0% found this document useful (0 votes)
203 views11 pages

DataKom 205 - USER

This document provides programming and installation instructions for an automatic mains failure unit. It includes 20 programmable parameters for configuring voltage and frequency limits, timers, and alarms. Instructions are provided for mounting the unit, making wiring connections to inputs like generator voltage and mains voltage, and outputs for controlling items like the generator contactor. Warnings are given about safety and ensuring proper wiring and protection.

Uploaded by

Khaleel Khan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
203 views11 pages

DataKom 205 - USER

This document provides programming and installation instructions for an automatic mains failure unit. It includes 20 programmable parameters for configuring voltage and frequency limits, timers, and alarms. Instructions are provided for mounting the unit, making wiring connections to inputs like generator voltage and mains voltage, and outputs for controlling items like the generator contactor. Warnings are given about safety and ensuring proper wiring and protection.

Uploaded by

Khaleel Khan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

DKG-205

AUTCMATIC MAINS
FAILUPE UNIT


TALE CF CCNTENTS

Sect|cn
1. PPCGPAMMING SUMMAPY
2. INSTALLATICN
2.1. Intrcduct|cn tc tbe Ccntrc| Pane|
2.2. Mcunt|ng tbe Un|t
2.3. W|r|ng tbe Un|t
2.4. Inuts and Cututs
2.5. D|g|ta| d|s|ay
2.6. Led d|s|ays
2.?. Per|cd|c ma|ntenance request d|s|ay
2.B. A|arms
2.9. Mcdes cI Cerat|cn
3. MAINTENANCE
4. TPCULESHCCTING
5. PPCGPAMMING
6. CALIPATICN
?. TECHNICAL SPECIFICATICNS
B. DECLAPATICN CF CCNFCPMITY
9. CCNNECTICN DIAGPAM














- 3 -


1. PPCGPAMMING SUMMAPY
To enter the program mode, press the PCM button. The disp|ay shovs
(Pr) vhen program mode is se|ected.

PGM
NUMEP
PPCGPAM CPTICN UNIT
FACT
SET
MIN.
VAL.
MAX.
VAL.
P01 Mains Vo|tage Lover Limit Vo|t 170 30 250
P02 Mains Vo|tage Upper Limit Vo|t 270 100 400
P03
Cenerator Vo|tage Lover
Limit
Vo|t
180 30 250
P04
Cenerator Vo|tage Upper
Limit
Vo|t
270 100 400
P05 Frequency Lover Limit Hz. 45 10 60
P06 Frequency Upper Limit Hz. 57 50 100
P07 Frequency De|ay Timer Sec. 3 0 15
P08 DC Supp|y Upper Limit Vo|ts 33.0 12.0 33.0
P09 Number oI Start Attempts - 3 1 6
P10 Wait beIore Start Timer Sec. 3 0 240
P11 Wait betveen Starts Timer Sec. 10 1 30
P12 Start Timer Sec. 10 2 15
P13 Stop Timer Sec. 0 0 60
P14 Mains Waiting Timer Min. 0.5 0 15
P15 Coo|ing Timer Min. 1.0 0 15
P16 Mains Contactor Timer Sec. 1 0 15
P17 Cenerator Contactor Timer Sec. 4 0 15
P18 Pe|ay ConIiguration - 0 0 7
P19
Maintenance Period (engine
hours)
hours
0 0 750
P20 Maintenance Period (duration) months 0 0 15

- 4 -

2. INSTALLATICN
2.1 Intrcduct|cn tc tbe Ccntrc| Pane|
The contro| pane| is designed to provide user Iriend|iness Ior both the
insta||er and the user. Programming is usua||y unnecessary, as the Iactory
settings have been careIu||y se|ected to Iit most app|ications. Hovever
programmab|e parameters a||ov the comp|ete contro| over the generating
set. Programmed parameters are stored in a Non Vo|ati|e Memory and
thus a|| inIormation is retained even in the event oI comp|ete |oss oI
pover.

2.2 Mcunt|ng tbe Un|t
The unit is designed Ior pane| mounting. The user shou|d not be ab|e to
access parts oI the unit other than the Iront pane|.
Mount the unit on a I|at, vertica| surIace. The unit Iits into a standard
pane| meter opening oI 140x68 mi||imeters. BeIore mounting, remove the
stee| spring Irom the unit, and then pass the unit through the mounting
opening. The unit vi|| be maintained in its position by the stee| spring.

2.3 W|r|ng tbe Un|t
WAPNING: THE UNIT IS NCT FUSED.
Use externa| Iuses Icr
Ma|ns bases: P-S-T
Generatcr base: L1-L2-L3
attery cs|t|ve: AT().
Insta|| tbe Iuses as near|y as css|b|e tc
tbe un|t |n a |ace eas||y access|b|e Icr tbe user.
Tbe Iuse rat|ng sbcu|d be 6 Ams.
WAPNING: ELECTPICITY CAN KILL
ALWAYS d|sccnnect tbe cwer EFCPE
ccnnect|ng tbe un|t.




- 5 -


1) ALWAYS remove the p|ug connectors vhen
inserting vires vith a screvdriver.
2) ALWAYS reIer to the Nationa| Wiring Pegu|ations
vhen conducting insta||ation.
3) An appropriate and readi|y accessib|e set oI
disconnection devices (e.g. automatic Iuses) MUST
be provided as part oI the insta||ation.
4) The disconnection device must NOT be Iitted in a
I|exib|e cord.
5) The bui|ding mains supp|y MUST incorporate
appropriate short-circuit backup protection (e.g. a
Iuse or circuit breaker) oI High Breaking Capacity
(HBC, at |east 1500A).
6) Use cab|es oI adequate current carrying capacity (at
|east 0.75mm
2
) and temperature range.



2.4 Inuts and Cututs
SEPIAL DATA CCNNECTICN: This connection is used to transIer data to
the PC via the seria| adapter.
1- GENEPATCP CCNTACTCP: This output provides energy to the
generator contactor. lI the generator phase vo|tage is outside oI the
programmed |imits, the generator contactor vi|| be de-energized. ln order
to provide extra security, norma||y c|osed contact oI the mains contactor
shou|d be seria||y connected to this output. Pe|ay contact rating is
16A/250V-AC
2/3/4- L1/L2/L3: Connect the generator phases to these inputs. The
generator phase vo|tage upper and |over |imits are programmab|e.
5- GENEPATCP NEUTPAL: Neutra| termina| Ior the generator phases.
6- MAINS NEUTPAL: Neutra| termina| Ior the mains phases.
?/B/9- T-S-P: Connect the mains phases to these inputs. The mains
vo|tages upper and |over |imits are programmab|e.
10- MAINS CCNTACTCP: This output provides energy to the mains
contactor. lI the vo|tage oI at |east one oI the mains vo|tages is outside oI
the programmed |imits, the mains contactor vi|| be de-energized. ln order
to provide extra security, norma||y c|osed contact oI the generator
contactor shou|d be seria||y connected to this output. Pe|ay contact rating
is 16A/250V-AC
11- AUXILIAPY PELAY CUTPUT: This re|ay Iu|Ii||s 4 diIIerent Iunctions
Io||oving programming. Pe|ay contact rating is 10A/28V-DC.
1) ALAPM PELAY. lI an a|arm occurs, the re|ay vi|| be activated. lt vi||

- 6 -

be deactivated vhen the ALAPM MUTE key is pressed.
2) STOP PELAY. The re|ay vi|| operate during programmed period in order
to stop the engine (Activate to Stop)
3) PPEHEAT PELAY. The re|ay vi|| operate the programmed de|ay beIore
the cranking oI the engine. lt vi|| be deactivated during cranking and
reactivated during the rest period betveen cranks. lt vi|| be deactivated
vhen the engine runs.
4) CHOKE PELAY. The re|ay vi|| operate the programmed de|ay beIore
the cranking oI the engine. lt vi|| be deactivated vhen the engine runs.
12- CPANK CUTPUT: Engine crank output. Pe|ay automatica||y turns oII
vhen the a|ternator vo|tage reaches 100 vo|ts or the a|ternator Irequency
reaches 10Hz.
Pe|ay contact rating is 10A/28V-DC.
13- FUEL CUTPUT: This output is used on engines equipped vith a Iue|
so|enoid. The unit activates this output beIore starting the engine and
deactivates it to stop it. By programming, this re|ay can a|so contro|
'Act|vate tc Stc type oI engines.
Pe|ay contact rating is 10A/28V-DC.
14- CHAPGE INPUT: Connect the charging a|ternators |amp output to
this termina|. lI the charging a|ternator Iai|s vhen the engine is running,
the re|ated a|arm indicator vi|| turn on and the a|arm output vi|| be
activated. This a|arm vi|| not prevent the norma| operation oI the
generating set.
15/16- AT() / AT(-): The positive () and negative (-) termina|s oI
the DC Supp|y sha|| be connected to these termina|s. Be careIu| Ior the
po|arization, in case oI po|arity error the unit vi|| not operate. The unit
operates on both 12V and 24V battery systems.
1?- PPCGPAM LCCK INPUT: This input is used to prevent unvanted
modiIication to programmed va|ues. lI this input is |eIt open, program
va|ues can be modiIied via the Iront pane| buttons, but iI this input is
connected to DC Supp|y (-) it vi|| not possib|e to change the program
va|ues.
1B- LCW CCCLANT LEVEL SWITCH: Connect the coo|ing radiator |iquid
|eve| svitch to this input. This svitch sha|| be negative c|osing in case oI
|ov |iquid |eve|. This input has de|ayed samp|ing Ieature to prevent Ia|se
detection.
19- SPAPE-3 ALAPM INPUT: Connect the spare a|arm svitch to this
input. The svitch sha|| be negative c|osing type.
20- SPAPE-2 ALAPM INPUT: Connect the spare a|arm svitch to this
input. The svitch sha|| be negative c|osing type.
21- SPAPE-1 ALAPM INPUT: Connect the spare a|arm svitch to this
input. The svitch sha|| be negative c|osing type.


- 7 -

22- HIGH TEMPEPATUPE SWITCH: Connect the high temperature svitch
to this input. This svitch sha|| be negative c|osing svitch type.
23- LCW CIL PPESSUPE SWITCH: Connect the |ov oi| pressure svitch
to this input. The svitch shou|d be negative c|osing in case oI |oss oI oi|
pressure. This input must be proper|y connected Ior the correct operation
oI the unit. lI oi| pressure is provided, the generator vi|| not start and the
oi| pressure a|arm indicator vi|| I|ash. Hovever, iI the oi| pressure is
removed, the unit vi|| resume norma| operation.
24- EMEPGENCY STCP INPUT: Emergency stop button is connected to
this input. The connection sha|| be made in order to give DC Supp|y (-) to
the input vhen the button is pushed. Pushing the STOP button on the
unit's Iront pane| makes the same eIIect as the EMEPCENCY STOP input.
The generator vi|| not operate vhen the emergency stop signa| is present.
When the signa| is removed, the unit vi|| resume norma| operation. This
input can a|so be used to prevent externa||y the automatic operation oI
the generator. (Ior ex. by time vatch).
25- CVEPLCAD SWITCH: Connect the over|oad re|ay output to this input.
The re|ay vi|| be oI negative c|osing type in case oI over|oad. This a|arm
vi|| cause the generator to re|ease the |oad, but the engine runs unti| the
end oI the coo|ing period.
26- ALTEPNATCP HIGH TEMPEPATUPE SWITCH: Connect the high
temperature svitch p|aced betveen vindings oI the a|ternator to this
input. WAPNING: This svitch sha|| be norma||y c|osed, and open in case
oI excess oI heat. lI this input is not used, connect it to DC Supp|y
negative termina|, e|se an a|arm vi|| be given continuous|y. This a|arm vi||
cause the generator to re|ease the |oad, but the engine runs unti| the end
oI the coo|ing period.
2?- CIL HIGH TEMPEPATUPE SWITCH: Connect the oi| high temperature
svitch to this input. This svitch sha|| be negative c|osing svitch type.















- 8 -

2.5 D|g|ta| D|s|ay
This disp|ay shovs.
- (P) phase vo|tage, vhen mains are on
- A|ternator Irequency, iI the generator is on
- Program va|ues in program mode

Be|ov va|ues can be read in sequence by pushing the MENU key in AUTO
or TEST modes.
- (P) phase vo|tage
- (S) phase vo|tage
- (T) phase vo|tage
- (L1) generator phase vo|tage
- (L2) generator phase vo|tage
- (L3) generator phase vo|tage
- (L1) generator phase Irequency (engine PPM)
- DC Supp|y vo|tage.

2.6 Led D|s|ays
MAINS CN: (green) The LED vi|| turn on vhen a|| 3 mains phase vo|tages
are vithin the |imits.
MAINS CFF: (red) The LED vi|| turn on vhen at |east one oI the mains
phase vo|tages are outside |imits.
GENEPATCP: (ye||ov) The LED vi|| turn on vhen a|| 3 generator phase
vo|tages are vithin the programmed |imits.
LCAD GENEPATCP: (ye||ov) it turns on vhen the generator contactor is
activated.
LCAD MAINS: (green) it turns on vhen the mains contactor is activated.
FUEL: (ye||ov) it turns on vhen the (activate beIore start) Iue| so|enoid is
activated. This LED is operative even iI the Iue| output is in activate to
stop mode.
STAPT: (ye||ov) it turns on vhen the start re|ay is activated.
WAITING/CCCLING: (ye||ov) it turns on during vait periods beIore and
betveen start attempts, mains vaiting period, coo|ing period and
contactor period.
PEPICDIC MAINTENANCE PEOUEST: (red) lt I|ashes vhen the
programmed maintenance period or the programmed engine-hours is
e|apsed.
TEST/AUTC/CFF/PGM/MAN. lt turns on vhen the re|ated operation mode
is se|ected. One oI these LEDs is a|vays on and indicates vhich operation
mode is se|ected.


- 9 -

2.? Per|cd|c Ma|ntenance Pequest D|s|ay
This |ed is designed to he|p the periodic maintenance oI the generator to
be made consistent|y.
The periodic maintenance is basica||y carried out aIter a given engine
hours (Ior examp|e 200 hours), but even iI this amount oI engine hours is
not Iu|Ii||ed, it is perIormed aIter a given time |imit (Ior examp|e 12
months).
The DKC-205 has both programmab|e engine hours and maintenance time
|imit. The engine hours is programmab|e betveen 0 and 750 hours at 50-
hour steps, the time |imit is programmab|e betveen 0 and 15 months. lI
any oI the programmed va|ue is zero, this means that the parameter vi||
not be used. For examp|e P19=200 and P20=0 means that DKC-205
vi|| request maintenance every 200 engine hours, but there vi|| be no
time |imit.
The remaining engine hours and the remaining time |imit are kept stored in
a non-vo|ati|e memory and are not modiIied by pover supp|y Iai|ures.
When the engine hours or the time |imit is over, the Periodic Maintenance
Pequest |ed (red) vi|| start to I|ash. To turn oII the |ed, the STOP key
shou|d be he|d pressed Ior 10 seconds. ln this case the digita| disp|ay vi||
shov SEP.

2.B A|arms
A|arms indicate an abnorma| situation in the generating set and most oI
them cause the engine to stop immediate|y.
lI an a|arm occurs, the re|ated LED vi|| turn on and iI the a|arm re|ay
option is se|ected, the a|arm re|ay vi|| be activated. lI the ALAPM MUTE
key is pressed, the a|arm re|ay vi|| be deactivated.
Except the emergency stop, a|arm LEDs vi|| stay on and disab|e the
operation oI the generating set even iI the a|arm source is removed. ln
order to reset the a|arm condition, Iirst choose OFF mode then resume to
the previous mode oI operation.

CHAPGE ALAPM: lt turns on in case oI a charging a|ternator Iai|ure. This
a|arm vi|| not cause the engine to stop.
CVEPLCAD ALAPM: lt turns on iI a signa| comes Irom the over|oad re|ay
output. This a|arm vi|| cause the generator to re|ease the |oad, but the
engine runs unti| the end oI the coo|ing period.





- 10 -

ALTEPNATCP HIGH TEMPEPATUPE ALAPM: lt turns on iI a signa| comes
Irom the high temperature svitch oI the a|ternator. WAPNING: This
svitch sha|| be norma||y c|osed, and open in case oI excess oI heat. lI this
input is not used, connect it to DC Supp|y negative termina|, e|se an a|arm
vi|| be given continuous|y. This a|arm vi|| cause the generator to re|ease
the |oad, but the engine runs unti| the end oI the coo|ing period.
HIGH TEMPEPATUPE ALAPM: lt is on vhen a signa| comes Irom the high
temperature input.
CIL ALAPM: lt is on vhen a signa| comes Irom the oi| pressure input. This
a|arm vi|| be contro||ed 4 seconds aIter the engine is running. lI oi|
pressure is provided vhen the unit attempts to start the engine, the oi|
a|arm indicator vi|| I|ash and the unit vi|| vait unti| oi| pressure
disappears.
LCW CCCLANT LEVEL ALAPM: lt is on vhen a signa| comes Irom the
coo|ing radiator vater |eve| svitch. This input has de|ayed samp|ing
Ieature to prevent Ia|se detection.
CIL HIGH TEMPEPATUPE ALAPM: lt is on vhen a signa| comes Irom the
oi| high temperature svitch.
FPEOUENCY ALAPM: lt is on vhen the a|ternator Irequency is out oI the
programmed |imits Ior a |onger period than the programmed timer.
A|ternator Irequency vi|| be contro||ed 4 seconds aIter the generator
contactor is on.
VCLTAGE ALAPM: lt is on vhen at |east one oI the a|ternator phase
vo|tages is out oI the programmed |imits. A|ternator vo|tage vi|| be
contro||ed 4 seconds aIter the generator contactor is on.
FAIL TC STAPT: lt is on iI the engine cannot start to run aIter the
programmed number oI start attempts. This a|arm vi|| be erased vhen the
mains are on in order to keep the engine ready Ior the next mains Iai|ure.
EMEPGENCY STCP ALAPM: lt arises iI emergency stop button (or Iront
pane| STOP key) has been pushed. This a|arm is not |atched. The a|arm
condition disappears vhen the signa| is removed. This input is a|so used
externa||y to prevent the operation oI the generator (Ior ex. by a timer).
DC SUPPLY ALAPM: lt is on vhen DC Supp|y vo|tage is above the
programmed |imit. lt arises at the end oI 2 seconds de|ay period. lt does
not occur iI DC Supp|y vo|tage goes back be|ov the |imit beIore the end
oI the de|ay period. This protection is particu|ar|y designed against charge
a|ternator Iai|ures.
SPAPE-1 ALAPM: lt turns on vhen a signa| comes Irom the spare-1 a|arm
input.
SPAPE-2 ALAPM: lt turns on vhen a signa| comes Irom the spare-2 a|arm
input
SPAPE-3 ALAPM: lt turns on vhen a signa| comes Irom the spare-3 a|arm
input. This a|arm vi|| not stop the engine.

- 11 -

2.9 Mcdes cI Cerat|cn
The modes oI operation are se|ected by pushing the Iront pane| keys. lI
the mode is changed vhi|e the engine is running, it vi|| be stopped. Do
not change the operation mode vhi|e the generator is in operation.

CFF: ln this mode, the mains contactor vi|| be energized iI mains phase
vo|tages are vithin the programmed |imits. The engine vi|| be stopped.
MANUAL: lt is used to start and stop the generator manua||y. lI the
manua| mode is se|ected, the Iue| re|ay vi|| be activated and the generator
vi|| be ready to be started.
STAPT: lt is used to manua||y start the generator un|imited times.
ln order to start, it is needed not to have the oi| pressure. When
the generator phase vo|tages are present or the generator
Irequency goes over 10 Hz, starting vi|| be automatica||y disab|ed
even iI the button is pressed.
STCP: lt is used to manua||y deactivate the Iue| so|enoid as |ong
as desired. When the stop button is pushed, the generator
contactor vi|| a|so be deactivated.
MAINS/GENEPATCP: lt is used to manua||y activate the mains
and the generator contactor. lI it is pressed once, the generator
contactor vi|| be activated, iI it is pressed once the mains
contactor vi|| be activated.
AUTC: lt is used Ior generator and mains automatic transIer. lI at |east
one oI the mains phase vo|tages is outside |imits, the mains contactor vi||
be deactivated.
The diese| vi|| be started Ior programmed times aIter the vait period.
When the engine runs, the crank re|ay vi|| be immediate|y deactivated.
AIter the a|ternator phase vo|tages are vithin |imits, the unit vi|| vait Ior
the generator contactor period and the generator contactor vi|| be
energized.
When a|| the mains phase vo|tages are vithin the |imits, the engine vi||
continue to run Ior the mains vaiting period. At the end oI this period the
generator contactor is deactivated and the mains contactor vi|| be
energized. lI a coo|ing period is given, the generator vi|| continue to run
during coo|ing period. At the end oI the period, the Iue| so|enoid vi|| be
de-energized and the diese| vi|| stop. The unit vi|| be ready Ior the next
mains Iai|ure.
TEST: lt is used to test the generator vhen the mains are on, or keep the
generator vaiting in the emergency backup mode. The operation oI the
generator is simi|ar to the AUTO mode, but the mains contactor vi|| not
be deactivated iI the mains are not oII. lI the mains are oII, mains
contactor vi|| be deactivated and the generator contactor vi|| be

- 12 -

activated. When the mains are on again, a changeover to the mains vi||
be made, but the engine is kept running. ln order to stop the engine, push
the OFF button.
PPCGPAM: lt is used to program the timers, operationa| |imits and the
conIiguration.


3. MAINTENANCE
WAPNING: DC NCT CPEN THE UNIT
Tbere are NC serv|ceab|e arts |ns|de tbe un|t.
Wipe the unit, iI necessary vith a soIt damp c|oth. Do not use chemica|
agents.


4. TPCULESHCCTING

Tbe genset starts tc cerate wb||e AC ma|ns are CK:
AC mains vo|tages may be outside programmed |imits. Pead AC vo|tages
by pressing the MENU button. Upper and |over |imits oI the mains
vo|tages may be too tight. Cet in the PPOCPAM mode and check Ior
the AC vo|tage upper and |over |imits. lI necessary, viden the |imits.

Tbe genset ccnt|nues tc cerate aIter AC ma|ns are reestab||sbed:
Widen the AC vo|tage |imits. The hysteresis va|ue Ior the AC vo|tages is
10 vo|ts. When the AC mains Iai|, the |over |imit is raised and the upper
|imit is reduced by the hysteresis va|ue to prevent a nev |oad transIer
aIter the |oad is transIerred to the mains.

AC vc|tages d|s|ayed cn tbe un|t are nct ccrrect:
The error margin oI the unit is /- 5 vo|ts.
lI there are Iau|ty measurements on|y vhen the engine is running, there
may be a Iau|ty charging a|ternator or vo|tage regu|ator on the engine.
Disconnect the charging a|ternator connection and check iI the error is
removed.




- 13 -

Wben tbe AC ma|ns Ia||s tbe un|t energ|zes tbe Iue| sc|enc|d, but dces nct
start, a|sc CIL PPESSUPE ALAPM |ed I|asbes:
The unit is not supp|ied vith battery (-) vo|tage at the oi| pressure input.
-Oi| pressure svitch not connected.
-Oi| pressure svitch connection vire cut.
-Oi| pressure svitch Iau|ty.
-Oi| pressure svitch c|oses too |ate|y. lI oi| pressure Ia||s, the unit vi||
start. Optiona||y oi| pressure svitch may be rep|aced.

Tbe eng|ne dces nct run aIter tbe I|rst start attemt, tben tbe un|t dces
nct start aga|n and tbe CIL PPESSUPE ALAPM |ed I|asbes:
-The oi| pressure svitch c|oses very |ate|y. As the unit senses an oi|
pressure, it does not start. When oi| pressure Ia||s the unit vi|| start.
Optiona||y the oi| pressure svitch may be rep|aced.

Wben tbe AC ma|ns Ia||s, tbe eng|ne starts tc run but tbe un|t g|ves FAIL
TC STAPT a|arm and tben tbe eng|ne stcs:
-The generator phase vo|tage is not connected to the unit. Measure the
AC vo|tage betveen termina|s (L1) and (Cenerator Neutra|) at the rear oI
the unit vhi|e engine is running. The Iuse protecting the generator phase
may be Iai|ed. A misconnection may be occurred. lI everything is OK, turn
a|| the Iuses oII, and then turn a|| the Iuses on, starting Irom the DC
supp|y Iuse. Then test the unit again.

Tbe un|t |s |ate tc remcve eng|ne crank|ng:
-The a|ternator vo|tage rises |ate|y. A|so the generator remanant vo|tage is
be|ov 10 vo|ts. The unit removes starting vith the generator Irequency,
and needs at |east 10 vo|ts to measure the Irequency. lI this situation is
to be avoided, the on|y so|ution is to add an auxi|iary re|ay. The coi| oI the
re|ay vi|| be betveen BATTEPY (-) and charging a|ternator LAMP termina|.
The norma||y c|osed contact oI the re|ay vi|| be connected seria||y to the
unit's STAPT output. So the starting vi|| a|so be removed vhen the
CHAPCE LAMP turns oII.

Tbe un|t |s |ncerat|ve:
Measure the DC-supp|y vo|tage betveen () and (-) termina|s at the
rear oI the unit. lI OK, turn a|| the Iuses oII, then turn a|| the Iuses on,
starting Irom the DC supp|y Iuse. Then try the unit again.



- 14 -




5. PPCGPAMMING
The programming mode is used to program the timers, operationa| |imits
and the conIiguration oI the unit.
To enter the program mode, press the PCM button. The disp|ay shovs
(Pr) vhen program mode is se|ected. When the MENU key is pressed the
program number vi|| be disp|ayed, vhen it is re|eased the program va|ue
vi|| be shovn. ln this vay a|| program parameters are accessed and the
va|ues can be increased or decreased by using () and () keys.
Programmed va|ues are stored in a Non Vo|ati|e Memory, vhich is not
aIIected by energy Iai|ures. Tc ex|t rcgramm|ng, press the OFF button.
P01=MAINS VCLTAGE LCWEP LIMIT: lI one oI the mains phases goes
under this |imit, it means that the mains are oII and it starts the transIer
to the generator in automatic and test modes.
P02=MAINS VCLTAGE UPPEP LIMIT: lI one oI the mains phases goes
over this |imit, it means that the mains are oII and it starts the transIer to
the generator in automatic and test modes.
P03=GENEPATCP VCLTAGE LCWEP LIMIT: lI the generator phase
vo|tage goes under this |imit vhen Ieeding the |oad, this vi|| mean a
generator vo|tage Iai|ure and the engine vi|| stop.
P04=GENEPATCP VCLTAGE UPPEP LIMIT: lI the generator phase
vo|tage goes over this |imit vhen Ieeding the |oad, this vi|| mean a
generator vo|tage Iai|ure and the engine vi|| stop.
P05=FPEOUENCY LCWEP LIMIT: lI the generator Irequency goes under
this va|ue, it causes an a|arm aIter the Irequency de|ay timer.
P06=FPEOUENCY UPPEP LIMIT: lI the generator Irequency goes over
this va|ue, it causes an a|arm aIter the Irequency de|ay timer.
P0?=FPEOUENCY DELAY: This is the period betveen the Irequency goes
out oI the |imits and an a|arm occurs
P0B=DC SUPPLY UPPEP LIMIT: lI DC Supp|y vo|tage exceeds this |imit,
it vi|| cause DC Supp|y a|arm aIter the 2 second de|ay and the diese| vi||
stop. This a|arm is particu|ar|y designed to prevent Iai|ure oI the unit in
case oI charge a|ternator Iai|ure.
P09=NUMEP CF STAPTS: Maximum number oI start attempts.
P10=WAIT EFCPE STAPT TIMEP: Waiting period betveen the Iue| on
and start command.
P11=WAIT TIMEP ETWEEN STAPTS: Waiting period betveen tvo start

- 15 -

attempts.
P12=STAPT TIMEP: Start period. Start vi|| be automatica||y deactivated
iI the generator starts running beIore the timer.
P13=STCP TIMEP: Stop so|enoid activation timer. Enter 0 Ior an
activate to start type oI engine.
P14=MAINS WAITING TIMEP: This is the time betveen the mains
vo|tages entered vithin the |imits and the generator contactor is
deactivated.
P15=CCCLING TIMEP: This is the period that the generator runs Ior
coo|ing purpose aIter the |oad is transIerred to mains.
P16=MAINS CCNTACTCP TIMEP: This is the period aIter the generator
contactor has been deactivated and beIore the mains contactor has been
activated.
P1?=GENEPATCP CCNTACTCP TIMEP: This is the period aIter the
generator phases are vithin the |imits and beIore the generator contactor
has been activated.
P1B=PELAY CCNFIGUPATICN: FUEL and AUXlLlAPY re|ay
conIiguration.

P1B VAL AUX PELAY FUNCTICN FUEL PELAY FUNCTICN
00 A|arm Activate beIore Start
01 Fue| (Activate to Stop) Activate beIore Start
02 Preheat Activate beIore Start
03 Choke Activate beIore Start
04 A|arm Activate to Stop
05 Fue| (Activate to Stop) Activate to Stop
06 Preheat Activate to Stop
07 Choke Activate to Stop

P19 = MAINTENANCE PEPICD (ENGINE HCUPS): This is the engine
periodic mainteance |iIe as engine-hours
P20 = MAINTENANCE PEPICD (DUPATICN): This periodic maintenance
|imit (as months) must be observed even iI the engine hours |imit is not
exceeded.




- 16 -





6. CALIPATICN
To enter the ca|ibration mode, ho|d pressed the OFF button, then press
PCM button. The rightmost decima| point oI the vo|tage disp|ay vi|| turn
on. For Io||oving operations it is necessary to disp|ay the proper
parameter by pressing the MENU key, and modiIy it by pressing using ()
and () keys. For more detai|ed exp|anation p|ease reIer to programming
chapter oI the user's manua|.

P22: MAINS AND GENEPATCP VCLTAGE DISPLAY CALIPATICN:
Connect mains phase vo|tages. Measure the vo|tage vith a digita|
mu|timeter. (Betveen phase and neutra|) Adjust P22 parameter unti| the
unit disp|ays the same vo|tage va|ue as the mu|timeter. Check other phase
vo|tages by pressing the MENU button in AUTO mode. (Max
error=2vo|ts)
P23: DC SUPPLY VCLTAGE DISPLAY CALIPATICN: Measure the DC
Supp|y vo|tage vith a digita| mu|timeter. Adjust P23 parameter unti| the
unit disp|ays the same vo|tage va|ue as the mu|timeter. (Max
error=0.2vo|ts)





















- 17 -




?. TECHNICAL SPECIFICATICNS

Ste Ccntrc| : 8 bit microprocessor.
Ma|ns Vc|tage: 277VAC (Ph-N)
Ma|ns Frequency: 50/60Hz.
Pcwer System Tye: TN or TT.
A|ternatcr Vc|tage: 277VAC (Ph-N)
A|ternatcr Frequency: 0-100Hz.
Measurement Categcry: CAT ll
DC Su|y Pange: 9.0 to 33.0 V-DC.
4.0 to 33.0 V-DC vhi|e cranking
Current Ccnsumt|cn: 100 mA-DC typica| (AUTO, mains OK,24vo|ts)
250 mA-DC max. (Pe|ay outputs open)
Tcta| DC Current Cutut Pat|ng: 10A-DC.
Tcta| AC Current Cutut Pat|ng: 10A-AC.
Current Pat|ng Icr eacb Cutut Term|na|: 10APMS.
Data Pcrt: Seria|, |ogic |eve|s (optiona| PS-232 |eve|s).
Ccmuter Hcst Prcgram: MS-Windovs
Cerat|ng Temerature Pange: -20C (-4F) to 70 C (158F).
Stcrage Temerature Pange: -30C (-22F) to 80 C (176F).
Max|mum Hum|d|ty: 95% non-condensing.
D|mens|cns: 72 x 144 x 70mm (WxHxD)
Mcunt|ng Cen|ng D|mens|cns: 140 x 68mm minimum.
We|gbt: 300 g (approx.)
Accuracy:
Phase vo|tages. 2% 1 vo|t
Battery Vo|tage. 2% 0.2 vo|ts
Cenerator Irequency. /- 0.5 Hz
Case Mater|a|: F|ame Petardant High Temperature ABS (UL94-V0, 110C)


WAPNING: Stresses exceed|ng abcve ||m|ts may
resu|t tc a degradat|cn cI tbe un|t's rctect|cn
|eve|.



- 18 -




B. DECLAPATICN CF CCNFCPMITY

The unit conIorms to the EU directives
-73/23/EEC and 93/68/EEC (|ov vo|tage)
-89/336/EEC, 92/31/EEC and 93/68/EEC (e|ectro-magnetic
compatibi|ity)
Norms oI reIerence.
EN 61010 (saIety requirements)
EN 50081-2 (EMC requirements)
EN 50082-2 (EMC requirements)

The CE mark indicates that this product comp|ies vith the European
requirements Ior saIety, hea|th environmenta| and customer protection.


























- 19 -



9. CCNNECTICN DIAGPAM


- 20 -







- 21 -
































DATAKCM E|ectrcn|cs L|m|ted
Te| . 90-216-466 84 60
Fax . 90-216-364 65 65
e-mai| . [email protected]
vebsite. vvv.datakom.com.tr

DATAKOM reserves the right oI making modiIications to the unit vithout prior notice.