White Paper - Residential HVAC Split System Basics

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

St

White Paper:
Residential HVAC Split System Basics


Prepared by:

Bracken Engineering, Inc.
2701 W. Busch Blvd, Ste 200
Tampa, Florida 33618

April, 2011

2 White Paper: HVAC-Split Systems
Bracken Engineering, Inc. April 2011
INTRODUCTION

In the process of conducting assessments on dwellings, particularly if the issues at hand
are related to the building envelope or to the interior environment, it is important to have
a basic understanding of the HVAC (heating, ventilation and air conditioning) system.
This tutorial is geared primarily toward typical or split system air conditioning systems
found in residential dwellings or light commercial buildings such as stand-alone houses,
town houses, condominiums, apartments and light commercial buildings.
Florida is located in the Cooling Climate Zone meaning that it is concerned primarily
with the cooling and dehumidifying aspects of HVAC. However, it is worth noting that
while Florida is in the Cooling Climate Zone, only heating of structures is required by
Floridas Building Code. Therefore, within Florida the HVAC system is usually used to
accomplish both heating and cooling. The heating is accomplished with a heat pump
and/or an electric heat strip within the air handler and the cooling is accomplished within
the air conditioning portion of the unit. These aspects will be discussed within this
tutorial.

HVAC SYSTEM - Types
The split system is the most common for homes where a minimum of one system is
utilized. However, package units can be used on smaller structures and multiple
systems can be used on larger more complex structures. Package units are most often
found in smaller structures such as mobile homes and modular units. The package unit
is a self-contained, all-inclusive unit which is usually configured as a thru-wall unit
attached to an exterior wall. Larger homes and building may utilize more than one
system depending on the square footage and other design criteria including the method
of construction, windows, ceiling height, solar exposure, etc.

HVAC SYSTEM - Components
Typical HVAC systems or split systems, also known as central air conditioning are
comprised of three primary components: the outside unit or the compressor /
condenser, the inside unit or the air handling unit (AHU), and the air distribution
3 White Paper: HVAC-Split Systems
Bracken Engineering, Inc. April 2011
system the ducts. Aside from the two copper lines (hot side and cold side) that
transport refrigerant between the compressor / condenser and the air handling unit, the
inside and outside units in a split system are physically separated.
Additional components include the refrigerant lines, the drain line or condensate line,
the filtration system, and the controls or thermostat / humidistat. Oftentimes the
condensate line will exit the house with or adjacent to the refrigerant lines. Normally
these lines/pipes will be clumped together and will either go below grade before
entering the house via the slab or will go up and through the attic space.

Compressor / Condenser
The outside unit of a split system consists primarily of a fabricated steel housing,
the refrigerant compressor, a condensing coil, and a cooling fan. The
compressor / condenser within the housing is designed to recompress
warm refrigerant gas (pulled from the indoor air handler cooling coil) back
to a liquid refrigerant that can be returned to the indoor cooling coil once
again. When the room thermostat calls for cooling, both the indoor blower
or air handler and the outdoor compressor/condenser begin to work. The
cooling fan on top of the housing moves outdoor air across the condensing
coil to cool it and assist in condensing the high pressure, high temperature
refrigerant gas back into a liquid. The outside unit is typically found secured to a
pad along the side or rear of the house. It should be noted that Floridas Building
Code has both prescriptive and performance requirements on the placement and
attachment of outside units based on wind loads and flood plains.

Air Handling Units
The indoor unit or the air handler unit is another steel housing comprised usually
of a squirrel-cage fan or blower driven by an electric motor, the evaporator coil,
an electric heat strip, and a filter. The cooled refrigerant circulated to and from
the outside compressor/condenser unit flows through the many feet of copper
making up the evaporator coil, while the fan blows air returning to the unit across
the coil to be delivered through the supply ducts to the living spaces. If equipped
4 White Paper: HVAC-Split Systems
Bracken Engineering, Inc. April 2011
with an electric heat strip, the heat strip will be activated during heating time
periods. AHUs are typically located either within the garage, in a utility closet, or
in the attic and are often configured such that return air is drawn through a filter
before reaching the evaporator coil.

Ducts
The duct system should be a closed loop system whereby ambient air
within the dwelling is returned to the AHU (through a filter) and is blown
across the evaporator coil such that conditioned air is delivered to the
living spaces via ceiling diffusers connected to tributary ducts within the
attic space. In smaller dwellings, particularly condos, and prior to building
codes changes, the return air was often accomplished via a single return
grill ducted directly to the AHU, or to a return air box under the AHU, or to
the closet which houses the AHU. Building codes now stipulate that
dedicated return air ducts be routed to individual living spaces, bedrooms,
etc. It is important to understand the configuration of the system with
respect to the return air configuration. Remember, conditioned air
circulation is only as good as the balance of the system as a whole, if air
from a space or room cannot get to the AHU (closed door, etc.), that space
will not benefit from the conditioned air circulation. The existence of mold
within room corners, along wall to ceilings, and along the apex of vaulted
ceilings is often indicative of ineffective conditioned air circulation.
In older homes (50s, 60s, and 70s) the ducts were often comprised of
sheet metal (both circular and rectangular in cross section) wrapped with
paper-covered insulation. Newer ducts typically consist of foil covered
fiberglass duct board panels configured in rectangular cross sections, as
well as flexible circular ducts made from coiled wire and plastic sheeting
covered with fiberglass insulation and foil. Generally the duct board
sections will be constructed as the return or supply plenums or the primary
trunks which are connected directly to the AHU, the flex ducts then serve
as the tributary ducts where diameters are stepped down (supply side)
5 White Paper: HVAC-Split Systems
Bracken Engineering, Inc. April 2011
based on flow requirements. Even in systems with individual air returns,
the supply ducts/diffusers will nearly always outnumber the return
ducts/grilles because supply air will be routed to closets and bathrooms as
opposed to the return air which is accomplished in a hallway, bedroom, or
a primary living space. Thus the return air ducts will usually be larger in
diameter as will the size of the grille attached to the wall or ceiling.

Refrigerant Lines
As stated previously the refrigerant lines which consist of copper tubing extend
between the exterior compressor/condenser and the interior air handler unit. The
smaller diameter copper or the cold copper line (when in the cooling mode)
delivers the recently compressed (thereby liquefied and under pressure) Freon
(R-22) or Puron (410A) from the outside unit to the air handler. At the air handler
it first passes through a metering device or expansion valve which lowers the
pressure of the refrigerant. The refrigerant is then circulated through the
evaporator coil where the return air is blown across it. At this point the heat is
drawn out of the air and absorbed by the refrigerant within the coil thereby
causing the refrigerant to heat up and return to a gaseous state. The larger
diameter copper line or the hot line in turn delivers the now heated gas, low in
pressure, back to the compressor where the cycle is repeated until the
thermostat signals the system to stop. Because of the moving mechanical parts
within the system, particularly the compressor piston(s), lubricating oil is
necessary. This oil is entrained within the refrigerant so as to circulate with the
refrigerant throughout the cycle.
The refrigerant utilized within a typical split system will either be Freon (R-22) or
Puron (R-410A). Until recently Freon was used in most air conditioning and heat
pump units, however under the Clean Air Act of 1990, no air conditioners can use
Freon as of 2010 and by 2020 production will be totally banned. Puron has
become the refrigerant of choice and is considered to be the answer for
preventing ozone damage from air conditioners.

6 White Paper: HVAC-Split Systems
Bracken Engineering, Inc. April 2011

Condensate Line
The condensate water or water removed from the air by the air handling units is
collected within the housing and routed to a drainage system. The drainage
system normally consists of a drain line or condensate line, a drainage pan with
float switch. The condensate line, usually a PVC pipe, is to extend to the exterior
of the house, often to a location adjacent the outside unit.
A secondary means of condensate water collection is employed by a drainage
pan which is placed beneath the AHU. This pan is usually equipped with a float
switch which shuts the system down if the water level within the pan rises to a
level causing the float to switch the unit off. Water in the secondary drainage pan
usually indicates that the condensate line is plugged (a common occurrence),
excessive condensation build-up is occurring and/or the system is in need of
service.
It is important to understand the layout or the routing of condensate drain lines
because they have been known to leak within wall cavities. It is also important to
realize that condensate drain lines can condensate if not properly insulated. This
byproduct can also result in minor staining to ceilings and walls where drain
lines pass through.

Thermostat / Humidistat
The thermostat setting within the air conditioned space ultimately determines
what the temperature will be assuming the system can operate to reach the
desired temperature. During cooling the thermostat would be set to the
temperature that is comfortable to the occupants (usually the highest comfortable
temperature, likely somewhere between 74 and 80 degrees). Attempting to
control humidity by maintaining a lower temperature may be counter-productive,
in fact relative humidity will likely rise as building materials cool and approach the
dew point, thereby resulting in condensation in unwanted locations such as wall
cavities or behind wall paper.
7 White Paper: HVAC-Split Systems
Bracken Engineering, Inc. April 2011
In some cases where the relative humidity must be controlled more definitively, a
humidistat may be used in conjunction with the thermostat. If a dehumidifier is
used in lieu of the air conditioner or as a supplement to it, it will in itself control
the humidity based upon its dialed-in setting. However in some cases a
humidistat will be used in conjunction with the air conditioner thermostat,
particularly in dwellings left vacant for extended periods. In this case the
humidistat may be the driver or the trigger for cycling of the air conditioner in
order that the relative humidity as selected is maintained. Or both the relative
humidity (via the humidistat) and the temperature setting (thermostat) control the
operation of the system. In either case, inspect the wall-mounted panel (either
digital or analogue) and determine if a humidistat is part of the system and the
setting being utilized. It is important to note that the 2010 Residential Energy
Efficiency Code section 403.1.3 states: Where a humidistat is used for comfort
dehumidification, it shall be capable of being set to prevent the use of fossil fuel
or electricity to reduce humidity levels below 60 percent.

Filtration System
System filtration is most often accomplished on the return air side with a
single or central air filter. The filter will usually be a slide-out filter which
nearly matches the cross section size of the AHU and fits within a slot on
the return side. With multiple return air ducts, the filters will usually be in
the ceiling or wall grilles. Look at the condition of the filters, if it looks like
air cant pass very well or if the filter tends to get sucked into the duct, they
are heavily soiled, need to be replaced, and conditioned air circulation may
be marginalized. Remember conditioned air circulation throughout is only
as good as the flow of the return air.

SYSTEM DESIGN A/C
Obviously the main duty of the A/C system is to cool the air within the living spaces,
however just as importantly the A/C must control humidity. The level of humidity is just
as critical to maintaining the feels-good temperature in the interior as is the cooling
8 White Paper: HVAC-Split Systems
Bracken Engineering, Inc. April 2011
function of the A/C system. The lower the relative humidity is, the cooler it will feel. It is
important to understand that not only is humidity brought in from the exterior, but
moisture vapor is created within the interior via showers, cooking, laundry, etc. This
humidity must be controlled or the feels-like temperature will be raised along with the
humidity level. Generally speaking, the interior relative humidity level should be
maintained between 40% and 60%.
As the return air moves across the evaporator coil within the air handling unit the
humidity is reduced as the relatively cold evaporator coil condenses the water vapor
from the air. This condensate water is then collected within the housing and routed to
the condensate drain system. This process whereby the moisture vapor is condensed
and collected serves to reduce relative humidity within the living spaces.
The adage bigger is not always better applies in this case, because if the system is
oversized it may not run long enough during the hot humid periods to reduce the interior
humidity level. In other words if the unit is too robust it will blow cool air until the
thermostat signals that the set temperature has been achieved while not allowing the
air mass to cycle through the unit enough to draw out the moisture. At the other end of
the spectrum, if the system is undersized, the air mass will not be moved enough to cool
or draw out the moisture. Therefore, HVAC systems MUST be properly sized and the air
flow properly designed. As discussed specific control of relative humidity may be
accomplished with a separate dehumidifier or a humidistat function included with the air
conditioning system.
Houses either blow or suck. In cooling climates we tend to want the house to blow a
little or create some positive internal pressure such that the moisture laden exterior air is
pushed away or held at bay. Depending upon the construction of the house, particularly
construction whereby the house is tighter and does not breathe, negative pressure
within the house can be created. Negative pressure can result from interior exhaust
fans, gas fired appliances and/or leaking ducts located outside of the conditioned
envelope. Nevertheless be mindful of the potential for negative interior pressures or
system imbalance creating an inward vapor drive. Excessive negative interior pressure
developed by the HVAC system can result in an inward vapor drive. Remember that
there will be natural convective or diffusive moisture vapor migration from areas of
9 White Paper: HVAC-Split Systems
Bracken Engineering, Inc. April 2011
higher pressure/temperature (hot exterior) to areas of lower pressure/temperature
(cooled interior).
Minimum Efficiencies for Cooling Equipment. According to the Florida Building Code
2010 Energy Conservation: 403.6.2.2 Cooling equipment installed in residential units
shall meet the minimum efficiencies of the 503.2.3 tables in chapter 5 of this code for
the type of equipment installed. Equipment used to provide water heating functions as
part of a combination system shall satisfy all stated requirements for the appropriate
space heating or cooling category. (Remember, this pertains to residential applications,
the specific energy code for commercial applications should be referenced as required.)
It is important to note that some air conditioning systems are capable of providing
heated water as a by-product of the system. This can be accomplished by a heat
exchanger which captures the heat given off by the hot/low-pressure copper line of a
split system. This is often used to preheat water thereby reducing the amount of
energy required to heat the residences hot water supply. This is accomplished by
running the incoming water through a heat exchanger.

SYSTEM DESIGN Heat
Within Florida the HVAC system is usually used to accomplish both heating and cooling.
The heating is accomplished with a heat pump and/or an electric heat strip within the
air handler unit. A heat pump system is a variant of the typical compressor/condenser
unit whereby the systems refrigerant is forced to flow in the opposite direction. Thus the
AHU fan blows across a heated coil instead of a cooled coil and heated air is delivered
into the dwelling. Heat pump systems are more common in cooling climates where
heating requirements are relatively limited. During cooling periods the outside
compressor/condenser fan will be blowing hot air and during heating periods the
air blown from the outside unit should be cooler. If and when interior heating
requirements are such that the heat pump cannot maintain the desired
temperature an electric heat strip located within the air handler will be activated
and the air drawn into the air handler will be blown across it such that the supply
air is heated. The odor that is experienced in the living space the first time the
10 White Paper: HVAC-Split Systems
Bracken Engineering, Inc. April 2011
heat strip is activated during the heating season is a result of the heat strip
burning off the dust and debris that collects on it.

Minimum Efficiencies for Heating Equipment. According to the Florida Building Code
2010 Energy Conservation: 403.6.2.3 Heating equipment installed in residential units
shall meet the minimum efficiencies of the 503.2.3 tables in chapter 5 of this code for
the type of equipment installed. Exception: Existing mechanical systems undergoing
alteration need not meet the minimum equipment efficiencies of this section except to
preserve the original approval or listing of the equipment. (Remember, this pertains to
residential applications, the specific energy code for commercial applications should be
referenced as required.)

TROUBLESHOOTING
Be sure to look for and consider the following:
If the filters are completely soiled the air flow will suffer.
If there is a single air return in the entire dwelling unit and the dwelling is
vacant, dark, and interior doors remain closed the air flow will suffer.
If the AHU is in a closet with a single air return thru the closet door and the top
of the closet has openings into the attic or a ceiling cavity, unwanted air
sources are drawn into the system.
The AHU is in a closet in the hall outside where the closet door is not sealed
thereby drawing in unwanted air.
The AHU is in a closet and the condensate drains into an open drain in the
floor of the closet.
The AHU condensate drain is leaking in a wall or floor cavity.
The ducts in the attic have loose tape joints or have been damaged by rats
allowing ambient attic air to intrude.
The supply diffuser is right next to a return grille. The code does stipulate
what the separation should be; therefore it is incumbent upon the A/C
contractor to configure properly.
11 White Paper: HVAC-Split Systems
Bracken Engineering, Inc. April 2011
The AHU in the attic is situated immediately below the hot roof deck.
Remember the AHU is trying to create 77 degree air, what is the net effect of a
145 degree roof deck next to it.
Ducts have been added to supply a Florida room or the garage, but the system
capacity was not designed for it.
Ducts in the attic bend tightly over truss members such that they are pinched.
The supply plenum in the attic had a hole cut into it to cool the A/C guy while
he was working and the hole was not properly sealed.
The supply diffusers on the ceilings are dripping condensation and are
corroded due to excessive moisture in the system.
There is no filtration and the
evaporation coil (sometimes visible
when looking into the return side of the
AHU) is completely covered with mold,
dust and debris.
Condensation is dripping from the attic
ducts at taped joints or rat holes and
staining the ceilings.
The refrigerant lines traversed under the slab through a large diameter PVC
pipe which has filled with ground water causing eventual deterioration of the
copper.
The sheet metal chase housing the refrigerant lines and which is attached to
the exterior wall of the house is not sealed, particularly at the top, thereby
letting water flow directly into the wall cavity.

About Bracken Engineering:
Brackens expertise ranges from design to forensics to construction to disaster support. They
work with a wide range of property types, including commercial, residential, municipal, industrial
and agricultural. They are experts at addressing code public safety, cost and risk management
issues for insurance, legal, construction and the real estate industries.
www.brackenengineering.com
SUPPLY RETURN

You might also like