Engineering Practices Laboratory Manual Subject Code: Ge1X03
Engineering Practices Laboratory Manual Subject Code: Ge1X03
Engineering Practices Laboratory Manual Subject Code: Ge1X03
440,3phase
ac supply
440,3phase
ac supply
440,3phase
ac supply
B
R
Y
10A
10A
10A
600V,10A
UPF Wm
(0-10)A MI
3 phase variable
resistive load
T
P
S
T
600V,10A
UPF Wm
18
TABULAR COLUMN:
SNO I W1 W2 POWER
P
P.F
(Amps) (Watts) (Watts) Watts COS
PROCEDURE:
1. Connections are given as per the circuit diagram.
2. AC supply is given by closing the TPST switch with no load included in
the circuit
3. Vary the load and note current and both the wattmeter readings.
4. Power and power factor are calculated using the given formula and
tabulated.
FORMULA USED:
1. Total power P = W1+W2 (W)
2. = Tan
-1
3[W1-W2/W1+W2]
3. P.F = Cos.
19
RESULT:
Thus the Power and Power factors for the given resistive load are
measured and tabulated.
20
Ex.No. CALIBRATION OF AMMETERS AND VOLTMETERS
Date:
Aim
To calibrate the given ac and dc ammeters and voltmeters.
Apparatus required
S.No Name of the
Apparatus
Range Type Quantity
1 Ammeter (0 10)A MI 2
2 Ammeter (0 10)A MC 2
3 Voltmeter (0 300)V MI 2
4 Voltmeter (0 300)V MC 2
5 Load - Rheostat 1
6 Single Phase
autotransformer
300V,5A - 1
Formula:
a) Percentage Error = (At As) * 100 / At
b) Percentage Error = (At As) * 100 / At
c) Percentage Error = (Vt Vs) * 100 / Vt
d) Percentage Error = (Vt Vs) * 100 / Vt
21
Circuit Diagram
a) DC AMMETER
b) AC AMMETER
10 A
Tested
Ammeter
Standard
Ammeter
Loading
Rheostat
(0-10)A
MI
(0 10)A
MI
230V AC
Supply
P
N
SPST
At
As
10A
10 A
Tested
Ammeter
Standard
Ammeter
Loading
Rheostat
(0-10)A
MC
(0 10)A
MC
220V DC
Supply
+
-
D
P
S
T
At As
22
c) DC VOLTMETER
d) AC VOLTMETER
5 A
(0 300)V
MI
(0 300)V
MI
230V AC
Supply
P
N
SPST
Single phase
Autotransformer
Vt
Vs
5A
5 A
(0 300)V
MC
400
ohms/
1.5A
(0300)V
MC
220V DC
Supply
+
-
D
P
S
T
+
- -
+
Vt Vs
23
Procedure
a) i)Connections are given as per the circuit diagram
ii) Close the DPST switch
iii) Vary the load, take the readings of both the ammeters and
tabulate them.
iv) Calculate the error and plot the graph between Percentage error
vs Current
b) i) Connections are given as per the circuit diagram
ii) Close the SPST switch
iii) Vary the load, take the readings of both the ammeters and
tabulate them.
iv) Calculate the error and plot the graph between Percentage error
vs Current
c) i) Connections are given as per the circuit diagram
ii) Close the DPST switch
iii) Vary the rheostat, take the readings of both the voltmeters and
tabulate them.
iv) Calculate the error and plot the graph between Percentage error
vs Voltage.
d) i) Connections are given as per the circuit diagram
ii) Close the SPST switch
iii) Vary the autotransformer, take the readings of both the
ammeters and tabulate them.
iv) Calculate the error and plot the graph between Percentage error
vs Voltage
24
Model Graph
Result
Thus the given ac and dc voltmeters and ammeters are calibrated.
Percent
Error
Voltage or
Current
25
Expt. No.6 MEASUREMENT OF ENERGY
AIM:
To measure the energy consumed in a single phase circuit.
APPARATUS REQUIRED
S.No Name of the
Apparatus
Range Type Quantity
1 Ammeter (0 10)A MI 1
2 Voltmeter (0 300)V MI 1
3 Load - Rheostat 1
4 Energymeter 300V,10A,
single phase
UPF 1
NAME PLATE DETAILS:
RATED CURRENT
RATED VOLTAGE
FREQUENCY
REVOLUTIONS/KWH
26
CIRCUIT DIAGRAM
V
P
N
SPST 10A
(0-300)V MI
(0-10)A MI
Single phase Energymeter
230V,single
phase ac
supply
Loading
Rheostat
27
PROCEDURE:
1.Connections are given as shown in the circuit diagram.
2.Supply is switched ON and load is increased in steps, each time noting the readings of
ammeter and wattmeter. Also the actual time taken for 1 revolution of the disc is
measured using stop watch.
3.Step 2 is repeated till rated current of the energymeter is reached.
4. % Error is calculated and calibration curve is drawn.
TABULAR COLUMN:
S.NO LOAD
CURRENT
I
(Amps)
WATTMETER
READING t
(Sec)
INDICATED
POWER
W1
(watts)
%
ERROR
28
CALCULATION:
Let x revolution / kwh be the rating.
Now x revolution = 1 kwh
= 1* 3600*1000* watt-sec.
Constant k of energymeter = 3600 * 10
3
/x watt-sec
For each load indicated power Wi is given as Wi = k/t watts
Where k energymeter constant (watt-sec)
t time for 1 revolution(sec).
Actual power is indicated by the wattmeter reading.
% error = Wi-Wa/Wi* 100.
It can be zero +ve or ve.
MODEL GRAPH:
COCLUSION AND REMARKS:
From the calibration curve it is possible to predict the error
in recording the energy. So the correction can be applied to the energymeter reading
so that correct energy reading can be obtained and used.