Nap 101
Nap 101
Nap 101
Remote I/O
12/11/2003 Revision: A
Altus Sistemas de Informtica S.A. Pgina: 1
Application Note NAP101
Profibus DP Network with DeltaV/EMERSON
Digital Automation System and Ponto
Series
Remote I/O
Summary
Description.........................................................................................................................1
1. Introduction............................................................................................................2
2. Installation..............................................................................................................3
3. Configuration .........................................................................................................3
3.1 PROFIBUS DP Network Project ........................................................................................3
3.2 PROFIBUS DP Setting.......................................................................................................9
4. Maintenance.........................................................................................................10
4.1 Diagnostic LEDs.............................................................................................................. 10
4.2 Diagnostic Messages...................................................................................................... 11
Revisions..........................................................................................................................11
Description
This document describes the installation, configuration and maintenance of a PROFIBUS DP
network with distributed I/ The system is assembled with Altus/Ponto Series
equipment
and DeltaV/EMERSON Automation System.
Chapter 1, Introduction, describes the main characteristics of Ponto Series
Remote I/O
12/11/2003 Revision: A
Altus Sistemas de Informtica S.A. Pgina: 2
Chapter 3, Configuration, presents all the steps to create a new project of distributed I/O.
The software used to configure and set the network and equipment is the software Exploring
DeltaV from EMERSON.
Chapter 4, Maintenance, shows the system functionality and the treatment of the diagnostic
messages.
1. Introduction
The Ponto Series
modules.
Application Note: Profibus DP Network with DeltaV/EMERSON Digital Automation
System and Ponto Series
Remote I/O
12/11/2003 Revision: A
Altus Sistemas de Informtica S.A. Pgina: 3
The picture shows a typical system for distributed controlling. It is based on remote I/O
modules and PROFIBUS DP Fieldbus.
1 PROFIBUS DP Slave: PO5063 module PROFIBUS DP Head Altus
2 32 Digital input 24Vdc module
3 16 Digital output relay module
4 Expansion module
5 16 Digital output relay module with fuse
6 Bus terminator
7 Expansion cable
8 PROFIBUS DP Fieldbus
9 PROFIBUS DP Master: DeltaV/EMERSON Controller
2. Installation
The PROFIBUS DP network installation includes basic equipment from Ponto Series
/
Altus and DeltaV / EMERSON manufacturer, according the following table.
Equipment Manufacturer Description
Controller EMERSON DeltaV Controller
Profibus Interface EMERSON Interface Module DeltaV PROFIBUS
PO5063 Altus PROFIBUS DP Head
PO1010 Altus 32 DI 24VDC Opto Module
PO2022 Altus 16 Isolated DO Relay NO Dry Contact Module
PO1112 Altus 8 Isolated Universal AI Module
AL-2303 Altus PROFIBUS Net Type A Cable
DeltaV EMERSON Software Exploring DeltaV
The assembling and installation must follow the instruction of each manufacturer, according
manuals and installation guides.
3. Configuration
3.1 PROFIBUS DP Network Project
The software Exploring DeltaV is used to create and configure the project of a distributed
PROFIBUS DP remote I/O network. The DeltaV Controller will be the master of the net.
It will not be described the process of DeltaV software installation and license. It is
considerate that the software is installed and working properly.
The Software DeltaV used for development is the V7.1. version.
Application Note: Profibus DP Network with DeltaV/EMERSON Digital Automation
System and Ponto Series
Remote I/O
12/11/2003 Revision: A
Altus Sistemas de Informtica S.A. Pgina: 4
(1) Start the software DeltaV (interface Exploring DeltaV).
(2) Configure the Controller : PlantWeb Systen Configuration.. CTRL-1(Master).
(3) Select the module PROFIBUS DP: CTRL-1 I/O CXX ( posicion).
This example will use the position (C07) for the module PROFIBUS DP.
(4) Configure Port P01: C07 P01 ( right button / mouse ) Properties.
(5) Enable Port P01, set the baud rate and address, which will be the Master PROFIBUS DP
address.
Application Note: Profibus DP Network with DeltaV/EMERSON Digital Automation
System and Ponto Series
Remote I/O
12/11/2003 Revision: A
Altus Sistemas de Informtica S.A. Pgina: 5
(6) Verify if the Slave PROFIBUS DP shows in the hardware catalog (in our case the
PO5063 head), otherwise it is necessary to install the GSD file following the next steps.
(7) Add the equipment GSD file: Library Profibus DP Devices.
(8) Use the right button on Profibus DP Devices and choose Add Device Definition to add
the PROFIBUS DP Head PO5063 as Slave PROFIBUS DP module.
Application Note: Profibus DP Network with DeltaV/EMERSON Digital Automation
System and Ponto Series
Remote I/O
12/11/2003 Revision: A
Altus Sistemas de Informtica S.A. Pgina: 6
(9) In the previously window select the GSD file (from PO5063 module). Each kind of
equipment has his own configuration parameter that is define by the manufacturer. The
parameters are listed in the GSD file.
(10) Now the PO5063 can be added as slave Profibus Device: I/O P01 New Profibus
Device .
(11) Select PO5063 using the DeltaV Browser.
Application Note: Profibus DP Network with DeltaV/EMERSON Digital Automation
System and Ponto Series
Remote I/O
12/11/2003 Revision: A
Altus Sistemas de Informtica S.A. Pgina: 7
(12) The PO5063 will appear in the list of Port P01 Devices PROFIBUS DP and can be
enable and configured by the window PO5063 Properties.
(13) The PO5063 is enable in this window and can be added a description. The address is set
according the physical address of the PROFIBUS DP Head (PO5063).
(14) With the head already set and addressed it is necessary to add Slots (I/O modules)
according the configuration: PO5063 Right button / mouse New Profibus Slot .
(15) Once the Slots are inserted (according the I/O modules) it is time to configure and set
each Slot. The option Properties of each Signal will set and configure the Slot, according the
following picture:
Application Note: Profibus DP Network with DeltaV/EMERSON Digital Automation
System and Ponto Series
Remote I/O
12/11/2003 Revision: A
Altus Sistemas de Informtica S.A. Pgina: 8
(16) After Exploring DeltaV configuration it is necessary the transference of information to
memory. We can check the diagnostic of the PROFIBUS DP Slave according the following
picture (DeltaV Controller must be in operation mode and physical connections done):
The parameter Diagnostic Messages must be set or reset to avoid the operation mode
information as diagnostic message in the PO5063 module.
Application Note: Profibus DP Network with DeltaV/EMERSON Digital Automation
System and Ponto Series
Remote I/O
12/11/2003 Revision: A
Altus Sistemas de Informtica S.A. Pgina: 9
3.2 PROFIBUS DP Setting
The Ponto Series
modules need a parameterization to define operation modes. It exist
common parameters and specific parameters for each module. The parameters are specified
by the GSD file.
The PO5063 head has the following common parameters.
Parameter Option Description
Hot swap disable
When the system is turned on all the modules
must be connected in the bus. They cant be
removed during on line mode operation.
Hot swap enable with no start
up consistency
The missing of declared modules on the bus or
the remove of the modules during on line
operation will not affected the power on and
head on line mode operation.
Power up system
Hot swap enable with start up
consistency (default)
All the declared modules must be placed on the
bus during the power on of the system. After
power on the modules can be replaced for
maintenance keeping the head on line
operation.
It does not allow operand
forcing (default)
The operand forcing by software is not allowed
(invalid code). Operand forcing
It allows operand forcing The operand forcing is allowed.
It does not allow output
disabling
The output disabling is not allowed by
programming software (invalid code). Disable Output
It allows output disabling The output disabling is allowed by.
Status and diagnostic errors
(default)
The extended diagnostic messages report the
status operation of the head and modules, also
indicates errors.
Diagnostic Messages
Only diagnostic errors The diagnostic messages only report errors.
No delay time
The scan time of the module will be active
immediately after physical detection.
1 second delay
The scan time of the module will be active 1
second after physical detection.
2 seconds delay (default)
The scan time of the module will be active 2
second after physical detection.
3 seconds delay
The scan time of the module will be active 3
second after physical detection.
5 seconds delay
The scan time of the module will be active 5
second after physical detection.
Delay time to module
activation
10 seconds delay
The scan time of the module will be active 10
second after physical detection.
The PO1112 has 8 analog inputs and it has the following parameters
Parameter Option Description
C (default) Temperature unit indicated in Celsius scale.
Temperature unit
F Temperature unit indicated in Farenheit scale.
100 ms (default) Inputs conversion period of 100 milliseconds.
Conversion time
2,5 ms Inputs conversion period of 2,5 milliseconds.
American standard
(default)
RTD graph according American standard.
Curva RTD
European standard RTD graph according European standard.
Channel not active Channel conversion not active. Channel X type
Voltage - 7 options Conversion channel voltage mode.
Application Note: Profibus DP Network with DeltaV/EMERSON Digital Automation
System and Ponto Series
Remote I/O
12/11/2003 Revision: A
Altus Sistemas de Informtica S.A. Pgina: 10
Current - 4 options
(default: 0 - 20 mA)
Conversion channel cuurent mode.
Thermocouple - 8 options Conversion channel thermocouple mode.
RTD - 3 options Conversion channel RTD mode.
Resistance - 2 options Conversion channel resistance mode.
1,3 ms not turbo 122 Hz
(default)
1,3 ms filter , not turbo, 122 Hz cut frequency
1,3 ms 780 Hz 1,3 ms Filter, 780 Hz cut frequency
100 ms 1,6 Hz 100 ms Filter, 1,6 Hz cut frequency
1 s 0,16 Hz 1 s Filter, 0,16 Hz cut frequency
Channel X Filter
10 s 0,016 Hz 10 s Filter, 0,016 Hz cut frequency
The technical characteristics of each I/O module must be consult for specific parameters
options and descriptions.
4. Maintenance
The base design, hot swap characteristics and fully diagnostic information are characteristics
from Ponto Series
Remote I/O
12/11/2003 Revision: A
Altus Sistemas de Informtica S.A. Pgina: 11
4.2 Diagnostic Messages
The diagnostic messages can be displayed on HMI or programming software that are
connected to the RS232 port of the PROFIBUS DP head.
The information will be placed in the memory of the PO5063 head, operand M512 to M641.
Total of 210 Operands M or 420 bytes: the first 20 bytes are used with diagnostic system,
followed by 400 bytes with modules diagnostic information (40 segments, 1 segment for each
module connected on the GBL bus).
The PO5063 Utilization Manual must be consulted for a complete description of diagnostic
information through RS232 port.
The diagnostic messages are transferred to the master via PROFIBUS DP network and they
are available for the application or to be monitored through network configuring software.
The diagnostic messages can be displayed in the Exploring DeltaV during online mode. The
slave PROFIBUS DP must be select to see the information.
Revisions
Reviso: A
Data: 12/11/2003
Traduo: Jos Lozano
Reviso Traduo:
Autor: Srgio H. C. Silva
Revisor: Fabiano Barboza / Rosana Casais
Aprovador: Luiz Francisco Gerbase
Natureza das alteraes: Primeira emisso do documento.