
1) Parameter transfer DONE, ERROR, STATUS
Supply lNPUT parameters
CALL FB4 (REQ=1)
Conversion of data from
the FMS format
and entry in the user data
area
Report
completed


FBs for PROFIBUS FMS
5.6 FB5 STATUS
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 179
5.6 FB5 STATUS
5.6.1 Meaning and call - STATUS
Meaning of the block
The STATUS function block allows status information to be requested from the
communications partner on the specified FMS connection.
The following information is available:
The logical status of the VFD;
for example information whether communication is possible.
The physical status of the VFD
information about the status of the device
Device-specific information
normally provides vendorspecific information
The following table provides information about the codes that a device can supply as a result
of the status request:

Device Message version Log Phys Local detail
1 00H:
Ready for
communication
CP in RUN, CPU
in RUN
10H:
Ready for
communication,
CPU in RUN
No entry S7 with
PROFIBUS CP
2 02H:
Limited services,
CP in RUN, CPU
in STOP
13H:
Maintenance
required, CPU in
STOP
No entry
Third-party device The following are
possible:
00H:
Ready for
communication
02H:
Number of
services limited
10H:
Operational

11H
Partly operational
12H
Not operational
13H
Maintenance
required
- vendor specific -
FBs for PROFIBUS FMS
5.6 FB5 STATUS
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
180 Programming Manual, 03/2008, C79000-G8976-C229-01
Call interface
FB 5
BYTE
WORD
BYTE PHYS
STATUS
ERROR
NDR
lD
REQ
LOG
BOOL
BYTE
ANY LOCAL
BYTE
ANY
BOOL
BOOL DWORD


Example in STL representation

STL Explanation
call FB 5, DB 21 (
REQ := M 1.0,
ID := DW#16#10001,
NDR := M 1.1,
ERROR := M 1.2,
STATUS := MW 20,
PHYS := MB 22,
LOG := MB 23,
LOCAL := P#DB18.DBX0.0 WORD8 );
//STATUS block call with instance DB
//Signal edge change to execute the FB
//Compared with configuration of FMS connection
//Indicates when new data is accepted
//Indicates incorrect execution
//Detailed error decoding
//Data area for physical status
//Data area for logical status
//Data area for "local detail"

FBs for PROFIBUS FMS
5.6 FB5 STATUS
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 181
5.6.2 How STATUS works
Operating principle
The following flow chart shows the normal sequence of a STATUS job.
The job is activated by a (positive-going) edge change at the parameter REQ.
Every STATUS job in the user program is confirmed by the PROFIBUS CP with values in the
output parameters NDR, ERROR and STATUS.
{
{
0, 0, XX
1)
PROFlBUS-CP
0, 0, XX
1)
1, 0, 0000
1)
STATUS
Confirmed-PDU
STATUS-PDU
PROFlBUS-CP
FMS-Client FMS-Server
Time
Supply lNPUT parameters
CALL FB5 (REQ=0)
User program
(CPU cycle)
Time Time
1) Parameter transfer NDR, ERROR, STATUS
Supply lNPUT parameters
CALL FB5 (REQ=1)
Prepare status information
Status query
active
Status code
exists


FBs for PROFIBUS FMS
5.7 FB6 WRITE
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
182 Programming Manual, 03/2008, C79000-G8976-C229-01
5.7 FB6 WRITE
5.7.1 Meaning and call - WRITE
Meaning
The WRITE FB transfers data from a specified local data area to a data area on the
communication partner. The local data area can be a data block, an area in the process
input or output image or a bit memory area. (See also parameter SD_1, FMS block
parameter (Page 168))
The data area of the communication partner is specified using a variable name or a variable
index.
Requirement: Configuration of communications variables
The structure of the variables on the communications partner (FMS server) is fixed. When
the FMS connection is established, the structure description is read out from the
communications partner. This is then available on the PROFIBUS CP to convert the data to
the FMS representation.
The structure description is only read when the connection is established if the
communications variable was selected during configuration of the FMS connection.
Access rights
Remember that access rights can be set for the data transfer. Data transmission is then only
possible if the FMS client has been assigned suitable rights.
Call interface
WRlTE
ANY
BOOL
BOOL
ANY
DWORD
WORD STATUS
ERROR
DONE
SD_1
VAR_1
lD
BOOL REQ BOOL


Example in STL representation

STL Explanation
call FB 6, DB 28 (
REQ := M 1.0,
//WRITE block call with instance DB
//Signal edge change to execute the FB
FBs for PROFIBUS FMS
5.7 FB6 WRITE
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 183
STL Explanation
ID := DW#16#10001,
VAR_1 := "SLAVE2".INDEX,
SD_1 := "PROZESS".Motor1,
DONE := M 1.1,
ERROR := M 1.2,
STATUS := MW 20 );
//Compared with configuration of FMS connection
//Names the C variable to be written
//Addresses the source data area
//Confirmation of execution
//Indicates incorrect execution
//Detailed error decoding

5.7.2 How WRITE works
Operating principle
The following flow chart shows the normal sequence of a data transfer triggered with WRITE
in the user program.
The job is activated by a (positive-going) edge change at the parameter REQ.
Every WRITE job in the user program is confirmed by the PROFIBUS CP with values in the
output parameters DONE, ERROR and STATUS.
{
{
0, 0, XX
1)
PROFlBUS-CP
0, 0, XX
1)
1, 0, 0000
1)
WRlTE
Confirmed-PDU
WRlTE Request-PDU
mit Daten
PROFlBUS-CP
FMS-Client FMS-Server
Time
Supply lNPUT parameters
CALL FB6 (REQ=0)
User program
(CPU cycle)
Time Time
1) Parameter transfer DONE, ERROR, STATUS
Supply lNPUT parameters
CALL FB6 (REQ=1)
Conversion of data from
the FMS format
and entry in the user data
area
Writing
active
Writing completed


FBs for PROFIBUS FMS
5.7 FB6 WRITE
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
184 Programming Manual, 03/2008, C79000-G8976-C229-01
Guarantee of data transfer
The diagram also shows that with the confirmation DONE=1, ERROR=0 and STATUS=0000,
data transfer to the communications partner and entry in the remote data area is functioning
correctly.
A positive confirmation of the job does not necessarily mean that the data has already been
received and processed by the partner application.
FBs for PROFIBUS FMS
5.8 Condition codes and error messages - FMS blocks
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 185
5.8 Condition codes and error messages - FMS blocks
Structure of the tables
The following tables explain the condition codes and error codes that must be handled in
your user program. The meanings of the parameters DONE/NDR, ERROR and STATUS are
explained in FMS block parameters (Page 168)
To provide a better overview, the error codes are listed as follows:
Grouped according to:
- Error class (explanation, see table below)
- Error code / meaning (see table below)
Error detected locally
Error detected by
FMS partner


Error-free job execution
If the job was executed free of errors, the parameters on the FB interface have the following
values:

DONE/NDR ERROR STATUS Meaning
1 0 0x0000 Job completed without errors
0 0 0x000B Job active
Error classes
The possible error codes are grouped into the following error classes:
Table 5-1 "Block" error class
Error class Meaning
Block Indicates errors or problems involving the following:
FB parameter assignment
Block execution in the CPU and CP
Application Indicates errors or problems on the interface between the user program and FB.
Definition Indicates errors that usually involve inconsistencies between the user program
and FMS configuration.
Components Indicates resource problems on the PROFIBUS CP.
Service Indicates errors or problems in conjunction with the requested FMS service.
Access Indicates denied access to objects due to the following:
Absence of access rights
Hardware problems
Other inconsistencies
FBs for PROFIBUS FMS
5.8 Condition codes and error messages - FMS blocks
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
186 Programming Manual, 03/2008, C79000-G8976-C229-01
Error class Meaning
OD (object
directory)
Indicates problems accessing the object dictionary of the VFD.
VFD status Unspecified error on the VFD
otherwise Other errors

5.8.1 Error detected locally
Table 5-2 "Application" error class
DONE/NDR ERROR STATUS Meaning
0 1 0x0001 Communications problem:
For example, communications bus connection not
established.
0 1 0x0002 The function cannot be executed: Either negative
acknowledgment from CP or error in the sequence,
for example communications bus error.
0 1 0x0003 The connection is not configured (invalid ID
specified). If the connection is configured, the error
message indicates that the permitted parallel job
processing limit has been exceeded. Example:
SAC=0 is configured and a REPORT job is sent.
0 1 0x0004 The receive data area is too short or the data types
do not match.
0 1 0x0005 A reset request has been received from the CP
(BRCV).
0 1 0x0006 The corresponding job execution on the CP is in the
DISABLED state or a reset request has been
received from the CP; the transfer is therefore
incomplete.
0 1 0x0007 Corresponding job execution on the CP is in the
wrong state.
For REPORT: The error is specified in greater detail
in the diagnostic buffer.
0 1 0x0008 Job execution on the CP signals an error accessing
the user memory.
0 1 0x000A Access to local user memory not possible (for
example, the DB was deleted).
0 1 0x000C When the underlying BSEND or BRCV SFBs were
called, an instance DB that does not belong to
SFB12/SFB13 was specified or no instance DB was
used, but rather a global DB.
0 1 0x0014 Not enough work or load memory available.


FBs for PROFIBUS FMS
5.8 Condition codes and error messages - FMS blocks
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 187

DONE/NDR ERROR STATUS Meaning
0 1 0x0200 Unspecified application reference error.
0 1 0x0201 The configured connection cannot be established at
present; for example LAN connection not
established.

Table 5-3 "Definition" error class
DONE/NDR ERROR STATUS Meaning
0 1 0x0300 Unspecified definition error.
0 1 0x0301 Object with requested index/name is not defined.
0 1 0x0302 Object attributes are inconsistent.
0 1 0x0303 Name exists already.

Table 5-4 "Resources" error class
DONE/NDR ERROR STATUS Meaning
0 1 0x0400 Unspecified resource error.
0 1 0x0401 No memory available.

Table 5-5 "Service" error class
DONE/NDR ERROR STATUS Meaning
0 1 0x0500 Unspecified service error.
0 1 0x0501 Conflict due to object status.
0 1 0x0502 Configured PDU size exceeded.
0 1 0x0503 Conflict due to object restrictions.
0 1 0x0504 Inconsistent parameters.
0 1 0x0505 Illegal parameters.

Table 5-6 "Access" error class
DONE/NDR ERROR STATUS Meaning
0 1 0x0600 Unspecified access error.
0 1 0x0601 Invalid object or no OD loaded;
0 1 0x0602 Hardware fault
0 1 0x0603 Object access was denied.
0 1 0x0604 Invalid address.
0 1 0x0605 Inconsistent object attributes.
0 1 0x0606 Object access not supported.
FBs for PROFIBUS FMS
5.8 Condition codes and error messages - FMS blocks
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
188 Programming Manual, 03/2008, C79000-G8976-C229-01
DONE/NDR ERROR STATUS Meaning
0 1 0x0607 Object does not exist in OD or GetOD still active.
0 1 0x0608 Type conflict or variable content outside permitted
range of values
0 1 0x0609 Access using names not supported.

Table 5-7 "Object dictionary" (OD) error class / VFD Status/Reject error class
DONE/NDR ERROR STATUS Meaning
0 1 0x0700 Unspecified OD error.
0 1 0x0701 Permitted name length exceeded.
0 1 0x0702 Overflow of the object dictionary.
0 1 0x0703 Object dictionary is write protected.
0 1 0x0704 Overflow of the extension length.
0 1 0x0705 Overflow of the object description length.
0 1 0x0706 Processing problem.



DONE/NDR ERROR STATUS Meaning
0 1 0x0100 Unspecified VFD status error.
0 1 0x0108 RCC/SAC/RAC error
0 1 0x0106 Service not supported.
0 1 0x0105 PDU length error
0 1 0x0102 Bad FMS-PDU

Table 5-8 "Other" error class
DONE/NDR ERROR STATUS Meaning
0 1 0x0800 Unspecified error.

5.8.2 Errors detected by FMS partner
Table 5-9 Application error class
DONE/NDR ERROR STATUS Meaning
0 1 0x8200 Unspecified application reference error.
0 1 0x8201 Application (e.g. user program) cannot be reached.

FBs for PROFIBUS FMS
5.8 Condition codes and error messages - FMS blocks
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 189
Table 5-10 Definition error class
DONE/NDR ERROR STATUS Meaning
0 1 0x8300 Unspecified definition error.
0 1 0x8301 Object with requested index/name is not defined.
0 1 0x8302 Object attributes are inconsistent.
0 1 0x8303 Name exists already.

Table 5-11 Resources error class
DONE/NDR ERROR STATUS Meaning
0 1 0x8400 Unspecified resource error.
0 1 0x8401 No memory available.

Table 5-12 Service error class
DONE/NDR ERROR STATUS Meaning
0 1 0x8500 Unspecified service error.
0 1 0x8501 Conflict due to object status.
0 1 0x8502 Configured PDU size exceeded.
0 1 0x8503 Conflict due to object restrictions.
0 1 0x8504 Inconsistent parameters.
0 1 0x8505 Illegal parameters.

Table 5-13 Access error class
DONE/NDR ERROR STATUS Meaning
0 1 0x8600 Unspecified access error.
0 1 0x8601 Invalid object.
0 1 0x8602 Hardware error.
0 1 0x8603 Object access was denied.
0 1 0x8604 Invalid address.
0 1 0x8605 Inconsistent object attributes.
0 1 0x8606 Object access is not supported.
0 1 0x8607 Object does not exist.
0 1 0x8608 Type conflict or variable content outside permitted
range of values
0 1 0x8609 Access using names is not supported.

FBs for PROFIBUS FMS
5.9 Quantity framework / resource requirements of FBs (PROFIBUS FMS)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
190 Programming Manual, 03/2008, C79000-G8976-C229-01
Table 5-14 OD (object dictionary) error class
DONE/NDR ERROR STATUS Meaning
0 1 0x8700 Unspecified OD error.
0 1 0x8701 Permitted name length exceeded.
0 1 0x8702 Overflow of the object dictionary.
0 1 0x8703 Object dictionary is write protected.
0 1 0x8704 Overflow of the extension length.
0 1 0x8705 Overflow of the object description length.
0 1 0x8706 Processing problem.

Table 5-15 VFD status error class / "Other" error class
DONE/NDR ERROR STATUS Meaning
0 1 0x8100 Unspecified VFD status error.



DONE/NDR ERROR STATUS Meaning
0 1 0x8000 Unspecified error detected by partner.

5.9 Quantity framework / resource requirements of FBs (PROFIBUS FMS)

Note
Please note the version information of the blocks. Blocks with other versions have different
resource requirements.


Table 5-16 Information for FBs with S7-400
NAME Version FB No. Load
memory
bytes
Work
memory
bytes
MC7
Bytes
Local
data
Bytes
Instance
DB
Block
Bytes
Instance
DB
MC7
Bytes
IDENT 1.3 2 1658 1364 1328 136 464 196
READ 1.5 3 2474 2086 2050 130 606 338
REPORT 1.5 4 2184 1818 1782 156 588 332
STATUS 1.3 5 1656 1390 1354 112 438 190
WRITE 1.5 6 2486 2094 2058 142 632 358

FBs for PROFIBUS FMS
5.9 Quantity framework / resource requirements of FBs (PROFIBUS FMS)
Functions (FC) and function blocks (FB) for SIMATIC NET S7 CPs
Programming Manual, 03/2008, C79000-G8976-C229-01 191

Table 5-17 Information for FBs with S7-300
NAME Version FB No. Block
bytes
Work
memory
bytes
MC7
Bytes
Local
data
Bytes
Instance
DB
Block
Bytes
Instance
DB
MC7
Bytes
IDENT 1.6 2 1462 1254 1218 86 306 158
READ 1.5 3 1998 1700 1664 64 218 70
REPORT 1.6 4 2024 1718 1682 76 230 72
STATUS 1.6 5 1430 1244 1208 60 182 46
WRITE 1.6 6 2016 1710 1674 76 230 72
-

You might also like