15

15
I
s
o
m
a
x
M
C
C
B
s
Isomax
Molded case circuit breakers
S3 S8
S4 N 250 B W - 2 xxx
Interrupting rating
class
B = Basic (240VAC)
N = Normal
H = High
L = Extra High
BQ = Basic, 100% rated
Current rating
015 = 15A
250 = 250A
400 = 400A
1200 = 1200A
Trip unit function
B = LI F = LSIG/K
C = LSI H = LSIG/D
D = Molded Case Switch (MCS) J = LSIG/DT
E = LSIG K = LSIG/DTK
T = Thermal-magnetic 10X Mag M = Magnetic only (MCP)
G = Thermal-magnetic 2.5 - 3X Mag 2
Type connectors
W = None
Number of poles
-2 = 2 pole
-4 = 4 pole
None = 3 pole
Accessories (added in alpha-numeric order)
1
A = Auxiliary Switch
BA = Bell Alarm
BA3 = Bell Alarm (S6/S7 only)
S_ = Shunt trip with voltage code
U_ = Undervoltage release with voltage code
Frame size
S3 = 150 /225A S6 = 600 /800A
S4 = 250A S7 = 1200A
S5 = 400A
1 Consult ABB for factory installed accessories.
2 Consult ABB for availability.
NQ = Normal, 100% rated
HQ = High, 100% rated
LQ = Extra High, 100% rated
D = Special molded case switch

(No trip IEC)
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.66 Low Voltage Products & Systems
UL/CSA Interrupting capacity (kA RMS)
UL489 / CSA C22.2
S3
150/225A
Standard thermal-magnetic
H x W x D
6.70" x 4.13" x 4.07"
Standard S3 package in cludes
complete cir cuit break er and mount ing
hard ware. Order cable lugs as a
separate item, standard copper/
aluminum (Cu/Al) lugs are no charge
when or dered with breaker.
General
The S3 breaker family ranges from 15 through 225 amperes. The S3 trip
mech a nisms are non-interchangeable and use sen si tive elec tro mag net ic relays
for overcurrent trip pro tec tion. Heat sensitive bimetals are used for ther mal
over cur rent protection. Short circuit cur rent protection begins at 10 times the
ther mal rating of the breaker and uses a magnetic coil principle.
Versions
To meet all application needs, the S3 is available in various versions:
T =Thermal-magnetic
Q =100% UL rated
D = Molded case switch
M = Magnetic only (MCP)
G = 3X Mag (100 - 225A 3-pole only)
Performance level
Each version is also available in different maximum fault in ter rupt ing levels
B = 240VAC
N = Normal
H = High
L = Extra high
Number of poles
In UL/CSA form, the S3 is avail able in two pole or three pole versions, both with
the same dimensions. A four pole ver sion is also available in UL/IEC form. For
price estimate, add 35% to list price of selected version three pole breaker,
contact ABB Control for details.
Accessory mounting
Internal accessories are UL/CSA ap proved for both factory or eld installation.
Accessories require control ca ble con nec tors. Shunt trips or UVR's mount in the
left cavity. Auxiliary or bell alarm switches mount in the right cavity.
Reverse feeding
All versions of the S3 family are suitable for reverse feed applications.
Molded case switches
UL489 switches in clude no overcurrent pro tec tion except for a high in stan ta neous
trip mech a nism for self protection. IEC type molded case switches with no trip
pro tec tion are also available.
Voltage N H L
230VAC 65 100 170
380/400/415VAC 35 65 85
440VAC 30 50 65
500VAC 25 40 50
690VAC 14 18 20
500VDC 35 50 65
750VDC 20 35 50
1 15-30A are 65kA at 480VAC
S3N S3H S3L S3B
Voltage N H L
240VAC 65 100 150
480VAC 25 50 85
1
600VAC 14 14 25
500VDC 35 50 65
600VDC 20 35 50
IEC-947 Interrupting capacity (kA RMS)
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
S3
150/225A
Standard thermal-magnetic
S3L
15A 500A S3L015TW-2 S3L015TW

65k
20A 500A S3L020TW-2
$ 634
S3L020TW
$ 824
25A 500A S3L025TW-2 S3L025TW
30A 500A S3L030TW-2 S3L030TW
35A 500A S3L035TW-2 S3L035TW
40A 500A S3L040TW-2
634
S3L040TW
824
50A 500A S3L050TW-2 S3L050TW
60A 600A S3L060TW-2 S3L060TW
S3L
85kA
70A 700A S3L070TW-2 S3L070TW
80A 800A S3L080TW-2
816
S3L080TW
1010
90A 900A S3L090TW-2 S3L090TW
100A 1000A S3L100TW-2 S3L100TW
125A 1250A S3L125TW-2 1818 S3L125TW 2260
150A 1500A S3L150TW-2 S3L150TW
175A
1
1750A S3L175TW-2 S3L175TW
65kA 200A
1
2000A S3L200TW-2 1818 S3L200TW 2260
225A
1
2250A S3L225TW-2 S3L225TW

Breaker
IC at
Rating
Magnetic 2 pole, 600VAC/500VDC List 3 pole, 600VAC/DC List
480VAC trip catalog number price catalog number price
15A 500A S3H015TW-2 S3H015TW
20A 500A S3H020TW-2 S3H020TW
25A 500A S3H025TW-2 S3H025TW
30A 500A S3H030TW-2
$ 527
S3H030TW
$ 619
35A 500A S3H035TW-2 S3H035TW
40A 500A S3H040TW-2 S3H040TW
50A 500A S3H050TW-2 S3H050TW
S3H 50kA 60A 600A S3H060TW-2 S3H060TW
70A 700A S3H070TW-2 S3H070TW
80A 800A S3H080TW-2
617
S3H080TW
702
90A 900A S3H090TW-2 S3H090TW
100A 1000A S3H100TW-2 S3H100TW
125A 1250A S3H125TW-2 S3H125TW
150A 1500A S3H150TW-2 S3H150TW
175A
1
1750A S3H175TW-2 1376 S3H175TW 1586
200A
1
2000A S3H200TW-2 S3H200TW
225A
1
2250A S3H225TW-2 S3H225TW
Breaker
IC at
Rating
Magnetic 2 pole, 600VAC/500VDC List 3 pole, 600VAC/DC List
480VAC trip catalog number price catalog number price
S3H
15A 500A S3N015TW-2 S3N015TW
20A 500A S3N020TW-2 S3N020TW
25A 500A S3N025TW-2 S3N025TW
30A 500A S3N030TW-2
$ 316
S3N030TW
$ 413
35A 500A S3N035TW-2 S3N035TW
40A 500A S3N040TW-2 S3N040TW
50A 500A S3N050TW-2 S3N050TW
S3N 25kA 60A 600A S3N060TW-2 S3N060TW
70A 700A S3N070TW-2 S3N070TW
80A 800A S3N080TW-2
407
S3N080TW
504
90A 900A S3N090TW-2 S3N090TW
100A 1000A S3N100TW-2 S3N100TW
125A 1250A S3N125TW-2 S3N125TW
150A 1500A S3N150TW-2 S3N150TW
175A
1
1750A S3N175TW-2 911 S3N175TW 1131
200A
1
2000A S3N200TW-2 S3N200TW
225A
1
2250A S3N225TW-2 S3N225TW

Breaker
IC at
Rating
Magnetic 2 pole, 600VAC/500VDC List 3 pole, 600VAC/DC List
480VAC trip catalog number price catalog number price
S3N
175A 1750A S3B175TW-2 S3B175TW
S3B 150kA 200A 2000A S3B200TW-2 $ 460 S3B200TW $ 590
225A 2250A S3B225TW-2 S3B225TW

Breaker
IC at
Rating
Magnetic 2 pole, 240VAC List 3 pole, 240VAC List
240VAC trip catalog number price catalog number price
S3B
1 480VAC maximum
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
S3
150/225A
100% UL rated
S3NQ
Note: When applied cor rect ly, UL tested 100% equipment rated breakers may be applied at full rating rather than on the sizing rules of the NEC where breakers and
cable are sized based on actual con tin u ous load current divided by 80%. This 100% rating can save the user the cost of larger cable or bus bar. Please consult the NEC
for details and other design factors needed for this application.

Breaker
IC at
Rating
Magnetic 3 pole 600VAC/DC List
480VAC trip catalog number price
S3HQ
S3LQ
Discount schedule S3
15A 500A S3LQ015TW

65kA
20A 500A S3LQ020TW
25A 500A S3LQ025TW
30A 500A S3LQ030TW
$ 916
35A 500A S3LQ035TW
40A 500A S3LQ040TW
50A 500A S3LQ050TW
60A 600A S3LQ060TW
S3LQ 85kA 70A 700A S3LQ070TW
80A 800A S3LQ080TW
1123
90A 900A S3LQ090TW
100A 1000A S3LQ100TW
125A 1250A S3LQ125TW
150A 1500A S3LQ150TW
175A1 1750A S3LQ175TW 2511
200A1 2000A S3LQ200TW
225A1 2250A S3LQ225TW

Breaker
IC at
Rating
Magnetic 3 pole List
480VAC trip catalog number price
15A 500A S3HQ015TW
20A 500A S3HQ020TW
25A 500A S3HQ025TW
30A 500A S3HQ030TW
$ 688
35A 500A S3HQ035TW
40A 500A S3HQ040TW
50A 500A S3HQ050TW
S3HQ 50kA 60A 600A S3HQ060TW
70A 700A S3HQ070TW
80A 800A S3HQ080TW
780
90A 900A S3HQ090TW
100A 1000A S3HQ100TW
125A 1250A S3HQ125TW
150A 1500A S3HQ150TW
175A1 1750A S3HQ175TW 1762
200A1 2000A S3HQ200TW
225A1 2250A S3HQ225TW

Breaker
IC at
Rating
Magnetic 3 pole List
480VAC trip catalog number price
15A 500A S3NQ015TW
20A 500A S3NQ020TW
25A 500A S3NQ025TW
30A 500A S3NQ030TW $ 459
35A 500A S3NQ035TW
40A 500A S3NQ040TW
50A 500A S3NQ050TW
S3NQ

25kA
60A 600A S3NQ060TW
70A 700A S3NQ070TW
80A 800A S3NQ080TW 560
90A 900A S3NQ090TW
100A 1000A S3NQ100TW
125A 1250A S3NQ125TW
150A 1500A S3NQ150TW
175A1 1750A S3NQ175TW 1257
200A1 2000A S3NQ200TW
225A1 2250A S3NQ225TW
1 480VAC maximum
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Molded case switches
Connection options
S3
150/225A, 600VAC
CU/AL front lugs 14AWG 2AWG 60 K3TA-2 $ 4 K3TA $ 6
CU/AL front lugs 14AWG 1/0 100 K4TB-2 4 K4TB 6
CU/ALfront lugs 2AWG 4/0 150 K4TC-2 4 K4TC 6
CU/AL front lugs 4AWG 300kcmil 225 K4TD-2 10 K4TD 15
CU front lugs (saddle) 14AWG 250kcmil 250 K4TES 30
CU rear lugs 6AWG 250kcmil 250 K4TER
Extended front bar 250 K4ET-250 46
Wire Set of 2 List Set of 3 List
Type range
Amps
catalog number price catalog number price
1 Suggested lugs for circuit breaker up to amps shown. Cable size and type determine maximum amperage.
2 480VAC maximum.
3 With fuse or MCCB protected circuit.

Type
Interruption
Amps
Magnetic 3 pole List
capacity 3 trip catalog number price
S3B-D 240VAC 150KA 225 2250A S3B225DW $ 410
240VAC 100kA
480VAC 50kA
S3H-D 600VAC 14kA 150 1500A S3H150DW 892
500VDC 65kA 225 2 2250A S3H225DW 1254
600VDC 50kA
Non-UL Withstand rating
switches
100 none S3D100W 531
without
600VAC 6.5kA

160 none S3D160W 892
overcurrent
250 none S3D250W 1393
protection
Magnetic only circuit breakers are instantaneous trip only devices which are Un der writ ers Lab o ra to ries Recognized. MCPs must be used with some other device that
will provide over load protection.
Magnetic only (MCP)
240VAC 50kA 3 12 36 S3L003MW
480VAC 25kA 5 20 60 S3L005MW
600VAC 10kA 10 40 120 S3L010MW

$ 710
240VAC 50kA
480VAC 25kA 25 100 300 S3L025MW
S3L 600VAC 10kA


240VAC 150kA
50 200 600 S3L050MW 710

480VAC 85kA
100 400 1200 S3L100MW 843

600VAC 25kA
125 500 1500 S3L125MW 1910
150 600 1500 S3L150MW 1910
480VAC 65kA 200 2 800 2400 S3L200MW 1910

Type
Interruption
Amps
Magnetic 3 pole List
capacity trip catalog number price
240VAC 35kA 3 12 36 S3N003MW
480VAC 18kA 5 20 60 S3N005MW
600VAC 10kA 10 40 120 S3N010MW

240VAC 35kA $ 568
480VAC 18kA 25 100 300 S3N025MW
S3N 600VAC 10kA


240VAC 75kA
50 200 600 S3N050MW 633

480VAC 35kA
100 400 1200 S3N100MW 763

600VAC 14kA
125 500 1500 S3N125MW 929
150 600 1500 S3N150MW 929

Type
Interruption
Amps
Magnetic 3 pole List
capacity trip catalog number price
Set of 6
catalog number
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.70 Low Voltage Products & Systems
S4
250A, 600VAC
Electronic trip type
H x W x D
10.0" x 4.13" x 4.07"
General
The S4 breaker family is a 250A frame utilizing a mi cro pro ces sor based
overcurrent pro tec tive trip sys tem. In the 250A version, the trip unit is ad just able
from 100A up to 250A without the addition of any parts or rating plugs. As
standard, the S4 includes adjustable long time func tion for overload protection
and ad just able in stan ta neous func tion for short circuit protection.
Versions
To meet all application needs, the S4 is available in various versions:
B = Adjustment LI
C = Adjustment LSI
E = Adjustment LSIG
Q = 100% UL rated
D = Molded case switch
M = Magnetic only (MCP)
Trip functions
These tripping functions are avail able:
L = Long time I = Instantaneous
S = Short time G = Ground fault
Performance level
Each version is also avail able in different maximum fault in ter rupt ing levels:
N = Normal
H = High
L = Extra high
Number of poles
In UL/CSA form, the S4 is avail able in two pole or three pole versions, both
with the same dimensions. A four pole version is also avail able in UL/IEC form.
For price estimate, add 35% to list price of selected version three pole breaker,
contact ABB Con trol for details.
Accessory mounting
Internal ac ces so ries are UL/CSA ap proved for both factory or eld installation.
Accessories require control ca ble con nec tors. Shunt trips or UVR's mount in the
left cavity. Auxiliary or bell alarm switches mount in the right cavity.
Reverse feeding
All versions of the S4 family are suitable for reverse feed applications.
Molded case switches
UL489 switches in clude no overcurrent pro tec tion except for a high in stan ta neous
trip mech a nism for self protection.
Voltage N H L
240VAC 65 150 200
480VAC 25 65 100
600VAC 18 22 35
Voltage N H L
230VAC 65 150 200
380/400/415VAC 35 65 100
440VAC 30 50 80
500VAC 25 40 65
690VAC 18 22 30
Standard S4 package includes com plete cir cuit breaker and mount ing hardware.
Order cable lugs or other connection scheme as a sep a rate item.
S4
UL/CSA Interrupting capacity (kA RMS)
UL489 / CSA C22.2
IEC-947 Interrupting capacity (kA RMS)
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
PR211 LI S4N100BW-2 $ 1073 S4N100BW $ 1347
S4N 25kA PR212 LSI S4N100CW-2 1679 S4N100CW 1913
PR212 LSIG S4N100EW 2813
PR211 LI S4H100BW-2 2572 S4H100BW 3030
S4H 65kA PR212 LSI S4H100CW-2 3138 S4H100CW 3596
PR212 LSIG S4H100EW 4496
PR211 LI S4L100BW-2 3159 S4L100BW 3950
S4L 100kA PR212 LSI S4L100CW-2 3725 S4L100CW 4516
PR212 LSIG S4L100EW 5416
The S4 breaker family uses two available mi cro pro ces sor based internal trip units.
The standard PR211 trip unit in cludes ad just ments for long time current pick-up
and in stan ta neous current trip point.
The optional PR212 trip unit includes ad just ments for long time current pick-
up/delay, short time pick-up/delay I
2
t (on/off), instantaneous current trip point and
further optional ground fault protection.
S4
250A, 600VAC
Electronic trip type
100A Frame (40 100A adjustable continuous range)
Breaker IC at 480VAC
Trip
Adjustment
2 pole List 3 pole List
type catalog number price catalog number price
250A Frame (100 250A adjustable continuous range)
Breaker IC at 480VAC
Trip
Adjustment
2 pole List 3 pole List
type catalog number price catalog number price
PR211 LI S4N250BW-2 $ 1073 S4N250BW $ 1347
S4N 25kA PR212 LSI S4N250CW-2 1679 S4N250CW 1913
PR212 LSIG S4N250EW 2813
PR211 LI S4H250BW-2 2572 S4H250BW 3030
S4H 65kA PR212 LSI S4H250CW-2 3138 S4H250CW 3596
PR212 LSIG S4H250EW 4496
PR211 LI S4L250BW-2 3159 S4L250BW 3950
S4L 100kA PR212 LSI S4L250CW-2 3725 S4L250CW 4516
PR212 LSIG S4L250EW 5416
Discount schedule S4
Continuous amperage settings (long time adjustment) PR211
Frame Set points
0.4 0.5 0.6 0.7 0.8 0.9 0.95 1.0 Setting
100A 40 50 60 70 80 90 95 100 Amps
250A 100 125 150 175 200 225 237 250 Amps

L
Long time pick-up 0.4 1.0 0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212
Long time delay 3.0 18 sec. A - B - C - D

S
Short time pick-up 1.0 10.0 Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating
Short time delay 0.05 0.5 sec. A - B - C - D (I
2
t On-Off)
I Instantaneous trip 1.5 12.0 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating

G
Ground fault 0.2 1.0 Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating
Ground fault delay 0.1 0.8 sec. A - B - C - D
Trip settings

Adjustment
Trip
Range
Individual
function settings
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
S4
250A, 600 VAC
100% UL rated
PR211 LI S4NQ100BW $ 1482
S4N 25kA PR212 LSI S4NQ100CW 2104
PR212 LSIG S4NQ100EW 3094
PR211 LI S4HQ100BW 3333
S4H 65kA PR212 LSI S4HQ100CW 3956
PR212 LSIG S4HQ100EW 4946
PR211 LI S4LQ100BW 4345
S4L 100kA PR212 LSI S4LQ100CW 4968
PR212 LSIG S4LQ100EW 5958
When applied cor rect ly, UL tested 100% equip ment rated breakers may be
applied at full rating rather than on the sizing rules of the NEC where breakers and
cable are sized based on actual con tin u ous load current divided by 80%. This
100A Frame (40 100A adjustable continuous range)

Breaker
IC at Trip
Adjustment
3 pole List
480VAC type catalog number price
250A Frame (100 250A adjustable continuous range)
PR211 LI S4NQ250BW $ 1482
S4N 25kA PR212 LSI S4NQ250CW 2104
PR212 LSIG S4NQ250EW 3094
PR211 LI S4HQ250BW 3333
S4H 65kA PR212 LSI S4HQ250CW 3956
PR212 LSIG S4HQ250EW 4946
PR211 LI S4LQ250BW 4345
S4L 100kA PR212 LSI S4LQ250CW 4968
PR212 LSIG S4LQ250EW 5958

Breaker
IC at Trip
Adjustment
3 pole List
480VAC type catalog number price
100% rating can save the user the cost of larger cable or bus bar. Please consult
the NEC for details and other design factors needed for this application.

L
Long time pick-up 0.4 1.0 0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212
Long time delay 3.0 18 sec. A - B - C - D

S
Short time pick-up 1.0 10.0 Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating
Short time delay 0.05 0.5 sec. A - B - C - D (I
2
t On-Off)
I Instantaneous trip 1.5 12.0 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating

G
Ground fault 0.2 1.0 Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating
Ground fault delay 0.1 0.8 sec. A - B - C - D
Trip settings

Adjustment
Trip
Range
Individual
function settings
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Type
Interruption
Amps
Magnetic 3 pole List
capacity 2 trip catalog number price
Molded case switch
All S4 magnetic only breakers utilize the electronic PR211 trip unit with an
adjustable range of 1.5 to 12 times frame rating. Both two and three pole MCPs
are 600VAC rated.
Type Amps
Interruption Adjustment 2 pole 600VAC List 3 pole 600VAC List
capacity range catalog number price catalog number price
CU/AL front lugs 14AWG 1/0 100 K4TB-2 $ 4 K4TB $ 6
CU/AL front lugs 2AWG 4/0 150 K4TC-2 4 K4TC 6
CU/AL front lugs 4AWG 300kcmil 225 K4TD-2 10 K4TD 15
CU/AL front lugs 6AWG 350kcmil 250 K4TE-2 20 K4TE 30
CU front lugs (saddle) 14AWG 250kcmil 250 K4TES 30
CU rear lugs 6AWG 250kcmil 250 K4TER
Extended front bar 250 K4ET-250 46

Amps
Catalog List
number price
Neutral GF current transformer (required for 4 wire GF sys tems)
S4
250A, 600VAC
Connection options

Type
Wire Amps Set of 2 List Set of 3 List
range catalog number price catalog number price
Magnetic only (MCP)
Set of 6
catalog number
1 Suggested lugs for a circuit breaker up to the amps shown. Cable size and type determine maximum amperage.
2 With fuse or MCCB protected circuit.

100
240VAC 65kA
150 1200A S4N100MW-2

S4N100MW

S4N
250
480VAC 25kA
375 3000A S4N250MW-2
$ 1073
S4N250MW
$ 1347
600VAC 18kA

100
240VAC 150kA
150 1200A S4H100MW-2

S4H100MW

S4H
250
480VAC 65kA
375 3000A S4H250MW-2
2572
S4H250MW
3030
600VAC 22kA

100
240VAC 200kA
150 1200A S4L100MW-2

S4L100MW

S4L
250
480VAC 100kA
375 3000A S4L250MW-2
3159
S4L250MW
3950
600VAC 35kA
240VAC 150kA
S4H-D 480VAC 65kA 250 3000A S4H250DW $ 1215
600VAC 22kA
100 K4NCT-100
$ 250
250 K4NCT-250
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.74 Low Voltage Products & Systems
S5
400A, 600V
Electronic and thermal-magnetic trip types
Standard S5 package in cludes com plete cir cuit breaker and mount ing hard ware.
Order ca ble lugs or other connection scheme as a sep a rate item.
General
The S5 breaker family is a 400A frame utilizing a microprocessor-based
overcurrent pro tec tive trip sys tem. In the 400A version, the trip unit is adjustable
from 160A up to 400A without the addition of any parts or rating plugs. As
standard the S5 includes adjustable long time func tion for overload protection
and ad just able in stan ta neous func tion for short circuit protection.
Versions
To meet all application needs, the S5 is available in various versions:
B = Adjustment LI
C = Adjustment LSI
E = Adjustment LSIG
Q = 100% UL rated
D = Molded case switch
M = Magnetic only (MCP)
T = Thermal magnetic
G = 2.5 Mag ( 3-pole only)
Trip functions
These tripping functions are avail able:
L = Long time I = Instantaneous
S = Short time G = Ground fault

Performance level
Each version is also avail able in different maximum fault in ter rupt ing levels
N = Normal
H = High
L = Extra high
Number of poles
In UL/CSA version, the S5 is available in two pole or three pole version, both
with the same dimensions. A four pole version is also avail able in UL/IEC form.
For price estimate, add 35% to list price of selected version three pole breaker,
contact ABB Con trol for details.
Accessory mounting
Internal ac ces so ries are UL/CSA ap proved for both factory or eld in stal la tion.
Accessories require control ca ble con nec tors. Shunt trips or UVR's mount in the
left cavity. Auxiliary or bell alarm switches mount in the right cavity.
Reverse feeding
All versions of the S5 family are suitable for reverse feed ap pli ca tions.
Molded case switches
UL489 switches in clude no overcurrent pro tec tion except for a high in stan ta neous
trip mech a nism for self pro tec tion.
UL/CSA Interrupting capacity (kA RMS)
UL489 / CSA C22.2
Voltage N H L
240VAC 65 150 200
480VAC 35 65 100
600VAC 22 22 35
500VDC
1
35 50 65
600VDC
1
20 35 50

IEC-947 Interrupting capacity (kA RMS)
Voltage N H L
230VAC 65 100 200
380/400/415VAC 35 65 100
440VAC 30 50 80
500VAC 25 40 65
690VAC 20 25 30
(a) With K5TF cable lugs, breaker is 10.0" tall.
(b) With K5TG cable lugs, terminal covers are provided and breaker is
13.62" tall.
S5
H x W x D
10.0" x 5.51" x 4.07" (a)
13.62" x 5.51" x 4.07" (b)
Discount schedule S5
1 Thermal magnetic only.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
The S5 breaker family uses two available mi cro pro ces sor based internal trip units.
The standard PR211 trip unit in cludes ad just ments for long time current pick-up
and in stan ta neous current trip point.
The optional PR212 trip unit includes ad just ments for long time current pick-up/
delay, short time pick-up/delay, I
2
t (on/off), instantaneous current trip point and
further optional ground fault protection.
S5
400A, 600 VAC
Electronic and thermal-magnetic trip types
Discount schedule S5
Continuous amperage settings (long time adjustment) PR211
Frame Set points
PR211 LI S5N400BW-2 $ 1798 S5N400BW $ 2151
S5N 35kA PR212 LSI S5N400CW-2 2464 S5N400CW 2817
PR212 LSIG S5N400EW 3717
PR211 LI S5H400BW-2 3285 S5H400BW 3654
S5H 65kA PR212 LSI S5H400CW-2 3951 S5H400CW 4320
PR212 LSIG S5H400EW 5220
PR211 LI S5L400BW-2 3945 S5L400BW 4733
S5L 100kA PR212 LSI S5L400CW-2 4611 S5L400CW 5399
PR212 LSIG S5L400EW 6299
400A Frame (160 400A adjustable continuous range)

Breaker IC at 480VAC Trip Adjustment
2 pole, 600VAC List 3 pole, 600VAC List
catalog number price catalog number price
300A (210 300A) 3000A S5N300TW-2
$ 1798
S5N300TW
$ 2151
S5N

35kA
400A (280 400A) 4000A S5N400TW-2 S5N400TW
S5H

50kA
300A (210 300A) 3000A S5H300TW-2
3285
S5H300TW
3654

400A (280 400A) 4000A S5H400TW-2 S5H400TW
S5L 65kA
300A (210 300A) 3000A S5L300TW-2
3945
S5L300TW
4733

400A (280 400A) 4000A S5L400TW-2 S5L400TW
S5 thermal-magnetic breakers, for AC and DC applications

Breaker IC at 500VDC Rating Magnetic trip
2 pole, 600VAC/500VDC List 3 pole, 600VAC/DC List
catalog number price catalog number price
0.4 0.5 0.6 0.7 0.8 0.9 0.95 1.0 Setting
400A 160 200 240 280 320 360 380 400 Amps

L
Long time pick-up 0.4 1.0 0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212
Long time delay 3.0 18 sec. A - B - C - D

S
Short time pick-up 1.0 10.0 Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating
Short time delay 0.05 0.5 sec. A - B - C - D (I
2
t On-Off)
I Instantaneous trip 1.5 12.0 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating

G
Ground fault 0.2 1.0 Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating
Ground fault delay 0.1 0.8 sec. A - B - C - D
Trip settings

Adjustment
Trip
Range
Individual
function settings
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
PR211 LI S5NQ400BW $ 2366
S5N 35kA PR212 LSI S5NQ400CW 3099
PR212 LSIG S5NQ400EW 4089
PR211 LI S5HQ400BW 4019
S5H 65kA PR212 LSI S5HQ400CW 4752
PR212 LSIG S5HQ400EW 5742
PR211 LI S5LQ400BW 5206
S5L 100kA PR212 LSI S5LQ400CW 5939
PR212 LSIG S5LQ400EW 6929
S5
400A, 600 VAC
100% UL rated, electronic trip type
When applied cor rect ly, UL tested 100% equip ment rated breakers may be
applied at full rating rather than on the sizing rules of the NEC where breakers and
cable are sized based on actual con tin u ous load current divided by 80%. This
400A Frame (160 400A adjustable continuous range)
100% rating can save the user the cost of larger cable or bus bar. Please consult
the NEC for details and other design factors needed for this application.

Breaker IC at 480VAC
Trip
Adjustment
3 pole, 600VAC List
type catalog number price
Discount schedule S5

L
Long time pick-up 0.4 1.0 0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212
Long time delay 3.0 18 sec. A - B - C - D

S
Short time pick-up 1.0 10.0 Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating
Short time delay 0.05 0.5 sec. A - B - C - D (I
2
t On-Off)
I Instantaneous trip 1.5 12.0 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating

G
Ground fault 0.2 1.0 Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating
Ground fault delay 0.1 0.8 sec. A - B - C - D
Trip settings

Adjustment
Trip
Range
Individual
function settings
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Molded case switch
All S5 magnetic only breakers utilize the electronic PR211 trip unit with an
adjustable range of 1.5 to 12 times frame rating. Both two and three pole MCP's
are 600VAC rated.
240 VAC 65kA
S5N 400 480VAC 35kA 600 4800A S5N400MW-2 $ 1798 S5N400MW $ 2151
600VAC 22kA
240VAC 150kA
S5H 400 480VAC 65kA 600 4800A S5H400MW-2 3285 S5H400MW 3654
600VAC 22kA
240VAC 200kA
S5L 400 480VAC 100kA 600 4800A S5L400MW-2 3945 S5L400MW 4733
600VAC 35kA
S5
400A, 600VAC

Type Amps
Interruption Adjustment 2 pole 600VAC List 3 pole 600VAC List
capacity range catalog number price catalog number price
1 Including lug cover.
2 Suggested lugs for a circuit breaker up to amps shown. Cable size and type determine maximum amperage.
3 With fuse or MCCB protected circuit.
Magnetic only (MCP)

Switch
Interruption Amps Magnetic 3 pole List
capacity 3 trip catalog number price
240VAC 150kA

S5H-D
480VAC 65kA
400A 5000A S5H400DW $ 1994
600VAC 22kA
600VDC 50kA

Type
Wire
Amps
2 Set of 2 List Set of 3 List
range catalog number price catalog number price
CU/AL front lugs 250kcmil 500kcmil 300 K5TF-2
$ 30
K5TF
$ 45
CU/AL front lugs (2) 3/0 250kcmil 400 K5TG-2
1
K5TG
1

CU front lugs (saddle) 250kcmil 500kcmil 400 K5TGS 90
CU rear lugs 250kcmil 500kcmil 400 K5TGR
Extended front bar 400 K5ET-400 114

Amps
Catalog List
number price
400 K5NCT-400 $ 250
Neutral GF current transformer (required for 4 wire GF sys tems)
Connection options
Set of 6
catalog number
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.78 Low Voltage Products & Systems
S6
600A / 800A, 600V
Electronic and thermal-magnetic trip type
General
The S6 breaker family is an 800A frame with a 600A and 800A version, both
utilizing a mi cro pro ces sor based over cur rent pro tec tive trip sys tem. Both
versions are adjustable from 40% to 100% of rating with out the ad di tion of any
parts or rating plugs. As standard, the S6 includes ad just able long time func tion
for over load pro tec tion and ad just able in stan ta neous func tion for short cir cuit
pro tec tion.
Versions
To meet all application needs, the S6 is available in various versions:
B = Adjustment LI
C = Adjustment LSI
E = Adjustment LSIG
Q = 100% UL rated
D = Molded case switch
M = Magnetic only (MCP)
T = Thermal magnetic
G = 2.5 Mag (3-pole only)
Trip functions
These tripping functions are avail able:
L = Long time I = In stan ta neous
S = Short time G = Ground fault

Performance level
Each version is also avail able in different maximum fault in ter rupt ing levels
N = Normal
H = High
L = Extra high
Number of poles
In UL/CSA version, the S6 is available as in two pole or three pole version, both
with the same dimensions. A four pole version is also avail able in UL/IEC form.
For price estimate, add 35% to list price of selected version three pole break er,
contact ABB Con trol for details.
Accessory mounting
Internal ac ces so ries are UL/CSA approved for both factory or eld in stal la tion.
Accessories require control ca ble con nec tors. Shunt trips or UVR's mount in the
left cavity. Auxiliary or bell alarm switches mount in the right cavity.
Reverse feeding
All versions of the S6 family are suitable for reverse feed ap pli ca tions.
Molded case switches
UL489 switches in clude no overcurrent pro tec tion except for a high in stan ta neous
trip mech a nism for self pro tec tion. IEC type molded case switches with no trip
pro tec tion are also avail able.
UL/CSA Interrupting capacity (kA RMS)
UL489 / CSA C22.2
IEC-947 Interrupting capacity (kA RMS)
H x W x D
10.55" x8.27" x 4.07" (a)
14.25" x 8.27" x 4.07" (b)
(a) With K6TH cable lugs breaker is
10.55" tall.
(b) With K6TJ cable lugs, terminal
covers are provided and breaker
is 14.25" tall.
S6
Standard S6 package includes com plete cir cuit breaker and mount ing hard ware.
Order ca ble lugs or other con nec tion scheme as a sep a rate item.
Voltage N H L
240VAC 65 150 200
480VAC 50 65 100
600VAC 25 35 42
500VDC
1
35 50 65
600VDC
1
20 25 50

Voltage N H L
230VAC 65 100 200
380/400/415VAC 35 65 100
440VAC 30 50 80
500VAC 25 40 65
690VAC 20 25 35
Discount schedule S6
1 Thermal magnetic only.
Catalog Number
Rating
Magnetic
number trip
S6N600GW 3 pole, 600 Amp thermal magnetic, Im=2.5 x Ith 1500A
S6N800GW 3 pole, 800 Amp thermal magnetic, Im=2.5 x Ith 2000A
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
PR211 LI S6N600BW-2 $ 2847 S6N600BW $ 3608
S6N 50kA PR212 LSI S6N600CW-2 4237 S6N600CW 4998
PR212 LSIG S6N600EW 6998
PR211 LI S6H600BW-2 4275 S6H600BW 5271
S6H 65kA PR212 LSI S6H600CW-2 5665 S6H600CW 6661
PR212 LSIG S6H600EW 8661
PR211 LI S6L600BW-2 5481 S6L600BW 6482
S6L 100kA PR212 LSI S6L600CW-2 6871 S6L600CW 7872
PR212 LSIG S6L600EW 8972
The S6 breaker family uses two available mi cro pro ces sor based internal trip units.
The standard PR211 trip unit in cludes ad just ments for long time current pick-up
and in stan ta neous current trip point.
The optional PR212 trip unit includes ad just ments for long time current pick-up/
delay, short time pick-up/delay, I
2
t (on/off), instantaneous current trip point and
further optional ground fault protection.
PR211 LI S6N800BW-2 $ 3842 S6N800BW $ 4802
S6N 50kA PR212 LSI S6N800CW-2 5232 S6N800CW 6192
PR212 LSIG S6N800EW 8192
PR211 LI S6H800BW-2 5275 S6H800BW 6465
S6H 65kA PR212 LSI S6H800CW-2 6665 S6H800CW 7855
PR212 LSIG S6H800EW 9855
PR211 LI S6L800BW-2 6476 S6L800BW 7676
S6L 100kA PR212 LSI S6L800CW-2 7866 S6L800CW 9066
PR212 LSIG S6L800EW 11,066
S6
600A / 800A, 600 VAC
Electronic and thermal magnetic trip type
600A Frame (240 600A adjustable continuous range)

Breaker IC at 480VAC
Trip
Adjustment
2 pole, 600VAC List 3 pole, 600VAC List
type catalog number price catalog number price
800A Frame (320 800A adjustable continuous range)
Discount schedule S6

Breaker IC at 480VAC
Trip
Adjustment
2 pole, 600VAC List 3 pole, 600VAC List
type catalog number price catalog number price
Continuous amperage settings (long time adjustment) PR211
Frame Set points
600A (420 600A) 6000A S6N600TW-2 $ 2847 S6N600TW $

3608
S6N

35kA
800A (560 800A) 8000A S6N800TW-2 3842 S6N800TW 4802
S6H

50kA
600A (420 600A) 6000A S6H600TW-2 4275

S6H600TW 5271

800A (560 800A) 8000A S6H800TW-2 5275 S6H800TW 6465
S6L 65kA
600A (420 600A) 6000A S6L600TW-2 5481 S6L600TW 6482

800A (560 800A) 8000A S6L800TW-2 6476 S6L800TW 7676
S6 thermal-magnetic breakers, for AC and DC applications

Breaker IC at 500VDC Rating Magnetic trip
2 pole, 600VAC /500DC List 3 pole, 600VAC/DC List
catalog number price catalog number price
0.4 0.5 0.6 0.7 0.8 0.9 0.95 1.0 Setting
600A 240 300 360 420 480 540 570 600 Amps
800A 320 400 480 560 640 720 760 800 Amps

L
Long time pick-up 0.4 1.0 0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212
Long time delay 3.0 18 sec. A - B - C - D

S
Short time pick-up 1.0 10.0 Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating
Short time delay 0.05 0.5 sec. A - B - C - D (I
2
t On-Off)
I Instantaneous trip 1.5 12.0 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating

G
Ground fault 0.2 1.0 Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating
Ground fault delay 0.1 0.8 sec. A - B - C - D
Trip settings

Adjustment
Trip
Range
Individual
function settings
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.80 Low Voltage Products & Systems
S6
600A / 800A, 600 VAC
100% UL rated, electronic trip type
When applied cor rect ly, UL tested 100% equip ment rated breakers may be
applied at full rating rather than on the sizing rules of the NEC where breakers and
cable are sized based on actual con tin u ous load current divided by 80%. This
100% rating can save the user the cost of larger cable or bus bar. Please consult
the NEC for details and other design factors needed for this application.
600A Frame (240 600A adjustable continuous range)
800A Frame (320 800A adjustable continuous range)
PR211 LI S6NQ600BW $ 3969
S6N 50kA PR212 LSI S6NQ600CW 5498
PR212 LSIG S6NQ600EW 7698
PR211 LI S6HQ600BW 5798
S6H 65kA PR212 LSI S6HQ600CW 7327
PR212 LSIG S6HQ600EW 9527
PR211 LI S6LQ600BW 7130
S6L 100kA PR212 LSI S6LQ600CW 8659
PR212 LSIG S6LQ600EW 9869

Breaker
IC at Trip
Adjustment
3 pole 600VAC List
480VAC type catalog number price
PR211 LI S6NQ800BW $ 5282
S6N 50kA PR212 LSI S6NQ800CW 6811
PR212 LSIG S6NQ800EW 9011
PR211 LI S6HQ800BW 7112
S6H 65kA PR212 LSI S6HQ800CW 8641
PR212 LSIG S6HQ800EW 10,841
PR211 LI S6LQ800BW 8444
S6L 100kA PR212 LSI S6LQ800CW 9973
PR212 LSIG S6LQ800EW 12,173

Breaker
IC at Trip
Adjustment
3 pole 600VAC List
480VAC type catalog number price

L
Long time pick-up 0.4 1.0 0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212
Long time delay 3.0 18 sec. A - B - C - D

S
Short time pick-up 1.0 10.0 Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating
Short time delay 0.05 0.5 sec. A - B - C - D (I
2
t On-Off)
I Instantaneous trip 1.5 12.0 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating

G
Ground fault 0.2 1.0 Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating
Ground fault delay 0.1 0.8 sec. A - B - C - D
Trip settings

Adjustment
Trip
Range
Individual
function settings
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
All S6 magnetic only breakers utilize the electronic PR211 trip unit with an
adjustable range of 1.5 to 12 times frame rating. Both two and three pole MCPs
are 600VAC rated.
Molded case switches
Neutral current transformer (required for 4 wire GF sys tems)

Amps
Catalog List
number price
600 K6NCT-600
$ 250
800 K6NCT-800
S6
600A / 800A

600
240VAC 65kA
900 7200A S6N600MW-2 $ 2847 S6N600MW $ 3608
S6N
800
480VAC 50kA
1200 9600A S6N800MW-2 3842 S6N800MW 4802
600VAC 25kA

600
240VAC 150kA
900 7200A S6H600MW-2 4275 S6H600MW 5271
S6H
800
480VAC 65kA
1200 9600A S6H800MW-2 5270 S6H800MW 6465
600VAC 35kA

600
240VAC 200kA
900 7200A S6L600MW-2 5481 S6L600MW 6482
S6L
800
480VAC 100kA
1200 9600A S6L800MW-2 6476 S6L800MW 7676
600VAC 42kA

Type
Interruption
Amps
Magnetic 3 pole List
capacity 3 trip catalog number price
Connection options
1 Includes lug cover.
2 Suggested lugs for a circuit breaker up to amps shown. Cable size and type determine maximum amperage.
3 With fuse or MCCB protected circuit.

Type
Wire
Amps
2 Set of 2 List Set of 3 List
range catalog number price catalog number price
CU/AL front lugs (2) 250kcmil 500kcmil 600 K6TH-2 $ 50 K6TH $ 75
CU/AL front lugs (3) 2/0 400kcmil 800 K6TJ-2
1
90 K6TJ
1
135
CU rear lugs (2) 250kcmil 350kcmil 600 K6THR 150
CU rear lugs (3) 250 350kcmil 800 K6TJR 170
Extended front bar 600 K6ET-600 150
Extended front bar 800 K6ET-800 170
Magnetic only (MCP)
240VAC 200kA
S6H-D 480VAC 100kA 600 10,000A S6H600DW $ 3275
600VAC 42kA 800 10,000A S6H800DW 4248
600VDC 50kA
Non-UL, switches without Withstand rating 400 none S6D400W 3275
overcurrent protection
600VAC

15kA
630 none S6D630W 3275
800 none S6D800W 4248

Type Amps
Interruption Adjustment 2 pole 600VAC List 3 pole 600VAC List
capacity range catalog number price catalog number price
Set of 6
catalog number
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.82 Low Voltage Products & Systems
S7
1200A, 600 VAC
Electronic trip type
H x W x D
15.98" x 8.27" x 5.45"
General
The S7 breaker family is a 1200A frame utilizing a mi cro pro ces sor based
overcurrent pro tec tive trip sys tem. In the 1200A version, the trip unit is adjustable
from 480A up to 1200A without the addition of any parts or rating plugs. As
standard, the S7 includes adjustable long time func tion for overload protection
and ad just able in stan ta neous func tion for short circuit protection.
Versions
To meet all application needs, the S7 is available in various versions:
B = Adjustment LI
C = Adjustment LSI
E = Adjustment LSIG
Q = 100% UL rated
D = Molded case switch
M = Magnetic only (MCP)
Trip functions
These tripping functions are avail able:
L = Long time I = In stan ta neous
S = Short time G = Ground fault

Performance level
Each version is also avail able in different maximum fault in ter rupt ing levels
H = High
L = Extra high (IEC only)
Number of poles
In UL/CSA version, the S7 is available as in two pole or three pole version, both
with the same dimensions. A four pole version is also avail able in a UL/IEC form.
For price estimate, add 35% to list price of selected three pole, contact ABB
Control.
Accessory mounting
Internal ac ces so ries are UL/CSA approved for both factory or eld in stal la tion.
Accessories require control ca ble con nec tors. Shunt trips or UVR's mount in the
left cavity. Auxiliary or bell alarm switches mount in the right cavity.
Reverse feeding
All versions of the S7 family are suitable for reverse feed ap pli ca tions.
Molded case switches
UL489 switches in clude no overcurrent protection except for a high in stan ta neous
trip mechanism for self pro tec tion. IEC type molded case switches with no trip
pro tec tion are also avail able.
Voltage H
240VAC 100
480VAC 65
600VAC 50
Voltage H L
230VAC 100 200
380/400/415VAC 65 100
440VAC 55 80
500VAC 45 70
690VAC 25 35
Standard S7 package includes com plete cir cuit breaker and mount ing hard ware.
Order cable lugs or other connection scheme as a sep a rate item.
S7
IEC-947 Interrupting capacity (kA RMS)
UL/CSA Interrupting capacity (kA RMS)
UL489 / CSA C22.2
Discount schedule S7
1 Consult factory
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
PR211 LI S7H1000BW-2 $ 6959 S7H1000BW $ 7724
S7H 65kA PR212 LSI S7H1000CW-2 8039 S7H1000CW 8804
PR212 LSIG S7H1000EW 10,604
The S7 breaker family uses two available mi cro pro ces sor based internal trip units.
The standard PR211 trip unit in cludes ad just ments for long time current pick-up
and in stan ta neous current trip point.
The optional PR212 trip unit includes ad just ments for long time current pick-up/
delay, short time pick-up/delay, I
2
t (on/off), instantaneous current trip point and
further optional ground fault protection.
S7
1200A, 600 VAC
Electronic trip type
1000A Frame (400 1000A adjustable continuous range)
1200A Frame (480 1200A adjustable continuous range)
PR211 LI S7H1200BW-2 $ 6959 S7H1200BW $ 7724
S7H 65kA PR212 LSI S7H1200CW-2 8039 S7H1200CW 8804
PR212 LSIG S7H1200EW 10,604


Breaker IC at 480VAC
Trip
Adjustment
2 pole, 600VAC List 3 pole, 600VAC List
type catalog number price catalog number price

Breaker IC at 480VAC
Trip
Adjustment
2 pole, 600VAC List 3 pole, 600VAC List
type catalog number price catalog number price
Continuous amperage settings (long time adjustment) PR211
Frame Set points
0.4 0.5 0.6 0.7 0.8 0.9 0.95 1.0 Setting
1000A 400 500 600 700 800 900 950 1000 Amps
1200A 480 600 720 840 960 1080 1140 1200 Amps
1 Consult factory.

L
Long time pick-up 0.4 1.0 0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212
Long time delay 3.0 18 sec. A - B - C - D

S
Short time pick-up 1.0 10.0 Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating
Short time delay 0.05 0.5 sec. A - B - C - D (I
2
t On-Off)
I Instantaneous trip 1.5 12.0 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating

G
Ground fault 0.2 1.0 Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating
Ground fault delay 0.1 0.8 sec. A - B - C - D
Trip settings

Adjustment
Trip
Range
Individual
function settings
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.84 Low Voltage Products & Systems
S7
1200A, 600VAC
UL 100% rated
When applied correctly, UL tested 100% equipment rated breakers may be
applied at full rating rather than on the sizing rules of the NEC where breakers and
cable are sized based on actual continuous load current divided by 80%. This
100% rating can save the user the cost of larger cable or bus bar. Please consult
the NEC for details and other design factors needed for this application.
PR211 LI S7HQ1000BW $ 8495
S7H 65kA PR212 LSI S7HQ1000CW 9684
PR212 LSIG S7HQ1000EW 11,664
1000A Frame (400 1000A adjustable continuous range)

Breaker
IC at Trip
Adjustment
3 pole List
480VAC type catalog number price
1200A Frame (480 1200A adjustable continuous range)
PR211 LI S7HQ1200BW $ 8495
S7H 65kA PR212 LSI S7HQ1200CW 9684
PR212 LSIG S7HQ1200EW 11,664
Discount schedule S7

Breaker
IC at Trip
Adjustment
3 pole List
480VAC type catalog number price
1 Consult factory.

L
Long time pick-up 0.4 1.0 0.4-0.5-0.55-0.6-0.65-0.7-0.75-0.8-0.85-0.875-0.9-0.925-0.95-0.975-1.0 x Frame rating PR212
Long time delay 3.0 18 sec. A - B - C - D

S
Short time pick-up 1.0 10.0 Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating
Short time delay 0.05 0.5 sec. A - B - C - D (I
2
t On-Off)
I Instantaneous trip 1.5 12.0 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating

G
Ground fault 0.2 1.0 Off-0.2-0.3-0.4-0.6-0.8-0.9-1.0 x Frame rating
Ground fault delay 0.1 0.8 sec. A - B - C - D
Trip settings

Adjustment
Trip
Range
Individual
function settings
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s

Type

Amps
Interruption Adjustment 2 pole List 3 pole List
capacity range catalog number price catalog number price
Molded case switches
Neutral current transformer (required for 4 wire GF sys tems)
S7
1200A, 600V
All S7 magnetic only breakers utilize the electronic PR211 trip unit with an
adjustable range of 1.5 to 12 times frame rating. Both two and three pole MCPs
are 600VAC rated.

Amps
Catalog List
number price
1000 K7NCT-1000
$ 250
1200 K7NCT-1200
Connection options

Type
Wire Amps Set of 2 List Set of 3 List
range 1 catalog number price catalog number price
CU/AL front lugs (4) 4/0 500kcmil 1200 K7TK-2 $ 120 K7TK $ 180
Extended front bar 1200 K7ET-1250 240
Magnetic only (MCP)

Type
Interruption
Amps
Magnetic 3 pole List
capacity 2 trip catalog number price
1 Suggested lugs for a circuit breaker up to amps shown. Cable size and type determine maximum amperage.
2 With fuse or MCCB protected circuit.
Set of 6
catalog number
240VAC 100kA
S7H
1000
480VAC 65kA
1500 12,000A S7H1000MW-2
$ 6959
S7H1000MW
$ 7724

1200
600VAC 50kA
1800 14,400A S7H1200MW-2

S7H1200MW

240VAC 100kA
S7H-D 480VAC 65kA 1000 20,000A S7H1000DW
600VAC 50kA 1200 20,000A S7H1200DW
$ 7300
600VDC 12kA
Non-UL, switches without
Withstand rating
1000 S7D1000W
overcurrent protection 600VAC 25kA 1250 S7D1250W
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.86 Low Voltage Products & Systems
Breaker catalog numbers
The breaker catalog number must be
completed. Please note that variations
can affect price.
unit includes cover to prevent tam per ing.
Front indicators for contact po si tion.
Uses convenient mounting pads for ease of
installation in enclosures.
Internal accessories are prewired to terminal block
mounted on right side of breaker.
Trip signal contact option indicates when breaker
has tripped due to overcurrent.
Canadian Standards As so ci a tion certication
under C22.2 No. 5 under File LR90467 for both
breakers and internal accessories.
In compliance with IEC947 in clud ing 690VAC.
Breakers are labeled with both UL/CSA and IEC
ratings.
Breakers are Underwriters Laboratories listed
under Standard UL 489 for molded case circuit
breakers per File E93565, internal accessories are
per File E116596.
Description
Insulated case type molded case circuit breaker
with manually operated stored energy mechanism.
Optional electric charging motor available
Three cycle closing time for use in generator
synchronizing applications.
Electric spring charging mech a nism rated for over
5,000 operations
Three different frame ratings, 1600, 2000 and
2500 amperes. All are same compact physical
size.
Solid state trip units are available in four different
congurations including adjustments for long
time, short time, instantaneous and ground fault.
Standard interrupting rating of 100kA at 480VAC.
Short time withstand rating of 35kA at 600VAC for
one second when breaker ordered with adjustable
short time trip.
Breaker includes charging handle for manual
energizing of closing/opening springs
Built-in ground fault (LSIG) for use with four-wire
systems requires neutral GF sensor. Meets NEC
ground fault requirements for service entrance
applications.
Internal accessories include electric charging
motor, shunt trips, a combination auxiliary/bell
alarm switch, and an undervoltage release.
Breakers are suitable for use in reverse feed
applications.
Wide range of adjustments on trip settings, trip
S8 2500A
S8
1600 / 2000 / 2500A
Insulated case circuit breaker
Catalog number information
Current
rating
16 - 1600A
20 - 2000A
25 - 2500A
Trip
C - LSI
E - LSIG
M - I
D - Molded
case switch

Connection scheme
W - Without con nec tors
R - Rear connectors, line & load
L - Cable terminals, line & load
D - Rear connectors, line side only
E - Rear connectors, load side only
S - Cable terminals, line side only
V - Cable terminals, load side only
H - Cable terminals, line side; rear connectors, load side
J - Rear connectors, line side; cable terminals, load side
M - K8TM lugs, line and load side
Closing coil
1 - 480VAC
2 - 240VAC
3 - 208VAC
4 - 120VAC
5 - 250VDC
6 - 125VDC
7 - 48VDC
8 - 24VAC/VDC
0 - None
Motor
2 - 240,208VAC/250VDC
4 - 120VAC/125VDC
7 - 48VDC
8 - 24 30 VAC/VDC
0 - None
Shunt trip
1 - 480VAC
2 - 240,208VAC/250VDC
3 - 24VAC/30VDC
4 - 120VAC/125VDC
7 - 48VAC/48VDC
8 - 24VDC
0 - None
UV release
1 - 480VAC
2 - 240VAC
4 - 120VAC
5 - 250VDC
6 - 125VDC
7 - 48VDC
8 - 24VDC
0 - None
Contacts
A - Aux switches
B - Trip Signal
P - Both
0 - None
S8V 16 E W X X X X X X
Frame size
Accessories
D - Locking button
device (open)
L - Key lock (open)
X - None
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Low Voltage Products & Systems 15.87
Three pole breakers are listed and approved for use in two pole applications with center-pole not connected.
2 Applies to MCS only.

Breaker

IC at 480VAC
Trip
Adjustment
Catalog List Catalog List Catalog List
type number price number price number price
3 pole, 600VAC maximum
1
Approximate dimensions
S8
1600 / 2000 / 2500A
Insulated case circuit breaker
LSI S8V16CW $ 12,540 S8V20CW $ 14,427 S8V25CW $ 21,561

S8V 100kA PR212
LSIG S8V16EW 14,505 S8V20EW 16,561 S8V25EW 24,487
I S8V16MW 11,267 S8V20MW 12,988 S8V25MW 20,916
MCS S8V16DW 9620 S8V20DW 10,999 S8V25DW 16,267
Description
Breaker is shipped complete with installed trip unit and accessories. Cable
terminals or rear T connectors can be included if desired. For four-wire systems
an external neutral ground fault sensor must be ordered separately.
Trip functions
L Long time pick-up and delay
S Short time pick-up and delay
I Instantaneous trip
G Ground fault pick-up and delay
Maximum continuous rating 1600A 2000A 2500A
Discount schedule S8
Catalog List
number price
1600A, S8 Frame
100% rated
S8VQ16CW $ 13,168
S8VQ16EW 15,231
S8VQ20CW $ 15,148
S8VQ20EW 17,390
2000A, S8 Frame
100% rated
Catalog List
number price
UL 100% equipment rated circuit breakers
Circuit breakers and cable are sized per the National Electric Code on a basis of
actual con tin u ous load current divided by 80%. For example, a 360 ampere load
should be connected by cable capable of handling 450 amperes (360A /0.80 =
450A) and therefore be protected by a 450 ampere rated circuit breaker. Other
factors may need to be considered when sizing breakers in special applications.
When applied correctly, UL-tested 100% equipment rated breakers may be ap-
plied at full rating, therefore saving the user the cost of larger cable or bus. Using
the example above, the 360 ampere load could be used with cable capable of
handling 360 amperes (360A /1.00 = 360A) and only a 400 ampere rated circuit
breaker (400A is next available size CB).
IEC-947 Interrupting capacity (kA RMS)
Voltage V
230VAC 120
300/400/415VAC 120
440VAC 100
500VAC 70
690VAC 50
UL/CSA Interrupting capacity (kA RMS)
UL489 / CSA C22.2
Voltage V
240VAC 125
480VAC 100
600VAC 85
600VDC
2
25
Continuous amperage settings (long time adjustment)
Frame Set points
0.4 0.5 0.6 0.7 0.8 0.9 0.95 1.0 Setting
1600A 640 800 960 1120 1280 1440 1520 1600 Amps
2000A 800 1000 1200 1400 1600 1800 1900 2000 Amps
2500A 1000 1250 1500 1750 2000 2250 2375 2500 Amps

L
Long time pick-up 0.4 1.0 0.4-0.5-0.6-0.7-0.8-0.9-0.95-1.0 x Frame rating PR212
Long time delay 3.0 18 sec. A - B - C - D

S
Short time pick-up 1.0 10.0 Off-1.0-2.0-3.0-4.0-6.0-8.0-10.0 x Frame rating
Short time delay 0.05 0.5 sec. A - B - C - D (I
2
t On-Off)
I Instantaneous trip 1.5 12.0 1.5-2.0-4.0-6.0-8.0-10.0-12.0 x Frame rating

G
Ground fault 0.2 1.0 Off-0.2-0.3-0.4 x Frame rating
Ground fault delay 0.1 0.8 sec. A - B - C - D
Trip settings

Adjustment
Trip
Range
Individual
function settings
15.75"
9.25" 15.98"
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.88 Low Voltage Products & Systems Discount schedule SA
S8
1600A, 2000A & 2500A
Accessories
Internal accessories
(Must be factory mounted for UL/CSA)
Factory installed List
Item Type
catalog number sufx price
Closing coil
Required for closing breaker electrically, the coil voltage must be specied at the
time of order entry.
Internal accessory ratings
Shunt trip All 100VA/120Watts
Undervoltage
AC/DC
30VA (12 Watts/
releases 10VA (4 Watts)
240VAC 10A Max.
Auxiliary contacts 125VDC 0.3A Max.
250VDC 0.15A Max
Closing coil AC/DC 30VA /40VA
Accessory
Voltage Rating
type

E.O. Type Inrush Normal Closing Opening Resetting
(VA) (watts) time time time
Stored energy electric motor operators
Mechanical life of 10,000 cycles at 20 operations per hour.
Item Type Catalog number List price
Connection accessories (includes sets of 3)
Note: Neutral GF CT required for proper GF operation.
Item Type Catalog number List price
Ground 1600A K8NCT-1600
Fault 2000A K8NCT-2000 $ 888
Neutral CT 2500A K8NCT-2500
Neutral ground fault current transformer
Item Catalog number List price
Door ange
Face plate K8FP $ 25
Cable terminals
1600A Max. 1/0 750kcmil (4) K8TL $ 274
2500A Max. 1/0 750kcmil (6) K8TM 315
Rear T conn. 2500A Max. K8RT2500 855
480VAC 1
240VAC 2
208VAC 3
Closing coil
120VAC 4

250VDC 5 $ 575
125VDC 6

48VDC 7
24VAC/VDC 8
Electric 240,208VAC
2

motor & 250VDC
(inc. spring 120VAC/125VDC 4 3217
charged signal 48VDC 7
contact) 24 30VAC/VDC 8
480VAC 1
240,208VAC
2
& 250VDC
Shunt trip 24VAC/30VDC 3
120VAC/125VDC 4
518
48VAC/48VDC 7
24VDC 8
480VAC 1
240VAC 2

Undervoltage
120VAC 4

release
250VDC 5 518
125VDC 6
48VDC 7
24VDC 8
Aux. contacts 2A/1B A 396
Trip signal 1A/1B B 192
Combo. aux. & 2A/1B Aux &
P 588
trip contacts 1A/1B Trip
Padlockable
button cover D 144
(open)
Key lock L 155
(open)
MS8
Stored
1000 230 0.05s 0.035s 9.0s
energy
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Low Voltage Products & Systems 15.89
Electrical accessories
Shunt trip, undervoltage release
S3 S7
K5S1
K5U1
K6C-SUP
480VAC/250VDC S1 K5S1 K7S1
240VAC S2 K5S2 K7S2
120VAC/125VDC S4 $ 430 K5S4 K7S4 $ 415
48VDC S7 K5S7 K7S7
24VAC/VDC S8 K5S8 K7S8
12VDC S9 K5S9 K7S9
Factory installation Field installation
Voltage Catalog number List Catalog numbers List
sufx 1 price adder S3 S4 S5 S6 S7 price
Discount schedule SA
S5 with K5S2
Shunt trips
24VDC SA
$ 430
K5SA K7SA
$ 415
120VAC SB K5SB K7SB
Factory installation Field installation
Voltage Catalog number List Catalog numbers List
sufx 1 price adder S3 S4 S5 S6 S7 price
Low power shunt trips
For remote opening of circuit breaker and includes internal cut-off switch to protect solenoid. All shunt trips are left pole
mounted and can not be used with UVRs. Except for 12VDC, all shunt trips are approved for use in GF systems. Shunt trips
must be ordered with correct connector.
480VAC U1 K5U1 K7U1
240VAC U2 K5U2 K7U2
120VAC U4 K5U4 K7U4
24VAC U3 $ 430 K5U3 K7U3 $ 415
250VDC U5 K5U5 K7U5
125VDC U6 K5U6 K7U6
48VDC U7 K5U7 K7U7
24VDC U8 K5U8 K7U8
Will trip CB when connected voltage drops to 35-70% of UVR voltage rating. Will allow CB to close (ON) when voltage is
approximately 85% of rated voltage. All UVRs are left pole mounted and can not be used with shunt trips. UVRs must be
ordered with correct connector.
Undervoltage releases
Factory installation Field installation
Voltage Catalog number List Catalog numbers List
sufx 1 price adder S3 S4 S5 S6 S7 price
Shunt trip connectors (required)
Fixed mounted All included K6C-SU K7C-SU
$ 15
Plug-in/Draw-out All included K6C-SUP K7C-SUP

V
24, 120, 240, 480VAC ~ 50/60 Hz
12, 24, 48, 125, 250 VDC
For S3-S5 100 VA~/120W
P Instantaneous duty
For S6-S7 150 VA~/150W
Electrical specications shunt trips (standard)

Type Factory

Field kit catalog number
circuit breaker
Voltage
installation 1 S3 S4 S5 S6 S7 List price
Undervoltage release connectors (required)
V
24, 120, 240, 480 VAC ~ 50/60 Hz
24, 48, 125, 250 VDC
For S3-S5 6 VA~/3W
P Continuous duty
For S6-S7 10 VA~/4W
Electrical specications UVR & low power shunt trips
Fixed mounted All included K6C-SU K7C-SU
$ 15
Plug-in/Draw-out All included K6C-SUP K7C-SUP

Type Factory

Field kit catalog number
circuit breaker
Voltage
installation
1
S3 S4 S5 S6 S7 List price
1 For factory installation add sufx given to end of circuit breaker catalog number per accessory format.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
1 For factory installation add sufx given to end of circuit breaker catalog number per accessory format.
2 Not UL approved for eld installation.
Electrical accessories
Auxiliary contacts
S3 S7
The auxiliary contacts are accessory contacts for the in di ca tion of circuit breaker open-closed or tripped. Bell alarm contacts
(B.A.) can be used to indicate circuit breaker tripping. All contacts are right pole mounted.
Auxiliary contacts S3 S7
2 Form Cs A $ 275 K5AS K7AS $ 260
1 BA & 1 C BA
365
K5BA K7BA
350
1 B BA & 1A+1B BA3 K7BA-3
Auxiliary contact connectors (required) S3 S7
N.O. = contact is open as circuit breaker is open
N.C. = contact is closed when circuit breaker is open
B.A. = will open/close only when circuit breaker trips
Voltage Maximum contact amperage rating
K6C-ABP
Fixed mounted All included K6C-AB K7C-AB
$ 15
Plug-in/Draw-out All included K6C-ABP K7C-ABP
Electrical specications
Factory installation Field installation

Contacts Catalog number List
Catalog numbers
List
sufx
1
price adder S3 S4 S5 S6 S7 price
Type Factory

Field kit catalog number
circuit breaker
Voltage
installation
1
S3 S4 - S5 S6 S7 List price
125 VDC 0.3 A
250 VDC 0.15 A
250 VAC 6 A
Discount schedule SA
K5AS
S5 with K6C-AB
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Type Field kit catalog number List
circuit breaker
Voltage
S3 S4 S5 price
240VAC/250VDC K5M2
120VAC/125VDC K5M4
$ 678
48VDC K5M7
24VDC K5M8
For remote control of circuit breaker opening and closing.
Complete with manual op er at ing lever, padlock device and emergency opening push-button.
When ordering the con nec tor always specify type and ver sion of the circuit-break er.
The following options are also available:
key lock for open position
key lock for open position of two or more circuit breakers (using the same key for groups of circuit breakers)
Motor operator
Motor operator connectors (required)

V
120, 240VAC ~ 50/60 Hz
24, 48, 125, 250 VDC
P inrush 500 VA~/500W
P normal 350 VA~/500W
Close time 0.1 s
Open time 0.1 s
Catalog number List
Voltage
S3 S4 S5 price
K5M2
K6C-M
Electrical accessories
Motor operators, stored energy motor operators
S3 S7
Electrical specications
Fixed mounted All K6C-M
$ 15
Plug-in/Draw-out All K6C-MP
K6M2
Type
Field kit catalog number
List
circuit breaker
Voltage
S6 S7 price
Stored-energy motor operator with springs automatically pre-loaded by motor.
Complete with shunt opening and closing release, and com part ment door ange.
When ordering the connector always specify type and version of the circuit-breaker.
The following options are also available:
key lock for open position
key lock for open position of two or more circuit-breakers (using the same key for groups of circuit-break ers).
Stored-energy motor operator
Stored-energy motor operator connectors (required)
240VAC/250VDC K6M2 K7M2
120VAC/125VDC K6M4 K7M4
$ 2407
48VDC K6M7 K7M7
24VDC K6M8 K7M8
Catalog number List
Voltage
S6 S7
price
Fixed mounted All K6C-M K7C-M
$ 15
Plug-in/Draw-out All K6C-MP K7C-MP
Electrical specications
Discount schedule SA

V
120, 240 VAC ~ 50/60 Hz
24, 48, 125, 250 VDC
P inrush 660 VA~/600W
P normal 180 VA~/180W
Close time 0.09 s
Open time 1.2 s
Reset time 2.0 s
S7 with K7M4
S4 with K5M2
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Standard cable lugs, for use on line and load side of circuit breaker. Suitable for use with Cu or Al. Special versions available
with taps and screws for control wire connection. Note: S6 and S7 lugs are Al9Cu (90C); all others Al7Cu (75C).
S3 60 14AWG 2AWG K3TA-2 $ 4 K3TA $ 6
S3 S4 100 14AWG 1/0 K4TB-2 4 K4TB 6
S3 S4 150 2AWG 4/0 K4TC-2 4 K4TC 6
S3 S4 S5 225 4AWG 300kcmil K4TD-2 10 K4TD 15
S4 250 6AWG 350kcmil K4TE-2 20 K4TE 30
S5 300 250kcmil 500kcmil K5TF-2 30 K5TF 45
S5 400 (2) 3/0 250kcmil K5TG-22 30 K5TG2 45
S6 600 (2)250kcmil 500kcmil K6TH-2 50 K6TH 75
S6 800 (3) 2/0 400kcmil K6TJ-22 90 K6TJ2 135
S7 1200 (4) 4/0 500kcmil K7TK-2 120 K7TK 180
Standard cable lug kits
Standard cable lug kits with control power taps
S3 S4 100 14AWG 1/0 K4TB-2C $ 8 K4TBC $ 12
S3 S4 150 2AWG 4/0 K4TC-2C 8 K4TCC 12
S3 S4 S5 225 4AWG 300kcmil K4TD-2C 14 K4TDC 21
S4 250 6AWG 350kcmil K4TE-2C 24 K4TEC 36
S5 300 250kcmil 500kcmil K5TF-2C 34 K5TFC 51
S5 400 (2) 3/0 250kcmil K5TG-2C2 34 K5TGC2 51
S6 600 (2) 250kcmil 500kcmil K6TH-2C 54 K6THC 81
S6 800 (3) 2/0 400kcmil K6TJ-2C2 94 K6TJC2 141
S7 1200 (4) 4/0 500kcmil K7TK-2C 124 K7TKC 186
Set of 2 Set of 3
For breakers Amps1
Wire
catalog
List
catalog
List

range
number
price
number
price
External accessories
Lugs and termination kits
S3 S7
K4ET-250
K4TES
K4TER
1 Suggested lugs for circuit breaker up to amps shown. Cable size and type determine maximum amperes.
2 Includes required lug covers.
K4TB
For adding onto standard circuit breaker front terminals, extending available connection area for user termination. Suitable
for spaded cable or bus connection. S3 S5 include terminal covers.
S3 S4 250 K4ET-250 $ 46
S5 400 K5ET-400 114
S6 630 K6ET-600 150
S6 800 K6ET-800 170
S7 1250 K7ET-1250 240
Extended front termination kits
Suitable for Maximum Set of 6 List
use with amps catalog number price
These special non-aluminum cable lugs are for use with copper cable. Lugs are intended for use with copper cable or where
non-aluminum connectors are required (marine, salt or corrosive environments).
S3 S4 250 14AWG 250kcmil K4TES $ 30
S5 400 250kcmil 500kcmil K5TGS 90
Saddle cable lug kits (Cu cable only)
Suitable for Max Wire Set of 6 List
use with amps range catalog number price
For use where cable connection from the back-rear of the breaker is desired.
Rear cable lug kits (Cu cable only)
S3 S4 250 6AWG 250kcmil K4TER $ 30
S5 400 250kcmil 500kcmil K5TGR 90
S6 600 (2) 2/0 350kcmil K6THR 150
S6 800 (3) 250kcmil 350kcmil K6TJR 170
Suitable for Max Wire Set of 6 List
use with amps range catalog number price
Set of 2 Set of 3
For breakers Amps1
Wire
catalog
List
catalog
List

range
number
price
number
price
Discount schedule SA
Distribution cable lug kit
S3 S4 250 (6) #14 - 6 K4TN $ 125
S5 400 (6) #14 - 1/0 K5TGD 240
Suitable for Max Wire Set of 3 List
use with amps range catalog number price
K4TN
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
External accessories
Rotary and variable depth handle operators
S3 S7
S3 S4 S5 K5RH $ 108
S6 K6RH 124
S7 K7RH 145
Rotary handle operating mechanism
Catalog List
Frame number price
K5RH
K5VD-M, K5VD-S12,
K5VD-H
Variable depth rotary handles

Frame
Catalog number List Shaft catalog number List Handle catalog number List
mechanism price (length in inches) price (length in inches) price
Pistol type 4, 4X
$ 24
S3S4S5 K5VD-M 49 26
OHB95J10 (3.7)
80
OXP10X148 (5.8) 32
OHG95J10 (3.7)

S6 K6VD-M 80
OXP10X225 (8.9) OHB125J10 (4.9)
90
OXP10X500 (19.7) OHG125J10 (4.9)

S7 K7VD-M 80
OHB175J10 (6.9)
100
OHG175J10 (6.9)
Discount schedule SH
Mounts directly onto breaker. Includes door interlock to prevent CB door opening while CB is in ON position. Pad lock
provision included to padlock CB in open position. Can also be key locked with optional cylinder lock assembly. Door
interlock bracket must be ordered separately, if required. See page 15.62.
New pistol type 1, 3R, 12
S3 S4 S5 K5VD-LSS $ 25
Variable depth shaft support

For frames
Catalog List
number price
NOTE: Complete assembly requires a mechanism, shaft and handle.

Frame
Catalog number List Shaft catalog number List Handle catalog number List
mechanism price (length in inches) price (length in inches) price
$ 24
S3S4S5 K5VD-M 49 26
OHB95L10 (3.7)
120
OXP10X148 (5.8) 32
OHG95L10 (3.7)

S6 K6VD-M 80
OXP10X225 (8.9) OHB125L10 (4.9)
130
OXP10X500 (19.7) OHG125L10 (4.9)

S7 K7VD-M 80
OHB175L10 (6.9)
140
OHG175L10 (6.9)
New pistol handle catalog number explanation
OHB 125 J 10
Color
B = black
G = gray
Y = yellow /red
Physical size (length in mm)
Shaft size (diameter in mm)
J = Type 1, 3R, 12
L = Type 1, 3R, 4, 4X, 12
OHB125J10
OHB65J10
OHB95J10
S3S4S5 K5VD-M 49 K5VD-S12 $ 24 K5VD-H $ 25
S6 K6VD-M 80 K7VD-S20 27 K7VD-H 28
S7 K7VD-M 80 K7VD-H 28
Square type 1
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
External accessories
Flange handle operators
S3 S6
1 Cable not included.
K7FHD-HS12
Available as complete kits including ange handle, shaft and breaker operating mechanism. Mechanism mounts directly onto
breaker and shaft can be cut to the desired length for the breaker enclosure. Door is interlocked with the handle when the
breaker is in the closed (ON) position; handles include interlock defeater for emergency override. Handle can be padlocked in
the open (OFF) position. Can be eld converted for left hand mounting.
Flange handle
Solid shaft linkage
K3FHD-12S12 240 K7FHD-S12 12 19
1,3R,12 K3FHD-17S12 248 K7FHD-S17 17 27 K7FHD-HS12 93

S3
K3FHD-22S12 255 K7FHD-S22 22.5 34
K3FHD-12S4 280 K7FHD-S12 12 19
4, 4X K3FHD-17S4 288 K7FHD-S17 17 27 K7FHD-HS4 133
K3FHD-22S4 295 K7FHD-S22 22.5 34
K4FHD-12S12 240 K7FHD-S12 12 19
1,3R,12 K4FHD-17S12 248 K7FHD-S17 17 27 K7FHD-HS12 93

S4
K4FHD-22S12 255 K7FHD-S22 22.5 34
K4FHD-12S4 280 K7FHD-S12 12 19
4, 4X K4FHD-17S4 288 K7FHD-S17 17 27 K7FHD-HS4 133
K4FHD-22S4 295 K7FHD-S22 22.5 34
K5FHD-12S12 240 K7FHD-S12 12 19
1,3R,12 K5FHD-17S12 248 K7FHD-S17 17 27 K7FHD-HS12 93

S5
K5FHD-22S12 255 K7FHD-S22 22.5 34
K5FHD-12S4 280 K7FHD-S12 12 19
4, 4X K5FHD-17S4 288 K7FHD-S17 17 27 K7FHD-HS4 133
K5FHD-22S4 295 K7FHD-S22 22.5 34
K6FHD-12S12 523 K7FHD-S12 12 19
1,3R,12 K6FHD-17S12 531 K7FHD-S17 17 27 K7FHD-HS12 93

S6
K6FHD-22S12 538 K7FHD-S22 22.5 34
K6FHD-12S4 563 K7FHD-S12 12 19
4, 4X K6FHD-17S4 571 K7FHD-S17 17 27 K7FHD-HS4 133
K6FHD-22S4 578 K7FHD-S22 22.5 34
NEMA Complete List Mechanism List Shaft Shaft List Handle List
Breaker
type handle kit price only price only length price only price
Discount schedule SH
Door hardware kits Solid shaft linkage & cable operated

Item
Catalog List
number price
Door hardware kit, right hand, 2 point latch for enclosures less than 40 inches high FH-DHK $ 150
Roller for 3 point latch, add to FH-DHK FH-3RL 30
Enclosure depths
Minimum
Breaker Depth (inches)
S3 - S5 10
S6 11
Maximum
For maximum depth, add 4 inches to the shaft length
K3FHD-M 128
K4FHD-M 128
K6FHD-M 411
K5FHD-M 128
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Low Voltage Products & Systems 15.95
External accessories
Flange handle operators
S3 S7
Flange handle
Cable linkage
Notes: For complete assembly; mechanism, cable and handle are required.
All cables mount onto the right side of the breaker.
Handle can be mounted on the right or left side.

Breaker
NEMA Mechanism List Cable Cable List Handle List
type only price only length price only price
K7FCH
Enclosure depths
Minimum
Breaker Depth (inches)
S3 - S6 8
S7 10
Maximum
Maximum depth is determined by cable length.
Discount schedule SH

1,3R,12 K4FPM 110

K5FCH 213

S3-S4


4, 4X K4FPM 110

K5FCH4 243


1,3R,12 K5FPM 128

K5FCH 213

S5


4, 4X K5FPM 128

K5FCH4 243


1,3R,12 K6FPM 220

K7FCH 310

S6


4, 4X K6FPM 220

K7FCH4 415


1,3R,12 K7FPM 220

K7FCH 310

S7


4, 4X K7FPM 220

K7FCH4 415

K7C048 48 (122cm) 190
K7C060 60 (152cm) 220
K7C072 72 (183cm) 256
K7C084 84 (213cm) 270
K7C096 96 (244cm) 320
K7C120 120 (305cm) 350
K5C036 36 (91cm) 114
K5C048 48 (122cm) 146
K5C060 60 (152cm) 160
K5C072 72 (183cm) 175
K5C084 84 (213cm) 204
K5C096 96 (244cm) 221
K5C108 108" (274cm) 238
K5C120 120" (305cm) 256
Door hardware kits S3 - S7 Cable operated

Item
Catalog List
number price
Door hardware kit, right hand, 2 point latch for enclosures less than 40 inches high KDH2R $ 200
Door hardware kit, right hand, 3 point latch for enclosures 40 inches high or greater KDH3R 225
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
S3 K3DMB $ 24
S4 K4DMB 26
S5 K5DMB 38
Kit consists of mounting bracket to x S3-S5 breakers onto 75mm DIN rail (EN 50023 rail) and includes 45mm high front face
plate to match up with miniature circuit breakers and manual motor starters. S1 breaker mounts on 35mm DIN rail.
DIN rail mounting kits

Suitable for use with breakers
Catalog List
number price
S3 S4 S5 K5LD $ 14
S6 K6LD 16
S7 K7LD 20
S3 S4 S5 K5LDW 1 14
S6 K6LDW 1 16
S7 K7LDW 1 20
Mounts directly onto front of CB. Includes padlock device for locking CB in open po si tion. Can be used as a manual handle
block, with padlock or with optional key lock accessory. Op tion al door interlock kit that will prevent CB door from opening
while CB is in the closed (ON) position.
Front locking device

Item
Catalog List
number price
External accessories
S3 S7
Bracket K7DB $ 5
Door interlock bracket
Catalog number List
Item S3 S7 price

Suitable for use with breakers
Used with List
LC covers price
These screws prevent the terminal covers from being removed.
Terminal cover seals
S3 S4 S5 S6 K6LC-S $ 5
K5LD
K7KL
K6LC
K6LCH
K6LC-S
K3DMB
S3 S4 K4LC 8 K4LCH $ 16
S5 K5LC 12 K5LCH 24
S6 K6LC 18 K6LCH 32
S7 K7LC 40
Both high and low types are available for xed circuit-breakers. Covers provide IP40 degree of protection for xed mounted
circuit breakers. Lug covers are required and included as standard with S5 400A and S6 800A cable lug kits. Covers up to S6
can be sealed with lug cover seal shown in next section.
Terminal covers for xed circuit breakers

Frame
Low prole List High prole List
catalog number price catalog number price
Provides for mounting of two similar breakers on a single mounting plate. CBs are interlocked via a walking beam type
interlock, preventing breakers from being ON or closed at the same type. Both breakers can be OFF or tripped. MIP is
available in two versions, one with breakers mounted horizontally and then also a version for vertical mounting of breakers.
Mechanical interlock plate

Frame
Horizontal List Vertical List
catalog number price catalog number price
S3 K3MI-H $ 570 K3MI-V $ 570
S4 K4MI-H 570 K4MI-V 570
S5 K5MI-H 590 K5MI-V 590
S6 K6MI-H 620 K6MI-V 620
S7 K7MI-H 630 K7MI-V 630

Electric operator
different K5KL-EO K7KL-EO
same K5KL-EO-2 K7KL-EO-2
$ 25

Rotary HM & locking device
different K7KL K7KL
same K7KL-2 K7KL-2
Keyed cylinder locks are available for mounting onto Isomax electric operators, rotary handle mechanisms and front locking
devices. Key locks can be for one individual circuit breaker (different keys in each order) or for two circuit breakers using the
same key.
Key locks

Accessory Keys

Catalog number
List
S3 S4 S5 S6 S7 price
Discount schedule SA
1 Required for drawout breakers.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Provides means to connect breakers directly onto rear bus bars.
S3 S4 250 K4RC $ 87
S5 400 K5RC 225
S6 800 K6RC 280
S7 1200 K7RC 340
Accessories
S3 S7
IEC
Rear connected stud kits1
For Max. Set of 6 List
breakers amps catalog number price
K4RC
Rear plug-in & drawout
circuit breakers
K7TUT
Isomax breakers are available in both rear plug-in and complete draw-out congurations. Plug-in breakers can be rear bus,
front bus or front cable connected and are available up to the S5 400A size. The draw-out conguration uses a unique
rack ing system and is available for all breakers from S3 through S7.
Rear plug-in and draw-out circuit breakers
Plug-in (3 pole)1
S4 S5 S6 S7 K7TUT $ 210
Hand-held test kit (for all electronic trip types)
Isomax Catalog List
frames number price
Isomax hand-held test kit is used to both test and exercise mi cro pro ces sor trip units in breakers S4 through S7. Unit includes
test forks that insert into the test plugs on all Isomax mi cro pro ces sor trip units. Tester gen er ates 15VDC signal that per forms
diagnostic on electronic trip func tions and will conrm test by tripping the CB. Will not test S3 nor any molded case switch
versions.
Four pole versions (plug-in and/or draw-out)
Take the above list prices times 1.35 for four (4) pole versions and add "-4" to the end of the catalog number.
S3 K4FCT $ 72
S4 K4FCT 72
S5 K5FCT 86
Frame Set of 6 List price
Cable termination kits (3 pole only)1
Compression type cable lug kit used to modify extended front bus connectors for direct cable connection.
Movable kit = parts needed to modify standard CB to movable type.
Fixed base kit = x mount onto panel.
Ext Fr bus = xed base with line and load side extended front bus connectors. (FF)
Rear Conn. = xed base with line and load side rear bus connectors. (FR)
Complete kit = includes all parts required for plug-in or draw-out connection; does not include CB.
Plug-in = open breaker can be physically removed from xed base without disconnecting cable or bus from xed base. (P)
Draw-out = also known as withdrawable, breaker can be removed from xed base via a through the door crank. Includes
ON, TEST and OFF position. (W)
Draw-out (3 pole) 13
S3 K4PMK 203 K3PFF 190 K3PFR 230 K3PF 393 K3PR $ 433
S4 K4PMK 203 K4PFF 203 K4PFR 243 K4PF 406 K4PR 446
S5 K5PMK 238 K5PFF 278 K5PFR 278 K5PF 516 K5PR 516
Separate kits xed and movable Complete plug-in kits
Movable kit Fixed base kit Includes both xed and movable portion
Frame Movable List price Front bus List price Rear conn. List price Front bus List price Rear conn. List price
S3 S7 K7WCR $ 20
Draw-out crank
Isomax Catalog List
frames number price
1 IEC ratings only.
2 Front cable connection.
3 Requires front locking device to prevent drawout while breaker is closed.
Discount schedule SA
S3 K4WMK $ 203 K3WFF $ 230 K3WFR $ 270 K3WF $ 433 K3WR $ 473
S4 K4WMK 203 K4WFF 283 K4WFR 323 K4WF 486 K4WR 526
S5 K5WMK 278 K5WFF 318 K5WFR 318 K5WF 596 K5WR 596
S6 Horiz K6WMK 523 K6WFF 1346 K6WFR-H 1346 K6WF 1869 K6WR-H 1869
S6 Vert K6WMK 523 K6WFF 1346 K6WFR-V 1346 K6WF 1869 K6WR-V 1869
S7 Horiz K7WMK 821 K7WFF 2111 K7WFR-H 2111 K7WF 2932 K7WR-H 2932
S7 Vert K7WMK 821 K7WFF 2111 K7WFR-V 2111 K7WF 2932 K7WR-V 2932
Separate kits xed and movable Complete draw-out kits
Movable kit Fixed base kit Includes both xed and movable portion
Frame Movable List price Front bus List price Rear conn. List price Front bus List price Rear conn. List price
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.98 Low Voltage Products & Systems
Enclosures
Type 1 & 3R/12
Discount schedule SE
Description
Type 1
General purpose indoor enclosure intended for use in normal
environments to provide a degree of protection against contact with
enclosed equipment.
Sheet steel, surface mount.
Breaker is front-operable and can be padlocked via front hasp.
Available through 2500A, 600VAC
UL Listed for use as service entrance equipment (SUSE), per UL le
E116374.
Type 3R/12
Type 3R is intended for outdoor use providing protection against
rain, sleet or snow.
Type 12 is for use in indoor atmospheres to provide a degree of
protection against circulating dust, lint, sawdust, falling dirt and
dripping non-corrosive liquids.
Surface-mounted, sheet steel enclosure.
Breaker can be operated via separately ordered handle
mechanism; door is interlocked with mechanism.
Available through 2500A, 600VAC.
UL Listed for use as service entrance equipment (SUSE), per UL le
E116374.
Type 7/9
Cast from copper-free aluminum (max. 0.025 copper content)
Stainless steel shotblasted or sandblasted natural nish
Standard conduit openings in top and bottom
Breaker is operated from front handle and can be padlocked
NEC Class I Groups D, Div. 1 & 2
NEC Class II Groups E, F & G, Div 1 & 2
NEC Class III
External machined ange joint design
Integral cast mounting feet
Machined ange for ease of hinge installation
Ground lug
Cast mounting pan bosses
All enclosures suitable for drilling & tapping
UL panel listed per UL File #E183868
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Enclosures
Type 1 & 3R/12
Enclosures (Price does not include circuit breaker; order as a separate item.) 4
NEMA Breaker Enclosure maximum rating Approximate dimensions1 Catalog List
designation type AL cables CU cables H x W x D (inches) number price
S3 150A 225A 22 x 12 x 4.5 S3E-1 235
S4 225A 250A 30 x 17.5 x 4.5 S4E-1 305
Type 1 S5 400A 400A 30 x 17.5 x 4.5 S5E-1 305
S6 800A 800A 44 x 22 x 6 S6E-1 685
S7 1000A 1200A 44 x 22 x 6 S7E-1 685
S8 2500A 2500A 88 x 36 x 24 S8ES250-1 5285
S1 100A 100A 14 x 10 x 8.8 S1E-3R12 305
S2 2 125A 125A 16 x 11 x 8 S2E-3R12 305
S3 150A 225A 22 x 12 x 9 S3E-3R12 395
S4 225A 250A 30 x 17.5 x 9 S4E-3R12 575
Type 3R/123 S5 400A 400A 30 x 17.5 x 9 S5E-3R12 575
S6 800A 800A 44 x 22 x 11 S6E-3R12 905
S7 1000A 1200A 44 x 22 x 11 S7E-3R12 905
S8 2500A 2500A 88 x 36 x 24 S8ES250-3R12 5285
1 Enclosures may not meet size requirement for UL 100% rated breakers.
2 Not UL approved.
3 Variable depth rotary handle must be ordered separately (S1 - S7).
4 Consult ABB for breakers installed in enclosures.
Discount schedule SE
S3E-1 S4E-3R12 3
Breaker Neutral cable capacity Neutral kit List
type and wire range catalog number price

S3
Neutral #6-250 kcmil
S3NK225 135
Bonding Lug #14-1/0

S4
Neutral #6-250 kcmil
S4NK250 155
Bonding Lug #14-1/0 kcmil

S5
Neutral (2) #6-250 kcmil
S5NK400 260
Bonding Lug #14-1/0 kcmil

S6
Neutral (2) #2-600 kcmil
S6NK800 350
Bonding Lug #6-250 kcmil

S7
Neutral (4) #2-600 kcmil
S7NK1200 535
Bonding Lug #6-250 kcmil

S8
Neutral (6) #1/0-750 kcmil
included
Bonding Lug (2) #2-600 kcmil
Neutral kits
NOTE: The list price adder for factory installation of an enclosed circuit breaker is 50% of the enclosure list price.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Additional options
Explosion-proof enclosures
(Price does not include circuit breaker; order as a separate item for factory assembly.)
NEMA Breaker Enclosure Approximate dimensions Catalog number List price
designation type max. rating H x W x D (inches) sufx adder
S3 Cu only 100A 17 x 10 x 8.65 7 $ 2100
S3 Cu only 225A 22.5 x 11.5 x 8.77 7 2850
S4 Cu only 250A 25 x 18 x 9.92 7 4700
Type 7/9 S5 Cu only 400A 30 x 17 x 9.25 7 6600
S6 Cu only 600A 35 x 17 x 11 7 8600
S6 Cu only 800A 41 x 17 x 11 7 10,450
S7 Cu only 1200A 51 x 17 x 13 7 22,450
Enclosures
Type 7/9
S5N400BW7
S3 Cu only 100A -X $ 130 -S $ 20 -B $ 145 -D
S3 Cu only 225A -X 145 -S 25 -B 170 -D
S4 Cu only 250A -X 145 -S 45 -B 355 -D
Type 7/9 S5 Cu only 400A -X 175 -S 60 -B 415 -D $ 110
S6 Cu only 600A -X 250 -S 60 -B 465 -D
S6 Cu only 800A -X 315 -S 60 -B 535 -D
S7 Cu only 1200A -X 430 -S 80 -B 600 -D
NEMA 4XStainless steel boltsCaptive boltsDrain
NEMA Breaker Enclosure Cat. no. List price Cat. no. List price Cat. no. List price Cat. no. List price
designation type max. rating adder adder adder adder adder adder adder adder
S4 N 250 B W 7 - 2 xxx
Catalog number information Type 7/9
Frame size
S3 = 150 /225A
S4 = 250A
S5 = 400A
S6 = 600 /800A
S7 = 1200A
Interrupting rating class
B = Basic (240VAC)
N = Normal
H = High
L = Extra high
D = Special molded case switch
Type connectors
W = None L = Lugs
Current rating
015 = 15A
250 = 250A
400 = 400A
600 = 600A
800 = 800A
1200 = 1200A
Trip unit function
B = LI F = LSIG/K
C = LSI H = LSIG/D
D = Molded case switch (MCS) J = LSIG/DT
E = LSIG K = LSIG/DTK
T = Thermal-magnetic M = Magnetic only (MCP)
NEMA enclosure 7/9
Number of poles
-2 = 2 pole
-4 = 4 pole
None = 3 pole
Accessories (added in alpha-numeric order)
A = Auxiliary switch
B = Captive bolts
BA = Bell alarm
BA3 = Bell alarm (S6/S7 only)
D = Breather/drain
H = Fixed rotary handle mounted on CB
S_ = Shunt trip with voltage code
S = Stainless steel bolts
U_ = Undervoltage release with voltage code
X = NEMA 7/9/4X
To order a breaker in an explosion-proof enclosure, add the sufx "7" to the end of the catalog number and add the list price adder to the list price
of the breaker.
Example: S5N400BW7
S5N400BW breaker ............... $ 2151
Explosion proof enclosure ........ 6600
Total ....................................... $ 8751
To add additional options, simply add the sufx to the end of the catalog number.
Example: S5N400BW7XSD
S5N400BW breaker ............... $ 2151
Explosion proof enclosure ........ 6600
NEMA 4X .................................... 175
Stainless steel bolts ...................... 60
Drain ........................................... 110
Total ....................................... $ 9096
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Low Voltage Products & Systems 15.101
Enclosures
Approximate dimensions
S3 S7, NEMA 1, 3R & 12
NEMA 1
NEMA 3R, 12
A
FRONT vlEW
B
SlDE vlEW
C
SECTlON
E
D
F
4-MTG. HOLES
FRONT vlEW
HAZARDOUS vOLTAGES ARE LOCATED lNSlDE
HAZARD OF ELECTRlCAL SHOCK OR BURN
DlSCONNECT POWER BEFORE WORKlNG ON THlS EQUlPMENT
DANGER
Y 6917 1000-061
B
A
SlDE vlEW SECTlON
F
4-MTG. HOLES
SACE S5
on
off D
E C
Cat. # A B C D E F
S3E-1
22.0
559.0
12.0
305.0
4.25
108.0
19.0
482.0
9.0
229.0
0.312
7.93
S4E-1
30.0
762.0
17.5
444.5
4.25
108.0
27.0
686.0
14.5
368.5
0.312
7.93
S5E-1
30.0
762.0
17.5
444.5
4.25
108.0
27.0
686.0
14.5
368.5
0.312
7.93
S6E-1
44.0
1118.0
22.0
559.0
5.75
146.0
41.0
1041.5
19.0
483.0
0.312
7.93
S7E-1
44.0
1118.0
22.0
559.0
5.75
146.0
41.0
1041.5
19.0
483.0
0.312
7.93
Cat. # A B C D E F
S3E-3R12
22.0
559.0
12.0
305.0
8.8
224.0
20.5
520.5
10.5
267.0
0.50
13.7
S4E-3R12
30.0
762.0
17.5
444.5
8.8
224.0
28.5
724.0
16.0
406.5
0.50
13.7
S5E-3R12
30.0
762.0
17.5
444.5
8.8
224.0
28.5
724.0
16.0
406.5
0.50
13.7
S6E-3R12
44.0
1118.0
22.0
559.0
10.8
274.5
42.5
1080.0
20.5
521.0
0.50
13.7
S7E-3R12
44.0
1118.0
22.0
559.0
10.8
274.5
42.5
1080.0
20.5
521.0
0.50
13.7
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.102 Low Voltage Products & Systems
Enclosures
Approximate dimensions
S8, NEMA 1, 3R & 12
CONDUIT
ENTRY SPACE
(16.2 X 28.0)
FRONT ELEVATION
( DOOR CLOSED )
CIRCUIT
BREAKER
ESCUTCHEON
CUT-OUT
TYPE 1 ONLY
FRONT
REAR
LEFT RIGHT
TOP VIEW
ENCLOSURE ROOF
(SOLID REMOVABLE ROOF PANEL)
BOTTOMVIEW
ENCLOSURE FLOOR
(SOLID NON-MOVABLE FLOOR PANEL)
0.50 DIA.
MTG. HOLES
( QTY. 4 )
FRONT
REAR
LEFT
RIGHT
CONDUIT
ENTRY SPACE
(28.0 X 13.8)
SILL CHANNEL
SILL CHANNEL
ABB
35.8
909
2.0
51
87.4
2220
1.5
38
2.0
51
4.0 x 1.5 INCHES
103 38
SILL CHANNEL
24.0
610
35.1
892
23.8
605
3.8
97
3.8
97
3.6
91
35.79 (OVER ALL)
909
26.73
679
4.53
115
4.53
115
4.00
102
5.00
127
13.8
351
5.00
127
5.20
132
3.9
99
3.36
85
15.09
383
23.80
605
711 351
411 711
13
3.36
85
21.81
554
16.2
411
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Low Voltage Products & Systems 15.103
Protective releases
Thermal-magnetic overcurrent release
Time-current curves, S3
1 Direct current may shift tripping characteristic. Consult ABB.
S3, R15 S3, R20-R30
S3, R35-R50 S3, R50-R100
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100
x Ith
t [s]
2
2000
200
20
R15
0,01
0,1
1
10
100
1000
10000
0,1 1 10 100
x Ith
t [s]
2
2000
200
20
R20
R25
R30
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100
xIth
t [s]
2
2000
200
20
R40
R50
R35
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100
x Ith
t [s]
2
2000
200
20
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.104 Low Voltage Products & Systems
Protective releases
Thermal-magnetic overcurrent release
Time-current curves, S3
S3, R125-R225 10X Im S3, R150-R225 3X Im
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100
x Ith
t [s]
2
2000
200
20
0.01
0.1
1
10
100
1000
10000
0.1 1 10 100
x Ith
t [s]
2
2000
200
20
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Low Voltage Products & Systems 15.105
Trip curves for distribution
Circuit breakers w/thermomagnetic trip units
Isomax S5 & S6
Consult factory
S5 400 TMD
In = 300 - 400 A
I
3
= 2.5 In
S5 400 TMD
In = 300 - 400 A
I
3
= 5 10 In
Consult factory
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.106 Low Voltage Products & Systems
Trip curves for distribution
Circuit breakers w/thermomagnetic trip units
Isomax S6
S6 600 TMD
In = 800 A
I
3
= 5 10 In
S6 800 TMD
In = 800 A
I
3
= 2.5 In
t [s]
1
x I1
10
10
-1
10
-2
10
2
1
10
10
2
10
3
10
4
10
-1
600A
t [s]
1
x I1
10
10
-1
10
-2
10
2
1
10
10
2
10
3
10
4
10
-1
800A
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Low Voltage Products & Systems 15.107
Trip curves for distribution
Circuit breakers w/thermomagnetic trip units
Isomax S6
S6 800 TMD
In = 800 A
I
3
= 5 10 In
t [s]
1
x I1
10
10
-1
10
-2
10
2
1
10
10
2
10
3
10
4
10
-1
800A
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.108 Low Voltage Products & Systems
Protective releases
Microprocessor trip release
S4, S5, S6, S7, S8
The microprocessor based overcurrent relays (actual RMS) for Isomax S circuit-
breakers offer a wide range of current and trip time settings.
They are available in two versions:
PR211/P with overcurrent protection Land instant short circuit protection I.
Available with functions L, I, or L+I. L function includes adjustable long-time
pick-up and long-time delay.
PR212/P with overcurrent protection L, selective short circuit protection S,
instant short circuit protection Iand ground fault protection G. Available with
functions L+S+Ior L+S+I+G. Functions S, Iand Gcan be excluded
manually by means of the trip current threshold selector (OFF position). In its most
complete conguration, i.e. with functions L+S+I+G, the PR212/P relay can be
combined, on request, with the following units:
PR212/D dialog unit
Essential for two-way communication with electrical plant management systems.
When the unit is present, it is possible to choose between the manually set
parameters (LOC), and the parameters set by the electrical plant control system
(REM) by means of the appropriate selector. The dialog unit must be supplied
with an auxiliary voltage of 24 V d.c.
The following information is made available through the dialog unit on the eld
bus:
protection parameters
current values of phases, neutral and ground
circuit-breaker state
number of operations of circuit-breaker
interrupted currents
state of the overcurrent relay with indication of:
- normal operation
- pre-alarm (0.9 x I1)
- overcurrent function L
- trip function S
- trip function I
- trip function G.
It is possible to provide and/or modify the protection parameters and the circuit-
breaker opening/closing controls. In the event of a serial communication error, the
overcurrent relay operates in accordance with the last parameters set and in any
event always in accordance with the manually programmed setting. The same
occurs in the event of a dialog unit fault, and in the absence of auxiliary supply.
The dialog unit is external for circuit breakers S4 and S5 and is located inside the
relay box for circuit breakers S6 and S7.
The external dialog unit is connected by means of a cable for supply and
communication with the PR212/P protection relay.
The standard version of the dialog interface has the following specications:
hardware: EIA RS485 serial transmission line
communication protocol: ABB Modbus
transmission speed: 150 19200 baud (bit/s).
PR212/K signalling unit
Can be connected directly to the PR212/P protection relay and provides contacts
for the protection unit trip and alarm signals: pre-alarm, overcurrent function L,
trip functions S, Iand G, trip by relay and internal communication error with
PR212/P.
PR212/T actuator unit
Can be installed only if the dialog unit is present, and by means of suitable
relays, controls the opening and closing of the circuit-breaker. In order that
opening and closing can be actuated, the circuit-breaker must be equipped with a
motor operator (direct-acting for S4 and S5; stored energy type for S6 and S7).
Note
The K and T units are always external.
Other important features of the microprocessor based relays are as follows:
protection of neutral with programmable automatic adjustment, executed
by the manufacturer, to 50% (standard) or 100% (on request) of the current
value selected for the phases. The optional version has no code in this
catalog;
reliable operation also when one phase only is live;
individual and simultaneous adjustment on the three phases and neutral;
no need for auxiliary supply;
trip specications not affected by the ambient temperature;
consistency of specications and reliability including in contaminated
environments;
signalling of tripped relay (available for all versions) by means of voltage-free
contact for 24 V d.c. or a.c. circuits maximum 3 W.
Circuit-breaker rated current change according to ambient temperature. The
tripping characteristics of Isomax S4 S8 with electronic trip units are unaffected
by ambient temperatures from -25C to +70C.
Microprocessor based overcurrent relays for alternating current for S4, S5, S6 and S7 circuit-breakers
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Rated and setting currents
PR211
Key
1 Dip-switch for function L setting (I1)
2 Dip-switch for function I setting (I3)
3 Rated current of current transformers
4 15 V d.c. input for release functioning check
5 Function L trip time setting dip switch (T1)
Protective releases
Microprocessor based overcurrent relays, PR211
for S4, S5, S6 & S7 breakers
Protection against Trip Symbol Set values (manual adjustment in steps)

Overload Long delay L
I1 = 0.4-0.5-0.6-0.7-0.8-0.9-0.95-1 x In
t1 = 4 curves A,B,C,D
Short-circuit Instantaneous adjustment I I3 = 1.5-2-4-6-8-10-12 x In
Protective functions and set values
1
5
2 3 4
S4 250
100 40 100 150 1200
250 100 250 375 3000

S5 400
300 120 300 450 3600
400 160 400 600 4800

S6 600/800
600 240 600 900 7200
800 320 800 1200 9600

S7 1200
1000 400 1000 1000 12,000
1200 480 1200 1800 14,400
Circuit-breaker Current transformer Functions

Iu-A In-A
L (I1) I (I3)
A (0.4 1 x In) A (1.5 12 x In)
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.110 Low Voltage Products & Systems
Protective releases
Microprocessor based overcurrent relays, PR211
Time-current curves, S4 S7
Function L - I
Key
In = Rated current of current transformers
t = Tripping time
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Protection functions and set values
Key
1 Function L setting dip-switch (I1)
2 Function L trip time setting dip-switch (t1)
3 Function S setting dip-switch (I2)
4 Function S trip time setting dip-switch (t2)
4b Fixed/variable trip time selection dip-switch
5 Function I setting dip-switch (I3)
6 Function G setting dip-switch (I4)
7 Function G trip time setting dip-switch (t4)
8 Rated current of current transformers
9 15 V d.c. input for release functioning check
10 Socket for connecting SACE PR010/T test unit
Protective releases
Microprocessor based overcurrent relays, PR212
Protection functions and set values, S4 S8
Protection against Overload Short-circuit Short circuit Earth fault
Trip Long delay Inverse or denite short delay Instantaneous adjustable Inverse short delay
Symbol L S I G 1
Set values
I1 = 0.4-0.5-0.55-0.6-0.65-0.7-0.75

I2 = 1-2-3-4-6-8-10

I4 = 0.2-0.3-0.4-0.7-0.8-0.9-1
(manual
0.8-0.85-0.875-0.9-0.925-0.95-0.975-1 x In

OFF x In
I3 = 1.5-2-4-6-8-10-12
adjustment
t1 = 4 curves A D

t2 = 4 curves A D
t4 = 4 curves A D
in steps
Set values
I1 = 0.4 - 1 x In

I2 = 1 10 OFF x In

I4 = 0.2 1 OFF x In
(electronic
t1 = 3 - 18s

t2 = 0.05 0.5
I3 = 1.5-12 OFF x In
t4 = 0.1 0.8s
adjustment)
PR212
1 S8 it = 0.2 - 0.4
1 3 5 6
8 2 9 4
4b
7 0
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Protective releases
Rated and setting currents, PR212
S4 S8
Rated and setting currents
Key
Iu = Rated uninterrupted current of circuit-breaker
In = Rated current of current transformers
I1 = Current setting value for relay overload protection
I2 = Current setting value for relay short-circuit selective protection
I3 = Current setting value for relay instantaneous short-circuit protection
I4 = Current setting value for earth fault protection
Circuit Current
Functions
breaker transformer

Iu In-A
L(I1) S (I1) I (I3) G (I4)
A (0.4 1.0 x In) A (1 10 x In) A (1.5 12 x In) A (0.2 1 x In) /S8 (0.2 0.4)

S4 250
100 40 100 100 .1000 150 1200 20 100
250 100 250 250 .2500 375 3000 50 250
S5 400
300 120 300 300 .3000 450 3600 60 300
400 160 400 400 .4000 600 4800 80 400
S6
600 600 240 600 600 .6000 900 7200 120 600
800 800 320 800 800 .8000 1200 9600 160 800
S7 1200
1000 400 1000 1000 .10,000 1500 12,000 200 1000
1200 480 1200 1200 .12,000 1800 14,400 240 1200
1600 640 1600 1600 .16,000 2400 19,200 320 640
S8 1600 2500 2000 800 2000 2000 .20,000 3000 24,000 400 800
2500 1000 2500 2500 .25,000 3750 30,000 500 1000
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Low Voltage Products & Systems 15.113
Function L - S - I
Key
In = Rated current of current transformers
t = Tripping time
Protective releases
Microprocessor based overcurrent relays, PR212
Time-current curves, S4 S8
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
15.114 Low Voltage Products & Systems
Function L - S - I
Protective releases
Microprocessor based overcurrent relays, PR212
Time-current curves, S4 S8
Key
In = Rated current of current transformers
t = Tripping time
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Function G
1

Key
In = Rated current of current transformers
t = Tripping time
Protective releases
Microprocessor based overcurrent relays, PR212
Time-current curves, S4 S8
1 S8 maximum setting is 0.4 per NEC guidelines.
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Motor horsepower ratings
Magnetic trip
1/2HP @ 575V to 100HP @ 575V

Horsepower per NEC 430-50
Motor full Isomax MCP
Approximate trip setting % of MFLA
208V 230V 460V 575V Load amps Type Rating 1.5X 2X 4X 6X 8X 10X 12X
% % % % % % %
1/2 0.9 S3 3 1300 2000 2700 3400 4000
1/2 1.1 S3 3 1100 1600 2200 3700 3300
3/4 1.3 S3 3 900 1400 1800 2300 2800
3/4 1.6 S3 3 800 1100 1500 1900 2300
1 1.7 S3 3 700 1100 1400 1800 2100
1 2.1 S3 5 1000 1400 1900 2400 2900
1/2 2.2 S3 5 900 1400 1800 2300 2700
1/2 1 1/2 2.4 S3 5 800 1300 1700 2100 2500
2 2.7 S3 5 700 1100 1500 1900 2200
1 1/2 3 S3 5 700 1000 1300 1700 2000
3/4 3.2 S3 5 600 900 1300 1600 1900
2 3.4 S3 5 600 900 1200 1500 1800
3/4 3.5 S3 10 1100 1700 2300 2900 3400
3 3.9 S3 10 1000 1500 2100 2600 3100
1 4.2 S3 10 1000 1400 1900 2400 2900
1 4.6 S3 10 900 1300 1700 2200 2600
3 4.8 S3 10 800 1300 1700 2100 2500
1 1/2 6 S3 10 700 1000 1300 1700 2000
5 6.1 S3 10 700 1000 1300 1600 2000
1 1/2 6.6 S3 10 600 900 1200 1500 1800
2 6.8 S3 10 600 900 1200 1500 1800
7.5 S3 25 1300 2000 2700 3300 4000
2 5 7.6 S3 25 1300 2000 2600 3300 3900
7 1/2 9 S3 25 1100 1700 2200 2800 3300
3 9.6 S3 25 1000 1600 2100 2600 3100
3 10.6 S3 25 900 1400 1900 2400 2800
7 1/2 10 11 S3 25 900 1400 1800 2300 2700
10 14 S3 25 700 1000 1400 1800 2100
5 15.2 S3 25 700 1000 1300 1600 2000
5 16.7 S3 25 600 900 1200 1500 1800
15 17 S3 25 600 900 1200 1500 1800
15 21 S3 50 1000 1400 1900 2400 2800
7 1/2 20 22 S3 50 900 1400 1800 2300 2700
7 1/2 24.2 S3 50 800 1200 1700 2100 2500
20 25 27 S3 50 700 1100 1500 1900 2200
10 28 S3 50 700 1100 1400 1800 2100
10 30.8 S3 50 600 1000 1300 1600 1900
30 32 S3 50 600 900 1300 1600 1900
25 34 S3 50 600 900 1200 1500 1800
30 40 S3 100 1000 1500 2000 2500 3000
40 41 S3 100 1000 1500 2000 2400 2900
15 42 S3 100 1000 1400 1900 2400 2900
15 46.2 S3 100 900 1300 1700 2200 2600
40 50 52 S3 100 800 1200 1500 1200 2300
20 54 S3 100 700 1100 1500 1900 2200
20 59.4 S3 100 700 1000 1300 1700 2000
60 62 S3 100 600 100 1300 1600 1900
50 65 S3 100 600 900 1200 1500 1800
25 68 S3 100 600 900 1200 1500 1800
25 74.8 S3 150 800 1200 1600 2000
60 75 77 S3 150 800 1200 1600 1900
30 80 S3 150 800 1100 1500 1900
30 88 S3 150 700 1000 1400 1700
75 96 S3 150 600 900 1300 1600
100 99 S3 150 600 900 1200 1500
Magnetic trip
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]
15
15
I
s
o
m
a
x
M
C
C
B
s
Motor horsepower ratings
Electronic trip
40HP @ 230V to 500HP @ 460V

Horsepower per NEC 430-50
Motor full Isomax MCP
Approximate trip setting % of MFLA
208V 230V 460V 575V Load amps Type Rating 1.5X 2X 4X 6X 8X 10X 12X
% % % % % % %
40 104 S4 250 350 500 1000 1400 1900 2400 2900
40 114 S4 250 350 450 900 1300 1800 2200 2600
100 124 S4 250 300 400 800 1200 1600 2000 2400
125 125 S4 250 300 400 800 1200 1600 2000 2400
50 130 S4 250 300 400 800 1200 1500 1900 2300
50 143 S4 250 250 350 700 1000 1400 1700 2100
150 144 S4 250 250 350 700 1000 1400 1700 2100
60 154 S4 250 250 300 600 1000 1300 1600 1900
125 156 S4 250 250 300 600 1000 1300 1600 1900
60 169 S4 250 200 300 600 900 1200 1500 1800
150 180 S5 400 350 450 900 1300 1800 2200 2700
75 192 S5 400 300 400 800 1300 1700 2100 2500
75 211 S5 400 300 400 800 1100 1500 1900 2300
200 240 S5 400 250 350 700 1000 1300 1700 2000
250 242 S5 400 250 350 700 1000 1300 1700 2000
100 248 S5 400 250 300 600 1000 1300 1600 1900
100 273 S6 600 350 450 900 1300 1800 2200 2600
300 289 S6 600 300 400 800 1200 1700 2100 2500
250 302 S6 600 300 400 800 1200 1600 2000 2400
125 312 S6 600 300 400 800 1200 1500 1900 2300
350 336 S6 600 250 350 700 1100 1400 1800 2100
125 343 S6 600 250 350 700 1100 1400 1700 2100
150 360 S6 600 250 350 700 1000 1300 1700 2000
300 361 S6 600 250 350 700 1000 1300 1700 2000
400 362 S6 600 250 300 600 900 1300 1600 1900
150 396 S6 600 250 300 600 900 1200 1500 1800
450 412 S6 800 300 400 800 1200 1600 1900 2300
350 414 S6 800 300 400 800 1200 1600 1900 2300
500 472 S6 800 250 350 700 1000 1400 1700 2000
400 477 S6 800 250 350 700 1000 1300 1700 2000
200 480 S6 800 250 350 700 1000 1300 1700 2000
450 515 S6 800 250 300 600 900 1200 1600 1900
200 528 S6 800 250 300 600 900 1200 1500 1800
500 590 S7 1000 250 350 700 1000 1400 1700 2000
Electronic trip
Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]