FASTFLEX

Model YN25, YB25, and YB28 Flexible Sprinkler Hose


700 mm to 3700 mm Nominal Assembly Lengths
Page 1 of 10 JULY 2009 TFP720
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Construction advantage. Adjust-
ments can be made to ceiling levels
after installation without impacting
sprinklers and drops.
Equipment cost savings. Using
FASTFLEX reduces cost by elim-
inating pipe wastage and reducing
the labor associated with cutting,
threading, and sealing pipe threads.
NOTICE
The FASTFLEX exible sprinkler hos-
es described herein must be installed
and maintained in compliance with
this document and with the applicable
standards recognized by the Approval
agency, in addition to the standards of
any other authorities having jurisdic-
tion. Failure to do so may impair the
performance of these devices.
The owner is responsible for maintain-
ing their re protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
General
Description
The Tyco

FASTFLEX is a unique
sprinkler drop assembly comprised of
the following: branchline adapter nip-
ple, stainless steel exible hose with
two slip nuts, sprinkler reducer, and
lightweight ceiling bracket compo-
nents. (Refer to Figure 1.)
Using FASTFLEX can save time and
costs since the system can be in-
stalled in false ceilings without cut-
ting and threading pipes associated
with installing a drop, armover, and el-
bows. FASTFLEX makes it possible to
test and charge the system with wa-
ter before the ceiling grid is installed.
Once the ceiling grid is in position, the
FASTFLEX hoses can be reshaped to
suit the nal sprinkler location without
draining the system.
FASTFLEX exible sprinkler hose is
installed quickly without large and ex-
pensive tools. Ideal projects are of-
ces, schools, libraries, hospitals,
and shopping complexes. FASTFLEX
sprinkler hoses are for use on wet pipe
sprinkler systems only.
FASTFLEX offers the following fea-
tures:
Reduced labor costs. Using FAST-
FLEX will reduce labor costs by in-
creasing efciency. The installation
rate is two to three times quick-
er when compared to traditional t-
ting methods of installing sprinkler
drops.
Reduced need to recut sprinkler
drops. It is not necessary to adjust
sprinkler location if ceiling alignment
and level are changed.
More convenient work ow. Using
FASTFLEX eases bending and ma-
neuvering around ducts and trays in
congested spaces and for unusu-
al ceiling types and curved plaster-
board ceilings.
Technical
Data
Approvals
LPCB, VdS, FM, and UL
(Specic details for laboratory approv-
als are given in Table A, and the ap-
provals apply to the service conditions
indicated in the applicable Design Cri-
teria sections on pages 6 and 7.)
APSAD accepted per Table A.
CSTB accepted for all models and as-
sembly lengths.
Inlet Connections (Ref Fig. 1)
- ISO 7/1-R 1
- ISO 7/1-R 1-1/4
Outlet Connections (Ref Fig. 2)
- ISO 7/1-Rc 3/8
- 1/2 inch NPT
- 3/4 inch NPT
Nominal Assembly Lengths
Refer to Table A.
Construction (Ref. Fig. 1)
The Inlet Nipple is mild steel, and the
Flexible Hose is SS AISI 304. The con-
nection at each end of the Flexible
Hose utilizes a brass Slip Nut, NBR/CR
o-ring, and Nylon W6 washer. The
Sprinkler Reducer is mild steel. The
Reducer Bracket, Bar Fixing Clamps,
and Support Bar are pressed steel.
FIGURE 1
FASTFLEX FLEXIBLE SPRINKLER HOSE
TFP720
Page 2 of 10
TYPICAL SPRINKLER
SEE FIGURE 2
FOR DETAILS
(STRAIGHT SHOWN)
HOSE THREADED
SPRINKLER REDUCER
INLET
NIPPLE
BRANCHLINE FITTING OUTLET
CLAMP WITH
CEILING
T-BAR
GRID
SCREW
BOLTS
BUTTERFLY
FIXING
ISO 7/1-R 1
PIPE THREADED
END
DROP-IN
CEILING PANEL
BOLTS
REDUCER
BUTTERFLY
BRACKET WITH
SUPPORT
BAR
600 mm
25 or 28 mm ID
HOSE THREADED
END
ASSEMBLY
25 or 28 mm ID
BAR
OR ISO 7/1-R 1-1/4
25 mm ID BRAIDED
28 mm ID BRAIDED
25 mm ID BRAIDED - FM
28 mm ID BRAIDED - FM
25 mm ID UNBRAIDED
WITH SLIP NUTS:
FLEXIBLE HOSE
BRACKET WITH
THREADED
HOSE
CEILING
T-BAR
GRID
SPRINKLER
REDUCER
(SEE FIGURE 2)
REDUCER
BUTTERFLY
BOLTS
DROP-IN
CEILING
PANEL
SUPPORT
BAR
THREADED
FITTING
OUTLET
SLIP NUT
ISO 7/1-R 1
SYSTEM
BRANCHLINE
IN ACCORDANCE WITH
MANUFACTURER'S
SPRINKLER INSTALLED
INSTRUCTIONS
INLET
NIPPLE
BRANCHLINE
(NOT INCLUDED)
FITTING
CLAMP WITH
BOLTS
BUTTERFLY
FIXING
BAR
OR ISO 7/1-R 1-1/4
25 mm ID BRAIDED
28 mm ID BRAIDED
25 mm ID BRAIDED - FM
28 mm ID BRAIDED - FM
25 mm ID UNBRAIDED
WITH SLIP NUTS:
FLEXIBLE HOSE
FIGURE 2
FASTFLEX FLEXIBLE SPRINKLER HOSE
NOMINAL DIMENSIONS
TFP720
Page 3 of 10
MALE HOSE
OUTLET
STRAIGHT
AND BRACKET
120 mm
THREADED
25 or 28 mm ID
INLET
or 3/4" NPT
1/2" NPT,
ISO 7/1-Rc 3/8,
FEMALE PIPE
THREADED
WRENCH
FLATS
BRANCHLINE
FITTING
TERMINATION
FERRULE
SPRINKLER
REDUCER
HOSE
FLEXIBLE
HOSE
NIPPLE
INLET
120 mm
45 DEGREE
125 mm
125 mm
90 DEGREE
133 mm
L1
L2
NUT
SLIP
FLATS
WRENCH
AND BRACKET
25 or 28 mm ID
THREADED
MALE HOSE
INLET
OUTLET
THREADED
FEMALE PIPE
1/2" NPT,
or 3/4" NPT
ISO 7/1-Rc 3/8, ISO 7/1-Rc 3/8,
FEMALE PIPE
THREADED
or 3/4" NPT
OUTLET
1/2" NPT,
WRENCH
AND BRACKET
FLATS
INLET
25 or 28 mm ID
THREADED
MALE HOSE
50 mm 90 mm
370
(YB)
2370
3370
2770
2170
1670
1470
1380
870
670
MODEL
SIZE
1500
3100
3700
2500
2700
1800
2000
700
1000
1200
1190 1380
2980
3580
2380
1880
1680
2580
2790
3390
2190
2390
1490
1690
NOMINAL LENGTH mm
580
(YN or YB)
L1
1080
880
390
890
690
L2
(YN)
L2
SPRINKLER REDUCERS
HOSE ASSEMBLIES
BAR FIXING CLAMPS
TFP720
Page 4 of 10
Model Type
Assembly
Length in
Millimeters
LPCB VdS FM UL* APSAD**
50 and 90 mm
Bar Fixing Clamp
50 and 90 mm
Bar Fixing Clamp
50 and 90 mm
Bar Fixing Clamp
50 mm
Bar Fixing Clamp
50 and 90 mm
Bar Fixing Clamp
Sprinkler
Reducer Type
Sprinkler
Reducer Type
Sprinkler
Reducer Type
Sprinkler
Reducer Type
Sprinkler
Reducer Type
0 45 90 0 45 90 0 45 90 0 45 90 0 45 90
YN25-700 Un-braided 700 x x x x x
YN25-1000 Un-braided 1000 x x x x x
YN25-1200 Un-braided 1200 x x x x x
YN25-1500 Un-braided 1500 x x x x x
YN25-1800 Un-braided 1800 x x x x
YN25-2000 Un-braided 2000 x x x
YN25-2500 Un-braided 2500 x x x
YN25-2700 Un-braided 2700 x x x
YN25-3100 Un-braided 3100 x x x
YN25-3700 Un-braided 3700 x x x
YB25-700 Braided 700 x x x x
YB25-1000 Braided 1000 x x x x
YB25-1200 Braided 1200 x x x x
YB25-1500 Braided 1500 x x x x
YB25-1800 Braided 1800 x x x x
YB25-2000 Braided 2000 x x x
YB25-2500 Braided 2500 x x x
YB25-700 Braided-FM 700 x
YB25-1000 Braided-FM 1000 x
YB25-1200 Braided-FM 1200 x
YB25-1500 Braided-FM 1500 x
YB25-1800 Braided-FM 1800 x
YB25-2000 Braided-FM 2000 x
YB25-2500 Braided-FM 2500 x
YB28-700 Braided 700 x x x x x
YB28-1000 Braided 1000 x x x x x
YB28-1200 Braided 1200 x x x x x
YB28-1500 Braided 1500 x x x x x
YB28-1800 Braided 1800 x x x x
YB28-2000 Braided 2000 x x x
YB28-2500 Braided 2500 x x x
YB28-700 Braided - FM 700 x
YB28-1000 Braided - FM 1000 x
YB28-1200 Braided - FM 1200 x
YB28-1500 Braided - FM 1500 x
YB28-1800 Braided - FM 1800 x
YB28-2000 Braided - FM 2000 x
YB28-2500 Braided - FM 2500 x
x Indicates Listed or Approved as applicable.
* UL Listing is based on the use of the ISO 7/1-R 1 Inlet Connection.
** Acceptance by APSAD is based on using the LPCB, VdS, FM, or UL Design Criteria as may be acceptable to the authority having jurisdiction.
TABLE A
FASTFLEX SPRINKLER HOSE ASSEMBLY
MODELS, ASSEMBLY LENGTHS, AND APPROVALS
FIGURE 3
FASTFLEX FLEXIBLE SPRINKLER HOSE
-INSTALLATION GUIDANCE-
TFP720
Page 5 of 10
DO route the FASTFLEX Flexible
Hose to permit entire draining either
back into the branch-line or through
the sprinkler reducer.
DO use the FASTFLEX Inlet Nipple
with the direction of ow arrow prop-
erly oriented to avoid mismatched
threads.
NOT PERMITTED NOT PERMITTED PERMITTED
NIPPLE
OR ISO 7/1-R 1-1/4
ISO 7/1-R 1
THREADED END
THREADED
MACHINE HOSE
END
FITTING
OUTLET
BRANCHLINE
SLIP NUT
FLEXIBLE HOSE
TO SPRINKLER
INLET
TFP720
Page 6 of 10
LPCB - Design Criteria
Refer to Table A for Model, Nominal Assembly Length,
and Sprinkler Reducer combinations.
Wet-pipe systems only.
Maximum service pressure of 16 bar.
Pendent sprinklers with nominal K57, K80, or K115.
Maximum ambient temperature of 148C for YN25.
Approved as a Type 2 hose of moderate fexibility in
accordance with LPS 1261. They may be used in ap-
plications where little or mo differential movement be-
tween the two ends is expected after installation (e.g.,
supply to single sprinklers in suspended ceilings).
Approved for the following locations:
Assembly
Length in
Millimeters
Pre-Calculated
Town Mains
Pre-Calculated
Pumps
Fully
Hydraulically
Calculated
Up to 700 Yes Yes Yes
Up to 1200 No Yes Yes
Up to 3700 No No Yes

All pipe work supplying FASTFLEX in pre-calculated
systems shall be sized as distribution mains.
In suspended ceilings FASTFLEX must be installed in
accordance with this data sheet.
In suspended ceiling, sprinkler reducer must be con-
nected to the ceiling support system with brackets
supplied. For other applications the installer must
supply brackets to ensure sprinkler is secure.
Minimum bend radius of 55 mm.
LPCB Friction Loss for YN25.
Assembly
Length in
Millimeters
Number of
90 Bends
Equivalent Length* of
DN25 Sch. 40 Pipe at
C=120 in Meters
700 2 8,9
1000 2 13,5
1200 2 11,9
1500 2 18,7
1800 3 24,7
2000 3 20,7
2500 3 21,7
2700 3 24,2
3100 3 25,9
3700 3 30,3
* Add 2,3 meters when using a 45 or 90 sprinkler reducer.
VdS - Design Criteria
Refer to Table A for Model, Nominal Assembly Length,
and Sprinkler Reducer combinations.
Wet-pipe systems only.
Maximum service pressure of 16 bar.
Pendent sprinklers with nominal K57, K80, or K115.
Maximum ambient temperature of 107C for YB25
and YB28.
Approved for use only in the following suspended
ceilings:
Odenwald Systems- S3 & S15
Richter Systems- 11.1 - 11.5
Armstrong Systems- Board and Tegular with panel
type Prima Sahara
API Systems- 15/38, 24/38, 24/60, 35/38, and 35/60
with panel type of a.m.
VdS Friction Loss
For compensation of pressure loss, the nominal as-
sembly length is to be multiplied by 12. The resulting
length will provide pressure drop in equivalent length
DN20 (26,9 x 2,3 mm) seamless metal tube per DIN
2448.
Add 2,3 m when using a 45 or 90 sprinkler reducer.
Minimum bend radius of 55 mm.
The tube assembly may not have more than one 90
bend or four 15 bends.
TFP720
Page 7 of 10
FM - Design Criteria
Refer to Table A for Model, Nominal Assembly
Length, and Sprinkler Reducer combinations.
Wet-pipe systems only.
Maximum service pressure of 12 bar.
Pendent sprinklers with a maximum K80 (K5.6) for
1/2 inch NPT or maximum K115 (K8.0) for 3/4 inch
NPT.
Maximum ambient temperature of 107C for Model
YB25 and YB28.
These connections are designed for use in ceilings
with grids that meet ASTM C 635 (Standard Speci-
cation for the Manufacture, Performance, and Test-
ing of Metal Suspension Systems for Acoustical Tile
and Lay-in Panel Ceilings) and ASTM C 636 (Stan-
dard Practice for Installation of Metal Ceiling Sus-
pension Systems for Acoustical Tile and Lay-in
Panels) referenced by IBC. The three structural clas-
sications are the following: Intermediate-Duty Sys-
tems and Heavy-Duty Systems. These connections
have been approved for use in all Intermediate-Duty
and Heavy-Duty structural classications.
Minimum bend radius of 150 mm for Model YB28 or
200 mm for Model YB25.
FM Friction Loss for YB25 and YB28:
Assembly
Length in
Millimeters
Outlet
(NPT)
Number
of 90
Bends
YB25 YB28
Equivalent
Length of DN25
Sch. 40 Pipe at
C=120 in Meters
Equivalent
Length of DN25
Sch. 40 Pipe at
C=120 in Meters
700
1/2
0 3,9 1,1*
1 5,7 1,1*
3/4
0 3,9* 1,1*
1 8,3* 1,6*
1000
1/2
0 5,7* 1,7
1 7,5* 1,7
3/4
0 5,7* 1,7
1 9,7* 2,2
1200
1/2
0 6,8* 2,0*
1 8,6* 2,1*
3/4
0 7,1* 2,1*
1 10,6* 2,6*
1500
1/2
0 8,6* 2,5*
1 10,4* 2,7*
3/4
0 9,3* 2,7*
1 12,3* 3,2*
1800
1/2
0 10,3* 3,0*
1 12,1* 3,2*
3/4
0 11,0* 3,2*
1 14,4* 3,8*
2000
1/2
0 11,5* 3,3*
1 13,3* 3,6*
3/4
0 12,5* 3,6*
1 15,5* 4,2*
2500
1/2
0 14,4 4,1
1 16,2 4,6
3/4
0 16,2* 4,6
1 18,3* 5,2
*Approximate value based on interpolation and extrapolation.
UL - Design Criteria
Refer to Table A for Model, Nominal Assembly
Length, and Sprinkler Reducer combinations.
Wet-pipe systems only.
The hose and fttings have limited fexibility and are
intended for direct connection to sprinklers in accor-
dance with NFPA 13, 13D, or 13R.
Maximum service pressure of 13 bar.
Pendent sprinklers with a maximum K80 (K5.6) for
1/2 inch NPT or maximum K115 (K8.0) for 3/4 inch
NPT.
Maximum ambient temperature of 107C for Model
YB25 and YB28, or maximum ambient temperature
of 148C for Model YN25.
These connections are designed for use in ceilings
with grids that meet ASTM C 635 (Standard Speci-
cation for the Manufacture, Performance, and Test-
ing of Metal Suspension Systems for Acoustical Tile
and Lay-in Panel Ceilings) and ASTM C 636 (Stan-
dard Practice for Installation of Metal Ceiling Sus-
pension Systems for Acoustical Tile and Lay-in
Panels) referenced by IBC. The three structural clas-
sications are the following: Intermediate-Duty Sys-
tems and Heavy-Duty Systems. These connections
have been approved for use in all Intermediate-Duty
and Heavy-Duty structural classications.
Minimum bend radius of 76 mm.
Assembly
Length in
Millimeters
Outlet
(NPT)
Maximum
Number
of 90
Bends*
YN25 and YB25 YB28
Equivalent
Length of DN25
Sch. 40 Pipe at
C=120 in Meters
Equivalent
Length of DN25
Sch. 40 Pipe at
C=120 in Meters
700
1/2 2 6,7 3,0
3/4 2 8,5 4,9
1000
1/2 2 9,8 4,9
3/4 2 11,6 7,0
1200
1/2 2 12,5 6,1
3/4 2 14,6 7,6
1500
1/2 2 14,9 7,0
3/4 2 16,5 8,5
1800
1/2
2 18,3 7,9
3 20,4 9,8
3/4
2 20,4 10,1
3 22,6 11,6
* Information in this column indicates the maximum number of
allowable bends and that hoses are installed with at least one bend.
FIGURE 4
MINIMUM RADIUS INDICATOR
MRI55
TFP720
Page 8 of 10
Installation
The Tyco

FASTFLEX Flexible Sprin-


kler Hose as shown in Figure 1, is
to be installed with the following
instructions.
NOTICE
Flexible Hoses are intended only to
connect sprinklers directly to system
piping; for an example, refer to Figure
1. Flexible Hoses cannot be joined to-
gether to form longer hoses. Joining
Flexible Hoses together creates an as-
sembly with unknown performance
that has not been accounted for in
system calculations or safe product
performance.
Step 1. Review the Design Criteria
section that applies to the Approval
agency recognized by the authority
having jurisdiction, as well as Figure 3
that provides Installation Guidance.
Step 2. Determine the approximate
place where the sprinkler will be locat-
ed. The Support Bar is 700 mm long
and shall be mounted on the 600 mm
width of the ceiling grid. The sprinkler
should be located as close as possible
to the center of the distance between
ceiling grid t-bars.
Step 3. Slide the Reducer Bracket
onto the Support Bar. Loosely attach
the Reducer Bracket and the two Bar
Fixing Clamps on the Support Bar and
place the Bar Fixing Clamps such that
the Support Bar crosses the location
where the sprinkler will be located.
Step 4. Attach one end of the Flexible
Hose onto the sprinkler reducer. Ap-
plying the wrench to the Slip Nut, and
not to the Flexible Hose, tighten to a
maximum torque of 35 Nm.
Step 5. Attach the Inlet Nipple on to
the branch line. Ensure that the arrow
is in the appropriate direction of ow
to the sprinkler and to use pipe thread
sealant at the connection to the branch
line.
Attach one end of the Flexible Hose on
to the Inlet Nipple. Applying the wrench
to the Slip Nut, and not to the Flexible
Hose, tighten to a maximum torque of
35 Nm. Do not twist the Flexible Hose.
Step 6. Bend the Flexible Hose into a
curve(s) that locates the Sprinkler Re-
ducer at the other end of the Flexible
Hose in the area where the sprinkler
will be located. The tube arc should
not be twisted, and the arc should be
as large and smooth as possible.
NOTICE
For minimum bend criteria, refer to the
Design Criteria section that applies to
the Approval agency recognized by the
authority having jurisdiction.
A bend radius smaller than provid-
ed by the minimum bend criteria
may adversely effect the friction loss
specications stated by the approval
laboratory.
For assembly lengths greater than
1800 mm the Flexible Hose shall be
supported to the structure to ensure
that the maximum unsupported length
does not exceed 1800 mm. In these
cases, it is recommended that the
tube be secured to a xed mounting
point every 600 mm, in order to pro-
vide a more stable installation.
For installations per LPCB, all bends
greater than 45 shall be ftted with a
MRI55 Plastic Clip Minimum Radius
Indicator (Refer Figure 4).
Step 7. Insert the Sprinkler Reducer
into the Reducer Bracket. Locate the
Reducer Bracket and Sprinkler Re-
ducer where the sprinkler will be, and
loosely tighten the Buttery Bolt on the
Reducer Bracket.
Step 8. Attach the sprinkler to the
Sprinkler Reducer. Put a wrench on the
Sprinkler Reducer to counteract the
tightening torque and prevent the Flex-
ible Hose from twisting. Reference the
sprinkler manufacturers sprinkler data
sheet for appropriate sprinkler tighten-
ing torque, sprinkler wrench, and other
guidance.
Step 9. Verify that the Sprinkler Re-
ducer is seated in the Reducer Brack-
et. Precisely locate the sprinkler in
all three axes in accordance with the
sprinkler manufacturers data sheet.
Tighten the Buttery Bolts on the Bar
Fixing Clamps and the Reducer Brack-
et. The tightening torque for the Bar
Fixing Clamp fastener is 4,5 to 5,7 Nm,
and the tightening torque for the Re-
ducer Bracket fastener, is a minimum
of 2,3 Nm.
Step 10. After tightening all the But-
tery Bolts, verify that the sprinkler is
properly located in accordance with
the manufactures instructions. If not,
loosen the Buttery Bolts and readjust
as required.
Care and
Maintenance
The owner is responsible for the in-
spection, testing, and maintenance of
their re protection system and devic-
es in compliance with this document,
as well as with the applicable stan-
dards of the authorities having jurisdic-
tion. The installing contractor or prod-
uct manufacturer should be contacted
relative to any questions.
It is recommended that automatic sprin-
kler systems be inspected, tested, and
maintained by a qualied Inspection
Service in accordance with local re-
quirements and/or national codes.
NOTICE
Before closing a re protection system
control valve for inspection or mainte-
nance work on the re protection sys-
tem that it controls, permission to shut
down the effected re protection sys-
tem must rst be obtained from the
proper authorities and all personnel
who may be affected by this action
must be notied.
After placing a re protection system
in service, notify the proper authorities
and advise those responsible for moni-
toring proprietary and/or central sta-
tion alarms.
FLEXIBLE
HOSE
YN25
INDICATOR
RADIUS
MINIMUM
MRI55
TFP720
Page 9 of 10
Limited
Warranty
Products manufactured by Tyco Fire
Suppression & Building Products
(TFSBP) are warranted solely to the
original Buyer for ten (10) years against
defects in material and workmanship
when paid for and properly installed
and maintained under normal use and
service. This warranty will expire ten
(10) years from date of shipment by
TFSBP. No warranty is given for prod-
ucts or components manufactured by
companies not afliated by ownership
with TFSBP or for products and com-
ponents which have been subject to
misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modied or repaired in
accordance with the standards rec-
ognized by the Approval agency, as
well as the standards of any other Au-
thorities Having Jurisdiction. Materi-
als found by TFSBP to be defective
shall be either repaired or replaced, at
TFSBPs sole option. TFSBP neither
assumes, nor authorizes any person
to assume for it, any other obligation
in connection with the sale of prod-
ucts or parts of products. TFSBP shall
not be responsible for sprinkler system
design errors or inaccurate or incom-
plete information supplied by Buyer or
Buyers representatives.
In no event shall TFSBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFSBP
was informed about the possibility of
such damages, and in no event shall
TFSBPs liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, express
or implied, including warranties of mer-
chantability and tness for a particular
purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the full
product name. Contact your local dis-
tributor for availability.
Flexible Hose Assembly*
Specify: Model (from Table A)
FASTFLEX Flexible Hose Assembly
with (specied) length, and (50 or 90
mm) Bar Fixing Clamps, P/N (specify):
* The FASTFLEX Flexible Hose Assembly
includes the following items:
- Flexible Hose
- Inlet Nipple, ISO 7/1-R 1
- Straight Sprinkler Reducer, 1/2 NPT
- Reducer Bracket
- Bar Fixing Clamps
- Support Bar
Model YN25, Un-braided, 50 mm Clamps
(LPCB to 3700 mm, UL to 1800 mm, and APSAD
to 1500 mm; Refer to Table A for details)
700 . . . . . . . . . . . . . . . . . . . . . . . . P/N YN250700
1000 . . . . . . . . . . . . . . . . . . . . . . . P/N YN251000
1200 . . . . . . . . . . . . . . . . . . . . . . . P/N YN251200
1500 . . . . . . . . . . . . . . . . . . . . . . . P/N YN251500
1800 . . . . . . . . . . . . . . . . . . . . . . . P/N YN251800
2000 . . . . . . . . . . . . . . . . . . . . . . . P/N YN252000
2500 . . . . . . . . . . . . . . . . . . . . . . . P/N YN252500
2700 . . . . . . . . . . . . . . . . . . . . . . . P/N YN252700
3100. . . . . . . . . . . . . . . . . . . . . . . . P/N YN253100
3700 . . . . . . . . . . . . . . . . . . . . . . . P/N YN253700
Model YN25, Un-braided, 90 mm Clamps
(LPCB to 3700 mm and APSAD to 1500 mm; Re-
fer to Table A for details)
700 . . . . . . . . . . . . . . . . . . . . . . . P/N YN250700C
1000 . . . . . . . . . . . . . . . . . . . . . . P/N YN251000C
1200 . . . . . . . . . . . . . . . . . . . . . . P/N YN251200C
1500 . . . . . . . . . . . . . . . . . . . . . . P/N YN251500C
1800 . . . . . . . . . . . . . . . . . . . . . . P/N YN251800C
2000 . . . . . . . . . . . . . . . . . . . . . . P/N YN252000C
2500 . . . . . . . . . . . . . . . . . . . . . . P/N YN252500C
2700 . . . . . . . . . . . . . . . . . . . . . . P/N YN252700C
3100. . . . . . . . . . . . . . . . . . . . . . . P/N YN253100C
3700 . . . . . . . . . . . . . . . . . . . . . . P/N YN253700C
Model YB28, Braided, 50 mm Clamps
(VdS to 2500 mm, UL to 1800 mm, and APSAD to
1500 mm; Refer to Table A for details)
700 . . . . . . . . . . . . . . . . . . . . . . . . .P/N YB280700
1000 . . . . . . . . . . . . . . . . . . . . . . . .P/N YB281000
1200 . . . . . . . . . . . . . . . . . . . . . . . .P/N YB281200
1500 . . . . . . . . . . . . . . . . . . . . . . . .P/N YB281500
1800 . . . . . . . . . . . . . . . . . . . . . . . .P/N YB281800
2000 . . . . . . . . . . . . . . . . . . . . . . . P/N YB282000
2500 . . . . . . . . . . . . . . . . . . . . . . . P/N YB282500
Model YB28, Braided - FM, 50 mm Clamps
(FM to 2500 mm; Refer to Table A for details)
700 . . . . . . . . . . . . . . . . . . . . . . .P/N YB280700-F
1000 . . . . . . . . . . . . . . . . . . . . . . P/N YB281000-F
1200 . . . . . . . . . . . . . . . . . . . . . . P/N YB281200-F
1500 . . . . . . . . . . . . . . . . . . . . . . P/N YB281500-F
1800 . . . . . . . . . . . . . . . . . . . . . . P/N YB281800-F
2000 . . . . . . . . . . . . . . . . . . . . . .P/N YB282000-F
2500 . . . . . . . . . . . . . . . . . . . . . .P/N YB282500-F
Inlet Nipple
Specify: (25 mm or 28 mm) hose thread
FASTFLEX Inlet Nipple with (ISO 7/1-
R1 or ISO 7/1-R1-1/4) inlet thread con-
nection, P/N (specify):
25 mm Hose Thread
ISO 7/1-R 1 . . . . . . . . . . . . . P/N HOSENIP25
ISO 7/1-R 1-1/4 . . . . . . . . . P/N HOSENIP25R
28 mm Hose Thread
ISO 7/1-R 1 . . . . . . . . . . . . . P/N HOSENIP28
ISO 7/1-R 1-1/4 . . . . . . . . . P/N HOSENIP28R
Sprinkler Reducer
Specify: (Straight, 45 Degree, or 90
Degree) for (25 mm or 28 mm hose
threads) FASTFLEX Sprinkler Reduc-
er with (ISO 7/1-Rc 3/8, 1/2 inch NPT,
or 3/4 inch NPT) outlet thread connec-
tion, P/N (specify):
Straight
25 mm Hose Thread
ISO 7/1-Rc 3/8 . . . . . . . . . . . . . . P/N PBR120
1/2 inch NPT . . . . . . . . . . . . . . . P/N RBR120
3/4 inch NPT . . . . . . . . . . . . . . . P/N SBR120
28 mm Hose Thread
ISO 7/1-Rc 3/8 . . . . . . . . . . . . P/N PBR28120
1/2 inch NPT . . . . . . . . . . . . . P/N RBR28120
3/4 inch NPT . . . . . . . . . . . . . P/N SBR28120
45 Degree
25 mm Hose Thread
ISO 7/1-Rc 3/8 . . . . . . . . . . . . . . P/N PBAR45
1/2 inch NPT . . . . . . . . . . . . . . . P/N RBAR45
3/4 inch NPT . . . . . . . . . . . . . . . P/N SBAR45
28 mm Hose Thread
ISO 7/1-Rc 3/8 . . . . . . . . . . . . P/N PB28AR45
1/2 inch NPT . . . . . . . . . . . . . P/N RB28AR45
3/4 inch NPT . . . . . . . . . . . . . P/N SB28AR45
90 Degree
25 mm Hose Thread
ISO 7/1-Rc 3/8 . . . . . . . . . . . . . . P/N PBAR90
1/2 inch NPT . . . . . . . . . . . . . . . P/N RBAR90
3/4 inch NPT . . . . . . . . . . . . . . . P/N SBAR90
28 mm Hose Thread
ISO 7/1-Rc 3/8 . . . . . . . . . . . . P/N PB28AR90
1/2 inch NPT . . . . . . . . . . . . . P/N RB28AR90
3/4 inch NPT . . . . . . . . . . . . . P/N SB28AR90
Bar Fixing Clamps
Specify: FASTFLEX (50 mm or 90 mm)
Bar Fixing Clamps, P/N (specify):
50 mm . . . . . . . . . . . . . . . . . . . . . . . . P/N RBF58T
90 mm . . . . . . . . . . . . . . . . . . . . . . . . P/N RBF90T
Minimum Radius Indicator
Specify: MRI55 Plastic Clip Mini-
mum Radius Indicator of 55 mm to
be attached to Sprinkler Hose YN25,
P/N MRI55.
Note: For installations per LPCB, all
bends greater than 45 shall be tted
with a MRI55 Plastic Clip Minimum Ra-
dius Indicator. (Refer to Figure 4.)
2009 TYCO FIRE SUPPRESSION & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
TFP720
Page 10 of 10