Evita Oxy Manual
Evita Oxy Manual
Evita Oxy Manual
OXY
521B0270
Analytical
1
I
n
t
r
o
d
u
c
t
i
o
n
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
M
e
c
h
a
n
i
c
a
l
I
n
s
t
a
l
l
a
t
i
o
n
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
E
l
e
c
t
r
i
c
a
l
I
n
s
t
a
l
l
a
t
i
o
n
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
I
n
i
t
i
a
l
S
t
a
r
t
U
p
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
P
r
o
g
r
a
m
m
i
n
g
U
S
C
5
0
0
0
/
6
0
0
0
/
7
0
0
0
.
.
.
.
.
.
.
C
a
l
i
b
r
a
t
i
o
n
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
M
a
i
n
t
e
n
a
n
c
e
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
O
t
h
e
r
S
e
t
t
i
n
g
s
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
T
r
o
u
b
l
e
s
h
o
o
t
i
n
g
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
T
e
c
h
n
i
c
a
l
D
a
t
a
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
H
A
R
T
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
A
p
p
e
n
d
i
c
e
s
I
,
I
I
a
,
I
I
b
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
C
o
n
t
a
c
t
s
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
2 4 1
4
2
0
3
0
3
2
3
4
4
0
4
8
5
2
5
4
5
8
1
8
C
o
n
t
e
n
t
s
2
Introduction
EVITA
communication.
Examples of coupling to loop-powered display and
PLC/SCADA system are shown in fig. 22, fig. 23
and fig. 24, respectively.
+
Shield
Black
Red
Fig. 22
EVITA
multidrop
protocol on only two wires.
Each transmitter should be connected in parallel
outside the USC connection box and only two wires
with shield mounted on the terminals in the USC
7000.
Digital input
Relay 1
Relay 2
Relay 3
Relay 4
Relay 5
I out 1
I out 2
I out 3
I out 4
USC 7000 and OXY 4100/4150 multidrop
Fig. 27
24V
24V
PE
Shield
Black
Red
18
1. Apply voltage with the OXY 1100 sensor pointing
upwards in free air for 2 minutes. This will zero
the sensor life counter. The life counter can be
read via the signal converter (USC) or HART
communication.
2. Place the transmitter so that the OXY 1100
sensor points downwards, still in free air. Leave
it in this position for 1 hour to allow the sensor to
stabilise.
3. Calibrate in accordance with the instructions in
the Calibration section p. 30.
Fig. 28
Fig. 29
Initial start up
OXY 4100/4150/3150 stand alone transmitter
19
1. Place the transmitter in free air so that the OXY
1100 sensor points downwards, see fig. 30.
2. Turn on the power to the signal converter USC
5000/6000/7000.
3. Leave the transmitter in this position for at least
1 hour to allow the sensor to stabilise before
calibrating.
Fig. 30
4. Check factory settings, see p. 21. Change if
necessary.
5. Reset the lifetime counter, see fig. 32, p. 22.
6. Calibrate in accordance with the instructions in
the Calibration section, p. 30.
7. After calibration is completed, place the
transmitter in the measuring media.
System with USC 5000/6000/7000
20
The keypad is used to set the EVITA
OXY and to
step through the menus. The function of the keys
are as follows:
TOP UP KEY
(ESC)
FORWARD KEY
BACKWARD KEY
CHANGE KEY
SELECT KEY
LOCK/
This key (hold for 2 sec.) is used to switch between
the operator menu and setup menu. A short press
will cause a return to the overlying menu.
This key is used to step forward through the menus
in the setup menu.
This key is used to step backward through the
menus.
This key changes the settings or numerical values
in the setup menu. In the operator menu it is used to
step through the menues.
This key selects which digits to be changed.
This key allows the operator to change settings and
gives access to submenus.
Ready for change
Value locked
Access to submenu
Confirmation of choice
Fig. 31
UNLOCK KEY
(ENTER)
Various display symbols
Programming USC 5000/6000/7000
Keypad and display layout
21
The EVITA
OXY
transmitter is factory delivered with the address 0,
which is used for point-to-point installations (USC
5000/6000).
To programme a transmitter address, all other
transmitters in the multidrop system need to be
disconnected from the HART
31
If during the 5 minutes calibration period the
transmitter is turned with the OXY 1100 sensor
downwards, calibration stops and measurements
continue with the previous calibration value.
Temperature compensation is made automatically
during calibration via an internal temperature
sensor. In addition, using factory settings,
compensation is also made for air pressure,
relative humidity and salinity. These factory-set
values can be changed via the USC signal
converter or via HART
communication.
The set values and the significance of deviations
from them are given in appendix I.
A system accuracy of 0.5 % can be achieved by
lifting the transmitter out of the medium and placing
it with the OXY 1100 sensor downwards for 1 hour
to make sure the sensor is completely stabilised.
Calibration can then be initiated.
Using the USC 5000/6000/7000
In operator menu use the key to select the
Calibration menu and press the key to initiate
a calibration.
Compensations for relative humidity and salinity
can be made by entering these values using the
USC 5000/6000/7000, see fig. 48, p. 37.
Fig. 41
USC 5000/6000/7000
calibration
* See Advanced settings, fig. 48, p. 37.
32
Maintenance
Under normal conditions, the OXY 1100 sensor will
operate for 2-3 years and can be replaced in a few
minutes.
General maintenance of the EVITA
OXY sensor is
limited to cleaning about every 2-3 months and
calibration about every 6 months.
1. Lift the transmitter out of the medium.
2. Clean the sensor with pure water, to which a
little cleaning agent/washing-up liquid can be
added.
3. Dry the sensor with a soft cloth.
4. Immerse the transmitter into the medium to be
measured.
Cleaning
During cleaning, the sensor must not be allowed to
remain pointing upwards for more than 3 minutes at
a time if the TILTCAL
function is enabled,
otherwise a calibration cycle will start. The
TILTCAL
communication it is necessary to
use a PC or PLC with a HART
modem and
associated software.
All Universal Commands are fully implemented, as
are the necessary Common Practice Commands,
but to ensure complete utilisation of the transmitter,
special Specific Device Commands are used.
HART
communication makes it possible to read
off:
oxygen concentration
temperature
remaining lifetime of the OXY 1100 sensor
alarms
indication of completed calibration
When calibrating/replacing an OXY 1100 sensor
the following can be performed with HART
communication:
- initiation of calibration
- keying in of values for relative humidity, air
pressure and salinity for compensation
purposes
- zero setting of life counter
The following programming is possible with
HART
communication:
setting of measuring range
deactivation of tilt-switch for initiating an
automatic calibration
setting of current output signal during calibration
for 4 mA, 20 mA or last measuring value
deactivation of alarms on current output
measurement start after completed calibration
change OXY 1100 sensor type
The USC 5000/6000/7000 can act as either a primary
master or a secondary master. This can be set as
shown in fig. 51.
Fig. 51
USC
HART Settings
USC
Change HART
Trm. Mode
USC
USC
USC
USC
0
8
1
R
9
4
0
3
. 0
2
. 0
1
Scan HART bus
USC
Scan HART bus
Are you sure ?
USC
Set mode to
Secondary master
Curr. Trm. mode
Primary master
Curr. Trm. mode
Secondary Master
Set mode to
Primary Master
53
54
Appendix I
Factory set values and the significance of deviations from them
Parameter Factory setting Deviation Significance (% of actual value)
Atmospheric air pressure 1013.25 mbar 10 mbar approx. 1
Relative humidity 100% 10% approx 0.3
Salinity 0 g/l 1 g/l approx. 1
55
0 / 32.0 14.62
1 / 33.8 14.22
2 / 35.6 13.83
3 / 37.4 13.46
4 / 39.2 13.11
5 / 41.0 12.77
6 / 42.8 12.45
7 / 44.6 12.14
8 / 46.4 11.84
9 / 48.2 11.56
10 / 50.0 11.29
11 / 51.8 11.03
12 / 53.6 10.78
13 / 55.4 10.54
14 / 57.2 10.31
15 / 59.0 10.08
16 / 60.8 9.87
17 / 62.6 9.66
18 / 64.4 9.47
19 / 66.2 9.28
C/F mg/l or ppm
Appendix IIa
21 / 69.8 8.91
22 / 71.6 8.74
23 / 73.4 8.58
24 / 75.2 8.42
25 / 77.0 8.26
26 / 78.8 8.11
27 / 80.6 7.97
28 / 82.4 7.83
29 / 84.2 7.69
30 / 86.0 7.56
Solubility of oxygen in water in
equilibrium with air (100%)
at 101.325 kPa
Source: DS/EN 25814
Temperature Temperature Solubility of oxygen in water in
equilibrium with air (100%)
at 101.325 kPa
C/F
20 / 68.0 9.09
56
Appendix IIb
Zero point check
1 g of sodium sulphite (Na
2
SO
3
) and
1 mg cobalt (II) salt (Cobalt(II)chloride-hexahydrate;
CoCl
2
, 6H
2
O) is added to 1 litre of water to remove
oxygen from the water. The water is then stirred
and oxygen concentration measured in order to
check the zero point.
Source: DS/EN 25814
57
58
Contacts
Great Britain
Danfoss Limited
Perivale Industrial Park
Horsenden Lane South
Greenford, Middx. UB6 7QE
Tel: 020 8 991 7000
Fax: 020 8 991 7171
Homepage: www.danfoss.co.uk
Ireland
Danfoss (Ireland) Ldt.
Unit A-1
Nangor Road Business Park
Dublin 12
Telephone: (01) 626 81 11/626 93 32
Telefax: (01) 626 93 34
E-mail: [email protected]
New Zealand
Danfoss (New Zealand) Limited
8 George Bourke Drive
P.O. Box 12-422, Penrose
Mt Wellington, Auckland
Tel: (09) 270 2110
Fax: (09) 270 2112
Singapore
Danfoss Industries Pte. Ltd.
6 Jalan Pesawat
Singapore 619364
Tel: (65) 2614088
Fax: (65) 2610488
USA
Danfoss Water
& Wastewater Division
8800 W. Bradley Road
Milwaukee, WI 53224-9541
Phone: 1 414 355 8800
Fax: 1 414 355 6117
Homepage: www.us.water.danfoss.com
Australia
Danfoss (Australia) Pty. Ltd.
Melbourne (Head Office)
1 Ricketts Road
Private Bag No. 20, Mt. Waverley,
Victoria, 3149
Tel: (3) 95431033
Fax: (3) 9543 4027
Canada
Davis Controls
2200 Bristol Circle :
Oakville, Ontario
L6H 5R3
Tel: (905) 829-2000
Fax: (905) 829-2630
Homepage: www.daviscontrols.com
E-mail: daviscontrols.on.ca
Please find below the extract of Danfoss
companies. Other company locations:
www.danfoss.com
Set factory settings
Output when not
measuring
Output during error
Time constant
Mfr. device type
Manufacturer Id.
Transmitter mode
TILTCAL
Event log Reset lifetime
Start measuring
TILTCAL
After calibration
Calibr. type
Scan HART bus
Further info.
HW version
SW version
Serial no.
Code no.
Event log
Digital input
Relay 1-5
Relay 1-5
Error pending
Scan HART bus
Password
0000.
Settings
USC
Output
USC
Reset
mode
USC
Service
mode
USC
Product
identity
USC
Operator menu
setup
USC
Password
USC
Language
USC
HART Settings
USC
Set default
setting
USC
I Out 1-4
USC
Type
USC5000
USC
Change HART
Trm. Mode
USC
OXY
USC
Basic settings
TR. 0
Advanced settings
TR. 0
Send command
TR. 0
Info
TR. 0
Settings OXY
Ser.No. SSSSVVNUU
TR. 0
Set transmitter
address 00
TR. 0
Oxygen unit
ppm
TR. 0
Calibration
TR. 0
Error pending
Time since last
calibr.
TR. 0
I out 1-4
USC
~ ~ ~ ~
0
8
1
R
9
4
1
8
. 0
2
. 0
1
Value at 4 mA
Value at 20 mA
Salinity
Rel. humidity
Rem. lifetime
Transmitter 0
72. h
No. of alarms
Transmitter 0
12. d
Calibration
Transmitter 0
42. d
Temperature
Transmitter 0
Oxygen
Transmitter 0
10.64 mg/l
Reset lifetime
Transmitter 0
Last calibration
Transmitter 0
Rem. lifetime
Transmitter 0
72. h
No. of alarms
Transmitter 0
12. d
Calibration
Transmitter 0
42. d
Temperature
Transmitter 0
Oxygen
Transmitter 0
10.64 mg/l
Reset lifetime
Transmitter 0
Last calibration
Transmitter 0
Temp. unit
Univ. cmd. rev.
Transm. cmd. rev.
SW version
HW version
Device id.
Sensor type
Overview
2 sec.
Fig. 52
Menus marked with grey are only visible in USC 7000
* Add-on module
* *
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies
to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Partnership with commitment
Purchasing Danfoss products gives you not only
high quality and unsurpassed reliability, but also a
lasting partnership that will always provide you with
the technology of tomorrow.
Danfoss is well-known for accurate mechanical
and electronic systems, and is perhaps even more
renowed for its intelligent, mechatronic products.
Water treatment processes always have been a vital
part of our business, and today our commitment to
the water and wastewater industry is stronger than
ever.
Our wastewater product range also contains
flowmeters,water valves, pressure transmitters and
frequency converters.
Flowmeters Water valves VLT
frequency converters
DKCFE.PS.202.B2.02/521B0270 EVITA