ControlLogix Controller Catalog Numbers 1756-L61, 1756-L62, 1756-L63, 1756-L63XT, 1756-L64, 1756-L65, 1756-L71, 1756-L72, 1756-L73, 1756-L73XT, 1756-L74, 1756-L75 GuardLogix Controller Catalog Numbers 1756-L61S, 1756-L62S, 1756-L63S, 1756-LSP, 1756-L71S, 1756-L72S, 1756-L73S, 1756-L7SP, 1756-L73SXT, 1756-L7SPXT Armor GuardLogix Catalog Number 1756-L72EROMS ControlLogix Redundancy Catalog Numbers 1756-RM, 1756-RMXT, 1756-RM2, 1756-RM2XT Topic Page 1756 ControlLogix Controllers 2 1756 ControlLogix-XT Controllers 8 1756 GuardLogix Controllers 13 1756 GuardLogix-XT Controllers 19 1756 Armor GuardLogix Controller 21 Controller Memory Use 24 Controller Compatibility 25 ControlLogix Redundancy 27 ControlLogix Connections 30 ControlLogix Controller Accessories 31 2 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers 1756 ControlLogix Controllers The ControlLogix controller provides a scalable controller solution that is capable of addressing a large amount of I/O points. The ControlLogix controller can be placed into any slot of a ControlLogix I/O chassis and multiple controllers can be installed in the same chassis. ControlLogix controllers can monitor and control I/O across the ControlLogix backplane, as well as over network links. To provide communication for a ControlLogix controller, install the appropriate communication interface module into the chassis. 1756-L7x ControlLogix Controllers Features and Specifications Feature 1756-L71, 1756-L72, 1756-L73, L73XT, 1756-L74, 1756-L75 Controller tasks 32 tasks 100 programs/task Event tasks: all event triggers Built-in communication ports 1 port USB (1) (1) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the USB port in hazardous locations. Communication options EtherNet/IP ControlNet DeviceNet Data Highway Plus Remote I/O SynchLink Third-party process and device networks USB port communication Programming, configuration, firmware flash and on-line edits only Controller connections supported, max 500 Network connections, per network module 100 ControlNet (1756-CN2/A) 40 ControlNet (1756-CNB/D, 1756-CNB/E) 128 ControlNet (1756-CN2/B) 256 EtherNet/IP; 128 TCP (1756-EN2x) 128 EtherNet/IP; 64 TCP (1756-ENBT) Controller redundancy Full support Integrated motion SERCOS interface Analog options (encoder input, LDT input, SSI input) EtherNet/IP (CIP Motion) Programming languages Relay ladder Structured text Function block SFC Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 3 1756 ControlLogix Controllers Table 1 - Technical Specifications - 1756-L7x ControlLogix Controllers Attribute 1756-L71 1756-L72 1756-L73 1756-L74 1756-L75 User memory 2 MB 4 MB 8 MB 16 MB 32 MB I/O memory 0.98 MB Optional nonvolatile memory storage 1 GB (1784-SD1 ships with every controller) 2 GB (1784-SD2) Digital I/O, max 128,000 Analog I/O, max 4000 Total I/O, max 128,000 Energy storage module 1756-ESMCAP capacitor energy storage module (removable, ships installed with every controller) 1756-ESMNSE capacitor energy storage module (removable, no residual WallClockTime power backup) 1756-ESMNRM capacitor energy storage module (nonremovable, secures controller by preventing USB connection an d SD card use) Current draw @ 1.2V DC 5 mA Current draw @ 5.1V DC 800 mA Power dissipation 2.5 W Thermal dissipation 8.5 BTU/hr Isolation voltage 30V (continuous), basic insulation type, USB port-to-system Type tested at 500V AC for 60 s USB port (1) (1) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the USB port in hazardous locations. USB 2.0, full speed (12 Mbps) Weight, approx 0.25 kg (0.55 lb) Slot width 1 Module location Chassis-based, any slot Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 Power supply, standard 1756-PA72, 1756-PA75, 1756-PB72, 1756-PB75 Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2 Wire category (2) (2) Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. 3 - on USB port North American temperature code T4A IEC temperature code T4 Enclosure type rating None (open-style) 4 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers
Table 2 - Environmental Specifications - 1756-L7x ControlLogix Controllers Attribute 1756-L71, 1756-L72, 1756-L73, 1756-L74, 1756-L75 Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 060 C (32140 F) Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) -4085 C (-40185 F) Temperature, surrounding air, max 60 C (140 F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) 595% noncondensing Vibration IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10500 Hz Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g (45 g with SD card installed) Emissions CISPR 11 IEC 61000-6-4 Class A ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz Table 3 - Certifications - 1756-L7x ControlLogix Controllers Certification (1) (1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. 1756-L71, 1756-L72, 1756-L73, 1756-L74, 1756-L75 c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) C-Tick Australian Radio communications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X KC Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 5 1756 ControlLogix Controllers 1756-L6x ControlLogix Controllers Features and Specifications Table 4 - Features - Standard ControlLogix 1756-L6x Controllers Feature 1756-L61, 1756-L62, 1756-L63, L63XT, 1756-L64, 1756-L65 Controller tasks 32 tasks 100 programs/task Event tasks: all event triggers Built-in communication ports 1 port RS-232 serial Communication options EtherNet/IP ControlNet DeviceNet Data Highway Plus Remote I/O SynchLink Third-party process and device networks Serial port communication ASCII DF1 full/half-duplex DF1 radio modem DH-485 Modbus via logic Controller connections supported, max 250 Network connections, per network module 100 ControlNet (1756-CN2/A) 40 ControlNet (1756-CNB/D, 1756-CNB/E) 128 ControlNet (1756-CN2/B) 256 EtherNet/IP; 128 TCP (1756-EN2x) 128 EtherNet/IP; 64 TCP (1756-ENBT) Controller redundancy Full support Integrated motion SERCOS interface Analog options (encoder input, LDT input, SSI input) EtherNet/IP (CIP Motion) Programming languages Relay ladder Structured text Function block SFC IMPORTANT Scan time for a project loaded in a 1756-L64 or 1756-L65 controller may be slower than for the same project loaded in one of the other 1756-L6x controllers. See the Logix5000 Controllers Instruction Execution Time and Memory Use Reference Manual, publication 1756-RM087, for instruction execution times. 6 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers Table 5 - Technical Specifications - 1756-L6x ControlLogix Controllers Attribute 1756-L61 1756-L62 1756-L63 1756-L64 1756-L65 User memory 2 MB 4 MB 8 MB 16 MB 32 MB I/O memory 478 KB Optional nonvolatile memory storage 128 MB (1784-CF128) Digital I/O, max 128,000 Analog I/O, max 4000 Total I/O, max 128,000 Replacement battery (1) (1) For Australian Mining certification applications, only a series A controller and a 1756-BA1 battery can be used. For more information, contact your local distributor or sales office. Series A: 1756-BA1, 1756-BATM, 1756-BATA Series B: 1756-BA2 1756-BA2 (0.50 g Lithium) Current draw @ 5.1V DC 1200 mA Current draw @ 24V DC 14 mA Power dissipation 3.5 W Thermal dissipation 11.9 BTU/hr Isolation voltage 30V (continuous), basic insulation type, RS-232 to system Type tested at 720V DC for 60 s Serial cables 1756-CP3 or 1747-CP3, right angle connector to controller, straight to serial port, 3 m (9.84 ft) Weight, approx Series A: 0.32 kg, (0.71 lb) Series B: 0.35 kg, (0.78 lb) Slot width 1 Module location Chassis-based, any slot Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 Power supply, standard 1756-PA72, 1756-PA75, 1756-PB72, 1756-PB75 Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2 Wire category (2) (2) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. 2 - on RS-232 port North American temperature code T4A Enclosure type rating None (open-style) Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 7 1756 ControlLogix Controllers Table 6 - Environmental Specifications - 1756-L6x ControlLogix Controllers Attribute 1756-L61, 1756-L62, 1756-L63, 1756-L64, 1756-L65 Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 060 C (32140 F) Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) -4085 C (-40185 F) Temperature, surrounding air, max 60 C (140 F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) 595% noncondensing Vibration IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10500 Hz Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g Emissions CISPR 11 IEC 61000-6-4 Class A ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz EFT/B immunity IEC 61000-4-4 4 kV at 5 kHz on RS-232 port Surge transient immunity IEC 61000-4-5 2 kV line-earth (CM) on RS-232 port Conducted RF immunity IEC 61000-4-6 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 8 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers 1756 ControlLogix-XT Controllers The ControlLogix-XT controllers function in the same way as the traditional ControlLogix controllers. The ControlLogix-XT products include control and communication system components that are conformally coated for extended protection in harsh, corrosive environments: When used with FLEX I/O-XT products, the ControlLogix-XT system can withstand temperature ranges from -2070 C (-4158 F). When used independently, the ControlLogix-XT system can withstand temperature ranges from -2570 C (-13158 F). Equipment designated as LXT is certified for use only within a surrounding air temperature of -2560 C (-13140 F) even when used with other XT equipment. Table 7 - Certifications - 1756-L6x ControlLogix Controllers Certification (1) (1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. 1756-L61, 1756-L62, 1756-L63, 1756-L64, 1756-L65 c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) C-Tick Australian Radio communications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n EN60079-0; General Requirements II 3 G Ex nA IIC T4 X IMPORTANT: The 1756-L64 and 1756-L65 controllers do not have this certification. KC Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 9 1756 ControlLogix Controllers 1756-L73XT ControlLogix Controller Specifications Table 8 - Technical Specifications - 1756-L73XT ControlLogix Controller Attribute 1756-L73XT User memory 8 MB I/O memory 0.98 MB Optional nonvolatile memory 1 GB (1784-SD1 ships with every controller) 2 GB (1784-SD) Digital I/O, max 128,000 Analog I/O, max 4000 Total I/O, max 128,000 Replacement battery Energy storage modules 1756-ESMCAPXT capacitor energy storage module (removable, ships installed with every controller) 1756-ESMNSEXT capacitor energy storage module (removable, no residual WallClockTime power backup) 1756-ESMNRMXT capacitor energy storage module (nonremovable, secures controller by preventing USB connection and SD card use) Current draw @ 5.1V DC 800 mA Current draw @ 1.2V DC 5 mA Power dissipation 2.5 W Thermal dissipation 8.5 BTU/hr Isolation voltage 30V (continuous), basic insulation type, USB port to backplane Type tested at 500V AC for 60 s USB port (1) (1) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. Do not use the USB port in hazardous locations. USB 2.0, full speed (12 Mbps) Weight, approx 0.25 kg (0.55lb) Slot width 1 Module location Chassis-based, any slot Chassis 1756-A4LXT, 1756-A5XT, 1756-A7LXT, 1756-A7XT Power supply, standard 1756-PAXT, 1756-PBXT Power supply, redundant None Wire category (2) (2) Use this conductor category information for planning conductor routing. Refer to the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. 3 - on USB ports North American temperature code T4A IEC temperature code T4 Enclosure type rating None (open-style) 10 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers Table 9 - Environmental Specifications - 1756-L73XT ControlLogix Controller Attribute 1756-L73XT Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) -2570 C (-13158 F) When using a 1756-A7LXT chassis, surrounding air temperature range is -2560 C (-13140 F) even when using an XT controller. Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) -4085 C (-40185 F) Temperature, surrounding air, max 70 C (158 F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) 595% noncondensing Vibration IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10500 Hz Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g (45 g with SD card installed) Emissions CISPR 11 IEC 61000-6-4 Class A ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz Table 10 - Certifications - 1756-L73XT ControlLogix Controller Certification (1) (1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. 1756-L73XT c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) C-Tick Australian Radio communications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X KC Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 11 1756 ControlLogix Controllers 1756-L63XT ControlLogix Controller Specifications Table 11 - Technical Specifications - 1756-L63XT Controller Attribute 1756-L63XT User memory 8 MB I/O memory 478 KB Optional nonvolatile memory storage 128 MB (1784-CF128) Digital I/O, max 128,000 Analog I/O, max 4000 Total I/O, max 128,000 Replacement battery 1756-BA2 Current draw @ 5.1V DC 1200 mA Current draw @ 24V DC 14 mA Power dissipation 3.5 W Thermal dissipation 11.9 BTU/hr Isolation voltage 30V (continuous), basic insulation type, RS-232 port to system Type tested at 720V DC for 60 s Serial cables 1756-CP3 or 1747-CP3, right angle connector to controller, straight to serial port, 3 m (9.84 ft) Weight, approx 0.35 kg (0.78 lb) Slot width 1 Module location Chassis-based, any slot Chassis 1756-A4LXT, 1756-A5XT, 1756-A7LXT, 1756-A7XT Power supply, standard 1756-PBXT, 1756-PAXT Power supply, redundant None Wire category (1) (1) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. 2 - on RS-232 port North American temperature code T4A IEC temperature code T4 Enclosure type rating None (open-style) 12 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers Table 12 - Environmental Specifications - 1756-L63XT Controller Attribute 1756-L63XT Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) -2570 C (-13158 F) When using a 1756-A7LXT chassis, surrounding air temperature range is -2560 C (-13140 F) even when using an XT controller Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) -4085 C (-40185 F) Temperature, surrounding air, max 70 C (158 F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) 595% noncondensing Vibration IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10500 Hz Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g Emissions CISPR 11 Group 1, Class A ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz EFT/B immunity IEC 61000-4-4 4 kV at 5 kHz on RS-232 port Surge transient immunity IEC 61000-4-5 2 kV line-earth (CM) on communication ports Conducted RF immunity IEC 61000-4-6 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz Table 13 - Certifications - 1756-L63XT Controller Certification (1) (1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. 1756-L63XT c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) C-Tick Australian Radio communications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X KC Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 13 1756 ControlLogix Controllers 1756 GuardLogix Controllers A GuardLogix controller is a ControlLogix controller that also provides safety control. The GuardLogix system is a dual controller solutionyou must use a 1756-L6xS/1756-L7xS primary controller and a 1756-LSP/1756-L7SP safety partner to achieve up to SIL CL 3/PLe/Cat. 4. A major benefit of this system is that its still a single project, safety and standard together. The safety partner controller is a part of the system, is automatically configured, and requires no user setup. During development, safety and standard have the same rules; multiple programmers, online editing, and forcing are all allowed. Once the project is tested and ready for final validation, you set the safety task to a SIL 3 integrity level, which is then enforced by the GuardLogix controller. When safety memory is locked and protected, the safety logic can't be modified and all safety functions operate with SIL 3 CL integrity. On the standard side of the GuardLogix controller, all functions operate like a regular Logix controller. Thus, online editing, forcing, and other activities are all allowed. With this level of integration, safety memory can be read by standard logic and external devices, like HMIs or other controllers, eliminating the need to condition safety memory for use elsewhere. The result is easy system-wide integration and the ability to display safety status on displays or marquees. Use Guard I/O modules for field device connectivity on Ethernet or DeviceNet networks, and for safety interlocking between GuardLogix controllers use Ethernet or ControlNet networks. Multiple GuardLogix controllers can share safety data for zone to zone interlocking, or a single GuardLogix controller can use remote distributed safety I/O between different cells/areas. In addition to the standard features of a ControlLogix controller, the GuardLogix controller has these safety-related features. Table 14 - Features - GuardLogix Controllers Feature 1756-L61S, 1756-L62S, 1756-L63S, 1756-L71S, 1756-L72S, 1756-L73S, 1756-L73SXT Safety communication options Standard and safety EtherNet/IP ControlNet DeviceNet Network connections, per network module 100 ControlNet (1756-CN2/A) 40 ControlNet (1756-CNB/D, 1756-CNB/E) 128 ControlNet (1756-CN2/B) 256 EtherNet/IP; 128 TCP (1756-EN2x) 128 EtherNet/IP; 64 TCP (1756-ENBT) Controller redundancy Not supported Programming languages Relay ladder with safety application instructions Primary Controller Safety Partner 1756-L61S, 1756-L62S, 1756-L63S 1756-LSP 1756-L71S, 1756-L72S, 1756-L73S 1756-L7SP 1756-L73SXT 1756-L7SPXT 14 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers 1756-L7xS GuardLogix Controllers Specifications Table 15 - Technical Specifications - 1756-L7xS GuardLogix Controllers Attribute 1756-L71S 1756-L72S 1756-L73S 1756-L7SP User memory 2 MB 4 MB 8 MB Safety memory 1 MB 2 MB 4 MB (2) (2) Same as corresponding primary controller. I/O memory 0.98 MB Optional nonvolatile memory storage 1 GB (1756-SD1 ships with every controller) 2 GB (1756-SD2)
Digital I/O, max 128,000
Analog I/O, max 4000 Total I/O, max 128,000 Replacement battery Energy storage modules 1756-ESMCAP capacitor energy storage module (removable, ships installed with every controller) 1756-ESMNSE capacitor energy storage module (removable, no residual WallClockTime power backup) 1756-ESMNRM capacitor energy storage module (nonremovable, secures controller by preventing USB connection an d SD card use) 1756-SPESMNSE capacitor energy storage module for the safety partner (removable, no residual WallClockTime power backup) 1756-SPESMNRM capacitor energy storage module for the safety partner (nonremovable, secures controller by preventing USB connection an d SD card use) Current draw @ 1.2V DC 5 mA Current draw @ 5.1V DC 800 mA Power dissipation 2.5 W Thermal dissipation 8.5 BTU/hr Isolation voltage 30V (continuous), basic insulation, USB port to backplane, type tested at 500V AC for 60 s Weight, approx 0.25 kg (0.55 lb) Slot width 2, (both modules needed; each is one slot) Module location Chassis-based, any slot (the safety partner must be installed in the slot to the immediate right of the primary controller) Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 Power supply, standard 1756-PA72, 1756-PB72, 1756-PA75, 1756-PB75 Wire category (1) (1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Wiring and Grounding Guidelines, publication 1770-4.1. 3 - on USB ports North American temperature code T4A IEC temperature code T4 Enclosure type rating None (open-style) Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 15 1756 ControlLogix Controllers Table 16 - Environmental Specifications - 1756-L7xS GuardLogix Controllers Attribute 1756-L71S, 1756-L72S, 1756-L73S, 1756-L7SP Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 060 C (32140 F) Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) -4085 C (-40185 F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) 595% noncondensing Temperature, surrounding air, max 60 C (140 F) Vibration IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10500 Hz Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g (45 g with SD card installed) Emissions CISPR 11 IEC 61000-6-4 Class A ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz Table 17 - Certifications - 1756-L7xS GuardLogix Controllers Certification (1) (1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. 1756-L71S, 1756-L72S, 1756-L73S, 1756-L7SP c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/42/EC MD, compliant with: EN 60204-1; Electrical equipment of machines EN ISO 13849-1; Safety-related parts of control systems EN 62061; Functional safety of safety-related control systems C-Tick Australian Radio communications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X KC Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 TV certified for functional safety (2) (2) When used with specified firmware revisions. Capable of SIL CL 3 according to IEC 61508, capable of Category 4 according to EN954-1, and capable of PL(e) according to ISO 13849-1 when used as described in the GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093. 16 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers 1756-L6xS GuardLogix Controllers Specifications Table 18 - Technical Specifications - 1756-L6xS GuardLogix Controllers Attribute 1756-L61S 1756-L62S 1756-L63S 1756-LSP User memory 2 MB 4 MB 8 MB Safety memory 1 MB 1 MB 3.75 MB Same as corresponding primary controller I/O memory 478 KB Optional nonvolatile memory storage 128 MB (1784-CF128) (2) 1 GB (1784-SD1, ships with every controller) 2 GB (1784-SD2) (2) RSLogix 5000 programming software, version 18 or later.
Digital I/O, max 128,000
Analog I/O, max 4000
Total I/O, max 128,000 Replacement battery 1756-BA2 (0.50 g lithium) Energy storage modules Current draw @ 1.2V DC Current draw @ 5.1V DC 1200 mA Current draw @ 24V DC 14 mA Power dissipation 3.5 W Thermal dissipation 11.9 BTU/hr Isolation voltage 30V (continuous), Basic Insulation Type, RS-232 to system Type tested at 720V DC for 60 s Serial cables 1756-CP3 or 1747-CP3, right angle connector to controller, straight to serial port, 3 m (9.84 ft) Weight, approx 0.32 kg (0.70 lb) Slot width 2, (both modules needed; each is one slot) Module location Chassis-based, any slot (the safety partner must be installed in the slot to the immediate right of the primary controller) Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 Power supply standard 1756-PA72, 1756-PA75, 1756-PB72, 1756-PB75 Wire category (1) (1) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. 2 - on RS-232 port North American temperature code T4A Enclosure type rating None (open-style) Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 17 1756 ControlLogix Controllers Table 19 - Environmental Specifications - 1756-L6xS GuardLogix Controllers Attribute 1756-L61S, 1756-L62S, 1756-L63S, 1756-LSP Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 060 C (32140 F) on 1756-L61S, 1756-L62S, 1756-L63S, 1756-LSP Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) -4085 C (-40185 F) Temperature, surrounding air, max 60 C (140 F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) 595% noncondensing Vibration IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10500 Hz Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g Emissions CISPR 11 IEC 61000-6-4 Class A ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz EFT/B immunity IEC 61000-4-4 4 kV at 5 kHz on RS-232 port Surge transient immunity IEC 61000-4-5 2 kV line-earth (CM) on RS-232 port Conducted RF immunity IEC 61000-4-6 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz 18 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers Table 20 - Certifications - 1756-L6xS GuardLogix Controllers Certification (1) (1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. 1756-L61S, 1756-L62S, 1756-L63S, 1756-LSP c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/42/EC MD, compliant with: EN 60204-1; Electrical equipment of machines EN ISO 13849-1; Safety-related parts of control systems EN 62061; Functional safety of safety-related control systems C-Tick Australian Radio communications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions FM FM Approved Equipment for use in Class I, Division 2 Group A, B, C, D Hazardous Locations KC Korean Registration of Broadcasting and Communication Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 TV certified for functional safety (2) (2) When used with specified firmware revision. Capable of Cat. 4/PL e according to EN ISO 13849-1 and SIL 3 according to EN 62061/IEC 61508 when used as described in the GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093. UL certified for functional safety (2) Capable of SIL CL 3, see UL File E256621. Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 19 1756 ControlLogix Controllers 1756 GuardLogix-XT Controllers The GuardLogix-XT controllers function the same way as the traditional GuardLogix controllers. The GuardLogix-XT controllers are conformally coated for extended protection in harsh, corrosive environments. The GuardLogix-XT system can withstand temperature ranges from -2570 C (-13158 F). You must use a 1756-L73SXT primary controller with a 1756-L7SPXT safety partner. Equipment designated as LXT is certified for use only within a surrounding air temperature of -2560 C (-13140 F) even when used with other XT equipment. Attribute 1756-L73SXT 1756-L7SPXT User memory 8 MB Safety memory 4 MB Same as corresponding primary controller I/O memory 0.98 MB Digital I/O, max 128,000 Analog I/O, max 4,000 Total I/O, max 128,000 Energy storage modules 1756-ESMCAPXT capacitor energy storage module extreme temperature (removable, ships installed with every controller) 1756-ESMNSEXT capacitor energy storage module extreme temperature (removable, no residual WallClockTime power backup) 1756-ESMNRMXT capacitor energy storage module extreme temperature (nonremovable, secures controller by preventing USB connection an d SD card use) 1756-SPESMNSEXT capacitor energy storage module for the safety partner extreme temperature (removable, no residual WallClockTime power backup) 1756-SPESMNRMXT capacitor energy storage module for the safety partner extreme temperature (nonremovable, secures controller by preventing USB connection an d SD card use) Current draw @ 1.2V DC 5 mA Current draw @ 5.1V DC 800 mA Power dissipation 2.5 W Thermal dissipation 8.5 BTU/hr Isolation voltage 30V (continuous), Basic Insulation, USB port to backplane Type tested at 500V AC for 60 s Weight, approx 0.25 kg (0.55lb) Slot width 2 (need 2 modules; each uses a slot) Module location Chassis-based, any slot (the safety partner must be in a slot to the right of the primary) Chassis 1756-A4LXT, 1756-A5XT, 1756-A7LXT, 1756-A7XT Power supply 1756-PAXT, 1756-PBXT Wire category (1) (1) Use this conductor category information for planning conductor routing as described in the system level installation manual. See the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. 3 - on USB ports North American temperature code T4A IEC temperature code T4 Enclosure type rating None (open-style) 20 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers Table 21 - Environmental Specifications - 1756 GuardLogix-XT Controllers Attribute 1756-L73SXT, 1756-L7SPXT Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) -2570 C (-13158 F) When using a 1756-A7LXT chassis, surrounding air temperature range is -2560 C (-13140 F) even when using an XT controller Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) -4085 C (-40185 F) Temperature, surrounding air, max 70 C (158 F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) 595% noncondensing Vibration IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10500 Hz Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g (45 g with SD card installed) Emissions CISPR 11 IEC 61000-6-4 Class A ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz Table 22 - Certifications - 1756 GuardLogix-XT Controllers Certification (1) (1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. 1756-L73SXT, 1756-L7SPXT c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/42/EC MD, compliant with: EN 60204-1; Electrical equipment of machines EN ISO 13849-1; Safety-related parts of control systems EN 62061; Functional safety of safety-related control systems C-Tick Australian Radio communications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X KC Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 TV certified for functional safety (2) (2) When used with specified firmware revision. Capable of SIL CL 3 according to IEC 61508, capable of Category 4 according to EN954-1, and capable of PL(e) according to ISO 13849-1 when used as described in the GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093. Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 21 1756 ControlLogix Controllers 1756 Armor GuardLogix Controller The Armor GuardLogix controller extends the ControlLogix platform to the On-Machine space, putting industrial control closer to the application and sometimes onto the machine itself. This safety controller provides 4 MB of memory and two independent Ethernet ports to connect to an EtherNet/IP network. This safety controller supports the full temperature range as ControlLogix controllers, while offering global certifications and ratings for IP67 dust and washdown protection. It is certified for use in safety applications up to and including Safety Integrity Level (SIL) 3 and Performance Level (e) in which the de-energized state is the safe state. With so many hardware functions in a single device, the Armor GuardLogix controller minimizes cabinet hardware, simplifies wiring layouts, does not require tools or specialty personnel for component replacement, improves Mean Time to Repair (MTTR), simplifies troubleshooting, and makes system status readily available without the need to open a cabinet or visit a control room. The Armor GuardLogix controller provides memory capacity for the most demanding applications and provides resiliency from loss of one network connection and allowing replacement of devices without stopping production. Similar to the 1756-L72S GuardLogix controller, this controller offers the standard features of a ControlLogix controller and safety features. Table 23 - Features - Armor GuardLogix Controller Feature 1756-L72EROMS Safety communication options Standard and safety on EtherNet/IP networks Network connections, 256 EtherNet/IP; 128 TCP Controller redundancy Not supported Programming languages Relay ladder with safety application instructions 22 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers 1756-L72EROMS GuardLogix Controller Specifications Table 24 - Technical Specifications - 1756-L72EROMS Armor GuardLogix Controller Attribute 1756-L72EROMS User memory 4 MB Safety memory 2 MB I/O memory 0.98 MB Optional nonvolatile memory storage 1 GB (1756-SD1 ships with every controller) 2 GB (1756-SD2) Digital I/O, max 128,000 Analog I/O, max 4000 Total I/O, max 128,000 Input voltage range 1832V DC Input voltage, nom 24V DC Input system power, pins 2 and 3 1832V DC @ 8 A Input pass through power, pins 1 and 4 Output external power, pins 2 and 3 1832V DC @ 6 A Output pass through power, pins 1 and 4 1832V DC @ 8 A Fusing Non-replaceable fuse is soldered in place (3) (3) This fuse is intended to guard against fire hazard due to short circuit conditions. Isolation voltage 30V (continuous), Basic Insulation Type, Power to enclosure, Ethernet channels to Power, and non-redundant EtherNet channels to non-redundant EtherNet channels. No isolation between redundant Ethernet channels Type tested at 707V DC for 60 s Weight, approx 6.5 kg (14.3 lb) Dimensions 240.0 x 292.0 x 164.52 mm (9.4 x 11.5 x 6.5 in.) Ethernet port 1 Ethernet RJ45 Category 5 Ethernet cable 802.3 compliant shielded or unshielded twisted pair USB port (1) (1) The USB port is intended for temporary local programming purposes only and not intended for permanent connection. USB 1.1, full speed (12 Mbps) Wire category (2) (2) Use this Conductor Category information for planning conductor routing. Refer to Industrial Wiring and Grounding Guidelines, publication 1770-4.1. 2 - on power ports 2 - on Ethernet ports Enclosure type rating Meets IP67 and Nema Type 1 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 23 1756 ControlLogix Controllers Table 25 - Environmental Specifications - 1756-L72EROMS Armor GuardLogix Controller Attribute 1756-L72EROMS Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 060 C (32140 F) Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) -4085 C (-40185 F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) 595% noncondensing Temperature, ambient, max 60 C (140 F) Vibration IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10500 Hz Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Emissions CISPR 11 IEC 61000-6-4 Class A ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz EFT/B immunity IEC 61000-4-4 3 kV at 5 kHz on power ports 3 kV at 5 kHz on Ethernet ports Surge transient immunity IEC 61000-4-5 1 kV line-line (DM) and 2 kV line-earth (CM) on signal ports 2 kV line-earth (CM) on Ethernet ports Conducted RF immunity IEC 61000-4-6 10V rms with 1 kHz sine-wave 80% AM from 150 kHz80 MHz Voltage variation IEC 61000-4-29 10 ms interruption on DC supply ports 24 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers Controller Memory Use The following equations provide a rough memory estimate. For redundant controller systems, double the memory estimate you calculate. For example, if you estimate you need 2 MB of memory, select a controller with 4 MB of memory. Reserve 2030% of the controller memory to accommodate growth. Table 26 - Certifications - 1756-L72EROMS Armor GuardLogix Controller Certification (1) (1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. 1756-L72EROMS c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) European Union 2006/42/EC MD, compliant with: EN 60204-1; Electrical equipment of machines EN ISO 13849-1; Safety-related parts of control systems EN 62061; Functional safety of safety-related control systems RCM Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions KC Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 TV certified for functional safety (2) (2) When used with specified firmware revisions. Capable of Cat. 4/PL e according to EN ISO 13849-1 and SIL 3 according to EN 62061/IEC 61508 when used as described in the GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM099. Controller tasks _____ x 4000 = _____ bytes (minimum 1 task) Digital I/O points _____ x 400 = _____ bytes Analog I/O points _____ x 2600 = _____ bytes DeviceNet modules (1) (1) The first DeviceNet module is 7400 bytes. Additional DeviceNet modules are 5800 bytes each. _____ x 7400 = _____ bytes Other communication modules (2) (2) Count all the communication modules in the system, not just those in the local chassis. This includes device connection modules, adapter modules, and ports on PanelView terminals. _____ x 2000 = _____ bytes Motion axis _____ x 8000 = _____ bytes FactoryTalk alarm instruction _____ x 1000 = _____ bytes (per alarm) FactoryTalk subscriber _____ x 10,000 = _____ bytes Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 25 1756 ControlLogix Controllers Controller Compatibility The following tables provide compatibility with I/O modules, display devices, and other controllers and communication devices. Control Distributed I/O Modules The controller can control these distributed I/O modules via the I/O Configuration tree in the programming software. Control Safety I/O Modules The GuardLogix controller can control these safety I/O modules in a safety system. Table 27 - Distributed I/O Modules I/O Modules EtherNet/IP ControlNet DeviceNet Remote I/O Chassis-based I/O 1715 Redundant I/O Yes No No Yes 1746 SLC I/O No No No Yes 1756 ControlLogix I/O Yes Yes No No 1769 Compact I/O No No Yes Yes (1)
(1) With a third-party module. 1771 Universal I/O No Yes No Yes In-cabinet I/O 1734 POINT I/O Yes Yes Yes No 1734D POINTBlock I/O No No Yes No 1790, 1790D, 1790P CompactBlock LDX I/O No No Yes No 1791D, 1791P, 1791R CompactBlock I/O No No Yes No 1794 FLEX I/O Yes Yes Yes Yes 1797 FLEX Ex I/O No Yes No No On-Machine I/O 1732 ArmorBlock I/O Yes No Yes No 1738 ArmorPOINT I/O Yes Yes Yes No 1792D ArmorBlock MaXum I/O No No Yes No 1799 Embedded I/O No No Yes No I/O Modules EtherNet/IP ControlNet DeviceNet In-cabinet I/O 1791DS CompactBlock Guard I/O No No Yes 1791ES CompactBlock Guard I/O Yes No No 1734 POINT Guard I/O Yes No No On-Machine I/O 1732DS ArmorBlock Guard I/O No No Yes 26 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers Communicate with Display Devices The controller can communicate with these display devices. Communicate with Other Controllers The controller can communicate with these programmable controllers. Display Devices EtherNet/IP ControlNet DeviceNet DH+ Remote I/O RS-232 (DF1) Industrial Computers Rockwell Automation industrial computers (all) (1) (1) Includes Rockwell Automation integrated display rotating media (HDD) and solid state (SSD) computers, Rockwell Automation non-display computers, and Rockwell Automation integrated display computers with keypad. Yes Yes Yes Yes Yes Yes Graphic Terminals PanelView Plus and PanelView e terminals Yes Yes Yes Yes Yes Yes PanelView Standard terminals Yes Yes Yes Yes Yes Yes PanelView e terminals No Yes No Yes Yes No Message Displays InView message displays Yes Yes Yes Yes Yes Yes Controller EtherNet/IP ControlNet DeviceNet DH+ RS-232 (DF1) DH-485 (5) (5) The 1756-DH485 module supports full DH-485 functionality. 1756 ControlLogix 1756 GuardLogix Yes Yes Yes Yes Yes Yes 1768, 1769 CompactLogix 1768 Compact GuardLogix Yes Yes Yes No Yes Yes 1789 SoftLogix 5800 Yes Yes Yes No Yes No 1794 FlexLogix Yes Yes Yes No Yes Yes PowerFlex with DriveLogix Yes Yes Yes No Yes Yes 1785 PLC-5 (1)
(2)(3)
(1) The Ethernet PLC-5 controller must be series C, firmware revision N.1 or later; series D, firmware revision E.1 or later; or series E, firmware revision D.1 or later. (2) The 1785-ENET Ethernet communication interface module must be series A, firmware revision D or later. (3) The PLC-5, SLC, and MicroLogix processors appear as I/O points to the Logix controller. Use the appropriate DeviceNet interface for the controller. Yes Yes Yes Yes Yes No 1747 SLC (4)(4)
(4) Use a 1747-L55x controller with OS501 or later. Yes Yes Yes ) Yes Yes Yes 1761 MicroLogix (4) Yes No Yes No Yes Yes 1762 MicroLogix (4) Yes No Yes No Yes Yes 1763 MicroLogix (4) Yes No Yes No Yes Yes 1764 MicroLogix (4) Yes No Yes No Yes Yes 1772 PLC-2 No No No Yes Yes No 1775 PLC-3 No No No Yes Yes No 5250 PLC-5/250 No No No Yes Yes No Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 27 1756 ControlLogix Controllers Communicate with Other Communication Devices The controller can communicate with these communication devices. ControlLogix Redundancy The ControlLogix controller supports controller redundancy. In a redundant controller system, you need these components: Two 1756 chassis, each with the same of the following: Number of slots Compatible modules in the same slots Redundancy firmware revisions in each module Two additional ControlNet nodes outside the redundant chassis pair if the application uses ControlNet networks One 1756-RM, 1756-RM2, 1756-RMXT, or 1756-RM2XT redundancy module per chassis that is connected by a 1756-RMCx cable (the 1756-RM2 redundancy modules cannot be paired with the 1756-RM redundancy modules) Up to two 1756-L6x or 1756-L7x controllers, or a combination of the two, in each chassis Up to seven enhanced or standard (not mixed) communication modules, that is, 1756-CN2/B, 1756-CN2R/B, 1756-CN2RXT modules 1756-EN2T, 1756-EN2TR, or 1756-EN2TXT modules Communication Device EtherNet/IP ControlNet DeviceNet DH+ Linking device (ControlLogix controllers only) 1788-EN2DN 1788-CN2DN 1788-CN2FF 1788-EN2DN 1788-CN2DN
Drives SCANport module (1) (1) Use a CIP generic MSG instruction to communicate with the 1203-FM1 SCANport module on a DIN rail that is remote to the controller. The remote DIN rail also requires a 1794-ACN15 or 1794-ACNR15 ControlNet adapter module. 1203-FM1 1203-FB1
Communication module (2) (2) Use the generic module configuration to configure the 1203-CN1 module and a CIP generic MSG instruction to communicate with the module. 1203-CN 1770-KFC15 1770-KFCD15 1747-KFC15 1770-KFD 1770-KFG 1770-KF2 Communication card 1784-PKTCS 1784-KTCS 1784-KTCX15 1784-PKTX 1784-PKTXD
USB communication device 1784-U2CN 1784-U2DN 1784-U2DHP 28 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers Table 28 - Technical Specifications - 1756 Redundancy Modules Attribute 1756-RM 1756-RM2 1756-RMXT 1756-RM2XT Current draw @ 1.2V DC 4 mA 4 mA Current draw @ 5.1V DC 1.2 A 1.16A 1.2 A 1.16A Current draw @ 24V DC 120 mA 3.4 mA 120 mA 3.4 mA Power dissipation 9.0 W 6 W, max 9.0 W 6 W, max Thermal dissipation 31 BTU/hr 21 BTU/hr 31 BTU/hr 21 BTU/hr Connector cables 1756-RMC1, 1 m (3.28 ft) 1756-RMC3, 3 m (9.84 ft) 1756-RMC10, 10 m (32.81 ft) Slot width 1 slot Module location Chassis-based, any slot Chassis 1756-A4, 1756-A7, 1756-A10, 1756-A13, 1756-A17 1756-A7XT, 1756-A4LXT, 1756-A5LXT, 1756-A7LXT Power supply, standard 1756-PA72, 1756-PA75, 1756-PB72, 1756-PB75 1756-PAXT, 1756-PBXT Power supply, redundant 1756-PA75R, 1756-PB75R, 1756-PSCA2 None North American temperature code T4 IEC temperature code T4 Enclosure type None (open-style) Weight, approx 0.29 kg (0.64 lb) Mounting ControlLogix-XT chassis, single-slot module Table 29 - Environmental Specifications - 1756 Redundancy Module Attribute 1756-RM 1756-RM2 1756-RMXT 1756-RM2XT Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 060 C (32140 F) -2570 C (-13158 F) When using a 1756-A7LXT chassis, surrounding air temperature range is -2560 C (-13140 F) even when using an XT redundancy module. -2570 C (-13158 F) Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) -4085 C (-40185 F) Temperature, surrounding air, max 60 C (140 F) 70 C (158 F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) 595% noncondensing Vibration IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10500 Hz Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 29 1756 ControlLogix Controllers Emissions CISPR 11 IEC 61000-6-4 Group 1, Class A Class A Group 1, Class A Class A ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz Table 30 - Certifications - 1756 Redundancy Module Certification (1) 1756-RM 1756-RMXT 1756-RM2 1756-RM2XT CSA CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CE European Union 2004/108/IEC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) C-Tick Australian Radio communications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions c-UL-us UL Listed Industrial Control Equipment, certified for U.S. and Canada. See UL file E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X Gc FM FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations FM Approved Equipment for use in Class I Division 2 Group A,B,C,D Hazardous Locations
KC Korean Registration of Broadcasting and Communications Equipment, compliant with:
Article 58-2 of Radio Waves Act, Clause 3 (1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. Table 29 - Environmental Specifications - 1756 Redundancy Module (continued) Attribute 1756-RM 1756-RM2 1756-RMXT 1756-RM2XT 30 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers ControlLogix Connections A ControlLogix system uses connections to establish communication links between devices. The types of connections include the following: Controller-to-local I/O modules or local communication modules Controller-to-remote I/O or remote communication modules Controller-to-remote I/O (rack-optimized) modules Produced and consumed tags Messages Access via the controller programming software Access via RSLinx software for HMI or other applications You indirectly determine the number of connections the controller uses by configuring the controller to communicate with other devices in the system. The limit of connections may ultimately reside in the communication module you use for the connection. If a message path routes through a communication module, the connection related to the message also counts towards the connection limit of that communication module. The 1756-L6x and 1756-L6xS controllers support 250 connections; the 1756-L7x and 1756-L7xS controllers support 500. To calculate the total connections for a controller, consider the connections to local I/O modules and the connections to remote modules. Use this table to figure local connections. Table 31 - Figure Local Connections Connection Type Device Quantity Connections per Device Total Connections Local I/O module (always a direct connection) 1 1756-M16SE, 1756-M08SE, 1756-M03SE SERCOS motion module 1756-M02AE, 1756-M02AS, 1756-HYD02 analog motion module 3 1756-CN2, 1756-CN2R communication module 1756-CNB, 1756-CNBR communication module 1756-CN2RXT communication module 0 1756-EN2F, 1756-EN2T communication module 1756-ENBT, 1756-EWEB communication module 1756-EN2TXT communication module 0 1756-DNB communication module 2 1756-DHRIO communication module 1756-RIO communication module 1756-DHRIOXT communication module 1 1756-DH485 communication module 1 Total Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 31 1756 ControlLogix Controllers Regardless of how you configure local I/O modules (rack-optimized or direct connect), the controller establishes a direct connection for each local I/O module. Remote connections depend on the communication module. The number of connections the module supports determines how many connections the controller can access through that module. Use this table to figure remote connections for the controller. ControlLogix Controller Accessories You can use the following accessories with ControlLogix controllers. Memory Cards Memory cards offer nonvolatile memory to permanently store a user program and tag data on a controller. The 1756-L7x ControlLogix controller comes with the 1784-SD1 Secure Digital (SD) card already installed in every controller. The 1756-L6x controllers support optional CompactFlash cards purchased separately. The memory cards are installed in a socket on the controller. Through the programming software, you can manually trigger the controller to save to, or load from, nonvolatile memory or configure the controller to load from nonvolatile memory on powerup. Table 32 - Figure Remote Connections Connection Type Device Quantity Connections per Device Total Connections Remote ControlNet communication module Configured as a direct connection Configured as a rack-optimized connection 0 1 Remote I/O module over a ControlNet network (direct connection) 1 Remote Ethernet communication module Configured as a direct connection Configured as a rack-optimized connection 0 1 Remote I/O module over an EtherNet/IP network (direct connection) 1 Remote device over a DeviceNet network (accounted for in rack-optimized connection for local 1756-DNB module) 0 Other remote communication adapter 1 Safety input module 1 Safety output module 2 Produced tag Each consumer 1 1 Consumed tag 1 Connected message 1 Block-transfer message 1 Total Table 33 - Technical Specifications - 1784 Memory Cards Attribute 1784-CF128 1784-SD1 1784-SD2 Memory 128 MB 1 GB 2 GB Supported controllers 1756-L6x, 1756-L6xS (1) 1756-L7x, 1756-L7xS Weight, approx 14.20 g (0.50 oz) 1.76 g (0.06 oz) 32 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers (1) For safety controllers using RSLogix 5000 programming software version 18 or later. Table 34 - Environmental Specifications - 1784 Memory Cards Attribute 1784-CF128 1784-SD1, 1784-SD2 Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) -2570 C (-13158 F) Temperature, storage IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) -4085 C (-40185 F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) 595% noncondensing Vibration IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10500 Hz Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g Emissions CISPR 11 Group 1, Class A ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz Table 35 - Certifications - 1784 Memory Cards Certification (1) (1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. 1784-CF128, 1784-SD1, 1784-SD2 CE European Union 2004/108/EC EMC Directive, compliant with: EN 61000-6-4; Industrial Emissions EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) C-Tick Australian Radio communications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions KC Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 33 1756 ControlLogix Controllers 1756 Energy Storage Modules Instead of a battery, the 1756-L7x and 1756-L7xS controllers are shipped with a 1756-ESMCAP energy storage module (ESM) already installed. Table 36 - Technical Specifications - 1756 Energy Storage Modules Attribute 1756-ESMCAP 1756-ESMNSE 1756-ESMNRM Description Capacitor energy storage module (removable, ships installed with every controller). Capacitor energy storage module (removable, no residual WallClockTime power backup). Use this ESM if your application requires that the installed ESM deplete its residual energy to 40 J or less before transporting it into or out of your application. Additionally, you can use this ESM with a 1756-L73 (8 MB) or smaller memory-sized controller only. Wait at least 20 minutes for the residual stored energy to decrease to 40 J or less before you remove the ESM. Capacitor energy storage module (nonremovable, secures controller by preventing USB connection an d SD card use). If the SD card is installed prior to insertion of the 1756-ESMNRM module, the SD card remains functional, but not removable. This ESM provides your application an enhanced degree of security. Current draw @ 5.1V DC 330 mA 300 mA 330 mA North American temperature code T4A IEC temperature code T4 Enclosure type rating None (open-style) Table 37 - Environmental Specifications - 1756 Energy Storage Modules Attribute 1756-ESMCAP, 1756-ESMNSE, 1756-ESMNRM Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 060 C (32140 F) Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) -4085 C (-40185 F) Temperature, surrounding air, max 60 C (140 F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) 595% noncondensing Vibration IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10 500 Hz Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g Emissions CISPR 11 Group 1, Class A ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges 34 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers Extreme Temperature Energy Storage Modules The 1756-L7xXT and the 1756-L7xSXT extreme temperature controllers are shipped with a 1756-ESMCAPXT installed. Radiated RF immunity IEC 61000-4-3 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz Table 38 - Certifications - 1756 Energy Storage Modules Certification (1) (1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. 1756-ESMCAP, 1756-ESMNSE, 1756-ESMNRM c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for US and Canada. See UL File E194810. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) C-Tick Australian Radio communications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X KC Korean Registration of Broadcasting and Communication Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 Table 39 - Technical Specifications - 1756 Extreme Temperature Energy Storage Modules Attribute 1756-ESMCAPXT 1756-ESMNSEXT 1756-ESMNRMXT Description Capacitor energy storage module extreme temperature (removable, ships installed with every controller). Capacitor energy storage module extreme temperature (removable, no residual WallClockTime power backup). Use this ESM if your application requires that the installed ESM deplete its residual energy to 40 J or less before transporting it into or out of your application. Additionally, you can use this ESM with a 1756-L73 (8 MB) or smaller memory-sized controller only. Wait at least 20 minutes for the residual stored energy to decrease to 40 J or less before you remove the ESM. Capacitor energy storage module extreme temperature (nonremovable, secures controller by preventing USB connection an d SD card use). If the SD card is installed prior to insertion of the 1756-ESMNRM module, the SD card remains functional, but not removable. This ESM provides your application an enhanced degree of security. Current draw @ 5.1V DC 330 mA 300 mA 330 mA North American temperature code T4A IEC temperature code T4 Enclosure type rating None (open-style) Table 37 - Environmental Specifications - 1756 Energy Storage Modules (continued) Attribute 1756-ESMCAP, 1756-ESMNSE, 1756-ESMNRM Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 35 1756 ControlLogix Controllers Table 40 - Environmental Specifications - 1756 Extreme Temperature Energy Storage Modules Attribute 1756-ESMCAPXT 1756-ESMNSEXT 1756-ESMNRMXT Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) -2570 C (-13158 F) Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) -4085 C (-40185 F) Temperature, surrounding air, max 70 C (158 F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) 595% noncondensing Vibration IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10 500 Hz Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g Emissions CISPR 11 Group 1, Class A ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz Table 41 - Certifications - 1756 Extreme Temperature Energy Storage Modules Certification (1) (1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. 1756-ESMCAPXT, 1756-ESMNSEXT, 1756-ESMNRMXT c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for US and Canada. See UL File E194810. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) C-Tick Australian Radio communications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X KC Korean Certification of Broadcasting and Communication Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 36 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers GuardLogix Safety Partner Energy Storage Modules The 1756-L7SP safety partner for a GuardLogix system has these energy storage modules available. Table 42 - Technical Specifications - 1756-L7SP Safety Partner Energy Storage Modules Attribute 1756-SPESMNSE 1756-SPESMNRM Description Capacitor energy storage module for the safety partner (removable, no residual WallClockTime power backup). Use this ESM if your application requires that the installed ESM deplete its residual energy to 40 J or less before transporting it into or out of your application. Additionally, you can use this ESM with a 1756-L73 (8 MB) or smaller memory-sized controller only. Wait at least 20 minutes for the residual stored energy to decrease to 40 J or less before you remove the ESM. Capacitor energy storage module for the safety partner (nonremovable, secures controller by preventing USB connection and SD card use). If the SD card is installed prior to insertion of the 1756-ESMNRM module, the SD card remains functional, but not removable. This ESM provides your application an enhanced degree of security. Current draw @ 5.1V DC 300 mA 330 mA North American temperature code T4A IEC temperature code T4 Enclosure type rating None (open-style) Table 43 - Environmental Specifications - 1756-L7SP Safety Partner Energy Storage Modules Attribute 1756-SPESMNSE 1756-SPESMNRM Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) 060 C (32140 F) Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) -4085 C (-40185 F) Temperature, surrounding air, max 60 C (140 F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) 595% noncondensing Vibration IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10500 Hz Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g Emissions CISPR 11 Group 1, Class A ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 37 1756 ControlLogix Controllers GuardLogix Extreme-temperature Safety Partner Energy-storage Modules The 1756-L7SPXT extreme-temperature safety partner is shipped with a 1756-SPESMNSEXT energy-storage module installed. Table 44 - Certifications - 1756-L7SP Safety Partner Energy Storage Modules Certification (1) 1756-SPESMNSE, 1756-SPESMNRM c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for US and Canada. See UL File E194810. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) C-Tick Australian Radio communications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X KC Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 (1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. Table 45 - Technical Specifications - 1756-L7SPXT Extreme-temperature Safety Partner Energy-storage Modules Attribute 1756-SPESMNSEXT 1756-SPESMNRMXT Description Capacitor energy-storage module for the extreme-temperature safety partner (removable, no residual WallClockTime power backup). Use this ESM if your application requires that the installed ESM deplete its residual energy to 40 J or less before transporting it into or out of your application. Additionally, you can use this ESM with a 1756-L73 (8 MB) or smaller memory-sized controller only. Wait at least 20 minutes for the residual stored energy to decrease to 40 J or less before you remove the ESM. Capacitor energy-storage module for the safety extreme-temperature partner (nonremovable, secures controller by preventing USB connection an d SD card use). If the SD card is installed prior to insertion of the 1756-ESMNRM module, the SD card remains functional, but not removable. This ESM provides your application an enhanced degree of security. Current draw @ 5.1V DC 300 mA 330 mA North American temperature code T4A IEC temperature code T4 Enclosure type rating None (open-style) 38 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 1756 ControlLogix Controllers Table 46 - Environmental Specifications - 1756-L7SPXT Extreme-temperature Safety Partner Energy-storage Modules Attribute 1756-SPESMNSEXT 1756-SPESMNRMXT Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) -2570 C (-13158 F) Temperature, nonoperating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock) -4085 C (-40185 F) Temperature, surrounding air, max 70 C (158 F) Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat) 595% noncondensing Vibration IEC 60068-2-6 (Test Fc, Operating) 2 g @ 10500 Hz Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 30 g Shock, nonoperating IEC 60068-2-27 (Test Ea, Unpackaged Shock) 50 g Emissions CISPR 11 Group 1, Class A ESD immunity IEC 61000-4-2 6 kV contact discharges 8 kV air discharges Radiated RF immunity IEC 61000-4-3 10V/m with 1 kHz sine-wave 80% AM from 802000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 20002700 MHz Table 47 - Certifications - 1756-L7SPXT Extreme-temperature Safety Partner Energy-storage Modules Certification (1) (1) When marked. See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. 1756-SPESMNSEXT, 1756-SPESMNRMXT c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for US and Canada. See UL File E194810. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B) C-Tick Australian Radio communications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions Ex European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection n EN 60079-0; General Requirements II 3 G Ex nA IIC T4 X KC Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3 Rockwell Automation Publication 1756-TD001H-EN-P - December 2013 39 1756 ControlLogix Controllers 1756 ControlLogix Batteries Each ControlLogix controller ships with a battery. The 1756-L6x controllers have nonvolatile memory if you install a 1784-CF128 industrial CompactFlash card. With nonvolatile memory, the controller can be used without a battery. If you do not use a battery, current tag data will remain in the state it was when the nonvolatile memory was saved. These tables summarize battery life, replacement battery compatibility, and recommendations for use of an externally-mounted battery assembly. Serial Communication Cables The 1756-L6x and 1756-L6xS controllers have a built-in serial port. Table 48 - Technical Specifications - 1756 ControlLogix Batteries Attribute 1756-BA1 1756-BA2 1756-BATM (2) (2) The 1756-BATM externally-mounted battery assembly is recommended for use with all 1756-L55x controllers, and is highly recommended for use with all series A 1756-L6x controllers, and provides longer battery life than the 1756-BA1 battery. The 1756-BATM assembly includes one 1756-BATA lithium battery assembly and a 1 m (3.28 ft) cable to connect housing to the controller. 1756-BATA Description Lithium battery (0.59 g) Lithium battery (0.59 g) Externally-mounted battery assembly Replacement lithium battery for 1756-BATM (5 g max lithium per each D cell; contains 2 D cells) ControlLogix controllers 1756-L61, 1756-L62, 1756-L63 controllers, series A 1756-L61, 1756-L62, 1756-L63 controllers, series B 1756-L64, 1756-L65 controllers 1756-L61, 1756-L62, 1756-L63 controllers, series A 1756-BATM battery module GuardLogix controllers 1756-L61S, 1756-L62S, 1756-L63S
1756-L60M03SE controller (1) The 1756-L55M22, 1756-L55M23, and 1756-L55M24 controllers have nonvolatile memory and can be used without a battery. 1756-L55Mx controllers (2) 1756-L60M03SE controller 1756-BATM battery module Table 49 - Technical Specifications - 1756 Serial Cables Attribute 1756-CP3 1747-CP3 Connector type Female 9-pin D-shell Connector angle Right angle connector to controller, straight to serial port Length 3 m (9.84 ft) Allen-Bradley, Rockwell Software, Rockwell Automation, Armor GuardLogix, ArmorBlock, ArmorBlock MaXum, ArmorPOINT, CompactBlock, CompactLogix, ControlLogix, ControlLogix-XT, Data Highway Plus, DH+, DriveLogix, FactoryTalk, FLEX Ex, FLEX, FLEX I/O-XT, FlexLogix, Gurard I/O, GuardLogix, InView, LISTEN.THINK.SOLVE., Logix5000, MicroLogix, On-Machine, PanelView, PLC-2, PLC-3, PLC-5, POINT I/O, POINT Guard I/O, PowerFlex, RSLinx, RSLogix, SCANport, SLC, SoftLogix, and SynchLink are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400 Publication 1756-TD001H-EN-P - December 2013 Supersedes Publication 1756-TD001G-EN-P - January 2013 Copyright 2013 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A. Power, Control and Information Solutions Headquarters Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacifc: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846 www.rockwellautomation.com Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this publication are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.