R410a Guide
R410a Guide
R410A
The
Natural
Choice
Contents >>
2 The facts on R410A refrigerant
4 A brief history of refrigerant
6 R410A in detail
8 Ensure correct system evacuation
11 When using copper pipework
12 The right tools
15 Summary
>>
The
facts
on R410A refrigerant
With more manufacturers introducing systems that use
R410A refrigerant, we’ve produced this booklet to explain
the hype that currently surrounds R410A and to present you
with the facts.
Handled correctly, many installers have already realised that R410A refrigerant
has some excellent benefits to offer. However, it’s being portrayed within
the industry as potentially dangerous to use or, it’s being labelled as the only
efficient refrigerant that’s available - which simply isn’t true.
The same is true of direct expansion systems, with the need to focus on
efficiency as a whole, not simply the type of refrigerant. How the refrigerant
is used is of paramount importance and good system installation is crucial.
The skills required today, are no different to those that
have always been required and although the
equipment and subsequent numbers may
differ, the need for good practice remains
the same.
Page 2
R410A refrigerant
has some excellent
benefits to offer
Page 3
A brief
histor y
Since 1985 it’s been well documented that
the ozone layer surrounding the earth
has been diminishing. Scientific evidence
suggests man-made chemicals are
responsible for creating the hole in the
ozone layer and that they’re likely to add
to global ozone depletion.
Page 4
of refr iger ant
R22 is a Hydrochlorofluorocarbon (HCFC)
As a result of legislation R22 refrigerant (an HCFC), has been virtually phased out
in all new equipment. The air conditioning industry now uses (HFC) as it has no
chlorine content and zero Ozone Depletion Potential (ODP).
Page 5
R410A in detail
evaporation process.
1
3
Enthalpy
Superheat [kJ/kg]
Page 6
R410A has zero Ozone Depletion Potential (ODP)
With the relatively high density and high efficiency of R410A , it is possible to reduce
the size of system components such as condensers, compressors, evaporators and
piping, etc. As operating pressures are higher compared to that of R22 and R407c,
all system components must all be designed for suitability with R410A.
R22 R410A
Suction 60psi (4 bar) 90 to 105 psi (6 to 7 bar)
Discharge 260psi (17 bar) 350 to 400 psi (23 to 28 bar)
When installing equipment using R410A refrigerant, there are a number of standards
that must be met:
Page 7
Ensure correct
system evacuation
To ensure problem-free operation of any air-conditioning system, it is
crucial to carry out thorough evacuation of the system. During the
evacuation any moisture is removed from all of the system components
and the pipework.
> Any non-condensible product left in the system can cause the
pressure in the condenser to increase and in turn, the
compression temperature to rise.
> The polyester oils used in the R410A refrigeration systems are
hydroscopic, which means that they absorb moisture from the air.
To prevent chemical reactions in the system, any moisture must
be removed at all costs.
> Oxygen (air) reacts with the refrigeration unit oil and can lead
to faults such as compressor failure.
Page 8
Essential tips for good evacuation
Before evacuating a system, it is essential to check for any potential leaks. Such leaks
may be discovered at brazed or flared joints. Evacuation can only start once the system
has been properly pressure tested and found to be completely leakproof.
Leak Testing
in 3 easy steps
Step 1 3.0 bar (N2) - Test for a minimum of 3 minutes
Step 3 33.3 bar (N2) - Test for a minimum of 24 hours (if using R410A)
Page 9
Tr iple evacuation
in 6 easy steps
Step 1 Evacuate the system to 10 ‘Torr’ from both service valves.
To measure the vacuum a ‘Torr gauge’ must be used at
all times - do not use a system manifold gauge
Step 5 Evacuate to the lowest pressure that the pump will achieve
(2 ‘Torr’ for 1 hour minimum)
Step 6 The rise test must then be carried out for a minimum of 30 minutes
Page 10
When using
copper
pipework
> Use only copper pipes with the correct wall thickness -
please refer to your usual copper pipe supplier for detail
> Make sure you cut the copper pipe with a proper pipe cutter only
> Make sure that no swarf or other impurities get into the piping
> When brazing make sure that Nitrogen (OFN) is used at all times
Page 11
The right tools
The right tools are required in to enable the
refrigeration system to be properly
evacuated and dried.
These include:
> R410A Manifold Gauges
> Flaring Tool
> Torque Wrench
> Vacuum Pump
> Refrigerant Weighing Scales
Page 12
R410A Refrigerant Manifold
A solid manifold gauge specifically used
for R410A.
Torr Gauge
A Torr gauge to be used to provide an
accurate evacuation level required.
Vacuum Pump
A Vacuum pump of sufficient quality and
working order to be used to pull the
correct vacuum to negate any moisture
being present in the system (pump oil
needs to be regularly changed).
Page 13
Flaring Tool
A suitable Flaring tool to be used so as
not to compromise the integrity of the
copper when flared.
Torque Spanners
Torque spanners must be used at all
times to tighten flares in accordance with
manufacturers guidelines.
Page 14
Summar y >>
To get the best from R410A
> Use the correct tools
> Adhering to BS EN378
> Strength test to 1.3 x Ps (43 bar)
> Leak test to 1.0 x Ps (33 bar)
> Observe regulations (Health & Safety at work, pressure equipment etc.)
> Use correct copper pipework with appropriate wall thickness
> Follow good working practice at all times (Nitrogen brazing, proper evacuation, etc.)
If you follow the guidelines contained within and carry out good refrigeration
practices at all times, then working with R410A will be no different from working with
previous refrigerants.
Page 15
All text, illustrations, diagrams and examples in this
guide are only intended to help with the handling
and proper use of the refrigerant R410A. The
information contained in this brochure has been
carefully researched and checked and is considered
correct at time of going to press.
Page 16