DISTRIBUTION TRANSFORMER
SPECIFICATION #1212.03
15kV Single Phase Submersible Transformer
Stainless Steel
12/2/2011 Page 2 of 8
1. SCOPE
This specification covers single-phase submersible transformers for use on a the Districts 12470
GrdY/7200 Volt 60 Hertz,. underground distribution system and appropriate for 3 banking The
transformers are intended for installation below ground in vaults and for operation on a primary
loop or radial system. The transformers shall be suitable for continuous submersion. The
transformers will be connected phase-to-neutral in both single-phase or three-phase applications.
The low voltage windings will be connected closed delta or closed Y.
2. STANDARDS
All material and equipment furnished under these specifications shall conform to the latest
applicable approved standards of the IEEE, ANSI, and NEMA, except as otherwise specified
herein.
3. RATINGS
3.1. All ratings shall be for 60 Hertz alternating current, oil immersed, self-cooled
transformers capable of continuous operation at rated kVA without exceeding either a
55C average temperature rise or a 70C hot spot temperature rise.
3.2. The electrical characteristics of the completely assembled high and low voltage terminals
shall be 7200/12470Y, and 120/240 (4 low-voltage bushings).
3.3. The basic impulse level (BIL) shall be 95 kV.
4. RADIAL FEED
Transformers will be suitable for radial feed.
5. CONSTRUCTION
5.1. Construction of the units shall be such that they can be lifted and lowered into place in a
suitably designed and constructed enclosure having a minimum diameter of 36 inches. To
allow for cabling space and proper airflow for cooling, the transformers covered by this
standard shall not have overall diameters in excess of 30 inches for sizes 100 kVA and
smaller, in excess of 33 inches for 167 kVA or 38 inches for 250kva and larger.
5.2. The transformer tank, cover, and all external appurtenances shall be of corrosion-resistant
304L stainless steel. This includes welds, plugs (may be brass), nameplates, etc.
5.3. A protective (paint) coating of semi-gloss sky gray similar in color to ANSI Standard no.
70 shall be applied that is at least 3 mils thick...
5.4. Welds shall be smooth and shall not cut workers hand or gloves. The tank and cover shall
be capable of withstanding a full vacuum.
5.5. Tank Cover
5.5.1. The tank cover shall be welded to the tank. No handhole shall be installed in the
cover.
5.5.2. The threads between the oil fill plug and the boss on the tank shall be sealed
with a liquid pipe thread compound. Teflon tape is undesirable as it leaves
shreds floating in the oil. Suggested products are Rectorseal, liquid Teflon, or
similar sealants. If a fill plug is not provided, a 1/4-inch NPT boss with a brass
plug shall be provided for the purpose of pressure testing.
12/2/2011 Page 3 of 8
5.6. Tank Ground
The tank grounding connection shall be per ANSI C57.12.20, Section 6.5.4 except:
5.6.1. The connection shall consist of a stainless steel boss or pad and shall be
equipped with a solder less tinned copper-alloy connector that will
accommodate #8 solid through #2 AWG stranded copper wire. The clamping
eye bolt threads shall be 3/8-16NC.
5.6.2. The tapped hole in the boss or pad and the stud of the connector shall be 1/2-
inch-13NC, Class 2 fit. The tapped hole shall be coated with an oxide-inhibiting
compound before installation of the connector.
5.6.3. This connection shall be plainly labeled G.
5.6.4. Extra tank ground bosses shall be protected with oxide-inhibiting compound
and a plastic flanged cup pressed into the threads (aluminum cups are not
acceptable).
5.7. Base bars of 401 Stainless Steel shall be provided on the transformer tank to protect the
bottom of the tank while in transit and when installed in the underground enclosure.
Minimum bar height is 1.00 inch.
5.8. The lifting provisions shall be permanently attached and arranged on the tank to provide a
distributive balanced lift in a vertical direction for the completely assembled transformer.
They shall be designed to provide a safety factor of 5.
6. TRANSFORMER TAPS
No transformer taps are required.
7. CONNECTORS AND TERMINALS
7.1. Primary Bushing
7.1.1. Transformers shall come equipped with two high voltage bushing wells (H1 and
H2), and corresponding load break inserts for dead front application. The
bushing wells shall be welded to the transformer cover, 200-amp rated,
separable, and rated for primary switching per IEEE 386. Gasketed bushing
wells are not acceptable. The bushing well shall have a cover or cap to prevent
the entrance of moisture or dirt during shipping or storage. The cap shall be
secured in a manner that prevents its loss during shipment or temporary storage.
7.1.2. The bushings shall conform to IEEE C57.12.23.
7.1.3. The load-break bushing inserts shall be Cooper Power Systems (Catalog No.
2604797B01M) or Elastimold (Catalog No. 1601A4).
7.1.4. One parking stand shall be welded in Segment 3 as shown in the latest IEEE
C57.12.23.
7.2. Secondary Terminals or Leads
7.2.1. Four low-voltage cable leads (eight for 167 kVA, 250 kVA, and 333 kVA)
extending 36 inches above the top of the cover shall be provided and arranged
for vertical takeoff. The secondary neutral shall be floating and extended for
external grounding.
7.2.2. The cable insulation and sizes shall be in accordance with IEEE C57.12.23. The
12/2/2011 Page 4 of 8
ends of the cable leads shall be water sealed. The secondary bushing shall be
plainly labeled X1, X3, X2, or X4, appropriately.
7.2.3. The cable ends shall be sealed with a heat or cold shrink cap and can not be
removed without cutting the cap.
7.3. Ground connections shall be suitably sized for the short-circuit rating of the transformer
as defined in the latest IEEE C57.12.00
8. FUSING
8.1. Transformer H1 bushing leads shall be provided with Cooper Power Systems Bay-O-Net,
dual sensing, load break, cover-mounted, externally removable links in series with under-
oil, internally mounted 15 kV partial range current limiting fuses (CLF). The partial
range fuse shall be manufactured by Cooper Power Systems (Type Multi-Coil ELSP).
8.2. The partial range current limiting fuses shall be placed in series with the Bay-O-Net fuse
holder and be mounted internally under oil. Partial range current limiting fuses shall have
a nominal voltage rating of 15 kV.
8.3. Fuses shall meet the Districts current fusing specifications which are shown below:
Single Phase
KVA
Bay-O-Net Fuse
(Dual Sensing)
Continuous
Ampere
Rating
ELSP
Rating
(A)
Current
Limiting
(ELSP
Backup)
25 4000358C05 15 CBUC15030C100 30
37.5 4000358C08 15 CBUC15050C100 50
50 4000358C08 15 CBUC15065C100 65
75 4000358C10 25 CBUC15100C100 100
100 4000358C10 25 CBUC15100C100 100
167 4000358C12 65 CBUC15165D100 165
250 4000358C14 65 CBUC15165D100* 330
333 4000358C14 65 CBUC15165D100* 330
*indicates parallel fusing
9. TRANSFORMER OIL
Transformers shall be insulated with new (unused) mineral oil. The oil shall meet the
requirements of ANSI C57.12.00, Article 6.6.1 (1), ANSI C57.106 and ASTM 3487 Type II. The
transformer nameplate shall indicate that the PCB content of said transformer is less than 1 PPM
or at time of manufacture gas chromatographic analysis certified non-detectable PCB. The oil
shall be inhibited mineral oil containing 0.2 % by weight DBPC.
10. NOISE
Transformer sound levels shall not exceed the values specified in the latest revision of NEMA
Publication TR 1-0.11.
11. PAINT FINISH NONE REQUIRED
12. NAMEPLATES
12.1. A stainless steel diagrammatic nameplate shall be affixed to the tank cover (or any
nameplate extension bracket) using stainless steel fasteners. The nameplate shall state all
12/2/2011 Page 5 of 8
information per ANSI C57.12.00, nameplate A, except the nameplate shall include the
following:
12.1.1. A manufacturers serial number barcode shall be etched into the nameplate
using a character size of 128A. The barcode shall be a maximum high and
2 wide. The manufacturers identification characters shall not be included in
the barcode.
12.1.2. The date (month/year) of manufacture. Serial numbers that include a date code
will not suffice.
12.1.3. The statement Contains less than one ppm PCB at time of manufacture.
Separate NON PCB stickers, labels, or extra nameplates will not suffice.
12.1.4. The gallons of oil.
12.1.5. The weight of the transformer for all sizes including 25 kVA.
12.1.6. The manufacturer and catalog number for the primary fuses and fuse holder.
12.1.7. Items a., c., d., and e., above, may be either on the nameplate or a separate
stainless steel nameplate. Stenciling or other labels will not be acceptable.
13. INSPECTION
The purchaser shall at any reasonable time be permitted to have a representative visit the
Contractors factory for the purpose of witnessing manufacture of the transformers to ascertain if
the material and process used in the manufacturing conform to the Specifications.
14. TESTS
14.1. Each transformer shall receive complete tests at the factory in accordance with latest
ANSI Standards. At the option of the District, transformers may be tested for acceptance
upon receipt.
14.2. Test Tags. Each transformer shall have a durable, weatherproof tag firmly attached,
reading:
This transformer has been tested at rated line voltage and has successfully passed all
applicable
tests specified by ANSI and NEMA. The tag shall show the transformer serial number, the
date,
and name of the person who made the test. (State of Washington, Safety Statutes, Section
19.29.010, Rule 5). NOTE: Slight variations in wording will be acceptable with prior
approval, and
computer-tested units need not include a persons name.
15. EVALUATION AND AWARD
15.1. For the purpose of evaluating bids in addition to the evaluation criteria set forth in
Section B, Evaluation of Bids, consideration will be given to the following three items.
Product Quality
Loss Evaluation
12/2/2011 Page 6 of 8
Adherence to Specifications.
15.2. Transformers will be evaluated on losses using the following criteria.
15.2.1. Losses furnished for evaluation shall be guaranteed maximum losses for each
transformer bid.
15.2.2. No load losses (NLL) shall be in watts, at 20C in accordance with ANSI
C57.12.00.
15.2.3. Full-load losses (FLL) shall be in watts, measured at rated nameplate load at
85C in accordance with ANSI C57.12.00.
15.2.4. Losses will be evaluated at the following values:
15.2.5. $4.07 per watt for no-load losses
15.2.6. $1.79 per watt for full-load losses
15.2.7. The manufacturer shall furnish with each transformer a certified test report of
the no-load and full-load losses. The test report shall be submitted with the
Contractors invoice.
15.3. Transformer evaluated prices will be determined as follows:
Evaluated $ ={$4.07 x NLL}+{$1.79 x FLL]}+
{Base Price x (Transformer Evaluation Factor)}
16. DATA TO BE SUBMITTED WITH BID
Each bidder shall submit with his proposal the data listed below. He shall submit a description of
any changes, additions or exceptions to the specification he proposes, together with reasons for
the departure. Product evaluation and conformance to specification will be determined on the
basis of information submitted. The drawings and data furnished must be in sufficient detail and
clarity to enable making a complete and positive check with the technical provisions of the
specification.
16.1. Outline drawings with overall dimensions.
16.2. Details of the primary and secondary bushings. Manufacturers name and catalog
numbers will suffice for primary bushings if no exceptions are requested. Secondary
bushing details shall include (1) materials (cable or spade), (2) finish, such as plating, (3)
dimensions (cable size + length or spade size and thickness).
16.3. Maximum core losses (no load) at 20 C and load losses (windings) at full load at 85 C.
If other temperatures are used, provide an explanation and correction factor.
16.4. That the transformer is a 55 C rise design.
16.5. Impedance of windings at rated load expressed in percent of rated voltage.
16.6. Information concerning details of construction, tank materials and tank finish. State grade
of stainless steel and total thickness of paint.
16.7. Make and specification of oil. Uninhibited oil is unacceptable.
16.8. Complete primary fuse data including fuses specified for each size of transformer.
Include manufacturer and catalog number of fuse and holder.
16.9. State all electrical tests given transformers at the factory and whether these tests apply to
12/2/2011 Page 7 of 8
all units or only sample units.
16.10. Total weight of completely assembled transformer, including oil.
16.11. A drawing of the transformer nameplate. Complete fuse data shall be shown on the
nameplate: type, size, catalog number and manufacturer.
17. WORKSMANSHIP, MATERIAL, AND FINISH
All workmanship and material used on the equipment shall be first class, the best of their
respective kinds and shall be in full accordance with the most modern manufacturing practices
for distribution transformers.
18. PAYMENT
The contractors invoice must include itemized list of size (kVA) voltage and serial numbers of
units sent, along with certified test reports before invoice will be paid. An order is not complete
until certified test reports on each transformer shipped is in the Districts possession.
19. DATA TO BE FURNISHED BY THE SUCCESSFUL BIDDER
The successful bidder shall supply:
19.1. Three copies of outline dimensions of the transformer with accessories.
19.2. Three copies of the transformer nameplate.
19.3. Three copies of an instruction book covering installation, operation, and maintenance of
the equipment furnished.
19.4. One copy of certified test data for each transformer supplied. The test data shall contain
the minimum following information:
(1) core loss,
(2) load loss,
(3) exciting current at rated voltage,
(4) insulation tests.
20. DELIVERY
20.1. The transformers shall be shipped F.O.B. destination to 1150 Hawley Street,
Wenatchee, WA, 98801. The delivery will be accepted Monday through Friday
between the hours of 9:00 AM and 2:00 PM. No delivery of transformers will be
accepted on holidays. Please call Hawley Street Warehouse Foreman at (509) 663-
8121, Ext. 4730, 24 hours prior to delivery. No transformers will be received on
national holidays.
20.2. Transformers shall be shipped completely assembled in an enclosed van and filled
with the proper amount of transformer oil.
20.3. Transformers shall be shipped on individual pallets (one transformer per pallet).
Transformers shall be securely attached to the pallets to allow for forklift handling.
20.4. Rejection Of Shipment
20.4.1. Transformers exhibiting damaged parts, broken securing devices, or are
dirty from lack of proper shipping, shall be cause for rejection of shipment.
12/2/2011 Page 8 of 8
21. SPECIFICATIONS REVISIONS LOG
# Date Description
1 9/18/07 Added Specifications Revision Log
2 9/18/07 Added requirement for heat or cold shrink secondary leads caps
3 9/18/07 Added requirement that all welds, plugs, nameplates shall be 401 SS or
brass.
4 9/18/07 Added requirement that unit be painted ANSI 70 Sky Gray.
5 12/2/11 Updated fuse part numbers and corrected formatting to match other specs