Inside302 PDF
Inside302 PDF
Inside302 PDF
X
5) Floor and deck welds.
X AWS D1.3
6. Inspection of steel frame joint details for compliance with
approved construction documents:
a. Details such as bracing and stiffening.
b. Member locations.
SBC 302 (2.3.2)
c. Application of joint details at each connection.
SPECIAL INSPECTIONS
SBC 302 2007 2/4
SECTION 2.4
CONCRETE CONSTRUCTION
2.4.0 Concrete construction. The special inspections and verifications for concrete
construction for compliance with approved design drawings and with SBC
requirements shall be as required by this section and Table 2.4.
Exception: Special inspections shall not be required for minor constructions such
as fence walls, driveways and nonstructural concrete elements.
2.4.1 Materials. In the absence of sufficient data or documentation providing evidence of
conformance to quality standards for materials, the building official shall require
testing of materials in accordance with the appropriate standards and criteria for the
material in Section 3.0 SBC 304.
TABLE 2.4
REQUIRED VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION
VERIFICATION AND INSPECTION
CONTINUOUS
during task
listed
PERIODIC
during task
listed
REFERENCE
STANDARD
1. Inspection of structural layout and members dimensions
for compliance with approved design drawings and
construction tolerances
X
2. Inspection of reinforcing steel, including prestressing
tendons, and placement.
X SBC 304 (3.5, 7.1-7.7)
3. Inspection of formwork X SBC 304 (6.1-6.2)
4. Inspection of concrete mix
a. Verify the use of required design mix X SBC 304 (4, 5.2-5.4)
b. Verify that the delivery is from certified batch
plant
X
5. At the time fresh concrete is sampled to fabricate
specimens for strength tests, perform slump and
determine the temperature of the concrete.
X
ASTM C 172
ASTM C 31
SBC 304 (5.6, 5.8)
6. Inspection of concrete placement for proper application
techniques.
X
SBC 304 (5.9, 5.10)
7. Inspection of curing techniques and hot weather
requirements.
X SBC 304 (5.11-5.13)
8. Inspection of prestressed concrete:
a. Application of prestressing forces. X SBC 304 (18.20)
b. Grouting of bonded prestressing tendons in the
seismic-force-resisting system.
X
SBC 304 (18.18.4)
9. Verification of in-situ concrete strength, prior to
stressing of tendons in post-tensioned concrete and
prior to removal of shores and forms from beams and
structural slabs.
X SBC 304 (6.2)
SECTION 2.5
PRECAST CONCRETE CONSTRUCTION
2.5.0 The special inspections and verifications for the precast concrete elements for
compliance with the approved design drawings, shop drawings, the approved
manufacturer procedure and SBC requirements shall be as required by this section
and Table 2.5.
Exception: Special inspection shall not be required for non-structural precast
elements such as curb stones, and pavers.
SPECIAL INSPECTIONS
SBC 302 2007 2/5
TABLE 2.5
REQUIRED VERIFICATION AND INSPECTION OF PRECAST CONCRETE
CONSTRUCTION
VERIFICATION AND INSPECTION
CONTINUOUS
during task
listed
PERIODIC
during task
listed
REFERENCE
STANDARD
1. Shop drawings shall be reviewed for compliances
with the contract specifications and drawings
prior to fabrication.
X
2. Form work, rebar, location of lifting hooks and
embedded items including pre-stressed tendons
and post tension duct.
X SBC 304 (3.5, 7.1-7.7,
16.7)
3. Concrete mix design approval and verify the use
of the approved concrete mix.
X SBC 304 (4, 5.2-5.4)
4.
a.
Conveying and placing concrete techniques. X SBC 304 (5.9 & 5.10)
b.
Samples of the concrete to determine slump
test, temperature, air and the strength of the
mix.
X ACI 301, Section
1.6.4.2.d, e, f & g
5.
Precast with pretension
a. Verification of tendons for prestressed
reinforcement.
X SBC 304 (3.5)
b. Verification tensile stresses in the tendons
and measurement of tendon elongation.
X SBC 304 (18.18)
c. Verification of anchorage end blocks
strength to support prestressing forces.
X SBC 304 (18.13.2)
6. Curing techniques including curing by high
pressure steam to accelerate strength gain and
reduce time of curing.
X SBC 304 (5.11 & 5.13)
7. Finishing
X ACI 301 Section 5.3.3
& 5.3.4
8. Precast with post-tension
a. Verification of the concrete strength before
the post tension takes place.
X
b. Verification of ducts and end anchorage
materials.
X ACI 301, Section 9.2
c. Verification of the profile of ducts in the
member as per design drawings.
X SBC 304 (18.15)
d. Verification of prestressing force and
measurement of tendon elongation.
X SBC 304 (18.18)
e. Grouting of ducts. X SBC 304 (18.16)
f. Verification of anchorage and couplers. X SBC 304 (18.19)
9.
Transportation
a. Verification of precast elements transported
position consistent with their shape and
design to avoid excessive handling stress.
X SBC 304 (16.6)
b. Verification of concrete strength before
transportation. Member should have
attained 85% of the concrete compressive
strength.
X SBC 304 (16.6)
10. Storage and handling at the job site. X SBC 304 (16.9)
11. Lifting and erection of the elements. X
12. Connection type and technique.
Refer to Table 2.3
X SBC 306, AWS (D1.1),
ASTM A 325, ASTM
A490,H-strength,
ASTM A 307 Regular
SPECIAL INSPECTIONS
SBC 302 2007 2/6
SECTION 2.6
MASONRY CONSTRUCTION
2.6.0 The special inspection and verifications for masonry construction shall be as
required by this section and table 2.6.
Exception: Special inspections shall not be required for minor construction such
as fence walls.
TABLE 2.6
REQUIRED VERIFICATION AND INSPECTION OF MASONRY CONSTRUCTION
REFERENCE STANDARD
VERIFICATION AND INSPECTION
Continuous
during task
listed
Periodic
during
task listed
SBC 305
ACI 530.1/ASCE
6/TMS 602
1-As masonry construction begins, the following
shall be verified to ensure compliance with the
approved submittals
a. Certificate for materials used in masonry
construction including but not limited
Masonry units,
Mortar and grout material,
Anchors, ties, fasteners, and metal accessories,
Reinforcement.
X
3.
Art. 1.5
Art. 2.6A
2-The inspection program shall verify
compliance with construction documents and
code provisions.
a. Size, location, and alignment of structural
elements and construction.
X
Art. 3.3G
b. Placement of masonry units and mortar.
X
Art. 3.2D
b. Placement of reinforcement and connectors.
X
Art. 3.4
c. Proportions of site-prepared grout.
X
Art. 2.6B
4-Grout placement shall be verified to ensure
compliance with code.
X
Art 3.5
5-Preparation of any required grout specimens,
mortar specimens and/or prisms shall be observed.
X 5.2.2, 5.3
Art. 1.4
SECTION 2.7
SOIL AND FOUNDATIONS
2.7.0 The special inspections for existing site soil conditions, fill placement and load-
bearing requirements shall be as required by this section and Table 2.7. The
approved soils report, required by Section 2.2 SBC 303, shall be used to determine
compliance.
SPECIAL INSPECTIONS
SBC 302 2007 2/7
TABLE 2.7
REQUIRED VERIFICATION AND INSPECTION OF SOIL AND FOUNDATIONS
REFERENCE STANDARD
VERIFICATION AND INSPECTION
Continuous
during task
listed
Periodic
during task
listed
SBC 303 ASTM
1. Geotechnical Investigation Chapter 2 D-420
a. Particle Size Analysis of Soils X D-422, D-1140
b. Liquid Limit, Plastic Limit X D4318
c. Standard Penetration Test X D-1586
d. Soil Classification X D-2487
2. Earthwork Chapter 3
a. Excavation X
b. Backfill - Compaction
b.1 Moisture Density Relations X D-698, D-1557
b.2 Density by Nuclear Methods X D-2922
c. Drainage X Chapter 13
3. Dewatering X Chapter 13
4. Bearing Capacity Chapter 4
a. Plate Load Test X D-1194
b. Field Vane Test in Cohesive Soils X D-2573
c. Direct Shear Strength X D-3080
5. Footings and Foundations X Chapters 5, 6, 8,
9, 10, 11, 12
6. Retaining Walls X Chapter 7
7. Damp proofing & Waterproofing X Chapter 13
8. Pier & Pile Foundations Chapter 14
a. Friction Cone Penetration Test X D-3441
b. (Testing) Pile under Axial Load X D-1143
9. Expansive & Collapsible Soils X Chapter 2
10. Sabkha Soils X SBC 302 (2.7.5)
11. Random & Artificial Backfill X SBC 302 (2.7.4)
2.7.1 Site preparation. Prior to placement of the prepared fill, the special inspector
shall determine that the site has been prepared in accordance with the approved
soils report.
2.7.2 During fill placement. During placement and compaction of the fill material, the
special inspector shall determine that the material being used and the maximum lift
thickness comply with the approved report, as specified in Section 3.10 SBC 303.
2.7.3 Evaluation of in-place density. The special inspector shall determine, at the
approved frequency, that the in-place dry density of the compacted fill complies
with the approved report.
2.7.4 Special conditions. Random backfill or artificial backfill when encountered in
reclaimed land (along shorelines, wadi slopes, etc.) shall be treated with utmost
care, to make sure that soil conditions are satisfactory, otherwise soil improvement
techniques should be used to avoid future structural damage.
2.7.5 Sabkha soils. Building foundations built over Sabkha soils, encountered in many
locations in the Kingdom of Saudi Arabia, should be protected. Special precaution
shall be taken regarding the control of humidity in the ground. Replacement of
Sabkha soils shall be considered where possible.
2.7.6 Pile foundations. A special inspector shall be present when pile foundations are
being installed and during tests. The special inspector shall make and submit to the
building official records of installation of each pile and results of load tests.
SPECIAL INSPECTIONS
SBC 302 2007 2/8
Records shall include the cutoff and tip elevation of each pile relative to a
permanent reference.
2.7.7 Pier foundations. Special inspection is required for pier foundations for buildings
assigned to Seismic Design Category C or D.
SECTION 2.8
SPRAYED FIRE-RESISTANT MATERIALS
2.8.0 Special inspections for sprayed fire-resistant materials applied to structural
elements and decks shall be in accordance with Section 2.8.1 through 2.8.5.
Special inspections shall be based on the fire-resistance design as designated
in the approved construction documents.
2.8.1 Structural member surface conditions. The surfaces shall be prepared in
accordance with the approved fire-resistance design and the approved
manufacturers written instructions. The prepared surface of structural members to
be sprayed shall be inspected before the application of the sprayed fire-resistant
material.
2.8.2 Application. The substrate shall have a minimum ambient temperature before and
after application as specified in the approved manufacturers written instructions.
The area for application shall be ventilated during and after application as required
by the approved manufacturers written instructions.
2.8.3 Thickness. The average thickness of the sprayed fire-resistant materials applied to
structural elements shall not be less than the thickness required by the approved
fire-resistant design. Thickness shall be determined in accordance with ASTM E
605. Samples of the sprayed fire-resistant materials shall be selected in accordance
with Section 2.8.3.1 and 2.8.3.2.
2.8.3.1 Floor, roof and wall assemblies. The thickness of the sprayed fire-resistant
material applied to floor, roof and wall assemblies shall be determined in
accordance with ASTM E 605, taking the average of not less than four
measurements for each 100 m
2
of the sprayed area on each floor or part thereof.
2.8.3.2 Structural framing members. The thickness of the sprayed fire-resistant material
applied to structural members shall be determined in accordance with ASTM E 605.
Thickness testing shall be performed on not less than 25 percent of the structural
members on each floor.
2.8.4 Density. The density of the sprayed fire-resistant material shall not be less than the
density specified in the approved fire-resistant design. Density of the sprayed fire-
resistant material shall be determined in accordance with ASTM E 605.
2.8.5 Bond strength. The cohesive/adhesive bond strength of the cured sprayed fire-
resistant material applied to structural elements shall not be less than 7 kN/m
2
. The
cohesive/adhesive bond strength shall be determined in accordance with the field test
specified in ASTM E 736 by testing in-place samples of the sprayed fire-resistant
material selected in accordance with 2.8.5.1 and 2.8.5.2.
2.8.5.1 Floor, roof and wall assemblies. The test samples for determining the cohesive/
adhesive bond strength of the sprayed fire-resistant materials shall be selected
from each floor, roof and wall assembly at the rate of not less than one sample for
SPECIAL INSPECTIONS
SBC 302 2007 2/9
every 1000 m
2
or part thereof of the sprayed area in each story.
2.8.5.2 Structural framing members. The test samples for determining the cohesive/
adhesive bond strength of the sprayed fire-resistant materials shall be selected
from beams, girders, joists, trusses and columns at the rate of not less than one
sample for each type of structural framing member for each 1000 m
2
of floor area
or part thereof in each story.
SEISMIC AND WIND RESISTANT CONSTRUCTIONS
SBC 302 2007 3/1
CHAPTER 3
SEISMIC AND WIND RESISTANT CONSTRUCTIONS
SECTION 3.1
SCOPE
The provisions of this chapter apply to Quality assurance, Special inspections and
Testing for Seismic Resistance and Special Inspections for Wind Requirements.
Provisions in Chapter 15 SBC 301 shall apply when not in conflict with the
seismic provisions of this chapter.
SECTION 3.2
QUALITY ASSURANCE FOR SEISMIC RESISTANCE
3.2.1 Scope. A quality assurance plan for seismic requirements shall be provided in
accordance with Section 3.2.2 for the following:
1. The seismic-force-resisting systems in structures assigned to Seismic Design
Category C or D.
2. Designated seismic systems in structures assigned to Seismic Design Category
D.
3. The following additional systems in structures assigned to Seismic Design
Category C:
a. Heating, ventilating and air-conditioning (HVAC) ductwork
containing hazardous materials and anchorage of such ductwork.
b. Piping systems and mechanical units containing flammable,
combustible or highly toxic materials.
c. Anchorage of electrical equipment used for emergency or standby
power systems.
4. The following additional systems in structures assigned to Seismic Design
Category D:
a. Systems required for Seismic Design Category C.
b. Exterior wall panels and their anchorage.
c. Suspended ceiling systems and their anchorage.
d. Access floors and their anchorage.
e. Steel storage racks and their anchorage, where the factor, Ip,
determined in Section 12.15, SBC 301, is equal to 1.5.
Exceptions:
A quality assurance plan is not required for structures designed and constructed
in accordance with the following:
1. The structure is constructed of light framed cold-formed steel; the design
spectral response acceleration at short periods, S
DS
, as determined in Section
9.4 SBC 301, does not exceed 0.5 g, and the height of the structure does
not exceed 10000 mm above grade plane; or
SEISMIC AND WIND RESISTANT CONSTRUCTIONS
SBC 302 2007 3/2
2. The structure is constructed using a reinforced masonry structural system or
reinforced concrete structural system; the design spectral response
acceleration at short periods, S
DS
, as determined in section 9.4 SBC 301,
does not exceed 0.5 g, and the height of the structure does not exceed 8000
mm above grade plane; or
3. The structure is a detached one- or two-family dwelling not exceeding two
stories in height; and
a. The structure is classified as Occupancy Category I, as determined in
Section 9.5, SBC 301; and
b. The structure does not have any of the following plan or vertical
irregularities as defined in Section 10.3.2, SBC 301:
i. Torsional irregularity.
ii. Nonparallel systems.
iii. Stiffness irregularityextreme soft story and soft story.
iv. Discontinuity in capacityweak story.
3.2.2 Quality assurance plan preparation. The design of each designated seismic
system shall include a quality assurance plan prepared by a registered
professional structural engineer. The quality assurance plan shall identify the
following:
1. The designated seismic systems and seismic-force-resisting systems that are
subject to quality assurance in accordance with Section 3.2.1.
2. The special inspections and testing to be provided as required by Chapter 2
and section 3.4 and other applicable sections of SBC, including the
applicable standards referenced by SBC.
3. The type and frequency of testing required.
4. The type and frequency of special inspections required.
5. The required frequency and distribution of testing and special inspection
reports.
3.2.3 Contractor responsibility. Each contractor responsible for the construction of a
seismic-force-resisting system, designated seismic system, or component listed in
the quality assurance plan shall submit a written contractors statement of
responsibility to the building official and to the owner prior to the commencement
of work on the system or component. The contractors statement of responsibility
shall contain the following:
1. Acknowledgment of awareness of the special requirements contained in
the quality assurance plan.
2. Acknowledgment that control will be exercised to obtain conformance
with the construction documents approved by the building official.
3. Procedures for exercising control within the contractors organization, the
method and frequency of reporting and the distribution of the reports.
4. Identification and qualifications of the person(s) exercising such control
and their position(s) in the organization.
SEISMIC AND WIND RESISTANT CONSTRUCTIONS
SBC 302 2007 3/3
SECTION 3.3
SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE
3.3.1 General. Special inspection as specified in this section is required for the
following, where required in Section 2.1. Special inspections itemized in Section
3.3.2 through 3.3.6 are required for the following:
1. The seismic-force-resisting systems in structures assigned to Seismic
Design Category C or D, as determined in Section 9.6, SBC 301.
2. Designated seismic systems in structures assigned to Seismic Design
Category D.
3. Architectural, mechanical and electrical components in structures
assigned to Seismic Design Category C or D that are required in Section
3.3.5 and 3.3.6.
3.3.2 Structural steel. Continuous special inspection for structural welding in
accordance with AISC 341.
Exceptions:
1. Single-pass fillet welds not exceeding 8 mm in size.
2. Floor and roof deck welding.
3.3.3 Cold-formed steel framing. Periodic special inspections during welding
operations of elements of the seismic-force-resisting system. Periodic special
inspections for screw attachment, bolting, anchoring and other fastening of
components within the seismic-force-resisting system, including struts, braces, and
hold-downs.
3.3.4 Storage racks and access floors. Periodic special inspection during the anchorage
of access floors and storage racks 2500 mm or greater in height in structures
assigned to Seismic Design Category D.
3.3.5 Architectural components. Periodic special inspection during the erection and
fastening of exterior cladding, interior and exterior nonbearing walls and interior and
exterior veneer in structures assigned to Seismic Design Category D.
Exceptions:
1. Special inspection is not required for architectural components in
structures 9000 mm or less in height.
2. Special inspection is not required for cladding and veneer weighing 250
N/m
2
or less.
3. Special inspection is not required for interior nonbearing walls
weighing 750 N/m
2
or less.
3.3.6 Mechanical and electrical components. Periodic special inspection is required
during the anchorage of electrical equipment for emergency or standby power
systems in structures assigned to Seismic Design Category C or D. Periodic
special inspection is required during installation of piping systems intended to
carry flammable, combustible or highly toxic contents and their associated
mechanical units in structures assigned to Seismic Design Category C or D. Periodic
SEISMIC AND WIND RESISTANT CONSTRUCTIONS
SBC 302 2007 3/4
special inspection is required during the installation of HVAC ductwork that will
contain hazardous materials in structures assigned to Seismic Design Category C
or D.
3.3.6.1 Component inspection. Special inspection required for the installation of the
following components, where the component has a Component Importance Factor
of 1.0 or 1.5 in accordance with Section 12.1.5 SBC 301, shall maintain an
approved quality control program. Evidence of the quality control program shall
be permanently identified on each piece of equipment by a label.
1. Equipment using combustible energy sources.
2. Electrical motors, transformers, switchgear unit substations and motor
control centers.
3. Reciprocating and rotating-type machinery.
4. Piping distribution systems 75 mm and larger.
5. Tanks, heat exchangers and pressure vessels.
3.3.6.2 Component and attachment testing. The component manufacturer shall test or
analyze the component and the component mounting system or anchorage for the
design forces in SBC 301 for those components having a Component Importance
Factor of 1.0 or 1.5 in accordance with SBC 301. The manufacturer shall submit a
certificate of compliance for review and acceptance by the registered design
professional responsible for the design, and for approval by the building official.
The basis of certification shall be by test on a shaking table, by three-dimensional
shock tests, by an analytical method using dynamic characteristics and forces from
SBC 301 or by more rigorous analysis. The special inspector shall inspect the
component and verify that the label, anchorage or mounting conforms to the
certificate of compliance.
SECTION 3.4
STRUCTURAL TESTING FOR SEISMIC RESISTANCE
3.4.1 Masonry. Testing and verification of masonry materials and assemblies
prior to construction shall comply with the requirements of Section 3.4.1,
and Table 3.4.
TABLE 3.4
MINIMUM TESTS AND SUBMITTALS
Certificates of compliance used in masonry construction.
Verification of prior to construction and every 500 square meters
during construction.
'
m
f
Verification of proportions of materials in mortar and grout as
delivered to the site.
3.4.2 Testing for seismic resistance. The tests specified in Section 3.4.3 through 3.4.5
are required for the following:
1. The seismic-force-resisting systems in structures assigned to Seismic
Design Category C or D, as determined in SBC 301.
2. Designated seismic systems in structures assigned to Seismic Design
SEISMIC AND WIND RESISTANT CONSTRUCTIONS
SBC 302 2007 3/5
Category D.
3. Architectural, mechanical and electrical components in structures
assigned to Seismic Design Category C or D that are required in Section
3.4.5.
3.4.3 Reinforcing and prestressing steel. Certified mill test reports shall be provided for
each shipment of reinforcing and prestressing steel used to resist flexural, shear and
axial forces in reinforced concrete intermediate frames, special moment frames and
boundary elements of special reinforced concrete or reinforced masonry shear
walls.
3.4.4 Structural steel. The testing shall be as required by AISC 341 and the additional
requirements herein. The acceptance criteria for nondestructive testing shall be as
required in AWS D1.1 or specified by the registered design professional.
3.4.5 Mechanical and electrical equipment. Each manufacturer of designated seismic
system components shall test or analyze the component and its mounting system or
anchorage and submit a certificate of compliance for review and acceptance by
the registered design professional in responsible charge of the design of the
designated seismic system and for approval by the building official. The evidence
of compliance shall be by actual test on a shake table, by three-dimensional shock
tests, by an analytical method using dynamic characteristics and forces, by the use
of experience data (i.e., historical data demonstrating acceptable seismic
performance) or by more rigorous analysis providing for equivalent safety. The
special inspector shall examine the designated seismic system and determine
whether the anchorages and label conform with the evidence of compliance.
SECTION 3.5
SPECIAL INSPECTIONS FOR WIND REQUIREMENTS
3.5.0 Inspection of Structural Connections in wind exposure Categories C and D where
the 3-second gust basic wind speed is 175 km/h or greater, shall be in accordance
to Table 3.5.
Exception: Fabrication of manufactured components and assemblies that have a
label indicating compliance with the wind-load and impact-resistance
requirements of this code.
SEISMIC AND WIND RESISTANT CONSTRUCTIONS
SBC 302 2007 3/6
TABLE 3.5
REQUIRED VERIFICATION AND INSPECTION OF STRUCTURAL
CONNECTIONS
VERIFICATION AND INSPECTION
Continuous
during task
listed
Periodic
during task
listed
References
Standard
1. Roof connections and roof framing
connections
X SBC 306
2. Wall connections to roof and floor
diaphragms and framing.
X SBC 306
3. Roof and floor diaphragm systems, including
collectors, drag struts and boundary elements.
X SBC 306
4. Vertical windforce-resisting systems,
including braced frames, moment frames and
shear walls.
X SBC 306
5. Windforce-resisting system connections to the
foundation.
X SBC 306
6. Fabrication and installation of components
and assemblies required to meet the impact-
resistance requirements.
X
SBC 306
7. Precast concrete wall elements during the
erection.
X SBC 306
SPECIAL CONDITIONS
SBC 302 2007 1 4/
CHAPTER 4
SPECIAL CONDITIONS
SECTION 4.1
ALTERNATIVE MATERIALS AND TEST PROCEDURES
4.1.1 Conformance to standards. The design strengths and permissible stresses of any
structural material that are identified by a manufacturers designation as to
manufacture and grade by mill tests, or the strength and stress grade is otherwise
confirmed to the satisfaction of the building official, shall conform to the
specifications and methods of design of accepted engineering practice or the
approved rules in the absence of applicable standards.
4.1.2 New materials. For new materials that are not specifically provided for in this
code, the design strengths and permissible stresses shall be established by tests as
provided for in Section 4.1.3.
4.1.3 Test procedure. In the absence of approved rules or other approved standards, the
building official shall make, or cause to be made, the necessary tests and
investigations; or the building official shall accept duly authenticated reports from
approved agencies in respect to the quality and manner of use of new materials or
assemblies as provided for in Section 1.4. The cost of all tests and other
investigations required under the provisions of this code shall be borne by the
permit applicant.
SECTION 4.2
TEST SAFE LOAD
4.2.0 Where proposed construction is not capable of being designed by approved
engineering analysis, or where proposed construction design method does not
comply with the applicable material design standard, the system of construction or
the structural unit and the connections shall be subjected to the tests prescribed in
Section 4.4. The building official shall accept certified reports of such tests
conducted by an approved testing agency, provided that such tests meet the
requirements of SBC and approved procedures.
SECTION 4.3
IN-SITU LOAD TESTS
4.3.1 General. Whenever there is a reasonable doubt as to the stability or load-bearing
capacity of a completed building, structure or portion thereof for the expected loads,
an engineering assessment shall be required. The engineering assessment shall
involve either a structural analysis or an in-situ load test, or both. The structural
analysis shall be based on actual material properties and other as-built conditions
that affect stability or load-bearing capacity, and shall be conducted in accordance
with the applicable design standard. If the structural assessment determines that
the load-bearing capacity is less than that required by the code, load tests shall be
conducted in accordance with Section 4.3.2. If the building, structure or portion
thereof is found to have inadequate stability or load-bearing capacity for the expected
loads, modifications to ensure structural adequacy or the removal of the inadequate
construction shall be required.
SPECIAL CONDITIONS
SBC 302 2007 2 4/
4.3.2 Test standards. Structural components and assemblies shall be tested in accordance
with the appropriate material standards listed in SBC. In the absence of a standard
that contains an applicable load test procedure, the test procedure shall be developed
by a registered design professional and approved. The test procedure shall simulate
loads and conditions of application that the completed structure or portion thereof
will be subjected to in normal use.
4.3.3 In-situ load tests. In-situ load tests shall be conducted in accordance with Section
4.3.3.1 or 4.3.3.2 and shall be supervised by a registered design professional. The
test shall simulate the applicable loading conditions specified in SBC 301 as
necessary to address the concerns regarding structural stability of the building,
structure or portion thereof.
4.3.3.1 Load test procedure specified. Where a specialized code or standard listed in SBC
contains an applicable load test procedure and acceptance criteria, the test
procedure and acceptance criteria in the standard shall apply. In the absence of
specific load factors or acceptance criteria, the load factors and acceptance criteria
in Section 4.3.3.2 shall apply.
4.3.3.2 Load test procedure not specified. In the absence of applicable load test
procedures contained within a standard referenced by this code or acceptance
criteria for a specific material or method of construction, such existing structure
shall be subjected to a test procedure developed by a registered design professional
that simulates applicable loading and deformation conditions. For components
that are not a part of the seismic-load-resisting system, the test load shall be equal
to two times the unfactored design loads. The test load shall be left in place for a
period of 24 hours. The structure shall be considered to have successfully met the
test requirements where the following criteria are satisfied:
1. Under the design load, the deflection shall not exceed the limitations
specified in SBC 301.
2. Within 24 hours after removal of the test load, the structure shall have
recovered not less than 75 % of the maximum deflection.
3. During and immediately after the test, the structure shall not show
evidence of failure.
SECTION 4.4
PRECONSTRUCTION LOAD TESTS
4.4.1 General. In evaluating the physical properties of materials and methods of
construction that are not capable of being designed by approved engineering
analysis or do not comply with applicable material design standards listed in SBC,
the structural adequacy shall be predetermined based on the load test criteria
established in Section 4.4.
4.4.2 Load test procedures specified. Where specific load test procedures, load
factors and acceptance criteria are included in the applicable design standards
listed in SBC, such test procedures, load factors and acceptance criteria shall apply.
In the absence of specific test procedures, load factors or acceptance criteria, the
corresponding provisions in Section 4.4.3 shall apply.
SPECIAL CONDITIONS
SBC 302 2007 3 4/
4.4.3 Load test procedures not specified. Where load test procedures are not specified
in the applicable design standards listed in SBC, the load-bearing and deformation
capacity of structural components and assemblies shall be determined on the basis
of a test procedure developed by a registered design professional that simulates
applicable loading and deformation conditions. For components and assemblies
that are not a part of the seismic-load-resisting system, the test shall be as specified
in Section 4.4.3.1. Load tests shall simulate the applicable loading conditions
specified in SBC 301.
4.4.3.1 Test procedure. The test assembly shall be subjected to an increasing
superimposed load equal to not less than two times the superimposed design load.
The test load shall be left in place for a period of 24 hours. The tested assembly
shall be considered to have successfully met the test requirements if the assembly
recovers not less than 75 % of the maximum deflection within 24 hours after the
removal of the test load. The test assembly shall then be reloaded and subjected
to an increasing superimposed load until either structural failure occurs or the
superimposed load is equal to two and one-half times the load at which the
deflection limitations specified in Section 4.4.3.2 were reached, or the load is
equal to two and one-half times the superimposed design load. In the case of
structural components and assemblies for which deflection limitations are not
specified in Section 4.4.3.2, the test specimen shall be subjected to an increasing
superimposed load until structural failure occurs or the load is equal to two and
one-half times the desired superimposed design load. The allowable superimposed
design load shall be taken as the lesser of:
1. The load at the deflection limitation given in Section 4.4.3.2.
2. The failure load divided by 2.5.
3. The maximum load applied divided by 2.5.
4.4.3.2 Deflection. The deflection of structural members under the design load shall not
exceed the limitations in SBC 301.
4.4.4 Wall and partition assemblies. Load-bearing wall and partition assemblies shall
sustain the test load both with and without window framing. The test load shall
include all design load components. Wall and partition assemblies shall be tested
both with and without door and window framing.
4.4.5 Test specimens. Test specimens and construction shall be representative of the
materials, workmanship and details normally used in practice. The properties of the
materials used to construct the test assembly shall be determined on the basis of
tests on samples taken from the load assembly or on representative samples of the
materials used to construct the load test assembly. Required tests shall be conducted
or witnessed by an approved agency.
SBC 302 2007 References/1
REFERENCED STANDARDS
These are the standards referenced within SBC 302. The standards are listed herein by the
promulgating agency of the standard, the standard identification, the effective date and title.
The application of the referenced standards shall be as specified in SBC.
1. American Concrete Institute (ACI), "Specifications for Masonry Structures", ACI
530.1-02, Farmington Hills, MI 483333-9094.
2. American Concrete Institute (ACI), "Specifications for Structural Concrete", ACI 301,
Farmington Hills, MI 483333-9094.
3. American Institute of Steel Construction, Inc. (AISC), Specification for Structural
Steel Buildings Allowable Stress Design and Plastic Design, including Supplement
No. 1, 2001, AISC 335-89S1 Chicago, IL 60601-2001.
4. American Institute of Steel Construction, Inc. (AISC), Load and Resistance Factor
Design Specification for Structural Steel Buildings LRFD 1999, Chicago, IL 60601-
2001.
5. American Institute of Steel Construction, Inc. (AISC), Seismic Provisions for
Structural Steel Buildings, AISC 341-02 Chicago, IL 60601-2001.
6. American Society of Civil Engineers (ASCE/SEI), Structural Engineering Institute,
Specification for Masonry Structures, ASCE 6-02, Reston, VA 20191-4400.
7. American Society for Testing and Materials (ASTM A 6/A 6M-01b Specification for
General Requirements for Rolled Steel, Structural Steel Bars, Plates, Shapes, and
Sheet Piling), West Conshohocken, PA 19428-2959.
8. American Society for Testing and Materials (ASTM A 307-00 Specification for
Carbon Steel Bolts and Studs, 60,000 psi Tensile Strength).
9. American Society for Testing and Materials (ASTM A 568/A 568M01
Specification for Steel, Sheet, Carbon, and High-Strength, Low-Alloy, Hot-Rolled and
Cold-Rolled, General Requirements).
10. American Society for Testing and Materials (ASTM C 31/31M98 Practice for
Making and Curing Concrete Test Specimens in the Field).
11. American Society for Testing and Materials (ASTM C 17299 Practice for Sampling
Freshly Mixed Concrete).
12. American Society for Testing and Materials (ASTM D 42298 Test Method for
Particle-size Analysis of Soils).
13. American Society for Testing and Materials (ASTM D114381 (1994) E01 Test
Method for Piles Under Static Axial Compressive Load).
14. American Society for Testing and Materials (ASTM D1557-00 Test Method for
Laboratory Compaction Characteristics of Soil Using Modified Effort (2,700kN
m/m
3
).
SBC 302 2007 References/2
15. American Society for Testing and Materials (ASTM D1586-99 Specification for
Penetration Test and Split-barrel Sampling of Soils).
16. American Society for Testing and Materials (ASTM D2487-00 Practice for
Classification of Soils for Engineering Purposes (Unified Soil Classification System).
17. American Society for Testing and Materials (ASTM E 605-00 Test Method for
Thickness and Density of Sprayed Fire-resistive Material (SFRM) Applied to
Structural Members)
18. American Society for Testing and Materials (ASTM E 73600 Test Method for
Cohesion/Adhesion of Sprayed Fire-resistive Materials Applied to Structural
Members)
19. American Society for Testing and Materials (ASTM A325M-93 Standard
Specification for High-Strength Bolts for Structural Steel Joints)
20. American Society for Testing and Materials (ASTM A490-97 Standard Specification
for Heat-Treated Steel Structural Bolts for Structural Steel Joints).
21. American Society for Testing and Materials (ASTM D420 Standard Guide to Site
Characterization for Engineering, Design, and Construction Purposes).
22. American Society for Testing and Materials (ASTM D1140 Standard Test Methods
for Amount of Material in Soils Finer than No. 200 (75 m ) Sieve).
23. American Society for Testing and Materials (ASTM D4318-05 Standard Test Methods
for Liquid Limit, Plastic Limit, and Plasticity Index of Soils)
24. American Society for Testing and Materials (ASTM D698 Standard Test Methods for
Laboratory Compaction Characteristics of Soil Using Standard Effort (600kN-m/m
3
)
25. American Society for Testing and Materials (ASTMD2922-01 Standard Test Methods
for Density of Soil and Soil-Aggregate in Place by Nuclear Methods (Shallow Depth).
26. American Society for Testing and Materials (ASTM, (D1194-94 Standard Test
Method for Bearing Capacity of Soil for Static Load and Spread Footings).
27. American Society for Testing and Materials (ASTM D2573-01Standard Test Method
for Field Vane Shear Test in Cohesive Soil).
28. American Society for Testing and Materials (ASTM D3080-04 Standard Test Method
for Direct Shear Test of Soils under Consolidated Drained Conditions).
29. American Society for Testing and Materials (ASTM D3441-05 Standard Test Method
for Mechanical Cone Penetration Tests of Soil).
30. American Welding Society (AWS), "Structural Welding CodeSteel", D1.100,
Miami, FL 33126.
INDEX
SBC 302 2007 Index/1
INDEX
BOLTS ..................................................................................................................................................... 2.3.3
High strength, steel .................................................................................................. 3.3.2, 3.4.3, 3.4.4
CONCRETE....................................................................................................................................... 2.4, 2.5
Inspections ................................................................................................................. 1.2, 1.3, 2.4
Materials ............................................................................................................................... 2.4.1
CONCRETE MASONRY ................................................................................................... 2.6, 3.4.1
Testing ........................................................................................................................ 1.5.5.1, 3.4
FOUNDATION .............................................................................................................................. 2.7
Special inspections ...................................................................................... 1.2, 2.1, 2.7, 3.3, 3.5
INSPECTIONS .............................................................................................................................. 2.1
Fire-resistant materials ..................................................................................................... 1.2, 2.8
Approval required ................................................................1.5, Table 2.3, Table 2.5, Table 2.6
Pile ....................................................................................................................................... 2.7.6
Reinforcing steel ..................................................................................................................... 3.4
Seismic .................................................................................................................................... 3.3
Special ......................................................................................................... 1.2, 2.1, 2.7, 3.3, 3.5
Steel, structural .................................................................................................... 2.3, 3.3.2, 3.4.4
Steel framing, cold-formed ........................................................................................... 2.3, 3.3.3
Welding ............................................................................................................... Table 2.3, 2.3.1
MASONRY ..................................................................................................................................... 2.6
Inspection ...................................................................................................................... Table 2.6
Test procedures .................................................................................................................... 4.1.3
MATERIALS .............................................................................................................................. 2.4.1
Testing .............................................................................................................. 1.5.5.1, 2.4.1, 3.4
MECHANICAL ................................................................................................................ 3.3.6, 3.4.5
Seismic inspection and testing ...................................................................................... 3.3, 3.4.2
REINFORCED CONCRETE .................................................................................................... 3.4.3
Inspections ................................................................................................................ 1.2, 1.3, 2.4
SEISMIC ...................................................................................................................................... 3.2.1
Structural observations ............................................................................................................ 3.4
Quality assurance .......................................................................................................... 3.2, 3.2.2
Structural testing ..................................................................................................................... 3.4
SPRAY-APPLIED FIRE RESISTANT MATERIALS ............................................. 1.2, 2.8, 2.8.5
Inspection ............................................................................................................................... 2.8,
STEEL ................................................................................................................................... 2.3, 3.3.2
High strength bolts ............................................................................................................... 2.3.1
STRUCTURAL TESTS AND SPECIAL INSPECTIONS ........................................................ 3.4
Alternative test procedure .......................................................................................... 4.1, 4.4.3.1
Approvals ................................................................................................................................ 1.5
INDEX
SBC 302 2007 Index/2
General .............................................................................................................................. 2.3.3.1
In-situ load tests ...................................................................................................................... 4.3
Material and test standards ................................................................................................... 4.3.2
Preconstruction load tests ....................................................................................................... 4.4
Quality assurance .......................................................................................................... 3.2, 3.2.2
Special inspections ...................................................................................... 1.2, 2.1, 2.7, 3.3, 3.5
Structural testing ..................................................................................................................... 3.4
Test safe load .......................................................................................................................... 4.2
TESTING
Roof tile ............................................................................................................................. 2.8.5.1
Seismic ................................................................................................................................. 3.4.2
Structural ................................................................................................................................. 3.4
WINDOW .................................................................................................................................... 4.4.4
Exterior, structural testing .................................................................................................... 3.3.5